midel en 1215 - midel americas€¦ · midel en 1215 moisture tolerance and asset life extension...
TRANSCRIPT
CONTENTS
Increased Fire Safety Page 3
Moisture Tolerance Page 4
Fluid Maintenance Guide – Distribution Transformers Page 6
Storage and Handling Guide Page 8
Safety Data Sheet Page 9
MIDEL eN 1215
Increased Fire Safety
June 2016 Page 3 of 13
®
Increased Fire Safety
Transformer fires are particularly
unforgiving, spreading very quickly and
causing extensive damage, often with the
tragic loss of human life. In short,
transformer fires are an everyday
occurrence in power networks worldwide.
MIDEL eN 1215 offers the perfect solution
in terms of fire risk mitigation. With a high
fire point and certified as a less flammable
fluid, MIDEL eN 1215 joins a set of
dielectric liquids that have an impeccable
100% fire safety record since their
introduction in the 1970s.
FM Global® and Underwriters Laboratory,
two internationally recognized insurance
companies, have listed MIDEL eN 1215 as
a less flammable fluid for dielectric
purposes. This means it requires lower fire
safety measures than mineral oil. In
addition MIDEL eN 1215’s fire safe
properties allow for use in transformers
inside buildings and other critical areas
where mineral oil would not be acceptable.
Flash and Fire Point
MIDEL eN 1215 has been specifically
formulated to give a high flash and fire
point, well in excess of those required for
less flammable status and far superior to
mineral oil (Table 1).
The high fire point of MIDEL eN 1215
ensures that it will be very difficult to ignite
and that the risk of pool fires is all but
eliminated. In addition, being a listed less
flammable fluid, MIDEL eN 1215 benefits
from reduced equipment spacing
requirements, as specified in the National
Electrical Code (NFPA 70), section 450-23.
Further recommendations for less
flammable fluids can be found in the FM
Global loss prevention datasheet 5-4
‘Transformers’. By applying the FM Global
advice signficant space savings can be
made, especially for small to medium
power transformers filled with
MIDEL eN 1215.
Figure 1 shows a comparison of
transformer installations with mineral oil
and FM Approved fluid, in the volume
range 5,000-10,000gal. An additional
benefit from these recommendations would
be shorter LV cable runs and hence lower
losses.
Table 1 - Flash and Fire Points
Parameter Test Method MIDEL eN 1215 Mineral Oil
Flash Point ISO 2592 /
ASTM D92 >315°C 160°C
Fire Point ASTM D92 >350°C 170°C
Net Calorific Value ASTM D240-02 37.5MJ/kg 46.0MJ/kg
Data quoted above are typical values
Figure 1 - Example installations, mineral oil and FM Approved fluid
MIDEL eN 1215
Moisture Tolerance and Asset Life Extension
March 2016 Page 4 of 13
®
Moisture Tolerance
MIDEL eN 1215 has a very high moisture
tolerance. This means it can absorb far
greater amounts of water than mineral oil
and silicone liquid without compromising its
dielectric properties. MIDEL eN 1215 can
also consume water which may slow down
cellulose ageing. In the case of mineral oil,
there is a danger that this water will be
released as condensation.
Why Moisture Tolerance is Important in
Transformers:
Dielectric strength - reduces as moisture
content increases
Rate of paper ageing - increases with
higher moisture content
Condensation during cool down - risk of
release of free water from mineral oil
Dielectric Strength
Figure 1 shows the breakdown voltage at
ambient temperature of MIDEL eN 1215,
mineral oil and silicone liquid with
increasing moisture levels. It clearly
illustrates that even a small amount of
water in mineral oil and silicone liquid
cause a rapid deterioration in breakdown
voltage. In contrast, MIDEL eN 1215
maintains a high breakdown voltage even
when moisture levels exceed 300ppm.
Paper Ageing and Asset Life
The rate of paper ageing is directly related
to water content. Various studies have
shown that the lifetime of paper reduces by
as much as a factor of ten for each extra
1% of water content in the cellulose. As the
cellulose ages it releases water, thus
accelerating the ageing process. Therefore
it is vital that cellulose is kept as dry as
possible.
