    PACS 350/3500 INTRODUCTION

  • 7/24/2019 Microsoft PowerPoint - PACS 350 Lansering 350_46

    2/57

    2

    PACS 300/3000 VS PACS 350/3500 Same system software in PACS 350 as PACS 3500 (ver. 5.06)

    New function - 64 Parameter Flags

    Dip Switches increased to 32 (earlier 16)

    User Flags increased to 256 (earlier 128) Timers increased to 95 (earlier 90)

    Possibility to have up to 64 programs on PACS 350(depending on size of program)

    Maximum 200 parameters/program and 60 parameters/phase

    PACS 350/3500 INTRODUCTIONSoftware

  • 7/24/2019 Microsoft PowerPoint - PACS 350 Lansering 350_46

    3/57

    3

    More memory on PACS 350 8Mbit Removable flash

    memory for program storage.

    Socket mounted.

    8Mbit SRAM memory for data

    storage.

    4Mbit flash memory fordatabase storage.

    Same memory on PACS 3500 CPU board not changed

    PACS 350/3500 INTRODUCTIONMemory

    CPU/relay board PACS 350

  • 7/24/2019 Microsoft PowerPoint - PACS 350 Lansering 350_46

    4/57

    4

    New CPU/relay board.

    Same size as PACS 300(16DI, 16DO, 2DO 12VDC, 4AI for PT1000 or PT100,2AI for 4-20mA, 2AI for 0-10V)

    Possibility to change between PT1000 and PT100 byjumpers.

    Prepared for NetCom connection.

    Three communication ports.

    X24 RS232

    X25 RS232/485 X32 RS232

    New type of connections placed on the componentside.

    PACS 350/3500 INTRODUCTIONHardware PACS 350

  • 7/24/2019 Microsoft PowerPoint - PACS 350 Lansering 350_46

    5/57

    5

    New expansion board

    Same size as PACS 300(6DI, 6DO, 2DO 12VDC, 1AO for 0, 6, 8 or 10DCV)

    Possibility to have up to four expansion boards.

    New type of connections placed on the component

    side.

    Display boards same as PACS 300.

    PACS 350/3500 INTRODUCTIONHardware PACS 350

  • 7/24/2019 Microsoft PowerPoint - PACS 350 Lansering 350_46

    6/57

    6

    Same CPU/relay board as PACS 3000. Same display board as PACS 3000.

    New range of IO-boards with new type of connections placed on thecomponent side.

    Digital Input board (16DI) Digital Output board (8DO)

    Analogue Input board (8AI for PT100, 4-20mA or 0-10V)

    Analogue Output/High speed counter board

    (4AO for 4-20mA or 0-10V, 4DI+4DO for pulse counting) Combination Module

    (24DI, 24DO, 5AI for PT100 and 3AI for PT100, 4-20mA or 0-10V)

    PACS 350/3500 INTRODUCTIONHardware PACS 3500

  • 7/24/2019 Microsoft PowerPoint - PACS 350 Lansering 350_46

    7/57

    7

    System program PC-program PC-CablePACS 300 CS-1000 ver. 3.03 501019100

    PACS 350 CS-1000 ver. 5.06 501019100

    PACS 3000 CS-1000 ver. 3.05 (5.06) 566115772

    PACS 3500 CS-1000 ver. 5.06 566115772

    SP-1000 family gen. 1 SPPC1 ver. 1.26.03 499403300

    SP-1000 family gen. 2 SPPC2 ver. 3.19 501019100 + 501140700

    N.B.

    Only one version of the CS-1000 can be installed at the same time.

    PACS 350/3500 INTRODUCTIONCables and programs

  • 7/24/2019 Microsoft PowerPoint - PACS 350 Lansering 350_46

    8/57

    8

    PACS 350/3500 INTRODUCTIONHardware and Software

    System program Machine typePACS 300 46- and 86-series

    PACS 350 88-Turbo46-series from week 40 2008

    S-1345 from week 46 200886-series will be implemented 2009

    PACS 3000 91-seriesPACS 3500 91-series from week 34 2008

    9027 from week 38 2008

    SP-1000 gen. 1 S-606/615, SP-2000, SP-6000 (Decomat hardware)SP-1000 gen. 2 S-607/608/617/618, SP-2000, SP-6000 (PACS hardware)

  • 7/24/2019 Microsoft PowerPoint - PACS 350 Lansering 350_46

    9/57

    9

    New dos monitor system DI12-DI15 special designed on CPU/relay board for PACS 350

    New Pulse Counting/Analogue Out board for PACS 3500

    PACS 350/3500 INTRODUCTIONDos monitoring

  • 7/24/2019 Microsoft PowerPoint - PACS 350 Lansering 350_46

    10/57

    10

    OFF

    BATTERY

    ON

    Normal

    Systemload

    Coldstart

    Flash

    Prom

    NormalSystem loadCold start

    Prom

    Flash

    OFFON

    Loading system file

    1. Connect the PC to X25.2. If it is an existing CPU board, make a

    backup and a Save RAM in Flash (the set

    calibration values will then be automatically

    removed back after loading of the program).

