microsoft powerpoint - sensors - how to specify

42
5/28/2018 MicrosoftPowerPoint-Sensors-HowtoSpecify-slidepdf.com http://slidepdf.com/reader/full/microsoft-powerpoint-sensors-how-to-specify 1/42 Temperature Level 200: Temperature Level 200: How to Specify Sensors and How to Specify Sensors and Thermowells Thermowells

Upload: kronikloops

Post on 19-Oct-2015

59 views

Category:

Documents


0 download

DESCRIPTION

Sensors - How to Specify

TRANSCRIPT

  • Temperature Level 200:Temperature Level 200:How to Specify Sensors and How to Specify Sensors and ThermowellsThermowells

  • Emerson Process Management

    Rosemount Division Confidential

    Slide 2

    Learning ObjectivesLearning ObjectivesLearning Objectives In this section you will

    learn:

    How to specify US and Metric style sensors, including Thermocouples and RTDs

  • Emerson Process Management

    Rosemount Division Confidential

    Slide 3

    Sensor OfferingSensor OfferingSensor Offering

    AIS (Application Industry Sensors)

    Sanitary Hygenic Models

    68Q US

    65Q Metric

    65B MetricModel

    58C CuttableModel 1075 High TemperatureModel 1080/1082 Multipoint

    RTD Metric

    Model 65

    RTD US (Inches)

    Model 68

    Model 78

    Thermocouples - Metric

    Model 185

    Thermocouples

    US (Inches)

    Model 183

  • Temperature Level 200:Temperature Level 200:How to Specify Sensors How to Specify Sensors and and ThermowellsThermowells

    General RulesGeneral Rules

  • Emerson Process Management

    Rosemount Division Confidential

    Slide 5

    Required FieldsRequired FieldsRequired FieldsRequired FieldsRequired Fields

    CodeCode Connection HeadConnection Head Cable/Conduit EntryCable/Conduit Entry

    CC Rosemount, Aluminum Rosemount, Aluminum MM20 x 1.5020 x 1.50

    DD Rosemount, Aluminum Rosemount, Aluminum in. NPTin. NPT

    GG Rosemount, Stainless Steel Rosemount, Stainless Steel M20 X 1.50M20 X 1.50

    HH Rosemount, Stainless Steel Rosemount, Stainless Steel in. NPTin. NPT

    JJ GRGR--A/BL (BUZ), AluminumA/BL (BUZ), Aluminum M20 x 1.50 (with cable M20 x 1.50 (with cable gland)gland)

    LL TZTZ--A/BL (BUZH), AluminumA/BL (BUZH), Aluminum M20 x 1.50 (with cable M20 x 1.50 (with cable gland)gland)

    11 Rosemount, Aluminum, with LCD display coverRosemount, Aluminum, with LCD display cover M20 x 1.50M20 x 1.50

    22 Rosemount, Aluminum, with LCD display coverRosemount, Aluminum, with LCD display cover in. NPTin. NPT

  • How to Specify: How to Specify: 0065 RTD and 0185 0065 RTD and 0185 ThermocoupleThermocouple

    MetricMetric

    Note:Note:Rosemount Catalog or the Rosemount Catalog or the Temperature and Sensor Temperature and Sensor Assembly PDS RequiredAssembly PDS Required

  • Emerson Process Management

    Rosemount Division Confidential

    Slide 7

    Sensor TypeSensor TypeSensor Type

    ModelModel 00650065 Resistance Thermometer, Pt100, Class B Standard, suitable for Resistance Thermometer, Pt100, Class B Standard, suitable for transmitter transmitter mountingmounting

    01850185 Thermocouples, DIN EN 60584 (IEC 584), Class 1, suitable for Thermocouples, DIN EN 60584 (IEC 584), Class 1, suitable for transmitter transmitter mountingmounting

