SEGMENTAL RETAINING WALL - DESIGN CHART (USA) MINI-CRETA 3” & 6”

Upload: others

Post on 20-Aug-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: MINI-CRETA 3” & 6”...DESIGN CHART 3 45657No su 4 HDPE VERTICAL KEY (alignment pin) TECHNICAL SPECIFICATIONS PHYSICAL CHARACTERISTICS DESIGN DATA MINI-CRETA 3” MINI-CRETA 6”

SEGMENTAL RETAINING WALL - DESIGN CHART (USA)

MINI-CRETA 3” & 6”

Page 2: MINI-CRETA 3” & 6”...DESIGN CHART 3 45657No su 4 HDPE VERTICAL KEY (alignment pin) TECHNICAL SPECIFICATIONS PHYSICAL CHARACTERISTICS DESIGN DATA MINI-CRETA 3” MINI-CRETA 6”

D E S I G N C H A R T M I N I - C R E TA

2

TABLE OF CONTENTS

PREFACE 3

PRODUCT OVERVIEW & TECHNICAL SPECIFICATIONS 4

PATTERNS 5

DESIGN CHARTS: NOTES AND ASSUMPTIONS 6

TYPICAL CROSS SECTION DETAILS 7

CLEAN SAND / GRAVEL /SAND & GRAVEL MIXES

Case N° 1: No surcharge, No backslope, No Toe Slope 8 (20)

Case N° 2: 100 psf Surcharge (1 ft behind wall), No backslope, No Toe Slope 9 (21)

Case N° 3: 250 psf Surcharge (1 ft behind wall), No backslope, No Toe Slope 10 (22)

Case N° 4: No surcharge, 1V:3H backslope, No Toe Slope 11 (23)

FINE SANDS & SILTY SANDS

Case N° 5: No surcharge, No backslope, No Toe Slope 12 (24)

Case N° 6: 100 psf Surcharge (1 ft behind wall), No backslope, No Toe Slope 13 (25)

Case N° 7: 250 psf Surcharge (1 ft behind wall), No backslope, No Toe Slope 14 (26)

Case N° 8: No surcharge, 1V:3H backslope, No Toe Slope 15 (27)

LOW PLASTICITY SILTS AND CLAYS

Case N° 9: No surcharge, No backslope, No Toe Slope 16 (28)

Case N° 10: 100 psf Surcharge (1 ft behind wall), No backslope, No Toe Slope 17 (29)

Case N° 11: 250 psf Surcharge (1 ft behind wall), No backslope, No Toe Slope 18 (30)

Case N° 12: No surcharge, 1V:3H backslope, No Toe Slope 19 (31)

(#) for near vertical walls

Page 3: MINI-CRETA 3” & 6”...DESIGN CHART 3 45657No su 4 HDPE VERTICAL KEY (alignment pin) TECHNICAL SPECIFICATIONS PHYSICAL CHARACTERISTICS DESIGN DATA MINI-CRETA 3” MINI-CRETA 6”

D E S I G N C H A R T M I N I - C R E TA

3

PREFACE

This document contains the design charts for the MINI-CRETA segmental retaining wall system with or without the use of geogrid reinforcement. The charts help to determine under specific conditions the maximum possible wall height without geogrid and for higher walls the necessary geogrid length and positioning.

First, evaluate the proposed conditions for the retaining wall project. It is important to determine the soil type, the load or surcharge and the backslope/toeslope conditions that most closely represent the final constructed wall. Second, select the chart case number and setback position (near vertical or 5.3° batter) that most closely resembles the final project conditions. Finally, select the wall height (including embedment) that will best fit the project wall profile.

This document has been prepared for the following cases:

SOIL SURCHARGE BACKSLOPE TOESLOPE

CASE N° 1 Clean sand / gravel /sand & gravel mixes No No No

CASE N° 2 Clean sand / gravel /sand & gravel mixes 100 psf (1 ft behind the wall) No No

CASE N° 3 Clean sand / gravel /sand & gravel mixes 250 psf (1 ft behind the wall) No No

CASE N° 4 Clean sand / gravel /sand & gravel mixes No 1V : 3H No

CASE N° 5 Fine Sands & Silty Sands No No No

CASE N° 6 Fine Sands & Silty Sands 100 psf (1 ft behind the wall) No No

CASE N° 7 Fine Sands & Silty Sands 250 psf (1 ft behind the wall) No No

CASE N° 8 Fine Sands & Silty Sands No 1V : 3H No

CASE N° 9 Low Plasticity Silts and Clays No No No

CASE N° 10 Low Plasticity Silts and Clays 100 psf (1 ft behind the wall) No No

CASE N° 11 Low Plasticity Silts and Clays 250 psf (1 ft behind the wall) No No

CASE N° 12 Low Plasticity Silts and Clays No 1V : 3H No

The information contained in this document is supplied for information purposes only and as such should only be used for preliminary design use only. A qualified engineer should be consulted for the final design to be used for construction. Techo-Bloc and its predecessors, successors, beneficiaries, employees, associates, administrators and insurers can not under any circumstances be held liable for the incorrect use of information contained in the design charts.

Page 4: MINI-CRETA 3” & 6”...DESIGN CHART 3 45657No su 4 HDPE VERTICAL KEY (alignment pin) TECHNICAL SPECIFICATIONS PHYSICAL CHARACTERISTICS DESIGN DATA MINI-CRETA 3” MINI-CRETA 6”

D E S I G N C H A R T M I N I - C R E TA

4

HDPE VERTICAL KEY (alignment pin)

TECHNICAL SPECIFICATIONS

PHYSICAL CHARACTERISTICS DESIGN DATA MINI-CRETA 3” MINI-CRETA 6”

Compressive Strength 5050 psi (35 MPa) Horizontal Setback 9/32 in. (7 mm) 9/16 in. (14 mm)

Water Absorption (max.) 9 lb/ft3 (144 kg/m3) Infilled Unit Weight 127 pcf (20.0 kN/m3)

Freeze-Thaw1.0% max. loss of mass after 100 cycles 1.5% max. loss of mass after 150 cycles

Infilled center of gravity(measured from the face of the unit) 4 15/16 in. (125 mm)

Dimensional Tolerances Height: ± 1/16 in. [1.5 mm] Length & Width: ± 1/8 in. [3 mm] Block Shear Strength (ASTM D 6916) Vub[lb/ft] = 0.68 + N*tan(34.5) ≤ 1892

Vub[kN/m] = 0.01 + N*tan(34.5) ≤ 27.61

Note: Meets and exceeds the requirements of the ASTM C 1372 Standard Specification for Dry-Cast Segmental Retaining Wall Units.

Block -Geogrid Shear Strength (Miragrid 3XT) (ASTM D 6916)

Vug[lb/ft] = 313 + N*tan(32.3) ≤ 2051 Vug[kN/m] = 4.6+ N*tan(32.3) ≤ 30

Block - Geogrid Connection Strength (Miragrid 3XT) (ASTM D 6638)

Tc[lb/ft] = 763 + N*tan(24.5) ≤ 2008 Tc[kN/m] = 11.14 + N*tan(24.5) ≤ 29.3

Note: The infilled unit weight shown here is based on an assumed aggregate unit weight of 96.8 lb/ft³ (1550 kg/m³) used to fill the core cavity of the block and the space between adjacent blocks.

UNIT A (Approx. weight) UNIT B (Approx. weight) UNIT B* (Approx. weight)

3” 17 lbs (7.8 kg) 23 lbs (10.5 kg) 25 lbs (11.4 kg)

6” 36 lbs (16.3 kg) 48 lbs (21.8 kg) 52 lbs (23.8 kg)

9 1/16"

(230 mm)9 13/16"

(250 mm)

7 1/16"

(180 mm)

2 15/16" / 5 7/8"

(75 mm / 150 mm)

11 13/16"

(300 mm)

9 13/16"

(250 mm)

9 13/16"(250 mm)

2 15/16" / 5 7/8"

(75 mm / 150 mm)

11 13/16"

(300 mm)

11 13/16"

(300 mm)

9 13/16"(250 mm)

2 15/16" / 5 7/8"

(75 mm / 150 mm)

UNIT C (Approx. weight) UNIT D (Approx. weight)

3” 29 lbs (13.3 kg) 31 lbs (14.1 kg)

6” 61 lbs (27.7 kg) 64 lbs (29.1 kg)

1'-2 3/4"

(375 mm)

1'-0 13/16"

(325 mm)

9 13/16"(250 mm)

2 15/16" / 5 7/8"

(75 mm / 150 mm)

1'-2 3/4"

(375 mm)

1'-1 3/4"

(350 mm)

9 13/16"(250 mm)

2 15/16" / 5 7/8"

(75 mm / 150 mm)

PRODUCT OVERVIEW

1"(25 mm)

3 3/16"

(80 mm)

1 1/4"(32 mm)

1"(25 mm)

3 3/16"

(80 mm)

1 1/4"(32 mm)

Page 5: MINI-CRETA 3” & 6”...DESIGN CHART 3 45657No su 4 HDPE VERTICAL KEY (alignment pin) TECHNICAL SPECIFICATIONS PHYSICAL CHARACTERISTICS DESIGN DATA MINI-CRETA 3” MINI-CRETA 6”

D E S I G N C H A R T M I N I - C R E TA

5

*See www.techo-bloc for more pattern combination examples

1-ROW PATTERN (3” + 6”)

8.9’(2.7m) long x 5 7/8” (150 mm) high | 5 different combinations*

67% Mini-Creta 3” | 33% Mini-Creta 6”

3-ROW PATTERN (3” + 6”)

8.9’(2.7m) long x 17 11/16” (450 mm) high | 4 different combinations*

78% Mini-Creta 3” | 22% Mini-Creta 6”

5-ROW PATTERN (3” + 6”)

8.9’(2.7m) long x 29 1/2” (750 mm) high | 3 different combinations*

73% Mini-Creta 3” | 27% Mini-Creta 6”

PATTERNS

MINI CRETA 3” LINEAR PATTERN

MINI CRETA 6” LINEAR PATTERN

Page 6: MINI-CRETA 3” & 6”...DESIGN CHART 3 45657No su 4 HDPE VERTICAL KEY (alignment pin) TECHNICAL SPECIFICATIONS PHYSICAL CHARACTERISTICS DESIGN DATA MINI-CRETA 3” MINI-CRETA 6”

D E S I G N C H A R T M I N I - C R E TA

6

DESIGN CHARTS: NOTES AND ASSUMPTIONS

This preliminary guide has been prepared for three different soil types to approximate good (Clean sand / gravel /sand & gravel mixes), medium (Fine Sands & Silty Sands) and poor (Low Plasticity Silts and Clays) soil conditions to cover the typical design range. The description of the soil is provided for information purposes; it is the actual shear strength parameter that will govern the design.

Additionally, the following four different load conditions were considered:

I. A horizontal surface above the wall with no surcharge to account for lawn or similar load conditions.

II. A horizontal surface above the wall with a uniform surcharge of 100 psf (4.8 kPa) to account for paved surfaces and/or parking or alleys for car and light vehicles traffic.

III. A horizontal surface above the wall with a uniform surcharge of 250 psf (12 kPa) to account for heavy vehicle traffic or fire lanes.

IV. A 1V:3H slope above the wall (backslope).

Furthermore, each case contains two setback alternatives: one for a wall with 5.3° batter and one for a near vertical wall. Near vertical walls have a slight positive batter (1.7°) achieved by tilting the top surface of the leveling pad from front to back.

All surcharges are applied at least 12 inches behind the tail of the units and No slope below the wall (Toeslope) conditions were considered. The design parameters and additional assumptions are shown in each chart.

