MICROGRIDS DESIGNING AN IMPROVED GRID WWW.SWITCHGEARPOWER.COM

North America

Page 2: MICROGRIDS DESIGNING AN IMPROVED GRID · 2015. 3. 6. · STANLEY WORKS CONCEPTUAL MICROGRID LAYOUT A STANLEY ONELINE 04.14.14 JJ 001 1/ 1 B NAT. GAS TURB. 4.6 MW 34.5 kV AC, UNDERGROUND

`

Utility Grade Central generation including renewables 50-25’000 MW • Grid has evolved, due to policies, and is primarily

central generation.

HV grid a backbone for long distance bulk power transmission at 110-1200 kV (AC or DC) • Costs and social resistance has increased on the build

out of transmission lines.

MV grid for a local power distribution at 6-69 kV Distributed generation including renewables 1-25 MW • Recent storms and unforeseen events have uncovered

serious weaknesses in our central/transmission/distribution grid.

LV grid for the “last mile” power distribution at 110-1000 V Sub-utility generation including renewables 0.005-1 MW Roof top solar, DER’s causing problems to grid operators.

Page 3: MICROGRIDS DESIGNING AN IMPROVED GRID · 2015. 3. 6. · STANLEY WORKS CONCEPTUAL MICROGRID LAYOUT A STANLEY ONELINE 04.14.14 JJ 001 1/ 1 B NAT. GAS TURB. 4.6 MW 34.5 kV AC, UNDERGROUND

IS THIS REAL AND PRACTICAL?

A Microgrid as Explained by Steve Jobs

New Campus

Apple AC2

Steve Jobs explains

the campus design

Grid is backup to Apple Power Plant

Page 4: MICROGRIDS DESIGNING AN IMPROVED GRID · 2015. 3. 6. · STANLEY WORKS CONCEPTUAL MICROGRID LAYOUT A STANLEY ONELINE 04.14.14 JJ 001 1/ 1 B NAT. GAS TURB. 4.6 MW 34.5 kV AC, UNDERGROUND

What’s a microgrid?

An integrated energy system consisting of interconnected

loads and distributed energy resources which can operate either

connected to or “islanded” from the existing utility power grid.

Page 5: MICROGRIDS DESIGNING AN IMPROVED GRID · 2015. 3. 6. · STANLEY WORKS CONCEPTUAL MICROGRID LAYOUT A STANLEY ONELINE 04.14.14 JJ 001 1/ 1 B NAT. GAS TURB. 4.6 MW 34.5 kV AC, UNDERGROUND

Power generation near consumption

Improved performance of Renewable Power

Byproduct (steam/hot water) of energy yields greater potential for efficiency and alternate services

Byproduct of production as well- biomass, biogas, etc.

Optimization of power

Production close to consumption = tighter coordination and repetition

Utility Grid support

Sell power back to grid due to financial optimization

Volt/Var

Voltage and frequency

Reliable Industrial Automation of Generation

Improve Reliability (truly redundant approach)

Grid is back-up

Power Automation improves performance

Highly reliable systems used in much more extreme cases (glass, steel, etc)

MV Distribution

Improved power backbone

Smaller switchgear to point of consumption

Better use of Capital

Eliminate:

Transfer Switches

Paralleling Gear

Limited UPS installation (IT only)

Government Incentives

Page 6: MICROGRIDS DESIGNING AN IMPROVED GRID · 2015. 3. 6. · STANLEY WORKS CONCEPTUAL MICROGRID LAYOUT A STANLEY ONELINE 04.14.14 JJ 001 1/ 1 B NAT. GAS TURB. 4.6 MW 34.5 kV AC, UNDERGROUND
Page 7: MICROGRIDS DESIGNING AN IMPROVED GRID · 2015. 3. 6. · STANLEY WORKS CONCEPTUAL MICROGRID LAYOUT A STANLEY ONELINE 04.14.14 JJ 001 1/ 1 B NAT. GAS TURB. 4.6 MW 34.5 kV AC, UNDERGROUND

