mfr 11 - protection relay - precision controls · mfr 11 manual © woodward governor company...

63
Manual MFR 11 - Protection Relay - Version 3.xxxx © All Rights reserved. Subject to technical modifications. Version 37140 2003-03-26 37140_NEW_Manual MFR11.doc Woodward Governor Company Leonhard-Reglerbau GmbH Handwerkstrasse 29 70565 Stuttgart - Germany Tel: +49 (0) 711 789 54-0 Fax: +49 (0) 711 789 54-100 eMail: [email protected] 37140

Upload: vuongdien

Post on 09-Apr-2018

215 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

Manual

MFR 11

- Protection Relay -

Version 3.xxxx

© All Rights reserved. Subject to technical modifications. Version 37140

2003-03-26 37140_NEW_Manual MFR11.doc

Woodward Governor Company Leonhard-Reglerbau GmbH Handwerkstrasse 29 70565 Stuttgart - Germany

Tel: +49 (0) 711 789 54-0 Fax: +49 (0) 711 789 54-100 eMail: [email protected]

37140

Page 2: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140

Table of Contents Page

1 INTRODUCTION.................................................................................................................................................4 1.1 Range of functions .........................................................................................................................................................4

1.1.1 Measurement values...............................................................................................................................................4 1.1.2 General functions....................................................................................................................................................4 1.1.3 Protective functions.................................................................................................................................................5 1.1.4 Packages ................................................................................................................................................................5

1.2 Safety notes for users ....................................................................................................................................................6 1.3 Rating ............................................................................................................................................................................7

1.3.1 Power supply (standard / option N) .....................................................................................................................7 1.3.2 Measuring inputs.....................................................................................................................................................7 1.3.3 Auxiliary and control inputs .....................................................................................................................................9 1.3.4 Auxiliary and control outputs .................................................................................................................................10 1.3.5 Interface (option S)..............................................................................................................................................12

2 DESCRIPTION OF FUNCTIONS......................................................................................................................13 2.1 Control inputs...............................................................................................................................................................13 2.2 Control outputs ............................................................................................................................................................14 2.3 Alarm ...........................................................................................................................................................................14

2.3.1 Alarm message.....................................................................................................................................................14 2.3.2 Acknowledge alarms.............................................................................................................................................14

3 DISPLAY AND OPERATING COMPONENTS.................................................................................................15 3.1 Front foil.......................................................................................................................................................................15 3.2 LEDs............................................................................................................................................................................15 3.3 Push-buttons................................................................................................................................................................16 3.4 Display.........................................................................................................................................................................17

3.4.1 Automatic mode (first line of the display: measuring values)..........................................................................17 3.4.2 Automatic mode (second line of the display: measuring value) .....................................................................17 3.4.3 Automatic mode (second line of the display: alarm indication).......................................................................18

4 CONFIGURATION MASKS (ENTERING PARAMETERS)..............................................................................19 4.1 Access to configuration ................................................................................................................................................20

4.1.1 Sealing function (up to version 1.9xx)................................................................................................................20 4.1.2 Password (from Version 2.0xx / 3.0xx) .............................................................................................................22 4.1.3 Change passwords (from v 2.0xx/3.0xx)............................................................................................................23

4.2 Configure basic settings...............................................................................................................................................24 4.2.1 Direct configuration (from version 3.0xx) ...........................................................................................................24 4.2.2 Voltage Measuring ................................................................................................................................................25 4.2.3 Configuration of the voltage transformer ...............................................................................................................25 4.2.4 Configuration of the rated values (option Yc) ......................................................................................................26 4.2.5 Configuration of the Type of Monitoring ................................................................................................................26

4.3 Configuration of control functions.................................................................................................................................27 4.3.1 Control function for the synchronization (option Yc) ............................................................................................27

4.4 Configuration of the protective device ..........................................................................................................................29 4.4.1 Overvoltage monitoring (option U).......................................................................................................................29 4.4.2 Undervoltage monitoring (option U).....................................................................................................................30 4.4.3 Zero voltage monitoring (option Un)....................................................................................................................31 4.4.4 Asymmetry monitoring (option U) ........................................................................................................................32 4.4.5 Overfrequency Monitoring (option U)...................................................................................................................33 4.4.6 Underfrequency monitoring (option U).................................................................................................................34 4.4.7 Phase/vector shift monitoring (option V)..............................................................................................................35 4.4.8 df/dt monitoring (option D)...................................................................................................................................36 4.4.9 Non-directional ground fault monitoring (option Iv) ..............................................................................................36

Page 3: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

© Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 MFR 11 Manual 37140 Page 3/63

4.5 Configuration of the relay .............................................................................................................................................38 4.5.1 Auto-clearing relays ..............................................................................................................................................39 4.5.2 Auto-clearing display.............................................................................................................................................40 4.5.3 Change relay assignment (relay manager; standard and option R)................................................................41

4.6 Analog outputs (options A1/2/3/4/6/8) ......................................................................................................................43 4.7 Interface (option Su/Sb).............................................................................................................................................44

4.7.1 Masks for protocol DK3964 (option Su)...............................................................................................................44 4.7.2 Masks for protocol Profibus DP slave (option Su) ...............................................................................................44 4.7.3 Masks for protocol MOD bus RTU slave (option Su/Sb) .....................................................................................44 4.7.4 Masks for protocol CAN bus (option Su/Sb) .......................................................................................................45 4.7.5 General masks for all types of interfaces (option Sb) ..........................................................................................45

5 COMMISSIONING ............................................................................................................................................46 6 APPENDIX........................................................................................................................................................48

6.1 Interface telegram........................................................................................................................................................48 6.1.1 Description of the data format ...............................................................................................................................50 6.1.2 Frame date for the interfaces ................................................................................................................................51

6.2 Accuracy......................................................................................................................................................................53 6.3 Technical data .............................................................................................................................................................54 6.4 Dimensions ..................................................................................................................................................................55 6.5 Wiring diagram.............................................................................................................................................................56

6.5.1 Package models ...................................................................................................................................................56 6.5.2 Optional models, 100 Vac and 400 Vac ................................................................................................................57 6.5.3 Optional models, 690 Vac .....................................................................................................................................58

7 LIST OF PARAMETERS ..................................................................................................................................59 7.1 List of the adjustment ranges for the analog outputs....................................................................................................63

NOTE

This manual has been developed are intended for a unit fitted with all available options. Inputs/outputs, functions, configuration screens and other details described, which do not exist on your unit may be ignored.

ATTENTION!

The present manual have been prepared to enable the installation and commissioning of the device. On account of the large variety of parameter settings, it is not possible to cover every possible combination. The manual are therefore only a guide. In case of incorrect entries or a total loss of functions, the default settings can be taken from the enclosed list of parameters.

Page 4: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page4/63 37140

1 Introduction

1.1 Range of functions

Depending on the model, the device is equipped with the following functions:

1.1.1 Measurement values

Voltage Three-phase r.m.s. value measurement of the star and the line-to-line voltages. (Op-tion Yc: Single-phase r.m.s.-value measurement of the synchronizing voltage UL1L2.) This device can be delivered with the following measuring voltage ranges (rated volt-ages). Please indicated the voltage required when ordering: • 57/100 (110) V AC • 230 V/400 V • 400 V/690 V

Frequency Time measurement from the digitally filtered measuring voltages. Three-phase

measurement of the frequency if all voltages exceed the nominal value (100/400/690 V AC) by 15 %. This guarantees a very fast and very exact measure-ment of the frequency. However the frequency is still measured correctly even if volt-age is only applied to one phase.

1.1.2 General functions

Function Option • A maximum of 7 relay outputs for free configuration (5 change-over contacts, 2

make contacts) R • 1 relay output (make contact) as readiness for operation relay • Discrete input for blocking or acknowledgement (not available for the 690 V-

Version) • Sealing function (Software, up to version 1.9xx) • Password system (Software, from version 2.0xx) • 8 analog outputs max., +/-20 mA or -10..10 V A1..A8 • Interfaces Su/Sb/Sf interface • Long range voltage input (75..265 V AC or 90..300 V DC) N

Page 5: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

© Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 MFR 11 Manual 37140 Page 5/63

1.1.3 Protective functions

• Three-phase over-/undervoltage protection (2stepped) U>, U< U • Zero voltage monitoring U ≠ 0 Un • Voltage unbalance protection Uas> U • Two-phase over-/underfrequency protection (2stepped) f>, f< U • Vector shift monitoring dϕ/dt V • df/dt monitoring df/dt D • Ground fault monitoring by displacement voltage measurement UE>• Synch-Check-Function (not available for 690 V-Version) Yc

1.1.4 Packages

Based on the MFR 11 you may order the following packages : MFR 11/MP

Mains protection with the option U

MFR 11/VDEW Mains protection with the options U/V

MFR 11/G59 Mains protection with the options U/V/D/R

MFR 11/G59N Mains protection with the options U/V/D/R/N

MFR 11/SC Synch-Check and zero-voltage monitoring with the options Un/Yc

Page 6: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page6/63 37140

1.2 Safety notes for users

The present documentation includes the information required for the correct use of the product described. It is intended to be read by qualified staff.

Danger warnings The following notes are intended for your personal safety, but also serve as safety notes to avoid damage of the product described or devices connected to the product. Safety notes and warnings intended to prevent any danger to the life and health of users or maintenance personnel and to avoid any damage will be identified in this documentation by means of the symbols and terms listed below. Within the frame-work of this documentation, the signals and terms which are used have the following meaning:

DANGER!!!

The DANGER symbol draws your attention to dangers while the description indicates how to handle and/or avoid such hazards. Any non-observance may cause fatal or serious injuries as well as considerable damage to property.

WARNING!

If the warnings are not observed, the unit and any devices attached to it may be destroyed. Please take into account appropriate precautions.

ATTENTION!

This symbol points to important notes concerning the mounting, installation and connection of the device. These note should absolutely be observed when connecting the unit.

NOTE

References to other notes and supplements as well as tables and lists are identified by the "I" symbol. Most of the referenced sections are included in the Appendix.

Intended use The device must only be used for those applications which are described in these manual. The prerequisite for a proper and safe operation of the product is correct transportation, storage, and installation as well as careful operation and mainte-nance.

