Page 1: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

MicroLogix™ Ethernet Interface (ENI)(Cat. No. 1761-NET-ENI)

User Manual

Page 2: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

Important User Information Because of the variety of uses for the products described in this publication, those responsible for the application and use of this control equipment must satisfy themselves that all necessary steps have been taken to assure that each application and use meets all performance and safety requirements, including any applicable laws, regulations, codes and standards.

The illustrations, charts, sample programs and layout examples shown in this guide are intended solely for purposes of example. Since there are many variables and requirements associated with any particular installation, Allen-Bradley does not assume responsibility or liability (to include intellectual property liability) for actual use based upon the examples shown in this publication.

Allen-Bradley publication SGI-1.1, Safety Guidelines for the Application, Installation and Maintenance of Solid-State Control (available from your local Allen-Bradley office), describes some important differences between solid-state equipment and electromechanical devices that should be taken into consideration when applying products such as those described in this publication.

Reproduction of the contents of this copyrighted publication, in whole or part, without written permission of Rockwell Automation, is prohibited.

Throughout this manual we use notes to make you aware of safety considerations:

Attention statements help you to:

• identify a hazard

• avoid a hazard

• recognize the consequences

Allen-Bradley is a trademark of Rockwell Automation

ATTENTION

!Identifies information about practices or circumstances that can lead to personal injury or death, property damage or economic loss

IMPORTANT Identifies information that is critical for successful application and understanding of the product.

Page 3: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

Table of Contents

Preface Who Should Use this Manual. . . . . . . . . . . . . . . . . . . . . . . P-1Purpose of this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . P-1Common Techniques Used in this Manual . . . . . . . . . . . . . P-2Rockwell Automation Support . . . . . . . . . . . . . . . . . . . . . . P-3

Chapter 1Product Overview Ethernet Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1

Non-Ethernet Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1Hardware Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2Operating Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4Device Compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4Ethernet Networks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5

Chapter 2Installation and Wiring European Communities (EC) Directive Compliance . . . . . . 2-1

Safety Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3ENI Port Identification. . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5External Power Supply Wiring . . . . . . . . . . . . . . . . . . . . . . 2-5Ethernet Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6RS-232 Port Connections . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8

Chapter 3Operation Operation Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1

Allocation of Ethernet Connections . . . . . . . . . . . . . . . . . . 3-1ENI Functional Overview . . . . . . . . . . . . . . . . . . . . . . . . . 3-2Program Upload/Download and On-Line Sessions . . . . . . . 3-2

Chapter 4ENI Configuration (Node 248 to 254)

Configuration Methods . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1ENI Configuration Utility . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1Controller Messaging. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5Configuring ENI Data Parameters. . . . . . . . . . . . . . . . . . . . 4-6Configuring ENI String Parameters . . . . . . . . . . . . . . . . . . . 4-8ENI Configuration Parameters . . . . . . . . . . . . . . . . . . . . . . 4-10

Chapter 5Peer-to-Peer Messaging Messaging Between the ENI and DF1 Devices . . . . . . . . . . 5-1

Message to Configuration Nodes (Nodes 100 to 149) . . . . . 5-3Sending a Message to a Destination Controller (Nodes 0 to 49). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4

i Publication 1761-UM006A-EN-P - February 2001

Page 4: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

Table of Contents ii

Chapter 6E-Mail Messages (Node 50 to 99) Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1

Configuring E-Mail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2Sending an E-Mail Message . . . . . . . . . . . . . . . . . . . . . . . . 6-5

Chapter 7Connecting 1769-L20 CompactLogix Controllers on Ethernet

System Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1Purpose . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2General Ethernet Information . . . . . . . . . . . . . . . . . . . . . . 7-3Configuring 1761-NET-ENI #1 . . . . . . . . . . . . . . . . . . . . . . 7-4Configuring 1761-NET-ENI #2 . . . . . . . . . . . . . . . . . . . . . . 7-6Configure RSLINX and Download the Program To the 1769-L20 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-13Create MSG Programs for the SLC 5/05 and the 5550 Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-15Configuring an Ethernet Driver in RSLINX . . . . . . . . . . . . . 7-21

Chapter 8Troubleshooting Network Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . 8-1

LED Sequence at Power-Up. . . . . . . . . . . . . . . . . . . . . . . . 8-1Troubleshooting Using the LED Indicators . . . . . . . . . . . . . 8-2Error Codes Generated by the ENI. . . . . . . . . . . . . . . . . . . 8-3Message Instruction Error Codes . . . . . . . . . . . . . . . . . . . . 8-3

Appendix ASpecifications Physical Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1

Ethernet Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1MicroLogix Web Site . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-2

Appendix BBOOTP Configuration Method (default)

Using BOOTP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-2Run the Boot Server Utility . . . . . . . . . . . . . . . . . . . . . . . . B-5

Glossary

Index

Publication 1761-UM006A-EN-P - February 2001

Page 5: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

Preface

Read this preface to familiarize yourself with the rest of the manual. It provides information concerning:

• who should use this manual

• the purpose of this manual

• related documentation

• conventions used in this manual

• Rockwell Automation support

Who Should Use this Manual

Use this manual if you are responsible for designing, installing, programming, or troubleshooting control systems that use Allen-Bradley Controllers on Ethernet.

You should have a basic understanding of Allen-Bradley programmable controllers and Ethernet networking. You should understand programmable controllers and be able to interpret the ladder logic instructions required to control your application. If you do not, contact your local Allen-Bradley representative for information on available training courses before using this product.

Purpose of this Manual This manual is a reference guide for the Ethernet Interface (ENI). It describes the procedures you use to install and configure the ENI.

This manual:

• gives you an overview of the ENI

• explains the procedures you need to install and use an ENI

1 Publication 1761-UM006A-EN-P - February 2001

Page 6: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

Preface P-2

Related Documentation

The following documents contain additional information concerning Rockwell Automation products. To obtain a copy, contact your local Rockwell Automation office or distributor.

Common Techniques Used in this Manual

The following conventions are used throughout this manual:

• Bulleted lists such as this one provide information, not procedural steps.

• Numbered lists provide sequential steps or hierarchical information.

• Italic type is used for emphasis.

For Read this Document Document Number

Instructions on installing a 1761-NET-ENI Interface Converter. Ethernet Interface Installation Instructions

1761-IN006A-MU-P

Information on DF1 open protocol. DF1 Protocol and Command Set Reference Manual

1770-6.5.16

In-depth information on grounding and wiring Allen-Bradley programmable controllers

Allen-Bradley Programmable Controller Grounding and Wiring Guidelines

1770-4.1

A description of important differences between solid-state programmable controller products and hard-wired electromechanical devices

Application Considerations for Solid-State Controls

SGI-1.1

An article on wire sizes and types for grounding electrical equipment National Electrical Code - Published by the National Fire Protection Association of Boston, MA.

A complete listing of current documentation, including ordering instructions. Also indicates whether the documents are available on CD-ROM or in multi-languages.

Allen-Bradley Publication Index SD499

A glossary of industrial automation terms and abbreviations Allen-Bradley Industrial Automation Glossary

AG-7.1

Publication 1761-UM006A-EN-P - February 2001

Page 7: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

Preface P-3

Rockwell Automation Support

Rockwell Automation offers support services worldwide, with over 75 Sales/Support Offices, 512 authorized Distributors and 260 authorized Systems Integrators located throughout the United States alone, plus Rockwell Automation representatives in every major country in the world.

Local Product Support

Contact your local Rockwell Automation representative for:

• sales and order support

• product technical training

• warranty support

• support service agreements

Technical Product Assistance

If you need to contact Rockwell Automation for technical assistance, please review the Troubleshooting information on page 8-1 in this manual first. Then call your local Rockwell Automation representative.

Your Questions or Comments on this Manual

If you find a problem with this manual, or you have any suggestions for how this manual could be made more useful to you, please contact us at the address below:

Rockwell AutomationControl and Information GroupTechnical Communication, Dept. A602VP.O. Box 2086Milwaukee, WI 53201-2086

or visit our internet page at:

http://www.rockwellautomation.com

Publication 1761-UM006A-EN-P - February 2001

Page 8: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

Preface P-4

Publication 1761-UM006A-EN-P - February 2001

Page 9: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

Chapter 1

Product Overview

This chapter gives an overview of the Ethernet Network Interface. The following topics are covered:

• Ethernet Connection

• Non-Ethernet Devices

• Hardware Features

• Operating Modes

• Device Compatibility

• Ethernet Networks

Ethernet Connection The 1761-NET-ENI provides Ethernet/IP connectivity for all MicroLogix controllers and other DF1 full-duplex devices. The Ethernet Network Interface (ENI) allows you to easily connect a MicroLogix onto new or existing Ethernet networks and upload/download programs, communicate between controllers, and generate e-mail messages via SMTP (simple mail transport protocol).

Ethernet/IP is an industry standard open protocol which provides inter-device compatibility. You can exchange information with other Allen Bradley Ethernet controllers (SLC, PLC, and ControlLogix) in a peer-to-peer relationship, so you do not need any master-type device.

Non-Ethernet Devices The ENI allows you to connect non-Ethernet Allen-Bradley programmable controllers to Ethernet networks. The ENI uses Ethernet/IP services to allow these controllers to intercommunicate via their native PCCC messaging.

The ENI allows a non-Ethernet controller to initiate a message to another device over Ethernet. The message can be sent to its application master, or to a peer device. These communications are also referred to as “report on exception” messaging.

When the ENI is connected to a programmable controller, the controller can be used for data acquisition (or Supervisory Control and Data Acquisition, SCADA) functions. This SCADA ability allows the controller to function as a smart RTU over Ethernet.

1 Publication 1761-UM006A-EN-P - February 2001

Page 10: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

1-2 Product Overview

The ENI also supports an SMTP mail service that allows an existing controller to send e-mail messages to any destination connected to the network. The e-mail can be used to initiate the transmission of data or status information.

Hardware Features Product Drawing

LED Indicators

The ENI has five LED indicators:

For more detailed information on LED operation, see Chapter 8, Troubleshooting.

ENI

CAT FRN1761-NET-ENI 1.01

SERA

EXTERNAL POWER REQUIREMENTS24 V dc +10/-15% AT 100 mA

N.E.C. CLASS 2

USE EXTERNAL DC SOURCEFOR CLASS I DIVISION 2 APPLICATIONS. SEEINSTALLATION INSTRUCTIONS

24VD

C

CH

SG

ND

NE

UT

DC

MADE IN U.S.A.

ETHERNETINTERFACE MODULE

ETHERNET ADDRESS

CRR

LISTED IND.CONT.EQ.FOR HAZ. LOC. A196

OPERATINGTEMPERATURECODE T3C

CLASS I , GROUPS A,B,C, AND D, DIV 2

WIN (21)1P6AA0BB Mfg. 1200 Fac. 1P

IP Address Write-On Area

Ethernet Hardware Address

Ethernet PortRS-232 Mini-DIN Port

LED Description Function Color

TX/RX RS-232 data transmission indicator

flashes when the RS-232 port is transmitting or receiving data

green

POWER module power lit when module is powered green

LINK Ethernet link status lit when there is a valid physical Ethernet connection

green

TX/RX Ethernet data transmission indicator

flashes when the Ethernet port is transmitting or receiving data

green

FAULT fault condition indicator lit when a fault condition is present red

FAULT

LINK

Ethernet TX/RX

RS-232 TX/RX

POWER

Publication 1761-UM006A-EN-P - February 2001

Page 11: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

Product Overview 1-3

Default Settings

The ENI’s RS-232 port has the following default settings:

Table 1.1 RS-232 Settings

Setting Default Other Options

Baud Rate Autobaud see table 4.7

Handshaking (hardware, software) none none

Data Bits 8 none

Stop Bits 1 none

Parity none none

Table 1.2 DF1 Settings

Setting Default Other Options

Duplicate Message Detection Enable none

Error Detection CRC, BCC Auto-detect when Autobaud is true, otherwise CRC

Embedded Response Operation Auto-Detect, for reception only(1)

(1) The ENI receives NAKs and ACKs, but does not generate them.

none

DLE ACK Timeout 1 second none

DLE NAK Receive 3 NAK retries none

DLE ENQ for Response 3 ENQs retries none

DF1 Node Address Don’t Care

Publication 1761-UM006A-EN-P - February 2001

Page 12: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

1-4 Product Overview

Operating Modes Messaging

When the ENI is connected to a programmable controller (and connected to an Ethernet network), the controller can be accessed from other devices on Ethernet, or initiate communications to other Ethernet/IP devices.

E-Mail

The ENI also supports SMTP mail service, that allows a controller to send e-mail messages to any e-mail address on the network. The e-mail can be used to initiate the transmission of data or status information.

Device Compatibility The ENI is compatible with the following devices and applications:

• All MicroLogix, SLC, and PLC-5 DF1 Full-Duplex capable controllers that have at least one RS-232 port

• Personal Computers using the RSLinx (V2.30.00 and higher) DF1 Full-Duplex Driver

• Other DF1 Full-Duplex compliant products that have at least one RS-232 port, for example, operator interface devices

• RSLinx (V2.30.00 and higher) Ethernet Driver

• CompactLogix

Publication 1761-UM006A-EN-P - February 2001

Page 13: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

Product Overview 1-5

Ethernet Networks Basic Ethernet Topology

The ENI Ethernet connector conforms to ISO/IEC 8802-3 STD 802.3 and utilizes 10Base-T media. Connections are made directly from the ENI to an Ethernet switch. The network setup is simple and cost effective. Typical network topology is pictured below.

Using a Web Browser with the ENI

You can access information about the ENI via your web browser. Simply enter the ENI’s TCP/IP address into the address field of your browser.