Evidence from a number of studies with
natural ester has demonstrated that this
type of fluid keeps the paper drier and can
enhance lifetime. The findings are
summarized in Annex B of IEEE C57.154,
published in 2012. This includes a unit life
prediction for thermally upgraded paper
immersed in natural ester, in comparison to
mineral oil, as shown in figure 2.
By using the information in this standard,
users can either extend the lifetime of
transformers, or alternatively run at a
higher temperature while maintaining the
same life. With thermally upgraded paper
the increase in temperature can be as
much as 20°C, which in turn allows more
compact transformer designs. Another way
to use this benefit is to allow overloading of
the transformer by up to 20%.
Figure 1 - Breakdown voltage vs. moisture content at 20°C (IEC 60156 2.5mm)
Figure 2 - TUP Unit Life vs Temperature IEEE C57.154 Annex B
0.001
0.01
0.1
1
10
100
100 105 110 115 120 125 130 135 140 145 150 155 160 165 170 175 180 185
Un
it o
f N
orm
al
Pap
er
Lif
eti
me
Temperature C
TUP in Mineral Oil
TUP in Natural Ester
≈7
MIDEL eN 1215
Moisture Tolerance and Asset Life Extension
March 2016 Page 5 of 13
®
Condensation During Cool Down
With mineral oil there is a potential for
water to be released when a transformer
cools from operating temperature to
ambient. This is because mineral oil has a
low moisture saturation limit, which reduces
as the temperature drops. MIDEL eN 1215
has a much higher saturation limit, which
means that it is far more difficult to reach
the saturation point.
For example if a transformer with mineral
oil and a paper water content of 1.5% was
running at 90°C the water content of the
mineral oil would be 65ppm. If the
transformer then shut down, the water
would tend to stay in the mineral oil. At
20°C the saturation limit of mineral oil is
55ppm, so the mineral oil would be 118%
saturated, releasing free water into the
transformer. The breakdown voltage of the
mineral oil will also be very low, increasing
risk of failure when restarting.
Using the same example for MIDEL eN
1215 at 90°C the water content would be
around 300ppm. The saturation limit for
MIDEL eN 1215 at 20°C is 1100ppm, so
even if all the water stays in the MIDEL eN
1215 it will only be 27% saturated. This
means there would be no free water and
still an excellent breakdown voltage.
Moisture Content Testing
Natural esters, such as MIDEL eN 1215
have a much higher affinity for water than
mineral oil and this is reflected in the
moisture content limits for the fluids. A
comparison of the standard values relating
to moisture content for new fluids are
shown in Table 1. New MIDEL eN 1215, as
delivered, is manufactured to very high
standards with a typical moisture content of
50ppm.
The different water behavior of esters has
practical implications for the interpretation
of moisture level analysis between MIDEL
eN 1215 and mineral oil in service. Users
should be careful to apply the correct limits
from guides such as IEEE C57.147. Also, if
moisture-monitoring equipment is
integrated within a transformer, it should be
calibrated for natural ester and tolerance
settings should be adjusted accordingly.
Moisture Removal
Should the moisture content rise above the
maximum recommended in-service limit,
the same methods and equipment that are
used for removing moisture from mineral oil
can also be used to remove moisture from
MIDEL eN 1215. Dissolved water can be
efficiently removed by the use of vacuum
dehydration equipment, or by the use of
molecular sieves.
For further advice on the moisture
tolerance and asset life extension benefits
of MIDEL eN 1215 please contact the
MIDEL technical team on:
Table 1 - Standards for moisture content in equipment at ≤69kV
Standard Moisture Content
IEEE C57.147 – Natural Ester max. 300ppm
IEEE C57.106 – Mineral Oil max. 35ppm
MIDEL eN 1215
Fluid Maintenance Guide - Distribution Transformers
April 2016 Page 6 of 13
®
General
MIDEL eN 1215 is a natural ester based
fluid which is designed for long service in
sealed transformer systems. As with
mineral oil, in order to ensure that MIDEL
eN 1215 gives continued good service it is
possible to monitor a number of the fluid
parameters throughout the life of the
transformer. Testing the fluid also has the
added benefit of picking up any potential
problems with the transformer before a
failure occurs.
