mobile air conditioning system design study

50
Mobile Air Conditioning System Design Study D. C. Zietlow, J. C. VanderZee, and C. O. Pedersen ACRCTR-49 For additional information: Air Conditioning and Refrigeration Center University of Illinois Mechanical & Industrial Engineering Dept. 1206 West Green Street Urbana, IL 61801 (217) 333-3115 September 1993 Prepared as part of ACRC Project 09 Mobile Air Conditioning Systems C. O. Pedersen. Principal Investigator ....

Upload: others

Post on 18-Dec-2021

1 views

Category:

Documents


0 download

TRANSCRIPT

Mobile Air Conditioning System Design Study

D. C. Zietlow, J. C. VanderZee, and C. O. Pedersen

ACRCTR-49

For additional information:

Air Conditioning and Refrigeration Center University of Illinois Mechanical & Industrial Engineering Dept. 1206 West Green Street Urbana, IL 61801

(217) 333-3115

September 1993

Prepared as part of ACRC Project 09 Mobile Air Conditioning Systems

C. O. Pedersen. Principal Investigator

....

The Air Conditioning and Refrigeration Center was founded in 1988 with a grant from the estate of Richard W. Kritzer, the founder of Peerless of America Inc. A State of Illinois Technology Challenge Grant helped build the laboratory facilities. The ACRC receives continuing support from the Richard W. Kritzer Endowment and the National Science Foundation. Thefollowing organizations have also become sponsors of the Center.

Acustar Division of Chrysler Allied-Signal, Inc. Amana Refrigeration, Inc. Carrier Corporation Caterpillar, Inc. E. I. du Pont de Nemours & Co. Electric Power Research Institute Ford Motor Company General Electric Company Harrison Division of G M ICI Americas, Inc. Johnson Controls, Inc. Modine Manufacturing Co. Peerless of America, Inc. Environmental Protection Agency U. S. Anny CERL Whirlpool Corporation

For additional information:

Air Conditioning & Refrigeration Center Mechanical & Industrial Engineering Dept. University of Illinois 1206 West Green Street Urbana IL 61801

2173333115

Table of Contents

Page

ABSTRACf .................................................................................. 1

1. INTRODUCTION ............................................................................. 1

2. SYSTEM MODEL ............................................................................. 2

2.1. Recalculation of Compressor Parameters ........................................ 4

2.2. Development of Physically Based Valve Model ................................ 5

2.3. Issues in Equation Solving ........................................................ 7

2.3.1. Newton-Raphson Damping ........................................... 7

2.3.2. Prevalence of the Unknown Variables ............................... 7

2.3.3. Selection of the Unknown Variables ................................. 8

2.3.4. Extent of the Unknown Variables .................................... 8

3. INFLUENCE COEFFICIENTS ............................................................. 9

3. 1. Model Data and Calculations ...................................................... 9

3.2. Influence of Operating Conditions .............................................. 12

3.3. Influence of Design Parameters .................................................. 15

3.3.1. Simulation of Design Changes ...................................... 16

3.3.2. Interpretation of Results .............................................. 16

4. DESIGN OPTIMIZATION EXAMPLE ................................................... 20

4.1. Introduction ........................................................................ 20

4.2. Method .............................................................................. 20

4.2.1. Influence Coefficients ................................................ 20

4.2.2. Finite Changes ......................................................... 22

4.3. Results .............................................................................. 24

APPENDIXA.

APPENDIXB

REFERENCES

CURRENT SYSlEM MODEL ............................................ 28

INDIVIDUAL INFLUENCE COEFFICIENTS ......................... 37

................................................................................. 46

Internal Publications ....................................................................... 46

External Reference ......................................................................... 46

MOBILE AIR CONDITIONING SYSTEM DESIGN STUDY

D.C. Zietlow, J.C. VanderZee and C.O. Pedersen

Department of Mechanical and Industrial Engineering

University of lllinois at Urbana-Champaign, 1993

ABSTRACT This study uses a semi-theoretical steady state computer simulation of an automotive air

conditioning system to evaluate design options. The simulation has been validated with experimental

data. Influence coefficients are used to combine energy and cost data to provide a reasonable basis

for comparison.

Influence coefficients are provided for evaluating seven different design changes. Four of

these are used in an example which illustrates the use of influence coefficients in making design

choices.

For the system modeled it is found that enhancing the internal surface of the condenser coil is

the best option for increasing capacity, increasing efficiency and decreasing head pressure. The other

three design changes included in the example were increasing the condenser length, evaporator length

and compressor displacement.

1. INTRODUCTION One of the intended purposes of the ACRC Project 09 steady state model of a mobile air

conditioning system is identifying aspects of design that significantly affect the system perfonnance.

Design changes can be simulated with the model, and different perfonnance criteria can be examined.

The basic system model is presented in ACRC Technical Report 36. Further modeling

efforts have resulted in improved model accuracy. Chapter 2 presents the current system model and

discusses the improvements made in the compressor and expansion valve components. It also

includes further insights into the modeling process.

Several influence coefficients have been calculated with the system model. First, the

influences of compressor speed in the model are compared to those in measured data. By the

comparisons, the validity of the modeling procedure is established. Then, influences of design

factors (e.g., heat exchanger area, enhancement) in the condenser, compressor, and evaporator are

calculated. By viewing this study from a designer's perspective, it was decided to include the

influence of these factors on cooling capacity, coefficient ofperfonnance (COP), and head pressure.

1

Chapter 3 presents the design sensitivity study. Finally, we demonstrate the use of these influence

coefficients in optimizing the air conditioning system based on cost in Chapter 4.

2. SYSTEM MODEL Improvements have been made on the system model since it was presented in ACRC TR-36.

One of the reasons that the fIrst system model was inaccurate was the compressor performance

deterioration during data collection. Therefore, the compressor parameters were recalculated using

only the data taken before the compressor began to deteriorate.

The fIrst model was incomplete, as well, because it required that the expansion valve pressure

drop be specifIed as an input. The current model uses a semi-theoretical model of the valve based on

the conservation of momentum.

Fig's 2.1 and 2.2 are corrected plots showing the accuracy of the current model for capacity

and COP. Both COP and capacity appear to be modeled quite well by the current model. This model

is complete since only the operational inputs(e.g., compressor speed, air flow rates) of the physical

system must be specifIed as inputs for the model rather than experimental outcomes (e.g., refrigerant

pressure drop).

2

~ u ]

~

! ~ 0 ..... ~ §-u ] .g ::E

Accuracy of COP-Current Model

3

2.5 . . . . .......................... : .......................... ~ ......................... ~ .......................... c- ....................... II ...................... .

~ ! ~ E :: :: :: ::

2 _· .. ············ .. +-.. · .. ·······-1-········· .. _····1 .. ······ .............. ...l ............. _/""" ................. .

1.5

1

~ E E . E .......................... : .......................... '0'......................... . ...................... t:" ......................... ~ ........................ .

i i . i i ..... 111 .................. :.......................... • ................ II.I .. ~I ......................... OOIII.III.I ............ II •• O ..... 111 ... 111 ••• 11 ..... .

E ::::::

~ ~ ~ ~ 0.5

i . ! i i .......................... ······ ........ · .... · .. ·r ............ ········· .. ·r ...... ·· ...... ··········-r···· ............ ······ .. ·r .. · .. ········ .. · .... ···· :: :: :: :: O~~~~~~~~~~~~~~-r~~~~~~~

20

16

12

8

4

o

o 0.5 1 1.5 2

Measured COP

Fig. 2.1. Accuracy of COP-Current Model Accuracy of Capacity-Current Model

. . .

2.5

-_················_·r···_ .... ·· .. ·_·········r·················································:-f···

········_ .. ··············r .. ··················r·_·······............. ························T·····················_···

·· .... ········ .... ···· .... ·····r··············· .. ···· .. · .. · .. · .... ······ .... · .. · ...... ·····r .. · .. ···· .. ·· .... ··· ...... ·· .. r· .. ······· ................. ..

I I I ....... _ ............. _ .... ····· .. ······_ .. T··························r··················_···r················ .. ·······

3

o 4 8 12 16 20

Measured Capacity (kBTU/hr)

Fig. 2.2. Accuracy of Capacity-Current Model

The following sections of this chapter detail the improvements that resulted in the current

model and raise some modeling issues that may merit further investigation.

3

2.1. Recalculation of Compressor Parameters Towards the end of the experimental testing there were signs of compressor deterioration. Oil

was leaking from the compressor and the leakage rate increased as time elapsed. A few months

earlier, when the refrigerant mass flow rate measurements became erratic, a piece of gasket material

was found lodged in the turbine of the flow meter. It is suspected that the material came from the

compressor.

