MITSUBISHI ELECTRIC F700 VSD Presentation COPYRIGHT © 2010 MITSUBISHI ELECTRIC ASIA PTE LTD. ALL RIGHTS RESERVED. CONFIDENTIAL Product Manager: Leong Wai Mun

Upload: trinhnga

Post on 21-Aug-2018

225 views

Category:

Documents


1 download

TRANSCRIPT

MITSUBISHI ELECTRICF700 VSD Presentation

COPYRIGHT © 2010 MITSUBISHI ELECTRIC ASIA PTE LTD. ALL RIGHTS RESERVED.CONFIDENTIAL

Product Manager: Leong Wai Mun

Corporate Overview

COPYRIGHT © 2010 MITSUBISHI ELECTRIC ASIA PTE LTD. ALL RIGHTS RESERVED.CONFIDENTIAL

Corporate Overview

COPYRIGHT © 2010 MITSUBISHI ELECTRIC ASIA PTE LTD. ALL RIGHTS RESERVED.CONFIDENTIAL

Mitsubishi Electric Industrial Automation System Product Overview

Redundant Q-Series PLCs

L- Series DDCHMI

COPYRIGHT © 2010 MITSUBISHI ELECTRIC ASIA PTE LTD. ALL RIGHTS RESERVED.CONFIDENTIAL

Product Overview

HVAC VSDs

LVS & Measuring InstrumentsSCADA

Mitsubishi Electric Industrial Automation Solution

COPYRIGHT © 2010 MITSUBISHI ELECTRIC ASIA PTE LTD. ALL RIGHTS RESERVED.CONFIDENTIAL

Variable Speed Variable Speed DrivesDrives

FR-F700 Series

Product Portfolio

Main Features:-

� 10 years design life!!

� Life diagnostic check function!!

COPYRIGHT © 2010 MITSUBISHI ELECTRIC ASIA PTE LTD. ALL RIGHTS RESERVED.CONFIDENTIAL

Best suitable for Fans & Pumps

6060%% Energy reductionEnergy reduction(Compared to Motor direct)(Compared to Motor direct)

Global standard Inverter

� Easy dial function!

� Compact in size!

� Built-in EMC Filter!

VSD Product lineupVSD Product lineupVSD Product lineupVSD Product lineupF

unct

ion/

perf

orm

ance

Fun

ctio

n/pe

rfor

man

ce

FRFR--F700/F746F700/F746 For HVAC applications e.g fans and pumps

FRFR--A700A700Vector controlReal sensorless vector controlAdvanced magnetic flux vector controlV/F control

FRFR--F700 F700 HVAC / BA / PA HVAC / BA / PA SeriesSeries

COPYRIGHT © 2010 MITSUBISHI ELECTRIC ASIA PTE LTD. ALL RIGHTS RESERVED.CONFIDENTIAL

CapacityCapacity

Fun

ctio

n/pe

rfor

man

ceF

unct

ion/

perf

orm

ance

SCSC--AA Compact (name card size)

FRFR--D700D700 Easy operation with the setting dial/compact

FRFR--E700E700 General-purpose magnetic flux vector control/compac t

FRFR--C500C500 Built-in PLC function

FRFR--F500JF500J For small fans

Symbol Voltage

2 200V class

Symbol VSD Capacity

0.75K to560K

Indicate capacity (kW)

F R ---- FFFF 7 4 0 –––– 11 K

�VSD type

FRFR--F700 series ConfigurationF700 series ConfigurationFRFR--F700 series ConfigurationF700 series Configuration

COPYRIGHT © 2010 MITSUBISHI ELECTRIC ASIA PTE LTD. ALL RIGHTS RESERVED.CONFIDENTIAL

4 400V class 560K (kW)

�Model lineup

●:Available -:Not Available

Applied motor ((((kW))))

0.750.750.750.75 1.51.51.51.5 2.22.22.22.2 3.73.73.73.7 5.55.55.55.5 7.57.57.57.5 11111111 15151515 18.518.518.518.5 22222222 30303030 37373737 45454545 55555555 75757575 90909090 110110110110 132132132132 160160160160 185185185185 220220220220 250250250250 280280280280 315315315315 355355355355 400400400400 450450450450 500500500500 560560560560

200V classFR-F720-□□□□□□□□

●●●● ●●●● ●●●● ●●●● ●●●● ●●●● ●●●● ●●●● ●●●● ●●●● ●●●● ●●●● ●●●● ●●●● ●●●● ●●●● ●●●● ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----