The design charts show the number, position, and length of the geogrids for a Techo-Bloc Mini-Creta wall, based on the height of the wall, the soil type and the load conditions. The wall height varies approximately from 1 ft (0.30 m) to 7.83 ft (2.40 m), gradually increasing in height increments of 0.50-1.48 ft (0.15-0.45 m). The wall height shown does not include the thickness of the cap.

First drawing of each case shows maximum height without geogrid under the specific conditions shown. Minimum reinforcement lengths were set to 4 feet (1.22 m) and a 70% reinforcement length to wall height ratio. All geogrid lengths shown are the actual lengths of geogrid required as measured from the front wall face to the end of the geogrid. The charts assume the use of geogrid Miragrid 3XT (by TenCate) with Tult=3500 plf (51.1 kN/m).

The geogrid and block positioning are shown with reference to Mini-Creta 6’’ units installed in a linear pattern. Any other pattern choice must respect geogrid elevation positions. For walls with Mini-Creta 3” units, simply stack two Mini-Creta 3” units for every block shown in the chart. For walls combining Mini-Creta 3” and 6” units, the 1-row pattern or 3-row pattern are recommended for ease of geogrid positioning.

Unless shown otherwise in the charts: top layers of geogrid shall never be more than 2 units from the top of the wall; and bottom layers of geogrid shall never be more than 2 units from the top of the leveling pad.

The design charts contained herein have been compiled and prepared by Techo-Bloc and to the best of its knowledge. Final determination of the suitability for the use of this document is the sole responsibility of the user. Structural design and analysis for construction purposes shall be performed, using the actual conditions of the proposed site, by a registered Professional Engineer. For further information, please contact our technical service department.

Page 7: MINI-CRETA 3” & 6”...DESIGN CHART 3 45657No su 4 HDPE VERTICAL KEY (alignment pin) TECHNICAL SPECIFICATIONS PHYSICAL CHARACTERISTICS DESIGN DATA MINI-CRETA 3” MINI-CRETA 6”

D E S I G N C H A R T M I N I - C R E TA

7

Geogrid length 3/4'' (20 mm)clean stone toextend at least 14''(350 mm) behindblocks

Geotextile

Perforated drain pipedraining to daylight orconnected to existingdrainage system

Leveling pad (As specified byEngineer)

Retained soil

Foundation soil

Mini-Creta 6"Block

Cap fromTecho-Bloc

Wall inclination(5.3°)

ExposedHeight

Embedment depth

Geogrid

Reinforced soil

Topsoil

Surcharge offset distance

Low permeabilitysoil

Backslope

ToeSlope

Surcharge

(5.3° BATTER)

HDPE horizontalkey inserted in

the back groove

Linear pattern or

3 row pattern

ExposedHeight

Embedment depth

Toeslope

Surcharge offset distance

Backslope (H:V)

TopsoilLow permeability soil

3/4'' (20 mm) clean stone to extendat least 14'' (350 mm) behind blocksGeotextile

Leveling pad. A negative 3.0 % minimumleveling pad slope is recommended. A3.0% slope is equivalent to an elevationdrop of 3/8 " along 12"

Retained soil

Foundation soil

Mini-creta 6" Block

HDPE horizontalkey inserted in the

front groove

Cap from Techo-Bloc

Wall inclination(+/-1.7°)

Surcharge

Perforated drain pipe draining to daylightor connected to existing drainage system

3.0 %

(NEAR VERTICAL)

GRAVITY WALL: TYPICAL CROSS SECTION DETAIL

REINFORCED WALL: TYPICAL CROSS SECTION DETAIL

Geogrid length3/4'' (20 mm)clean stone toextend at least14'' (350 mm)behind blocks

Geotextile

Perforated drain pipedraining to daylightor connected toexisting drainagesystem

Retained soil

Foundation soil

Mini-Creta6" Block

Cap fromTecho-Bloc

Wall inclination(+/-1.7°)

ExposedHeight

Embedment depth

Geogrid

Reinforced soil

Surcharge offset distance

ToeSlope

Surcharge

HDPE horizontalkey inserted in

front groove

Linear patternor

3 row pattern

TopsoilLow permeabilitysoil

Leveling pad (As Specified byEngineer). A negative 3.0 %minimum leveling pad slope isrecommended. A 3.0% slope isequivalent to an elevation drop of3/8 " along 12".

3.0 %

(NEAR VERTICAL)

ExposedHeight

Embedment depth

Toeslope

Surcharge offset distance

Backslope (H:V)

TopsoilLow permeability soil

3/4'' (20 mm) clean stone toextend at least 14'' (350 mm)behind blocksGeotextile

Leveling pad (AsSpecified by Engineer)

Retained soil

Foundation soil

Mini-creta 6" Block

HDPE horizontal key insertedin the back groove

Cap from Techo-Bloc

Wall inclination(5.3°)

Surcharge

Perforated drain pipe draining todaylight or connected to existingdrainage system

(5.3° BATTER)

Page 8: MINI-CRETA 3” & 6”...DESIGN CHART 3 45657No su 4 HDPE VERTICAL KEY (alignment pin) TECHNICAL SPECIFICATIONS PHYSICAL CHARACTERISTICS DESIGN DATA MINI-CRETA 3” MINI-CRETA 6”

8

CASE N° 1 :No SurchargeNo BackslopeNo Toe Slope

CLEAN SAND/GRAVEL/ SAND AND GRAVEL MIXES (Ø=34°, = 120 pcf)GEOGRID: MIRAGRID 3XT BY TENCATE (RFd=1.10, RFcr=1.45, RFid=1.25, Cds=0.9, Ci=0.9)

1. The information contained in the design charts is supplied for information purposes only and as such should only be used for preliminarydesigns.

2. The height (H) of the wall is the total height from the leveling pad to the top of the wall not including the thickness of the cap.3. Soil parameters: reinforced soil (φ = 34°, γ = 120 pcf); retained soil (φ =34°, γ = 120 pcf); foundation soil (φ=34°, γ = 120 pcf)4. A qualified engineer should be consulted for the final design to be used for construction.5. The foundation soil must be able to support the wall system. The bearing capacity of the foundation soil, settlement, and global stability

must be verified and validated by a qualified geotechnical engineer.6. The seismic analysis is not included.7. The design charts do not apply to tiered walls.8. The charts assume that the walls are constructed in accordance with Techo-Bloc specifications, good construction practice and an

adequate drainage system.9. The geogrid layout has been optimized to satisfy the design requirements of the NCMA's Design Manual for Segmental Retaining Walls,

3rd Edition.10. The minimum burial depth must be 6 in (150 mm) or 10% of the exposed height, whichever is greater.11. Engineering judgement should be used when interpolating between heights.

12. Techo-Bloc and its predecessors, successors, beneficiaries, employees, associates, administrators and insurers accepts no liability forthe incorrect use of information contained in the design charts.

13. For further information, please contact our technical service department.

DESIGN CHARTMINI-CRETA 6"

(EQUIVALENT TO TWICE THE MINI-CRETA 3")SETBACK POSITION

6'-0'' (1.83 m)

6'-0'' (1.83 m)

7'-10"(2.40m)

4'-0'' (1.22 m)4'-0'' (1.22 m)

4'-0'' (1.22 m)

6'-5"(1.95m)

4'-11"(1.50m)

2'-6"(0.75m)

2'-11"(0.90m)

3'-11"(1.20m)

5'-0'' (1.52 m)

5'-0'' (1.52 m)

5'-0'' (1.52 m)

5'-0'' (1.52 m)

6'-0'' (1.83 m)

6'-0'' (1.83 m)

6'-0'' (1.83 m)

4'-6'' (1.37 m)

4'-6'' (1.37 m)

4'-6'' (1.37 m)

5.3°5.3°

5.3°

5.3°5.3°

5.3°

Page 9: MINI-CRETA 3” & 6”...DESIGN CHART 3 45657No su 4 HDPE VERTICAL KEY (alignment pin) TECHNICAL SPECIFICATIONS PHYSICAL CHARACTERISTICS DESIGN DATA MINI-CRETA 3” MINI-CRETA 6”

9

2'-0"(0.60m)

2'-11"(0.90m) 4'-0'' (1.22 m)

3'-5"(1.05m)

4'-0'' (1.22 m)

4'-0'' (1.22 m)

4'-11"(1.50m)

6'-5"(1.95m)

5'-0'' (1.52 m)

5'-0'' (1.52 m)

5'-0'' (1.52 m)

5'-0'' (1.52 m)

6'-0'' (1.83 m)

6'-0'' (1.83 m)

7'-10"(2.40m)

6'-0'' (1.83 m)

6'-0'' (1.83 m)

6'-0'' (1.83 m)

1'-0"(0.30m) 100 psf

1'-0"(0.30m) 100 psf

1'-0"(0.30m) 100 psf

1'-0"(0.30m) 100 psf

1'-0"(0.30m) 100 psf

1'-0"(0.30m) 100 psf

4'-6'' (1.37 m)

4'-6'' (1.37 m)

4'-6'' (1.37 m)

CASE N° 2 :100 psf Surcharge (1 ft behind the wall)No BackslopeNo Toe Slope

CLEAN SAND/GRAVEL/ SAND AND GRAVEL MIXES (Ø=34°, = 120 pcf)GEOGRID: MIRAGRID 3XT BY TENCATE (RFd=1.10, RFcr=1.45, RFid=1.25, Cds=0.9, Ci=0.9)

1. The information contained in the design charts is supplied for information purposes only and as such should only be used for preliminarydesigns.

2. The height (H) of the wall is the total height from the leveling pad to the top of the wall not including the thickness of the cap.3. Soil parameters: reinforced soil (φ = 34°, γ = 120 pcf); retained soil (φ =34°, γ = 120 pcf); foundation soil (φ=34°, γ = 120 pcf)4. A qualified engineer should be consulted for the final design to be used for construction.5. The foundation soil must be able to support the wall system. The bearing capacity of the foundation soil, settlement, and global stability

must be verified and validated by a qualified geotechnical engineer.6. The seismic analysis is not included.7. The design charts do not apply to tiered walls.8. The charts assume that the walls are constructed in accordance with Techo-Bloc specifications, good construction practice and an

adequate drainage system.9. The geogrid layout has been optimized to satisfy the design requirements of the NCMA's Design Manual for Segmental Retaining Walls,

3rd Edition.10. The minimum burial depth must be 6 in (150 mm) or 10% of the exposed height, whichever is greater.11. Engineering judgement should be used when interpolating between heights.

12. Techo-Bloc and its predecessors, successors, beneficiaries, employees, associates, administrators and insurers accepts no liability forthe incorrect use of information contained in the design charts.

13. For further information, please contact our technical service department.

DESIGN CHARTMINI-CRETA 6"

(EQUIVALENT TO TWICE THE MINI-CRETA 3")SETBACK POSITION

5.3°

5.3° 5.3°

5.3°5.3°

5.3°

Page 10: MINI-CRETA 3” & 6”...DESIGN CHART 3 45657No su 4 HDPE VERTICAL KEY (alignment pin) TECHNICAL SPECIFICATIONS PHYSICAL CHARACTERISTICS DESIGN DATA MINI-CRETA 3” MINI-CRETA 6”

10

1'-6"(0.45m)

1'-0"(0.30m)

4'-0'' (1.22 m)

3'-5"(1.05m)

4'-0'' (1.22 m)

1'-0"(0.30m) 250 psf

250 psf

2'-0"(0.60m)

1'-0"(0.30m)

4'-0'' (1.22 m)

250 psf

4'-11"(1.50m)

6'-5"(1.95m)

1'-0"(0.30m) 250 psf

1'-0"(0.30m) 250 psf

7'-10"(2.40m)

1'-0"(0.30m) 250 psf

4'-6'' (1.37 m)

4'-6'' (1.37 m)

4'-6'' (1.37 m)

5'-6'' (1.68 m)

5'-6'' (1.68 m)

5'-6'' (1.68 m)

5'-6'' (1.68 m)

6'-6'' (1.98 m)

6'-6'' (1.98 m)

6'-6'' (1.98 m)

6'-6'' (1.98 m)

6'-6'' (1.98 m)

CASE N° 3 :250 psf Surcharge (1 ft behind the wall)No BackslopeNo Toe Slope

CLEAN SAND/GRAVEL/ SAND AND GRAVEL MIXES (Ø=34°, = 120 pcf)GEOGRID: MIRAGRID 3XT BY TENCATE (RFd=1.10, RFcr=1.45, RFid=1.25, Cds=0.9, Ci=0.9)

1. The information contained in the design charts is supplied for information purposes only and as such should only be used for preliminarydesigns.