    Required Fields

  • Emerson Process Management

    Rosemount Division Confidential

    Slide 8

    Required FieldsRequired FieldsRequired Fields

    CodeCode Connection HeadConnection Head Cable/Conduit EntryCable/Conduit Entry

    CC Rosemount, Aluminum Rosemount, Aluminum MM20 x 1.5020 x 1.50

    DD Rosemount, Aluminum Rosemount, Aluminum in. NPTin. NPT

    GG Rosemount, Stainless Steel Rosemount, Stainless Steel M20 X 1.50M20 X 1.50

    HH Rosemount, Stainless Steel Rosemount, Stainless Steel in. NPTin. NPT

    JJ GRGR--A/BL (BUZ), AluminumA/BL (BUZ), Aluminum M20 x 1.50 (with cable M20 x 1.50 (with cable gland)gland)

    LL TZTZ--A/BL (BUZH), AluminumA/BL (BUZH), Aluminum M20 x 1.50 (with cable M20 x 1.50 (with cable gland)gland)

    11 Rosemount, Aluminum, with LCD display coverRosemount, Aluminum, with LCD display cover M20 x 1.50M20 x 1.50

    22 Rosemount, Aluminum, with LCD display coverRosemount, Aluminum, with LCD display cover in. NPTin. NPT

    NN No connection headNo connection head N/AN/A

    Required FieldsRequired Fields

  • Emerson Process Management

    Rosemount Division Confidential

    Slide 9

    Required FieldsRequired FieldsRequired FieldsRequired FieldsRequired Fields

    Sensor Lead Wire TerminationSensor Lead Wire Termination 00 Flying Leads Flying Leads no springs on DIN plate no springs on DIN plate

    22 Terminal Block Terminal Block DIN 43762DIN 43762

  • Emerson Process Management

    Rosemount Division Confidential

    Slide 10

    Required FieldsRequired FieldsRequired FieldsRequired FieldsRequired Fields

    0065 SENSOR ONLY0065 SENSOR ONLY

    CodeCode Sensor TypeSensor Type Temperature rangeTemperature range

    11 RTD single element, 4RTD single element, 4--wire wire --50 to 450 C 50 to 450 C ((--58 to 842 F)58 to 842 F)

    22 RTD dual element, 3RTD dual element, 3--wire wire --50 to 450 C50 to 450 C((--58 to 842 F)58 to 842 F)

    33 RTD single element, 4RTD single element, 4--wire wire --196 to 600 C196 to 600 C((--321 to 1112 F)321 to 1112 F)

    44 RTD dual element, 3RTD dual element, 3--wire wire --196 to 600 C 196 to 600 C ((--321 to 1112 F)321 to 1112 F)

  • Emerson Process Management

    Rosemount Division Confidential

    Slide 11

    Required FieldsRequired FieldsRequired FieldsRequired FieldsRequired Fields

    0185 SENSOR ONLY0185 SENSOR ONLY

    CodeCode Sensor TypeSensor Type Temperature rangeTemperature range

    03J103J1 Thermocouple, Type J, single element, ungrounded Thermocouple, Type J, single element, ungrounded --40 to 750 C 40 to 750 C ((--40 to 1382 F)40 to 1382 F)

    03K103K1 Thermocouple, Type K, single element, ungroundedThermocouple, Type K, single element, ungrounded --40 to 1000 C40 to 1000 C((--40 to 1832 F)40 to 1832 F)

    03N103N1 Thermocouple, Type N, single element, ungroundedThermocouple, Type N, single element, ungrounded --40 to 1000 C40 to 1000 C((--40 to 1832 F)40 to 1832 F)

    05J105J1 Thermocouple, Type J, dual element, isolated, ungroundedThermocouple, Type J, dual element, isolated, ungrounded --40 to 750 C 40 to 750 C ((--40 to 1382 F)40 to 1382 F)

    05K105K1 Thermocouple, Type K, dual element, isolated, ungroundedThermocouple, Type K, dual element, isolated, ungrounded --40 to 1000 C40 to 1000 C((--40 to 1832 F)40 to 1832 F)

    05N105N1 Thermocouple, Type N, dual element, isolated, ungroundedThermocouple, Type N, dual element, isolated, ungrounded --40 to 1000 C40 to 1000 C((--40 to 1832 F)40 to 1832 F)