400V classFR-F740-□□□□□□□□

●●●● ●●●● ●●●● ●●●● ●●●● ●●●● ●●●● ●●●● ●●●● ●●●● ●●●● ●●●● ●●●● ●●●● ●●●● ●●●● ●●●● ●●●● ●●●● ●●●● ●●●● ●●●● ●●●● ●●●● ●●●● ●●●● ●●●● ●●●● ●●●●

Protection ratings: IP20/IP54

• In addition to the IP20 protectionratings the VSDs in the output range upto 55kW are also available with an IP54 model(F746 Series)

COPYRIGHT © 2010 MITSUBISHI ELECTRIC ASIA PTE LTD. ALL RIGHTS RESERVED.CONFIDENTIAL

Numeric Protection from Solid Objects

Protected against solid objects > 12mm

Dust protected

Numeric Protection from moisture

Non protected

Protected against splashing water

IP

2 0

5 4

Secondary Chilled Water Pump Condenser Water Pumps Primary Chilled Water Pumps

COPYRIGHT © 2010 MITSUBISHI ELECTRIC ASIA PTE LTD. ALL RIGHTS RESERVED.CONFIDENTIAL

Key Application Area in HVAC System

VAV AHU Supply Fan Cooling Tower Fans Ventilation Fan Control System

CC-Link Cable

Fan

1

Fan

2

Fan

3

Fan

N

CC-Link Remote I/O

Terminal

Master PLC

• Fire Signal• CO Sensor

Repeater required for > 1km distance

(1) Impressive Savings with Optimum Excitation Cont rolOEC ensures that motor always gets optimum magnetic flux for maximum motor efficiency.

1.More Energy Savings 1.More Energy Savings

35Hz

COPYRIGHT © 2010 MITSUBISHI ELECTRIC ASIA PTE LTD. ALL RIGHTS RESERVED.CONFIDENTIAL

57% less power consumption

Additional 10% less power with OEC technology!

(2) Energy Saving Operations

COPYRIGHT © 2010 MITSUBISHI ELECTRIC ASIA PTE LTD. ALL RIGHTS RESERVED.CONFIDENTIAL

Best effect w/ 5 Points

Adjustable V/F control

(3) The effect of energy savings is obvious

The effect of energy savings can be confirmed using the operation panel, output terminal (FM, AM terminal) and via networks with the newly developed energy saving monitor .

COPYRIGHT © 2010 MITSUBISHI ELECTRIC ASIA PTE LTD. ALL RIGHTS RESERVED.CONFIDENTIAL

(1) Adjustable 5 points V/FPossible to set the torque pattern that is optimum for the machine’s characteristic.

Possible to expect even more energy savings with ‘Optimum Excitation Control’ and optimum V/F pattern working together.

2.Ideal for Fans and Pumps2.Ideal for Fans and Pumps

COPYRIGHT © 2010 MITSUBISHI ELECTRIC ASIA PTE LTD. ALL RIGHTS RESERVED.CONFIDENTIAL

(2) Enhanced PID function

Energy savings in low speed region…PID shutoff (sleep Mode) function

Monitor of PID set point/measured value/deviation possible

Shorter PID startup time…PID control switchover function

COPYRIGHT © 2010 MITSUBISHI ELECTRIC ASIA PTE LTD. ALL RIGHTS RESERVED.CONFIDENTIAL

Monitor of PID set point/measured value/deviation possible

Convenient for HVAC usage…forward/reverse operation switchover is simple using an external signal

Corresponds to a wide range of detectors…set point and measured value for PID input can either be voltage (0 to 5V/0 to 10V) or current (4 to 20mA)

Can be used for staircase fan control application and fire mode

(3) Automatic restarts after instantaneous power fa ilure

Operation continues without the motor coasting when an instantaneous power failure occurred in fan and blower applications.

The VSD may trip and the motor may coast depending on the load condition*

COPYRIGHT © 2010 MITSUBISHI ELECTRIC ASIA PTE LTD. ALL RIGHTS RESERVED.CONFIDENTIAL

condition*

15ms

(4) Flying start

Smoothly restarts a motor that is rotating even in the opposite direction due to the windmill effect.

(5) Regeneration avoidance function

COPYRIGHT © 2010 MITSUBISHI ELECTRIC ASIA PTE LTD. ALL RIGHTS RESERVED.CONFIDENTIAL

(5) Regeneration avoidance function

Avoid shutdown due to regenerative overvoltage load. Temporarily increases the output frequency above the setpoint and continue operation when the inverter-controlled fan set speed is increased by the draft from another fan operating in the same duct.

(6) PTC thermistor input

Protect the motor from overheating with the built-in PTC of the motor input directly to the inverter electronic thermal relay function.