Page 7: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

© Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 MFR 11 Manual 37140 Page 7/63

1.3 Rating

WARNING!

A circuit breaker must be provided near to the device and in a position easily accessible to the operator. This must also bear a sign identifying it as an isolating switch for the unit.

NOTE

Inductors connected (e. g. inductors of an open circuit or undervoltage release, or of contactor relays or power contactors) have to be interconnected with an appropriate interference suppressor.

1.3.1 Power supply (standard / option N)

75..265 V AC bzw. 90..300 V DC

18..30 V DC

BA

78

Wide-range power supply (option N)

- / N+ / L

0 V18..30 V DC

Standard

Power supply

Power supply

Terminal Description Amax

Standard 8 18..30 V DC, 10 W 2.5 mm² 7 0 V reference point 2.5 mm²

up to version 1.xxx/2.xxx - wide range power supply unit (option N) A 17 75..265 V AC, max. 10 VA or 90..300 V DC, max. 10 W 2.5 mm² B 18 Reference potential 2.5 mm²

from Version 3.xxx – wide range power supply unit (option N) A 8 75..265 V AC, max. 10 VA or 90..300 V DC, max. 10 W 2.5 mm² B 7 Reference potential 2.5 mm²

1.3.2 Measuring inputs

a.) Voltage measuring inputs

• 100/400 V-Version

Measuringvoltage

L3L2L1

N

G

12

34

L3L2L1

N

Terminal Measurement Description Amax 1 Measuring voltage L1 2.5 mm² 2 Measuring voltage L2 2.5 mm² 3 Measuring voltage L3 2.5 mm² 4

400 V direct or via ../100 V

measurement transducer Neutral point of the 3-phase system/transformer 2.5 mm²

Page 8: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page8/63 37140

• 690 V-Version

Measuringvoltage

L3L2L1

N

G

34

56

L3

L2

N

21 L1

Terminal Measurement Description Amax 1 Measuring voltage L1 2.5 mm² 2 2.5 mm² 3 Measuring voltage L2 2.5 mm² 4 2.5 mm² 5 Measuring voltage L3 2.5 mm² 6

690 V direct

Neutral point of the 3-phase system/transformer 2.5 mm²

b.) Synchronizing voltage (option Yc - option Iv not available)

NOTE

Option Yc cannot be used for the 690 V-devices.

L3L2L1

N

G

L3L2L1

Synchronizingvoltage

CB

7071

72

a)

a) not measured

Terminal Measurement Description Amax 70 Synchronizing voltage L1 2.5 mm² 71 Synchronizing voltage L2 2.5 mm² 72

400 V direct or via ../100 V

meas.transd. Synchronizing voltage L3 (not measured) 2.5 mm²

Page 9: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

© Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 MFR 11 Manual 37140 Page 9/63

c.) Displacement voltage (option Iv)

v

WARNING!

If voltage transducers are higher than ../110 V AC, voltage divider should be used.

L2L3

L1L1 G3~

G3~

L2L3

71 NUe70

72

Displacementvoltage

Rb Rb

e-n-winding Zero point transformer

Rb = Loading resistor

Terminal Measurement Description Amax Zero point transformer

70 Ue (displacement voltage) 2.5 mm² 71 N 2.5 mm² 72

via zero point transformer

not assigned 2.5 mm² Open-circuit e-n-winding

70 Ue (displacement voltage) 2.5 mm² 71 N 2.5 mm² 72

via e-n-winding not assigned 2.5 mm²

1.3.3 Auxiliary and control inputs

a.) Discrete inputs

NOTE

The subsequent input "Blocking of watchdog functions / remote acknowledgment" does not exist in version 690 V (see chapter 2.1 "Control inputs" on page 13.)

Signal device

Digital input

18..250 V (AC/DC)

AB

Terminal Associated

common Description (according to DIN 40 719 Part 3, 5.8.3)

Amax

A B 5 6 Blocking of watchdog functions / remote acknowl-

edgment 2.5 mm²

Page 10: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page10/63 37140

1.3.4 Auxiliary and control outputs

a.) Relay outputs (standard / option R)

• Relay (general)

AB

Relay output

Relay outputexternal device

external device

external device

CD

E

max. 250 V AC

Description Amax Make-contact

Root Closing A B 9 10 Relay 1 2.5 mm²

31 32 Relay 8 Option R 2.5 mm² Change-over contact closing Root Opening

C D E 11 12 13 Relay 2 2.5 mm² 14 15 16 Relay 3 2.5 mm² 19 20 21 Relay 4 Option R 2.5 mm² 22 23 24 Relay 5 Option R 2.5 mm² 25 26 27 Relay 6 Option R 2.5 mm² 28 29 30 Relay 7 Option R 2.5 mm²

Page 11: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

© Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 MFR 11 Manual 37140 Page 11/63

b.) Analog outputs (option A1..A8)

Possible combinations The analog outputs and the interface can be combined as follows:

Option S A1- A4 A6-A8 • • - simultaneous

use of ... - - •

NOTE

All 20 mA-outputs are metallically separated each; the 10 V-outputs 1-4 and 5-8 are metallically separated once.

Analog outputs

I

D 0 V

C

AU

AB 0 V

A

Analog output

Analog output

Description Amax 0..20 / 4..20 / -20..+20 mA

IA 0 V A B 51 50 Analog output 1 Option A2/3/6 1.5 mm² 53 52 Analog output 2 Option A3/6 1.5 mm² 55 54 Analog output 3 Option A3/6 1.5 mm² 82 81 Analog output 4 Option A6 1.5 mm² 84 83 Analog output 5 Option A6 1.5 mm² 87 86 Analog output 6 Option A6 1.5 mm²

0..10 / -10..+10 V UA 0 V C D 51 Analog output 1 Option A1/4/8 1.5 mm² 52 50 Analog output 2 Option A4/8 1.5 mm² 54 Analog output 3 Option A4/8 1.5 mm² 55 53 Analog output 4 Option A4/8 1.5 mm² 82 Analog output 5 Option A8 1.5 mm² 83 81 Analog output 6 Option A8 1.5 mm² 85 Analog output 7 Option A8 1.5 mm² 86 84 Analog output 8 Option A8 1.5 mm²

Page 12: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page12/63 37140

1.3.5 Interface (option S)

ACA B D E B DC E A B C D E CEA B C D A B D E

GN

D

Inte

rface

RS4

22 in

terfa

ce

Inte

rface

RS2

32 in

terfa

ce

A (n

on-in

verte

d)

B (in

verte

d)

GN

D

RTSRxD

CTS TxD

Inte

rface

RS4

85 in

terfa

ceM

OD

bus

RTU

sla

ve

Z (in

verte

d)

Y (n

on-in

verte

d)

B (in

verte

d)

A (n

on-in

verte

d)

GN

D

Inte

rface

CAN

bus

Inte

rface

TTY

inte

rface

The

trans

mitt

er d

rives

the

curre

nt.

RxD

+

RxD

-

TxD

+

TxD

-

Term

inat

ion

NC

GN

D

CAN

-H

CAN

-L

DA B C

Inte

rface

Prof

i bus

DP

Scre

en

A-Li

ne

GN

D

+5 V

E F

B-Li

ne

RTS

Terminal Description

A (X1) B (X2) C (X3) D (X4) E (X5) RxD RTS GND CTS TxD RS232

A B GND Z Y RS422 GND B A RS485, MOD bus RTU slave

RxD- RxD+ NC TxD- TxD+ TTY (transmitter drives current) GND CAN-H CAN-L CAN bus

A (X1) B (X2) C (X3) D (X4) E (X5) F (X6) Shield +5 V GND A-Line B-Line RTS Profi-Bus DP (use the file

LEON00D9.GSD )

NOTE

Please note that the CAN bus must be terminated with an impedance which corresponds to the wave impedance of the cable (e.g. 120 Ohm).

NOTE

In order to carry configuration out via the configuration plug (direct configuration), you require a direct configuration cable (order code "DPC"), the LeoPC 1 program (supplied with the cable) and the corresponding configuration files. Please consult the online help installed when the program is installed for a description of the LeoPC 1 PC program and its setup.

Page 13: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

© Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 MFR 11 Manual 37140 Page 13/63

2 Description of functions

2.1 Control inputs

NOTE

The subsequent input "Blocking of watchdog functions / remote acknowledgment" does not exist in version 690 V.

Blocking protective device Remote acknowledgement Terminal 5/6

Due to a non-reset high-signal at the discrete input the release of various protection devices may be blocked. This may be useful for instance if the device is used as a generator protection device. Thus, tripping can be avoided for messages ( such as undervoltage or underfrequency) which are permanently active during a machine standstill. If blocking is not required, the discrete input should be permanently inter-connected with zero potential. The following functions can not be blocked with this discrete input : • Overvoltage • Overfrequency • Zero voltage • Ground fault monitor

External acknowledgement of the

relays via the discrete input "Blocking of watchdog functions / remote ac-

knowledgment".

External Clearing OFF

If you don't want the device to reset the relays automatically as soon as the alarm is no longer present, you must first set the function "Auto-clearing relay" to "OFF" (see chapter 4.5.1 "Auto-clearing relay" on page 39).

OFF ..........Alarms which cannot be blocked are no longer reset automatically if the tripping alarm is no longer present. Press the button "Clear" to re-set the relays.

ON ............All alarms which are present are reset if a rising edge is detected at the blocking input. (The discrete input "Blocking of watchdog functions / remote acknowledgment" must be reset from "0" to "1".) Alarms which cannot be blocked are only reset if the alarm is no longer pre-sent.

External acknowledgement of the

alarm messages via the discrete input "Blocking protective device / remote acknowledgement".

External Clearing OFF

If you want the device to automatically reset the relays as soon as the alarm is no longer present, but not delete the messages on the display, you must first set the functions "Auto-clearing relay" to "ON" and "Auto-clearing message" to "OFF" (see chapter 4.5.1 "Auto-clearing relay" on page 39).

OFF ..........To reset the messages on the display, press the button "Clear". ON ............All display messages which are present are reset if a rising edge is

detected at the blocking input. (The discrete input "Blocking of watch-dog functions / remote acknowledgment" must be set from "0" to "1" .) Alarms which cannot be blocked are only reset if the alarm is no longer present.