Utilities and Consumers Different Evolution Path

Source: Greentech Media Research

Page 8: MICROGRIDS DESIGNING AN IMPROVED GRID · 2015. 3. 6. · STANLEY WORKS CONCEPTUAL MICROGRID LAYOUT A STANLEY ONELINE 04.14.14 JJ 001 1/ 1 B NAT. GAS TURB. 4.6 MW 34.5 kV AC, UNDERGROUND

i. Concept

i. Conceptual business case analysis and technical services

ii. Engineering Services

i. Includes: Interconnect, protection and control, load flow, static and dynamic modeling, etc.

iii. Control Platform

i. Must be real time automation – hardware/firmware

ii. Software for optimization

iv. Grid Stabilization Solution

i. Important for seamless power

v. Integration Services

vi. 24/7 Monitoring

Page 9: MICROGRIDS DESIGNING AN IMPROVED GRID · 2015. 3. 6. · STANLEY WORKS CONCEPTUAL MICROGRID LAYOUT A STANLEY ONELINE 04.14.14 JJ 001 1/ 1 B NAT. GAS TURB. 4.6 MW 34.5 kV AC, UNDERGROUND

14MW PV Power Plant

TITLE:

CLIENT: Internal

DRAWING NO.:

FILE NAME: For internal use

REV DESCRIPTION DRN DATE CKD

SHEET NO.

TYPICAL MICROGRID CRITICAL POWER

A MB Layout bl 06.15.13 BL

0011/1

GEN 3 4MW

B

BESS 12MW

Energy Storage SystemGrid Stabilization

GEN 2 2MW

GEN 1 4MW

Feeder

Utility

Feeder

Feeder

Feeder

Utility

MV

Pow

er Bus

CT

MG Controller

MG Controller

MG Controller

MG Controller

MG Controller

MG Controller

MG Controller CT

Feeder Controller

Feeder Controller

Feeder Controller

Feeder Controller

LV G

en B

us

Server Utility

MG Controller

LVMV

Page 10: MICROGRIDS DESIGNING AN IMPROVED GRID · 2015. 3. 6. · STANLEY WORKS CONCEPTUAL MICROGRID LAYOUT A STANLEY ONELINE 04.14.14 JJ 001 1/ 1 B NAT. GAS TURB. 4.6 MW 34.5 kV AC, UNDERGROUND

60

60.05

59.95

f [Hz]

t [sec]

Absorb power

Supply power

Stored energy [MWh]

Stored energy [MWh]

Frequency regulation Load leveling

10

5

Load [MW]

t [hrs]

Supply power

Absorb power

Grid

ESS

G

r

i

d

S

t

a

b

i

l

i

z

a

t

i

o

n

B

a

t

t

e

r

y

E

n

e

r

g

y

S

t

o

r

a

g

e

Page 11: MICROGRIDS DESIGNING AN IMPROVED GRID · 2015. 3. 6. · STANLEY WORKS CONCEPTUAL MICROGRID LAYOUT A STANLEY ONELINE 04.14.14 JJ 001 1/ 1 B NAT. GAS TURB. 4.6 MW 34.5 kV AC, UNDERGROUND

Inherent volatility of renewable energy can compromise grid stability

The renewable energy integration solution must address requirements traditionally fulfilled by diesel generation (base load)

Frequency and voltage control

Sufficient spinning reserve

Sufficient active and reactive power supply

Peak shaving and load levelling

Load sharing between generators

Fault current provision

Renewable energy generation capacity should be sized to maximize ROI and fuel savings

Page 12: MICROGRIDS DESIGNING AN IMPROVED GRID · 2015. 3. 6. · STANLEY WORKS CONCEPTUAL MICROGRID LAYOUT A STANLEY ONELINE 04.14.14 JJ 001 1/ 1 B NAT. GAS TURB. 4.6 MW 34.5 kV AC, UNDERGROUND