  • Emerson Process Management

    Rosemount Division Confidential

    Slide 12

    Required FieldsRequired FieldsRequired FieldsRequired Fields

    CodeCode Extension Type Extension Type Head ConnectionHead Connection Instrument ConnectionInstrument Connection MaterialMaterial

    DD DIN DIN standard, 12 x 1.5standard, 12 x 1.5 M24 x 1.5M24 x 1.5 --in. NPTin. NPT SST SST (min N = 35mm)(min N = 35mm)

    T T DIN DIN standard, 12 x 1.5standard, 12 x 1.5 M24 x 1.5M24 x 1.5 M18 x 1.5M18 x 1.5 SSTSST(min N = 35mm)(min N = 35mm)

    F F Nipple Nipple Union Union NippleNipple --in. NPT in. NPT --in. NPTin. NPT SSTSST

    (min N = 110mm)(min N = 110mm)

    JJ Nipple Nipple Union (Sensor LeadUnion (Sensor Lead no headno head in. NPTin. NPT SSTSSTWire Terminal Option code 3 only)Wire Terminal Option code 3 only) (min N = 80mm)(min N = 80mm)

    N N No Extension (use when ordering the sensor alone, only availableNo Extension (use when ordering the sensor alone, only available with Extension Length (N) code 0000)with Extension Length (N) code 0000)

    W W No Extension Head ConnectionNo Extension Head Connection M24 x 1.5M24 x 1.5

    LL No ExtensionNo Extension --in. NPT in. NPT

  • Emerson Process Management

    Rosemount Division Confidential

    Slide 13

    Required FieldsRequired FieldsRequired Fields

    CodeCode Extension Length (mm)Extension Length (mm)

    0000 0000 No extension No extension use with Extension Type code Nuse with Extension Type code N

    0035 0035 35 mm35 mm

    0080 0080 80 mm 80 mm standard for Extension Type code Jstandard for Extension Type code J

    0110 0110 110 mm 110 mm standard for Extension Type code F and Jstandard for Extension Type code F and J

    0135 0135 135 mm 135 mm standard for DIN Extension used with standard for DIN Extension used with withwithRosemount Connection Head Material codes C, D, G, H, 1, Rosemount Connection Head Material codes C, D, G, H, 1, and 2and 2

    0150 0150 150 mm 150 mm standard for DIN Extension used with Form B standard for DIN Extension used with Form B Connection Head Material codes J and LConnection Head Material codes J and L

    XXXX XXXX NonNon--standard extension length standard extension length available from 35 to 500 available from 35 to 500 mmmm

    Required Fields

  • Emerson Process Management

    Rosemount Division Confidential

    Slide 14

    Required FieldsRequired FieldsRequired Fields

    CodeCode ThermowellThermowell MaterialMaterial

    NN No thermowellNo thermowell

    DD 1.4404 (AISI 316L)1.4404 (AISI 316L)

    YY 1.4571 (AISI 316Ti)1.4571 (AISI 316Ti)

    Required Fields

  • Emerson Process Management

    Rosemount Division Confidential

    Slide 15

    Required FieldsRequired FieldsRequired Fields

    CodeCode Sensor LengthSensor Length

    01450145 145 mm145 mm

    02050205 205 mm205 mm

    0275 0275 275 mm275 mm

    0315 0315 315 mm315 mm

    0375 0375 375 mm375 mm

    0405 0405 405 mm405 mm

    0435 0435 435 mm435 mm

    0555 0555 555 mm555 mm

    XXXX XXXX NonNon--standard sensor length standard sensor length available from available from

    minimum 100 mm, maximum 9999 mmminimum 100 mm, maximum 9999 mm

    Required Fields

  • Emerson Process Management

    Rosemount Division Confidential

    Slide 16

    Common OptionsCommon OptionsCommon Options

    OptionOption CodeCode DescriptionDescription

    Sensor Options (65 Only)Sensor Options (65 Only) A1A1 Single element Class A sensor from Single element Class A sensor from

    --50 to 405 C (50 to 405 C (--58 to 842 F)58 to 842 F)