The deterioration is evident from the volumetric efficiency, which should vary systematically

with the compressor speed. The data are calculated directly from experimental measurements and

shown in Fig. 2.3.

>. g Q)

'0 e ~ u 'E

~ ~

0.8

0.7

0.6

0.5

0.4

Compressor Deterioration Based on Experimental Measurements

. . e ; ; ~ Le~d ; ................... .1. ........................................... L .................... r..... .. ............. ; ...................... .1................. .. . 1 ; 01 1 0 jial113-14l1993 ; ; d ; ; ; I I ~ o! -+- ffter Jan t4 .................... + .................. l .................... r .................... l .................. ~ ...................... r .............. · .. ..

.................... t-................ ·t-................ ·t .................. ·t ...................... 1 .................... 1 .................... · I + • t-+-+ I ...................... r .................. · .. t .................. ·1t-.................. + .............. ~ ........ ·+-...... ·t .................. · .. 1 1 + 1 ~ 1 i i 1 i ... i

0.3~~~~~~~~~~~~~~~~~~~~

500 1000 1500 2000 2500 3000 3500 4000

Compressor Speed (rpm)

Fig. 2.3. Compressor Deterioration

The 13 points in the top band are data taken on January 13 and 14, 1993. They demonstrate a

smooth, continuous functional relationship. The remaining points are data taken on January 15th and

later. It is not clear what happened between the 14th and the 15th, but the laboratory records include

some high pressure and temperature alarms. It is clear that after the 14th the compressor efficiency

both decreased and became less consistent. Current compressor equations and coefficients based on

the first 13 points can be found in the FORTRAN residual equations subroutine in Appendix A. The

first version can be found in ACRC TR-36 or ACRC TR-37.

4

2.2. Development of Physically Based Valve Model The fIrst system model used an exact valve model in which the measured pressure drop for

each point was given as input. The current model uses a physically based model to characterize the

performance of the valve. Therefore, experimental pressure drop data is not needed in order to run

the model.

Several theoretically based correlations have been examined to model the valve pressure drop.

Equation. 2.1 is the current equation for the valve model in the system. One even more complicated

and accurate but less theoretically defensible equation was tested. With that more accurate equation,

the system accuracy is not noticeably better, and the range of operating conditions that converges

includes only 12 of the 13 experimental points.

m2 ( C3 ) rn2 ( C5 C6 ) M> = vdi Cl + C2·.1Tsc + rnA + vdo C4 + rnB + vdo (2.1)

where M> is pressure drop, vdi and vdo are inlet and outlet densities, respectively, rh is mass flow rate, .1 T sc is inlet subcooling, and A, B, and C are eight experimentally determined parameters.

5

Figures 2.4 and 2.5 compare the measured system pressures to the modeled pressures. Accuracy of Condenser Inlet Pressure-Current Model

350

'2 310 ..... 00

S

~ 270 00 00

£

_ .......................... ""1" .............................. 1 .. -···· .. ··l··O ... ~ .......... 4- i~··················· .. ··· : : : :

_··························r·····························r---.. · .. ·· ······················ .. ·· .. r····················· 'E 230 ..... .g ~ 190 :::::::::~:=-.= ... :~::::~:::r:::::::::::::::::::::::::::::I::::::::::::::~:~:::I:::::::::::::~:::~::::

150~~~~~~~~·~~~-r· ~~~r'~~~~

150 190 230 270 310 350

Measured Pressure (psia)

Fig. 2.4. Accuracy of Condenser Inlet Pressure-Current Model

Accuracy of Evaporator Outlet Pressure-Current Model

50~~~~~~~-+-r~~~~~r-~~~~

. . . . 45 . . . . .... ··· .. · .. ···· .............. ·r .. · ........ ········· .......... r .. ··········· .... ·· .. · ...... ·r .. · .. · .. ········ .... · ·· .... r ........ ·· .. · .. · ............ · : : : : E E . E

~ ~ . ~ ............................... : ................................ : .............. ...... •••• .. ··~.·· ••• • .... ••••• ............... oco •••••••••••••• ••••••••••••••••

I ! I I 40

35 ............................. .J.... . ............... G··r-·························/····················· .. ········1··················· .. ·· .. ··· 0000 ; ; ;

O! ! ! ! ! !

30~~--~~~~-r~~--r-~-+-+------~

30 34 38 42 46 50

Measured Pressure (psia)

Fig. 2.5. Accuracy of Evaporator Outlet Pressure-Current Model

6

The valve model has a root-mean-square error of over 10 psi, so the visible error is expected.

A more sophisticated valve model might provide greater accuracy, but the current system model

already has good accuracy for heat transfer modeling and should predict correctly the influence of

various factors on the pressures.

2.3. Issues in Equation Solving Several aspects of the solution process have been considered during the development of the

mobile air conditioning system model. ACRC TR-36 mentions some of them briefly. Further

comments on the method of solution are collected in this section.

A Newton-Raphson method is used to solve the model equations. This method numerically

finds the derivatives of each residual equation with respect to each unknown, thus finding a

linearized system about the initial values. That linearized system is solved exactly by linear algebra to

calculate the next values. Unless the actual system is linear, iteration is required until the residuals

are sufficiently small. Even univariate functions can be selected that fail in this method even with

fairly accurate initial values.

2.3.1. Newton-Raphson Damping One modification to the implementation of the method is that it is damped by 50% on the first

iteration, that is, the second values are selected between the initial guesses and the first linearized

solution. This is useful primarily because this system of equations uses refrigerant property routines

that are discontinuous across the saturation dome. When values change too drastically, the

assumptions about refrigerant states around the loop can be violated.

More general issues center on the design of the residual equations themselves. Three of them

addressed below are called, for the purpose of this report, the prevalence, selection, and extent of

the unknowns.

2.3.2. Prevalence of the Unknown Variables The prevalence of the unknowns is simply the number of them. Early models were solved in

the Engineering Equation Solver (EES) program. Every variable, unless it is contained in a function

or can be algebraically solved initially, is treated as an unknown by EES. An EES version of the

system model could have hundreds of variables. As reported in ACRC TR-36, the number of

unknowns in the FORTRAN model has been reduced to 16, fewer than the sum of those in the

component models.

One benefit of a reduced number of variables is the reduction in computation and thus

increased speed of solution. Increased stability can also be expected, because equations that embody

knowledge of the system are being used as constraints instead of residual equations.

7

2.3.3. Selection of the Unknown Variables Selection of unknowns involves choices after the number of equations has been determined.

First, by the ordering of the equations, different variables can be eliminated or left as unknowns.

Also, the same variable can be found in different ways. For example, a pressure can be an unknown

itself, be found as an unknown pressure drop from another pressure in the system, or be a saturation

pressure for some unknown temperature.

Careful selection can result in useful, physically-based unknowns. Such variables allow

simple derivation of accurate initial guesses and variable bounds, and they are easily interpreted to

gain understanding of the solution process. Selection of unknowns seems to affect convergence, as

well.

2.3.4. Extent of the Unknown Variables The extent of the unknowns has to do with how often the unknowns are used in the model

equations. An example of this issue is the condenser outlet pressure in this system model. One of the

unknowns is the condenser pressure drop, and that is compared to the condenser model pressure

drop equations in one of the residual equations. The condenser outlet pressure also appears in the

expansion valve equations. The extent of the unknown is greater if the unknown pressure drop rather

than the result of the condenser equations is used to determine this outlet pressure.

The most striking example of an unknown with variable extent is the refrigerant mass flow

rate. That was an unknown in an early version of the system model. The compressor is the fIrst

component treated in the system, and the compressor equations provide a calculated mass flow rate.

Either of these could be used for all the succeeding components. Perhaps unknowns of truly variable

extent can always be eliminated. The condenser pressure equations require the density calculated

from the outlet pressure, so that unknown must be included; however, it does therefore influence the

calculated pressure drop and extend indirectly when the calculated value is substituted.

Limiting the extent of the unknowns might be considered as performing steps of a successive

substitution within each Newton-Raphson step. Since order of substitution is of critical importance in

successive substitution, the order of evaluation in the residuals block must be important in

determining the benefIt of substituting calculated values there.

8

3. INFLUENCE COEFFICIENTS Design infonnation can be obtained from the model by simulating design changes instead of

constructing and testing many prototypes. This study presents infonnation in the fonn of influence

coefficients. An influence coefficient is a ratio of the effect on one variable to the exclusive small

change in another variable. For this report, the influence coefficient represents the influence of design

variables (e.g., heat exchanger length and heat transfer enhancement) upon system performance

variables (e.g., coefficient ofperfonnance and capacity)

This study ftrst calculates influence coefficients for compressor speed, an operating

condition. Since compressor speed varies in the experimental data, the simulation results are

compared to the experimental results to further validate the model accuracy and calculation of

influence coefficients. Then design changes in the condenser, compressor, and evaporator are

simulated. An example is presented in chapter four to demonstrate how these influence coefficients

can be used for guiding design efforts.

