Mid-Sized Data Center UPS Solutions Overview
© 2008 Eaton Corporation. All rights reserved.
2 2
Mid-Range System Concerns
Cooling Designs
Future Growth
Efficiency
Energy Costs
ConsolidationGreen
Virtualization
IT / ENGINEERS / BUYERS
3 3
Power PerformanceHigher output with lower operating costs
Five Compelling Values:
Power DensitySmallest space, leaving more room for IT equipment
ScalabilityEasy upgrades because you KNOW you’ll grow
Battery ManagementImportant data on key maintenance items longer life
ServiceabilitySomeone WILL be there to support you!
Mid-Range UPS Application Needs
4 4
Next-Generation Three-Phase UPS System
Advanced performance» Transformerless (Native 208V, 400V, 480V) » Active Front-End Converter» Double Conversion
Increased reliability» Advanced Battery Management» Remote UPS/Battery Monitoring (eNotify)
Better serviceability» Front access» Warranty/Service coverage
Consistent design for entire system» UPS modules» Battery cabinets» Integrated Distribution Cabinet» Integrated Accessory Cabinet
Eaton 9390 UPS
9390 System Overview (20-160kVA)
5 5
Competitor M5 <3% 0.8 94% / 97%
Competitor M-C <10%* 0.8 90-95%
Competitor N <3% 0.9 94% / 97%
Competitor C <7% 0.8 87-93%
Competitor G <7% 0.8 90%-93.3%
Competitor T <3% 0.8 88.5%-94%
Competitor M <3-7% 0.8 87%??
Manufacturer Input THD Output PF Efficiency
Eaton 9390 <4.5% 0.9 94.5% / 99%
*w/filter (~30% w/out)
9390 provides the best overall power performance
Eaton 9390 UPS
9390 Power Performance
6 6
Eaton 9390 160kVA Efficiency Curve
% LOAD
% E
FFIC
IEN
CY
Eaton 9390 UPS
9390 Efficiency
Higher efficiency at 50% load than many competitors at full load!
7 7
MANUFACTURER (kVA RATING)
SQU
ARE
INC
HES
Eaton 9390 UPS
FOOTPRINT
Power Density
9390 provides the highest power density» Over 33% smaller footprint than our nearest competitor» Even more powerful considering 0.9 output power factor» Front access only required» Even the 9390 160kVA is smaller than many competitive 80kVA units!
8 8
POU
ND
S
Eaton 9390 UPS
MANUFACTURER (kVA RATING)
9390 saves installation costs» Half the weight of the nearest competitor» Reduced transportation and installation costs» Easy to handle» Even the 9390 160kVA is lighter than competitive 80kVA units!
Power Density
9 9
“Inside the Box” - Single module upgradeability» 9390-40/xxxx = 20, 30, or 40kVA» 9390-80/xx xx = 40, 50, 60, or 80kVA» 9390-120/xx xx = 100 or 120kVA » 9390-160/xx xx = 100, 120, or 160kVA
“Outside the Box” - Multi-Module Systems» Parallel for redundancy or capacity» Up to six modules without central bypass » Individual battery support removes a single-point-of-failure
possibility
Powerware® Hot Sync Paralleling Technology» Eliminates a single point of failure opportunity» Peer-to-peer paralleling without wires» Eliminates BUNDLES of inter-cabling» Easy to parallel units» Firmware setting changes» Hot Sync CAN bridge Card
Eaton 9390 UPS
Scalability
9390 provides simple connections and multiple levels of scalability designed to save installation costs and time
10 10
Protected AC from InvertersIf total system is redundant (N+1), failure of any one systems does not effect critical bus
Parallel System Operation
200kVA load with 320kVA total capacity
11 11
Protected AC from InvertersIf UPSs are installed as a capacity system, failure of any system…
Parallel System Operation
250kVA load with 320kVA total capacity
12 12
Power through static bypass… forces all units to static bypass
Parallel System Operation
250kVA load with 320kVA total capacity
13 13
Tolerance+/- 10%
9390 Applications: Parallel Installation
14 14
9390 features a Variable Battery Bus:» 384 – 480VDC (192-240 cells, varies on AC voltage) » Pay only for the runtime you need!» Increase/decrease runtime» Match existing battery installations
Advanced Battery Management™ technology» Advanced charging algorithms » Automatic self tests » Patent pending “constant load test” no matter what’s on output» Temperature compensated charging available
Battery test results can be monitoredremotely “standard”» eNotify monitoring program
9390 provides the best total battery management
Eaton 9390 UPS
Battery Management