    Mounting OptionMounting Option XAXA Assemble sensor to specific temperature Assemble sensor to specific temperature

    transmittertransmitter

    Hazardous Location Hazardous Location CertsCerts I1I1 EExEEx iaia ATEX/ATEX/IBExUIBExU Intrinsic Safety ApprovalIntrinsic Safety Approval

    N1N1 EExEEx n n ATEX/CENELEC ATEX/CENELEC TyleTyle nn ApprovalApproval

    E1E1 EExEEx d ATEX/CENELEC Flamed ATEX/CENELEC Flame--Proof ApprovalProof Approval

    NDND ATEX Dust Ignition ProofATEX Dust Ignition Proof

    E7E7 SAA Flame Proof ApprovalSAA Flame Proof Approval

    E5E5 EExEEx d d FM Explosion Proof ApprovalFM Explosion Proof Approval

    AccessoriesAccessories G1G1 External Ground ScrewsExternal Ground Screws

    G3G3 Cover ChainCover Chain

    G6G6 Aluminum extension ring for dual transmitter mount in headAluminum extension ring for dual transmitter mount in head

    TBTB Terminal Block for use with sensor Termination Code 3Terminal Block for use with sensor Termination Code 3

    Optional Fields

  • Emerson Process Management

    Rosemount Division Confidential

    Slide 17

    Common OptionsCommon OptionsCommon Options

    OptionOption CodeCode DescriptionDescription

    Calibration Options (65 Only)Calibration Options (65 Only) V10V10 Works Certificate Works Certificate sensor calibration from sensor calibration from --50 to 450 C with 50 to 450 C with

    A, B, and C CVD A, B, and C CVD constants constants

    V11V11 Works Certificate Works Certificate sensor calibration from 0 to 100 C with A, sensor calibration from 0 to 100 C with A,

    B, and C CVD B, and C CVD constants constants

    XBXB Works Certificate Works Certificate sensor calibration over specified sensor calibration over specified

    temperature range with A, B, and C CVD temperature range with A, B, and C CVD -- constantsconstants

    Optional Fields

  • Emerson Process Management

    Rosemount Division Confidential

    Slide 18

    Check for KnowledgeCheck forCheck for KnowledgeKnowledge

  • Emerson Process Management

    Rosemount Division Confidential

    Slide 19

    If a customer has an extremely high temp application, If a customer has an extremely high temp application, what would be the most suitable metric sensor?what would be the most suitable metric sensor?

    A) 0065 Type K

    C) 0185 Type J

    D) 0065 Dual Element

    B) 0185 Type N

  • How to Specify How to Specify 0068 / 0078 RTD 0068 / 0078 RTD SensorSensor

    Volume 1Volume 1

    Note:Note:Rosemount Catalog or the Rosemount Catalog or the Temperature and Sensor Temperature and Sensor Assembly PDS RequiredAssembly PDS Required

  • Emerson Process Management

    Rosemount Division Confidential

    Slide 21

    Required FieldsRequired FieldsRequired Fields

    ModelModel 00780078 Platinum ThinPlatinum Thin--Film Temperature Sensors and Film Temperature Sensors and Sensor AssembliesSensor Assemblies

    00680068 Platinum WirePlatinum Wire--Wound Temperature Sensors and Wound Temperature Sensors and Sensor AssembliesSensor Assemblies

    Lead Wire TerminationLead Wire Termination DD Rosemount Aluminum Connection HeadRosemount Aluminum Connection Head

    CC Polypropylene Connection HeadPolypropylene Connection Head

    RR Aluminum Connection Head, 6 Terminals, Flat Cover, Aluminum Connection Head, 6 Terminals, Flat Cover, UnpaintedUnpainted

    TT Aluminum Connection Head, 6 Terminals, Extended Aluminum Connection Head, 6 Terminals, Extended Cover, UnpaintedCover, Unpainted

    PP Aluminum Connection Head, 6 Terminals, Flat Cover, Aluminum Connection Head, 6 Terminals, Flat Cover, PaintedPainted