2. The height (H) of the wall is the total height from the leveling pad to the top of the wall not including the thickness of the cap.3. Soil parameters: reinforced soil (φ = 34°, γ = 120 pcf); retained soil (φ =34°, γ = 120 pcf); foundation soil (φ=34°, γ = 120 pcf)4. A qualified engineer should be consulted for the final design to be used for construction.5. The foundation soil must be able to support the wall system. The bearing capacity of the foundation soil, settlement, and global stability

must be verified and validated by a qualified geotechnical engineer.6. The seismic analysis is not included.7. The design charts do not apply to tiered walls.8. The charts assume that the walls are constructed in accordance with Techo-Bloc specifications, good construction practice and an

adequate drainage system.9. The geogrid layout has been optimized to satisfy the design requirements of the NCMA's Design Manual for Segmental Retaining Walls,

3rd Edition.10. The minimum burial depth must be 6 in (150 mm) or 10% of the exposed height, whichever is greater.11. Engineering judgement should be used when interpolating between heights.

12. Techo-Bloc and its predecessors, successors, beneficiaries, employees, associates, administrators and insurers accepts no liability forthe incorrect use of information contained in the design charts.

13. For further information, please contact our technical service department.

DESIGN CHARTMINI-CRETA 6"

(EQUIVALENT TO TWICE THE MINI-CRETA 3")SETBACK POSITION

5.3°5.3°

5.3°

5.3°5.3°

5.3°

Page 11: MINI-CRETA 3” & 6”...DESIGN CHART 3 45657No su 4 HDPE VERTICAL KEY (alignment pin) TECHNICAL SPECIFICATIONS PHYSICAL CHARACTERISTICS DESIGN DATA MINI-CRETA 3” MINI-CRETA 6”

11

2'-0"(0.60m)

13

2'-6"(0.75m) 4'-0'' (1.22 m) 4'-0'' (1.22 m)

3'-5"(1.05m)

4'-0'' (1.22 m)

4'-11"(1.50m)

6'-5"(1.95m)

7'-10"(2.40m)

6'-0'' (1.83 m)

6'-0'' (1.83 m)

6'-0'' (1.83 m)

6'-0'' (1.83 m)

5'-0'' (1.52 m)

5'-0'' (1.52 m)

5'-0'' (1.52 m)

7'-0'' (2.13 m)

7'-0'' (2.13 m)

7'-0'' (2.13 m)

7'-0'' (2.13 m)

7'-0'' (2.13 m)

13

13

13

13

13

CASE N° 4 :No SurchargeBackslope 1V : 3HNo Toe Slope

CLEAN SAND/GRAVEL/ SAND AND GRAVEL MIXES (Ø=34°, = 120 pcf)GEOGRID: MIRAGRID 3XT BY TENCATE (RFd=1.10, RFcr=1.45, RFid=1.25, Cds=0.9, Ci=0.9)

1. The information contained in the design charts is supplied for information purposes only and as such should only be used for preliminarydesigns.

2. The height (H) of the wall is the total height from the leveling pad to the top of the wall not including the thickness of the cap.3. Soil parameters: reinforced soil (φ = 34°, γ = 120 pcf); retained soil (φ =34°, γ = 120 pcf); foundation soil (φ=34°, γ = 120 pcf)4. A qualified engineer should be consulted for the final design to be used for construction.5. The foundation soil must be able to support the wall system. The bearing capacity of the foundation soil, settlement, and global stability

must be verified and validated by a qualified geotechnical engineer.6. The seismic analysis is not included.7. The design charts do not apply to tiered walls.8. The charts assume that the walls are constructed in accordance with Techo-Bloc specifications, good construction practice and an

adequate drainage system.9. The geogrid layout has been optimized to satisfy the design requirements of the NCMA's Design Manual for Segmental Retaining Walls,

3rd Edition.10. The minimum burial depth must be 6 in (150 mm) or 10% of the exposed height, whichever is greater.11. Engineering judgement should be used when interpolating between heights.

12. Techo-Bloc and its predecessors, successors, beneficiaries, employees, associates, administrators and insurers accepts no liability forthe incorrect use of information contained in the design charts.

13. For further information, please contact our technical service department.

DESIGN CHARTMINI-CRETA 6"

(EQUIVALENT TO TWICE THE MINI-CRETA 3")SETBACK POSITION

5.3°5.3°

5.3°

5.3°

5.3°5.3°

Page 12: MINI-CRETA 3” & 6”...DESIGN CHART 3 45657No su 4 HDPE VERTICAL KEY (alignment pin) TECHNICAL SPECIFICATIONS PHYSICAL CHARACTERISTICS DESIGN DATA MINI-CRETA 3” MINI-CRETA 6”

12

2'-0"(0.60m)

2'-6"(0.75m) 4'-0'' (1.22 m) 4'-0'' (1.22 m)

3'-5"(1.05m)

4'-0'' (1.22 m)

4'-11"(1.50m)

4'-6'' (1.37 m)

4'-6'' (1.37 m)

4'-6'' (1.37 m)

6'-5"(1.95m)

5'-6'' (1.68 m)

5'-6'' (1.68 m)

5'-6'' (1.68 m)

5'-6'' (1.68 m)

7'-10"(2.40m)

6'-6'' (1.98 m)

6'-6'' (1.98 m)

6'-6'' (1.98 m)

6'-6'' (1.98 m)

6'-6'' (1.98 m)

CASE N° 5 :No SurchargeNo BackslopeNo Toe Slope

FINE SANDS & SILTY SANDS (Ø=30°, = 120 pcf)GEOGRID: MIRAGRID 3XT BY TENCATE (RFd=1.10, RFcr=1.45, RFid=1.10, Cds=0.8, Ci=0.8)

1. The information contained in the design charts is supplied for information purposes only and as such should only be used for preliminarydesigns.

2. The height (H) of the wall is the total height from the leveling pad to the top of the wall not including the thickness of the cap.3. Soil parameters: reinforced soil (φ = 30°, γ = 120 pcf); retained soil (φ =30°, γ = 120 pcf); foundation soil (φ=30°, γ = 120 pcf)4. A qualified engineer should be consulted for the final design to be used for construction.5. The foundation soil must be able to support the wall system. The bearing capacity of the foundation soil, settlement, and global stability

must be verified and validated by a qualified geotechnical engineer.6. The seismic analysis is not included.7. The design charts do not apply to tiered walls.8. The charts assume that the walls are constructed in accordance with Techo-Bloc specifications, good construction practice and an

adequate drainage system.9. The geogrid layout has been optimized to satisfy the design requirements of the NCMA's Design Manual for Segmental Retaining Walls,

3rd Edition.10. The minimum burial depth must be 6 in (150 mm) or 10% of the exposed height, whichever is greater.11. Engineering judgement should be used when interpolating between heights.

12. Techo-Bloc and its predecessors, successors, beneficiaries, employees, associates, administrators and insurers accepts no liability forthe incorrect use of information contained in the design charts.

13. For further information, please contact our technical service department.

DESIGN CHARTMINI-CRETA 6"

(EQUIVALENT TO TWICE THE MINI-CRETA 3")SETBACK POSITION

5.3°5.3°

5.3°

5.3°

5.3°

5.3°

Page 13: MINI-CRETA 3” & 6”...DESIGN CHART 3 45657No su 4 HDPE VERTICAL KEY (alignment pin) TECHNICAL SPECIFICATIONS PHYSICAL CHARACTERISTICS DESIGN DATA MINI-CRETA 3” MINI-CRETA 6”

13

1'-6"(0.45m)

1'-0"(0.30m) 100 psf

2'-0"(0.60m) 4'-0'' (1.22 m)

1'-0"(0.30m) 100 psf

4'-0'' (1.22 m)

3'-5"(1.05m)

4'-0'' (1.22 m)

1'-0"(0.30m) 100 psf

4'-11"(1.50m)

1'-0"(0.30m) 100 psf

6'-5"(1.95m)

5'-6'' (1.68 m)

5'-6'' (1.68 m)

5'-6'' (1.68 m)

5'-6'' (1.68 m)

7'-10"(2.40m)

6'-6'' (1.98 m)

6'-6'' (1.98 m)

6'-6'' (1.98 m)

6'-6'' (1.98 m)

6'-6'' (1.98 m)

1'-0"(0.30m) 100 psf

1'-0"(0.30m) 100 psf

CASE N° 6 :100 psf Surcharge (1 ft behind the wall)No BackslopeNo Toe Slope

5'-0'' (1.52 m)

5'-0'' (1.52 m)

5'-0'' (1.52 m)

FINE SANDS & SILTY SANDS (Ø=30°, = 120 pcf)GEOGRID: MIRAGRID 3XT BY TENCATE (RFd=1.10, RFcr=1.45, RFid=1.10, Cds=0.8, Ci=0.8)

1. The information contained in the design charts is supplied for information purposes only and as such should only be used for preliminarydesigns.

2. The height (H) of the wall is the total height from the leveling pad to the top of the wall not including the thickness of the cap.3. Soil parameters: reinforced soil (φ = 30°, γ = 120 pcf); retained soil (φ =30°, γ = 120 pcf); foundation soil (φ=30°, γ = 120 pcf)4. A qualified engineer should be consulted for the final design to be used for construction.5. The foundation soil must be able to support the wall system. The bearing capacity of the foundation soil, settlement, and global stability

must be verified and validated by a qualified geotechnical engineer.6. The seismic analysis is not included.7. The design charts do not apply to tiered walls.8. The charts assume that the walls are constructed in accordance with Techo-Bloc specifications, good construction practice and an

adequate drainage system.9. The geogrid layout has been optimized to satisfy the design requirements of the NCMA's Design Manual for Segmental Retaining Walls,

3rd Edition.10. The minimum burial depth must be 6 in (150 mm) or 10% of the exposed height, whichever is greater.11. Engineering judgement should be used when interpolating between heights.

12. Techo-Bloc and its predecessors, successors, beneficiaries, employees, associates, administrators and insurers accepts no liability forthe incorrect use of information contained in the design charts.