15 15
Advanced Battery Management» Extend your VRLA battery life » Reduce or eliminate the #1 cause of critical load shutdown» Catch weak batteries and predict possible failure
Eaton 9390 UPS
ABM Technology
16 16
9390 provides the best serviceability
»
100% Front Access» Fast, easy access» Unit can be backed up against wall
or into a corner» No clearance needed at rear or sides
Fast repair and return to service» Mean time to repair (MTTR) less
than 30 minutes» Power modules are field-replaceable units» Fan tray is a field-replaceable unit» Slide in/out design
Serviceability
17 17
Replaceable converter/inverter modules
Slide out fan tray
Modular static switch assembly
Input/Output connections
Redundant power supplies
X-Slotcommunication bays
DC connections
Bottom cable entry area
Top cable entry area
System Control and interface boards
Serviceable Design (40/80kVA)
18 18
Eaton 9390 UPS
One year parts and labor» 5 x 8 start-up with 7 x 24 on-site labor
Three year battery warranty with Eaton brand batteriesThree year full, seven year proratedbattery warranty with Enersys brand batteriesOne year battery warranty with C&D brand batteries
All batteries come with 1 year on-site labor service coverage
Tech Support - 7 x 24 Help desk available for technical support questions
Services - Many service options to meet the customers demands
Warranty and Service
19 19
Standard Communications:» Four X-Slot communication bays» Language support, select any of 14,
including Mandarin and Russian» 6 building alarm inputs» 512 event log history storage» Enhanced alarm configuration» Real time clock
Other Communications Options:» ConnectUPS WEB/SNMP Hub card» Modbus card» Hot Sync CAN bridge card
• Used to interface parallel units• Allow connection to RMP/SCM/RIM
» Industrial Relay card» Four (4) 250V/5A relay contacts
9390 Communication Snapshot
20 20
IBC-L Battery Cabinet(Integrated Battery Cabinet)
IBC-L Battery Cabinet(Integrated Battery Cabinet)
Consistent Accessory Design
21 21
IBC-L 1085mm/42.7” WIDE
IBC-S 570mm/22.5” WIDE
9390 Integrated Battery Cabinet
Variable battery bus configurations» 384VDC – 480VDC» (192 – 240 cells) » Virtually limitless runtime possibilities» Size batteries based on runtime, or» Size batteries based on lowest cost
0.8 and 0.9pf runtime Charts for sizingkVA upgrade supportIBC-S» Up to 16 minutes @ 40kVA» Up to 7 minutes @ 80kVA
IBC-L» 10 minutes to several hours…
22 22
Alternate Back-up Sources – Ni-CD Batteries
» Longer battery life thanVRLAs (20yr design)
» Wide temperature range(-40 deg C to + 60 deg C)
» Excellent resistance againstelectrical and mechanical stress
» Low to zero maintenance» Robust construction
» Long storage life
» Eaton has tested and certifiedprogramming for specific Ni-CDbrands and batteries
23 23
ReliabilityUsing flywheels in either stand-a-lone or parallel with battery configurations to improve reliability of the energy storage sub-system
Space savingsDeploying flywheels to free up space for revenue generating equipment or better utilization of available data center space
Installation or site issueLimited space, floor loading, temperature control, hazardous material
“Green Tech” by eliminating use of lead in a facility
Lower life-cycle cost than either VRLA or Wet cell batteries
Introduction to Flywheels - Market drivers
24 24
» Green power solution
» Power output of 70 to 300KW with a single unit
» Average runtime 12 sec. @ 275kVA 26 sec. @ 160kVA
» Able to parallel units forhigher power or longerrun-time
» 20 year life
» 6 year service intervals
» UL/C_UL and CE listed
Key Flywheel System Features
25 25
100-160kVA IDCBypass/transformer/Distribution Cabinet(Integrated Battery Cabinet)
40-80kVA IDCBypass/transformer/Distribution Cabinet(Integrated Battery Cabinet)
Consistent Accessory Design
26 26
Three mix-and-match functions:» Maintenance bypass » Voltage transformation or isolation» Power Distribution options
Up to (2) 42 pole panel boardsUp to (3) Sub-feed breakersin place of each panel board
Eliminates need for separate PDU’s» Combine with Integrated Accessory
Cabinet (IAC) for many uniquedistribution options.