    3. Switch of the power on the main switch4. Move jumper 1 on the board for the PACS

    350 control system from Normal to System

    Load. Check that jumper 2 is in the Flash

    position and that jumper 3 is in the ON

    position.5. Switch on the power to the machine with the

    main switch. The display lights up but

    without text.

    6. Start flashloader from PC.

    PACS 350 INTRODUCTIONLoading system programs to flash memory

    Jumper 3

    Jumper 1

    Jumper 2

    (3 pcs)

  • 7/24/2019 Microsoft PowerPoint - PACS 350 Lansering 350_46

    11/57

    11

    OFF

    BATTE

    RY

    O

    N

    Normal

    Systemload

    Coldstart

    Flash

    prom

    Flash prom

    Without CS-10001. Switch off the power and remove the old prom.

    2. Move jumper 1 to cold start.

    3. Power on the machine and wait for a beep.

    4. Switch off the power to the machine.

    5. Install the new flash prom.6. Switch on the power and the software will be loaded

    from flash prom to the processor.

    7. Move jumper 1 to the Normal position without

    switching of the power.

    PACS 350 INTRODUCTIONReloading the backup from flash prom to PACS

    Normal

    System load

    Cold start

    Prom

    Flash

    Jumper 1

  • 7/24/2019 Microsoft PowerPoint - PACS 350 Lansering 350_46

    12/57

    12

    Cold start

    Do a cold start when the machine has hung and you cannot

    proceed with the program.

    1. Switch off the power to the machine.

    2. Move the programming jumper (1) from Normal to Cold.

    3. Switch on the power.

    4. Move the programming jumper (1) from Cold to Normal.

    NOTE: The power is still on.

    NormalSystem load

    Cold start

    PromFlash

    PT1000

    PT100

    OFF

    ON

    PACS 350 INTRODUCTIONCold start

    Jumper 1

  • 7/24/2019 Microsoft PowerPoint - PACS 350 Lansering 350_46

    13/57

    13

    PACS 350 INTRODUCTIONCSTool

    CSTool

    CSTool is used forlanguage programming

    Text can also be changedfrom CS-1000

    Select always PACS 3500

  • 7/24/2019 Microsoft PowerPoint - PACS 350 Lansering 350_46

    14/57

    14

    PACS 350 INTRODUCTIONCSTool

    There are no supportfor Greek or Chinese

    in CSTool or CS-1000

  • 7/24/2019 Microsoft PowerPoint - PACS 350 Lansering 350_46

    15/57

    15

    PACS 350 INTRODUCTION

    46-Series

  • 7/24/2019 Microsoft PowerPoint - PACS 350 Lansering 350_46

    16/57

    16

    PACS 350 INTRODUCTIONP/I diagram 46-series

  • 7/24/2019 Microsoft PowerPoint - PACS 350 Lansering 350_46

    17/57

    17

    PACS 350 INTRODUCTION46-seriesWater inlets

    Water quality Preheated drinking water with max 5 dH

    [Temperature Hot water 45-60 C (113 - 140 F)]

    Connection 15 mm (1/2")Pressure 100-800 kPa

    Flow rate, min. 20 l/min

  • 7/24/2019 Microsoft PowerPoint - PACS 350 Lansering 350_46

    18/57

    18

    PACS 350 INTRODUCTION46-seriesWater circulation system

    Water circulation

    Drain system

    Level control

    Conductivity

    Temperature

    Pump pressure

    Over heat protector

  • 7/24/2019 Microsoft PowerPoint - PACS 350 Lansering 350_46

    19/57

    19

    PACS 350 INTRODUCTION46-seriesDrying system

    Capacity 125-150m/h, 35 C (95 F)

    Humidity 100% 40 sec< 40% after 2 min.Air gap min 50 mm

    Condensate from

    heat exchanger

    Drainagewater

    DP Monitoring

    Temperature

    Leakage control

  • 7/24/2019 Microsoft PowerPoint - PACS 350 Lansering 350_46

    20/57

    20

    Flow meter placed in detergent cabinet..