IMPORTANT The ENI provides a 10Base-T, RJ45 Ethernet connector which connects to standard Ethernet hubs and switches via an 8-wire twisted pair straight-through cable. To access other Ethernet mediums, use 10Base-T media converters or Ethernet switches that can be connected together via fiber, thin-wire, or thick-wire coaxial cables, or any other physical media commercially available with Ethernet switches. See page 2-7 for more cable information.

IMPORTANT The IP addresses in any of the examples in this manual were arbitrarily assigned and should only be used on an isolated Ethernet network. Contact your system administrator for unique IP addresses if you are connecting your Ethernet devices to your employer’s Ethernet network.

Ethernet Switch

to PC Ethernet Card or other Ethernet Device

to ENI

RJ45 connectors on both ends of cable (10Base-T)

Publication 1761-UM006A-EN-P - February 2001

Page 14: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

1-6 Product Overview

Publication 1761-UM006A-EN-P - February 2001

Page 15: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

Chapter 2

Installation and Wiring

This chapter covers installation and wiring for the ENI. It is divided into the following sections:

• European Communities (EC) Directive Compliance

• Safety Considerations

• Mounting

• External Power Supply Wiring

• ENI Port Identification

• Ethernet Connections

• RS-232 Port Connections

European Communities (EC) Directive Compliance

This product has the CE mark. It is approved for installation within the European Union and EEA regions. It has been designed and tested to meet the following directives.

EMC Directive

This product is tested to meet the Council Directive 89/336/EC Electromagnetic Compatibility (EMC) by applying the following standards, in whole or in part, documented in a technical construction file:

• EN 50081-2 EMC — Generic Emission Standard, Part 2 — Industrial Environment

• EN 50082-2 EMC — Generic Immunity Standard, Part 2 — Industrial Environment

This product is intended for use in an industrial environment.

Low Voltage Directive

This product is tested to meet Council Directive 73/23/EEC Low Voltage, by applying the safety requirements of EN 61131-2 Programmable Controllers, Part 2 - Equipment Requirements and

1 Publication 1761-UM006A-EN-P - February 2001

Page 16: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

2-2 Installation and Wiring

Tests. For specific information required by EN 61131-2, see the appropriate sections in this publication, as well as the Allen-Bradley publication Industrial Automation Wiring and Grounding Guidelines For Noise Immunity, publication 1770-4.1.

Open style devices must be provided with environmental and safety protection by proper mounting in enclosures designed for specific application conditions. See NEMA Standards publication 250 and IEC publication 529, as applicable, for explanations of the degrees of protection provided by different types of enclosure.

Safety Considerations This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D, or non-hazardous locations only. The following WARNING statement applies to use in hazardous locations.

Use only the following communication cables and replacement connectors in Class I Division 2 Hazardous Locations.

WARNING

!Explosion Hazard

• Substitution of components may impair suitability for Class I, Division 2.

• Do not replace components or disconnect equipment unless power has been switched off and the area is known to be non-hazardous.

• Do not connect or disconnect connectors or operate switches while circuit is live unless the area is known to be non-hazardous.

• This product must be installed in an enclosure. All cables connected to the product must remain in the enclosure or be protected by conduit or other means.

• The ENI must be operated from an external power source.

• All wiring must comply with N.E.C. article 501-4(b).

Environment Classification Communication Cable and Connectors

Class I, Division 2 Hazardous Environment

1761-CBL-PM02 Series C 2707-NC8 Series B

1761-CBL-HM02 Series C 2707-NC9 Series B

1761-CBL-AM00 Series C 2707-NC10 Series B

1761-CBL-AP00 Series C 2707-NC11 Series B

Publication 1761-UM006A-EN-P - February 2001

Page 17: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

Installation and Wiring 2-3

Mounting The 1761-NET-ENI must be mounted in the vertical position, as shown. Horizontal mounting is not recommended due to thermal considerations. Allow 50 mm (2 in.) of space on all sides for adequate ventilation. See page A-1 for operating temperature specification.

DIN Rail Mounting

Installation

ATTENTION

!Do not remove the protective debris strip until after all the equipment in the panel is mounted and wiring is complete. Once wiring is complete, remove protective debris strip. Failure to remove strip before operating can cause overheating.

protective debris strip

ETHERNET

FAULT

RS232

NET

TX/RXTX/RX

PWR

CABLE

EXTERNAL

IP

top

bottom

side side

DIN

Rail

Latch

1. Mount your DIN rail.

2. Snap the DIN rail latch into the closed position.

3. Hook the top slot over the DIN rail.

4. While pressing the unit against the rail, snap the unit into position.

Publication 1761-UM006A-EN-P - February 2001

Page 18: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

2-4 Installation and Wiring

Removal

Panel Mounting

Template

See Appendix A for panel mounting template.

Installation

ATTENTION

!Be careful of metal chips when drilling mounting holes for your equipment within the enclosure or panel. Drilled fragments that fall into the equipment could cause damage. Do not drill holes above mounted equipment if the protective debris strip has been removed.

1. Place a screwdriver in the DIN rail latch at the bottom of the unit.

2. Holding the unit, pry downward on the latch until the unit is released from the DIN rail.

DIN

RailSide

View

1. Remove the mounting template from the back of this document.

2. Secure the template to the mounting surface.

3. Drill holes through the template.

4. Remove the mounting template.

5. Mount the unit.

MountingTemplate

Publication 1761-UM006A-EN-P - February 2001

Page 19: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

Installation and Wiring 2-5

ENI Port Identification

External Power Supply Wiring

ETHERNET

FAULT

RS232

NET

TX/RXTX/RX

PWR

CABLE

EXTERNAL

IPWrite-on area for Ethernet IP address

RS-232 Mini-DIN (ENI Port 2)Ethernet Port (ENI Port 1)

WARNING

!EXPLOSION HAZARD - In Class I Division 2 applications, an external, Class 2 power supply must be used. The DC Power Source selector switch on the ENI must be set to EXTERNAL before connecting the power supply to the ENI.

IMPORTANT • In non-hazardous locations, external power is not required. Some devices (such as a MicroLogix controller) provide power to the ENI via a cable connected to ENI port 2. Be sure to set the DC power source selector switch to match your particular configuration, CABLE or EXTERNAL.

• Always connect the CHS GND (chassis ground) terminal to the nearest earth ground. This connection must be made whether or not an external 24V dc supply is used.

VDC24

DCNEUT

CHSGND

Bottom View

Publication 1761-UM006A-EN-P - February 2001

Page 20: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

2-6 Installation and Wiring

Ethernet Connections Ethernet 8-Pin 10Base-T Connector (Port 1)

The Ethernet connector is an RJ45, 10Base-T connector. The pin-out for the connector is shown below:

When to use straight-through and cross-over cable:

• ENI Ethernet port to 10Base-T Ethernet switch cables utilize a straight-through pin-out (1-1, 2-2, 3-3, 6-6).

• Direct point-to-point 10Base-T cables connecting the ENI Ethernet port directly to another ENI Ethernet port (or a computer 10Base-T port) require a cross-over pin-out (1-3, 2-6, 3-1, 6-2).

Pin Pin Name

1 Tx+

2 Tx-

3 Rx+

4 not used by 10Base-T

5 not used by 10Base-T

6 Rx-

7 not used by 10Base-T

8 not used by 10Base-T

Publication 1761-UM006A-EN-P - February 2001

Page 21: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

Installation and Wiring 2-7

Ethernet Cables

Shielded and non-shielded twisted-pair 10Base-T cables with RJ45 connectors are supported. The maximum cable length between an ENI Ethernet port and a 10Base-T port on an Ethernet switch (without repeaters or fiber) is 100 meters (323 feet). However, in an industrial application, the cable length should be kept to a minimum.

With media converters or Ethernet switches, you can also connect to the following media:

• fiber optic

• broadband

• thick-wire coaxial cable (10Base-5)

• thin-wire coaxial cable (10Base-2)

Maintain ENI Connections

The unshielded twisted pair (UTP) patch cable on a switch should be labeled and treated as dedicated. Be careful when moving any cables, as port identity may be effected. If you are using a switch and must move the ENI to a new port for any reason, power-cycle the ENI. The power cycle forces a new Address Resolution Protocol (ARP) sequence which should immediately associate the ENI’s IP address with the port it is connected to.

You should also discourage any field personal from treating the ports of a switch as “all the same”. This helps to prevent any problems with network communications being effected by moving cables.

Publication 1761-UM006A-EN-P - February 2001

Page 22: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

2-8 Installation and Wiring

RS-232 Port Connections RS-232 Connector

RS-232 Cables

Port 2 of the ENI is an 8-pin mini-DIN RS-232 port that provides connection to DF1 compatible RS-232 devices. The table below describes the RS-232 compatible cables.

See page 2-2 for the list of cables that can be used in a hazardous environment.

Table 2.1 RS-232 Connector Pin Assignments

Pin Port 2

1 24V dc

2 ground (GND)

3 no connection

4 ENI input data, RxD

5 no connection

6 no connection

7 ENI output data, TxD

8 ground (GND)

ENI Connected to: Catalog Number Use Cable

MicroLogix (all series)1761-CBL-AM001761-CBL-HM02

Mini DIN to Mini DIN45 cm (17.7 in)2m (6.5 ft.)

SLC 5/03, SLC 5/04, or SLC 5/05 Channel 0 1761-CBL-AP00

1761-CBL-PM02

Mini DIN to D-Shell45 cm (17.7 in)2m (6.5 ft.)

PLC-51761-CBL-AP001761-CBL-PM02

Mini DIN to D-Shell 45 cm (17.7 in)2m (6.5 ft.)

8-pin mini-DIN

4

2 1

5

87

6

3

Publication 1761-UM006A-EN-P - February 2001

Page 23: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

Chapter 3

Operation

This chapter describes ENI operation. The following information is included:

• Operation Overview

• Allocation of Ethernet Connections

• ENI Functional Overview

• Program Upload/Download and On-Line Sessions

Operation Overview Ethernet is the protocol used to transport TCP/IP messages. On top of TCP, Ethernet/IP is the open protocol used by the ENI. Ethernet/IP allows devices to exchange information (data); or to upload, download, and edit logic programs over Ethernet.

To communicate between devices, Ethernet/IP uses a “connection” model. Connections are dedicated paths across Ethernet between devices.

Allocation of Ethernet Connections

The ENI supports a maximum of 6 connections, allowing simultaneous communication with up to 6 other devices or applications. The connections are dedicated as follows:

Number of Connections Dedicated to:

2 outgoing messages

2 incoming messages

2 either incoming or outgoing messages

TIP For peer connections, no more than one connection per destination node is established. If multiple MSG instructions use the same destination node, they use the same connection.

1 Publication 1761-UM006A-EN-P - February 2001

Page 24: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

3-2 Operation

ENI Functional Overview The ENI provides Ethernet/IP connectivity for RS-232 devices that use DF1 full-duplex protocol. DF1 full-duplex is an open, point-to-point protocol used in any Allen-Bradley controller with an RS-232 port, and in many other devices. DF1 full-duplex supports up to 256 nodes. The ENI uses these nodes for different functions.

The ENI uses a memory (node) map to provide access to the different functions you can perform. Each function uses a different group of node addresses. The following table illustrates the ENI functions by groups of node numbers:

Program Upload/Download and On-Line Sessions

The ENI allows you to connect from your PC to controllers over Ethernet. The following procedure can be used when the computer has a connection directly onto Ethernet (PCI card, PCMCIA interface, built in TCP/IP port, etc.) and the ENI is plugged into the computer’s RS-232 (COMM) port.

RSLinx on Ethernet (PC Connected to Ethernet)

Follow these steps to configure RSLinx for Ethernet operation.

1. Open RSLinx and open the driver configuration dialog.

ENI Function Node Group Node Function Valid Data Type For More Information

Message Routing Node 100 to 149 Configure Route Address Integer see chapter 5

Node 0 to 49 Route DF1 MSG to IP at Configured Route Address

Integer see chapter 5

E-Mail Node 150 to 199 Configure SMTP e-mail address String see chapter 6

Node 50 to 99 Send e-mail message to configured SMTP e-mail address

String see chapter 6

ENI Configuration Node 248 to 254 ENI Configuration Registers Integer or String depending on parameter

see chapter 4

IMPORTANT You must use RSLinx version 2.30.00 or newer to connect with the 1761-NET-ENI.

Publication 1761-UM006A-EN-P - February 2001

Page 25: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

Operation 3-3

2. The “Configure Dialog” will open, select Ethernet devices from the available drivers, and then click “OK” to load the driver into RSLinx.

Once the Ethernet driver is loaded, either highlight and select “Configure” or simply double click on the Ethernet driver.

Publication 1761-UM006A-EN-P - February 2001

Page 26: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

3-4 Operation

At that point the station mapping screen will appear as illustrated here. Double click on the row below “Host Name”, and enter the TCP/IP addresses that match the devices on your network that you will need access to.

When you are done entering the stations, click OK to close the station mapping window.

Publication 1761-UM006A-EN-P - February 2001

Page 27: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

Operation 3-5

3. Open the AB_ETH-1 tree on your computer, autobrowse should be running and any active device that you have configured should be shown on the screen as illustrated below.

RSLogix 500

1. Open RSLogix 500 and select “Comms”

Publication 1761-UM006A-EN-P - February 2001

Page 28: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

3-6 Operation

2. Select “AB_ETH-1, Ethernet.

3. Either expand the tree (select the + in the box, or select the device from the table to the right. From this point, you can then either go online or perform an upload or download.