Generally, for distribution transformers,
sampling of the fluid is recommended
before energizing, after the first year of
service and at five year intervals thereafter.
For larger power transformers, highly
loaded or critical units, the frequency of
testing may be increased and annual
checks are commonly used.
It is important to understand some
fundamental differences between MIDEL
eN 1215 and mineral oils when carrying out
fluid testing for maintenance. Many
laboratories are now experienced in the
testing of ester based fluids, but at times a
failure can be logged against a sample
when the incorrect mineral oil limits are
applied.
Applying the limits from this guide will
ensure that the MIDEL eN 1215 fluid is in
suitable condition for continued use. Users
can also refer to the IEEE C57.147 ’IEEE
Guide for Acceptance and Maintenance of
Natural Ester Fluids in Transformers’. It
should be noted that this guide and the
IEEE standard do not apply to retrofilled
transformers, i.e. those that have been
previously filled with another fluid. If there
is any doubt about how the limits from
these guides may be applied to MIDEL eN
1215 in service, please contact the MIDEL
technical team.
Breakdown Voltage Testing
The breakdown voltage of new MIDEL eN
1215 is typically in excess of 50kV when
tested to the ASTM D 1816 2mm gap
method. Even at high moisture contents, up
300ppm at ambient temperature, testing
has shown that the breakdown voltage of
MIDEL eN 1215 will be preserved at a high
level.
There are some issues that can cause a
drop in breakdown voltage and the first is
particulate matter in the fluid. Particles can
float between the test probes and cause a
localized weakness when carrying out the
breakdown test. This can usually be
identified by erratic results when comparing
a series of breakdowns. If particles are
suspected to be causing a breakdown
issue then the fluid can be filtered through
a fine paper filter and re-tested.
Another issue that can arise is if not
enough settling time is allowed between
each breakdown test. In this case, gas
bubbles formed by the breakdown arc are
not given sufficient time to dissipate and
can cause a weak link between the probes.
Typically an average of six breakdown
tests are taken and it is recommended to
leave a minimum settling time of fifteen
minutes before the first breakdown test and
then five minutes between each
subsequent breakdown test to ensure that
gas bubbles have sufficient time to
disperse.
Kinematic Viscosity
If a natural ester fluid, such as MIDEL eN
1215, is exposed to air at elevated
temperatures, for example when there is a
leak in the transformer seal, then there will
be a gradual increase in viscosity as the
fluid reacts with oxygen. To monitor the
sealing of a transformer system it is
therefore possible to test the fluid viscosity
periodically. When measured at 40°C an
increase of more than 10% from the
original starting value of 32mm2/s should
be a trigger for further investigation.
Fire Point Testing
Fire point testing can be conducted to
determine if the MIDEL fluid has been
contaminated with another fluid with a
lower fire point, such as mineral oil.
However, fire point is less indicative of the
condition of the fluid than other tests, such
as the neutralization value. If there is no
possibility of cross contamination then fire
point testing may not be required on a
routine basis.
Table 1 - Common Test Parameters and Guidance Limits for Equipment at
≤69kV
Parameter Test Method IEEE C57.147 (2008)
Table 5
Water Content ASTM D1533 max. 540mg/kg*
Breakdown Voltage ASTM D1816 2mm min. 40kV
Fire Point ASTM D92 min.300°C
* same relative saturation as mineral oil at 20°C
MIDEL eN 1215
Fluid Maintenance Guide - Distribution Transformers
April 2016 Page 7 of 13
®
DGA and Furan Analysis
Diagnosis of transformer performance by
traditional DGA and Furan analysis is still
applicable to MIDEL eN 1215 filled
transformers. The methods to diagnose
faults with DGA in mineral oil can still be
used, but adjustments need to be made to
Duval triangle boundaries and table ratios.
Guidance on DGA for ester fluids is
contained in IEEE C57.155 ‘IEEE Guide for
Interpretation of Gases Generated in
Natural Ester and Synthetic Ester-
Immersed Transformers’. For further
information regarding ester DGA and
maintenance users can also contact the
MIDEL technical department on:
MIDEL eN 1215
Storage & Handling Guide
January 2016 Page 8 of 13
®
Introduction
MIDEL eN 1215 is a natural ester-based
dielectric fluid that is manufactured from
renewable, edible seed oil. MIDEL eN 1215
has been formulated to provide a cost
effective fluid for use in sealed
transformers under temperate climate
conditions. It is also ideally suited to indoor
installations where fire safety is a priority.