    LL Aluminum Connection Head, 6 Terminals, Extended Aluminum Connection Head, 6 Terminals, Extended Cover, PaintedCover, Painted

    NN Sensor only with 6 in Teflon insulated, 22 gauge lead wiresSensor only with 6 in Teflon insulated, 22 gauge lead wires

    Required Fields

  • Emerson Process Management

    Rosemount Division Confidential

    Slide 22

    Sensor Type (0068 Only)Sensor Type (0068 Only) Single Element Single Element --50 to 400 C (50 to 400 C (--58 to 752 F)58 to 752 F)

    0101 Capsule StyleCapsule Style

    1111 General Purpose StyleGeneral Purpose Style

    2121 Spring Loaded StyleSpring Loaded Style

    3131 Bayonet Spring Loaded Style (1 in. increments from 1Bayonet Spring Loaded Style (1 in. increments from 1--2121))

    Required Fields

    Required FieldsRequired FieldsRequired Fields

  • Emerson Process Management

    Rosemount Division Confidential

    Slide 23

    Sensor Type (0078 Only)Sensor Type (0078 Only) Single ElementSingle Element --200 to 500 C (200 to 500 C (--328 to 932 F)328 to 932 F)

    0101 Capsule StyleCapsule Style

    1111 General Purpose StyleGeneral Purpose Style

    2121 Spring Loaded StyleSpring Loaded Style

    3131 Bayonet Spring Loaded Style (1 in. increments from 1Bayonet Spring Loaded Style (1 in. increments from 1--2121))

    Single Element High Temperature Single Element High Temperature 0 to 600 C (32 to 1112 F)0 to 600 C (32 to 1112 F)

    0303 Capsule Style (1 in. increments from 3Capsule Style (1 in. increments from 3--2424 lengths)lengths)

    1313 General Purpose Style General Purpose Style (1/2 in. increments from 3(1/2 in. increments from 3--2424 lengths)lengths)

    2323 Spring Loaded Style Spring Loaded Style (1/2 in. increments from 3(1/2 in. increments from 3--2424 lengths)lengths)

    3333 Bayonet Spring Loaded (1 in. increments from 3Bayonet Spring Loaded (1 in. increments from 3--2121 lengths)lengths)

    Dual Element Dual Element --200 to 500 C (200 to 500 C (--328 to 932 F)328 to 932 F)

    0505 Capsule StyleCapsule Style

    1515 General Purpose StyleGeneral Purpose Style

    2525 Spring Loaded StyleSpring Loaded Style

    3535 Bayonet Spring Loaded Style (1 in. increments from 1Bayonet Spring Loaded Style (1 in. increments from 1--2121))

    Required Fields

    Required FieldsRequired FieldsRequired Fields

  • Emerson Process Management

    Rosemount Division Confidential

    Slide 24

    Extension TypeExtension Type AA Nipple Coupling Nipple Coupling -- SSTSST

    CC Nipple Union Nipple Union -- SSTSST

    NN None (use with extension length option code 00)None (use with extension length option code 00)

    Extension Length (E)Extension Length (E) 0000 0.0 in.0.0 in.

    3030 3.0 in.3.0 in.

    6060 6.0 in.6.0 in.

    (X) Sensor length = (E) extension length + (L) (X) Sensor length = (E) extension length + (L) thermowellthermowell length length -- .25.25 (see Fig. 4 in PDS)(see Fig. 4 in PDS)

    Required Fields

    Required FieldsRequired FieldsRequired Fields

  • Emerson Process Management

    Rosemount Division Confidential

    Slide 25

    ThermowellThermowell MaterialMaterial AA Type 316 SSTType 316 SST

    BB Type 304 SSTType 304 SST

    CC Carbon SteelCarbon Steel

    DD 316L SST316L SST

    EE 304L SST304L SST

    FF Alloy 20Alloy 20

    GG MonelMonel

    HH InconelInconel 600600

    JJ HastelloyHastelloy C (with 304 SST Flange, if flange C (with 304 SST Flange, if flange style is ordered)style is ordered)

