min purge gas rate

4
US Customary Units: where: Q = pure gas rate, SCFH D = flare stack diameter, inch Hydrogen: K = +5.783 Helium: K = +5.078 Methane: K = +2.328 Nitrogen: K = +1.067 (No wind) Nitrogen: K = +1.707 (Wind 15 to 20 MPH or 6.7 to 8.9 m/s) Ethane: K = -1.067 Propane: K = -2.651 C4+: K = -6.856 Note that steam or other condensable is not a suitable purge gas SI units: where: D = flare stack diameter, m Note: Lower oxygen concentrations should be used for certain flared gases US Customary Units: purge gas is heavier than air, purge rate based on nitrogen should be use as below: y = stack column depth at which the oxygen concentration (O2) is to be pr O2 = oxygen concentration, volume percent Ci = Volume fraction of i th component Ki = Constant for component i. Typical values for Ki are: CO2: K = -2.651 Q = pure gas rate, m 3 /h y = stack column depth at which the oxygen concentration (O2) is to be pr O2 = oxygen concentration, volume percent Ci = Volume fraction of i th component Ki = Constant for component i (see above) These equations can be simplified using the standard criteria of limiting volume, 25 ft (7.62 m) down the flare stack. Simplified equation considering O2 volume percent as 6% and at a depth of 25 ft (7.62 m) of Q = 0.0035283*D 3.46 *K Q = 0 . 07068 × D 3.46 × ( 1/y ) × ln (20.9/ O 2 ) × [ i n C i 0.65 × K i ] Q = 190 . 8 × D 3. 46 × ( 1/y ) × ln( 20.9/ O 2) × [ i n C i 0.65 × K i ]

Upload: chemkumar16

Post on 28-Nov-2015

133 views

Category:

Documents


16 download

DESCRIPTION

purge rate

TRANSCRIPT

Page 1: Min Purge Gas Rate

US Customary Units:

where:Q = pure gas rate, SCFHD = flare stack diameter, inch

Hydrogen: K = +5.783Helium: K = +5.078Methane: K = +2.328Nitrogen: K = +1.067 (No wind)Nitrogen: K = +1.707 (Wind 15 to 20 MPH or 6.7 to 8.9 m/s)Ethane: K = -1.067Propane: K = -2.651

C4+: K = -6.856Note that steam or other condensable is not a suitable purge gas

SI units:

where:

D = flare stack diameter, m

Note: Lower oxygen concentrations should be used for certain flared gases such as hydrogen

US Customary Units:

Husa correlation should be used to calculate minimum purge gas flow rates for gases lighter than air. If purge gas is heavier than air, purge rate based on nitrogen should be used. Husa correlation is expressed as below:

y = stack column depth at which the oxygen concentration (O2) is to be predicted, ft

O2 = oxygen concentration, volume percent

Ci = Volume fraction of ithcomponent

Ki = Constant for component i. Typical values for Ki are:

CO2: K = -2.651

Q = pure gas rate, m3/h

y = stack column depth at which the oxygen concentration (O2) is to be predicted, m

O2 = oxygen concentration, volume percent

Ci = Volume fraction of ithcomponent

Ki = Constant for component i (see above)

These equations can be simplified using the standard criteria of limiting the O2 concentration to 6% by volume, 25 ft (7.62 m) down the flare stack.

Simplified equation considering O2 volume percent as 6% and at a depth of 25 ft (7.62 m) of the flare stack

Q = 0.0035283*D3.46*K

Q = 0 . 07068 × D3.46× (1/y ) × ln (20 . 9/ O 2 ) × [∑i

n

Ci0.65× K i ]

Q = 190 .8 × D3.46× (1/y ) × ln (20 . 9/ O 2 ) × [∑i

n

Ci0.65× K i ]

Page 2: Min Purge Gas Rate

where:Q = purge gas rate, SCFHD = flare stack diameter, inch K = constant (see above)

SI units:

where:

D = flare stack diameter, m K = constant (see above)

where:

Q = 31.25*D3.46*K

Q = purge gas rate, Nm3/h

Values of Ki for gases lighter than air are determined from

Ki = exp(0.065*(29 - MWi))

Values of Ki for gases heavier than air are determined from an amended Husa correlation where (MWi - 29) is substituted for MWi as follows:

Ki = exp(0.065*(MWi - 29))

MWi = molecular weight of the ith component of n components

Note: Husa correlation is generally applicable for no wind to wind speeds up to 30 MPH (13 m/s). Where prevailing wind speeds are higher, higher purge rates may be required.

Page 3: Min Purge Gas Rate

Note: Lower oxygen concentrations should be used for certain flared gases such as hydrogen

Husa correlation should be used to calculate minimum purge gas flow rates for gases lighter than air. If purge gas is heavier than air,

concentration to 6% by volume, 25 ft (7.62 m) down the

volume percent as 6% and at a depth of 25 ft (7.62 m) of the flare stack

Page 4: Min Purge Gas Rate

for gases heavier than air are determined from an amended Husa correlation where (MWi - 29) is substituted for MWi as

Note: Husa correlation is generally applicable for no wind to wind speeds up to 30 MPH (13 m/s). Where prevailing wind