Page 14: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page14/63 37140

2.2 Control outputs

NOTE

Please heed to the description of the relay manager in chapter 4.5.3 "Change relay assignment (relay manager; standard and option R)" from page 41.

Relay 2 Terminal 11-13

Output relay (version: Change-over contact) This relay is managed by the "relay manager" .

Relay 3 Terminal 14-16

Output relay (version: Change-over contact) This relay is managed by the "relay manager". If the option Yc is available, the mes-sage "networks are synchronous" is displayed.

Option R relay 47 Terminal 19-30

Output relay (version: Change-over contact) - Only if the option R is available. These relays are controlled by the relay manager.

Option R Relay 8 Terminal 31/32

Output relay (version: make contact) - only, if option R is available. This relay is managed by the "relay manager" . If Option R is available in addition to option Yc, the message "networks are synchronous" is displayed. The relay 3 is also managed by the relay manager.

2.3 Alarm

2.3.1 Alarm message

Type of alarm yyyyyyyyyyyyyyyy

Overvoltage, level 1 / level 2 Option U Overvoltage.1 / 2 Undervoltage, level 1 / level 2 Option U Undervoltage.1 / 2 Asymmetry Option U Asymmetry Overfrequency, level 1 / level 2 Option U Overfrequency. 1 / 2 Underfrequency, level 1 / level 2 Option U Underfrequency. 1 / 2Phase/vector shift Option V Phase shift df/dt Option D error df line-to-ground fault Ue, level 1 Option Iv earth-fault Ue Line-to-ground fault Ue, level 2 Option Iv earth-fault. Ue>>

2.3.2 Acknowledge alarms

An alarm is signaled with the LED "Alarm". Press the button "Clear" to acknowledge the alarms which are present. The following differences are made: The alarm ... ... is still present ................As long as the alarm is still present, it cannot be ac-

knowledged. This is signaled by the blinking LED "Alarm" on the front side.

... is no longer present ......As soon as the alarm has been eliminated, the blinking

light of the LED "Alarm" becomes a steady light. If the mask "auto acknowledge messages" is set to "ON", the LED is extinguished after the resetting time. If the mask "auto acknowledge messages" is set to "OFF", the LED is only extinguished after the button "Clear" is pressed.

Page 15: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

© Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 MFR 11 Manual 37140 Page 15/63

3 Display and operating components

3.1 Front foil

The pressure-sensitive membrane of the front panel consists of a plastic coating. All keys have been designed as touch-sensitive membrane switch elements. The display is a LC display, consisting of 2 × 16 characters, with indirect green illumination. The contrast of the display can be infinitely adjusted via a rotary potentiometer positioned on the left.

[ ]

Hz Reversible Display

L1 / L12 L2 / L23 L3 / L31

Operating

Display Menu

Digit Cursor

Clear

Alarm

MFR 1Converting, Controlling, Monitoring

Select

14

1/2

131243

5

________________________Light-emitting diodes ___________________________________ buttons 1 "Star" .......................... Display of the star voltages 12 "Display↓" .................................Advance message 2 "Delta"........................Display of the delta voltages 12 "Select" ...................................... Confirm selection 1 "Operation" .................................. Automatic mode 13 "Menu" ............................................... Select menu 4 "Alarm"......................................................... Alarm 13 "Digit↑"............................................Increment digit

14 "Clear" ...................Acknowledge alarm messages ____________________________________ Display 14 "Cursor→"........................ One position to the right 5 "LC-Display"..........................................LC-Display

3.2 LEDs

1 ........................................ LED "Star"

Indication of the star voltages Color "YELLOW"

If this LED lightens, the values indicated on the display are the star voltages (wire-zero).

2 ........................................ LED "Delta"

Indication of the delta voltages Color "YELLOW"

If this LED lightens, the values indicated on the display are the delta voltages (wire-wire).

3 ........................................ LED "Operation"

Operation Color "GREEN"

If the device is in automatic mode, this LED lights up. If this LED is blinking, you are in configuration mode.

4 ........................................ LED "Alarm"

Alarm Color "RED"

This light-emitting diode is blinking as long as a certain limiting value is exceeded. As soon as all measuring values are beyond the limiting value again and "auto ac-knowledge messages" is set to "OFF" this light-emitting diode becomes a steady light.

Page 16: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page16/63 37140

3.3 Push-buttons

To facilitate the setting of the parameters, the buttons are equipped with a „AUTO-ROLL-function" . It allows to switch to the next setting and configuration screens, the digits, or the cursor. The AUTOROLL-function will only be activated when the user depresses the corresponding keys for a certain period of time.

12 ................................ BUTTON "Display↓..Select"

Display↓..Select Color "NONE"

Automatic mode........ "Display↓" From the display of the first line (star voltages, delta voltages), switch on to the next display. The LEDs "Star" and "Delta" light up correspondingly.

Configuration ............ "Select" Shifts to the next input mask. If the value originally indicated has been modified with the but-tons "Digit↑" or "Cursor→" , the new value is memorized by depressing the button "Select" once. By depressing the button again, the display switches on to the next input mask.

13 ................................ BUTTON

"Menu..Digit↑" Menu..Digit↑ Color "NONE"

Automatic mode........ "Menu" Switching on from the display of the second line. (Various actual values and alarm messages, if any, are indicated

Configuration ............ "Digit↑" With this button the cursor position in-creased by one digit. The position can be increased within the setting limits which are listed in the list of pa-rameters in the Appendix. In case the maximum number is reached which can be set, the number automatically re-turns to the lowest admissible number.

14 ................................ BUTTON

"Clear..Cursor→" Clear..cursor → Color "NONE"

Automatic mode........ "Clear" By depressing this button, alarms are acknowledged which have occurred and are no longer present.

Configuration ............ "Cursor→" With this button the cursor is moved one position to the right. When the last right-hand position is reached, the cursor automatically moves to the first po-sition left-hand of the value to be entered.

Page 17: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

© Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 MFR 11 Manual 37140 Page 17/63

3.4 Display

5 ................................DISPLAY "LC Display"

LC Display

Depending on the operating mode, the two-lined LC display outputs corresponding messages and values. While in configuration mode, the parameters are changed, and while in automatic mode, values such as voltages and currents are indicated.

3.4.1 Automatic mode (first line of the display: measuring values)

NOTE

With the button "Display ↓" you can scroll through the first line.

"Star" = 1, "Delta" = 0 • star voltages

230 230 230 V ----------------

"Star" = 0, "Delta" = 1 • delta voltages

400 400 400 V ----------------

Display in automatic mode, first line: measuring values

Depending on the LEDS "Star" and "Delta") the following measuring values are indi-cated: • The LED "Star" lights up, and the LED "Delta" is off.

The star voltages (UL1-N, UL2-N and UL3-N) of the phase-neutral system are indi-cated. If the current mains is only a phase to phase installation, the configuration -mask "voltage measuring" must be set to "phase to phase installa-tion". Thus, "Star" is not indicated.

• The LED "Star" is off, and the LED "Delta" lights up. The delta voltages (UL1-L2, UL2-L3 and UL3-L1) of the phase-neutral/phase to phase system are indicated.

3.4.2 Automatic mode (second line of the display: measuring value)

NOTE

With the button "Menu" you can scroll through the second line. It is also possible to scroll through all alarms that may be present with the button "Menu" .

---------------- 00,00 xxxxxxxxxx

Display in automatic mode, second line: measuring values

The frequency in [Hz] is always displayed. Instead of "xxxxxxxxxx" the following measuring value is indicated: • Displacement voltage Ue........ unit static in [%] Option Iv• Synchronizing voltage............ unit dynamic in [V / kV] Option Yc• Synchronizing frequency........ unit static in [Hz] Option Yc• Synchronizing angle............... unit static in [°] Option Yc

Page 18: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page18/63 37140

3.4.3 Automatic mode (second line of the display: alarm indication)

v

NOTE

With the button "Menu" you can scroll through the alarm messages in the second line.

---------------- 00,00 yyyyyyyyyy

Display in automatic mode, second line: alarm indication

If alarms occur, the corresponding alarm message is indicated in the bottom line of the LC display, according to the following list. Type of alarm yyyyyyyyyyyyyyyy

Overvoltage, level 1 / level 2 Option U Overvoltage.1 / 2 Undervoltage, level 1 / level 2 Option U Undervoltage.1 / 2 Asymmetry Option U Asymmetry Overfrequency, level 1 / level 2 Option U Overfrequency. 1 / 2 Underfrequency, level 1 / level 2 Option U Underfrequency. 1 / 2Phase/vector shift Option V Phase shift df/dt Option D error df line-to-ground fault Ue, level 1 Option Iv earth-fault Ue Line-to-ground fault Ue, level 2 Option Iv earth-fault. Ue>>

Page 19: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

© Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 MFR 11 Manual 37140 Page 19/63

4 Configuration masks (entering parameters)

While in configuration mode, (simultaneous depression of "Digit↑" and "Cursor→"), you can step through the input masks with "Select". Depressing the button "Select" for a certain period of time will activate the scroll function, and the displays are quickly stepped through. Please note that it is possible to scroll backwards through the last four configuration masks (Exception: Switching from the first to last mask is not possible). To do so, you must simultaneously depress and let go the buttons "Se-lect" and "Cursor→". If for a period of time of 120 seconds, no input, modification or any other action is made, the device will automatically switch back to the automatic mode.

NOTE

There are three different hardware versions, which are described in this operating manual: A 100 V-version [1], a 400 V-version [4] and a 690 V-version [7]. There is a difference as far as the configuration masks and the input of the parameters of the two versions are concerned, and the setting limits are also different. The three types are marked by putting the respective voltages before the name ([1] ..., [4] ... or [7] ...).

Adjust Settings: SELECT (ANWAHL)

Configuration mode Button "Select"

By depressing the button "Select" the configuration mode is activated, and the sub-sequent masks can be viewed and modified within the preset limits. Please note that by depressing the button "Select" the subsequent masks are stepped through one by one. If the parameters of the options are set to "OFF", they are neither indicated nor processed.