    LL HastelloyHastelloy B (with 304 SST Flange, if flange B (with 304 SST Flange, if flange style is ordered)style is ordered)

    Required Fields

    Required FieldsRequired FieldsRequired Fields

    MM 304 SST with Teflon (PTFE) 304 SST with Teflon (PTFE) coatingcoating

    NN No No thermowellthermowell

    PP Chrome Molybdenum F22Chrome Molybdenum F22

    RR Nickel 200Nickel 200

    TT TitaniumTitanium

    UU 316 SST 316 SST wirhwirh Tantalum SheathTantalum Sheath

    WW 321 SST321 SST

    ZZ Chrome Molybdenum F11Chrome Molybdenum F11

    X - Other

  • Emerson Process Management

    Rosemount Division Confidential

    Slide 26

    Required Fields

    Required FieldsRequired FieldsRequired Fields

    LengthLength

    Code Code UU LL TT

    080080 8.0 in.8.0 in. 12.0 in12.0 in 2.5 in2.5 in

    Ranges from 1.0 in. (010) to 25.5 in. (255) (U Length)Ranges from 1.0 in. (010) to 25.5 in. (255) (U Length)

    L and T length dependant on U lengthL and T length dependant on U length

    Refer to PDS for complete length breakdown, Figure 4 Refer to PDS for complete length breakdown, Figure 4

    for dimension imagesfor dimension images

  • Emerson Process Management

    Rosemount Division Confidential

    Slide 27

    Required Fields

    Required FieldsRequired FieldsRequired Fields

    CodeCode ThermowellThermowell MountingMounting StemStem Tip A (in.) Root B (in.)Tip A (in.) Root B (in.)

    T20T20 ThreadedThreaded --14 ANPT14 ANPT SteppedStepped 0.500.50 0.750.75

    T34T34 ThreadedThreaded --14 ANPT14 ANPT StraightStraight 0.750.75 0.750.75

    W38W38 WeldedWelded --in. pipein. pipe SteppedStepped 0.500.50 0.750.75

    W46W46 WeldedWelded 1 1 --in. pipein. pipe TaperedTapered 0.750.75 1.251.25

    F10F10 FlangedFlanged 22--in., Class 150in., Class 150 StraightStraight 0.750.75 0.750.75

    F54F54 FlangedFlanged 11--1/2 in., Class 1501/2 in., Class 150 SteppedStepped 0.500.50 0.750.75

    Q02Q02 Sanitary, TriSanitary, Tri--ClampClamp 11--in., Triin., Tri--ClampClamp SteppedStepped 0.500.50 0.750.75

  • Emerson Process Management

    Rosemount Division Confidential

    Slide 28

    Optional Codes

    Common OptionsCommon OptionsCommon Options

    Sensor:Sensor: AA IEC 751 Class A sensorIEC 751 Class A sensor

    Product Certification:Product Certification: E5E5 FM ExplosionFM Explosion--proof approvalproof approval

    Calibration:Calibration: V1V1 CallendarCallendar--van Dusen Constantsvan Dusen Constants

    Calibration:Calibration: X8Q4X8Q4 Calibrate to customerCalibrate to customer--specified temperature specified temperature

    rangerange

    Mounting Adapters:Mounting Adapters: XAXA Assemble connection head or Assemble connection head or

    transmitter to a sensor assemblytransmitter to a sensor assembly

  • Emerson Process Management

    Rosemount Division Confidential

    Slide 29

    Check for KnowledgeCheck forCheck for KnowledgeKnowledge

  • Emerson Process Management

    Rosemount Division Confidential

    Slide 30

    Which of these is NOT a style of sensor?Which of these is NOT a style of sensor?A) Capsule

    B) Spring Loaded

    C) Bayonet Spring Loaded

    E) General Purpose

    D) Dual Sensor Casing

  • How to Specify 0183 How to Specify 0183 Thermocouple Thermocouple SensorSensor

    Note:Note:Rosemount Catalog or the Rosemount Catalog or the Temperature and Sensor Temperature and Sensor Assembly PDS RequiredAssembly PDS Required