To provide excellent dielectric properties
MIDEL eN 1215 is dried and degassed
prior to filling the shipping containers. In
order to keep it in optimum condition it is
necessary to take some precautions when
handling or storing the fluid.
Receiving New MIDEL eN 1215
MIDEL eN 1215 can be delivered in 5
gallon, 55 gallon drums and 330 gallon
totes.
Totes users may notice a slight
deformation of the containers. This is due
to the degassed fluid absorbing the small
amount of air in the headspace, creating a
vacuum. This is perfectly normal and a
good indication that the seal has not been
compromised. In contrast 55 gallon drums
of MIDEL eN 1215 are not likely to deform.
This lack of deformation does not mean
that the drum seal has been compromised.
Storage
If kept in the original unopened containers
MIDEL eN 1215 has a long shelf life. Once
opened precautions should be taken to
preserve the fluid. In common with other
natural ester fluids MIDEL eN 1215 is less
oxidation stable than mineral oil, so contact
with oxygen from the air should be avoided,
especially if the fluid is heated. MIDEL eN
1215 is also hygroscopic and contact with
moist air for prolonged periods will result in
the fluid absorbing atmospheric moisture. If
a partially emptied container is necessary
for storage the head space should ideally
be back-filled with dry nitrogen to exclude
oxygen before properly resealing.
If the fluid is kept in intermediate bulk
containers the ideal location will be indoors
to avoid extremes of temperature and
exposure to the weather. Where outdoor
storage is unavoidable exposure to direct
sunlight should be prevented using a
simple covering. Storage tanks suitable for
standard mineral oil can be used for storing
MIDEL eN 1215. The tank headspace must
have a dry nitrogen blanket to keep out air
and moisture.
Pumping
MIDEL eN 1215 is an excellent lubricant,
so no specialist pumping equipment is
required. The viscosity of MIDEL eN 1215
is slightly higher than mineral oil at ambient
temperatures and this must be taken into
account when specifying pumping systems.
A higher capacity pump will be needed to
maintain the same flow rate as mineral oil
at a given temperature.
If MIDEL eN 1215 is stored outside in
ambient temperatures below 10°C it may
be necessary to heat the fluid prior to
pumping, in order to reduce the viscosity.
As with any dielectric fluid there is a
possibility of static charge build up when
MIDEL eN 1215 is flowing through the
pipes. The user should ensure that all
pumps, lines and vessels are adequately
bonded and earthed during pumping
operations.
Transformer Filling and Cellulose
Impregnation
To avoid air entrapment in the transformer
cellulose the tank should be filled from the
bottom, ideally under vacuum. In order to
aid impregnation of the cellulose it is
recommended that MIDEL eN 1215 be
heated to between 60 and 80°C when filling
and that this temperature is maintained for
the impregnation period. At 70°C the
viscosity of the fluid is very close to that of
mineral oil at 20°C, and a similar
impregnation rate has been observed in
laboratory testing.
Throughout all stages of the filling
operation it is recommended that the
introduction of air or particulate matter be
avoided. If exposure to the air is
unavoidable then the duration of this
contact should be minimized to avoid any
degradation of the fluid.
The outlet side of any pump used during
filling should be protected by a fine mesh or
paper element filter. The use of degassing
and vacuum filling is possible with MIDEL
eN 1215, using the same type of
equipment and methods employed with
mineral oil.
Thin Films of Natural Ester
Particular care should be taken to avoid
contact between the air and thin films of
natural ester based fluids, such as MIDEL
eN 1215. This is especially true if the
surface is warm, since there is a risk of
polymerization of the fluid if left for an
extended period, which would lead to
gelling and the formation of tacky surfaces.
Due to this risk of oxidation, if equipment
has been drained of MIDEL eN 1215 it is
recommended that it is filled with an inert
gas, or refilled with fluid as soon as
possible. Furthermore hot air drying is not
suitable for active parts already
impregnated with natural ester fluid.