NOTE

The following mask "language selection" is not included in the standard devices. If bilingualism was included in the order, you can select the user language with the following mask.

SPRACHE/LANGUAGE English

Language selection German/English

The masks (configuration masks and display masks) can be indicated either in Ger-man or in English, at your choice.

Software version X.xxx

Software version

Indication of the software version.

Page 20: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page20/63 37140

4.1 Access to configuration

4.1.1 Sealing function (up to version 1.9xx)

NOTE

If no protection against the modification of setting values is required, we recommend not to switch on the sealing function; Parameter to "OFF". If the sealing function will become necessary, we recommend to only activate it after the setting has been completed!

FLOWCHART on the next page! The input of a five-digit code number protects the device against unauthorized opera-tor actions or modifications. The function is the exact software equivalent of a me-chanical sealing.

Coding (seal) ON

Sealing function ON/OFF

On delivery of the hardware, the sealing function is set to "OFF". ON ............The input of the following values is protected by a code word. The sub-

sequent masks of this option are indicated. OFF ..........There is no protection by a sealing function, and the subsequent masks

of this option are not indicated.

Code no. 000 Code? ?????

Code for seal number XXX 0..60.000

On delivery, the code number is set to "00100" . Code number correct...... If the code number for the active seal was entered cor-

rectly, the values are entered according to the sequence of the masks.

Code number incorrect... If the code number for the active seal was entered incor-rectly, the subsequent masks are indicated.

Incorrect entry! [Next: SELECT]

Incorrect code Button "Select"

The code number for the active seal was entered incorrectly! Please confirm this message with the button "Select".

Code no. 000 Break? NO

Breaking the seal number XXX YES/NO

By entering "YES" you can break the seal and release the input mode. The number of the seal is however automatically increased by 1. Thus, it is possible to check at any time if modifications have been carried out without entering the correct code number. If you select "NO" the code is inquired again. The interrogation can only be left by terminating the input mode.

Code no. 001 New code: ?????

Code for seal 001 (new entry) 0..60.000

After breaking the old seal the device requests the code number for the new seal. Sealing can now be effected with a new code number.

Enter value [Next: SELECT]

Enter values Button "SELECTION"

Input: Button "Select".

Page 21: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

© Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 MFR 11 Manual 37140 Page 21/63

Code no. 000Breake?

Code no. 001New code:

Adjust settings[ANWAHL/SELECT]

Code no. 000Code ?

SEALING

Wrong Code![ANWAHL/SELECT]

Sealing

ON

OFF

Code O.K.

NO

JA

To leave thesealing, pleasechange intoautomaticmodus.

Page 22: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page22/63 37140

4.1.2 Password (from Version 2.0xx / 3.0xx)

The device is equipped with a three-step code and configuration hierarchy which al-lows to make different configuration masks visible for different users. The difference is made between:

Code level 0 User: External person (CS0) This code level does not allow any access to the parameters. The enter function is

blocked.

Code level 1 User: Client (CS1) This code level authorizes the user to modify a few pre-selected parameters. The

password cannot be changed at this level.

Code level 2 User: Commissioning engineer (CS2) With this code level 2 the user obtains all access rights, thus having direct access to

all parameters (viewing and changing) Moreover, at this level, the user is also author-ized to establish passwords for levels 1 and 2.

NOTE

Once the code level is set, it will not be changed even after entering the configuration repeatedly. If entering an incorrect code number, the code level is set to CS0, thus locking the device for external persons (Entering of the passwords on page 23). Two hours after the last operator action, the device automatically switches to the code level CS0. By entering the appropriate code number you go back to the corresponding level.

Enter code number XXXX

Enter code number 0..9.999

When entering the configuration mode, a code number to identify the different users is inquired first. The number XXXX, which is indicated is a random number and is confirmed with the button "Select". If the random number is confirmed with "Select" without changing it, the code level of the device is not changed. In order to change the code level and to install new passwords for the users, there are two four-digit code numbers(0000..9999). For the user level "External person" no assignment is necessary, since normally, the user does not obtain the right to access the configu-ration level (protected by the codes).

Page 23: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

© Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 MFR 11 Manual 37140 Page 23/63

4.1.3 Change passwords (from v 2.0xx/3.0xx)

NOTE

Once the code level is set, it will not be changed even after entering the configuration repeatedly an incorrect code number has been entered, the code level is set to CS0, thus locking the device for external persons. If for 2 hours uninterruptedly supply voltage is applied, the device automatically switches to code level 0.

Define level 1 code 0000

Code level 1 (client) 0..9.999

This masks appears only from code level 2. After entering the digits into this mask, the code level for level 1 (client) is set. After entering the code, the client only has the access rights assigned to him. This code level (CS) is preset to CS1 = 0 0 1

Define level 2 code 0000

Code level 2 (commissioning engineer) 0..9.999

This masks only appears from code level 2. After entering the digits into this mask, the code level for level 2 (technician) is set. After entering the code, the technician has the access rights with which he was assigned. This code level (CS) is preset to CS2 = 0 0 0 2

Page 24: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page24/63 37140

4.2 Configure basic settings

WARNING!

An incorrect input may lead to wrong measuring values and trippings!

4.2.1 Direct configuration (from version 3.0xx)

NOTE

For the configuration via the lateral connector (direct configuration) you need a direct configuration cable (order code "DPC"), the program LeoPC 1 (will be delivered with the cable) and the appropriate configuration files. For the description and setting up of the PC program LeoPC 1 please refer to the online help which will also be installed when installing the program.

WARNING!

If the following parameter "direct parameter" is set to "YES", the communication via the interface is blocked with terminals X1..X5 . If, after the configuration of the device, communication via the interface X1..X5 should be established again,(e. g. CAN-Bus-connection via a gateway GW 4), the subsequent parameter must be set to "NO"! The following restrictions also apply: Option Su: Communication via the interface is locked. Option A6: The analog outputs 3 to 6 are without function during configuration. Option A8 or A82: The analog outputs 5 to 8 are without function during configuration. If, after the configuration of the device, communication via the interface should be established and the corresponding analog output should function again, the subsequent parameter must be set to "NO" !

Direct para. YES

Configuration via the configuration connector YES/NO

YES ..........Configuration via the side connector is possible, and an interface con-nection that may be existing via the terminals X1..X5, is deactivated. The function of existing analog outputs is restricted. The following require-ments must be met for the configuration via the lateral connector: - A connection between the device and the PC must be established with

the direct configuration cable, - the baudrate of the program LeoPC must be set to 9.600 Baud and - the appropriate configuration file must be used (file name: "xxxx-xxxx-

yyy-zz.asm"). NO ............Configuration via the lateral connector cannot be carried out, and an in-

terface connection that may be existing via the terminals X1..X5 , is acti-vated. All existing analog output do function without any restriction.

Page 25: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

© Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 MFR 11 Manual 37140 Page 25/63

4.2.2 Voltage Measuring

Volt.-Measuring Phase to phase

This mask has only an effect on the display. The masks for

the protective device will be de-fined below.

Voltage measuring Phase to phase/phase neutral

This parameter defines how the voltage is to be measured. If this parameter is set to "Phase to phase", the configuration mask "Monitoring of" in chapter 4.2.5 "Configuration of the Type of Monitoring" on page 26 does not appear.

4.2.3 Configuration of the voltage transformer

NOTE

The masks described in the following section are not available for the 690 V-version.

a.) without option Yc

Volt.transformer secondary 000V

Voltage transformer secondary [1] 50..120 V; [4] 50..480 V

Here, the secondary voltage is set in V. This information is needed for the indication of the secondary voltages on the display. For measuring voltages of 400 V without a measurement transformer, "400V" must be set here.

Volt.transformer primary 00,00kV

Voltage transformer primary 0.1..65.0 kV

Here, the primary voltage is set in kV. This information is needed for the indication of the primary voltages on the display. For measuring voltages of 400 V without a measurement transformer, "00.40kV" must be set here.

b.) with option Yc

Volt.transformer secondary 000V

Voltage transformer generator secondary [1] 50..120 V; [4] 50..480 V

Here, the secondary voltage is set in V . This information is needed for the indication of the secondary voltages on the display. For measuring voltages of 400 V without a measurement transformer, "400V" must be set here.

Volt.transformer primary 00,00kV

Voltage generator primary 0.1..65.0 kV

Here, the primary voltage is set in kV. This information is needed for the indication of the primary voltages on the display. For measuring voltages of 400 V without a measurement transformer "00.40kV" must be set here.

Volt.transformer secondary 000V

Voltage transformer mains secondary [1] 50..120 V; [4] 50..480 V

Here, the secondary voltage for the synchronizing input is set in V. This information is needed for the indication of the secondary voltages on the display. For measuring voltages of 400 V without a measurement transformer, "400V" must be set here.

Volt.transformer primary 00,00kV

Voltage mains primary 0.1..65.0 kV

Here, the primary voltage for the synchronizing input is set in kV. This information is needed for the indication of the primary voltages on the display. For measuring volt-ages of 400 V without a measurement transformer, "00.40kV" must be set here.

Page 26: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page26/63 37140

4.2.4 Configuration of the rated values (option Yc)

NOTE

The option Yc cannot be used for 690 V-devices; please refer to chapter 1.3.2b.) "Synchronizing voltage (option Yc - option Iv not available) on page 8.

Nominal voltage 000V

Rated voltage [1] 5..125 V; [4] 10..480 V

By entering this value, the rated voltage is preset. The rated voltage has an effect on the admissible range for the synchronization (see chapter 4.3.1 "Control function for the synchronization (option Yc)" on page 27).

Nomin. Frequency 00,0Hz

Rated frequency 40.0..70.0 Hz

By entering this value, the rated frequency is preset. The rated frequency has an ef-fect on the admissible range for the synchronization (see chapter 4.3.1 "Control function for the synchronization (option Yc)" on page 27).

4.2.5 Configuration of the Type of Monitoring

NOTE

This configuration mask does not appear if a "Three-wire installation"-voltage measuring has been selected in the configuration mask "voltage measuring" see chapter 4.2.2 "Voltage Measuring" on page 25.