Publication 1761-UM006A-EN-P - February 2001

Page 29: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

Chapter 4

ENI Configuration (Node 248 to 254)

This chapter describes configuration methods and parameters. It is arranged as follows:

• Configuration Methods

• ENI Configuration Utility

• Controller Messaging

• Configuring ENI Data Parameters

• Configuring ENI String Parameters

• ENI Configuration Parameters

Configuration Methods The ENI’s IP information can be entered using either:

• the ENI Configuration Utility

• a write message from the Allen-Bradley controller to node address 250

• the BOOTP Utility over Ethernet (BOOTP configuration is described in Appendix B of this manual)

ENI Configuration Utility The ENI Configuration Utility is free software designed for configuring the ENI. It is available from http://www.ab.com/micrologix.

TIP When using the ENI Configuration Utility, be sure to use a 1761-CBL-PM02 Series C cable between the ENI and the computer.

1 Publication 1761-UM006A-EN-P - February 2001

Page 30: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

4-2 ENI Configuration (Node 248 to 254)

COM Port Settings

Use the Utility Settings screen to set the following:

• COM Port - The PC’s RS-232 port that the communications cable is plugged into.

• Baud Rate - Select a baud rate or choose Autobaud. See page 4-15 for more information.

• Parameter Upload Behavior and Parameter Download Behavior - This setting controls which parameters will be saved or loaded when you use the Load From or Save To buttons.

RS-232 Baud Rate and TCP/IP Parameters

Use the ENI IP Addr screen to set the following:

• 232 Baud Rate - Select a baud rate or choose Autobaud. See page 4-15 for more information.

• TCP/IP Parameters - See page 4-12 for more information on valid addresses.

Publication 1761-UM006A-EN-P - February 2001

Page 31: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

ENI Configuration (Node 248 to 254) 4-3

Save to ENI RAM or ENI ROM

You must save the configurations you have set. Click ENI RAM for temporary setups or ENI ROM to permanently save your settings. If you do not save the settings, they will revert to “out-of-box” on the next power-up.

E-Mail Settings

Use the Email screen to fill in the information for e-mail messages. E-mail servers are described on page 4-15. See chapter 6 for information on the “To” and “From” strings.

TIP If you want to obtain the TCP/IP information via BOOTP, you must do that separately from the ENI Configuration Utility. See Appendix B.

Publication 1761-UM006A-EN-P - February 2001

Page 32: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

4-4 ENI Configuration (Node 248 to 254)

Message Routing

Use the Message Routing screen to fill in the destination addresses for DF1 messaging. Message routing is described in chapter 5.

Reset

Use the Reset screen to issue reset commands and to set the type of behavior that will occur at reset. The reset behavior options are described on page 4-11.

Publication 1761-UM006A-EN-P - February 2001

Page 33: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

ENI Configuration (Node 248 to 254) 4-5

Controller Messaging When using this method, a write message is used to configure the TCP/IP configuration parameters. A CIF write message is initiated to the controller. CIF stands for Common Interface File and is supported by all Allen-Bradley programmable controllers that have an RS-232 port.

The first item to configure is the ENI’s IP address on your network. See the following section, Configuring ENI Data Parameters, for that configuration procedure.

The configuration parameters are described in more detail later in this chapter.

IMPORTANT The IP addresses in any of the examples in this manual were arbitrarily assigned and should only be used on an isolated Ethernet network. Contact your system administrator for unique IP addresses if you are connecting your Ethernet devices to your employer’s Ethernet network.

Publication 1761-UM006A-EN-P - February 2001

Page 34: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

4-6 ENI Configuration (Node 248 to 254)

Configuring ENI Data Parameters

This example illustrates how to configure the ENI’s TCP/IP address (Node 250).

1. Create an integer data file. Inside the file arrange your TCP/IP data in groups of 4 words (as illustrated in file N50 below).

2. Create your message logic using whatever conditional instructions you may need. In this example, bit B3:0/8 is used to condition the message instruction and message file 10, element 1 is used to manage the message session.

TIP This procedure can also be used for any parameter that requires integer numbers (nodes 50 to 150, 250, 251, 252 and 253).

Publication 1761-UM006A-EN-P - February 2001

Page 35: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

ENI Configuration (Node 248 to 254) 4-7

3. Open the message instruction and enter the appropriate variables. The variables are described in Table 4.1.

4. With the controller in Run, initiate the message. The new TCP/IP information is transmitted to the ENI.

Table 4.1 Message Instruction Variables for Configuring ENI Data Parameters

Variable Setting

This Controller Parameters:

Communication Command

For the ENI configuration, this must be set to:• 485CIF for MicroLogix and SLC• an unprotected write command for CompactLogix and

PLC-5

Data Table Address In this example we are using integer file 50, element 5 (instruction starts at N50:5).

Size in Elements For all ENI TCP/IP data configuration, always set this to 4 (4 words).

Channel The RS-232 communication channel that is connected to the ENI, typically 0 or 1.

Target Device Parameters:

Message Timeout Leave this value at the default.

Data Table Offset Always 0.

Local Node Addr (dec). This is the destination node address, in this example it is 101.

Local/Remote Always Local.

ATTENTION

!At this point, the new configuration has NOT been saved to permanent memory. See Node 248 information on page 4-11 for instructions.

Publication 1761-UM006A-EN-P - February 2001

Page 36: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

4-8 ENI Configuration (Node 248 to 254)

Configuring ENI String Parameters

Configuring the ENI E-Mail From String

This example illustrates configuring the ENI E-mail From String (Node 249). To configure the E-mail From String, initiate a message with a string element as the data.

1. Create a valid string file element as illustrated below. This example has data file 25 configured for string elements. In File ST25, element 0 has a valid e-mail from string, Station_0@My_Company.com.

EXAMPLE Node 249 - E-Mail From String

Node 249 holds the ASCII string that will be sent with any e-mail message initiated by the ENI. To configure the E-mail From String, initiate a message with a string element as the data. To do this, follow the procedure below.

TIP This procedure can also be used for any parameter that requires string data (nodes 150 to 199 and 249).

Publication 1761-UM006A-EN-P - February 2001

Page 37: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

ENI Configuration (Node 248 to 254) 4-9

2. Create your message logic using whatever conditional instructions you may need. This example uses bit B3:0/7 to condition the MSG instruction and message file 10, element 16 to manage the message session.

3. Open the message instruction and enter the appropriate variables. The variables are described in Table 4.2.

Table 4.2 Message Instruction Variables for Configuring ENI String Parameters

Variable Setting

This Controller Parameters:

Communication Command For the ENI configuration, this must be set to:• 485CIF for MicroLogix and SLC• an unprotected write command for CompactLogix and

PLC-5

Data Table Address In this example we are using string file 25, element 0 (ST25:0)

Size in Elements For all ENI parameters that require a string configuration, always set this to 1.

Channel The RS-232 communication channel that is connected to the ENI, typically 0 or 1.

Target Device Parameters:

Message Timeout Leave this value at the default.

Data Table Offset Always 0.

Local Node Addr (dec). This is the destination node address, in this example it is 249.

Local/Remote Always Local.

Publication 1761-UM006A-EN-P - February 2001

Page 38: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

4-10 ENI Configuration (Node 248 to 254)

ENI Configuration Parameters

The following table shows the functions that nodes 248 to 255 perform and their default values. Descriptions of each function can be found following the table.

These parameters are described in more detail in the following sections.

Node Function Data Type Number of Elements

Options Default

248 Save/Reset(1) Integer 1 0 = save configuration to flash1 = simple reset2 = reset to factory defaults3 = conditional reset

n/a

249 From String ASCII String 1 ENI Identifier [email protected](2)

250 TCP/IP Configuration Integers 4, 8, 12, 16, or 20 TCP/IP Parameters 000.000.000.000

251 E-Mail Server Integers 4 E-Mail Server Address 000.000.000.000

252 BOOTP Configuration Integer 1 0 = BOOTP configuration1 = soft configuration

0

253 Baud Rate(3) Integer 1 See page 4-16. Autobaud enabled(4)

254 Ethernet Hardware Address ASCII String 1 Factory Value Factory Value - Read Only(see nameplate on unit)

255 Reserved

(1) See page 4-11 for more information on Save/Reset.

(2) The ENI address, “0.0.0.0” will be replaced by the IP address assigned to the ENI. For example, the string may be [email protected]. If the ENI does not have an assigned IP address, the string will be read as [email protected].

(3) Changes to the Baud Rate take effect when the ENI power is cycled, or the configuration is saved to flash.

(4) Autodetect of CRC/BCC also occurs when autobaud is selected.

Publication 1761-UM006A-EN-P - February 2001

Page 39: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

ENI Configuration (Node 248 to 254) 4-11

Node 248 - Save/Reset Function

Depending on the value of the Save/Reset option, the ENI performs the following operations when receiving a PCCC Unprotected Write message of one element (integer) to Node 248.

Node 249 - From String

Node 249 holds the ASCII string that is sent with any e-mail message initiated by the ENI. Criteria for a valid E-mail From String include:

• The From String remains at the default value unless changed by the user. See page 4-10 for default information.

• The From String must contain an “@” symbol.

• The From String cannot contain any spaces or special ASCII characters.

• The maximum length of the From String is 64 characters. Any additional characters are ignored.

• The From String is sent from a String Table consisting of 84 characters.

• To configure the From String, initiate a message with a string element as the data. The message instruction procedure is shown on page 4-8.

Value of Save/Reset

ENI Operation

0 The ENI immediately stops all normal operations and saves the configuration to non-volatile memory.

IMPORTANT The ENI may take up to 60 seconds to complete this save operation. The configuration is not permanently saved until the Save command is sent.

1 The ENI immediately stops all normal operations and performs a soft reset.

2 The ENI immediately stops all normal operations, performs a soft reset, and returns all parameters to their “out-of-box” settings.

3 The ENI immediately stops all normal operations, performs a soft reset, and returns all parameters to their “out-of-box” settings (except for the IP address, Subnet Mask, Gateway ID, and Security Mask).

Publication 1761-UM006A-EN-P - February 2001

Page 40: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

4-12 ENI Configuration (Node 248 to 254)

Node 250 - TCP/IP Configuration

This procedure describes configuration for the TCP/IP parameters. The TCP/IP parameters are configured by sending a message instruction to the ENI (or by using the ENI Configuration Utility).

1. Configure a 485CIF write message in the Allen-Bradley controller.

2. Set the destination (target) node to 250. Using node address 250 directs this message to the TCP/IP configuration function.

3. The local integer file must be set up for at least 4 integer locations. The first 4 words define the IP address and are required. All remaining variables are optional.

The table below describes the TCP/IP functions that can be configured. The sections following the table describe the functions in more detail.

IMPORTANT Only PLC2 type or 485CIF read/write messages can be used to configure the ENI.

Table 4.3 TCP/IP Configuration Parameters

Function(1)

(1) The IP address must be configured. All other functions are optional.

Data Type Length Notes

IP Address Integer 4 words Format aaa.bbb.ccc.ddd. The ENI verifies the first/highest octet of any IP as follows:

• The first octet is between 1 and 223 and not equal to 127 or 169

• The first octet is 0, and the entire IP is 0.0.0.0

• otherwise the IP address is treated as an error

For example, 0.168.0.75 is an error, or 127.0.0.0 is an error.

Subnet Mask Integer 4 words If not sent, the default mask is derived from the class of the IP address as shown in Table 4-13.

Gateway Integer 4 words Only needed if a Gateway is present on the Subnet. The default is 000.000.000.000.

Security Mask 1 Integer 4 words If not present, the default is no security mask 000.000.000.000.Security Mask 2

Publication 1761-UM006A-EN-P - February 2001

Page 41: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

ENI Configuration (Node 248 to 254) 4-13

Subnet Mask

A subnet mask is used to interpret IP addresses when the network is divided into subnets. If your network is not divided into subnets, then leave the subnet mask at the default or allow the ENI Configuration Utility to assign a default.

The subnet mask defaults to auto-detect mode “out-of-box”. As long as the subnet mask is not manually set, the auto-detect mode follows the rules as shown below:

Subnet Mask Auto-Detect Rules:

• Reading the subnet mask when the IP address is 0.0.0.0 returns a value of 0.0.0.0.

• When you manually configure the subnet mask, auto-detect is switched off and the configured mask is used.

• The ENI validates the configured subnet mask and if:

– The first octet is not equal to 255, the ENI returns status 0x10 and reverts to the previous mask, or

– The first octet is 255, but the remaining mask is not proper, the ENI returns status 0x10 and reverts to the previous mask.

• The definition of “proper” is that the mask must be a contiguous series of 1’s with no zeroes in between (i.e. 255.0.0.0 or 255.224.0.0 or 255.192.0.0 are valid, but 255.160.0.0 is not).

Security Mask

The Security Mask, when configured, allows you to restrict controller access to sources with IP addresses that are within some prescribed range. For example, if you wanted to restrict all message sources to be from within a company’s allocated IP address range, a Security Mask could be configured that would block any IP address outside that range. This only applies to messages to the controller. Web page access, for example, is not restricted.

Table 4.4 Subnet Mask Auto-Detect Operation

When the IP Address is set to: And the Subnet Mask is in auto-detect:The Subnet Mask is set to:

Out of Box: 0.0.0.0 Switch-on auto-detect

Class A address 255.0.0.0

Class B address 255.255.0.0

Class C address 255.255.255.0

Publication 1761-UM006A-EN-P - February 2001

Page 42: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

4-14 ENI Configuration (Node 248 to 254)

The security masks default value is 0.0.0.0 out-of-box, which is defined as “accept all register session requests”. A Security Mask of 255.255.255.255 is also defined as “accept all register session requests”.

The follow examples illustrate the behavior of the security masks:

You can use one or two security masks. If you wish to use only one security mask, use Security Mask 1 because it takes precedence over Security Mask 2 (for example, if Security Mask 1 is accepted, Security Mask 2 is not evaluated). Details of the relationship between the two masks are shown in the following table.