    PACS 350 INTRODUCTIONDosing system 46-series

  • 7/24/2019 Microsoft PowerPoint - PACS 350 Lansering 350_46

    21/57

    21

    Signal exchange box.

    PACS 350 INTRODUCTIONTransformer and signal exchange 46-series

    New position of transformer.

    (200 / 208 / 240V) View from clean side.

  • 7/24/2019 Microsoft PowerPoint - PACS 350 Lansering 350_46

    22/57

    22

    Steam pipe in copperreplaced by insulated

    flexible hoses.

    PACS 350 INTRODUCTIONSteam pipes 46-series

  • 7/24/2019 Microsoft PowerPoint - PACS 350 Lansering 350_46

    23/57

    23

    New heating element built-in over heat protector.

    all connecting cables are solderedand go directly to the terminals onthe electrical cabinet.

    Possible to have a main switch(option)

    PACS 350 INTRODUCTIONHeating element 46-series

  • 7/24/2019 Microsoft PowerPoint - PACS 350 Lansering 350_46

    24/57

    24

    Heat baffle plates on thedrying unit on 46-4/5 forbetter ventilation.

    PACS 350 INTRODUCTIONHeat baffles plate 46-series

  • 7/24/2019 Microsoft PowerPoint - PACS 350 Lansering 350_46

    25/57

    25

    New lamp 230V 50Wwith GU10 socket.

    PACS 350 INTRODUCTIONChamber light 46-series

  • 7/24/2019 Microsoft PowerPoint - PACS 350 Lansering 350_46

    26/57

    26

    Pressure transmitter forcirculation water moved to thetop of the water cannel.

    PACS 350 INTRODUCTIONPump pressure 46-series

  • 7/24/2019 Microsoft PowerPoint - PACS 350 Lansering 350_46

    27/57

    27

    Condensate trap implemented on46-2/3 to prevent water dropsgoing back into the chamberduring the drying phase.

    PACS 350 INTRODUCTIONCondensate trap 46-series

  • 7/24/2019 Microsoft PowerPoint - PACS 350 Lansering 350_46

    28/57

    28

    Electrical cabinet with cooling

    PACS 350 INTRODUCTIONElectrical cabinet 46-series

  • 7/24/2019 Microsoft PowerPoint - PACS 350 Lansering 350_46

    29/57

    29

    Circulating pump F01K01X101

    Heating Chamber F02K02X102

    Heating Dryer F04K04X103

    Noise filter Z01X104CPU X23 (power supply) X104:1 N and X105:6 L1

    CPU X16 (pump & heating) X105:8

    Interlock door ss X9:2 /X9:6X202:1K11

    Interlock door cs X9:3 /X9:7X202:2K12

    Power supply X201 24 V DC & 5VDC

    Transformer 24 V DC U3Transformer 5 V DC U4

    Net com

    Process info. X105

    Miniature circuit F 11

    BreakersCooling fan M18

    K04

    K01

    K02

    F04

    Z

    01

    X50

    X10

    2

    X103

    X105 X201

    M18

    F01

    F02

    K11

    F11

    K

    12

    X106 X101 X104 X202

    M18 U

    04

    U03

    PACS 350 INTRODUCTIONElectrical cabinet 46-series

  • 7/24/2019 Microsoft PowerPoint - PACS 350 Lansering 350_46

    30/57

    30

    P01 POWER CLEAN60.0C

    Select cycle

    Change parameters

    P RINSE 1 SEL

    0001 P

    P RINSE 2 SEL

    0000 PWASH SELECTOR

    0001 P

    P RINSE F TYPE

    0001 P

    Password

    PACS 350 INTRODUCTION46-series

    Parameters

    A and P parameters can be changed from the display.Password

    Operator 558387 (Acknowledge alarm, Change A parameters)