3.1. Model Data and Calculations Convenient input data are used for the simulation to produce organized results for plotting.

Figures 3.1 and 3.2 show the two primary data sets.

9

Inlet Air Temperature

to Evaporator (OF)

120

100

§ 8 N ~ ~ §

Speed of Compressor N

(rpm)

Values of Other Operating Variables: Barometric Pressure=14.4 psia

Air Flow Rate through Condenser=37oo CFM Inlet Air Temperature to Condenser=85 of Inlet Humidty Ratio to Condenser=.005 Inlet Humidity Ratio to Evaporator=.01

Ambient Temperature=80 of

Air Flow Rate Through

Evaporator (CFM)

Figure 3.1. Simulation Data Set A with Evaporator Side Variations

10

100

2000 2500 3000

2000

Speed of Compressor (rpm) 3000

Values of Other Operating Variables: Barometric Pressure=14.4 psia

Air Flow Rate through Evaporator=700 CFM Inlet Air Temperature to Evaporator=110 of

Inlet Humidty Ratio to Condenser=.005 Inlet Humidity Ratio to Evaporator=.01

Ambient Temperature=80 of

Air Flow Rate Through

Condenser (CFM)

Figure 3.2. Simulation Data Set B with Condenser Side Variations

Figure 3.1, input set A, has three values for evaporator air flow rate and two for temperature

in almost all possible combinations. One combination is absent because it is outside the region of

convergence for the modeL Figure 3.2, input set B, has three values for condenser air flow rate and

two for temperature in all possible combinations. Both data sets have three values for compressor

speed. The remaining operating variables remain constant at average values throughout the

simulation.

11

Simulated output provides a prediction of system perfonnance; these predicted values are as

accurate as the model. To calculate the influence of each parameter, the complete input sets are

simulated with a change in that parameter. Compressor speed is changed by changing the input

values. Design factors are changed by altering the appropriate parameters in the residual equations of

the model.

One convenient fonn of influence coefficient is a dimensionless ratio of the percentage change

in effect to the percentage change in cause. Most of the simulation changes are 1 % increases in

design variable (the independent variable) so that the resulting percentage change in the performance

variable (the dependent variable) is the influence coefficient. Equation 3.1 uses coefficient of

performance, COP, and compressor speed in rpm, to show an example of a definition of this type of

influence coefficient (I.C.) The subscripted variables are the original values from the unchanged

input data.

%~COP I.C.= %&-pm

(COP 0 -COP) rpm 0

COP 0 rpmo -rpm

3.2. Influence of Operating Conditions

(3.1)

The only operating condition influence studied is compressor speed. The primary motivation

for studying the influence of operating conditions on the perfonnance variables is for model

validation. The model was validated for function values in Chapter 2. This validation looks at the

ability of the model to predict derivative values (influence coefficients). Since operating variables

were changed, during the experimental testing, the actual experimental influence coefficients can be

calculated and compared with the model's predictions. The input data is the same as that shown in

Figure 3.1 where the evaporator's operating conditions are varied. Figures 3.3 and 3.4 show the

calculated effects on system COP and capacity of increasing speed by 1 %. As might be expected, the

influence on COP is negative and on capacity is positive.

12

Influence of Compressor Speed on COP

-0.58 o 5OO1b~evap.arr x 700 Ib~ evap. air .................... J; ................... --r ............. ······r·······~··· b. 900 Ib~ evap. arr

~ j j x. . .

I] -~r~:I~jl:: , I I ~ I I ~

······················,······················r····· .............. -r .................... "1" .................... -r ..................... !"" ................... .

: ; ; b.; ; ~ ..................... ~...... evap. arr Tin .............. evap. arr flow rate .. j ..................... .

I (100 & 120 OF) r -0.7~~~~~~~~~~~~~~~~-r~~+

-0.6

13 -0.62 8-en

~ - -0.64 -~ u -0.66 ~

-0.68

1800 2000 2200 2400 2600 2800 3000 3200

Compressor Speed (rpm)

Fig. 3.3. Influence of Compressor Speed on COP

Influence of Compressor Speed on Capacity

0.22

0.2

] 0.18 0.. en

0.16 ~ -- 0.14 a .... ~ 0.12 ~ u

0.1 ~

0.08

0.06 1800 2000 2200 2400 2600 2800 3000 3200

Compressor Speed (rpm)

Fig. 3.4. Influence of Compressor Speed on Capacity

13

The previous graphs illustrate the variation in influence the compressor speed has upon the

performance variables as the evaporator operates through its entire range.

To calculate the experimental influence coefficients data points were selected where the

evaporator air flow rate was held constant at around 700 lbm/hr. They are shown in Figure 3.5 with

a curve fit that accurately gives COP as a function of compressor speed. These points were selected

from the set of data which was taken prior to the deterioration of the compressor.

Measured COP as Function of Compressor Speed

3~~~~~~~~~~~~~~~~~~~~~~

2.5 ... ····················r························l·························r························r·························r························

2 .......................... : ....................... .1. ........................ .1 ......................... .1 ......................... .1. ........................ .

-1;--~--1-I---1.5

! ! ! 11-~~~~~~~~~~~~~~~~~~~~

1000 1500 2000 2500 3000 3500 4000

Compressor Speed (rpm)

Fig. 3.5. Measure COP as Function of Compressor Speed

The curve fit is needed because influence coefficients are calculated for small changes in the

independent variable and the experimental changes were fairly large. The equation of the curve is

given by Equation 3.2. By taking the derivative, Equation 3.3 is found, which allows the calculation

of the influence coefficient by Equation 3.4. The exact ratio of rpm to COP from the measured data is

used in this equation. Equation 3.4 corresponds to Equation 3.1 if the partial derivative is changed to

a fmite difference.

COP = 153.4 . (rpm) -0.58804

OCOP 88 drpm = 153.4· (-0.58804) . (rpm) -1.5 04

I C _..!P!!!.. acop .. - COP drpm

14

(3.2)

(3.3)

(3.4)

Fig. 3.6 shows the influence coefficients calculated for COP by the above equations for the

experimental data and compares them with the model results. The model used experimental data for

its inputs rather than the simulation data sets.

Influence of Compressor Speed on COP

-0.56

-0.58

1 -0.6 en ~ -0.62

¢ . ¢ . ¢ i

·=:l···r·~:··~=t:Jr: i :k iii i

··········----····---·i-···-··-·-·----·----·-~-··-···················i···········--······---.t----··········· ........ ~ ...... -............... { ..... --........ ---.--. i * i ~ i i --Po. -0.64

0 u ~ -0.66

-0.68

j j j j ~ j ······················i······················1·······················?····------············t······················r···---···········--···i······················

1 j ! l 1 l iii i )/: i ---.-...... --......... ~-.-........... ----.. -."-.-.-....... _-_._-_ .... , .............. __ .. __ .................. ·········f······ __ ··············I······················

i 0 experimental data fit i ~ .. ····· .. ········ .. t········· x model run · .. '1" .... · .. ··· ........ ·1 ...... ·· .......... · ..

-0.7~~~~; ~~~~~~~~~~~;~~~; ~~+

500 1000 1500 2000 2500 3000 3500 4000

Compressor Speed (rpm)

Fig. 3.6. Comparison of Experimental and Model Influence Coefficients

The results agree to within 10 percent for the midrange of the compressor's operating

envelope but diverge at the extremes. The model can be used to predict the influence coefficients of

operating variables within a reasonable range of operating conditions. We expect the model to also

predict the influence of design changes accurately.

3.3. Influence of Design Parameters Unfortunately, the designer does not have control over many of the operating variables.

These variables are normally a constraint of the system. A much more interesting exploration is the

influence of design variables upon the performance of the system. Examples from the second data

set, in which the inputs to the condenser were varied, are included in Appendix B. Figures B.l-B. 8

show results for factors affecting condenser design. Figures B.9 - B.12 show results for the

compressor. Figures B.13 - B.16 show results for the evaporator. These data are provided so that

analysis can be performed without again running the model. The next section describes the changes

made in the residual equations for simulating the design changes studied.