Methods which do not expose the
impregnated parts to air, such as vapor
phase drying can be utilized.
MIDEL eN 1215
Safety Data Sheet
November 2016 Page 9 of 13
®
1. Identification of the
Substance/Mixture and of the
Company/Undertaking
1.1 Product Identifier
Material Name: MIDEL eN 1215.
CAS No: 68956-68-3.
1.2 Relevant identified uses of the substance or mixture and uses advised against
Product Use: Dielectric fluid.
Uses advised against: None.
1.3 Details of the supplier of the substance or mixture
Company: M&I Materials Inc., 3675 Crestwood Parkway, Suite 400, Duluth, GA 30096,
USA.
Telephone: +1 770 817 7637.
Emergency Telephone: US Toll free: +1 844 835 4911. UK: +44 (0)161 864 5439.
Email: [email protected].
2. Hazards Identification This product is not classified as hazardous and therefore there is no legal requirement to
provide an SDS in Europe. This document has been compiled for information purposes, in
accordance with Regulation (EU) No 453/2010 and OSHA hazard communication
guidelines.
2.1 Classification of the substance or mixture
Regulation (EC) No 1272/2008 (CLP): Not classified.
2.2 Label elements
Regulation (EC) No 1272/2008 (CLP): No symbol or signal word.
2.3 Other hazards
None.
3. Composition/Information on
Ingredients
3.1 Substance
CAS No.: 68956-68-3. Description: Blend of natural triglyceride esters (vegetable oil). Composition:
Constituent CAS Number Contents
Blend of natural triglyceride esters
68956-68-3 >98.5%
Performance enhancing additives
Proprietary <1.5%
All constituents are listed on the TSCA inventory. Additives used in this product are a trade secret, but do not lead to classification of the substance as hazardous.
4. First Aid Measures 4.1 Description of first aid measures
Inhalation: None envisaged due to the low vapor pressure of the substance.
Skin: Wash with soap and water. Obtain medical attention if irritation develops.
Eyes: Irrigate with copious amounts of water. Obtain medical attention if irritation
develops.
Ingestion: Do not induce vomiting, obtain medical attention.
MIDEL eN 1215
Safety Data Sheet
November 2016 Page 10 of 13
®
4.2 Most important symptoms and effects, both acute and delayed
No adverse effects expected.
4.3 Indication of any immediate medical attention and special treatment needed
No special treatment required.
5. Fire Fighting Measures 5.1 Extinguishing media
Carbon dioxide, dry powder, foam or water fog. Do not use water jets.
5.2 Special hazards arising from the substance or mixture
None.
5.3 Advice for fire fighters
Self-contained breathing apparatus may be required.
6. Accidental Release
Measures
6.1 Personal precautions, protective equipment and emergency procedures
Spilt product constitutes a slip hazard. Avoid contact with skin and eyes.
6.2 Environmental precautions
Do not contaminate any lakes, streams, ponds, groundwater or soil. Avoid flushing into drains. In the event of a large spillage contain product as thoroughly as possible and dispose of in accordance with local regulations.
6.3 Methods and material for containment and cleaning up
Soak up spilt material with absorbent granules for disposal.
7. Handling and Storage 7.1 Precautions for safe handling
Avoid eye and prolonged skin contact.
7.2 Conditions for safe storage, including any incompatibilities
No special precautions required.
7.3 Specific end use(s)
Exposure to air should be minimized. Opened containers should be properly resealed
8. Exposure Controls/
Personal Protection
8.1 Control parameters
No relevant control parameters.
8.2 Exposure controls
Eye washes should be available for emergency use.
Respiratory protection: None required.
Skin protection: Wear coveralls.
Hand protection: Wash hands after use. For prolonged or repeated skin contact gloves
are recommended.
Eye protection: If splashes are likely to occur wear safety glasses.
MIDEL eN 1215
Safety Data Sheet
November 2016 Page 11 of 13
®
9. Physical and Chemical
Properties
9.1 Information on basic physical and chemical properties
Appearance: Pale amber liquid.
Odor: None.
pH: Not applicable.