TIP The security mask acts as a filter on the source IP address such that any mask octet set to the value of 255 becomes “don’t care” octets in the source IP address and all other fields must match exactly.

Table 4.5 Security Mask Behavior

Example Condition Security Mask Behavior

If a security mask is set to 192.168.15.255 and an IP address 203.129.75. 23 attempts to message into the controller

The packet is rejected because 203.129.75 does not equal 192.168.15 (the 4th octet, 23, is “don’t care”).

and an IP address 192.168.15.76 attempts to message into the controller

The packet is processed because the upper 3 octets match (the 4th octet is still “don’t care”).

If a security mask is set to 192.168.255.76 All source IPs that equal 192.168.xxx.76 are accepted because 255 is “don’t care”.

Table 4.6 Using Security Mask 1 and Security Mask 2

Example Condition Security Mask Behavior

Security masks 1 and 2 are evaluated using the following logic:

If the security mask 1 filter results in an “Accept” decision

security mask 2 is not evaluated and the register session request is processed.

If the security mask 1 filter results in a “Deny” decision

security mask 2 is evaluated as follows:• If the security mask 2 filter results in an “Accept” decision, the register session

request is processed• If the security mask 2 filter results in a “Deny” decision, the register session

request is not replied to and the socket is closed.

Publication 1761-UM006A-EN-P - February 2001

Page 43: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

ENI Configuration (Node 248 to 254) 4-15

Node 251 - E-Mail Server

The TCP/IP address stored in this location defines the mail server. The ENI sends all e-mail requests to this server, which then sends the e-mail message to the destination.

Node 252 - BOOTP Configuration

The ENI allows the BOOTP request to be disabled by clearing the BOOTP Enable parameter in the channel Configuration File. BOOTP Enable behaves as follows:

• 0 = BOOTP configuration

• 1 = soft configuration

When BOOTP Enable is disabled, the ENI will wait for a manual configuration.

The BOOTP enable/disable setting is only evaluated on power-up. Changes to the BOOTP configuration will not take effect until the next power cycle.

See Appendix B for information on using BOOTP.

Node 253 - Baud Rate

The first time the ENI is powered-up (out-of-the-box), it is set to Autobaud so that it can synchronize to the attached controller. The baud rate can be changed by sending a message to address 253 with one of the configuration values shown in the table below. Changes to the baud rate take effect when the ENI power is cycled or when a Save configuration to flash command (write to node 248) is received. The configuration value is sent as a 2-byte integer (1 element from an integer file).

The ENI also performs a CRC/BCC check when autobaud is operational. It reads a test PCCC_Diagnostic Status Request to determine if CRC or BCC is being used and adjusts to it.

IMPORTANT If BOOTP is disabled, or no BOOTP server exists on the network, you must use a soft configuration method to enter or change the IP address for each ENI. See page 4-1 for more information.

Publication 1761-UM006A-EN-P - February 2001

Page 44: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

4-16 ENI Configuration (Node 248 to 254)

Node 254 - Ethernet Hardware Address

You will find the hardware address on a label affixed to the ENI as shown to the left. The hardware address can also be read from node address 254.

Table 4.7 ENI Baud Rate Options

Configuration Value (Integer) Baud Rate

0x0000 Autobaud Enabled

0x0001 1200

0x0002 2400

0x0003 4800

0x0004 9600

0x0005 19.2K

0x0006 38.4K(1)

(1) All CompactLogix devices must be configured to use two stop bits when communicating with the ENI at 38.4K.

0x0007 57.6K(1)

8 to 65535 Autobaud Enabled

IMPORTANT The ENI cannot Autobaud to 57.6K to synchronize to the attached controller. You must manually set the baud rate to 57.6K. If the controller’s baud rate is from 1200 to 38.4K, and the ENI is configured for Autobaud, the ENI will synchronize with the controller’s baud rate.

Autodetect of CRC/BCC occurs when autobaud is selected. CRC is used when a fixed baud rate is selected.

ENI

CAT FRN1761-NET-ENI 1.01

SERA

EXTERNAL POWER REQUIREMENTS24 V dc +10/-15% AT 100 mA

N.E.C. CLASS 2

USE EXTERNAL DC SOURCEFOR CLASS I DIVISION 2 APPLICATIONS. SEEINSTALLATION INSTRUCTIONS

24VD

C

CH

SG

ND

NE

UT

DC

MADE IN U.S.A.

ETHERNETINTERFACE MODULE

ETHERNET ADDRESS

CRR

LISTED IND.CONT.EQ.FOR HAZ. LOC. A196

OPERATINGTEMPERATURECODE T3C

CLASS I , GROUPS A,B,C, AND D, DIV 2

WIN (21)1P6AA0BB Mfg. 1200 Fac. 1P

Hardware Address

Publication 1761-UM006A-EN-P - February 2001

Page 45: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

Chapter 5

Peer-to-Peer Messaging

This chapter describes messaging between the ENI and DF1 devices. The following topics are covered:

• Messaging Between the ENI and DF1 Devices

• Message to Configuration Nodes (Nodes 100 to 149)

• Sending a Message to a Destination Controller (Nodes 0 to 49)

Messaging Between the ENI and DF1 Devices

The ENI can route a DF1 message received from the attached controller to a compatible destination TCP/IP device.

This is accomplished by using DF1 node addresses 0 through 49. ENI Node addresses 100 through 149 store TCP/IP destination addresses. When the ENI receives a write message to nodes 100 to 149, it stores the TCP/IP destination address in the corresponding map register.

To configure the destination TCP/IP addresses, you can use either the ENI Configuration Utility, or you can send a 485CIF message to each node as described in this section.

1 Publication 1761-UM006A-EN-P - February 2001

Page 46: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

5-2 Peer-to-Peer Messaging

The table below illustrates the relationship between messages and their corresponding configuration addresses.

If the ENI receives a PCCC read message to any of its configuration addresses (nodes 100 to 149), the ENI responds with the current configuration of that node/address.

Using the configuration shown in Table 5-2; if the controller initiates a read or write message to node 0, the ENI forwards the request to the TCP/IP address at Node 100 (111.222.233.200).

Table 5.1 Message Routing

ENI receives read or write PCCC message to

ENI TCP/IP route configuration

Message forwarded to destination node TCP/IP address

Node 0 Node100 111.222.233.200 (stored at Node 100)

Node 1 Node101 111.222.233.201 (stored at Node 101)

IMPORTANT When the ENI receives a PCCC write message to a configuration node address (100 through 149), it closes any open communications currently active on that connection and reconfigures the IP address to match the new configuration.

If the received data matches the current configuration, the ENI closes any open communications with the destination device.

Publication 1761-UM006A-EN-P - February 2001

Page 47: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

Peer-to-Peer Messaging 5-3

Message to Configuration Nodes (Nodes 100 to 149)

When the ENI receives a message to Node Address 0 to 49, it looks up the TCP/IP address associated with the address at Nodes 100 to 149. The ENI preserves the original DF1 address when sending back a reply.

The following table illustrates the relationship between configuration addresses and their corresponding messaging address.

To configure the route address (nodes 100 to 149), write a 485CIF message with 4 integer data words. An example is shown in the next section of this chapter.

Table 5.2 Peer-to-Peer Message Routing

Node Number(1)

(1) See IMPORTANT note below about assigning Nodes to various devices.

Function Node Number

Routing Table Data Type

0 DF1 Route 0 MSG 100 Route 0 Address Integer (4 words)

1 DF1 Route 1 MSG 101 Route 1 Address Integer (4 words)

2 DF1 Route 2 MSG 102 Route 2 Address Integer (4 words)

3 DF1 Route 3 MSG 103 Route 3 Address Integer (4 words)

↓ ↓ ↓ ↓ ↓

49 DF1 Route 49 MSG 149 Route 149 Address Integer (4 words)

IMPORTANT In the ENI, node addresses 45 through 49 are dedicated for sending messages to 1756-ENET/ControlLogix controllers. When sending messages to a 1756-ENET/ControlLogix controller, the controller MUST be in slot 0 of the ControlLogix chassis for the message to be delivered to it.

Node addresses 0 through 44 are to be used for all other Ethernet devices, such as other 1769-L20 controllers connected to ENI modules and SLC 5/05 controllers.

Publication 1761-UM006A-EN-P - February 2001

Page 48: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

5-4 Peer-to-Peer Messaging

Sending a Message to a Destination Controller (Nodes 0 to 49)

The ENI uses a pair of node addresses to send data messages over TCP/IP. For data, two sets of addresses are used as illustrated in the table below. Node numbers 100 to 149 are used to define or store the actual TCP/IP address, and nodes 0 to 49 are used to send the data to the destination.

The procedure to send configuration data (nodes 100 to 149), or data (nodes 0 to 49) is exactly the same as discussed previously in “Configuring ENI Data Parameters” on page 4-6.

Table 5.3 DF1 Message Routing

ENI Node(1)

(1) See IMPORTANT note below about assigning Nodes to various devices.

Function ENI Node Function

0 Route DF1 MSG to IP@address 100 100 Route 0 Address

1 Route DF1 MSG to IP@address 101 101 Route 1 Address

2 Route DF1 MSG to IP@address 102 102 Route 2 Address

3 Route DF1 MSG to IP@address 103 103 Route 3 Address

↓ ↓ ↓ ↓

48 Route DF1 MSG to IP@address 148 148 Route 48 Address

49 Route DF1 MSG to IP@address 149 149 Route 49 Address

IMPORTANT In the ENI, node addresses 45 through 49 are dedicated for sending messages to 1756-ENET/ControlLogix controllers. When sending messages to a 1756-ENET/ControlLogix controller, the controller MUST be in slot 0 of the ControlLogix chassis for the message to be delivered to it.

Node addresses 0 through 44 are to be used for all other Ethernet devices, such as other 1769-L20 controllers connected to ENI modules and SLC 5/05 controllers.

Publication 1761-UM006A-EN-P - February 2001

Page 49: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

Peer-to-Peer Messaging 5-5

Open the message instruction and enter the appropriate variables. The variables are described in Table 5.4.

Table 5.4 Message Instruction Variables for Sending a Message to a Destination Controller

Variable Setting

This Controller Parameters:

Communication Command Use any command supported by your controller.

Data Table Address Use any valid file.

Size in Elements For all ENI data configuration, always set this to 4 (4 words).

Channel The RS-232 communication channel that is connected to the ENI, typically 0 or 1.

Target Device Parameters:

Message Timeout Leave this value at the default.

Data Table Offset Always 0.

Local Node Addr (dec). The destination node address, Nodes 0 to 49.

Local/Remote Always Local.

Publication 1761-UM006A-EN-P - February 2001

Page 50: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

5-6 Peer-to-Peer Messaging

Publication 1761-UM006A-EN-P - February 2001

Page 51: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

Chapter 6

E-Mail Messages (Node 50 to 99)

This chapter describes using the ENI’s e-mail feature. The following topics are included:

• Overview

• Configuring E-Mail

• Sending an E-Mail Message

Overview The ENI is capable of transmitting e-mail messages generated by the attached controller. This provides an extremely versatile mechanism to report alarms, status, and other data-related functions.

To send an e-mail message, the controller generates a write message, with a string element as the data, to a node number that correlates to the e-mail destination address. ENI e-mail behavior in a system is described by the following diagram.

Controller

Destination Server

Destination Mailbox

DF1 String Message

Mail Queue

SMTP Client

Primary Relay Agent

mailgate.xyz.com

PCCC Message with Embedded E-Mail

Local Ethernet or Internet

TCP Connection

ENI

1 Publication 1761-UM006A-EN-P - February 2001

Page 52: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

6-2 E-Mail Messages (Node 50 to 99)

Configuring E-Mail SMTP E-Mail Address

To configure the e-mail function, two parameters must be configured:

• SMTP mail server IP address - configured by sending a write message to node 251 (e-mail server). See page 4-15 for more information.

• A “From” String - configure by sending a write message to node 249 (from string). The string element text can be stored in a String File as shown below. The string element text (ASCII characters) contains the verbatim “from” string. See page 4-8 for more information.

IMPORTANT The ENI only accepts the configuration in the form of 4 elements (words) from an Integer file.

Publication 1761-UM006A-EN-P - February 2001

Page 53: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

E-Mail Messages (Node 50 to 99) 6-3

Destination Addresses

The ENI stores e-mail addresses; it does not store the e-mail messages. To store a destination address, write a message to a specific node number (nodes 150 to 199). The message data must be a string element that contains a valid e-mail ASCII text string address, as illustrated in ST15:0 through ST15:5 in the example below.

Message Text

To send the actual e-mail message, the controller generates a write message, with a string element as the data (see ST15:7 to ST15:9 in the example above) to a node number (50 to 99) that correlates to the e-mail address (150 to 199).

The following table shows the relationship between the e-mail message and the e-mail address. The maximum size of the message is 1 string element of 84 bytes.

IMPORTANT Remember the following when setting up destination addresses:

• The ENI can store up to 50 e-mail addresses.

• E-mail addresses can be up to 45 characters long, exceeding this will result in an error.

• The e-mail address must contain an “@” character.

• E-mail addresses cannot contain any spaces or any other special ASCII characters other than the “@” character.

Publication 1761-UM006A-EN-P - February 2001

Page 54: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

6-4 E-Mail Messages (Node 50 to 99)

Message Fields (to, from, subject)

The ENI includes the “to”, “from”, and “subject” fields in the body of the message.

The default “from” text is [email protected]. This can be changed in the ENI configuration, Node 249. See page 6-2 or Chapter 4.