15

3.3.1. Simulation of Design Changes Design changes are simulated by changing the residual equations in the model, see the code in

appendix A. Condenser length is increased 1 % by setting the third zone length fraction to 1.01 minus

the fIrst two fractions. The simulated air side heat transfer coeffIcient and air temperatures are not

affected because the model scales the air flow rate proportionately. The condenser air side heat

transfer coeffIcient is increased 1 % by scaling the fourth condenser parameter by 1.01. The

condenser refrigerant side heat transfer coeffIcient is increased 1 % by scaling the first three

condenser parameters by 1.01. Since pressure drop in the condenser has little effect on the system,

the condenser friction factor needed to be increased by 100%. This was accomplished by doubling

the last four condenser parameters.

The compressor volume is increased 1 % by scaling the displacement by 1.01 and specifying

the same clearance fraction. The displacement volume alone is increased 1 % when the clearance

fraction is also scaled, by the inverse of 1.01.

Evaporator heat transfer coefficients are scaled 10% by dividing the refrigerant side resistance

or both wet and dry air side resistances by 1.1. The evaporator length was changed by increasing the

wet and dry fractions by 10% along with other relevant heat transfer and pressure drop residual

equations.

3.3.2. Interpretation of Results Figure 3.7 and Table 3.3 contains averages over each data set for all of the influence

coefficients previously discussed.

16

Summary of Average Influence Coefficients

0.6 0.4 0.2

O-tCIII~ Influence -0.2

Coefficien' -0.4 -0.6 -0.8

-1

~d~.El<l= uuu~~ trl cd

~~ Influencing Facto -

Performa nCE Variable

Figure 3.7 Summary of Average Influence Coefficients

17

KS Ehr

ress.-A -B

Influencin Factor

Table 3.3. Summary of Average Influence Coefficients

Only the first fIfteen points of set A are included in the averages because the last two points

tended to be extreme. Although the graphs present more information, the summary table is

convenient for comparing the effects of different operating and design factors. Influence on COP,

capacity, and head pressure are reported in the table. Together these two data sets represent a

reasonable operating range of the air conditioning system. Under the assumption that the air

conditioning system operates under each of these conditions for an equal amount of time over the life

of the system, these numbers represent the influence of the design change on the performance

variable for the life of the system. Weighting factors can be used in conjunction with the data in

Appendix B to evaluate conditions which differ from this assumption.

From a purely energy standpoint, the condenser length is the most promising to improve all

measures of perfonnance. The fIgures show, also, that the influence is less at higher condenser air

flow rates, but on average, a 10% increase in condenser size improves COP around 5%, capacity

around 2%, and decreases head pressure around 8%.

One might consider using enhanced condenser tubes with both a higher heat transfer

coeffIcient and a higher pressure drop. The table shows that in order to maintain or reduce the head

pressure, the heat transfer improvement must be at least 1.5% per multiple of pressure drop increase.

18

A 15% increase in heat transfer coefficient with a factor of 10 increase in friction factor would

improve capacity around 1 % and COP over 1.5%.

Increased compressor displacement has effects similar to operating at a higher compressor

speed. The same increase in capacity is achieved with smaller decrease in COP and smaller increase

in head pressure by increasing displacement, however. The compressor simulation assumed the same

rate of heat loss and same efficiencies at the larger size.

Evaporator heat transfer coefficients do not leave as much room for improvement, but the

data do show that improvements an the air side are four times as effective. It is interesting that at the

lower evaporator air flow rates, the improved evaporator heat transfer tended to have a greater,

though still small effect of increasing head pressure.

19

4. DESIGN OPTIMIZATION EXAMPLE

4.1. Introduction In Chapter 3 we evaluated the design options based strictly on energy criteria. This is an

inadequate measure of the feasibility of a design change. It is important to look at the cost to

implement each measure. If increasing the length of the condenser increases the capacity by twice as

much as enhancing the tubes then from an energy standpoint it is the best option. But if it costs four

times as much to increase length as to enhance the tubes then the tube enhancement becomes the best

option.

This next section demonstrates how cost information can be integrated with the influence

coefficients calculated in the previous chapter to evaluate design choices. One of the objectives of a

manufacturer of air conditioning systems for automotive applications is to increase the cooling

capacity. This will reduce the time to reach comfort when the vehicle is first used. First, the least

costly way to increase the capacity of the system is determined. Then the same method is applied to

finding the least costly way to reduce head pressure (the pressure at the outlet of the compressor) and

increase the coefficient of performance.

4.2. Method

4.2.1. Influence Coefficients To use the influence coefficients from the previous section we need to put cost information in

a form which can be used. Below is the general form used to apply the cost information. ~design variable

~cost (4.1)

For small changes in the design variable Equation 4.1 becomes ddesign variable

dcost (4.2)

If this is then multiplied by the influence coefficient of interest, the influence of cost on

capacity can be determined as follows in Equation 4.3:

acapacity

acost

acapacity

adesign variable

adesign variable

acost (4.3)

When this is done for several different design variables a comparison can be made to find out

which change in design variable has the most effect on increasing the capacity at the lowest cost.

The following design variables were evaluated for this example.

20

1) Replace smooth tubes with microfm tubes in the condenser

2) Increase the length of the evaporator

3) Increase the displacement of the compressor

4) Increase the length of the condenser

Below are the relevant specifications of the air conditioning system tested in this study.

1) Evaporator length (refrigerant path): 3.6 m

2) Weight of evaporator plates and fins: 1.04 lb/m

3) Evaporator material: aluminum

4) Compressor displacement volume: 170 cc

5) Condenser length (refrigerant path): 30 m

6) Weight of condenser tubing: .411b/m (ASHRAE 1992 Systems Handbook)

7) Weight of condenser fins: .41Ib/m (estimated)

8) Condenser material: aluminum

Cost data were obtained from various members of the Industrial Advisory Board. These

figures are current but should be modified for your particular application. This modification is made

by following the method described above in Equations 4.1 through 4.3. The cost figures are

incremental, not average, costs. It is the cost for adding the design change assuming the fixed costs

for setting up the production line would be the same even if the design change were not implemented.

Table 4.1 shows the cost figures used for this example along with the corresponding change in the

design variable.

T bl 41In alCh a e . crement dC ·De· V·bl angesan ostsm SIgn ana es

Design change Change in design variable Incremental Cost

Enhance condenser tubes ahr=I00%(Eckels, 1991) $.40/lb

M7=100%(Eckels, 1991)

Increase evaporator len$h aEL=10% $.95/lb

Increase compressor Mm=lO% $2.50

displacement

Increase condenser length aCL=lO% $. 95/lb

where, hr-heat transfer coefficient on the refrigerant side

Pr-pressure drop on the refrigerant side

A word should be added about the assumptions which were made to determine the changes in

heat transfer coefficient and pressure drop by enhancing the condenser tubes. The work by

Eckels(I991) shows the heat transfer coefficient improves by 75 to 150% and the pressure drop

increase was less this. For this analysis it was assumed that the pressure drop increase was the same

as the improvement in the heat transfer coefficient. This adds a slight penalty to the enhancement

design option since an increase in pressure drop decreases the capacity. The actual calculation of the

21

influence of enhancement on the capacity was made up of two components (the influence of heat

transfer coefficient and pressure drop on capacity) which were added together and then used in

equation 4.3

The previous cost data were used to construct influence coefficients of the influence of cost

on the design variable, the rightmost factor in Equation 4.3. These are contained in Table 4.2.

T bl 4 2 Infl f C th De' V' bl a e . uenceo oston e Slgn ana es

Design Variable Influence Coefficient

ddesign variable(% )/Ckost($)

Enhance condenser tubes 96

Increase evaporator length 26

Increase compressor displacement 4.2

Increase condenser length 4.5

4.2.2. Finite Changes Influence coefficients work well in evaluating changes if they are relatively small. If the

change in a design variable is relatively large then influence coefficients begin to lose their

effectiveness. The reason for this is that an influence coefficient is the slope of a curve at a point.

When it is applied one assumes that this slope is constant over the range of interest. If the curve is

nonlinear and the range is large, the error can become significant. This is illustrated below in Figure

4.1.

22

» .... • - roo..

~.E. a~ 8~ ~o .... 0 00 ~,...; >'-' ~

Prediction Using Influence Coefficients 24 ~~~~~~~~~~~~~~~~~~+-~~~

22

20

18

16

. . . . . ······· .. ··············r······················r······················r·····················T···· ·················r······················

I I I I

rf-'rr ·······················t·················· ··t······················~·······················t······················9·······················

I r ! ! ! . : : : :

j 1 l ! . ! : : : ················o···-r·······················r·····················"j·······················r················ ...... ]"" ..................... .

o Actual Model Capacity

--Predicted Capacity Using

14 ···············_······r················ Influence Coefficient

12 4-~~~~~~~~~~~~~~~~~~~~~

o 100 200 300 400

Scaling of the Refrigerant Side Heat Transfer Coefficient in Condenser

(%)

500

Figure 4.1. Error from Using Influence Coefficients

600

This graph was generated by scaling the appropriate parameters in the condenser model to

simulate an change in the refrigerant side heat transfer coefficient. The influence coefficient was

calculated at the baseline condition (scaling factor = 100%) and was used to predict the effect of

changes in the refrigerant side heat transfer coefficient on the evaporator capacity. The error between

the prediction and the model results is small for small changes in the design variable but increases

significantly for large changes.