    Service 118118 (Change P parameters)Supervisor

    Sysdba

    PACS 350 INTRODUCTION

  • 7/24/2019 Microsoft PowerPoint - PACS 350 Lansering 350_46

    31/57

    31

    PACS 350 INTRODUCTION46-seriesProgram structure

    Wash 2 on

    Pre Rinse 1 on

    Pre Rinse 1Pre Rinse 1 off

    Wash 1 on

    Wash 1 Wash 1 off

    START

    Wash 2 Wash 2 off

    Pre Rinse 2 on

    Pre Rinse 2 Pre Rinse 2 off

    Rinse 2 on

    Neutr offNeutralizing

    Rinse 1 on

    Rinse 1 Rinse 1 off

    Rinse 2 Rinse 2 off

    Rinse 3 Rinse 3 off

    Chem. off

    Chem. on

    ChemicalDisinfection

    Rinseoff

    PROCESSCOMPLETE

    Descaling on

    Descaling off

    Chamber emptyand Drying off

    Final Rinse on

    Final Rinse /Disinfection

    Descaling

    Drain / Drying

    Final Rinse off

    Rinse 3 on

    Neutr on

    Draining / Drying on

    1-3

    loops

    PACS 350 INTRODUCTION

  • 7/24/2019 Microsoft PowerPoint - PACS 350 Lansering 350_46

    32/57

    32

    Fill type 1=CW 2=HW 3=CW+HW 4=DWRinse time 0-10 min.

    PACS 350 INTRODUCTION46-seriesParameters Pre Rinse and Rinse

    PACS 350 INTRODUCTION

  • 7/24/2019 Microsoft PowerPoint - PACS 350 Lansering 350_46

    33/57

    33

    Fill type 1=CW 2=HW 3=CW+HW 4=DWDosage type 0,1,2,3,4

    Dosage temp 20-85C

    Wash time 0-10 minWash temp 40-90C

    PACS 350 INTRODUCTION46-seriesParameters Wash 1 and 2

    PACS 350 INTRODUCTION

  • 7/24/2019 Microsoft PowerPoint - PACS 350 Lansering 350_46

    34/57

    34

    Fill type 1=CW 2=HW 3=CW+HW 4=DWDosage type 0,1,2,3,4

    Dosage temp 20-85C

    Neutralize time 0-10 minNeutralize temp 40-90C

    PACS 350 INTRODUCTION46-seriesParameters Neutralizing

    PACS 350 INTRODUCTION

  • 7/24/2019 Microsoft PowerPoint - PACS 350 Lansering 350_46

    35/57

    35

    Fill type 1=CW 2=HW 3=CW+HW 4=DWDosage type 0,1,2,3,4

    Dosage temp 20-85C

    Chem.. Time 0-10 minChem.. Temp40-90C

    PACS 350 INTRODUCTION46-seriesParameters Chemical Disinfection

    PACS 350 INTRODUCTION

  • 7/24/2019 Microsoft PowerPoint - PACS 350 Lansering 350_46

    36/57

    36

    Disinfection Ao Print

    Disinfection Ao ControlDisinfection PF 30Fill type 1=CW 2=HW 3=CW+HW 4=DW

    Dosage type 0,1,2,3,4Dosage temp 20-85C

    Finale rinse time 0-10 minFinale rinse temp 40-90CFinale rinse conductivity select

    Finale rinse conductivity repeatFinale rinse conductivity value

    Start Ao calculationDisinfection Ao value

    PACS 350 INTRODUCTION46-seriesParameters Finale Rinse/ Disinfection

    PACS 350 INTRODUCTION

  • 7/24/2019 Microsoft PowerPoint - PACS 350 Lansering 350_46

    37/57

    37

    Descaling temperature 40-90CDescaling time 0-60 min

    PACS 350 INTRODUCTION46-seriesParameters Descaling

    PACS 350 INTRODUCTION

  • 7/24/2019 Microsoft PowerPoint - PACS 350 Lansering 350_46

    38/57

    38

    Drying time 0-60 min

    Drying temperature 80-120CDrying max chamber 60-90C

    Cool temp chamber 60-90C

    PACS 350 INTRODUCTION46-seriesParameters Drying

    PACS 350 INTRODUCTION

  • 7/24/2019 Microsoft PowerPoint - PACS 350 Lansering 350_46

    39/57

    39

    PACS 350 INTRODUCTIONCommunication

    CS 1000 ver. 5.06 only forPACS 350PACS 3000

    PACS 3500

    PACS 350 INTRODUCTION

  • 7/24/2019 Microsoft PowerPoint - PACS 350 Lansering 350_46

    40/57

    40

    PACS 350 INTRODUCTION46-seriesComPorts

    Com Port 1 X32 PC (CS-1000 and application load)

    Com Port 2 X24 Printer or NetCom (T-Doc native log)

    Com Port 3 X25 NetCom (T-Doc analogue signals)PC (system load)

    PACS 350 INTRODUCTION

  • 7/24/2019 Microsoft PowerPoint - PACS 350 Lansering 350_46

    41/57

    41

    46-seriesDipswitch Definition

    DS13 HUMIDITY SENSOR - (future option,

    not available). DS14 ROT. FLUSH WING - (future option,

    not available).