The standard format of the “subject” line is:

Subject: 1761ENI.MSG(plus the first 32 characters of text)

For example, if the message text was “The quick brown fox jumped over the lazy dog’s back”, the “subject” line would read:

Subject 1761ENI.MSG(The quick brown fox jumped over )

E-Mail Message

E-Mail Address Configuration

Description

Node 50 Node 150 The data within the message is sent to Node 50 and forwarded to the e-mail address stored at Node 150.

Node 51 Node 151 The data within the message is sent to Node 51 and forwarded to the e-mail address stored at Node 151.

Node 52 Node 152 The data within the message is sent to Node 52 and forwarded to the e-mail address stored at Node 152.

↓ ↓ ↓

Node 98 Node 198 The data within the message is sent to Node 98 and forwarded to the e-mail address stored at Node 198.

Node 99 Node 199 The data within the message is sent to Node 99 and forwarded to the e-mail address stored at Node 199.

IMPORTANT The ENI does not support non-printable ASCII characters and may exhibit unpredictable behavior when these characters are used in an e-mail message. Avoid using non-printable ASCII characters such as Carriage Return, Line Feed, Tabs, etc.

Publication 1761-UM006A-EN-P - February 2001

Page 55: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

E-Mail Messages (Node 50 to 99) 6-5

Sending an E-Mail Message

The ENI uses a pair of node addresses to send e-mail or data messages over TCP/IP. To send e-mail, two sets of addresses are used as illustrated in the table below. Node numbers 150 to 199 are used to define or store the actual e-mail address, and nodes 50 to 99 are used to send the string element to the e-mail recipient.

1. Start by configuring a MSG instruction.

TIP The procedure to send configuration strings (nodes 150 to 199), or message strings (nodes 50 to 99) is exactly the same as discussed, “Configuring ENI String Parameters” on page 4-8.

Publication 1761-UM006A-EN-P - February 2001

Page 56: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

6-6 E-Mail Messages (Node 50 to 99)

2. Open the message instruction and enter the appropriate variables. The variables are described in Table 6.1.

Table 6.1 Message Instruction Variables for Sending an E-Mail Message

Variable Setting

This Controller Parameters:

Communication Command Use any command supported by your controller.

Data Table Address Any valid string, such as ST25:21 as shown below.

Size in Elements 1

Channel The RS-232 communication channel that is connected to the ENI, typically 0 or 1.

Target Device Parameters:

Message Timeout Leave this value at the default.

Data Table Offset Always 0.

Local Node Addr (dec). This is the destination node address. Nodes 50 to 99 send e-mail messages.

Local/Remote Always Local.

Publication 1761-UM006A-EN-P - February 2001

Page 57: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

Chapter 7

Connecting 1769-L20 CompactLogix Controllers on Ethernet

The chapter contains an example of using the ENI on an Ethernet network. It is arranged as follows:

• System Diagram

• Purpose

• Scope

• General Ethernet Information

• Configuring 1761-NET-ENI #1

• Configuring 1761-NET-ENI #2

• Configure RSLINX and Download The Program To The 1769-L20

• Create MSG Programs for the SLC 5/05 and the 5550 Controllers

• Configuring an Ethernet Driver in RSLINX

System Diagram Figure 7.1 Example Network

ETHERNET

FAULT

RS232

NET

TX/RXTX/RX

PWR

CABLE

EXTERNAL

IP

ETHERNET

FAULT

RS232

NET

TX/RXTX/RX

PWR

CABLE

EXTERNAL

IP

< > ETHERNET...

1747-L552 (SLC 5/05)

1769-L20(CompactLogix)

1756-L1 (ControlLogix)

1761-NET-ENI #2 Personal Computer with RSLogix 5000, RSLogix 500 and RSLinx

1756-ENET

1761-NET-ENI #1

Ethernet Hub/Switch(10 Base T)

ENI Network

PC COMM Port

RS-232/DF1

PC Ethernet Interface Card

RS-232/DF1

1 Publication 1761-UM006A-EN-P - February 2001

Page 58: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

7-2 Connecting 1769-L20 CompactLogix Controllers on Ethernet

The computer must include the following software:

• RSLOGIX5000, version 7.00 or later

• RSLINX, version 2.30.00 or later

• RSLOGIX500

• ENI Configuration Tool

The 1769-L20 controller must contain firmware 7.17 or later.

The Ethernet Interface Card in the computer is used to connect directly to the SLC 5/05 controller (channel 1) and to the 5550 controller via the 1756-ENET card. The computer COMM Port is used to connect to the 1769-L20 controller via the 1761-NET-ENI modules and an Ethernet hub/switch.

Purpose Provide Ethernet connectivity for 1769-L20 CompactLogix controllers via the RS-232 serial port and the 1761-NET-ENI module.

Scope Connecting 1769-L20 controllers on Ethernet requires one 1761-NET-ENI per L20 controller. The ENI converts RS-232 hardware connections and DF1 full-duplex protocol to Ethernet, TCP/IP.

The ENI must be configured with IP addresses assigned to node numbers 0 to 49. The Destination Node Address in DF1 messages is then used by the ENI to route the message to the proper device on Ethernet.

This application example will show how to configure the ENI module and how to send messages from the 1769-L20 controller to the other Controllers on Ethernet. This example will also show how to initiate messages from the Ethernet controllers to the L20 controller. Messages sent to the ENI module’s IP address will be delivered to the serial port of the L20 controller.

TIP In the ENI, node addresses 45 through 49 are dedicated for 1756-ENET/ControlLogix controllers. Node addresses 0 through 44 are to be used for all other Ethernet devices, such as other 1769-L20 controllers connected to ENI modules and SLC 5/05 controllers.

Publication 1761-UM006A-EN-P - February 2001

Page 59: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

Connecting 1769-L20 CompactLogix Controllers on Ethernet 7-3

General Ethernet Information

Each Ethernet device requires a unique IP address. If your Ethernet network is isolated from the company-wide network, any valid IP addresses may be used. If your Ethernet hub is connected to a larger Ethernet network, contact your System Administrator for unique IP addresses. For this example, the following IP addresses will be assigned to the various Ethernet devices on our network:

The subnet mask for each Ethernet device is then, 255.255.0.0.

Rungs 0 and 1, shown in Figure 7.2, of the 1769-L20 controller’s ladder program show an example of throttling two message (MSG) instructions. In this case, sending a MSG to the SLC 5/05, and then when it’s Done, initiating a MSG to the 1756-ENET/5550 controller and so on. The two MSG Instructions will toggle, with only one outstanding MSG at a time.

This is recommended for the 1769-L20 controller to keep the amount of user memory needed for incoming and outgoing messages to a minimum. Each message requires approximately 1.1K bytes of user memory, allocated when the message is to be sent or received. If two messages were enabled at the same time, 2.2K bytes of user memory would need to be available.

Table 7.1 Example Network IP Addresses

IP Address Device

131.200.50.92 SLC 5/05 controller

131.200.50.93 1756-ENET

131.200.50.94 1761-NET-ENI #2 (1769-L20 controller)

131.200.50.95 1761-NET-ENI #1 (computer COMM port)

131.200.50.96 computer’s Ethernet card

IMPORTANT The RS-232/DF1 interface between the L20 controller and its ENI module, and between the computer (RSLOGIX5000/RSLINX) and its ENI module, should use 38400 baud. This will allow fast upload/download of programs.

When using 38400 baud, the number of Stop Bits in RSLINX and in the L20 controller must be set to 2.

Publication 1761-UM006A-EN-P - February 2001

Page 60: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

7-4 Connecting 1769-L20 CompactLogix Controllers on Ethernet

Figure 7.2 Throttling Message Instructions

Configuring 1761-NET-ENI #1

Refer to Chapter 4 of this manual for information on how to obtain the free ENI Configuration Software Tool.

The first task is to configure the ENI module that will be connected to the computer. This is ENI #1 per Figure 7.1. A 1761-CBL-PMO2 serial cable is used to connect a computer serial communication port to the RS-232 mini-din serial port on the ENI. The ENI Configuration Tool will be used to configure this ENI. Double click the “eniutiCE.exe” icon on your desktop to start the ENI configuration tool. The following screen should appear:

Figure 7.3 ENI Configuration Tool ENI IP Addr Screen

Publication 1761-UM006A-EN-P - February 2001

Page 61: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

Connecting 1769-L20 CompactLogix Controllers on Ethernet 7-5

For this example, we will be using 38400 baud on all serial connections. We will also assign IP addresses to all Ethernet products rather than using BOOTP.

Two tabs in the ENI software tool must be modified for the purposes of this example, the “ENI IP Addr” tab and the “Message Routing” tab. The IP address for the ENI connected to the 1769-L20 controller (ENI #2) is the only address we need to add to the ENI #1 Message Routing table. The other two Ethernet devices are accessed by the computer via the computer’s Ethernet card. Make the two ENI #1 tabs look like the following:

Figure 7.4 ENI #1 Configuration - ENI IP Addr Screen

Figure 7.5 ENI #1 Configuration - Message Routing Screen

Before we download our configuration to ENI #1, we must configure the “Utility Settings” tab in the ENI configuration tool. Make this tab look like the following.

Figure 7.6 ENI #1 Configuration - Utility Settings Screen

Publication 1761-UM006A-EN-P - February 2001

Page 62: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

7-6 Connecting 1769-L20 CompactLogix Controllers on Ethernet

Then, connect the serial cable between your computer and ENI #1 and click on the ENI IP Addr tab. From this tab, under the “Save To” column, click the ENI ROM button. This will download your configuration parameters to ENI #1 and save it to non-volatile memory.

Configuring 1761-NET-ENI #2

ENI #2 is connected to the L20 controller. This ENI must be configured with its own IP address (131.200.50.94 for this example) and we must add the IP addresses of the SLC 5/05 controller and the 1756-ENET/5550 controller to its Message Routing table. The Message Routing table allows for up to 50 IP addresses to be linked to DF1 destination node addresses, for the following purposes:

At this point we could merely configure ENI #2 as we did ENI #1. Or, we could use the method outlined in Chapter 5 to configure ENI #2. This method sends configuration Messages from the L20 controller via the DF1 link. If for any reason this ENI would need to be replaced, it could then be easily and quickly configured via messages from the L20 controller. A ladder program to accomplish this is as follows:

Table 7.2 Message Routing

Nodes Function

Nodes 0 to 44 When sending messages to any Ethernet device, other than ControlLogix, that supports the same command set as the 1769-L20 controller, i.e. SLC 5/05, PLC-5E and other ENI modules. We will use the PLC-5 Typed Write commands for this example. CIP commands are not supported by the ENI.

Nodes 45 to 49 When sending messages to a 1756-ENET/ControlLogix Controller, the controller MUST be in slot 0 of the ControlLogix chassis for the message to be delivered to it.

Publication 1761-UM006A-EN-P - February 2001

Page 63: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

Connecting 1769-L20 CompactLogix Controllers on Ethernet 7-7

Figure 7.7 ENI #2 Configuration - RSLogix 5000 Ladder Program

The above ladder rungs, 2 through 7 and the rungs, 0 and 1 shown earlier in this application example, make up the ladder program for the L20 controller. Details of each MSG Instruction will follow.

In the above program, Rung 2 initiates the string of configuration messages with input instruction “Reconfig_ENI”. This could be an alias to an input connected to a pushbutton for example, for quick configuration of the ENI module.

Publication 1761-UM006A-EN-P - February 2001

Page 64: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

7-8 Connecting 1769-L20 CompactLogix Controllers on Ethernet

The 5 rungs used to configure ENI #2 are defined as follows:

The following table contains the information needed to send messages to the ENI to configure it for this example. For a complete list of ENI configurable features, please refer to Chapters 4 and 5.

Table 7.3 ENI #2 Configuration - Rung Descriptions

Rung Function

Rung 2 This rung initiates the process and configures the ENI module’s Serial port for 38400 Baud.

Rung 3 This rung is initiated by the Done bit of the previous MSG and it disables BOOTP.

Rung 4 This rung configures the ENI with its own IP address.

Rung 5 This rung adds the IP address of the SLC 5/05 controller to the ENI module’s Message Routing table at DF1 node 1. This means that any message sent by the -L20 controller with a DF1 destination address of 1, will be sent to the SLC 5/05 controller on Ethernet.

Rung 6 This rung adds the IP address of the 1756-ENET module to the ENI module’s Message Routing table at DF1 node 45. This means that any message sent by the -L20 controller with a DF1 destination address of 45, will be sent to the 5550 controller in slot 0, via the 1756-ENET module on Ethernet.

Rung 7 This rung instructs the ENI module to save the configuration data sent to it in non-volatile memory.

Table 7.4 ENI #2 Configuration - Message Instructions Parameters

Configuration Node Number

Configuration Function Data Type Message Node Number

Message Length (bytes)

Message Function

101 Configure Route 1 Address Integers 1 8 Route DF1 MSG to IP at Address 1

145 Configure Route 45 Address Integers 45 8 Route DF1 MSG to IP at Address 2

248 Save/Reset Integer N/A 2 0 = save configuration to flash

250 TCP/IP Config. Integer N/A 8 Assign an IP Address to the ENI

252 BOOTP Integer N/A 2 1 = disable BOOTP

253 Baud Rate Integer N/A 2 6 = 38400 Baud

Publication 1761-UM006A-EN-P - February 2001

Page 65: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

Connecting 1769-L20 CompactLogix Controllers on Ethernet 7-9

For this example, as mentioned earlier, we will assign the following IP addresses to the devices on Ethernet:

The Message Instructions for the L20 controller, Rungs 2 through 7, used to configure the ENI module, must be “PLC2 Unprotected Write” Message Type. The “Destination Element” can be any valid PLC2 command value. “010” is used in this example because it is the first available valid value. This parameter is not used by the ENI, but must be a valid value for RSLOGIX5000 to accept it.