23

4.3. Results The influence coefficient for the four design changes under consideration were calculated using

Equation 4.3. The results are displayed in the Figure 4.2.

12

10

8

6

4

2

o

Influence of Design Changes on Capacity

e f ra ~

DeSIgn Change

M ... o s:: Vl Q)

~ E M Q) 0.. u E ~ rq e-

Figure 4.2. Influence of Design Changes on Capacity Using Influence Coefficients

This shows that for small changes in the design variables, enhancing the condenser tubes is

the most cost effective option for increasing the evaporator capacity for the system tested. One of the

biggest problems members of the Industrial Advisory Board say they face is rmding enough space to

install the heat exchangers. One recommendation based on these results is that the condenser and

evaporator lengths be reduced to conserve space. It is possible to do this, if the condenser tubes are

enhanced at the same time, without degrading the capacity of the evaporator.

24

In the real world finite changes are made in the design variables. These can be evaluated with

the model fairly easily. As we saw in the previous section, using influence coefficients can introduce

error when applied over a fmite change. For this reason the model was used to evaluate actual

changes in the capacity given the fmite changes in design variables listed in Table 4.1. Then equation

4.3 was modified by replacing the partial derivative operators (a) with fmite difference operators (L\).

The results are displayed in the following figure.

~ !U --0 0 ~ QJ ~

.e-. .-v !U ~ !U U .5 QJ

ff .2 u d QJ V ~ QJ ~

12

10

8

6

4

2

0

Influence of Design Changes on Capacity

Condenser Enhanced

Tubes

III Influence Coefficients

Evaporator length

o Finite changes

Compressor Displacement

Design Change

Condenser length

Figure 4.3. Influence of Finite Design Changes on Capacity

The result for enhancing the condenser tubes does change significantly when compared to the

influence coefficient prediction because there is a relatively large change in the design variable

(100%). Therefore, the error from using the influence coefficient is large. The result for the

evaporator does not change because the 10% difference in length used to calculate the influence

coefficient is equal to the finite change. The results for the compressor displacement and condenser

length do not change much. The reason for this is there is only a 10% change in the design variable

and the corresponding influence coeffienct is based on a 1 % change.

25

The overall conclusion from this example is, however, the same. Adding enhanced tubes to

the condenser is the least expensive way to increase the capacity of the system. With more capacity

the time to reach comfort in the passenger compartment will be reduced. This conclusion is only

applicable to the system and set of operating conditions used for this study. To do a similar study for

other systems, new parameters should be developed for those systems.

Although capacity is an important performance variable, the other two performance variables

are also useful. The influence coefficient for the coefficient of performance tells which design

variable improves the system efficiency for the least cost. The influence coefficient for head

pressure(the refrigerant pressure at the outlet of the compressor) is important since Rl34a is a higher

pressure refrigerant. Figure 4.4 displays influence coefficients for all three perfonnance variables

based on finite changes in the design variables.

Influence Coefficient (% change in performance variablel$)

Design Variable

Influence of Design Changes Based on Finite Changes in DeSign Variables

J -8 c:

COP Capacity

Head Pressure Performance

Variable

Figure 4 4. Influence of Design Changes on Three Performance Variables

This figure shows enhancing the tubes of the condenser is the best option for all three performance

variables. It produces the largest increase in both capacity and COP for each dollar of investment. It

also produces the largest decrease in head pressure.

26

5. CONCLUSIONS From this study the following conclusions can be drawn.

1) The computer simulation has been validated with experimental data. It models the capacity,

coefficient ofperformance(COP), pressures, and the influence of compressor speed on COP

accurately.

2) Influence coefficients can be used to rank design options when small changes are made in the

design variables. The simulation should be used to model large changes in the design variables.

3) For the air conditioning system studied, enhancing the condenser tubes is the best alternative to

increase capacity and COP and lower head pressure. The other three design variables studied were

increasing condenser or evaporator lengths and compressor displacement.

4) Cost analysis, as opposed to energy analysis alone, provides a better basis of comparison among

design options. From an energy standpoint alone, increasing the condenser length would be the

best option.However, the cost analysis found enhanced tubes to be the best option since it is less

expensive to implement.

27

APPENDIX A. CURRENT SYSTEM MODEL

C University of illinois at Urbana-Champaign

C Department of Mechanical and Industrial Engineering

C ACRC Project 09

C

C 1993 by Joel VanderZee

C

C This routine must be linked with refrigerant property routines.

Subroutine sysresid(input,out,resids)

double precision hundred,unity,zero,negone,pi,Hair,third

double precision input(1O),out(16),resids(16)

C** accumulator and acc.-comp. ref. line

double precision acl,ac2,aR(2)

double precision Pdrop,arpo,atsat,arh

C** compressor

double precision kparm(8),kR(I),ktsat

double precision krpi,krhi,hrpo,rpm,kTamb,mr,power,krho

double precision krsi,krri,krhos,krros,krti

double precision V disp,Kcl, ClearEff, V doCS, VolEff, V dot

double precision workc, workcs,IsenEff,kQ,krdh,xx,yy ,zz

C** comp.-cond. ref. line

double precision krpo

double precision crpi,krro,kcdp

C** condenser

double precision cparm(9),cR(7),calcpo

double precision cK,D,A,m,cMa,cHumRat

double precision crti,crhi,crdi,crp 1 ,crt 1 ,crh 1 ,crdl

double precision crp2,crt2,crh2,crd2,crpo,crto,crho,crdo

double precision cati,cato_sh,cato_c,cato_sc

double precision cahi,caho_sh,caho3,caho_sc

double precision Tbar,Tabar,UA,FF,Q,Qa,Qcalc,DP,DPcalc

double precision shfrac,cfrac,scfrac,UA1,UA2,FF1,FF2,DP1,DP2

28

C** expansion valve

double precision xp(8),xdrop,xR(I),ctsat,subcool

C** evaporator

double precision epann(1O),eR(5)

double precision pamb,Rflow ,Eaflow ,Erpi,Erhi,Eawi,Eati

double precision Erpo,Tsur,Qad,Qaw,hab,Erho,Eawo

double precision fd,rr,rm,rad,raw

double precision Erti,Erto,Eahi,Eaho,Erdi,Erdo,Erxi

double precision hasurw ,hasurd, wasurw, wasurd

hundred = 100.0

unity = 1.0

zero =0.0

negone = -1.0

pi = 3.141592653589793

third = 1.0/3.0

C** compressor

kTamb = input(8)

rpm = input(9)

krpi = out(2)

Call Fsatp(krpi,ktsat,xx,yy)

krti = ktsat + out(l)

krpo = out(3)

krho = out( 4)

xx = hundred

Call Mixptq(krpi,krti,xx,krri,krhi,krsi)

C ref. density (lb/ft"3)

C suction entropy (Btullb-R)

C for mass flow rate:

kpann(l) = 0.682718

kpann(2) = -1.017ge-4

C (rpm"-I)

kpann(8) = 0.11761

29

C (lb/ftA3)

C for isen. eff.:

kpann(3) = 0.758856

kpann(4) = -7.00616e-5

C (rpmA-l)

kpann(5) = 0.0070387

C (lb/ftA3)

C for heat loss:

kpann( 6) = 26.74

C (Btu/rpm-hr)

kpann(7) = 15.32

C (B tu/hr-F)

C Vcl =0.243

C clearance vol (in.A3)

V disp = 10.37

C displacement (in.A3)

C Kcl = VcWdisp

Kcl = 0.243/10.37

C clearance fraction

Call Mixsp(krsi,krpo,xx,krhos,krros,yy)

C discharge enth. at const. ent. (BTU/lb)

C discharge density at const. ent. (lb/ftA3)

ClearEff = 1 - Kcl * (krros/krri - 1)

C clearance volum. eff.

V doCS = ClearEff*rpm*V disp/1728

C isen. volum. flow rate (cfm)

VolEff = kpann(1) + kpann(2)*rpm + kpann(8)/krri

C isen. volum. eff.

C NOTE! Called this "effrat" in analyzer!!

C It is NOT the SAME as the "voleff' there!!