Mask for "phase-neutral":

Volt.-Monitoring phase-neutral

Mask for "phase to phase":

Volt.-Monitoring phase-phase

Monitoring Phase to phase/phase-neutral

The device may monitor either the phase voltages (four wire installation) or the lline-to-line voltages (three-wire installation). Usually, when using alow-voltage system (400/690 V-version) the phase voltages are monitored (mask text: v(phase-N)), and line-to-line voltages are monitored when using a medium-high-voltage system (100 V-Version) (mask text: v(ph-ph)). Monitoring of the line-to-line voltage is par-ticularly necessary to avoid the tripping of the voltage relays by a line-to-ground fault in an isolated-neutral or compensated system. The mask "voltage measuring" has no effect on this mask but the one described under . The settings in the mask ".Volt. Monitoring" do have the following effect on the configuration masks: Phase-neutral ............ The voltages at the terminals 1 to 4 are measured as if for a

phase-neutral installation and the voltage monitoring of all subsequent masks are referred to the phase-to-zero voltage (UL-N). In the configuration masks, this is indicated by adding "(phase-N)".

Phase to phase.......... If the voltage system connected to the terminals 1 to 4 is a phase to phase installation, this setting must be selected. The measurement and all subsequent masks referring to voltage monitoring are related to the wire-to-wire voltage (UL-

L). In the configuration masks, this is indicated by adding "v(ph-ph)".

Page 27: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

© Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 MFR 11 Manual 37140 Page 27/63

4.3 Configuration of control functions

4.3.1 Control function for the synchronization (option Yc)

NOTE

This option Yc cannot be used for 690 V-devices; please refer to chapter 1.3.2b.) "Synchronizing voltage (option Yc - option Iv not available) on page 8.

a.) Output of the signal "voltages are synchronous"

Considering various criteria, an add-on order is output by the device to a power cir-cuit breaker which is designed to connect two sub networks after adjusting the re-spective voltages and frequencies. The add-on order has a predefined minimum turn-on time and is output to a relay. The relay output is firmly assigned to relay 3 (for de-vices without option R) or to relay 8 (for devices with option R).

Function "Synchronization with differential frequency" The electrical phase lead for the output of the add-on order is calculated for each de-vice in a way to always keep the lead time constant, regardless of the current differ-ential frequency. If both, differential voltage and differential frequency, fall below the values adjusted between the two voltage systems, the add-on order can be output, considering the following conditions: • The current r.m.s. voltages of both networks must be more than 75 % each, and

less than 112.5 % of the adjusted rated voltage. • The voltage must fall below the maximum admissible differential voltage adjusted

between the two networks. • The frequency must fall below the maximum adjusted differential frequency be-

tween the two networks. • The electrical angle between two cophasal phases must be smaller than the corre-

sponding maximum admissible error angle (depending on the slip, max. 8 °el.).

b.) Synchronous networks

For synchronous networks, an add-on order is also output by the device as long as the electrical angle between the systems is less than +/-2 °el. and the voltage falls below the voltage difference adjusted.

c.) Configuration screens

Synchronization functions ON

Synchronous functions ON/OFF

ON ............The synchronization is monitored and the subsequent masks of this op-tion are indicated.

OFF ..........There is no monitoring, and the subsequent masks of this function are not indicated.

Synchronization df max. 0,18Hz

Max. admissible differential frequency for synchronization 0.02..0.49 Hz

A required condition for the output of an add-on order is that the frequency falls be-low the adjusted differential frequency. This value is valid for a positive slip. Positive slip means: Generator frequency greater than mains frequency (synchroni-zation voltage).

Page 28: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page28/63 37140

Synchronization df min. -0,10Hz

Min. admissible differential frequency for synchronization 0.00..-0.49 Hz

A required condition for the output of an add-on order is that the frequency falls be-low the adjusted differential frequency. This value is valid for a negative slip. Nega-tive slip means: Generator frequency less than mains frequency (synchronization voltage).

Synchronization dU max = 00,0%

Max. admissible differential voltage 0.1 .. 15.0 %

The percentage indication refers to the secondary voltage adjusted. A required con-dition for the output of an add-on order is that the voltage falls below the adjusted differential voltage.

Synchronization Time pulse>200ms

Min. pules time of the add-on relay 50..250 ms

The duration of the add-on pulse can be adjusted to the subsequent switch unit. The minimum time required for the output of the add-on order is adjusted here.

Circuit breaker Pick-up t. 080ms

Switcher time delay generator switch 40..300 ms

The adjusted value corresponds to the lead time of the add-on order. The add-on order is independent of the differential frequency and is output at the pre-set time before the synchronous point.

Page 29: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

© Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 MFR 11 Manual 37140 Page 29/63

4.4 Configuration of the protective device

4.4.1 Overvoltage monitoring (option U)

Function "Voltage not within admissible range" At least one phase of the voltage is not within the adjusted limits for the overvoltage. An alarm message is displayed This message cannot be suppressed with the dis-crete input "Blocking of watchdog functions / remote acknowledgment".

Overvoltage Monitoring ON

Overvoltage monitoring ON/OFF

ON ............The voltage is monitored, and the subsequent masks of this function are indicated.

OFF ..........There is no monitoring, and the subsequent masks of this function are not indicated.

Mask for "phase to phase":

Overvoltage 1 V(ph-ph) >000V

Mask for "phase-neutral":

Overvoltage 1 (Phase-N) >000V

Threshold (wire, 3-L) [1] 20..130 V; [4] 20..520 V; [7] 20..900 V Overvoltage, level 1 (phase, 4-L) [1] 10..75 V; [4] 10..300 V; [7] 10..520 V

The value of the overvoltage (level 1), to be monitored is adjusted in this mask. If the value is reached or exceeded, the device outputs an alarm message. If additionally, a relay has been configured with the relay manager, another output is made to this relay.

Overvoltage 1 Delay 00,10s

Pickup delay, level 1 0.02..99.98 s

For a tripping, the threshold must be continuously exceeded for at least as long as indicated in this mask.

Mask for "phase to phase":

Overvoltage 2 V(ph-ph) >000V

Mask for "phase-neutral":

Overvoltage 2 (Phase-N) >000V

Threshold (wire, 3-L) [1] 20..130 V; [4] 20..520 V; [7] 20..900 V Overvoltage, level 2 (phase, 4-L) [1] 10..75 V; [4] 10..300 V; [7] 10..520 V

The value of the overvoltage (level 2), to be monitored is adjusted in this mask. If the value is reached or exceeded, the device outputs an alarm message. If additionally, a relay has been configured with the relay manager, another output is made to this relay.

Overvoltage 2 Delay 00,04s

Pickup delay, level 2 0.02..99.98 s

For a tripping, the threshold must be continuously exceeded for at least as long as indicated in this mask.

Overvoltage Hysteresis 00V

Hysteresis for the overvoltage monitoring 0..99 V

In order to avoid that the signal relay keeps picking up and releasing when ap-proaching the adjusted threshold for the overvoltage (both levels), it is possible to indicate an absolute value for the difference between the threshold and release value (hysteresis), referring to the threshold.

Page 30: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page30/63 37140

4.4.2 Undervoltage monitoring (option U)

Function "Voltage not within the admissible range" At least one phase of the voltage is not within the adjusted limiting values for the un-dervoltage. An alarm message is displayed. This message can be suppressed with the discrete input "Blocking of watchdog functions / remote acknowledgment".

Undervoltage Monitoring ON

Undervoltage monitoring ON/OFF

ON ............The voltage is monitored, and the subsequent masks of this function are indicated.

OFF ..........There is no monitoring, and the subsequent masks of this function are not indicated.

Mask for "phase to phase":

Undervoltage 1 V(ph-ph) >000V

Mask for "phase-neutral":

Undervoltage 1 (Phase-N) >000V

Threshold (wire, 3-L) [1] 20..130 V; [4] 20..520 V; [7] 20..900 V Undervoltage, level 1 (phase, 4-L) [1] 10..75 V; [4] 10..300 V; [7] 10..520 V

The value of the undervoltage (level 1) to be monitored is adjusted in this mask. If the value as reached or exceeded, an alarm message is displayed by the device. If additionally, a relay has been configured with the relay manager, another output is made to this relay.

Undervoltage 1 Delay 00,10s

Pickup delay, level 1 0.02..99.98 s

For a tripping, the value must fall below the threshold for at least as long as indi-cated in this mask.

Mask for "phase to phase":

Undervoltage 2 V(ph-ph) >000V

Mask for "phase-neutral":

Undervoltage 2 (Phase-N) >000V

Threshold (wire, 3-L) [1] 20..130 V; [4] 20..520 V; [7] 20..900 V Undervoltage, level 2 (phase, 4-L) [1] 10..75 V; [4] 10..300 V; [7] 10..520 V

The value of the undervoltage (level 2) to be monitored is adjusted in this mask. If the value is reached or exceeded, an alarm message is displayed by the device. If additionally, a relay has been configured with the relay manager, another output is made to this relay.

Undervoltage 2 Delay 00,04s

Pickup delay, level 2 0.02..99.98 s

For a tripping, the value must fall below the threshold for at least as long as indi-cated in this mask.

Undervoltage 2 Hysteresis 00V

Hysteresis for the undervoltage monitoring 0..99 V

In order to avoid that the signal relay keeps picking up and releasing when ap-proaching the adjusted threshold for the overvoltage (both levels), it is possible to indicate an absolute value for the difference between the threshold and release value (hysteresis), referring to the threshold.

Page 31: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

© Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 MFR 11 Manual 37140 Page 31/63

4.4.3 Zero voltage monitoring (option Un)

Function "Voltage within the admissible range" All three phases of the voltage fall below the adjusted limiting value for the zero volt-age. This function may be for instance used for the detection of a dead busbar and as a clear signal of switching actions. An alarm message is displayed. This message cannot be suppressed with the discrete input "Blocking of watchdog functions / re-mote acknowledgment" and does not generate a display.

Zero-voltage Monitoring ON

Zero voltage monitoring ON/OFF

ON ............The voltage is monitored and the subsequent masks of this function are indicated.

OFF ..........There is no monitoring, and the subsequent masks of this function are not indicated.