Grid Stabilization System

Page 13: MICROGRIDS DESIGNING AN IMPROVED GRID · 2015. 3. 6. · STANLEY WORKS CONCEPTUAL MICROGRID LAYOUT A STANLEY ONELINE 04.14.14 JJ 001 1/ 1 B NAT. GAS TURB. 4.6 MW 34.5 kV AC, UNDERGROUND

Spinning Reserve / Step Load / Real Case

60

55

65

Grid Stabilization System

Page 14: MICROGRIDS DESIGNING AN IMPROVED GRID · 2015. 3. 6. · STANLEY WORKS CONCEPTUAL MICROGRID LAYOUT A STANLEY ONELINE 04.14.14 JJ 001 1/ 1 B NAT. GAS TURB. 4.6 MW 34.5 kV AC, UNDERGROUND

850 kW load steps – Test of Reaction

©

ABB

Gro

up

850kW ON 850kW OFF

60hz

59hz

62hz

61hz

Page 15: MICROGRIDS DESIGNING AN IMPROVED GRID · 2015. 3. 6. · STANLEY WORKS CONCEPTUAL MICROGRID LAYOUT A STANLEY ONELINE 04.14.14 JJ 001 1/ 1 B NAT. GAS TURB. 4.6 MW 34.5 kV AC, UNDERGROUND

Features:

High power; low energy

High Duty Cycle

Grid Stabilizing

Scalable & Modular

Frequency Control

Voltage Control

Fault Ride Through

Spinning Reserve (Virtual

Generator)

Step Load Capabilities

Voltage reference for renewables

only mode

Power

AC/DC

Grid

480V 60Hz

Reactive

Real

Power

Real

Power

G

• Battery

• Capacitor

• Flywheel

Page 16: MICROGRIDS DESIGNING AN IMPROVED GRID · 2015. 3. 6. · STANLEY WORKS CONCEPTUAL MICROGRID LAYOUT A STANLEY ONELINE 04.14.14 JJ 001 1/ 1 B NAT. GAS TURB. 4.6 MW 34.5 kV AC, UNDERGROUND

Remote

control

center

Office

Local

control

center

Plant floor

Power

grid

Embedded software

From protection logic in protection relays to

interactive functionality in measurement devices

and robot controllers, embedded software is a key

component for most products and systems.

Software systems

Used to control and coordinate operational

processes across industry sectors, from chemical

plants, building management, IT, to power grids.

Enterprise software

Bridge the divide between operational data and

business intelligence, delivering actionable

information

Plant Optimization

Enhancing operations and improving performance

Page 17: MICROGRIDS DESIGNING AN IMPROVED GRID · 2015. 3. 6. · STANLEY WORKS CONCEPTUAL MICROGRID LAYOUT A STANLEY ONELINE 04.14.14 JJ 001 1/ 1 B NAT. GAS TURB. 4.6 MW 34.5 kV AC, UNDERGROUND

Data Center Campus

G G G G

480 V AC

Grid Stabilization

NAT. GAS TURB.4.6 MW

STEAM TURB2 MW

DIESEL GEN1.5 MW

TITLE:

CLIENT: Internal

DRAWING NO.:

FILE NAME: For internal use

REV DESCRIPTION DRN DATE CKD

SHEET NO.

STANLEY WORKS CONCEPTUAL MICROGRID LAYOUT

A STANLEY ONELINE 04.14.14 JJ

0011/1

B

NAT. GAS TURB.4.6 MW

34.5 kV AC, UNDERGROUND DISTRIBUTION

CL&P 690TO BLACKROCK

SUBSTATION

69

kV

69

kV

TO RAINBOW DAM

SOLAR PV FARM

A

B

DATA CENTER LOAD 1

DATA CENTER LOAD 2

Feeder ControllerFeeder Controller

MG Controller

MG Controller MG Controller

MG Controller MG Controller

MG Controller

MG ControllerMG Controller

Server