An example of the MSG Configuration tab and the Communication tab for the MSG Instruction used to configure the IP address for the ENI (Rung 4) are as follows:

Table 7.5 Example IP Addresses for Ethernet Devices

Device Node Address (for L20 MSG) IP Address

SLC-5/05 1 131.200.50.92

1756-ENET 45 131.200.50.93

1761-NET-ENI #2 N/A 131.200.50.94

1761-NET-ENI #1 N/A 131.200.50.95

Computer Ethernet Card N/A 131.200.50.96

IMPORTANT The IP addresses in Table 2 were arbitrarily assigned for this demonstration and should only be used on an isolated Ethernet network as in this example. Contact your system administrator for unique IP addresses if you are connecting your Ethernet devices to your companies Ethernet network.

Publication 1761-UM006A-EN-P - February 2001

Page 66: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

7-10 Connecting 1769-L20 CompactLogix Controllers on Ethernet

Figure 7.8 ENI #2 Configuration - Message Configuration Tab

Figure 7.9 ENI #2 Configuration - Message Communication Tab

Note that the MSG length is 8 bytes or 4 integer words. These 4 words contain the IP address for ENI #2 and are stored in tag ENI_IP_VALUE, which is a tag address containing 4 integer words. This is shown in

Publication 1761-UM006A-EN-P - February 2001

Page 67: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

Connecting 1769-L20 CompactLogix Controllers on Ethernet 7-11

the L20 controller’s tag database shown below. On the MSG Instruction’s Communication tab above, the path is “2,250”, where the 2 represents the L20 controllers serial port and the 250 tells the ENI module that the 4 words of data contain its IP address.

Figure 7.10 L20 Controller’s Tags

Per Table 7.4, The MSGs in Rungs 2, 3 and 7 are 2 bytes or 1 integer word in length. Their Paths are “2,253”, “2,252” and “2,248” respectively; where 253 represents Baud Rate, 252 represents BOOTP Enable/Disable, and 248 represents the Save function.

The single integer data value for these messages is shown in Table 7.4. “0” is the value for the Save MSG data tag (ENI_SAVE_TO_FLASH_VALUE), which instructs the ENI to save its configuration to non-volatile memory. “6” is the value for the Baud Rate MSG data tag (ENI_BAUD_VALUE) which instructs the ENI to begin communicating on its RS-232 port at 38400 Baud. “1” is the value to disable BOOTP (BootP_disable_value).

Per Table 7.4, The MSGs in Rungs 5 and 6 assign IP addresses to node numbers in the ENI module’s Message Routing Table. These two MSG Instructions are the same as the MSG Instruction in Rung 3, except the paths are 2,101 and 2,145 and the data tags have different names; this time containing the IP addresses of the SLC 5/05 and 1756-ENET module.

Publication 1761-UM006A-EN-P - February 2001

Page 68: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

7-12 Connecting 1769-L20 CompactLogix Controllers on Ethernet

Enter your 1769-L20 ladder program per Rungs 0 through 7 as shown and described above. Be sure to enter your IP addresses for ENI #2, the SLC 5/05, and the 1756-ENET into the proper tags in the controller’s tag database. Before saving your program, enter the Controller Properties window by clicking on the Edit pull-down menu and select Controller Properties. Click on the System Protocol tab and change Error Detection from BCC to CRC and the Baud Rate from 19200 to 38400. Click APPLY, then OK. The ENI modules use CRC Error Detection.

If you do not change this parameter in your -L20 controller, it will not be able to communicate with the ENI. The Baud Rate of 38400 is being used to increase the upload/download speed.

Finally, since Logix controllers do not use the structured data table addressing scheme used by PLC and SLC controllers, we must map file numbers used in the commands sent to any Logix controller to tag names within them. For example, a MSG sent by an SLC 5/05 controller to the L20 controller uses a PLC-5 Typed Write command. The target data table address used is N12:0. This file 12 must be mapped to a valid tag name in the L20. Since the MSG is 20 integer words in length, a tag in the L20 controller called “Data_From_505” was created as a 20 integer word tag.

While offline in the L20 controller project, click on the Logic pull-down menu and select “Map PLC/SLC Messages”. The following screen appears:

Figure 7.11 File Mapping in RSLogix 5000

Publication 1761-UM006A-EN-P - February 2001

Page 69: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

Connecting 1769-L20 CompactLogix Controllers on Ethernet 7-13

In the File Number column enter 12. Under the Tag Name, click on the right side in the white box to reveal your Controller Tags and select the tag name you created for this purpose (“Data_From_505” for this example). More than one entry may be mapped. When finished, your Map PLC/SLC screen for the L20 controller should look like the following:

Figure 7.12 File Mapping for the L20 Controller in RSLogix 5000

Save your program.

Configure RSLINX and Download The Program To The 1769-L20

The ladder program written for the L20 controller is downloaded to the controller via the two ENI modules. A full-duplex DF1 driver must be configured in RSLINX to initiate the download to ENI #1.

Start RSLINX. From the “Communication” pull down menu, select “Configure Drivers”. From the Configure Driver screen, click on the arrow next to the “Available Drivers Box” to reveal all RSLINX drivers. Click on “RS232 DF1 devices”, then click on “Add New”. Click OK to the “AB_DF1-1” driver name that appears. The “Configure RS232 DF1 Devices” screen appears. Modify the DF1 parameters on this screen to look like the following:

Publication 1761-UM006A-EN-P - February 2001

Page 70: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

7-14 Connecting 1769-L20 CompactLogix Controllers on Ethernet

Figure 7.13 Modify DF1 Parameters Using RSLInx

It is very important that the “Station Number” match the “Destn” number in ENI #1, assigned to the IP address for ENI #2. In this example, we arbitrarily used Destn address 2 to represent IP address 131.200.50.94, which is the IP address of ENI #2.

DO NOT click on the “Auto Configure” button on this screen.

When you have properly modified the parameters on this screen, click OK. Then close the Configure Drivers screen.

Open the WHO Active screen by clicking on the Communications pull-down menu and select Who Active. If your system is properly connected, you should be able to click on the + sign left of the AB_DF1-1 driver you created and the CompactLogix controller should appear beneath the driver. Minimize, but do not close RSLINX.

Start RSLOGIX5000. Open the 1769-L20 program created earlier. Click on the Communications pull-down menu and select Who Active. From the Who Active screen. Click on the + sign left of “AB_DF1-1, DF1”. The CompactLogix controller should appear. Single-click on it to highlight it, then click Download. Your program should download to the controller. You should be online with the controller when the download is complete. The software will soon time out, placing your computer in the offline mode. At this point, if you are still online, you may click on the Communications pull down menu and select offline. Online monitoring of the -L20 controller via two ENI modules is not supported at this time.

Publication 1761-UM006A-EN-P - February 2001

Page 71: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

Connecting 1769-L20 CompactLogix Controllers on Ethernet 7-15

Create MSG Programs for the SLC 5/05 and the 5550 Controllers

We must now create MSG ladder programs for our other two controllers on Ethernet. The following is the MSG ladder program for the SLC 5/05 controller, developed with RSLOGIX500. Following the ladder program are four additional screens showing the two tabs for each MSG Instruction. Before saving your program, be sure to configure Channel 1 with its IP address, subnet mask and disable BOOTP. Then, save your program.

Figure 7.14 SLC 5/05 Controller Ladder Program

Publication 1761-UM006A-EN-P - February 2001

Page 72: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

7-16 Connecting 1769-L20 CompactLogix Controllers on Ethernet

Figure 7.15 SLC 5/05 Rung 0 MSG “General” Tab

Figure 7.16 SLC 5/05 Rung 0 MSG “Multihop” Tab

Publication 1761-UM006A-EN-P - February 2001

Page 73: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

Connecting 1769-L20 CompactLogix Controllers on Ethernet 7-17

Figure 7.17 SLC 5/05 Rung 1 MSG “General” Tab

Figure 7.18 SLC 5/05 Rung 1 MSG “Multihop” Tab

Publication 1761-UM006A-EN-P - February 2001

Page 74: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

7-18 Connecting 1769-L20 CompactLogix Controllers on Ethernet

The following is the MSG ladder program for the 5550 controller, developed with RSLOGIX5000. Following the ladder program are four additional screens showing the two tabs for each MSG Instruction. As part of your program, you must configure your 1756-ENET module with the proper IP address.

Figure 7.19 ControlLogix 5550 Controller Ladder Program

Publication 1761-UM006A-EN-P - February 2001

Page 75: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

Connecting 1769-L20 CompactLogix Controllers on Ethernet 7-19

Figure 7.20 ControlLogix 5550 Rung 0 Message Configuration Tab

Figure 7.21 ControlLogix 5550 Rung 0 Message Communication Tab

Publication 1761-UM006A-EN-P - February 2001

Page 76: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

7-20 Connecting 1769-L20 CompactLogix Controllers on Ethernet

Figure 7.22 ControlLogix 5550 Rung 1 Message Configuration Tab

Figure 7.23 ControlLogix 5550 Rung 1 Message Communication Tab

The 1761-NET-ENI modules do not support CIP commands. Therefore, all commands between controllers used in this application example are PLC_5 Typed Write commands. These commands require a PLC-5 type address to send the data to the receiving controller. Such

Publication 1761-UM006A-EN-P - February 2001

Page 77: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

Connecting 1769-L20 CompactLogix Controllers on Ethernet 7-21

addresses do not exist in Logix controllers, so they must be mapped to existing tags in these controllers.

From the Logic pull down menu, select “Map PLC/SLC Messages”. Your mapped table for your 5550 program should look like the following:

Figure 7.24 File Mapping for the ControlLogix 5550 Controller in RSLogix 5000

Save your program.

Configuring an Ethernet Driver in RSLINX

In order to download your programs to the SLC 5/05 controller and to the 5550 controller via Ethernet, we must configure an Ethernet driver in RSLINX.

In RSLINX, click on the Communications pull-down menu and select Configure Drivers. Click on the arrow associated with the Available Driver Types box. Select Ethernet Devices, then click Add New.

Modify this screen to include the IP addresses of the SLC 5/05 and the 1756-ENET as shown below:

Publication 1761-UM006A-EN-P - February 2001

Page 78: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

7-22 Connecting 1769-L20 CompactLogix Controllers on Ethernet

Figure 7.25 Configure Ethernet Driver Using RSLinx

From the RSLOGIX500 programming software, you should now be able to download your SLC 5/05 program. Then, from the RSLOGIX5000 software you should now be able to download your 5550 controller program.

Once all programs are downloaded to their respective controllers, place each controller into the RUN mode and a MSG from each controller will be sent to each of the other controllers. Each controller will only send one MSG at any given time. Go online with the SLC 5/05 and 5550 controllers to verify the successful completion of their Messages.

IMPORTANT You cannot go online with the -L20 controller at this time, but you can verify that the -L20 messages are completing successfully by looking at the destination in the two other controllers where the -L20 is writing data. Verify that the data is being received.

Publication 1761-UM006A-EN-P - February 2001

Page 79: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

Chapter 8

Troubleshooting

This chapter covers the following Troubleshooting topics:

• Network Troubleshooting

• LED Sequence at Power-Up

• Troubleshooting Using the LED Indicators

• Error Codes Generated by the ENI

• Message Instruction Error Codes

Network Troubleshooting Maintain ENI Connections

The UTP (unshielded twisted pair) patch cable on a switch should be labeled and treated as dedicated. Be careful when moving any cables, as port identity may be effected. If you must move the ENI to a new port for any reason, power-cycle the ENI. The power cycle forces a new ARP (address resolution protocol) request to be sent which should immediately associate the ENI’s IP address with the port it is connected to.

You should also discourage any field personal from treating the ports of a switch as “all the same”. This helps to prevent any problems with network communications being effected by moving cables.

LED Sequence at Power-Up The following LED test is performed at power-up.

LED Power-Up Sequence

Ethernet TX/RX, Link and FAULT 1. on solid for 2 seconds

FAULT 2. flashes for 4 seconds

Ethernet TX/RX and FAULT 3. on solid for 1/4 second

All LEDs 4. off, unless an error condition exists (see troubleshooting table on page 8-2)

1 Publication 1761-UM006A-EN-P - February 2001

Page 80: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

8-2 Troubleshooting

Troubleshooting Using the LED Indicators

The ENI status LEDs provide a mechanism to determine the current status of the ENI if a programming device is not present or available. The LED behavior is described in the following table.

LED Description Color State Indicates

RS-232 TX/RX

RS-232 data transmission indicator

green flashing data is being transmitted or received over the RS-232 port

off no RS-232 traffic

POWER module power green on module is powered

off module may not be powered

LINK Ethernet link status green on the module detects a valid Ethernet connection

off the module does not detect a valid Ethernet connection

Ethernet TX/RX

Ethernet data transmission indicator

green flashing steady During normal operation (Fault LED is off) the Ethernet port is transmitting or receiving NetLinx packets. For example, if you use “Ping” or “Telnet”, the Ethernet TX/RX LED will not flash.

flash sequence When the Fault LED is on steady, the Ethernet TX/RX LED flashes the following error codes:

• ROM Error - 1 flash, then off• RAM Error - 2 flashes, then off• Net Controller Error - 3 flashes, then off• EEPROM error: 4 flashes, then off• Duplicate IP: 5 flashes, then off

When the FAULT LED is flashing, the Ethernet TX/RX LED flashes the following error codes:

• Faulty Network Connection: 4 flashes, then off• ENI Not Configured: 5 flashes, then off• Unspecified Fault: off

off no Ethernet traffic

FAULT fault condition indicator red on lit when a fault condition is present, possible causes• ROM Checksum Error• RAM Test Error• Network Controller Error• EEPROM Checksum Error• Duplicate IP

(see Ethernet TX/RX LED behavior above for error codes)

flashing one of the following:• faulty network connection• ENI does not have a valid IP address

off hardware is functioning normally

Publication 1761-UM006A-EN-P - February 2001

Page 81: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

Troubleshooting 8-3

Error Codes Generated by the ENI

This table shows the error codes that may be generated by the ENI. A full listing of error codes that may be generated by the Message Instruction is shown below.