Mask for "phase to phase":

Zero-voltage V(ph-ph) <000V

Mask for "phase-neutral":

Zero-voltage (Phase-N) <000V

Threshold (wire, 3-L) [1] 3..130 V; [4] 12..520 V; [7] 20..900 V Zero voltage (phase, 4-L) [1] 2..75 V; [4]: 6..300 V; [7] 12..520 V

The value of the zero voltage to be monitored is adjusted in this mask. If the value is reached or falls below the adjusted value, the device internally outputs an alarm message. If additionally, a relay has been configured over the relay manager, an-other output is made to this relay.

Zero-voltage Delay 00,00s

Pickup delay 0.02..99.98 s

For a tripping, the value must continuously fall below the threshold for at least as long as indicated in this mask.

Zero-voltage Hysteresis 00V

Hysteresis for the zero voltage monitoring 0..99 V

In order to avoid that the signal relay keeps picking up and releasing when ap-proaching the adjusted threshold for the zero voltage it is possible to indicate an ab-solute value for the difference between the threshold and release value (hysteresis), referring to the threshold.

Page 32: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page32/63 37140

4.4.4 Asymmetry monitoring (option U)

Each line-to-line voltage is monitored.

Function "Voltage asymmetry not within admissible range" The voltage difference between the three monitored phases of the line-to-line volt-ages is not within the adjusted limiting value for asymmetry (asymmetric voltage vec-tors; the threshold corresponds to the differential value). An alarm message is dis-played. This message can be suppressed with the discrete input "Blocking of watchdog functions / remote acknowledgment".

Asymmetry- Monitoring ON

Asymmetry monitoring ON/OFF

ON ............The voltage difference is monitored, and the subsequent masks of this function are indicated.

OFF ..........There is no monitoring, and the subsequent masks of this function are not indicated.

Asymmetry release v. 00V

Maximum admissible asymmetry 0..99 V

The maximum differential voltage admissible is entered here as an absolute value. If the value is reached or falls below the value adjusted, the device outputs an alarm message. If additionally, a relay has been configured with the relay manager, an-other output is made to this relay.

Asymmetry Delay 00,00s

Pickup delay of the asymmetry monitoring 0.02..99.98 s

For a tripping, the threshold must be continuously exceeded for at least as long as indicated in this mask.

Asymmetry Hysteresis 00V

Hysteresis for the asymmetry monitoring 0..99 V

In order to avoid that the signal relay keeps picking up and releasing when ap-proaching the adjusted threshold for the asymmetry it is possible to indicate an ab-solute value for the difference between the threshold and release value (hysteresis), referring to the threshold.

Page 33: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

© Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 MFR 11 Manual 37140 Page 33/63

4.4.5 Overfrequency Monitoring (option U)

The frequency monitoring is two-stepped. A three-phase measurement of the fre-quency is carried out if all voltages exceed the nominal value by 15 % (100 V or 400 V). This guarantees a very fast and exact measurement of the frequency. The frequency is however still measured correctly even if voltage is applied to only one phase.

Function "Frequency not within the admissible range" The frequency is not within the adjusted limiting value for the overfrequency. An alarm message is displayed. This message cannot be suppressed with the discrete input "Blocking of watchdog functions / remote acknowledgment".

Overfrequency- Monitoring ON

Overfrequency monitoring ON/OFF

ON ............The frequency is monitored, and the subsequent masks of this function are indicated.

OFF ..........There is no monitoring, and the subsequent masks of this function are not indicated.

Overfrequency 1 f > 00,00Hz

Threshold overfrequency , level 1 40.00..80.00 Hz

The value of the overfrequency (level 1) to be monitored is adjusted in this mask. If this value is reached or exceeded, the device outputs an alarm message. If addi-tionally, a relay has been configured with the relay manager, another output is made to this relay.

Overfrequency 1 Delay 00,00s

Pickup delay, level 1 0.02..99.98 s

For a tripping, the threshold must be continuously exceed for at least as long as in-dicated in this mask.

Overfrequency 2 f > 00,00Hz

Threshold overfrequency, level 2 40.00..80.00 Hz

The value of the overfrequency (level 2), to be monitored, is adjusted in this mask. If this value is reached or exceeded, the device outputs an alarm message. If addi-tionally, a relay has been configured with the relay manager, another output is made to this relay.

Overfrequency 2 Delay 00,00s

Pickup delay, level 2 0.02..99.98 s

For a tripping, the threshold must be continuously exceeded for at least as long as indicated in this mask.

Overfrequency Hysteres. 0,00Hz

Hysteresis for the overfrequency monitoring, levels 1+2 0.01..9.99 Hz

In order to avoid that the signal relay keeps picking up and releasing when ap-proaching the adjusted threshold for the overfrequency (both levels), it is possible to indicate an absolute value for the difference between the threshold and release value (hysteresis), referring to the threshold.

Page 34: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page34/63 37140

4.4.6 Underfrequency monitoring (option U)

The frequency monitoring is two-stepped. Three-phase measurement of the fre-quency if all voltages exceed the nominal value by 15 % (100 V or 400 V) . This guarantees a very fast and exact measurement of the frequency. The frequency is however still measured correctly even if voltage is only applied to one phase.

Function "Frequency not within the admissible range" The frequency is not within the adjusted limiting value for the underfrequency. An alarm message is displayed. This message can be suppressed with the discrete input "Blocking of watchdog functions / remote acknowledgment".

Underfrequency- Monitoring ON

Underfrequency monitoring ON/OFF

ON ............The frequency is monitored, and subsequent masks of this function are indicated.

OFF ..........There is no monitoring, and the subsequent masks of this function are not indicated.

Underfrequency 1 f > 00,00Hz

Threshold underfrequency, level 1 40.00..80.00 Hz

The value of the underfrequency (level 1) to be monitored is adjusted in this mask. If the value is reached or falls below the adjusted value, the device outputs an alarm message. If additionally, a relay has been configured with the relay manager, an-other output is made to this relay.

Underfrequency 1 Delay 00,00s

Pickup delay, level 1 0.02..99.98 s

For a tripping, the frequency must fall continuously fall below the threshold for at least as long as indicated in this mask.

Underfrequency 2 f > 00,00Hz

Threshold underfrequency, level 2 40.00..80.00 Hz

The value of the underfrequency (level 2), to be monitored is adjusted in this mask. If the value is reached or falls below the value adjusted, the device outputs an alarm message. If additionally, a relay has been programmed with the relay manager, an-other output is made to this relay.

Underfrequency 2 Delay 00,00s

Pickup delay, level 2 0.02..99.98 s

For a tripping, the frequency must fall below the threshold for at least as long as in-dicated in this mask.

Underfrequency Hysteres. 0,00Hz

Hysteresis for the underfrequency monitoring, levels 1+2 0.01..9.99 Hz

In order to avoid that the signal relay keeps picking up and releasing when ap-proaching the adjusted threshold for the underfrequency (both levels), it is possible to indicate an absolute value for the difference between the threshold and release value (hysteresis), referring to the threshold.

Page 35: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

© Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 MFR 11 Manual 37140 Page 35/63

4.4.7 Phase/vector shift monitoring (option V)

A phase/vector shift is defined as the sudden variation of the voltage curve which may be caused by a major load change of a generator. In this case, a one-time varia-tion of the cycle duration is detected by the measuring circuit. This modified cycle du-ration is compared with a calculated mean value from earlier measurements. The monitoring is three-phased. The threshold in degrees indicates the time difference between mean value and instantaneous value, referring to a full period. The monitor-ing can be set in different ways. The phase/vector shift monitor may used as an addi-tional equipment for the mains decoupling. The minimum voltage to activate the phase/vector shift is 70 % of the nominal secondary voltage.

Function "Cycle duration of the voltage not within the admissible range" The cycle duration of the voltage is not within the adjusted limiting value for the phase/vector shift. An alarm message is displayed. This message can be suppressed with the discrete input "Blocking of watchdog functions / remote acknowledgment".

Phase shift monitoring ON

Phase/vector shift monitoring ON/OFF

ON ............The voltage/frequency is monitored, and a phase/vector shift is regis-tered within the defined range. The subsequent masks of this function are indicated.

OFF ..........There is no monitoring, and the subsequent masks of this function are not indicated.

Phase shift mon. one/three phase

Phase/vector shift monitoring single-/three-phase..only three-phase

single-/three-phase ... When single-phase voltage monitoring is used for a phase/vector shift, tripping is released if at least one of the three phases exceeds the adjusted threshold. This kind of monitoring is very sensitive and may lead to false tripping if the selected phase angle is too small.

three-phase only ..When three-phase voltage monitoring is used for a phase/vector shift, tripping is only released if the phase/vector shift exceeds the adjusted threshold within 2 periods.

NOTE

If monitoring is set to "three-phase only", only the bottom mask of the two subsequent mask is visible; if monitoring is set to "single-/three-phase", both parameter masks are visible.

Phase-jump value (One phase) 00°

The mask is only visible, if monitoring is set to "sin-

gle/three-phase" .

Phase angle phase/vector shift monitoring, single-phase 2..90 °

Tripping is released if the electrical angle shift of the voltage curve in a phase ex-ceeds the adjusted angle. If the value is reached or exceeded, the device outputs an alarm message. If additionally, a relay has been configured with the relay manager, another output is made to this relay.

Phase-jump value (3-phase) 00°

Phase angle phase/vector shift monitoring, three-phase 3..90 °

Tripping is released if the electrical angle shift of the voltage curve exceeds the value of the adjusted angle in all three phases simultaneously. If the value is reached or exceeded, the device outputs an alarm message. If additionally a relay has been configured with the relay manager, another output is made to this relay.

Page 36: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page36/63 37140

4.4.8 df/dt monitoring (option D)

Function "Frequency change per unit time of the voltage not within the admissible range" The device calculates a measuring value for the frequency change per unit time. In order to guarantee a reliable differentiation between phase/vector shift and df/dt, measurements made during 4 periods. The result is a minimum tripping time of ap-prox. 100 ms (at 50 Hz). This message can be suppressed with the discrete input "Blocking of watchdog functions / remote acknowledgment".

df/dt- Monitoring ON

df/dt monitoring ON/OFF

ON ............The frequency change is monitored and the subsequent masks of this function are indicated.