    DS15 EXT PRINTER prevent processstart before the printer is ready.

    DS17 NETCOM When NetCom ismounted.

    DS23 PC DISK LOG log to PC or T-Doc.

    DS29 PROCESS LOGCHECK activatetime out function if T-Doc connection drops.

    PACS 350 INTRODUCTION

  • 7/24/2019 Microsoft PowerPoint - PACS 350 Lansering 350_46

    42/57

    42

    46-seriesDipswitch Definition

    DS20 MAX/MIN PRINT max and min temp

    is printed in each heated phase. DS21 A0 VALUE PRINT system regulates

    on time and temperature. Counted A0 valueonly printed.

    DS22 A0 CONTROL system regulates ontemperature and A0 value.

    DS24 SERVICE MESSAGES IT57 SERVICE is shown on the display after

    1000 cycles.

    PACS 350 INTRODUCTION

  • 7/24/2019 Microsoft PowerPoint - PACS 350 Lansering 350_46

    43/57

    43

    46-seriesPH9710 PHASE SELECTOR

    PACS 350 INTRODUCTION

  • 7/24/2019 Microsoft PowerPoint - PACS 350 Lansering 350_46

    44/57

    44

    46-seriesPH9715 PHASE PARAMETERS (part 1)

    PACS 350 INTRODUCTION

  • 7/24/2019 Microsoft PowerPoint - PACS 350 Lansering 350_46

    45/57

    45

    46-seriesPH9715 PHASE PARAMETERS (part 2)

    PACS 350 INTRODUCTION

  • 7/24/2019 Microsoft PowerPoint - PACS 350 Lansering 350_46

    46/57

    46

    46-seriesPH9716 GENERAL PARAM

    PACS 350 INTRODUCTION

    46 series

  • 7/24/2019 Microsoft PowerPoint - PACS 350 Lansering 350_46

    47/57

    47

    PH9700 TIMER 1 contain all timers

    PH9702 LIMIT 1 contain all limits

    46-seriesPH9700 TIMER 1

    PH9702 LIMIT 1

    PACS 350 INTRODUCTION46 i

  • 7/24/2019 Microsoft PowerPoint - PACS 350 Lansering 350_46

    48/57

    48

    PH9706 COUNTER contain all

    counters CT00 CT09 Water selection:

    1 = Cold water2 = Warm water3 = Mixed water4 = Treated water

    CT10 CT14 Dos pump selection1 = Dos pump 12 = Dos pump 23 = Dos pump 34 = Dos pump 4

    CT15Counter for maximum final rinsesteps when treated water is usedtogether with conductivity control

    46-seriesPH9706 COUNTER

    PACS 350 INTRODUCTION46 series

  • 7/24/2019 Microsoft PowerPoint - PACS 350 Lansering 350_46

    49/57

    49

    46-seriesPH9704 PARAMETER FLAG

    PH9704 PARAMETER FLAG contain all parameter flags

    0 = Not activated1 = Activated

    PF00 PF12 activates phases

    PF30 activate disinfection function

    PF32 activate pipette function

    PF34 activate A0 printout-regulated by time and temperature-start counting at 75C

    PF35 activate A0 controller- regulated by A0-value set on LI51

    - low limit = 60 => A0 = 600- high limit = 300 => A0 = 3000

    PF36 activate pass through

    PF40 activate start password

    PACS 350 INTRODUCTION46 series

  • 7/24/2019 Microsoft PowerPoint - PACS 350 Lansering 350_46

    50/57

    50

    PH9704 CONTROLER

    contain all control functions- temperature regulatingvalues for all heated phases

    46-seriesPH9708 CONTROLER

    PACS 350 INTRODUCTIONError code 46 series

  • 7/24/2019 Microsoft PowerPoint - PACS 350 Lansering 350_46

    51/57

    51

    Soiled side door does not unlock within 3 sec. at

    the end of a program.

    A06 UNLOCK SSET06

    Soiled side door not lock within 3 sec. of program

    start or that the door is unlocked while a program

    is running.Soiled side door switches locked and unlocked

    activated simultaneous.