COPYRIGHT © 2010 MITSUBISHI ELECTRIC ASIA PTE LTD. ALL RIGHTS RESERVED.CONFIDENTIAL

(1) Operating life of parts are further lengthened

Newly developed cooling fan (design life of 10 years). ON/OFF control of the cooling fan.

Long life of capacitors (design life of 10 years).

3.Long Life and Simple Operation3.Long Life and Simple Operation

COPYRIGHT © 2010 MITSUBISHI ELECTRIC ASIA PTE LTD. ALL RIGHTS RESERVED.CONFIDENTIAL

Long life of capacitors (design life of 10 years).

Life indication of the components

*3. Excerpts from “Periodic check of the transistorized inverter” of JEMA (Japan Electrical Manufacturer’s Association)

Display the life of inverter parts:-- Main circuit capacitor- Control circuit capacitor - Inrush current limit circuit- Cooling fan

Automatic life alarm can be output and triggered when end of service life reached.

(2) Parts life diagnostic check function

Excellent for preventive

maintenance!!

COPYRIGHT © 2010 MITSUBISHI ELECTRIC ASIA PTE LTD. ALL RIGHTS RESERVED.CONFIDENTIAL

service life reached.Automatic life alarm output signal

• Easy replacement of cooling fancassette without disconnecting main circuit wires

• Parameter Copy and Paste formultiple settings

• RS-485 terminal• Up to past 8 alarm history canbe displayed

(3) Improved workability

COPYRIGHT © 2010 MITSUBISHI ELECTRIC ASIA PTE LTD. ALL RIGHTS RESERVED.CONFIDENTIAL

• Wiring is easy with thecombed shaped wire cover

• Removable terminal block

Comparison of Dimensions for 37KW Inverter Drives

COPYRIGHT © 2010 MITSUBISHI ELECTRIC ASIA PTE LTD. ALL RIGHTS RESERVED.CONFIDENTIAL

Mitsubishi Mitsubishi Electric F700Electric F700

European European Inverter DriveInverter Drive

(1) Reduction of electromagnetic noises

VSD noises have been reduced with the adoption of newly developed built-in EMC filter.

4.Free of Environmental Worries4.Free of Environmental Worries

VSD complies to EMC Directive (1st & 2nd

COPYRIGHT © 2010 MITSUBISHI ELECTRIC ASIA PTE LTD. ALL RIGHTS RESERVED.CONFIDENTIAL

VSD complies to EMC Directive (1st & 2nd

Environment, category C1, C2), EN55011 Standards (Conduction, immunity).

(2) Countermeasures for harmonics current output

Low Harmonics Drive – complies to EN61000-3-12(built-in DC Harmonic Link)AC reactor and DC reactor options* for further suppression of harmonics current & power factor improvements can be connected. AC reactor (FR-

HAL)DC reactor (FR-

HEL)* DC reactor standard for 75kW and above

COPYRIGHT © 2010 MITSUBISHI ELECTRIC ASIA PTE LTD. ALL RIGHTS RESERVED.CONFIDENTIAL

Connection with high power factor converter(FR-HC/M T-HC) is possible for effective suppressions of power-supply harmonics to 5% THDi at the VSD incoming point.

(3) Equipped with inrush current limit circuit

Because of the built-in inrush current limit circuit, thecurrent at power on is restricted to prevent overcurrent.

HAL) HEL)* DC reactor standard for 75kW and above

(1) Equipped with the setting dial

Operation is easy with the setting dial.

Frequency and parameters can be set without frustrations.

5.Simple operation5.Simple operation

COPYRIGHT © 2010 MITSUBISHI ELECTRIC ASIA PTE LTD. ALL RIGHTS RESERVED.CONFIDENTIAL

Operation panel is detachable. (Cable connector option is required)

Dial/Key operation lock function.

PU/EXT (operation mode) switchover key.

(2) Simple Testing & Commissioning

COPYRIGHT © 2010 MITSUBISHI ELECTRIC ASIA PTE LTD. ALL RIGHTS RESERVED.CONFIDENTIAL

(1) RS-485 terminal is standard equipped

6.Enhanced Networks6.Enhanced Networks

The RS-485 terminals are equipped as standard in addition to the PU connector.