OFF ..........There is no monitoring, and the subsequent masks of this function are not indicated.

df/dt Release >0,0Hz/s

Tripping df/dt 1.0..9.9 Hz/s

If the value is reached or exceeded, the device outputs an alarm message. If addi-tionally, a relay has been programmed with the relay manager, another output is made to this relay.

df/dt Delay T= 0,0s

Pickup delay 0.1..9.9 s

For a tripping, the threshold must be exceeded for at least as long as indicated in the mask.

4.4.9 Non-directional ground fault monitoring (option Iv)

The device may be used for the logging of ground faults in the stator winding of three phase machines feeding the mains via a unit connected transformer. In case of an ground fault, the occurrence of displacement voltage is primarily used to release a tripping, thus reaching a protection range of up to approx. 95 % of the winding.

a.) First tripping level for the displacement voltage

Function Measurement of the displacement voltage The displacement voltage is usually measured by the open delta winding (e-n-winding) of a voltage transducer or by the zero point transformer in the machine star point. If transformers are used which supply voltages greater than 100 V during terminal ground fault (e. g. 240 V, 500 V), voltage has to be reduced externally to a level of 0..100 V, using a voltage divider. The single-phase contents of the third har-monic which occurs particularly when synchronous machines are used, are added by summation, so that an interference-free measurement is only guaranteed if a highly effective filter method is used. An alarm message is displayed. This message can be operated with the relay manager, but cannot be suppressed with the discrete input "Blocking of watchdog functions / remote acknowledgement".

Page 37: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

© Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 MFR 11 Manual 37140 Page 37/63

Earth fault Ue monitoring ON

Non-directional ground fault monitor ON/OFF

ON ............The non-directional line-to-ground fault is monitored, and the subsequent masks of this function are indicated.

OFF ..........There is no monitoring, and the subsequent masks of this function are not indicated.

Earth fault Ue> Release 000V

Threshold displacement voltage, level 1 3..100 %

If the adjusted threshold is exceeded after the pre-set time lag, a tripping is released. If additionally, a relay has been configured with the relay manager, another output is made to this relay. The threshold in percent is referred to the nominal displacement voltage (normally 100 V).

Earth fault Ue> Delay 00,00s

Time lag displacement voltage, level 1 0.02..99.98 s

For a tripping, the threshold must be continuously exceeded for at least as long as indicated in this mask.

b.) Second tripping level for the displacement voltage

Function "line-to-ground fault Ue>> for switching loading device" For insulated or compensated networks loading devices may be used to increase the earth current. The performance of these devices is usually not designed for continu-ous load with full displacement. Therefore these devices have to be switched off as soon as the displacement voltage exceeds a critical value. Please note however that the loading device may only be switched off after the tripping of the ground fault monitor. The reaction of the second level must therefore be slower if user to switch off a loading device. Moreover, the threshold must exceed the thresh-old of the first level. An alarm message is displayed. This message can be operated with the relay manager, however cannot be suppressed with discrete input "Blocking of watchdog functions / remote acknowledgment".

Earth fault Ue>> Release 00V

Threshold residual voltage, level 2 3..100 %

Exceeding of the adjusted threshold after the adjusted time lag releases the tripping. If additionally, a relay has been configured with the relay manager, another output is made to this relay. The percentage value of the threshold is referred to the nominal-displacement voltage (normally 100 V).

Earth fault Ue>> Delay 00,00s

Time lag residual voltage, level 2 0.02..99.98 s

For a tripping, the value of threshold must be exceeded continuously for at least as long as indicated in this mask.

Page 38: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page38/63 37140

4.5 Configuration of the relay

NOTE

Operating current (NO) The relay picks up during the tripping, i. e. current flows through the coil while in operate condition.

In case of a loss of the supply voltage the state of the relay remains un-changed and no tripping is released. In this case the readiness for opera-tion of the device should be monitored.

Closed-circuit current (NC) The relay drops out during the tripping, i. e. current flows through the coil

while in release condition. The relay picks up while in release condition (= no tripping).

In case of a loss of the supply voltage the state of the relay is changed and a tripping is released.

Relay programmed as 'operating current relay'Operating currencontact

Idle-currentcontact

RELEASERelay operates

RELEASE

curr

ent f

low

0 V

24 V

Operating currencontact

Idle-currentcontact

RELEASERelay releases

Relay programmed as 'idle-current relay'

RELEASE

no c

urre

nt fl

ow0 V

24 V

NOTE

The subsequent input "Blocking of watchdog functions / remote acknowledgment" is not available for the 690 V-version .

Blocking protective device Remote acknowledgement Terminal 5/6

Due to a non-reset high-signal at the discrete input the release of various protection devices may be blocked. This may be useful for instance if the device is used as a generator protection device. Thus, tripping can be avoided for messages ( such as undervoltage or underfrequency) which are permanently active during a machine standstill. If blocking is not required, the discrete input should be permanently inter-connected with zero potential. The following functions can not be blocked with this discrete input : • Overvoltage • Overfrequency • Zero voltage • Ground fault monitor

Page 39: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

© Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 MFR 11 Manual 37140 Page 39/63

NOTE

The subsequent function "External clearing" has various consequences, depending on the setting of the configuration masks "Auto-clearing relays" and "Auto-clearing display". Below please find the corresponding explanations.

External Clearing OFF

External acknowledgement of the

relays via the discrete input "Blocking of watchdog functions /

remote acknowledgment".

Acknowledgement via the discrete input ON/OFF

If the device should not automatically reset the relays as soon as the alarm is no longer present, it is necessary to first set the function "Auto-clearing relays" to "OFF" (see chapter 4.5.1 "Auto-clearing relay" on page 39).

OFF ..........Alarms which cannot be blocked are no longer automatically reset, if the releasing alarm is no longer present. The relays are reset by pressing the button "Clear".

ON ............All active alarms are reset if a rising edge is detected at the blocking in-put. (The discrete input "Blocking of watchdog functions / remote ac-knowledgment" must be set from "0" to "1".) Alarms which cannot be blocked are only reset if the alarm is no longer present.

External Clearing OFF

External acknowledgement of the alarm messages via the discrete input "Blocking protective device

remote acknowledgement".

Acknowledgement via the discrete input ON/OFF

If the device should automatically reset the relays as soon as the alarm is no longer present however leave the messages on the display unchanged, it is necessary to first set the functions "Auto-clearing relays" to "ON" and "Auto-clearing display" to "OFF" (see chapter 4.5.1 "Auto-clearing relay" on page 39).

OFF ..........The display messages are reset by pressing the button "Clear". ON ............All active display messages are reset if a rising edge is detected at the

blocking input. (The discrete input "Blocking of watchdog functions / re-mote acknowledgment" must be set from "0" to "1" .) Alarms which can-not be blocked are only reset if the alarm is no longer active.

4.5.1 Auto-clearing relays

Auto-clearing Relays ON

Auto-clearing of the relays ON/OFF

(Description for operating current output; depending on the setting in the mask "Auto-clearing display"!) ON ............The relays drop out automatically after the alarm is no longer present at

the alarm input. Handling of the alarm message on the display depends on the setting in the mask "Auto-clearing display". The subse-quent masks of this function are not indicated.

OFF ..........The relays remain picked up until acknowledged. Handling of the alarm message on the display depends on the setting in the mask "Auto-clearing display" .

NOTE The following setting is blocked:

• "Auto-clearing relays" = "OFF" and • "Auto-clearing display" = "ON".

Page 40: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page40/63 37140

NOTE

The subsequent masks become only visible if the corresponding protection device is switched on. If monitoring is set to "OFF", these masks won't appear. The subsequent masks are neither visible if the configuration mask "Auto-clearing relays" is set to "OFF". Of course, these masks are neither visible if the corresponding function is not included in the device.

Release delay xxxxxxxxx 00,00s

Resetting time delay of the relays 0.02..99.98 s

To make sure that the signal relay drops out again after a tripping, the threshold must be continuously exceeded/fall below the adjusted value (referring to the moni-toring) for at least as long as indicated in this mask (including hysteresis). If the ac-tual value exceeds/falls below the threshold within this period of time, the time calcu-lation is restarted. The following resetting time delays of the protective devices can be adjusted. Monitoring for ... Display instead of

xxxxxxxxx Remark

Zero voltage Option Un Zero voltage no display message Overvoltage Option U Overvoltage Level 1 and level 2 Undervoltage Option U Undervoltage Level 1 and level 2 Asymmetry Option U Asymmetry Overfrequency Option U Overfrequency. Level 1 and level 2 Underfrequency Option U Underfrequency Level 1 and level 2 Phase/vector shift Option V Phase shift. df/dt Option D df/dt Line-to-ground fault Ue>, Ue>>Option Iv

Line-to-earth-fault Ue

Level 1 and level 2, level 2 auto-clearing

4.5.2 Auto-clearing display

Auto-clearing Display ON

Auto-clearing display ON/OFF

ON ............As soon as the alarm condition is no longer detected, the message on the display is cleared.

OFF ..........As soon as the alarm condition is no longer detected, the message on the display is not cleared, and the subsequent mask is not indicated.

NOTE The following setting is blocked:

• "Auto-clearing display" ="ON" and • "Auto-clearing relays" = "OFF"

Clearing display after 00s

Resetting time relay messages 1..99 s

The corresponding alarm messages are acknowledged after the indicated time-(measured from the time moment: threshold + hysteresis not reached/exceeded).

Page 41: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

© Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 MFR 11 Manual 37140 Page 41/63

4.5.3 Change relay assignment (relay manager; standard and option R)

Change relay- allocation? YES

Change relay assignment? YES/NO

With this mask you select whether in case of alarm trippings, the relay assignment for the signal relay can be modified or if it remains unchanged "as is" (see list of pa-rameters). YES ..........The relay assignments can be configured and the subsequent masks are

indicated. NO ............The relay assignment remains unchanged and the subsequent masks

are not indicated.

Example Relay 1..3

NOTE

The outputs are configured in the same way for all relays. Exemplary configuration is shown here for the relays 1 to 3. With option R, it is possible to use another 5 relays. The relay 1 is always linked with the message "Readiness for operation".