Freezing point: -18°C.
Initial boiling point and boiling range: >300°C.
Flash point: >315°C (open cup).
Flammability (solid, gas): Nonflammable.
Upper/lower flammability or explosive limits: Data not available.
Vapor pressure: Data not available.
Vapor density: Not applicable.
Relative density: 0.92 at 20°C.
Water solubility: <1mg/l.
Solubility: Not applicable.
Partition coefficient: Data not available.
Auto-ignition temperature: No auto-ignition expected.
Decomposition temperature: Data not available.
Viscosity: 32mm2/s at 40°C.
Explosive properties: Non-explosive.
Oxidizing properties: Non-oxidizing.
9.2 Other information
Not applicable.
10. Stability and Reactivity 10.1 Reactivity
Stable under normal conditions of use.
10.2 Chemical stability
Stable under normal conditions of use.
10.3 Possibility of hazardous reactions
Data not available.
10.4 Conditions to avoid
Temperatures >250°C.
10.5 Incompatible materials
Strong oxidizing agents.
10.6 Hazardous decomposition products
None.
11. Toxicological Information 11.1 Information on toxicological effects
Likely routes of exposure: Skin and eyes are the most likely routes for exposure.
Accidental ingestion may occur. Inhalation is not expected to be a relevant route of
exposure. Product is vegetable oil based and as such non-toxic.
Acute oral toxicity: Considered to be low toxicity, vegetable oil.
MIDEL eN 1215
Safety Data Sheet
November 2016 Page 12 of 13
®
Acute dermal toxicity: Considered to be low toxicity.
Acute inhalation toxicity: Low volatility makes inhalation unlikely.
Skin corrosion/irritation: Considered to be not irritating.
Eye corrosion/irritation: Considered to be not irritating.
Respiratory or skin sensitization: Considered to be not sensitizing.
Aspiration hazard: Not considered an aspiration hazard.
Carcinogenicity/mutagenicity: Not considered a mutagenic hazard or carcinogen. This
product is not considered to be a carcinogen by IARC, ACGIH, NTP or OSHA.
12. Ecological Information When used and/or disposed of as indicated no adverse environmental effects are
foreseen. Eco toxicological effects based on knowledge of similar substances.
12.1 Toxicity
Substances of this type do not pose a hazard to aquatic organisms. 12.2 Persistence and degradability
Readily biodegradable.
12.3 Bio accumulative potential
No potential for bioaccumulation.
12.4 Mobility in soil
Considered to have low mobility in soil.
12.5 Results of PBT and vPvB assessment
The product does not meet criteria for toxicity which requires further assessment. It is not
considered PBT or vPvB.
12.6 Other adverse effects
No other adverse effects envisaged.
13. Disposal Considerations 13.1 Waste treatment methods
Product and packaging must be disposed of in accordance with local and national
regulations. May be incinerated. Unused product may be returned for reclamation.
14. Transport Information Not classified as hazardous under air (ICAO/IATA), sea (IMDG), road (ADR) or rail (RID)
regulations.
14.1 UN number
Not relevant.
14.2 UN proper shipping name
Not relevant.
14.3 Transport hazard class
Not relevant.
14.4 Packing group
Not relevant.
MIDEL eN 1215
Safety Data Sheet
November 2016 Page 13 of 13
®
14.5 Environmental hazards
Not relevant.
14.6 Special precautions for user
Not relevant.
15. Regulatory Information 15.1 Safety, health and environmental regulations/legislation specific for the
substance or mixture
Product is exempt from REACH registration.
All constituent substances in this product are listed in the TSCA inventory.
15.2 Chemical safety assessment
A chemical safety assessment has not been carried out for this product.
16. Other Information Compiled according to regulation 1907/EC/2006, Annex II, as amended by Regulation
(EU) No. 453/2010 and OSHA hazard communication guidelines.
16.1 Changes from last issue:
Additional regulatory information to comply with OSHA guidelines. Emergency telephone
number.
The information provided in this Safety Data Sheet is correct to our best knowledge, information and belief at the date of its publication. It
is intended to describe the product for the purposes of health, safety and environmental requirements only. It should not be construed as
guaranteeing any specific property of the product.