    A05 LOCK SSET05

    Water leakage in to the drying unit.A04 W LEAK DRYERET04

    Draining of the washing chamber takes more then

    5 min.

    A03 SLOW DRAINET03

    Slow filling of chamber tank. Filling of chamber

    tank takes more then 10min.

    A02 CH SLOW FILLET02

    Summary alarm overloaded MCCB.A01 MCCB TRIPET01

    Power failure.A00 POWER FAILET00

    DescriptionAlarm text (16char)Alarm

    Error code 46-series

    PACS 350 INTRODUCTIONError code 46-series

  • 7/24/2019 Microsoft PowerPoint - PACS 350 Lansering 350_46

    52/57

    52

    DescriptionAlarm text (16char)Alarm

    Clean side door does not unlock within 3 sec. at

    the end of a program.

    A10 UNLOCK CSET10

    Clean side door not lock within 3 sec. of program

    start or that the door is unlocked while a

    program is running.

    Clean side door switches locked and unlocked

    activated simultaneous.

    A09 LOCK CSET09

    SpareA08ET08

    Soiled side door not close within 20 sec. ofprogram start or that the door is opened while a

    program is running or that the squeeze protection

    has been activated while a program is running.

    Soiled side door switches open and close activated

    simultaneous.

    A07 CLOSED SSET07

    Error code 46-series

    PACS 350 INTRODUCTIONError code 46-series

  • 7/24/2019 Microsoft PowerPoint - PACS 350 Lansering 350_46

    53/57

    53

    DescriptionAlarm text (16char)Alarm

    Low flow of detergent 3.

    Detergent amount has not increase 5ml within 10

    sec. of dosing.

    A15 DOSING 3ET15

    Low flow of detergent 2.Detergent amount has not increase 5ml within 10

    sec. of dosing.

    A14 DOSING 2ET14

    Low flow of detergent 1.

    Detergent amount has not increase 5ml within 10

    sec. of dosing.

    A13 DOSING 1ET13SpareA12ET12

    Clean side door not close within 20 sec. of

    program start or that the door is opened while a

    program is running.

    Clean side door switches open and close activated

    simultaneous.

    A11 CLOSED CSET11

    Error code 46 series

    PACS 350 INTRUDUCTIONError code 46-series

  • 7/24/2019 Microsoft PowerPoint - PACS 350 Lansering 350_46

    54/57

    54

    DescriptionAlarm text (16char)Alarm

    Pressure higher then 750Pa in drying unit.A22 DRY PRESS HET22

    Pressure lower then 150Pa in drying unit. Delay

    time 5s from that the dryer fan has started.

    A21 DRY PRESS LET21

    Pressure from circulating pump higher then130kPa.

    A20 CIRC PRESS HET20

    Pressure from circulating pump lower then

    20kPa. Delay time 5s from that the circulating

    pump has started.

    A19 CIRC PRESS LET19

    Conductivity value higher then 4S/cm after 3

    efforts of final rinse.

    A18 CONDUCTIV HET18

    SpareA17ET17

    Low flow of detergent 4.Detergent amount has not increase 5ml within 10

    sec. of dosing.

    A16 DOSING 4ET16

    Error code 46 series

    PACS 350 INTRODUCTIONError code 46-series

  • 7/24/2019 Microsoft PowerPoint - PACS 350 Lansering 350_46

    55/57

    55

    Final rinse time + 60sec elapsed.A28 DISINF TEM LET28

    Difference between the sensors in the chamber

    differs more than 3C. Delay time 3 sec. Alarm

    only activated when set point is reached.

    A27 T DIFF CHAMBET27

    Low temperature in washing chamber.Temperature in washing chamber has not

    increase 10C within 8 min. of heating.

    A25 CHAMB TEMP LET25

    Temperature in chamber more than 5C above

    highest selected set point.

    A26 CHAMB TEMP HET26

    DescriptionAlarm text (16char)Alarm

    Temperature in dryer unit more than 130C.A24 DRYER TEMP HET24

    Low temperature in drying unit. Temperature inthe dryer unit has not increased to 80C within 4

    min. of heating.

    A23 DRYER TEMP LET23

    Error code 46 series

  • 7/24/2019 Microsoft PowerPoint - PACS 350 Lansering 350_46

    56/57

    PACS 350 INTRODUCTION46-series

  • 7/24/2019 Microsoft PowerPoint - PACS 350 Lansering 350_46

    57/57

    57

    Power Clean

    50

    100C

    Power Clean

    120 mlDetergent

    12 ml

    rinse