  • Emerson Process Management

    Rosemount Division Confidential

    Slide 32

    Required FieldsRequired FieldsRequired Fields

    ModelModel 01830183 Thermocouple Temperature Sensors and Thermocouple Temperature Sensors and Sensor AssembliesSensor Assemblies

    Lead Wire TerminationLead Wire Termination DD Rosemount Aluminum Connection HeadRosemount Aluminum Connection Head

    CC Polypropylene Connection HeadPolypropylene Connection Head

    RR Aluminum Connection Head, 6 Terminals, Flat Cover, Aluminum Connection Head, 6 Terminals, Flat Cover, UnpaintedUnpainted

    TT Aluminum Connection Head, 6 Terminals, Extended Aluminum Connection Head, 6 Terminals, Extended Cover, UnpaintedCover, Unpainted

    PP Aluminum Connection Head, 6 Terminals, Flat Cover, Aluminum Connection Head, 6 Terminals, Flat Cover, PaintedPainted

    LL Aluminum Connection Head, 6 Terminals, Extended Aluminum Connection Head, 6 Terminals, Extended Cover, PaintedCover, Painted

    NN Sensor only with 6 in Teflon insulated, 22 gauge lead wiresSensor only with 6 in Teflon insulated, 22 gauge lead wires

    Required Fields

  • Emerson Process Management

    Rosemount Division Confidential

    Slide 33

    Required FieldsRequired FieldsRequired FieldsRequired Fields

    Code Sensor Style

    1X General-purpose Sensors

    2X Spring-loaded Sensors

    3X Bayonet spring-loaded Sensors

    Code Sensor Type Junction

    X1 Single Grounded

    X2 Dual Grounded

    X3 Single Ungrounded

    X4 Dual, Unisolated Ungrounded

    X5 Dual, Isolated Ungrounded

    Example

    Code Sensor Style Sensor Type Junction

    13 General-purpose Sensors Single Ungrounded

  • Emerson Process Management

    Rosemount Division Confidential

    Slide 34

    Required FieldsRequired FieldsRequired FieldsRequired Fields

    Thermocouple Type J2 Type J 0 to 760 C (32 to 1400 F)

    K2 Type K 0 to 1150 C (32 to 2102 F)

    E2 Type E 0 to 871 C (32 to 1600 F)

    T2 Type T -180 to 371 C (-292 to 700 F)

    Extension Type A Nipple Coupling

    C Nipple Union

    N None

    Extension Length 00 0.0 in.

    30 3.0 in.

    60 6.0 in.

  • Emerson Process Management

    Rosemount Division Confidential

    Slide 35

    ThermowellThermowell MaterialMaterial AA Type 316 SSTType 316 SST

    BB Type 304 SSTType 304 SST

    CC Carbon SteelCarbon Steel

    DD 316L SST316L SST

    EE 304L SST304L SST

    FF Alloy 20Alloy 20

    GG MonelMonel

    HH InconelInconel 600600

    JJ HastelloyHastelloy C (with 304 SST Flange, if flange C (with 304 SST Flange, if flange style is ordered)style is ordered)

    LL HastelloyHastelloy B (with 304 SST Flange, if flange B (with 304 SST Flange, if flange style is ordered)style is ordered)

    Required FieldsRequired FieldsRequired Fields

    MM 304 SST with Teflon (PTFE) 304 SST with Teflon (PTFE) coatingcoating

    NN No No thermowellthermowell

    PP Chrome Molybdenum F22Chrome Molybdenum F22

    RR Nickel 200Nickel 200

    TT TitaniumTitanium

    UU 316 SST 316 SST wirhwirh Tantalum SheathTantalum Sheath

    WW 321 SST321 SST

    ZZ Chrome Molybdenum F11Chrome Molybdenum F11

    Required Fields

    X - Other

  • Emerson Process Management

    Rosemount Division Confidential

    Slide 36

    Optional Codes

    Common OptionsCommon OptionsCommon Options

    Product Certification:Product Certification: E5E5 FM ExplosionFM Explosion--proof approvalproof approval