13. For further information, please contact our technical service department.

DESIGN CHARTMINI-CRETA 6"

(EQUIVALENT TO TWICE THE MINI-CRETA 3")SETBACK POSITION

5.3°5.3°

5.3°

5.3°5.3°

5.3°

Page 14: MINI-CRETA 3” & 6”...DESIGN CHART 3 45657No su 4 HDPE VERTICAL KEY (alignment pin) TECHNICAL SPECIFICATIONS PHYSICAL CHARACTERISTICS DESIGN DATA MINI-CRETA 3” MINI-CRETA 6”

14

1'-6"(0.45m)

1'-0"(0.30m) 250 psf

2'-0"(0.60m) 4'-0'' (1.22 m)

1'-0"(0.30m)

3'-5"(1.05m)

1'-0"(0.30m)

250 psf

250 psf

4'-6'' (1.37 m)

4'-6'' (1.37 m)

4'-11"(1.50m)

1'-0"(0.30m)

5'-6'' (1.68 m)

5'-6'' (1.68 m)

5'-6'' (1.68 m)6'-5"

(1.95m)

1'-0"(0.30m)

6'-6'' (1.98 m)

6'-6'' (1.98 m)

6'-6'' (1.98 m)

6'-6'' (1.98 m)

7'-10"(2.40m)

1'-0"(0.30m)

7'-6'' (2.29 m)

7'-6'' (2.29 m)

7'-6'' (2.29 m)

7'-6'' (2.29 m)

7'-6'' (2.29 m)

250 psf

250 psf

250 psf

CASE N° 7 :250 psf Surcharge (1 ft behind the wall)No BackslopeNo Toe Slope

FINE SANDS & SILTY SANDS (Ø=30°, = 120 pcf)GEOGRID: MIRAGRID 3XT BY TENCATE (RFd=1.10, RFcr=1.45, RFid=1.10, Cds=0.8, Ci=0.8)

1. The information contained in the design charts is supplied for information purposes only and as such should only be used for preliminarydesigns.

2. The height (H) of the wall is the total height from the leveling pad to the top of the wall not including the thickness of the cap.3. Soil parameters: reinforced soil (φ = 30°, γ = 120 pcf); retained soil (φ =30°, γ = 120 pcf); foundation soil (φ=30°, γ = 120 pcf)4. A qualified engineer should be consulted for the final design to be used for construction.5. The foundation soil must be able to support the wall system. The bearing capacity of the foundation soil, settlement, and global stability

must be verified and validated by a qualified geotechnical engineer.6. The seismic analysis is not included.7. The design charts do not apply to tiered walls.8. The charts assume that the walls are constructed in accordance with Techo-Bloc specifications, good construction practice and an

adequate drainage system.9. The geogrid layout has been optimized to satisfy the design requirements of the NCMA's Design Manual for Segmental Retaining Walls,

3rd Edition.10. The minimum burial depth must be 6 in (150 mm) or 10% of the exposed height, whichever is greater.11. Engineering judgement should be used when interpolating between heights.

12. Techo-Bloc and its predecessors, successors, beneficiaries, employees, associates, administrators and insurers accepts no liability forthe incorrect use of information contained in the design charts.

13. For further information, please contact our technical service department.

DESIGN CHARTMINI-CRETA 6"

(EQUIVALENT TO TWICE THE MINI-CRETA 3")SETBACK POSITION

5.3°5.3°

5.3°

5.3°

5.3°

5.3°

Page 15: MINI-CRETA 3” & 6”...DESIGN CHART 3 45657No su 4 HDPE VERTICAL KEY (alignment pin) TECHNICAL SPECIFICATIONS PHYSICAL CHARACTERISTICS DESIGN DATA MINI-CRETA 3” MINI-CRETA 6”

15

2'-0"(0.60m)

2'-6"(0.75m)

3'-5"(1.05m)

4'-11"(1.50m)

6'-5"(1.95m)

6'-6'' (1.98 m)

6'-6'' (1.98 m)

6'-6'' (1.98 m)

6'-6'' (1.98 m)

7'-10"(2.40m)

13 1

31

3

13

13

13

5'-0'' (1.52 m)

5'-0'' (1.52 m)

6'-0'' (1.83 m)

6'-0'' (1.83 m)

6'-0'' (1.83 m)

8'-0'' (2.44 m)

8'-0'' (2.44 m)

8'-0'' (2.44 m)

8'-0'' (2.44 m)

8'-0'' (2.44 m)

CASE N° 8 :No SurchargeBackslope 1V : 3HNo Toe Slope

4'-6'' (1.37 m)

FINE SANDS & SILTY SANDS (Ø=30°, = 120 pcf)GEOGRID: MIRAGRID 3XT BY TENCATE (RFd=1.10, RFcr=1.45, RFid=1.10, Cds=0.8, Ci=0.8)

1. The information contained in the design charts is supplied for information purposes only and as such should only be used for preliminarydesigns.

2. The height (H) of the wall is the total height from the leveling pad to the top of the wall not including the thickness of the cap.3. Soil parameters: reinforced soil (φ = 30°, γ = 120 pcf); retained soil (φ =30°, γ = 120 pcf); foundation soil (φ=30°, γ = 120 pcf)4. A qualified engineer should be consulted for the final design to be used for construction.5. The foundation soil must be able to support the wall system. The bearing capacity of the foundation soil, settlement, and global stability

must be verified and validated by a qualified geotechnical engineer.6. The seismic analysis is not included.7. The design charts do not apply to tiered walls.8. The charts assume that the walls are constructed in accordance with Techo-Bloc specifications, good construction practice and an

adequate drainage system.9. The geogrid layout has been optimized to satisfy the design requirements of the NCMA's Design Manual for Segmental Retaining Walls,

3rd Edition.10. The minimum burial depth must be 6 in (150 mm) or 10% of the exposed height, whichever is greater.11. Engineering judgement should be used when interpolating between heights.

12. Techo-Bloc and its predecessors, successors, beneficiaries, employees, associates, administrators and insurers accepts no liability forthe incorrect use of information contained in the design charts.

13. For further information, please contact our technical service department.

DESIGN CHARTMINI-CRETA 6"

(EQUIVALENT TO TWICE THE MINI-CRETA 3")SETBACK POSITION

5.3°5.3°

5.3°

5.3°5.3°

5.3°

Page 16: MINI-CRETA 3” & 6”...DESIGN CHART 3 45657No su 4 HDPE VERTICAL KEY (alignment pin) TECHNICAL SPECIFICATIONS PHYSICAL CHARACTERISTICS DESIGN DATA MINI-CRETA 3” MINI-CRETA 6”

16

1'-6"(0.45m)

2'-0"(0.60m)

3'-5"(1.05m)

4'-11"(1.50m)

6'-5"(1.95m)

7'-10"(2.40m)

4'-0'' (1.22 m)

4'-6'' (1.37 m)

4'-6'' (1.37 m)

5'-6'' (1.68 m)

5'-6'' (1.68 m)

5'-6'' (1.68 m)

CASE N° 9 :No SurchargeNo BackslopeNo Toe Slope

7'-6'' (2.29 m)

7'-6'' (2.29 m)

7'-6'' (2.29 m)

7'-6'' (2.29 m)

7'-6'' (2.29 m)

6'-6'' (1.98 m)

6'-6'' (1.98 m)

6'-6'' (1.98 m)

6'-6'' (1.98 m)

LOW PLASTICITY SILTS AND CLAYS (Ø=26°, = 120 pcf)GEOGRID: MIRAGRID 3XT BY TENCATE (RFd=1.10,RFcr=1.45, RFid=1.05, Cds=0.7, Ci=0.7)

1. The information contained in the design charts is supplied for information purposes only and as such should only be used for preliminarydesigns.

2. The height (H) of the wall is the total height from the leveling pad to the top of the wall not including the thickness of the cap.3. Soil parameters: reinforced soil (φ = 26°, γ = 120 pcf); retained soil (φ =26°, γ = 120 pcf); foundation soil (φ=26°, γ = 120 pcf)4. A qualified engineer should be consulted for the final design to be used for construction.5. The foundation soil must be able to support the wall system. The bearing capacity of the foundation soil, settlement, and global stability

must be verified and validated by a qualified geotechnical engineer.6. The seismic analysis is not included.7. The design charts do not apply to tiered walls.8. The charts assume that the walls are constructed in accordance with Techo-Bloc specifications, good construction practice and an

adequate drainage system.9. The geogrid layout has been optimized to satisfy the design requirements of the NCMA's Design Manual for Segmental Retaining Walls,

3rd Edition.10. The minimum burial depth must be 6 in (150 mm) or 10% of the exposed height, whichever is greater.11. Engineering judgement should be used when interpolating between heights.12. Techo-Bloc and its predecessors, successors, beneficiaries, employees, associates, administrators and insurers accepts no liability for

the incorrect use of information contained in the design charts. 13. For further information, please contact our technical service department.

DESIGN CHARTMINI-CRETA 6"

(EQUIVALENT TO TWICE THE MINI-CRETA 3")SETBACK POSITION

5.3°5.3°

5.3°

5.3°

5.3°

5.3°

Page 17: MINI-CRETA 3” & 6”...DESIGN CHART 3 45657No su 4 HDPE VERTICAL KEY (alignment pin) TECHNICAL SPECIFICATIONS PHYSICAL CHARACTERISTICS DESIGN DATA MINI-CRETA 3” MINI-CRETA 6”

17

1'-6"(0.45m)

1'-0"(0.30m) 100 psf

2'-0"(0.60m) 4'-0'' (1.22 m)

1'-0"(0.30m)

3'-5"(1.05m)

1'-0"(0.30m)

4'-6'' (1.37 m)

4'-6'' (1.37 m)

4'-11"(1.50m)

1'-0"(0.30m)

6'-5"(1.95m)

1'-0"(0.30m)

7'-0'' (2.13 m)

7'-0'' (2.13 m)

7'-0'' (2.13 m)

7'-0'' (2.13 m)

7'-10"(2.40m)

1'-0"(0.30m)

8'-0'' (2.44 m)

8'-0'' (2.44 m)

8'-0'' (2.44 m)

8'-0'' (2.44 m)

8'-0'' (2.44 m)

100 psf

100 psf

100 psf

100 psf

100 psf

CASE N° 10 :100 psf Surcharge (1 ft behind the wall)No BackslopeNo Toe Slope

6'-0'' (1.83 m)

6'-0'' (1.83 m)

6'-0'' (1.83 m)

LOW PLASTICITY SILTS AND CLAYS (Ø=26°, = 120 pcf)GEOGRID: MIRAGRID 3XT BY TENCATE (RFd=1.10,RFcr=1.45, RFid=1.05, Cds=0.7, Ci=0.7)

1. The information contained in the design charts is supplied for information purposes only and as such should only be used for preliminarydesigns.

2. The height (H) of the wall is the total height from the leveling pad to the top of the wall not including the thickness of the cap.3. Soil parameters: reinforced soil (φ = 26°, γ = 120 pcf); retained soil (φ =26°, γ = 120 pcf); foundation soil (φ=26°, γ = 120 pcf)4. A qualified engineer should be consulted for the final design to be used for construction.5. The foundation soil must be able to support the wall system. The bearing capacity of the foundation soil, settlement, and global stability

must be verified and validated by a qualified geotechnical engineer.6. The seismic analysis is not included.7. The design charts do not apply to tiered walls.8. The charts assume that the walls are constructed in accordance with Techo-Bloc specifications, good construction practice and an

adequate drainage system.9. The geogrid layout has been optimized to satisfy the design requirements of the NCMA's Design Manual for Segmental Retaining Walls,

3rd Edition.10. The minimum burial depth must be 6 in (150 mm) or 10% of the exposed height, whichever is greater.11. Engineering judgement should be used when interpolating between heights.12. Techo-Bloc and its predecessors, successors, beneficiaries, employees, associates, administrators and insurers accepts no liability for

the incorrect use of information contained in the design charts. 13. For further information, please contact our technical service department.