40-80kVA870mm/34” Wide
100-160kVA1085mm/42” Wide
9390 Integrated Distribution Cabinets
27 27
9390 IDC
28 28
9390 IDC
2,3 or 4 breaker maintenance bypass with slide plate to ensure proper sequencing
Distribution breakers and/or panels
Transformer location
Cabinet used for:» Maintenance Bypass
requirements » Voltage matching or isolation
requirements» Distribution requirements
How can you configure» With or without bypass » With (2) 42 pole load centers » With (1 to 6) distribution breakers» With (1) 42 pole panel and
(1-3) 225A SFBs» Standard 200% rated neutral
29 29
IAC-D Distribution CabinetIAC-T Tie CabinetIAC-B Maintenance BypassCabinet (100-160kVA 208V only)(Integrated Accessory Cabinet)
IAC-SB Bypass CabinetIAC-ST Tie Cabinet(Integrated Accessory Cabinet “S”=Side Car)
Consistent Accessory Designs
30 30
Major functions» Maintenance bypass » Parallel Tie Cabinet» Distribution Cabinet
Up to (2) 42 pole panel boardsUp to (3) Sub-feed breakersin place of each panel board
Two form factors» 200mm / 8” sidecar bolted to UPS
MBM or Tie» 570mm / 22.5” free-standing cabinet
MBM, Tie, or Distribution
9390 Integrated Accessory Cabinets
Sidecar IAC Free-standing IAC
31 31
Bypass Input
Bypass Breaker
UPS Output (Isolation)
Rectifier Input (not shown)
9390 IAC-B Maintenance Bypass (160kVA)
32 32
System Load Breaker (SLB)
UPS #1 Output (MOB 1)
UPS #2 Output (MOB 2)
9390 IAC-T Parallel Tie Cabinet (160kVA)
33 33
42 pole panel board
Distribution Breakerselectronic adjustablewith 250A sensors 100-250A with 100A sensors 40-100A
Main Breaker (225A)for 42 pole panel board
Neutral connectionsDistribution breakers
9390 IAC-D Distribution Cabinet
34 34
160kVA 480V/480V with matching 480V IAC-SB
9390 Applications
35 35
80kVA with IAC-SB & 252 poles of distribution
9390 Applications
36 36
9390 Applications
80kVA system 5th floor computer room
Cabinet 1Aisle 6
Cabinet 3Engineering3rd Floor
Cabinet 2Finance2nd Floor
37 37
9390 Applications
38 38
160kVA 480/208V with IDC w / transformer & IAC-D(4) - 42 pole panel boards
9390 Applications
39 39
80kVA Two module redundant system using IAC-ST
9390 Applications
40 40
Scalable UPS with flexible power distribution
9390 Applications
41 41
» Efficient operation for energy savings and lower Total Cost of Ownership.
» Small size/weight for smaller footprint, easiershipping, handling, and installation. Keep valuable space open for computing equipment.
» Scalability for growth.
» Flexibility of design.
» Proven product design.
Focus Points for mid-size UPS
42 42