V dot = VolEff*V doCS

C suction ref. volumetric flow rate (cfm)

C kR(1) = mr - Vdot*60*krri

mr = V dot*60*krri

C ref. mass flow rate (lbm/hr)

30

workcs = krhos - krhi

C isen. work (BTU/lb)

IsenEff = kpann(3) + kpann(4)*rpm + kpann(5)/krri

C isen. eff.

workc = workcs/lsenEff

C actual work compo

C kR(2) = (power - mr*workc)/12000

power = mr*workc

C required compo power (divide by 12,000 to norm.)

kQ = kpann(6)*rpm**0.5 + kpann(7)*(kTamb-krti)

C heat loss

krdh = (power - kQ)/mr

C enth. rise

kR(1) = krho - (krdh + krhi)

C compo discharge ref. enth.

C** comp.-cond. ref. line

kcdp = 6.285674e-4

C empirical pressure drop coefficient (hr"2-ftA3-psi/lbA3)

crhi = krho

C no heat transfer

Call Mixhp(krho,krpo,xx,yy,krro,zz)

crpi = krpo - kcdp*(mr**2)/krro

C pressure drop

C** condenser

C for heat transfer:

cpann(l) = 0.1632045994812011

cpann(2) = 5.2751165442019870E-02

cpann(3) = 0.2198721449019462

C (ftA2-F-hr-lbAO.8/BTU-hrAO.8)

cpann(4) = 0.2831501216515262

C (ftA2-F-hr-lbAO.67/BTU-hrAQ.67)

C for pressure drop:

31

cpann(5) = 2.914678168647671

cpann(6) = 0.4834631486447542

cpann(7) = -0.7516406390569577

C (1h"0.25/hr"0.25)

cpann(8) = 8.20520338402oo130E-02

C (-)

cK = 1.66546E-ll

C this above to convert Ihm-ft/ft"2-hr"2 to psi

D =0.02083

C (ft)

A = pi*D**2/4

C (ft"2)

m=mr

cMa = input(2)

cati = input(3)

cato_sh = out(7)

cato_c = out(8)

cato_sc = out(9)

cHumRat = input(4)

cahi = Hair(cati,cHumRat)

caho_sh = Hair(cato_sh,cHumRat)

caho_c = Hair(cato_c,cHumRat)

caho_sc = Hair(cato_sc,cHumRat)

Call Mixhp( crhi,crpi,crti,xx,crdi,yy)

crpl = crpi - out(lO)

crp2 = crpi - out(ll)

crtl = 0

Call Mixptq( crp 1 ,crt 1, unity ,crd 1 ,crh 1 ,xx)

crt2 =0

Call Mixptq( crp2,crt2,zero,crd2,crh2,xx)

crpo = crpi - out(l2)

crto = crt2 - out(13)

xx =negone

Call Mixptq( crpo,crto,xx,crdo,crho,yy)

32

Q = m*(crhi - crhl)

VA = 2/(cparm(4)!cMa**O.67 + cparm(I)/(m/2.0)**O.S)

shfrac = Q / (VA *«crti + crtl) - (cati + cato_sh»/2)

Qa = cMa*(caho_sh - cahi)*shfrac

cR(I) = (Q - Qa)/IOOO

DP = crpi + cK*(m/2)**2/(A **2 * crdi) - crp I - cK*(m!2)**2/(A **2

& * crdl)

FF = cparm(S) + cparm(5)/(m/2)**O.25

DPcalc = (cK* (m!2)* *2/(A **2 * 2*crdi» * (shfraclD) * FF

cR(2) = DP - DPcalc

Q = m*(crhl - crh2)

VAl = 2/(cparm(4)!cMa**O.67 + cparm(2)/(m/2.0)**O.S)

VA2 = 1!(cparm(4)!cMa**O.67 + cparm(2)/m**O.S)

cfrac = (Q / «(crtl + crt2) - (cati + cato_c»/2) -

& (third - shfrac)*VAI)IUA2 + third - shfrac

Qa = cMa*(caho_c - cahi)*cfrac

cR(3) = (Q - Qa)/IOOO

DP = crpl + cK*(m/2)**2/(A**2 * crdl) - crp2 - cK*m**2/

& (A **2 * crd2)

FFI = cparm(S) + cparm(6)/(m/2)**O.25

FF2 = cparm(S) + cparm(6)/m**O.25

DPI = (cK*(m/2)**2/(A**2 * 2*crdl» * «third - shfrac)lD) * FFI

DP2 = (cK*m**2/(A**2 * 2*crdl» * «cfrac - third + shfrac)lD) *

& FF2

cR(4) = DP - DPI- DP2

calcpo = crpi - DPcalc - DPI - DP2

Q = m*(crh2 - crho)

scfrac = I - shfrac - cfrac

Qa = cMa*(caho_sc - cahi)*scfrac

cR(5) = (Q - Qa)/lOOO

VA = 1!(cparm(4)/cMa**O.67 + cparm(3)/m**O.S)

Qcalc = scfrac*VA*«crt2 + crto) - (cati + cato_sc»/2

cR(6) = (Q - Qcalc)/IOOO

33

DP = crp2 + cK*m**2/(A**2 * crd2) - crpo - cK*m**2/(A**2 * crdo)

FF = cparm(7)/m**0.25

DPcalc = (cK*m**2/(A**2 * 2*crd2» * (scfraclD) * FF

cR(7) = DP - DPcalc

calcpo = calcpo - DPcalc

C** accumulator and acc.-comp. ref. line

Erho=krhi

Erpo = krpi + out( 14)

C evaporator ref. pressure out

Call Mixhp(Erho,Erpo,Erto,xx,Erdo,yy)

arpo = (Erpo + krpi)/2

atsat = zero

Call Mixptq(arpo,atsat,unity,xx,arh,yy)

acl = 7.934e-5

ac2 = 0.002621

Pdrop = «acl + ac2/(mr/(Erdo+krri»**1.2) * mr**2)/

& (Erdo+krri)

aR(l) = Pdrop - (Erpo - krpi)

aR(2) = arh - Erho

C** evaporator

{Empirical Parameters}

eparm(1) = 6.827159

eparm(2) = 17.4617806

eparm(3) = 14.2347895

eparm(4) = 1.2538474

eparm(5) = 0.9397954

eparm(6) = 0.8186460

eparm(7) = 0.9220678

34

eparm(8) = 0.5342494

eparm(9) = 1.38431e-5

eparm(lO) = 9.7207e-4

pamb = input( 1)

C ambient pressure

Rflow=mr

C refrigerant flow

Eaflow= input(5)

C airflow

Eati = input( 6)

C evaporator air temperature in

Eawi = input(7)

C evaporator air humidity ratio in

Erpi = Erpo + out( 5)

C evaporator ref. pressure in

hab = out(16)

C air enthalpy at border of wet/dry

Eawo = out( 6)

C evaporator air humidity ratio out

Erhi = crho

C evaporator ref. enthalpy in

Q = Rflow*(Erho-Erhi)

C evaporator heat transfer

CALL Mixhp(Erhi,Erpi,Erti,xx,Erdi,Erxi)

Tsur = (Erto + Erti)/2 + out( 15)

C coil surface temperature

Eahi = Hair(Eati,Eawi)

C solves for air enthalpy given temperature and humidity ratio

Eaho = Eahi - QlEaflow

C evaporator air enthalpy out from energy balance

CALL Moisth(pamb,hundred, Tsur,hasurw, wasurw)

C surface enthalpy and humidity ratio wet

If (Eawi .It. wasurw) then

35

wasurd = Eawi

Else

wasurd = wasurw

Endif

hasurd = Hair(Tsur,wasurd)

C surface enthalpy dry

fd=(abs(wasurd/Eawi»* *eparm(4)

C fraction of the dry evap

IT = eparm(I)*le-3/(Erxi**eparm(5)*Rflow**0.8)

C refrigerant heat transfer resistance

rad = eparm(2)* 1 e-2/Eaflow**eparm( 6)

C dry air resistance

raw = eparm(3)*le-2/Eaflow**eparm(6)

C wet air resistance

Qad = fd*«Eahi+hab)/2-hasurd)/rad

C heat transfer of dry section

Qaw = (l-fd)*«hab+Eaho )!2-hasurd)/raw

C heat transfer of wet section

C heat transfer

eR(I) = (Q - (Qad+Qaw»/lOOO

eR(2) = (Q - (Tsur-(Erti+Erto)/2)/rr)/lOOO

eR(3) = (Qad-Eaflow*(Eahi-hab»)!I000

C pressure

eR(4) = (Erpi-Erpo)-(Rflow**2/«Erdi+Erdo)/2»