DESIGN CHARTMINI-CRETA 6"

(EQUIVALENT TO TWICE THE MINI-CRETA 3")SETBACK POSITION

5.3° 5.3°

5.3°

5.3°5.3°

5.3°

Page 18: MINI-CRETA 3” & 6”...DESIGN CHART 3 45657No su 4 HDPE VERTICAL KEY (alignment pin) TECHNICAL SPECIFICATIONS PHYSICAL CHARACTERISTICS DESIGN DATA MINI-CRETA 3” MINI-CRETA 6”

18

1'-0"(0.30m)

1'-0"(0.30m) 250 psf

2'-0"(0.60m)

1'-0"(0.30m)

5'-6'' (1.68 m)

3'-5"(1.05m)

1'-0"(0.30m)

7'-0'' (2.13 m)

4'-11"(1.50m)

1'-0"(0.30m)

7'-0'' (2.13 m)

7'-0'' (2.13 m)

6'-0'' (1.83 m)

6'-0'' (1.83 m)

6'-5"(1.95m)

1'-0"(0.30m)

8'-0'' (2.44 m)

8'-0'' (2.44 m)

8'-0'' (2.44 m)

8'-0'' (2.44 m)

7'-10"(2.40m)

1'-0"(0.30m)

9'-6'' (2.90 m)

9'-6'' (2.90 m)

9'-6'' (2.90 m)

9'-6'' (2.90 m)

9'-6'' (2.90 m)

250 psf

250 psf

250 psf

250 psf

250 psf

CASE N° 11 :250 psf Surcharge (1 ft behind the wall)No BackslopeNo Toe Slope

LOW PLASTICITY SILTS AND CLAYS (Ø=26°, = 120 pcf)GEOGRID: MIRAGRID 3XT BY TENCATE (RFd=1.10,RFcr=1.45, RFid=1.05, Cds=0.7, Ci=0.7)

1. The information contained in the design charts is supplied for information purposes only and as such should only be used for preliminarydesigns.

2. The height (H) of the wall is the total height from the leveling pad to the top of the wall not including the thickness of the cap.3. Soil parameters: reinforced soil (φ = 26°, γ = 120 pcf); retained soil (φ =26°, γ = 120 pcf); foundation soil (φ=26°, γ = 120 pcf)4. A qualified engineer should be consulted for the final design to be used for construction.5. The foundation soil must be able to support the wall system. The bearing capacity of the foundation soil, settlement, and global stability

must be verified and validated by a qualified geotechnical engineer.6. The seismic analysis is not included.7. The design charts do not apply to tiered walls.8. The charts assume that the walls are constructed in accordance with Techo-Bloc specifications, good construction practice and an

adequate drainage system.9. The geogrid layout has been optimized to satisfy the design requirements of the NCMA's Design Manual for Segmental Retaining Walls,

3rd Edition.10. The minimum burial depth must be 6 in (150 mm) or 10% of the exposed height, whichever is greater.11. Engineering judgement should be used when interpolating between heights.12. Techo-Bloc and its predecessors, successors, beneficiaries, employees, associates, administrators and insurers accepts no liability for

the incorrect use of information contained in the design charts. 13. For further information, please contact our technical service department.

DESIGN CHARTMINI-CRETA 6"

(EQUIVALENT TO TWICE THE MINI-CRETA 3")SETBACK POSITION

5.3°

5.3°

5.3°

5.3°5.3°

5.3°

Page 19: MINI-CRETA 3” & 6”...DESIGN CHART 3 45657No su 4 HDPE VERTICAL KEY (alignment pin) TECHNICAL SPECIFICATIONS PHYSICAL CHARACTERISTICS DESIGN DATA MINI-CRETA 3” MINI-CRETA 6”

19

1'-6"(0.45m)

2'-0"(0.60m)

3'-5"(1.05m)

4'-11"(1.50m)

6'-5"(1.95m)

7'-10"(2.40m)

13 1

3

13

13

13

13

4'-0'' (1.22 m)

5'-6'' (1.68 m)

6'-6'' (1.98 m)

CASE N° 12 :No SurchargeBackslope 1V : 3HNo Toe Slope

10'-6'' (3.20 m)

10'-6'' (3.20 m)

10'-6'' (3.20 m)

10'-6'' (3.20 m)

8'-0'' (2.44 m)

LOW PLASTICITY SILTS AND CLAYS (Ø=26°, = 120 pcf)GEOGRID: MIRAGRID 3XT BY TENCATE (RFd=1.10,RFcr=1.45, RFid=1.05, Cds=0.7, Ci=0.7)

1. The information contained in the design charts is supplied for information purposes only and as such should only be used for preliminarydesigns.

2. The height (H) of the wall is the total height from the leveling pad to the top of the wall not including the thickness of the cap.3. Soil parameters: reinforced soil (φ = 26°, γ = 120 pcf); retained soil (φ =26°, γ = 120 pcf); foundation soil (φ=26°, γ = 120 pcf)4. A qualified engineer should be consulted for the final design to be used for construction.5. The foundation soil must be able to support the wall system. The bearing capacity of the foundation soil, settlement, and global stability

must be verified and validated by a qualified geotechnical engineer.6. The seismic analysis is not included.7. The design charts do not apply to tiered walls.8. The charts assume that the walls are constructed in accordance with Techo-Bloc specifications, good construction practice and an

adequate drainage system.9. The geogrid layout has been optimized to satisfy the design requirements of the NCMA's Design Manual for Segmental Retaining Walls,

3rd Edition.10. The minimum burial depth must be 6 in (150 mm) or 10% of the exposed height, whichever is greater.11. Engineering judgement should be used when interpolating between heights.12. Techo-Bloc and its predecessors, successors, beneficiaries, employees, associates, administrators and insurers accepts no liability for

the incorrect use of information contained in the design charts. 13. For further information, please contact our technical service department.

DESIGN CHARTMINI-CRETA 6"

(EQUIVALENT TO TWICE THE MINI-CRETA 3")SETBACK POSITION

5.3°5.3°

5.3°

5.3°

5.3°

5.3°

5'-6'' (1.68 m)

5'-6'' (1.68 m)

6'-6'' (1.98 m)

6'-6'' (1.98 m)

6'-6'' (1.98 m)

8'-0'' (2.44 m)

8'-0'' (2.44 m)

8'-0'' (2.44 m)

8'-0'' (2.44 m)

10'-6'' (3.20 m)

10'-6'' (3.20 m)

Page 20: MINI-CRETA 3” & 6”...DESIGN CHART 3 45657No su 4 HDPE VERTICAL KEY (alignment pin) TECHNICAL SPECIFICATIONS PHYSICAL CHARACTERISTICS DESIGN DATA MINI-CRETA 3” MINI-CRETA 6”

20

CASE N° 1 :No SurchargeNo BackslopeNo Toe Slope

7'-10"(2.40m)

4'-0'' (1.22 m)

6'-5"(1.95m)

4'-11"(1.50m)

2'-0"(0.60m)

2'-11"(0.90m)

3'-11"(1.20m)

4'-0'' (1.22 m)

4'-0'' (1.22 m)

4'-6'' (1.37 m)

4'-6'' (1.37 m)

4'-6'' (1.37 m)

5'-6'' (1.68 m)

5'-6'' (1.68 m)

5'-6'' (1.68 m)

5'-6'' (1.68 m) 6'-6'' (1.98 m)

6'-6'' (1.98 m)

6'-6'' (1.98 m)

6'-6'' (1.98 m)

6'-6'' (1.98 m)

CLEAN SAND/GRAVEL/ SAND AND GRAVEL MIXES (Ø=34°, = 120 pcf)GEOGRID: MIRAGRID 3XT BY TENCATE (RFd=1.10, RFcr=1.45, RFid=1.25, Cds=0.9, Ci=0.9)

1. The information contained in the design charts is supplied for information purposes only andas such should only be used for preliminary designs.

2. The height (H) of the wall is the total height from the leveling pad to the top of the wall notincluding the thickness of the cap.

3. Soil parameters: reinforced soil (φ = 34°, γ = 120 pcf); retained soil (φ =34°, γ = 120 pcf);foundation soil (φ=34°, γ = 120 pcf)

4. A qualified engineer should be consulted for the final design to be used for construction.5. The foundation soil must be able to support the wall system. The bearing capacity of the

foundation soil, settlement, and global stability must be verified and validated by a qualifiedgeotechnical engineer.

6. The seismic analysis is not included.7. The design charts do not apply to tiered walls.8. The charts assume that the walls are constructed in accordance with Techo-Bloc

specifications, good construction practice and an adequate drainage system.9. The geogrid layout has been optimized to satisfy the design requirements of the NCMA's

Design Manual for Segmental Retaining Walls, 3rd Edition.10. The minimum burial depth must be 6 in (150 mm) or 10% of the exposed height, whichever is

greater.11. Engineering judgement should be used when interpolating between heights.

12. Techo-Bloc and its predecessors, successors, beneficiaries, employees, associates,administrators and insurers accepts no liability for the incorrect use of information containedin the design charts.

13. For further information, please contact our technical service department.

HDPE horizontal key isinserted in the front groove

Note:Near Vertical walls shall be constructed withpositive batter by tilting units back towards fillon leveling pad. A negative 3.0 % minimumleveling pad slope is recommended. A 3.0%slope is equivalent to an elevation drop of 3/8 "along 12"

Front of unit1.7°

3.0 %

DESIGN CHARTMINI-CRETA 6"

(EQUIVALENT TO TWICE THE MINI-CRETA 3")NEAR VERTICAL

12"3/8 "

Page 21: MINI-CRETA 3” & 6”...DESIGN CHART 3 45657No su 4 HDPE VERTICAL KEY (alignment pin) TECHNICAL SPECIFICATIONS PHYSICAL CHARACTERISTICS DESIGN DATA MINI-CRETA 3” MINI-CRETA 6”

21

CASE N° 2 :100 psf Surcharge (1 ft behind the wall)No BackslopeNo Toe Slope

4'-11"(1.50m)

6'-5"(1.95m)

7'-10"(2.40m)

4'-6'' (1.37 m)

4'-6'' (1.37 m)

4'-6'' (1.37 m)

1'-0"(0.30m) 100 psf

1'-0"(0.30m) 100 psf

5'-6'' (1.68 m)

5'-6'' (1.68 m)

5'-6'' (1.68 m)

5'-6'' (1.68 m)

1'-0"(0.30m) 100 psf

6'-6'' (1.98 m)

6'-6'' (1.98 m)

6'-6'' (1.98 m)

6'-6'' (1.98 m)

6'-6'' (1.98 m)

2'-6"(0.75m)

1'-0"(0.30m) 100 psf

1'-0"(0.30m) 100 psf

4'-0'' (1.22 m)

CLEAN SAND/GRAVEL/ SAND AND GRAVEL MIXES (Ø=34°, = 120 pcf)GEOGRID: MIRAGRID 3XT BY TENCATE (RFd=1.10, RFcr=1.45, RFid=1.25, Cds=0.9, Ci=0.9)

1. The information contained in the design charts is supplied for information purposes only andas such should only be used for preliminary designs.

2. The height (H) of the wall is the total height from the leveling pad to the top of the wall notincluding the thickness of the cap.

3. Soil parameters: reinforced soil (φ = 34°, γ = 120 pcf); retained soil (φ =34°, γ = 120 pcf);foundation soil (φ=34°, γ = 120 pcf)

4. A qualified engineer should be consulted for the final design to be used for construction.5. The foundation soil must be able to support the wall system. The bearing capacity of the

foundation soil, settlement, and global stability must be verified and validated by a qualifiedgeotechnical engineer.

6. The seismic analysis is not included.7. The design charts do not apply to tiered walls.8. The charts assume that the walls are constructed in accordance with Techo-Bloc

specifications, good construction practice and an adequate drainage system.9. The geogrid layout has been optimized to satisfy the design requirements of the NCMA's

Design Manual for Segmental Retaining Walls, 3rd Edition.10. The minimum burial depth must be 6 in (150 mm) or 10% of the exposed height, whichever is

greater.11. Engineering judgement should be used when interpolating between heights.

12. Techo-Bloc and its predecessors, successors, beneficiaries, employees, associates,administrators and insurers accepts no liability for the incorrect use of information containedin the design charts.