RS-485 terminal

COPYRIGHT © 2010 MITSUBISHI ELECTRIC ASIA PTE LTD. ALL RIGHTS RESERVED.CONFIDENTIAL

Modbus-RTU (Binary) protocol – Standard Built-InMitsubishi Electric VSD protocol

PU connector:The operation panel or parameter unit can be connected

ORRS485-terminal:

Multi-drop connection is also easily done with other VSDs

terminal

(2) Possible to correspond with major networks

Possible to connect various communications protocol as such• RS-485 / Modbus-RTU(Built-in)• LON Works• Profibus / DP• CC-Link• Devicenet

Metasys -N2

COPYRIGHT © 2010 MITSUBISHI ELECTRIC ASIA PTE LTD. ALL RIGHTS RESERVED.CONFIDENTIAL

• Metasys -N2• BACNet (EC series)

(1) Complies with UL, cUL, EN (LVD) standards

7.Global Compliance7.Global Compliance

COPYRIGHT © 2010 MITSUBISHI ELECTRIC ASIA PTE LTD. ALL RIGHTS RESERVED.CONFIDENTIAL

(2) Possible to switch sink/source with one-touchPossible to switch the logic of I/O terminals. Possible to use inall regions.

(3) Wide voltage rangeAccommodate both 240 V power supply (55K or less) and480V power supply as standard.

(1) Remote output function

You can utilize the on/off of the VSD's output signals instead of the remote output function of the programmable logic controller.

(2) Enhanced I/O is standard

8.Wide Range of Functions8.Wide Range of Functions

COPYRIGHT © 2010 MITSUBISHI ELECTRIC ASIA PTE LTD. ALL RIGHTS RESERVED.CONFIDENTIAL

12 contact inputs, 3 analog inputs, 5 open collector outputs, 2 relay outputs, analog output and pulse output are all standard.

Possible to assign variety of functions to contact inputs, open collector outputs and relay outputs.

Possible to switch between voltage and current for the analog input.

Possible to display the ON/OFF status of the I/O terminals on the operation panel.

Market Leader in AsiaMarket Leader in Asia

COPYRIGHT © 2010 MITSUBISHI ELECTRIC ASIA PTE LTD. ALL RIGHTS RESERVED.CONFIDENTIAL

MITSUBISHI F700 VSD – MAIN BENEFITSLONG LIFE 10 YEARS – SAVE RESOURCES!

LIFE DIAGNOSIS FUNCTION – MAINTENANCE TIMER TRACK LIFESPAN + LIFE ALARM SIGNAL OUTPUT

HIGH MTTF 87360 hrs (Mean Time To Failure) LOW HEAT DISSIPATION – No Over-Heating

COPYRIGHT © 2010 MITSUBISHI ELECTRIC ASIA PTE LTD. ALL RIGHTS RESERVED.CONFIDENTIAL

COMPACT SIZE; EASE OF USE – SIMPLE DIAL (EASY OPERATION)

COUNTRY ORIGIN, MANUFACTURE: JAPAN, NAGOYA WORKS

WIDELY RECOGNITION BY M&E CONSULTANTS

MITSUBISHI CSR ACHIEVEMENT & COMMITMENT TOWARDS GREEN VISION

COMMITTED TOWARDS ENVIRONMENTAL PRESERVATION AND EN ERGY

MITSUBISHI ELECTRIC CORPORATION ANNOUNCEMENT OF “ENVIRONMENTAL VISION 2021”

COPYRIGHT © 2010 MITSUBISHI ELECTRIC ASIA PTE LTD. ALL RIGHTS RESERVED.CONFIDENTIAL

COMMITTED TOWARDS ENVIRONMENTAL PRESERVATION AND EN ERGY SAVINGS -- 3Rs (REDUCE, REUSE, RECYCLE)

COMPLY WITH THE EU RoHS DIRECTIVES TO USE ALTERNATIVES TO HAZARDOUS SUBSTANCES

COPYRIGHT © 2010 MITSUBISHI ELECTRIC ASIA PTE LTD. ALL RIGHTS RESERVED.CONFIDENTIAL

MITSUBISHI VSD AWARDS

HONORABLE AWARDS AT 2006 ELECTRICAL MANUFACTURERS AWARDS awarded BY JAPAN ELECTRICAL MANUFACTURERS ASSOCIATION

LONG LIFE OF 10 YEARS OR MAJOR CONSUMABLES, EFFECTIVELY

COPYRIGHT © 2010 MITSUBISHI ELECTRIC ASIA PTE LTD. ALL RIGHTS RESERVED.CONFIDENTIAL

MITSUBISHI ELECTRIC, RATED TOP “4” GREEN COMPANIES IN 2005 BY PORTFOLIO 21, GLOBAL MUTUAL FUND THAT INVESTS IN COMPANIES MAKING REAL CONTRIBUTIONS TO A SUSTAINABL E FUTURE

HELP SAVE RESOURCES

IMS AWARD 2003 – EUROPEAN MOTOR DRIVE OF THE YEAR 2003