& *(eparm(9) + eparm(10)/(0.5*Rflow*(I/Erdi+l/Erdo»**0.55)

C Mass Transfer

eR(5) = «Eawi - Eawo) - (Eawi-wasurd)*(l-fd)

& *(eparm(7) + eparm(8)*le-3*Eaflow»*I000

C** expansion valve

xp(l) = 0.65131

xp(2) = 5.66012e-3

xp(3) = 22.7314

36

xp(4) = -0.061575

xp(5) = 328.399

xp(6) = 0.0692206

xp(7) = 1.17394

xp(8) = 1.88389

Call Fsatp(crpo,ctsat,xx,yy)

subcool = ctsat - crto

C xdrop = input( 10)

xdrop = mr**2*(xp(l) + xp(2)*subcool + xp(3)/mr**xp(7»/crdo

xdrop = xdrop + mr**2*(xp(4) + xp(5)/mr**xp(8) + xp(6)/Erdi)/Erdi

xR(1) = Erpi - (calcpo - xdrop)

resids(1) = aR(2)

resids(2) = xR(1)

resids(3) = kR(1)

resids( 4) = cR(1)

resids(5) = cR(2)

resids(6) = cR(3)

resids(7) = cR( 4)

resids(8) = cR(5)

resids(9) = cR(6)

resids(lO) = cR(7)

resids(11) = eR(1)

resids(12) = eR(2)

resids(13) = eR(3)

resids(14) = eR( 4)

resids(15) = eR(5)

resids(16) = aR(1)

return

end

APPENDIX B INDIVIDUAL INFLUENCE COEFFICIENTS

37

Influence of Condenser Length on COP

6 11 I I I I O. 4-~~~~~~-r~-r~~~~~~~~~

~ condo air Tin l 0 l \ ! <p o .55 - .................... cb-...... (80 ~ 90 OF) + ........ 0. ....... + ................ ···I·····················f···················· -

0.5--W·~~IJ-··*·-~ ~ : : : '; :

0.45--·H-+ 1n~ arr flrW mre/ __ ~ : : ~: : ~

0.4- -·······T--I'··· ~ ~r~l==t ~ ~ 0.35~~~~:~~-r,:~~~:~~~,-----~,----~,--~

1800 2000 2200 2400 2600 2800 3000 3200

Compressor Speed (rpm)

Fig. B.I. Influence of Condenser Length on COP

Influence of Condenser Length on Capacity

0.35;-~-r~'~~_~'-r~J~~~~-r~~'~~_~'~~

iii i \ i 9 o .3- ·····················-1-·····················+······················I·········Q········-1-·············· ······1·····················-1-····················· -

i condo air Tin iii rh <p (80 & 90 oF) 1 1 1 r

o .25 - ······················I······················t···~ .. ················/·········~·········l·················.···/····················t···················· r-i i II' iii :

0.2 ----!-·-···t·-!~ 1nd arr fliw mre t-···-O. 1 5 - ·····················4-·····················t······T············r·········~ 0 2975 lbm/hr condo air -

l I I x 3700lbm/hrcond.~ iii II 5150 lbm/hr condo arr

0.1~~~~1~~-~1~~1~~~1----~1-----~1--~

1800 2000 2200 2400 2600 2800 3000 3200

Compressor Speed (rpm)

Fig. B.2. Influence of Condenser Length on Capacity

38

Influence of Condenser Air Side U on COP

0.22 I I I I I ~

; I I § I I , o .2 - ·····················-r·····················r····················r····················-r·················\····r···················-r····················· r-

O. 18 - ····················*····················f············ ........ + ........ ~ ......... j .................... ..f.···················f···················· ~ ! cond. air Tin ! ! ~ !

0.1'6 - ······················1········· (80 & 90 oF) ·i······················j·······················i····· ................. j ...................... -

! i ! 6 condo air flow rate !

0.14--H-i~rj--t-r 0.12--i--I! ~ !r~l=Ea~-

i ! ! 0.1~~~+1~~-~1~~1~~~1-----~1--~1~--~

1800 2000 2200 2400 2600 2800 3000 3200

Compressor Speed (rpm)

Fig. B.3. Influence of Condenser Air Side U on COP

Influence of Condenser Air Side U on Capacity 0.14 I I ~ ~ I I

o 1 2 - ...................... 1.. .................... 1. .................... .1 ...................... 1. ............ \ ....... L ................... ~ .................... -. I con1 air Tin I 0 I I ~ <D ::::

o ~~: ~=r=~:r:·:-G:I;l=I:~=:: i I I c~nd. air fl~w rate l

::::~:=~~t=--f-~=P--~iste;~~i~ 0.02 I I I I I I

1800 2000 2200 2400 2600 2800 3000 3200

Compressor Speed (rpm)

Fig. B.4. Influence of Condenser Air Side U on Capacity

39

Influence of Condenser Refrigerant Side U on COP

0.34-~~4~~~-~i'~~~1~~~'~~~'~~-~'~~

i condo air Tin i

::::~ ~jJ~·:t~t.,tj~ * I I ~ I I ~ 0024--Hi--rmr rnre t-

0.22 - ······················,····················t···················t··········· ~ ~~~ ~~= ~~~~:: ~ iii f). 5150 Ibm/hr condo air

0.2;-~~~;~~-r,:~~~;~~~,-----~,----~,----r

1800 2000 2200 2400 2600 2800 3000 3200

Compressor Speed (rpm)

Fig. B.5. Influence of Condenser Refrigerant Side U on COP

Influence of Condenser Refrigerant Side U on Capacity

0.161-~~+'~~_~'~~'~~~'~~_~'~~y~~~

0\* O. 1 4 - .................... ~ ................... + ..................... + ..................... j ............... ······f·····················+····················· ~

i condo air Tin iii cb I (80 ~ 90 oF) I x I I 1

0.12 - ·····················f·················T·~················r······~·········r················fr···················f···················· -

001 --it -/:-t m fltw rnret- ~

Ooos----rrrr ~ ~r~!==~-0.06 I I I I I I

1800 2000 2200 2400 2600 2800 3000 3200

Compressor Speed (rpm)