13. For further information, please contact our technical service department.

HDPE horizontal key isinserted in the front groove

Note:Near Vertical walls shall be constructed withpositive batter by tilting units back towards fillon leveling pad. A negative 3.0 % minimumleveling pad slope is recommended. A 3.0%slope is equivalent to an elevation drop of 3/8 "along 12"

Front of unit1.7°

3.0 %

DESIGN CHARTMINI-CRETA 6"

(EQUIVALENT TO TWICE THE MINI-CRETA 3")NEAR VERTICAL

12"3/8 "

1'-6"(0.45m)

3'-5"(1.05m)

4'-0'' (1.22 m)

4'-0'' (1.22 m)

1'-0"(0.30m) 100 psf

Page 22: MINI-CRETA 3” & 6”...DESIGN CHART 3 45657No su 4 HDPE VERTICAL KEY (alignment pin) TECHNICAL SPECIFICATIONS PHYSICAL CHARACTERISTICS DESIGN DATA MINI-CRETA 3” MINI-CRETA 6”

22

CASE N° 3 :250 psf Surcharge (1 ft behind the wall)No BackslopeNo Toe Slope

3'-5"(1.05m)

2'-0"(0.60m)

6'-5"(1.95m)

7'-10"(2.40m)

1'-0"(0.30m)

1'-0"(0.30m)

4'-0'' (1.22 m)1'-6"(0.45m)

4'-0'' (1.22 m)

4'-0'' (1.22 m)

1'-0"(0.30m)

250 psf

250 psf

250 psf

4'-11"(1.50m)

5'-0'' (1.52 m)

5'-0'' (1.52 m)

5'-0'' (1.52 m)

6'-0'' (1.83 m)

6'-0'' (1.83 m)

6'-0'' (1.83 m)

6'-0'' (1.83 m)

7'-0'' (2.13 m)

7'-0'' (2.13 m)

7'-0'' (2.13 m)

7'-0'' (2.13 m)

7'-0'' (2.13 m)1'-0"

(0.30m) 250 psf

1'-0"(0.30m) 250 psf

1'-0"(0.30m) 250 psf

CLEAN SAND/GRAVEL/ SAND AND GRAVEL MIXES (Ø=34°, = 120 pcf)GEOGRID: MIRAGRID 3XT BY TENCATE (RFd=1.10, RFcr=1.45, RFid=1.25, Cds=0.9, Ci=0.9)

1. The information contained in the design charts is supplied for information purposes only andas such should only be used for preliminary designs.

2. The height (H) of the wall is the total height from the leveling pad to the top of the wall notincluding the thickness of the cap.

3. Soil parameters: reinforced soil (φ = 34°, γ = 120 pcf); retained soil (φ =34°, γ = 120 pcf);foundation soil (φ=34°, γ = 120 pcf)

4. A qualified engineer should be consulted for the final design to be used for construction.5. The foundation soil must be able to support the wall system. The bearing capacity of the

foundation soil, settlement, and global stability must be verified and validated by a qualifiedgeotechnical engineer.

6. The seismic analysis is not included.7. The design charts do not apply to tiered walls.8. The charts assume that the walls are constructed in accordance with Techo-Bloc

specifications, good construction practice and an adequate drainage system.9. The geogrid layout has been optimized to satisfy the design requirements of the NCMA's

Design Manual for Segmental Retaining Walls, 3rd Edition.10. The minimum burial depth must be 6 in (150 mm) or 10% of the exposed height, whichever is

greater.11. Engineering judgement should be used when interpolating between heights.

12. Techo-Bloc and its predecessors, successors, beneficiaries, employees, associates,administrators and insurers accepts no liability for the incorrect use of information containedin the design charts.

13. For further information, please contact our technical service department.

HDPE horizontal key isinserted in the front groove

Note:Near Vertical walls shall be constructed withpositive batter by tilting units back towards fillon leveling pad. A negative 3.0 % minimumleveling pad slope is recommended. A 3.0%slope is equivalent to an elevation drop of 3/8 "along 12"

Front of unit1.7°

3.0 %

DESIGN CHARTMINI-CRETA 6"

(EQUIVALENT TO TWICE THE MINI-CRETA 3")NEAR VERTICAL

12"3/8 "

Page 23: MINI-CRETA 3” & 6”...DESIGN CHART 3 45657No su 4 HDPE VERTICAL KEY (alignment pin) TECHNICAL SPECIFICATIONS PHYSICAL CHARACTERISTICS DESIGN DATA MINI-CRETA 3” MINI-CRETA 6”

23

CASE N° 4 :No SurchargeBackslope 1V : 3HNo Toe Slope

2'-0"(0.60m)

13

4'-11"(1.50m)

7'-10"(2.40m)

13

13

13

13

3'-5"(1.05m)

4'-0'' (1.22 m)

4'-0'' (1.22 m)

5'-6'' (1.68 m)

5'-6'' (1.68 m)

5'-6'' (1.68 m)6'-5"

(1.95m)

6'-0'' (1.83 m)

6'-0'' (1.83 m)

6'-0'' (1.83 m)

6'-0'' (1.83 m)

7'-0'' (2.13 m)

7'-0'' (2.13 m)

7'-0'' (2.13 m)

7'-0'' (2.13 m)

7'-0'' (2.13 m)

13

CLEAN SAND/GRAVEL/ SAND AND GRAVEL MIXES (Ø=34°, = 120 pcf)GEOGRID: MIRAGRID 3XT BY TENCATE (RFd=1.10, RFcr=1.45, RFid=1.25, Cds=0.9, Ci=0.9)

1. The information contained in the design charts is supplied for information purposes only andas such should only be used for preliminary designs.

2. The height (H) of the wall is the total height from the leveling pad to the top of the wall notincluding the thickness of the cap.

3. Soil parameters: reinforced soil (φ = 34°, γ = 120 pcf); retained soil (φ =34°, γ = 120 pcf);foundation soil (φ=34°, γ = 120 pcf)

4. A qualified engineer should be consulted for the final design to be used for construction.5. The foundation soil must be able to support the wall system. The bearing capacity of the

foundation soil, settlement, and global stability must be verified and validated by a qualifiedgeotechnical engineer.

6. The seismic analysis is not included.7. The design charts do not apply to tiered walls.8. The charts assume that the walls are constructed in accordance with Techo-Bloc

specifications, good construction practice and an adequate drainage system.9. The geogrid layout has been optimized to satisfy the design requirements of the NCMA's

Design Manual for Segmental Retaining Walls, 3rd Edition.10. The minimum burial depth must be 6 in (150 mm) or 10% of the exposed height, whichever is

greater.11. Engineering judgement should be used when interpolating between heights.

12. Techo-Bloc and its predecessors, successors, beneficiaries, employees, associates,administrators and insurers accepts no liability for the incorrect use of information containedin the design charts.

13. For further information, please contact our technical service department.

HDPE horizontal key isinserted in the front groove

Note:Near Vertical walls shall be constructed withpositive batter by tilting units back towards fillon leveling pad. A negative 3.0 % minimumleveling pad slope is recommended. A 3.0%slope is equivalent to an elevation drop of 3/8 "along 12"

Front of unit1.7°

3.0 %

DESIGN CHARTMINI-CRETA 6"

(EQUIVALENT TO TWICE THE MINI-CRETA 3")NEAR VERTICAL

12"3/8 "

2'-6"(0.75m) 4'-0'' (1.22 m)

Page 24: MINI-CRETA 3” & 6”...DESIGN CHART 3 45657No su 4 HDPE VERTICAL KEY (alignment pin) TECHNICAL SPECIFICATIONS PHYSICAL CHARACTERISTICS DESIGN DATA MINI-CRETA 3” MINI-CRETA 6”

24

CASE N° 5 :No SurchargeNo BackslopeNo Toe Slope

2'-0"(0.60m)

2'-6"(0.75m) 4'-0'' (1.22 m)

3'-5"(1.05m)

4'-0'' (1.22 m)

4'-0'' (1.22 m)

4'-11"(1.50m)

4'-6'' (1.37 m)

4'-6'' (1.37 m)

4'-6'' (1.37 m)

6'-5"(1.95m)

5'-6'' (1.68 m)

5'-6'' (1.68 m)

5'-6'' (1.68 m)

5'-6'' (1.68 m)

7'-10"(2.40m)

6'-6'' (1.98 m)

6'-6'' (1.98 m)

6'-6'' (1.98 m)

6'-6'' (1.98 m)

6'-6'' (1.98 m)

FINE SANDS & SILTY SANDS (Ø=30°, = 120 pcf)GEOGRID: MIRAGRID 3XT BY TENCATE (RFd=1.10, RFcr=1.45, RFid=1.10, Cds=0.8, Ci=0.8)

1. The information contained in the design charts is supplied for information purposes only andas such should only be used for preliminary designs.

2. The height (H) of the wall is the total height from the leveling pad to the top of the wall notincluding the thickness of the cap.

3. Soil parameters: reinforced soil (φ = 30°, γ = 120 pcf); retained soil (φ =30°, γ = 120 pcf);foundation soil (φ=30°, γ = 120 pcf)

4. A qualified engineer should be consulted for the final design to be used for construction.5. The foundation soil must be able to support the wall system. The bearing capacity of the

foundation soil, settlement, and global stability must be verified and validated by a qualifiedgeotechnical engineer.

6. The seismic analysis is not included.7. The design charts do not apply to tiered walls.8. The charts assume that the walls are constructed in accordance with Techo-Bloc

specifications, good construction practice and an adequate drainage system.9. The geogrid layout has been optimized to satisfy the design requirements of the NCMA's

Design Manual for Segmental Retaining Walls, 3rd Edition.10. The minimum burial depth must be 6 in (150 mm) or 10% of the exposed height, whichever is

greater.11. Engineering judgement should be used when interpolating between heights.

12. Techo-Bloc and its predecessors, successors, beneficiaries, employees, associates,administrators and insurers accepts no liability for the incorrect use of information containedin the design charts.

13. For further information, please contact our technical service department.

HDPE horizontal key isinserted in the front groove

Note:Near Vertical walls shall be constructed withpositive batter by tilting units back towards fillon leveling pad. A negative 3.0 % minimumleveling pad slope is recommended. A 3.0%slope is equivalent to an elevation drop of 3/8 "along 12"

Front of unit1.7°

3.0 %

DESIGN CHARTMINI-CRETA 6"

(EQUIVALENT TO TWICE THE MINI-CRETA 3")NEAR VERTICAL

12"3/8 "

Page 25: MINI-CRETA 3” & 6”...DESIGN CHART 3 45657No su 4 HDPE VERTICAL KEY (alignment pin) TECHNICAL SPECIFICATIONS PHYSICAL CHARACTERISTICS DESIGN DATA MINI-CRETA 3” MINI-CRETA 6”

25

CASE N° 6 :100 psf Surcharge (1 ft behind the wall)No BackslopeNo Toe Slope

1'-6"(0.45m)

3'-5"(1.05m)

4'-0'' (1.22 m)

4'-0'' (1.22 m)

2'-0"(0.60m) 4'-0'' (1.22 m)

4'-11"(1.50m)

5'-0'' (1.52 m)

5'-0'' (1.52 m)

5'-0'' (1.52 m)6'-5"

(1.95m)

6'-0'' (1.83 m)

6'-0'' (1.83 m)

6'-0'' (1.83 m)

6'-0'' (1.83 m)

7'-10"(2.40m)

7'-0'' (2.13 m)

7'-0'' (2.13 m)

7'-0'' (2.13 m)

7'-0'' (2.13 m)

7'-0'' (2.13 m)

1'-0"(0.30m) 100 psf

1'-0"(0.30m)

1'-0"(0.30m)

1'-0"(0.30m)

1'-0"(0.30m)

1'-0"(0.30m)

100 psf

100 psf

100 psf

100 psf

100 psf

FINE SANDS & SILTY SANDS (Ø=30°, = 120 pcf)GEOGRID: MIRAGRID 3XT BY TENCATE (RFd=1.10, RFcr=1.45, RFid=1.10, Cds=0.8, Ci=0.8)

1. The information contained in the design charts is supplied for information purposes only andas such should only be used for preliminary designs.

