70TH ANNUAL CONFERENCE FOR PROTECTIVE RELAY ENGINEERS TEXAS A&M UNIVERSITY – COLLEGE STATION, TEXAS APRIL 3 – APRIL 6, 2017
MICROPROCESSOR RELAY DIRECTIONAL CHANGE DURING CURRENT REVERSAL
MICHEAL DAVIS, JR, P.E.CENTERPOINT ENERGY – HOUSTON, TEXAS
![Page 2: MICROPROCESSOR RELAY DIRECTIONAL …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2-MAD...MICROPROCESSOR RELAY DIRECTIONAL CHANGE DURING CURRENT REVERSAL MICHEAL DAVIS, JR,](https://reader034.vdocuments.us/reader034/viewer/2022051308/5af94b8c7f8b9a32348c3189/html5/thumbnails/2.jpg)
DISCLAIMERThis presentation is being provided for informational purposes only and does not purport to be comprehensive. Neither CenterPoint Energy, Inc., together with its subsidiaries and affiliates (the “Company”), nor its employees or representatives, make any representation or warranty (express or implied) relating to this information. By reviewing this presentation, you agree that the Company will not have any liability related to this information or any omissions or misstatements contained herein. You are encouraged to perform your own independent evaluation and analysis.
![Page 3: MICROPROCESSOR RELAY DIRECTIONAL …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2-MAD...MICROPROCESSOR RELAY DIRECTIONAL CHANGE DURING CURRENT REVERSAL MICHEAL DAVIS, JR,](https://reader034.vdocuments.us/reader034/viewer/2022051308/5af94b8c7f8b9a32348c3189/html5/thumbnails/3.jpg)
OVERVIEW OF EVENTS• An SLG fault occurred on one transmission line of a parallel
circuitFault duration was 83.33 ms (5 cyc at 60 Hz).
• After one end cleared, one terminal of a parallel line operated.There was no fault on this parallel line.A reverse fault appeared to be forwardReverse fault current value was higher than the
instantaneous overcurrent pickup value.
![Page 4: MICROPROCESSOR RELAY DIRECTIONAL …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2-MAD...MICROPROCESSOR RELAY DIRECTIONAL CHANGE DURING CURRENT REVERSAL MICHEAL DAVIS, JR,](https://reader034.vdocuments.us/reader034/viewer/2022051308/5af94b8c7f8b9a32348c3189/html5/thumbnails/4.jpg)
PROTECTION ELEMENTS• The relays used communication schemes and non-
communication tripping schemes• The element that misoperated was a directional
ground instantaneous overcurrent elementThis is a non-communication element meant to under-
reach and trip with no intentional time delay67G1 requires a high pickup value for the current and an
established forward direction.The relay uses other elements to establish the direction
![Page 5: MICROPROCESSOR RELAY DIRECTIONAL …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2-MAD...MICROPROCESSOR RELAY DIRECTIONAL CHANGE DURING CURRENT REVERSAL MICHEAL DAVIS, JR,](https://reader034.vdocuments.us/reader034/viewer/2022051308/5af94b8c7f8b9a32348c3189/html5/thumbnails/5.jpg)
TOPOLOGY OF AREA – FAULT CURRENT DIRECTION
Relay with the unintended operated
1 2
3 4
![Page 6: MICROPROCESSOR RELAY DIRECTIONAL …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2-MAD...MICROPROCESSOR RELAY DIRECTIONAL CHANGE DURING CURRENT REVERSAL MICHEAL DAVIS, JR,](https://reader034.vdocuments.us/reader034/viewer/2022051308/5af94b8c7f8b9a32348c3189/html5/thumbnails/6.jpg)
TOPOLOGY OF AREA – CURRENT REVERSAL
1 2
3 4
BKRs Tripped
Strong Source Weak Source
![Page 7: MICROPROCESSOR RELAY DIRECTIONAL …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2-MAD...MICROPROCESSOR RELAY DIRECTIONAL CHANGE DURING CURRENT REVERSAL MICHEAL DAVIS, JR,](https://reader034.vdocuments.us/reader034/viewer/2022051308/5af94b8c7f8b9a32348c3189/html5/thumbnails/7.jpg)
CONTRIBUTING FACTORS
• This event involved a combination of contributing factorsParallel LinesLocation and clearing of the faultRelative strength of the fault current sourcesRelay philosophy update was needed to account for
manufacturer relay logic change
![Page 8: MICROPROCESSOR RELAY DIRECTIONAL …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2-MAD...MICROPROCESSOR RELAY DIRECTIONAL CHANGE DURING CURRENT REVERSAL MICHEAL DAVIS, JR,](https://reader034.vdocuments.us/reader034/viewer/2022051308/5af94b8c7f8b9a32348c3189/html5/thumbnails/8.jpg)
PARALLEL LINES
• There’s a current reversal on the parallel line after an end has cleared
• This is more likely to happen on parallel lines
![Page 9: MICROPROCESSOR RELAY DIRECTIONAL …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2-MAD...MICROPROCESSOR RELAY DIRECTIONAL CHANGE DURING CURRENT REVERSAL MICHEAL DAVIS, JR,](https://reader034.vdocuments.us/reader034/viewer/2022051308/5af94b8c7f8b9a32348c3189/html5/thumbnails/9.jpg)