Message Instruction Error Codes

When the controller detects an error during the transfer of message data, the controller sets the ER bit and enters an error code that you can monitor from your programming software.

Error Code Description of Error Condition

10H Target node cannot respond because of incorrect command parameters or unsupported command. Possible causes:• The data size of the message is invalid.• The data format is incorrect for any of the supported PCCC messages.• Register parameters are not formatted correctly, or there is not enough data provided.• RS-232 configuration packet data is not the correct size.• The Node Address is invalid or out-of-range.• The distant ENI, controller, or device may not be responding.• There may be a break in the connection between the ENI devices or controllers.• BOOTP/DF1 parameter is invalid.

30H PCCC Description: Remote station host is not there, disconnected, or shutdown.

D0H One of the following:• No IP address configured for the network or ENI not configured for Node Address used.• Bad command - unsolicited message error.• Bad address - unsolicited message error.• No privilege - unsolicited message error.

Error Code Description of Error Condition

02H Target node is busy. NAK No Memory retries by link layer exhausted.

03H Target node cannot respond because message is too large.

04H Target node cannot respond because it does not understand the command parameters OR the control block may have been inadvertently modified.

05H Local processor is off-line (possible duplicate node situation).

06H Target node cannot respond because requested function is not available.

07H Target node does not respond.

08H Target node cannot respond.

09H Local modem connection has been lost.

0BH Target node does not accept this type of MSG instruction.

0CH Received a master link reset (one possible source is from the DF1 master).

10H Target node cannot respond because of incorrect command parameters or unsupported command.

12H Local channel configuration protocol error exists.

13H Local MSG configuration error in the Remote MSG parameters.

Publication 1761-UM006A-EN-P - February 2001

Page 82: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

8-4 Troubleshooting

15H Local channel configuration parameter error exists.

16H Target or Local Bridge address is higher than the maximum node address.

17H Local service is not supported.

18H Broadcast is not supported.

21H Bad MSG file parameter for building message.

30H PCCC Description: Remote station host is not there, disconnected, or shutdown.

37H Message timed out in local processor.

39H Local communication channel reconfigured while MSG active.

3AH STS in the reply from target is invalid.

40H PCCC Description: Host could not complete function due to hardware fault.

45H MSG reply cannot be processed. Either Insufficient data in MSG read reply or bad network address parameter.

50H Target node is out of memory.

60H Target node cannot respond because file is protected.

70H PCCC Description: Processor is in Program Mode.

80H PCCC Description: Compatibility mode file missing or communication zone problem.

90H PCCC Description: Remote station cannot buffer command.

B0H PCCC Description: Remote station problem due to download.

C0H PCCC Description: Cannot execute command due to active IPBs.

D0H One of the following:No IP address configured for the network or ENI not configured for Node Address used.Bad command - unsolicited message error.Bad address - unsolicited message error.No privilege - unsolicited message error.

D1H Maximum connections used - no connections available.

D2H Invalid internet address or host name.

D3H No such host / Cannot communicate with the name server.

D4H Connection not completed before user–specified timeout.

D5H Connection timed out by the network.

D7H Connection refused by destination host.

D8H Connection was broken.

D9H Reply not received before user–specified timeout.

DAH No network buffer space available.

E1H PCCC Description: Illegal Address Format, a field has an illegal value.

E2H PCCC Description: Illegal Address format, not enough fields specified.

E3H PCCC Description: Illegal Address format, too many fields specified.

E4H PCCC Description: Illegal Address, symbol not found.

E5H PCCC Description: Illegal Address Format, symbol is 0 or greater than the maximum number of characters support by this device.

Error Code Description of Error Condition

Publication 1761-UM006A-EN-P - February 2001

Page 83: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

Troubleshooting 8-5

E6H PCCC Description: Illegal Address, address does not exist, or does not point to something usable by this command.

E7H Target node cannot respond because length requested is too large.

E8H PCCC Description: Cannot complete request, situation changed (file size, for example) during multi–packet operation.

E9H PCCC Description: Data or file is too large. Memory unavailable.

EAH PCCC Description: Request is too large; transaction size plus word address is too large.

EBH Target node cannot respond because target node denies access.

ECH Target node cannot respond because requested function is currently unavailable.

EDH PCCC Description: Resource is already available; condition already exists.

EEH PCCC Description: Command cannot be executed.

EFH PCCC Description: Overflow; histogram overflow.

F0H PCCC Description: No access.

F1H Local processor detects illegal target file type.

F2H PCCC Description: Invalid parameter; invalid data in search or command block.

F3H PCCC Description: Address reference exists to deleted area.

F4H PCCC Description: Command execution failure for unknown reason; PLC-3 histogram overflow.

F5H PCCC Description: Data conversion error.

F6H PCCC Description: The scanner is not able to communicate with a 1771 rack adapter. This could be due to the scanner not scanning, the selected adapter not being scanned, the adapter not responding, or an invalid request of a “DCM BT (block transfer)”.

F7H PCCC Description: The adapter is not able to communicate with a module.

F8H PCCC Description: The 1771 module response was not valid size, checksum, etc.

F9H PCCC Description: Duplicated Label.

FAH Target node cannot respond because another node is file owner (has sole file access).

FBH Target node cannot respond because another node is program owner (has sole access to all files).

FCH PCCC Description: Disk file is write protected or otherwise inaccessible (off-line only).

FDH PCCC Description: Disk file is being used by another application; update not performed (off-line only).

FFH Local communication channel is shut down.

Error Code Description of Error Condition

TIP For 1770-6.5.16 DF1 Protocol and Command Set Reference Manual users: The MSG error code reflects the STS field of the reply to your MSG instruction.

• Codes E0 to EF represent EXT STS codes 0 to F.

• Codes F0 to FC represent EXT STS codes 10 to 1C.

Publication 1761-UM006A-EN-P - February 2001

Page 84: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

8-6 Troubleshooting

Publication 1761-UM006A-EN-P - February 2001

Page 85: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

Appendix A

Specifications

Physical Specifications

Ethernet Specifications Communication Rate: 10 Mbps

Connector: 10Base-T

MicroLogix Web Site Visit http://www.ab.com/micrologix for more information on MicroLogix products. You can find a variety of application information and White Papers covering specific technical topics.

Description ENI Specification24V dc Power Source Requirement 20.4 to 26.4V dc24V dc Current Draw 50 mA typical, 100 mA maximumMaximum Inrush Current 200 mAInternal Isolation 500V ac for one minuteVibration operating: 10 to 500 Hz, 5.0g, 0.030 in. peak-to-peak, 2 hour each axisShock operating: 30g, ±3 times each axis

non-operating: 35g (DIN Rail Mount) 50g (Panel Mount), ±3 times each axisOperating Ambient Temperature 0°C to +55°C (+32°F to +131°F)Storage Temperature -40°C to +85°C (-40°F to +175°F)Humidity 5% to 95% relative humidity (non-condensing)Agency Certification • UL 1604

• C-UL C22.2 No. 213• Class I Division 2 Groups A,B,C,D • CE compliant for all applicable directives

Radiated and Conducted Emissions: EN 50081-2, Class AThe module has passed testing at the following levels:

• ESD Immunity (EN 1000-4-2) • 4 kV contact, 8 kV air, 4 kV indirect• Radiated Immunity (EN 1000-4-3) • 10V/m, 80 to 1000 MHz, 80% amplitude modulation, and 900 MHz keyed carrier• Fast Transient Burst (EN 1000-4-4) • Power supply: 2 kV, 5 kHz

• RS-232 and Ethernet: 1kV, 5 kHz• Surge Immunity (EN 1000-4-5) • Power Supply: 500V

• Ethernet (unshielded cable): 2 kV• RS-232 and Ethernet (shielded cable): 1 kV galvanic gun

• Conducted Immunity (EN 1000-4-6) • Power Supply: 10V, 0.15 to 80 MHz• RS-232 and Ethernet (unshielded cable): 3V, 0.15 to 80 MHz• RS-232 and Ethernet (shielded cable): 10V, 0.15 to 80 MHz

1 Publication 1761-UM006A-EN-P - February 2001

Page 86: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

A-2 Specifications

Dimensions

52.07 mm(2.05 in.)

27.7 mm(1.09 in.)

118 mm(4.64 in.)

107 mm(4.20 in.)

64.8 mm(2.55 in.)

Allow 15 mm (0.6 in.) clearance for DIN rail latch movement during installation and removal.

52.07 mm(2.05 in)

27.7 mm(1.09 in)

107 mm(4.20 in)

118 mm(4.64 in)

Allow 15 mm (0.6 in.) clearance for DIN rail latch movement during installation and removal.

Product Dimensions

Mounting Dimensions

Publication 1761-UM006A-EN-P - February 2001

Page 87: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

Appendix B

BOOTP Configuration Method (default)

BOOTP (Bootstrap protocol) is a low-level protocol that provides configuration information to other nodes on a TCP/IP network with DOS, Microsoft Windows, Windows NT, Windows 9x, VMS, and HP-UNIX platforms. BOOTP configuration files let you automatically assign IP addresses to the ENI. You can also set Subnet Masks and Gateway addresses using BOOTP.

To use BOOTP, a BOOTP Server must exist on the local Ethernet Subnet. The server is a computer that has BOOTP Server software installed and running which reads a text file containing network information for individual nodes on the network.

When the ENI receives a configuration message via BOOTP, it uses the data within the message to configure its TCP/IP parameters.

TIP If you do not have BOOTP Server capabilities on your network, and you want to dynamically configure the ENI, you can obtain the BOOTP software by contacting your local Rockwell Automation representative.

Table 2.1 TCP/IP Parameters

Function Format Notes

IP Address Integer This is a unique IP Address for the ENI.Format is aaa.bbb.ccc.ddd.Default is 000.000.000.000.

Subnet Mask optional(1)

(1) Depending upon whether your BOOTP server allows these optional fields to be included, you might not be able to configure these parameters using the BOOTPTAB file. If that is the case, configure them using the soft configuration method. See page 4-1 for more information. If you do not need to define a Subnet Mask or Gateway, simply ignore these parameters.

If not sent, the default mask is derived from the class of the IP address. See page 4-13 for more information on the subnet mask.

Gateway optional(1) Only needed if a Gateway is present on the Subnet. Default is 000.000.000.

Security Mask 1 Zero The default is no security mask 000.000.000.000. See page 4-13 for more information on the Security Mask.Security Mask 2

1 Publication 1761-UM006A-EN-P - February 2001

Page 88: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

B-2 BOOTP Configuration Method (default)

When BOOTP is enabled, the following events occur at power-up:

• The ENI broadcasts a BOOTP-request message containing its hardware address over the local network or subnet.

• The BOOTP server compares the hardware address with the addresses in its look-up table in the BOOTPTAB file.

• The BOOTP server sends a message back to the ENI with the IP address and other network information that corresponds to the hardware address it received.

With all hardware and IP addresses in one location, you can easily change IP addresses in the BOOTP configuration file if your network needs change.

The ENI allows the BOOTP request to be disabled by clearing the BOOTP Enable parameter. See Node 252 - BOOTP Configuration on page 4-15.

Using BOOTP The optional BOOTP Server file contains DOS-based and Windows-based BOOTP server utilities. Both provide BOOTP services for the ENI. Regardless of the platform you are using, you must:

• install the boot-server utility

• edit the boot-server configuration file

• run the boot-server utility

Install the BOOTP Server

To install the DOS BOOTP server:

1. Unzip the software to a known directory.

2. Change to that directory.

3. Type install , and press [Enter] .

4. The software is installed in C:\ABIC\BIN. If you are using DOS, put this directory in the path statement of your AUTOEXEC.BAT file.

IMPORTANT Do not use the BOOTP utility disk if you already have INTERCHANGE software installed. Instead, use the boot-server capabilities that came with your INTERCHANGE software.

Publication 1761-UM006A-EN-P - February 2001

Page 89: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

BOOTP Configuration Method (default) B-3

Edit the BOOTP Configuration File

The boot-server configuration file, BOOTPTAB, is located in the C:\ABIC\BIN directory. BOOTPTAB is an ASCII file that looks like:

#Legend:gw -- gateways#ha -- hardware address

#ht -- hardware type (1)

#ip -- host IP address#sm -- subnet mask

#vm -- BOOTP vendor extensions format (2)

#tc -- template host#Default string for each type of Ethernet clientdefaults5E: ht=1:vm=rfc1048#Entries for SLC 5/05 processors:sigma1: tc=defaults5E:ip=12.34.56.1:ha=0000BC1D1234sigma2: tc=defaults5E:ip=12.34.56.2:ha=0000BC1D5678sigma3: tc=defaults5E:ip=12.34.56.3:ha=0000BC1D9012

This file contains the information needed to boot the ENI.

You must edit the BOOTPTAB file to include the name, IP address, and hardware address for each ENI you want the server to boot. To edit this file:

1. Open the BOOTPTAB file using a text editor such as Notepad or Wordpad.

The file contains text that look like this:#Default string for each type of Ethernetclientdefaults5E: ht=1:vm=rfc1048

These are the default parameters for the ENI and must always precede the client lines in the BOOTPTAB file.

The file also contains a line that looks like this:#Entries for SLC 5/05 processors:sigma1:tc=defaults5E:ip=12.34.56.1:ha=0000BC1D1234

The “#” character defines the line as information, not configuration data.