2. The height (H) of the wall is the total height from the leveling pad to the top of the wall notincluding the thickness of the cap.

3. Soil parameters: reinforced soil (φ = 30°, γ = 120 pcf); retained soil (φ =30°, γ = 120 pcf);foundation soil (φ=30°, γ = 120 pcf)

4. A qualified engineer should be consulted for the final design to be used for construction.5. The foundation soil must be able to support the wall system. The bearing capacity of the

foundation soil, settlement, and global stability must be verified and validated by a qualifiedgeotechnical engineer.

6. The seismic analysis is not included.7. The design charts do not apply to tiered walls.8. The charts assume that the walls are constructed in accordance with Techo-Bloc

specifications, good construction practice and an adequate drainage system.9. The geogrid layout has been optimized to satisfy the design requirements of the NCMA's

Design Manual for Segmental Retaining Walls, 3rd Edition.10. The minimum burial depth must be 6 in (150 mm) or 10% of the exposed height, whichever is

greater.11. Engineering judgement should be used when interpolating between heights.

12. Techo-Bloc and its predecessors, successors, beneficiaries, employees, associates,administrators and insurers accepts no liability for the incorrect use of information containedin the design charts.

13. For further information, please contact our technical service department.

HDPE horizontal key isinserted in the front groove

Note:Near Vertical walls shall be constructed withpositive batter by tilting units back towards fillon leveling pad. A negative 3.0 % minimumleveling pad slope is recommended. A 3.0%slope is equivalent to an elevation drop of 3/8 "along 12"

Front of unit1.7°

3.0 %

DESIGN CHARTMINI-CRETA 6"

(EQUIVALENT TO TWICE THE MINI-CRETA 3")NEAR VERTICAL

12"3/8 "

Page 26: MINI-CRETA 3” & 6”...DESIGN CHART 3 45657No su 4 HDPE VERTICAL KEY (alignment pin) TECHNICAL SPECIFICATIONS PHYSICAL CHARACTERISTICS DESIGN DATA MINI-CRETA 3” MINI-CRETA 6”

26

CASE N° 7 :250 psf Surcharge (1 ft behind the wall)No BackslopeNo Toe Slope

1'-0"(0.30m)

1'-0"(0.30m) 250 psf

4'-11"(1.50m)

1'-0"(0.30m)

6'-0'' (1.83 m)

6'-0'' (1.83 m)

6'-0'' (1.83 m)

2'-0"(0.60m)

1'-0"(0.30m)

4'-6'' (1.37 m)

3'-5"(1.05m)

1'-0"(0.30m)

5'-0'' (1.52 m)

5'-0'' (1.52 m)

6'-5"(1.95m)

1'-0"(0.30m)

7'-0'' (2.13 m)

7'-0'' (2.13 m)

7'-0'' (2.13 m)

7'-0'' (2.13 m)

7'-10"(2.40m)

1'-0"(0.30m)

8'-0'' (2.44 m)

8'-0'' (2.44 m)

8'-0'' (2.44 m)

8'-0'' (2.44 m)

8'-0'' (2.44 m)

250 psf

250 psf

250 psf

250 psf

250 psf

FINE SANDS & SILTY SANDS (Ø=30°, = 120 pcf)GEOGRID: MIRAGRID 3XT BY TENCATE (RFd=1.10, RFcr=1.45, RFid=1.10, Cds=0.8, Ci=0.8)

1. The information contained in the design charts is supplied for information purposes only andas such should only be used for preliminary designs.

2. The height (H) of the wall is the total height from the leveling pad to the top of the wall notincluding the thickness of the cap.

3. Soil parameters: reinforced soil (φ = 30°, γ = 120 pcf); retained soil (φ =30°, γ = 120 pcf);foundation soil (φ=30°, γ = 120 pcf)

4. A qualified engineer should be consulted for the final design to be used for construction.5. The foundation soil must be able to support the wall system. The bearing capacity of the

foundation soil, settlement, and global stability must be verified and validated by a qualifiedgeotechnical engineer.

6. The seismic analysis is not included.7. The design charts do not apply to tiered walls.8. The charts assume that the walls are constructed in accordance with Techo-Bloc

specifications, good construction practice and an adequate drainage system.9. The geogrid layout has been optimized to satisfy the design requirements of the NCMA's

Design Manual for Segmental Retaining Walls, 3rd Edition.10. The minimum burial depth must be 6 in (150 mm) or 10% of the exposed height, whichever is

greater.11. Engineering judgement should be used when interpolating between heights.

12. Techo-Bloc and its predecessors, successors, beneficiaries, employees, associates,administrators and insurers accepts no liability for the incorrect use of information containedin the design charts.

13. For further information, please contact our technical service department.

HDPE horizontal key isinserted in the front groove

Note:Near Vertical walls shall be constructed withpositive batter by tilting units back towards fillon leveling pad. A negative 3.0 % minimumleveling pad slope is recommended. A 3.0%slope is equivalent to an elevation drop of 3/8 "along 12"

Front of unit1.7°

3.0 %

DESIGN CHARTMINI-CRETA 6"

(EQUIVALENT TO TWICE THE MINI-CRETA 3")NEAR VERTICAL

12"3/8 "

Page 27: MINI-CRETA 3” & 6”...DESIGN CHART 3 45657No su 4 HDPE VERTICAL KEY (alignment pin) TECHNICAL SPECIFICATIONS PHYSICAL CHARACTERISTICS DESIGN DATA MINI-CRETA 3” MINI-CRETA 6”

27

CASE N° 8 :No SurchargeBackslope 1V : 3HNo Toe Slope

2'-0"(0.60m)

2'-6"(0.75m) 4'-6'' (1.37 m)

3'-5"(1.05m)

5'-6'' (1.68 m)

5'-6'' (1.68 m)

4'-11"(1.50m)

6'-0'' (1.83 m)

6'-0'' (1.83 m)

6'-0'' (1.83 m)

6'-5"(1.95m)

6'-6'' (1.98 m)

6'-6'' (1.98 m)

6'-6'' (1.98 m)

6'-6'' (1.98 m)

7'-10"(2.40m)

8'-0'' (2.44 m)

8'-0'' (2.44 m)

8'-0'' (2.44 m)

8'-0'' (2.44 m)

8'-0'' (2.44 m)

13 1

31

3

13

13

13

FINE SANDS & SILTY SANDS (Ø=30°, = 120 pcf)GEOGRID: MIRAGRID 3XT BY TENCATE (RFd=1.10, RFcr=1.45, RFid=1.10, Cds=0.8, Ci=0.8)

1. The information contained in the design charts is supplied for information purposes only andas such should only be used for preliminary designs.

2. The height (H) of the wall is the total height from the leveling pad to the top of the wall notincluding the thickness of the cap.

3. Soil parameters: reinforced soil (φ = 30°, γ = 120 pcf); retained soil (φ =30°, γ = 120 pcf);foundation soil (φ=30°, γ = 120 pcf)

4. A qualified engineer should be consulted for the final design to be used for construction.5. The foundation soil must be able to support the wall system. The bearing capacity of the

foundation soil, settlement, and global stability must be verified and validated by a qualifiedgeotechnical engineer.

6. The seismic analysis is not included.7. The design charts do not apply to tiered walls.8. The charts assume that the walls are constructed in accordance with Techo-Bloc

specifications, good construction practice and an adequate drainage system.9. The geogrid layout has been optimized to satisfy the design requirements of the NCMA's

Design Manual for Segmental Retaining Walls, 3rd Edition.10. The minimum burial depth must be 6 in (150 mm) or 10% of the exposed height, whichever is

greater.11. Engineering judgement should be used when interpolating between heights.

12. Techo-Bloc and its predecessors, successors, beneficiaries, employees, associates,administrators and insurers accepts no liability for the incorrect use of information containedin the design charts.

13. For further information, please contact our technical service department.

HDPE horizontal key isinserted in the front groove

Note:Near Vertical walls shall be constructed withpositive batter by tilting units back towards fillon leveling pad. A negative 3.0 % minimumleveling pad slope is recommended. A 3.0%slope is equivalent to an elevation drop of 3/8 "along 12"

Front of unit1.7°

3.0 %

DESIGN CHARTMINI-CRETA 6"

(EQUIVALENT TO TWICE THE MINI-CRETA 3")NEAR VERTICAL

12"3/8 "

Page 28: MINI-CRETA 3” & 6”...DESIGN CHART 3 45657No su 4 HDPE VERTICAL KEY (alignment pin) TECHNICAL SPECIFICATIONS PHYSICAL CHARACTERISTICS DESIGN DATA MINI-CRETA 3” MINI-CRETA 6”

28

CASE N° 9 :No SurchargeNo BackslopeNo Toe Slope

1'-6"(0.45m)

2'-0"(0.60m) 4'-0'' (1.22 m)

3'-5"(1.05m)

4'-6'' (1.37 m)

4'-6'' (1.37 m)

4'-11"(1.50m)

5'-6'' (1.68 m)

5'-6'' (1.68 m)

5'-6'' (1.68 m)

6'-5"(1.95m)

7'-0'' (2.13 m)

7'-0'' (2.13 m)

7'-0'' (2.13 m)

7'-0'' (2.13 m)

7'-10"(2.40m)

8'-0'' (2.44 m)

8'-0'' (2.44 m)

8'-0'' (2.44 m)

8'-0'' (2.44 m)

8'-0'' (2.44 m)

LOW PLASTICITY SILTS AND CLAYS (Ø=26°, = 120 pcf)GEOGRID: MIRAGRID 3XT BY TENCATE (RFd=1.10,RFcr=1.45, RFid=1.05, Cds=0.7, Ci=0.7)

1. The information contained in the design charts is supplied for information purposes only and assuch should only be used for preliminary designs.

2. The height (H) of the wall is the total height from the leveling pad to the top of the wall notincluding the thickness of the cap.

3. Soil parameters: reinforced soil (φ = 26°, γ = 120 pcf); retained soil (φ =26°, γ = 120 pcf);foundation soil (φ=26°, γ = 120 pcf)

4. A qualified engineer should be consulted for the final design to be used for construction.5. The foundation soil must be able to support the wall system. The bearing capacity of the

foundation soil, settlement, and global stability must be verified and validated by a qualifiedgeotechnical engineer.

6. The seismic analysis is not included.7. The design charts do not apply to tiered walls.8. The charts assume that the walls are constructed in accordance with Techo-Bloc

specifications, good construction practice and an adequate drainage system.9. The geogrid layout has been optimized to satisfy the design requirements of the NCMA's

Design Manual for Segmental Retaining Walls, 3rd Edition.10. The minimum burial depth must be 6 in (150 mm) or 10% of the exposed height, whichever is

greater.11. Engineering judgement should be used when interpolating between heights.

12. Techo-Bloc and its predecessors, successors, beneficiaries, employees, associates,administrators and insurers accepts no liability for the incorrect use of information contained inthe design charts.