LOCATION OF FAULT – FAULT CLEARING
• Since the fault was located near a terminal, that relay operated quickly to send a trip
• This led to one of the parallel lines being single-ended
![Page 10: MICROPROCESSOR RELAY DIRECTIONAL …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2-MAD...MICROPROCESSOR RELAY DIRECTIONAL CHANGE DURING CURRENT REVERSAL MICHEAL DAVIS, JR,](https://reader034.vdocuments.us/reader034/viewer/2022051308/5af94b8c7f8b9a32348c3189/html5/thumbnails/10.jpg)
SOURCE STRENGTH
• One end of the line had a much stronger source• When the current was reversed due to the end opening,
most of the fault contribution came from the stronger source This fault current went through the line where the relay
misoperated• This also led to the fault current being above the
instantaneous ground overcurrent pickup
![Page 11: MICROPROCESSOR RELAY DIRECTIONAL …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2-MAD...MICROPROCESSOR RELAY DIRECTIONAL CHANGE DURING CURRENT REVERSAL MICHEAL DAVIS, JR,](https://reader034.vdocuments.us/reader034/viewer/2022051308/5af94b8c7f8b9a32348c3189/html5/thumbnails/11.jpg)
DIRECTIONALITY
• It was also realized that the relay settings didn’t account for a change in the directionality logic
• A directional element dropout timer led to the relay still seeing a forward fault when other directional elements dropped out
• This forward decision and the high reverse current led to the ground instantaneous overcurrent element operating
![Page 12: MICROPROCESSOR RELAY DIRECTIONAL …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2-MAD...MICROPROCESSOR RELAY DIRECTIONAL CHANGE DURING CURRENT REVERSAL MICHEAL DAVIS, JR,](https://reader034.vdocuments.us/reader034/viewer/2022051308/5af94b8c7f8b9a32348c3189/html5/thumbnails/12.jpg)
CHANGE IN RELAY LOGIC
• There was a dropout timer added to the relay’s directionality logic for ground directional elements
![Page 13: MICROPROCESSOR RELAY DIRECTIONAL …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2-MAD...MICROPROCESSOR RELAY DIRECTIONAL CHANGE DURING CURRENT REVERSAL MICHEAL DAVIS, JR,](https://reader034.vdocuments.us/reader034/viewer/2022051308/5af94b8c7f8b9a32348c3189/html5/thumbnails/13.jpg)
RELAY OSCILLOGRAPHY - OVERVIEW
![Page 14: MICROPROCESSOR RELAY DIRECTIONAL …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2-MAD...MICROPROCESSOR RELAY DIRECTIONAL CHANGE DURING CURRENT REVERSAL MICHEAL DAVIS, JR,](https://reader034.vdocuments.us/reader034/viewer/2022051308/5af94b8c7f8b9a32348c3189/html5/thumbnails/14.jpg)
RELAY DIGITAL ELEMENTS
![Page 15: MICROPROCESSOR RELAY DIRECTIONAL …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2-MAD...MICROPROCESSOR RELAY DIRECTIONAL CHANGE DURING CURRENT REVERSAL MICHEAL DAVIS, JR,](https://reader034.vdocuments.us/reader034/viewer/2022051308/5af94b8c7f8b9a32348c3189/html5/thumbnails/15.jpg)
NOTES
• Initially, the torque control was set to 1 since there was no dropout time delay between F32QG and 32GF in the original logic32GF used to establish forward direction for the ground
instantaneous overcurrent tripping elementAn adjustment can be made by torque controlling with the
F32QG element• The forward ground instantaneous element picking up for a
reverse fault would have been difficult to test since studies are usually done to test the forward pickup
![Page 16: MICROPROCESSOR RELAY DIRECTIONAL …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2-MAD...MICROPROCESSOR RELAY DIRECTIONAL CHANGE DURING CURRENT REVERSAL MICHEAL DAVIS, JR,](https://reader034.vdocuments.us/reader034/viewer/2022051308/5af94b8c7f8b9a32348c3189/html5/thumbnails/16.jpg)
LESSONS LEARNED
• Relays and their logic can be updated after the initial company practice is established
• As relays are updated, it’s important to track changes in relay logic and other updates
• There could be logic changes that would change current relaying philosophy
![Page 17: MICROPROCESSOR RELAY DIRECTIONAL …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2-MAD...MICROPROCESSOR RELAY DIRECTIONAL CHANGE DURING CURRENT REVERSAL MICHEAL DAVIS, JR,](https://reader034.vdocuments.us/reader034/viewer/2022051308/5af94b8c7f8b9a32348c3189/html5/thumbnails/17.jpg)
REFERENCES1. Schweitzer Engineering Laboratories SEL-421 Instruction
Manual
![Page 18: MICROPROCESSOR RELAY DIRECTIONAL …prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/2-MAD...MICROPROCESSOR RELAY DIRECTIONAL CHANGE DURING CURRENT REVERSAL MICHEAL DAVIS, JR,](https://reader034.vdocuments.us/reader034/viewer/2022051308/5af94b8c7f8b9a32348c3189/html5/thumbnails/18.jpg)
QUESTIONS/ COMMENTS?