MICROPACK ‘ETM’ SERIES

HEATING & CHILLED SYSTEM PRESSURISATION UNITS

Datasheet No: 209Issue No: 8Date: 01/10/07group member

For more information on AquaTech Pressmain visit www.barbourproductsearch.info

ITEM MODEL/SERIES STANDARD/CLASS REMARKSQuality System Manufacturing ISO 9001:1994 Cert No. FM33090

Wiring Standards BSEN 60204: Part 1:1998Electro Magnetic Compatibility European Directive 89/336/EEC:1992

European Directive 89/392/EEC:1994Mains Water Breaktank 5 Litres Nominal Capacity

Mains Float Valve TB Mk.2 WRC.950 2008 0.5" Type 'AB' Air GapPipework Polyurethane Type TU

Pipe Fittings TUV 9205-8323-501Pumps ET 508 IMQ & VDE Standards

Pump Motors T.E. Encapsulated IP55, Class F Insulation Thermal Overload ProtectedControl Cabinet AQ-HM-S IP54

Interlocked Door Isolator LA2 & LA3 BS, UL, CSA, VDE, IECMicroprocessor Enhanced MPC or 2000Plus

Transducer Control 292 SS/Ceramic 8 Bar Max. Test Pressure

Construction Standards 'Micropack' ETM Series

HEATING & CHILLED WATERPRESSURISATION EQUIPMENT

MICROPACK ‘ETM’ SeriesMICROPROCESSOR CONTROLLED

GENERAL

The “Micropack” ETM Series system pressurisation unit is designed to maintain a minimum set pressure in a sealed heating or chilled water system.

Once the system has been initially filled via a quick filling loop, should the pressure fall below the cold fill pressure the ETM unit operates automatically to restore that pressure.

If high or low pressure conditions occur the boiler/chiller operation can be interrupted via thevolt-free contacts provided.

The unit is used in conjunction with a suitably sized expansion vessel from the “Aquatank” range of repla-cable diaphragm vessels to BS6144 (see table on page 3).

FEATURES of STANDARD MODEL 2ETM40

• Microprocessor/Transducer control (For long term accuracy & reliability)• Low water protection in break tank• Common Boiler / Chiller interlock fault relay (volt-free)• Mains water break tank with type ‘AB’ air gap to Water Supply Regulations 1999.

• Two pressurisation pumps• Compact wall mounted cabinet. (300 wide x 400 high x 170 deep)• Automatic alternation of duty pump (for even wear)• Automatic periodic pump pulsing (To prevent pump seizure)

2

• RS232 or 422/485 serial communications port• 8 Volt free signal relays (Functions can be varied to suit requirements)• Indicators for pump run, tripped, hand, off & auto• Additional analogue & digital inputs & outputs available if required

(Note, Both units are fully adjustable on site)

• High water protection in break tank• Keypad for ease of setting parameters• Illuminated comprehensive 2 line LCD display• Non volatile Eprom memory

FEATURES of ENHANCED MODEL 2ETM40-E (as above with addition of below)

For more information on AquaTech Pressmain visit www.barbourproductsearch.info

30°C

AM

BIENT 2

5% G

LYCOL

100

200

300

400

500

600

700

800

900

1000

2000

3000

4000

5000

1500

SYSTEM CONTENT IN LITRES

20 30 40 50 60 70 80 9010

0

200

300

400

50010

BOILER POWER IN KW FOR MEDIUM CONTENT SYSTEMS (10L/Kw)

10

20

30

40

50

60

708090

100

185

60V

R20

0VR

300V

R50

0VR

100V

R

EX

PA

NS

ION

VO

LUM

E O

F S

YS

TE

M IN

LIT

RE

S

30°C

0%

GLY

COL

6000

7000

8000

9000

1000

0

0 20V

R

82°C

(LTHW

) BOILE

R FLO

W T

EMPERATURE

170

50

110

All Dimensions in mm.

300

400

InterlockedDoor Isolator

Mains Power 20mm

System Connection15mm

Mains WaterSupply 15mm

Overflow

Approx. weight 12Kg.

8

370

9

35

333mm fixing centres

160

210

290

205

Warning 22mm

Interlocked Electrical SupplyIsolator and ON/OFF switch

flow restrictorFloat valve

Display1 Pair ofWall Brackets

DIMENSIONS

3

EXPANSION VESSEL SELECTION GUIDE

EXAMPLE:1250 Ltr LTHW system at 82oCSelect 200VR expansion vessel

D

H

DN

60 VR —› 300 VR

Type 25 HR 60 VR 100 VR 200 VR 300 VRNominal Content –litres 25 60 100 200 300

D mm 295 409 480 634 634

D1 mm 228 - - - -

H mm 485 740 840 980 1280

Water Connection DN BSP 1” 1” 1” 1 ¼” 1 ¼”

Dry Weight Kg 5.6 25 32 50 55

Max. working Pressure-bar 10 10 10 10 10

AQUATANK ‘VR’ Series:The diaphragm vessels for special appli-cations: Meets or exceeds EC norms for pressure vessels 97/23/EC; Max working pressure: 10 bar; Vessel Material: Steel RSt 37-2.; All vessel parts in contact with water are coated against corrosion; Diaphragm: Made of special high quality rubber material; Filling Valve: Schraeder-valve-type;Surface Treatment: Blue, durable powder coating finish.