13. For further information, please contact our technical service department.

HDPE horizontal key isinserted in the front groove

Note:Near Vertical walls shall be constructed withpositive batter by tilting units back towards fillon leveling pad. A negative 3.0 % minimumleveling pad slope is recommended. A 3.0%slope is equivalent to an elevation drop of 3/8 "along 12"

Front of unit1.7°

3.0 %

DESIGN CHARTMINI-CRETA 6"

(EQUIVALENT TO TWICE THE MINI-CRETA 3")NEAR VERTICAL

12"3/8 "

Page 29: MINI-CRETA 3” & 6”...DESIGN CHART 3 45657No su 4 HDPE VERTICAL KEY (alignment pin) TECHNICAL SPECIFICATIONS PHYSICAL CHARACTERISTICS DESIGN DATA MINI-CRETA 3” MINI-CRETA 6”

29

CASE N° 10 :100 psf Surcharge (1 ft behind the wall)No BackslopeNo Toe Slope

1'-6"(0.45m)

2'-0"(0.60m)

1'-0"(0.30m)

4'-6'' (1.37 m)

100 psf1'-0"(0.30m) 100 psf 3'-5"

(1.05m)

1'-0"(0.30m) 100 psf

5'-0'' (1.52 m)

5'-0'' (1.52 m)

4'-11"(1.50m)

6'-0'' (1.83 m)

6'-0'' (1.83 m)

6'-0'' (1.83 m)6'-5"

(1.95m)

7'-0'' (2.13 m)

7'-0'' (2.13 m)

7'-0'' (2.13 m)

7'-0'' (2.13 m)

7'-10"(2.40m)

8'-6'' (2.59 m)1'-0"(0.30m) 100 psf

1'-0"(0.30m) 100 psf

1'-0"(0.30m) 100 psf

LOW PLASTICITY SILTS AND CLAYS (Ø=26°, = 120 pcf)GEOGRID: MIRAGRID 3XT BY TENCATE (RFd=1.10,RFcr=1.45, RFid=1.05, Cds=0.7, Ci=0.7)

1. The information contained in the design charts is supplied for information purposes only and assuch should only be used for preliminary designs.

2. The height (H) of the wall is the total height from the leveling pad to the top of the wall notincluding the thickness of the cap.

3. Soil parameters: reinforced soil (φ = 26°, γ = 120 pcf); retained soil (φ =26°, γ = 120 pcf);foundation soil (φ=26°, γ = 120 pcf)

4. A qualified engineer should be consulted for the final design to be used for construction.5. The foundation soil must be able to support the wall system. The bearing capacity of the

foundation soil, settlement, and global stability must be verified and validated by a qualifiedgeotechnical engineer.

6. The seismic analysis is not included.7. The design charts do not apply to tiered walls.8. The charts assume that the walls are constructed in accordance with Techo-Bloc

specifications, good construction practice and an adequate drainage system.9. The geogrid layout has been optimized to satisfy the design requirements of the NCMA's

Design Manual for Segmental Retaining Walls, 3rd Edition.10. The minimum burial depth must be 6 in (150 mm) or 10% of the exposed height, whichever is

greater.11. Engineering judgement should be used when interpolating between heights.

12. Techo-Bloc and its predecessors, successors, beneficiaries, employees, associates,administrators and insurers accepts no liability for the incorrect use of information contained inthe design charts.

13. For further information, please contact our technical service department.

HDPE horizontal key isinserted in the front groove

Note:Near Vertical walls shall be constructed withpositive batter by tilting units back towards fillon leveling pad. A negative 3.0 % minimumleveling pad slope is recommended. A 3.0%slope is equivalent to an elevation drop of 3/8 "along 12"

Front of unit1.7°

3.0 %

DESIGN CHARTMINI-CRETA 6"

(EQUIVALENT TO TWICE THE MINI-CRETA 3")NEAR VERTICAL

12"3/8 "

8'-6'' (2.59 m)

8'-6'' (2.59 m)

8'-6'' (2.59 m)

8'-6'' (2.59 m)

Page 30: MINI-CRETA 3” & 6”...DESIGN CHART 3 45657No su 4 HDPE VERTICAL KEY (alignment pin) TECHNICAL SPECIFICATIONS PHYSICAL CHARACTERISTICS DESIGN DATA MINI-CRETA 3” MINI-CRETA 6”

30

CASE N° 11 :250 psf Surcharge (1 ft behind the wall)No BackslopeNo Toe Slope

1'-0"(0.30m)

1'-0"(0.30m) 250 psf

2'-0"(0.60m) 6'-0'' (1.83 m)

3'-5"(1.05m)

6'-6'' (1.98 m)

6'-6'' (1.98 m)

4'-11"(1.50m)

7'-6'' (2.29 m)

7'-6'' (2.29 m)

7'-6'' (2.29 m)6'-5"

(1.95m)

8'-6'' (2.59 m)

8'-6'' (2.59 m)

8'-6'' (2.59 m)

8'-6'' (2.59 m)

7'-10"(2.40m)

10'-0'' (3.05 m)

10'-0'' (3.05 m)

10'-0'' (3.05 m)

10'-0'' (3.05 m)

10'-0'' (3.05 m)

1'-0"(0.30m) 250 psf

1'-0"(0.30m) 250 psf

1'-0"(0.30m) 250 psf

1'-0"(0.30m) 250 psf

1'-0"(0.30m) 250 psf

LOW PLASTICITY SILTS AND CLAYS (Ø=26°, = 120 pcf)GEOGRID: MIRAGRID 3XT BY TENCATE (RFd=1.10,RFcr=1.45, RFid=1.05, Cds=0.7, Ci=0.7)

1. The information contained in the design charts is supplied for information purposes only and assuch should only be used for preliminary designs.

2. The height (H) of the wall is the total height from the leveling pad to the top of the wall notincluding the thickness of the cap.

3. Soil parameters: reinforced soil (φ = 26°, γ = 120 pcf); retained soil (φ =26°, γ = 120 pcf);foundation soil (φ=26°, γ = 120 pcf)

4. A qualified engineer should be consulted for the final design to be used for construction.5. The foundation soil must be able to support the wall system. The bearing capacity of the

foundation soil, settlement, and global stability must be verified and validated by a qualifiedgeotechnical engineer.

6. The seismic analysis is not included.7. The design charts do not apply to tiered walls.8. The charts assume that the walls are constructed in accordance with Techo-Bloc

specifications, good construction practice and an adequate drainage system.9. The geogrid layout has been optimized to satisfy the design requirements of the NCMA's

Design Manual for Segmental Retaining Walls, 3rd Edition.10. The minimum burial depth must be 6 in (150 mm) or 10% of the exposed height, whichever is

greater.11. Engineering judgement should be used when interpolating between heights.

12. Techo-Bloc and its predecessors, successors, beneficiaries, employees, associates,administrators and insurers accepts no liability for the incorrect use of information contained inthe design charts.

13. For further information, please contact our technical service department.

HDPE horizontal key isinserted in the front groove

Note:Near Vertical walls shall be constructed withpositive batter by tilting units back towards fillon leveling pad. A negative 3.0 % minimumleveling pad slope is recommended. A 3.0%slope is equivalent to an elevation drop of 3/8 "along 12"

Front of unit1.7°

3.0 %

DESIGN CHARTMINI-CRETA 6"

(EQUIVALENT TO TWICE THE MINI-CRETA 3")NEAR VERTICAL

12"3/8 "

Page 31: MINI-CRETA 3” & 6”...DESIGN CHART 3 45657No su 4 HDPE VERTICAL KEY (alignment pin) TECHNICAL SPECIFICATIONS PHYSICAL CHARACTERISTICS DESIGN DATA MINI-CRETA 3” MINI-CRETA 6”

31

CASE N° 12 :No SurchargeBackslope 1V : 3HNo Toe Slope

1'-0"(0.30m)

1'-6"(0.45m) 4'-0'' (1.22 m)

3'-5"(1.05m)

4'-11"(1.50m)

6'-5"(1.95m)

7'-10"(2.40m)

13 1

3

13

13

13

13

LOW PLASTICITY SILTS AND CLAYS (Ø=26°, = 120 pcf)GEOGRID: MIRAGRID 3XT BY TENCATE (RFd=1.10,RFcr=1.45, RFid=1.05, Cds=0.7, Ci=0.7)

1. The information contained in the design charts is supplied for information purposes only and assuch should only be used for preliminary designs.

2. The height (H) of the wall is the total height from the leveling pad to the top of the wall notincluding the thickness of the cap.

3. Soil parameters: reinforced soil (φ = 26°, γ = 120 pcf); retained soil (φ =26°, γ = 120 pcf);foundation soil (φ=26°, γ = 120 pcf)

4. A qualified engineer should be consulted for the final design to be used for construction.5. The foundation soil must be able to support the wall system. The bearing capacity of the

foundation soil, settlement, and global stability must be verified and validated by a qualifiedgeotechnical engineer.

6. The seismic analysis is not included.7. The design charts do not apply to tiered walls.8. The charts assume that the walls are constructed in accordance with Techo-Bloc

specifications, good construction practice and an adequate drainage system.9. The geogrid layout has been optimized to satisfy the design requirements of the NCMA's

Design Manual for Segmental Retaining Walls, 3rd Edition.10. The minimum burial depth must be 6 in (150 mm) or 10% of the exposed height, whichever is

greater.11. Engineering judgement should be used when interpolating between heights.

12. Techo-Bloc and its predecessors, successors, beneficiaries, employees, associates,administrators and insurers accepts no liability for the incorrect use of information contained inthe design charts.

13. For further information, please contact our technical service department.

HDPE horizontal key isinserted in the front groove

Note:Near Vertical walls shall be constructed withpositive batter by tilting units back towards fillon leveling pad. A negative 3.0 % minimumleveling pad slope is recommended. A 3.0%slope is equivalent to an elevation drop of 3/8 "along 12"

Front of unit1.7°

3.0 %

DESIGN CHARTMINI-CRETA 6"

(EQUIVALENT TO TWICE THE MINI-CRETA 3")NEAR VERTICAL

12"3/8 "

5'-6'' (1.68 m)

5'-6'' (1.68 m)

5'-6'' (1.68 m)

6'-6'' (1.98 m)

8'-0'' (2.44 m)

11'-6'' (3.50 m)

6'-6'' (1.98 m)

8'-0'' (2.44 m)

11'-6'' (3.50 m)

6'-6'' (1.98 m)

8'-0'' (2.44 m)

11'-6'' (3.50 m)

6'-6'' (1.98 m)

8'-0'' (2.44 m)

11'-6'' (3.50 m)

8'-0'' (2.44 m)

11'-6'' (3.50 m)

11'-6'' (3.50 m)

Page 32: MINI-CRETA 3” & 6”...DESIGN CHART 3 45657No su 4 HDPE VERTICAL KEY (alignment pin) TECHNICAL SPECIFICATIONS PHYSICAL CHARACTERISTICS DESIGN DATA MINI-CRETA 3” MINI-CRETA 6”

D E S I G N C H A R TM I N I - C R E TA

• DE-ICING SALT RESISTANT

• STRENGTH & DURABILITY

• TRANSFERABLE LIFETIME WARRANTY

• COLOR THROUGH & THROUGH

TOLL FREE:

1.877.832.4625

WWW.TECHO-BLOC.COM

PROUD MEMBER OF

MONTREAL5255 Albert-Millichamp Street, Saint-Hubert, QC J3Y 8Z8

OTTAWA3455 Hawthorne Road, Ottawa, ON K1G 4G2

TORONTO10 Freshway Drive,Vaughan, ON L4K 1S3

TORONTO1050 Industrial Road,Ayr, ON N0B 1E0

C A N A D A

PENNSYLVANIA852 W. Pennsylvania Avenue,Pen Argyl, PA 18072

PENNSYLVANIA23 Quarry Road,Douglassville, PA 19518

MASSACHUSETTS70 East Brookfi eld Rd.,North Brookfi eld, MA 01535