Fig. B.6. Influence of Condenser Refrigerant Side U on Capacity

40

Influence of Condenser Pressure Drop on COP

-0.00054-~~~~~~_~I~~i~~~'~~~'~~_~I~~

.... -0 .001 - ····················~····················t······················I········g·········j·················· ····I·····················qL ................. '""" B iii Xii * ~ -0 .001 5 - ..................... * ......... cond air Tin 1······················j·················· ... ~ .................... ~ .................... -~ i (80 & 90 OF) i 0 iii c:: : : A: : A .g -0 . 002 - ····················-Q····················t············ .......... [......... ·········1················~ , ... [ ..................... * .................... r-.g ~ i ,~ i X l l i

~~~~:~~:~==-E=t=Ej~3~=: ~ 1 1 1 0 2975 Ibm/hr condo air

-0 .004 - ····················i···················+············· ...... +........... x 3700 Ibm/hr condo air r-i 1 1 f::. 5150 Ibm/hr condo air

-0.0045 ; : ; I I I

1800 2000 2200 2400 2600 2800 3000 3200

Compressor Speed (rpm)

Fig. B.7. Influence of Condenser Pressure Drop on COP

Influence of Condenser Pressure Drop on Capacity

-0.0002;-~~~1~~_~1~~1~~~1----~1----_~1--~ o 29751bm/hrcond.air

~ -0.0003 - ······················1······················+······················1············ x 3700 Ibm/hr condo ~ r-~ i l i f::. 5150 Ibm/hr condo alf ~ . d' T' . 5 -0.0004 - .................... ·9 ...... · (~3 & ~ 0:.) ·1 ........ ·0 ........ 1 .................... ·+ .................... + .................... ·-

!~:: :::: ~ :=·~;=i1-=t~-;ftj~=t:~:: '0 ~ 1 1 ~ 1 1 A I:ts - 0 . 0007 - .................. · .. ·1 ................ · .. · .. + ................... + ..................... ~ ....... : .............. f ..................... 'f .................... r-fJ< 1 1 1 condo alf flow rate 1

~ -0 .0008 - .................. · .. ·1 .................... ·+ .................... ·1 .................... ·+ ................... + .................... 1-................... r-! i ! ! ! !

-0.0009;-~~+:~~-r,:~~~;~~~;~~-~,:~~-,~: ~~~

1800 2000 2200 2400 2600 2800 3000 3200

Compressor Speed (rpm)

Fig. B.8. Influence of Condenser Pressure Drop on Capacity

41

Influence of Compressor Volume on COP

-0.484-~-r~'-r~~'~~~'~~_~'-r~~'-r~~'~~ . ~

-0 . 5 - .. ······ .... ··········/ ...................... j····· .. ··········· .... ·I .. ·······~· ...... ··j.· .... · ................ 1 ........ ····· ........ 6 .. ···· ............ ·· r-6 condo air !in l l l

- 0 . 52 - .................... ·f .. · .... · (80 i& 90 F) i ...................... 1" ..................... , ...................... 1" .................... -

: :,: : : ~ -0 . 54 - .................... ·t .................... ·j .. · .................. f ...................... j .................... · .. f ...................... t .................... r-; ; ; 0; ; ;

-0 . 5 6 --I-Ij-~!j-·+ ~ _ 0 58 - ...................... ; ...................... j ...................... ·i............ 0 2975 lbm/hr condo air -

. 0:: X 3700lbm/hrcond.air ± I I D. 5150 lbm/hr condo air -0.6~~~~,~~~,~~~,~~-~,----r-,----~,----r

1800 2000 2200 2400 2600 2800 3000 3200

Compressor Speed (rpm)

Fig. B.9. Influence of Compressor Volume on COP

Influence of Compressor Volume on Capacity

0.34

t ~ 0.3 ='

-0 > 0.26 ~ -' -C-.... 0.22 ~ §' U ~ 0.18

0.14

..................... ~ ..................... ~ ................... ) ...................... i ....................... 1 ...................... i .................... .. x : : D.' . : ! j j D. condo air flow rate j 8: ; ; ! ! ; . : : x: : :

...................... 1 ...................... ( .................. ·( .. · .............. ·: .............. · ...... ! ..................... ~ .................... . : : : x: : X l j l <:5 i l *

...................... 1.... condo air Tin ..... j .................... ) .................... ) .................... ..j ..................... .

I (80 & 90 OF) I I I $

-Ill ~ ~I~ leE :s: ~ 1800 2000 2200 2400 2600 2800 3000 3200

Compressor Speed (rpm)

Fig. B.I0. Influence of Compressor Volume on Capacity

42

Influence of Compressor Displacement on COP

-0.621-~~~'~~~'-r~~'~~~'~~_~'-r~~'-r~~ :::! i ; t

-0 . 64 - ···· .. ········ .. ······j···················· .. t· .. ··········· .. ·····+········~···· .. ···I······················+···· ................ + ..................... -~ condo air Tin . co~d. air fl~w rate *

o 2975 lbm/hr condo air e­x 37oolbm/hrcond.air

j j j l!1 5150 lbm/hr condo air -0.741-~~~I~~~,~~~,~~-~,----r-,----~,----r

1800 2000 2200 2400 2600 2800 3000 3200

Compressor Speed (rpm)

Fig. B.1l. Influence of Compressor Displacement on COP

Influence of Compressor Displacement on Capacity

0.44-~~~'~~~'~~~'~~_~'~~~'~~~'~~~

!

* o . 355 - ····················i····················t······················I·········~···· c~nd. air fl~w rate .. j ...................... r-

0.31 ---I <:i ~:~ J~l-!.~J- ~ 1 : 1 1 1 ),<

I I I I I ~ 0.265- ········ ...... · ...... ·j .. · ...... · ........ · .. ·t .. · .......... ·· ...... ·1 ...... · .. · ............ i ...................... .: ...................... i ..................... .

! ! ! 0 2975 lbm/hr condo air ! ! ! x 3700 lbm/hr condo air I I I l!1 5150 lbm/hr condo air

0.221-~~~,~~~,~~~,~~~,-----r-,----r-,----r

1800 2000 2200 2400 2600 2800 3000 3200

Compressor Speed (rpm)

Fig. B.12. Influence of Compressor Displacement on Capacity

43

Influence of Evaporator Air Side U on COP

0.08~~~~'~~_~'~~'~~~'----~'----_~'----r i l ' 0 2975 lbm/hr condo air

o .07 - ······················1····················+·····················1············ x 3700 lbm/hr condo air -~ i i ~ 5150Ibm/hrcond.air

o .06 - ······················1·· .. condo !rr flow ~te ··ts·······t·····················(···················l ...................... r-

0.05 - ····················t··················+····~········· ... + ........ ~ ......... j ................. ····1·····················1-··················· r-

:·::~:=~t=t:--~j~::t:t=t=~~ ~ . !! I 0 Icond.~Tin I

o . 02 - ·····················r···················r···················r···················"/" (80 & 90 OF) ........ ~ .................... r-! i ! i ! 0.01~~~~1~~-~1~~1~~~1~~~~1~~1~~~

1800 2000 2200 2400 2600 2800 3000 3200

Compressor Speed (rpm)

Fig. B.13. Influence of Evaporator Air Side U on COP

Influence of Evaporator Air Side U on Capacity

O 155 I 1 I I I I . 1---0--.29-7-5-lb-m/hr~-c-o-nd-.• arr-.~~~~~~~~~~i ~-r~

X 3700lbm/hrcond.air l 0.15 - ~ 5150 lbm/hr condo air ~·········J·······················i··················· ... j ...................... -

ii'

O. 1 45 - ·····················J····················t··· ·················f·········~·········j··· condo ~ Tin ....... j ...................... r-i ! ~ ! x ! (80 & 90 OF) ~

001·::~=h[:~:t::II=t~~~ I I I I I f 0.13;-~~+,~~-~,~~,~~~,~~-~,~~,~~~

1800 2000 2200 2400 2600 2800 3000 3200

Compressor Speed (rpm)

Fig. B.14. Influence of Evaporator Air Side U on Capacity

44

Influence of Evaporator Refrigerant Side U on COP 0.018 I I I I I I

0.016 - ················· .... t.··· ..... ····· ... ····t······················1············ ~ ~~~ ~~= ~~~~:: ~ 1 1 1 ~ 51501b~cond.arr 0.014- ······················i······················i-········ .............. ! ......... ~ ....... : ............................................................ .

! condo ~ flow ~te ! ! ! o . 0 1 2 - .................... )ir .................... , ...................... , ..................... .,. .................... , ...................... , ...................... -~ 1 ~ 1 ~ 1 1 t o .01 - ·····················+·····················t····· ···············I······················j··············· ... ····t······················!······················ -

~ i i xii ~

~:~~:~~=+=1= =T:~.r~~f=::=: iii i condo arrTm cb

0.004- ······················1······················t······················[······················1· (80 & 90 OF) ......... ( ................... -

0.0024-~~+!~~_~I1~~~!~~~!~~-~I~~~~~~ 1800 2000 2200 2400 2600 2800 3000 3200

Compressor Speed (rpm)

Fig. B.15. Influence of Evaporator Refrigerant Side U on COP

Influence of Evaporator Refrigerant Side U on Capacity

I:ci 0.038

8 0.036 ~ 0.034 c,.;;, fI)

~ F= 0.032 ~

~ 0.03 ~

0.028 --~ 0.026 .... ~ g.

0.024 u ~

0.022

o 29751b~cond.arr .................... A .................... L .................. .L........... x 3700 Ib~ condo arr

, 1 1 ~ 51501b~cond. arr ...................... , ... condo r flow rafe ················r···················· ., .................... 1" .................. . ·····················t·····················t······ ···········I·········~·········j······················I······················j······················

==~B=t __ ~!====£=~~f.:= iii 0 i condo arrTin i ······················j······················t······················1······················)··· (80 & 90 OF) ....... ) ..................... .

! ! ! i <b

1800 2000 2200 2400 2600 2800 3000 3200

Compressor Speed (rpm)

Fig. B.16. Influence of Evaporator Refrigerant Side U on Capacity

45

REFERENCES

Internal Publications

Kempiak, M. Three-Zone Modeling of a Mobile Air Conditioning Condenser. ACRC TR-03, April, 1991.

Siambekos, C. Two-Zone Modeling of a Mobile Air Conditioning Plate-Fin Evaporator. ACRC TR-05, October, 1991.

Darr,l. Modeling of an Automotive Air Conditioning Compressor Based on Experimental Data. ACRC TR-14, March, 1992.

VanderZee, 1. Semi-Theoretical Steady State and Transient Modeling of a Mobile Air Conditioning Condenser. ACRe TR-36, May, 1993.

Smith, S. Semi-Theoretical Steady State and Transient Modeling of an Automotive Air Conditioning Evaporator. ACRC TR-37, May, 1993.

External Reference

Eckels, S.l. and Pate, M.B.1991. Evaporation and Condensation of HFC-134a and CFC-12 in a Smooth Tube and a Micro-Fin Tube. ASHRAE Transactions Vol. 97 Part 2. Atlanta, GA.

46