(1) 1 = 10 MB Ethernet

(2) Use rfc 1048.

IMPORTANT Use the sigma1 line as the configuration template for the ENI.

Publication 1761-UM006A-EN-P - February 2001

Page 90: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

B-4 BOOTP Configuration Method (default)

2. Make one copy of the configuration template for each ENI in your system.

3. Edit each copy of the template as follows:

a. Replace “sigma1” with the name of the ENI. Use only letters and numbers; do not use underscores.

b. Replace “12.34.56.1” with the IP address to be assigned to the ENI.

c. Replace “ha=0000BC1D1234” with the ENI’s hardware address. Use only hexadecimal digits (0-9, A-F); do not use the hyphens that separate the numbers.

4. Save, close, and make a backup copy of this file.

Example BOOTPTAB File

In this example there are three SLC 5/05 processors and an HP 9000 programming terminal. The names and hardware addresses are device specific:

Device Name IP Address Hardware AddressSLC 5/05 sigma1 12.34.56.100 00-BC-1D-12-34SLC 5/05 sigma2 12.34.56.200 00-BC-1D-56-78SLC 5/05 sigma3 12.34.56.300 00-BC-1D-90-12

BOOTP Server

HP 9000HP UNIX Computer

802.3 Ethernet (TCP/IP)

sigma1SLC 5/05 Processor

sigma2SLC 5/05 Processor

sigma3SLC 5/05 Processor

Publication 1761-UM006A-EN-P - February 2001

Page 91: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

BOOTP Configuration Method (default) B-5

Based on this configuration, the BOOTPTAB file looks like:#Legend:gw -- gateways#ha -- hardware address

#ht -- hardware type (1)

#ip -- host IP address#sm -- subnet mask

#vm -- BOOTP vendor extensions format (2)

#tc -- template host#Default string for each type of Ethernet clientdefaults5E: ht=1:vm=rfc1048#Entries for SLC 5/05 processors:sigma1: tc=defaults5E:ip=12.34.56.1:ha=0000BC1D1234sigma2: tc=defaults5E:ip=12.34.56.2:ha=0000BC1D5678sigma3: tc=defaults5E:ip=12.34.56.3:ha=0000BC1D9012

Run the Boot Server Utility You can run either the DOS-based utility or the Windows-based BOOTP utility, but not both.

If you have BOOTP enabled and the message BOOTP response notreceived appears, check the cabling connections and the BOOTP server system.

Both utilities are located in the C:\ABIC\BIN directory and use the information contained in the BOOTPTAB file.

Be sure to place the BOOTPTAB file in the directory from which you are running the BOOTP utility. If this file is not found in that directory, the utility will try to find the file in the directory specified by the environment variable ABIC_CONFIG.

(1) 1 = 10 MB Ethernet(2) Use rfc 1048.

If you’re using this platform

then invoke this executable

from the See page

DOS-based DTLBOOTD.EXE DOS command line (specify optional parameters if necessary)

B-6

Windows DTLBOOTW.EXE Windows Program Manager B-6

Publication 1761-UM006A-EN-P - February 2001

Page 92: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

B-6 BOOTP Configuration Method (default)

Running the DOS-Based Utility

To run the boot-server utility, DTLBOOTD.EXE, follow these steps:

1. At the DOS prompt, type:

DTLBOOTD [-D] [-T <timeout>] [-B <numboots>] [-F <numfiles>] [configfile] [logfile]

Once you invoke the utility, it runs until the specified exit parameter is satisfied. Exit any time by pressing [Esc] .

2. Apply power to all ENIs. At power-up, each ENI broadcasts a BOOTP request (if BOOTP was enabled). The Ethernet boot server compares the hardware address with those listed in the BOOTPTAB file and responds by sending the corresponding IP address and other configuration data to the client via a BOOTP reply.

Running the Windows-Based Utility

To run the boot-server utility, DTLBOOTW.EXE, follow these steps:

1. Start Microsoft Windows®, if it is not already running.

2. Start the utility. It will run until you terminate it by closing the DTLBOOTW.EXEwindow and exiting from Windows.

3. Apply power to all ENIs. At power-up, each ENI broadcasts a BOOTP request. The Ethernet boot server compares the hardware address with those listed in the BOOTPTAB file and responds by sending the corresponding IP address and other configuration data to the client via a BOOTP reply.

Parameter Description

-D provide additional information for debug purposes.

-T <timeout> exit after <timeout> seconds of inactivity.

-B <numboots> exit after answering <numboots> number of boot requests.

-F <numfiles> exit after answering <numfiles> number of file requests.

configfile name of the boot server configuration file to use. The default configuration file is %ABIC_CONFIG%\BOOTPTAB.

logfile name of the log file to use. The default log file is %ABIC_CONFIG%\DTLBOOTD.LOG.

Publication 1761-UM006A-EN-P - February 2001

Page 93: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

Glossary

ASA (Advanced System Architecture)

Autobaud

A feature that allows a communications port to automatically synchronize to the device or network that it is attached to. This feature typically minimizes the amount of configuration required, and also makes is easier to replace devices.

Auto BCC/CRC

Sends a test message during autobaud to detect which Error Detecting setting to use, BCC or CRC. This will not occur for fixed baud rate settings. The ENI uses CRC for fixed baud rates.

Baud Rate

The speed of communication between devices on a network. All devices must communicate at the same baud rate. For example, the DH-485 network devices default to 19,200 baud.

CIP (Control and Information Protocol)

DNI (DeviceNet Network Interface)

Allen-Bradley catalog number 1761-NET-DNI. The DNI allows you to connect DF1 devices to DeviceNet networks.

DF1 Full-Duplex

DF1 is a standard (open) point-to-point communication protocol. Virtually all Allen-Bradley controllers (PLC-3, PLC-5, SLC, MicroLogix) that have an RS-232 communications port support DF1.

DF1 Protocol

A peer-to-peer link-layer protocol that combines features of ANSI X3.28-1976 specification subcategories D1 (data transparency) and F1 (two-way simultaneous transmission with embedded responses).

ENI (Ethernet Network Interface)

Allen-Bradley catalog number 1761-NET-ENI. The ENI allows you to connect DF1 devices to Ethernet networks.

Ethernet Network

A local area network with a baseband communication rate of 10M bits per second.

1 Publication 1761-UM006A-EN-P - February 2001

Page 94: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

Glossary 2

Full-duplex

A high-performance protocol that allows simultaneous two-way data transmission. For point-to-point applications only.

IP (Internet Protocol)

IP specifies the format of packets and the addressing scheme. Most networks combine IP with a higher-level protocol called Transport Control Protocol (TCP), which establishes a virtual connection between a destination and a source.

IP by itself is something like the postal system. It allows you to address a package and drop it in the system, but there's no direct link between you and the recipient. TCP/IP, on the other hand, establishes a connection between two hosts so that they can send messages back and forth for a period of time.

IP Address

A 32-bit address assigned to hosts that want to participate in a TCP/IP internet. IP addresses are the abstraction of physical hardware addresses, with a network and host partition which makes routing efficient.

NetLinx Services

The NetLinx services occur over the well-known port 0xAF12 and define a connection protocol that exists after a TCP/IP connection is established. It also defines a set of services and packet formats to support the protocol. Also implied by this protocol is that the end devices have implemented some portion of the ASA CIP addressing architecture.

Network

A series of stations (nodes) connected by some type of communication medium. A network may be made up of a single link or multiple links.

Node

Also called a station. An address or software location on the network.

MTA (Mail Transfer Agent)

The software function responsible for delivering outgoing mail to its final destination.

Publication 1761-UM006A-EN-P - February 2001

Page 95: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

Glossary 3

PCCC (Programmable Controller Communications Commands)

RS-232

An EIA standard that specifies electrical, mechanical, and functional characteristics for serial binary communication circuits.

Security Mask

The Security Mask, when configured, allows you to restrict incoming TCP/IP and/or UDP messages to have source IP addresses that are within some prescribed range. For example, if you wanted to restrict all message sources to be from within a company’s allocated IP address range, a Security Mask could be configured that would block any IP address outside that range.

SMTP (Simple Mail Transfer Protocol)

This protocol defines the interface and commands with the Mail Transfer Agent and defines how the ENI will deliver the outgoing mail.

Single-Hop/ Multi-Hop

Term that refers to how many “different” networks a message must traverse to reach its destination. For the ENI, a single-hop message is one whose source and destination nodes are both TCP/IP end points.

TCP (Transmission Control Protocol)

TCP is one of the main protocols in TCP/IP networks. Whereas the IP protocol deals only with packets, TCP enables two hosts to establish a connection and exchange streams of data. TCP guarantees delivery of data and also guarantees that packets will be delivered in the same order in which they were sent.

TCP/IP (Transmission Control Protocol/Internet Protocol)

The suite of communications protocols used to connect hosts on the Internet. TCP/IP uses several protocols, the two main ones being TCP and IP. TCP/IP is built into the UNIX operating system and is used by the Internet, making it the de facto standard for transmitting data over networks. Even network operating systems that have their own protocols, such as Netware, also support TCP/IP.

UCMM (Unconnected Message Manager)

The UCMM is an object defined in the CIP protocol. This object is responsible for handling connection requests and unconnected message traffic.

Publication 1761-UM006A-EN-P - February 2001

Page 96: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

Glossary 4

UTP (Unshielded Twisted Pair)

The type of cable used in 10BaseT systems.

Publication 1761-UM006A-EN-P - February 2001

Page 97: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

Index

AAllen-Bradley

contacting for assistance P-3support P-3

ASAdefinition G-1

Auto BCC/CRCdefinition G-1

Autobauddefinition G-1restrictions 4-16

BBaud Rate

configuring 4-15definition G-1

BOOTPedit configuration file B-3example B-4IP address B-4

BOOTP Configuration 4-15, B-1Boot-Server Host B-2

CCables 2-2, 2-6, 2-7, 2-8CE Mark 2-1CIP

definition G-1Common Techniques Used in this Manual P-2Compatibility 1-4Configuration 4-1

BOOTP 4-15controller messaging 4-5e-mail 6-2list of parameters 4-10via BOOTP B-1via message instruction 5-3

Configuration Utility 4-1Configuring

BOOTP host B-2Connections

allocation of Ethernet connections 3-1Ethernet switch 2-7

Contacting Allen-Bradley for Assistance P-3

DDF1 Full-Duplex

definition G-1messaging 5-1

DF1 Protocoldefault settings 1-3definition G-1

Dimensions A-2DNI

definition G-1DOS Host

for BOOTP B-2

EE-Mail Message Fields 6-4E-Mail Messages 6-1E-Mail Server 4-15E-Mail, sending a message 6-5EMC Directive 2-1ENI

configuration 4-1definition G-1functional overview 3-2LED indicators 1-2operating modes 1-4operation 3-1overview 1-1port identification 2-5product drawing 1-2

ENI Configuration Utility 4-1Error Codes 8-3Ethernet Connections 2-6Ethernet Hardware Address 4-16Ethernet Network

connections 1-5definition G-1ENI connection 1-1example 7-1non-Ethernet devices 1-1

Ethernet Port 1-2Example

BOOTP B-4using the CompactLogix serial port to connect to an

Ethernet network 7-1Explosion Hazard 2-2

Publication 1761-UM006A-EN-P - February 2001

Page 98: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

2 Index

FFault LED 1-2From String 4-11, 6-2Full-Duplex

definition G-2

GGrounding 2-5

HHardware Address 1-2, 4-16Hardware Features 1-2Hazardous Location 2-2

IInstallation and Wiring 2-1Integer Files 4-6IP

definition G-2IP Address

assigning 1-5definition G-2ENI write-on area 1-2

LLED Indicators 1-2LED Sequence at Power-Up 8-1LInk LED 1-2Low Voltage Directive 2-1

MManuals, Related P-2Memory Map 3-2Messaging 4-5, 5-1Mounting 2-3

dimensions A-2

MTAdefinition G-2

NNetlinx Services

definition G-2Network

definition G-2Node

definition G-2

OOperating Modes 1-4Operation 3-1

PPCCC

definition G-3Peer Connections 3-1Peer-to-Peer Messaging 5-1Power LED 1-2Power Supply Wiring 2-5Product Overview 1-1Program Upload/Download 3-2Publications, Related P-2Purpose of this Manual P-1

RRelated Publications P-2RS-232

cables 2-8connector 2-8default settings 1-3definition G-3ENI port 1-2pin assignments 2-8

RSLinx 3-2

Publication 1761-UM006A-EN-P - February 2001

Page 99: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

Index 3

SSafety Considerations 2-2Save/Reset 4-11Security Mask 4-13

definition G-3Single-Hop

definition G-3SMTP

definition G-3SMTP E-Mail Address 6-2Specifications A-1String Files 4-8Subnet Mask 4-13

TTCP

definition G-3TCP/IP

configuration 4-12definition G-3

Troubleshootingcontacting Allen-Bradley for assistance P-3maintain ENI connnections 2-7procedure 8-1

TX/RX LED 1-2

UUCMM

definition G-3Upload/Download 3-2UTP

definition G-4

WWeb Browser 1-5Wiring 2-1

Publication 1761-UM006A-EN-P - February 2001

Page 100: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

4 Index

Publication 1761-UM006A-EN-P - February 2001

Page 101: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download
Page 102: MicroLogix™ Ethernet Interface (ENI) · installation, Allen-Bradley does not assume responsibility or liability ... MicroLogix onto new or existing Ethernet networks and upload/download

Publication 1761-UM006A-EN-P - February 2001 2 PN XXXXXX-XXSupersedes Publication XXXX-X.X.X - Month Year © 2001 Rockwell International Corporation. Printed in the U.S.A.