    E6E6 CSA Explosion proof approvalCSA Explosion proof approval

    E7E7 SAA Flameproof approvalSAA Flameproof approval

    E1E1 ATEX Flameproof approvalATEX Flameproof approval

    Mounting Adapters:Mounting Adapters: M5M5--M7M7 Mounting adapters, lead wire extensions, connectors, and Mounting adapters, lead wire extensions, connectors, and

    sealsseals

    Assembly OptionsAssembly Options XAXA Assemble connection head or transmitter to a sensor Assemble connection head or transmitter to a sensor

    assemblyassembly

    Required Fields

  • Emerson Process Management

    Rosemount Division Confidential

    Slide 37

    Check for KnowledgeCheck forCheck for KnowledgeKnowledge

  • Emerson Process Management

    Rosemount Division Confidential

    Slide 38

    E

    X

    U

    T + 1.75

    L

    Length Relationships:

    L = U + T + 1.5

    X = E + L

    X = E + U + T + 1.5 0.25(tip thickness)

    Understanding the dimensions and their relationships!Understanding the dimensions and their relationships!

    X = sensor length (GP is -0.25 to

    avoid bottoming in a T-well)

    (SL is +0.50, no compression)

    E = extension fitting length

    L = thermowell length, (- 0.25 for

    sensor length)

    U = thermowell immersion length

    T = t-well additional lagging length

    Sensor, Thermowell, and Accessory DimensionsSensor, Sensor, ThermowellThermowell, and Accessory , and Accessory DimensionsDimensions

  • Emerson Process Management

    Rosemount Division Confidential

    Slide 39

    Exercise: Replacing a failed sensor.Exercise: Replacing a failed sensor.Exercise: Replacing a failed sensor.

    Your customers general purpose RTD failed, and he needs to replace it.

    6.25

    Tip of

    Sensor

    Include 1/2

    of threads

    Fill in the blanks to finish the Series 68 RTD Model number:

    0068 N __ N __ N __ E5

    Note: For general purpose sensors the actual sensor length is 0.25 less than the specified

    length to avoid bottoming out in a Thermowell.

  • Emerson Process Management

    Rosemount Division Confidential

    Slide 40

    Exercise: Replacing a failed sensor.Exercise: Replacing a failed sensor.Exercise: Replacing a failed sensor.

    Your customers general purpose RTD failed, and he needs to replace it.

    6.25

    Tip of

    Sensor

    Include 1/2

    of threads

    General Purpose -> 11

    There is no extension needed -> 00

    The actual length of the sensor (including the of threads) is 6.25

    but the length specified is .25 longer to avoid bottoming in the thermowell,

    making the length 6.50

    Fill in the blanks to finish the Series 68 RTD Model number:

    0068 N 11 N 00 N 065 E5

  • Emerson Process Management

    Rosemount Division Confidential

    Slide 41

    Exercise: Replacing a failed sensor.Exercise: Replacing a failed sensor.Exercise: Replacing a failed sensor.

    Your customers spring loaded RTD failed, and he needs to replace it.

    17.0

    Tip of

    Sensor

    Include 1/2

    of threads

    Fill in the blanks to finish the Series 68 RTD Model number:

    0068 N __ N __ N __ E5Note: For spring-loaded sensors the actual sensor length (uncompressed) is 0.50 longer than the

    length specified to allow for 0.50 spring compression when installed in the Thermowell

  • Emerson Process Management

    Rosemount Division Confidential

    Slide 42

    Exercise: Replacing a failed sensor.Exercise: Replacing a failed sensor.Exercise: Replacing a failed sensor.

    Your customers spring loaded RTD failed, and he needs to replace it.

    17.0

    Tip of

    Sensor

    Include 1/2

    of threads

    Simple Spring-loaded style -> 21

    No extensions needed -> 00

    Although the length of the uncompressed sensor is 17.0, the sensor tip

    must be compressed .50 to ensure contact with the thermowell

    Fill in the blanks to finish the Series 68 RTD Model number:

    0068 N 21 N 00 N 165 E5