H

DN

D1

D

25 HR

For more information on AquaTech Pressmain visit www.barbourproductsearch.info

N

Supply

Pressure fault

Control

TYPICAL BOILER/CHILLER INTERRUPT CIRCUIT

L N E 20 21 22

C NC NO

LNEE E NNP2

Power Supply240VAC 50Hz 2 Amp

Boiler/ChillerVolt Free240VAC 5A max non-inductive

Pum

p 1

Pum

p 2

Setpoint Adjust

High Pressure Setting

Boiler/ChillerInterlock Terminals

thermostat

Controlrelay

CNO NC

P1

MPC Microprocessor

STANDARD 2ETM40 ELECTRICAL CONNECTIONS

CONNECTION NOTESSafety Interrupt Volt free terminals 20/22 change state when either High or Low pressure is sensed on the system. The control relay de-energises in a fault condition.

SPECIFICATION FOR STANDARD “MICROPACK” 2ETM40 SERIES

Twin pump pressurisation unit suitable for a cold fill pressures of up to 3.0 bar (45 psi), complete with MPC microprocessor and 292 pressure transducer incorporating: combined high/low system pressure cut out single pole relay with “volt-free” contacts; digital pressure and faultdisplay; solid state drive for pressurisation pumps with thermal overload; automatic cut-out and reset on low water level in breaktank.5 litre mains water breaktank with 15mm float valve having type A air gap to BS6281:Part 1.All contained within powder coated sheet steel enclosure, with interlocked door isolator and interconnect-ing piping and wiring.Electrical supply: 240v. 1 Phase, 50 Hz, 2 Amp; Max Power: 0.07 Kw

4

OPERATIONAL/WARNING DISPLAY“L.P” = Low System Pressure, (Scrolls with pressure reading).“H.P” = High System Pressure, (Scrolls with pressure reading).“L.L” = Low Water Level in Mains Water Break Tank.

For more information on AquaTech Pressmain visit www.barbourproductsearch.info

ENHANCED 2ETM40-E ELECTRICAL CONNECTIONS

5

SPECIFICATION FOR MICROPACK 2ETM40-E (ENHANCED)As standard specification with additions: 2000Plus microprocessor control, two thermal overload protected pump motors, Fascia controls to provide 5 indicating lights for each pump condition or status:- run, tripped, hand, off auto.Fascia keypad to enter & set operational parameters, reset alarm & mute.Fascia 2 line LCD illuminated display to provide:

OPERATIONAL DATA DISPLAY: INFORMATION DISPLAYS:System Pressure Hours Run for Each PumpSystem Status Including Warnings Hours Elapsed Since Last ServiceAlarms With Type of Fault Parameter Settings DisplayPump/s Tripped High Pressure Cut-out SettingTransducer Fault Duty Pressure (Cold Fill Pressure)Boiler/s Cut-out Low Pressure Cut-out Setting Support Pump Delay Time

BMS VOLT FREE RELAY CONNECTIONS: * WARNING DISPLAYS:High System Pressure High Pressure ApproachLow System Pressure Low Pressure ApproachLow/High Water Level Low Water Level ApproachExcessive Frequency of Start/Demand Servicing ReminderPump Tripped/Failed Transducer FaultCommon Warning Signal for all Warning Displays*Boiler/Chiller Cut-out

PUMP 1

PUMP 2

Tripped

Running

Tripped

Running

OffAuto

HandOffAuto

Parameters

P

Reset

Mute

Enter

R

M

Hand

Set Operational Parameters or View Data

Alarm ResetAlarm Mute

Enter Operational Parameters

Audible Fault Alarm

Pump Run, Tripped, Hand, Off, Auto LightsPump 1

Pump 2

Optional Solid State Relay (SS) Output (break tank filling etc..)

8 VOLT FREE RELAYS FOR:Pump/s TrippedLow/High Water LevelBoiler/s Cut-outFrequency of StartsHigh System PressureLow System PressureTransducer FailureCommon Warning Display (see below)

A A D D A/D

Special Analogue/Digital (A/D) Input

2 Optional Digital Inputs5 Level Sensing Probes in Mains Water Break Tank

292 Pressure Transducer

Interconnecting Ribbon Cable

2 Line LCD (backlight) Display

Keypad For:-

Mother Board

Facia Board

FUS

E

FUS

E

SS

R

SS

R SS

R

SS

R

For more information on AquaTech Pressmain visit www.barbourproductsearch.info

WORK AT SITE

• Bolt unit to wall.• Connect 15mm mains water supply.• Fit 22mm over flow warning pipe.• Provide 2 amp 240 V AC 50Hz electrical supply and connect to unit.

PUMP 1

PUMP 2

PUMP 3

PUMP 4

Tripped

Running

Tripped

Running

Tripped

Running

Tripped

Running

HandOffAuto

HandOffAuto

HandOffAuto

HandOffAuto

AquaTech LimitedWivenhoe, Essex, CO7 9DR, UK.

Phone: 01206 825254

2000Plus Controller

Parameters

PReset

Mute

Enter

R

M

• Wire boiler/chiller control to terminals. • Connect MICROPACK ETM unit to system.• Fill system via quick-filling loop.• CAUTION: Test pressure must not exceed 8.0 bar (115 psi)

Main Heating Return Header

2 Amp, 240V AC Fused Spur Mains Supply2ETM40

‘Micropack’ Pressurisation Unit

Lockshield Isolating Valve

15 mm Incoming Mains Water Supply

AquaTank Dia-phragm Expan-

sion Vessel(Floor Standing)

Drain Cock

22mm Overflow to Drain

Air Charg-ing Valve

Isolating Valveand Union

Please Note:All pipework & valves are supplied and fitted by contractor.

Use intermediate cooling vessel if flow exceeds 90oC.

INSTALLATION DIAGRAM OF AN AQUATECH MICROPACK UNIT

Connection to un-derside of return header on suction side of circulator pumps

For connection size see Aqua-tank Vessel Table, page 3

The information in this specification is correct at time of issue; as AquaTech Pressmain design and development programmes are continuous, we reserve the right to make any changes to this specification without prior notice.