Funct. relay 123 (R=releases) RRR

Function of the relays 1, 2 and 3 A/R

By selecting operating current or closed-circuit contact the various control principles are differentiated. It is possible to use an operating current output if a wire break cannot lead to a major alarm; the closed circuit output fulfills further tasks, e.g. for conductors relevant for safety. The relay 1 is permanently configured for R (closed-circuit current) and cannot be modified. For the description of the difference between operating current and closed circuit output please refer to chapter 4.5 "Configuration of the relay" on page 38.

Page 42: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page42/63 37140

NOTE

The subsequent masks are only visible if the corresponding protective device is switched on. If monitoring is set to "OFF", the mask does not appear. Neither are the subsequent masks visible if the configuration masks "Change relay allocation" is set to "OFF". Of course, these masks are not visible if the corresponding option is not included in the device.

xxxxxxxxxxxxxxxx to relay 0000

Output of the protective devices to the relays 0..4/8

The device is designed for the following setting options: 0 ...............Non of the output relays will pick up/drop out when the corresponding

protective device respond. An appropriate message will however appear on the display. If less than four relays respond when a protective device is tripped, the other numbers have to be set to "0".

1/2/3 .........These relays are included in every device. The relay outputs are output to the terminals 9/10 (relay 1), 11/12/13 (relay 2) and/or 14/15/16 (re-lay 3) .

4/5/6/7/8....These relays are only available if option R is included in the device. The relay outputs are output to the terminals 19/20/21 (relay 4), 22/23/24 (re-lay 5), 25/26/27 (relay 6), 28/29/30 (relay 7) and/or 31/32 (relay 8).

Example ...A protective device is to be output simultaneously to the relays 2, 4 and 7

; option R is available. The setting must be: 2470. The sequence of the digits entered is of no importance.

By simultaneously allocating a relay number to several protective device the relay will not only pick up with one, but with several protective devices. If a relay is to allo-cated to a certain protective device, don't use the number more than once. Monitoring of ... ... output to relay

Display instead of xxxxxxxxxxxxxxxx

Overvoltage, level 1 Option U Overvoltage step 1 Overvoltage, level 2 Option U Overvoltage step 2 Undervoltage, level 1 Option U Undervoltage step 1 Undervoltage, level 2 Option U Undervoltage step 2 Zero voltage Option Un Zero voltage Asymmetry Option U Asymmetry Overfrequency, level 1 Option U Overfrequency. step 1 Overfrequency, level 2 Option U Overfrequency step 2 Underfrequency, level 1 Option U Underfrequency step 1 Underfrequency, level 2 Option U Underfrequency step 2 Phase/vector shift Option V phase shift df/dt Option D df/dt Line-to-ground fault Ue, level 1 Option Iv Line-to-earth fault Ue > Line-to-ground fault Ue, level 2 Option Iv Line-to-earth fault Ue >> Centralized alarm Centralized error

Page 43: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

© Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 MFR 11 Manual 37140 Page 43/63

4.6 Analog outputs (options A1/2/3/4/6/8)

NOTE

The common use of analog outputs, interfaces and discrete inputs depends on their configuration. Please observe the possible combinations as explained in the introduction.

ATTENTION!

The function of the analog outputs is restricted during configuration via the side connector (ver-sion 3.xxx). The parameter "direct-parameter" must be set to "NO" to make all analog outputs available (also see chapter 4.2.1 "Direct configuration (from version 3.0xx)" on page 24).

It is possible to allocate a certain measuring value to each existing analog output us-ing the buttons (for possible measuring values see the following table). For -20/0/4..20 mA-analog outputs, the output may be either made as -20..+20 mA, as 0..20 mA-value or as 4..20 mA-value; for -10/0..10 V-analog outputs there is the op-tion of an output as -10..+10 V-value or as 0..10 V-value. The value to be output can be scaled via an upper or lower input value, with linear scaling. The inputs can also be signed numbers. Value Lower and upper setting value 0 V, -10 V

0 mA, 4 mA, -20 mA 10 V, 20 mA

U L1-N 0..65.000 V U L2-N 0..65.000 V U L3-N 0..65.000 V U L-N mean value 0..65.000 V U L-N Max value 0..65.000 V U L-N Min value 0..65.000 V U L1-L2 0..65.000 V U L2-L3 0..65.000 V U L3-L1 0..65.000 V U L-L mean value 0..65.000 V U L-L Max value 0..65.000 V U L-L Min value 0..65.000 V Frequency 40.0..80.0 Hz

Example Analog output 2 (-10/0..10 V: Terminals 50/52, -20/0/4..20 mA: Terminals 52/53

Output of the wire-wire-voltage L12:

20 mA-output

Analog. output 2 0 .. 00 mA

10 V-output

Analog. output 2 0 .. 00 V

Output range of the (20 mA) -20..+20 / 0..20 / 4..20 mA / OFF analog output 2 (10 V) -10..+10 / 0..10 V / OFF

20 mA-analog output (the upper value is always +20 mA) -20..20 mA.... For the output of the lower value -20 mA are output. 0..20 mA....... For the output of the lower value 0 mA are output. 4..20 mA....... For the output of the lower value 4 mA are output. OFF .............. If this option is set to "OFF", 0 mA are output, and the subsequent

masks of this functionare not indicated.

10 V-analog output (the upper value is always +10 V) -10..+10 V ..... When the lower value is output, -10 V are output. 0..10 V .......... When the lower value is output, 0 V are output. OFF .............. If this function is set to "OFF", 0 V are output, and the following masks

of this function are not indicated.

Page 44: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page44/63 37140

Analog. output 2 Active power

Output value of the analog output 2 see a.m. table

Select of the quantity to be output (please observe table above).

Example for the 20 mA-output

Analog. output 0mA = 00000kW

Scaling of the lower output value see above table

Determination of the lower value.

Example for 20 mA-output

Analog. output 20mA = 00000kW

Scaling of the upper output value see above table

Determination of the upper value.

4.7 Interface (option Su/Sb)

ATTENTION!

The function of the interface is restricted during configuration via the side connector (version 3.xxx). The parameter "Direct-parametr." must be set to "NO" to make the interface available (also see chapter 4.2.1 "Direct configuration (from version 3.0xx)" on page 24).

4.7.1 Masks for protocol DK3964 (option Su)

Data block RK512 000

Data block RK512 0..255

Data block address for receiver (e. g. PLC).

Data word RK512 000

Data word RK512 0..255

Data word address for receiver (e. g. PLC).

4.7.2 Masks for protocol Profibus DP slave (option Su)

Device number Profibus 000

Device number Profi Bus DP Slave 0..126

Device number for the Profi-Bus DP Slave.

4.7.3 Masks for protocol MOD bus RTU slave (option Su/Sb)

Device number MOD-Bus 000

Device number MOD-Bus RTU Slave 0..255

Device number for the MOD-Bus RTU Slave.

Baudrate 0000

Baudrate MOD-Bus RTU Slave 1.200 / 2.400 / 4.800 / 9.600 / 19.200 Baud

The baudrate of the MOD-Bus RTU Slave is defined here.

Parity none

Parity MOD-Bus RTU Slave none / even / odd

The parity of the MOD-Bus RTU Slave is defined here.

Stopbits one

Stoppbits MOD-Bus RTU Slave one / two

The number of stoppbits of the MOD-Bus RTU Slave is defined here.

Page 45: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

© Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 MFR 11 Manual 37140 Page 45/63

Delay to send MOD-Bus 00,0ms

Waiting time sending after read request 0.2 .. 50.0 ms

After the read request by the master waiting time for the response is at least as long as the pre-set time. This way, the time behaviour of the master can be adjusted ap-propriately, thus ensuring an adequate processing of the response.

4.7.4 Masks for protocol CAN bus (option Su/Sb)

Device number CAN-Bus 0

Device number CAN-Bus 1..8

The device number with CAN-Bus is entered here. The device number interferes with the calculation of the sending and control-ID.

Baudrate 000

Baudrate CAN-Bus 125/250/500 kBaud

Setting of the baudrate.

Base-ID (send)

Base - ID Send 0 ..2015

The ID, from which the device is sending its operating data, is calculated from the base-ID-send plus the device number.

Base-ID (remote)

Base - ID remote 0 ..2015

The ID, by which the device receives control data, is calculated from the base-ID-control plus the device number CAN-Bus.

4.7.5 General masks for all types of interfaces (option Sb)

Serial control ON

Control via interface ON/OFF

ON ............The control via the serial interface is activated and accepts control orders coming from the interface, if this function is included in the device and the mask is set to "ON" (description of the serial interface in the Appen-dix).

OFF ..........The acceptance of control data is rejected.

Serial interface Monitoring ON

Interface monitoring ON/OFF

ON ............The control expects the master control to write the bits 2 and 3 in the control word to 00 after a maximum of 15 seconds (see interface tele-gram). If not, an unsuccessful data exchange is detected, and the alarm message "interface" is displayed.

OFF ..........Interface monitoring is deactivated.

Interface fault to relay 0000

Message interface error on relay 0..3 / 0..8

The alarm message is displayed to the adjusted relays, if the setting in the mask "Interface monitoring" is set to "ON" .

Inhibit via Interface ON

Blocking via the interface ON/OFF

ON ............Blocking of the messages of the protective devices may be effected via the interface. This function corresponds to the function of the discrete in-put "Blocking of watchdog functions / remote acknowledgment".

OFF ..........The blocking of the messages of the protective device cannot be effected via the interface.

Page 46: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page46/63 37140

5 Commissioning

DANGER!!!

When commissioning the unit, please observe the five safety rules which apply to the handling of live equipment. Make sure that you know how to provide first aid in current-related accidents and that you know where the first-aid kit and the nearest telephone are. Never touch any live components of the system or on the back of the system:

D A N G E R T O L I F E

WARNING!

The unit may only be commissioned by a qualified technician. The "EMERGENCY -OFF" function must safely function prior to the start-up and must not depend on the device.

ATTENTION!

1. Connect the device according to the wiring diagram. Prior to the start-up, make sure that all measuring voltages are connected correctly. The rotating field must be measured. Any lack or incorrect connection of measuring voltages or other signals may lead to incorrect functions and damage the unit as well as engines and components connected to the item.

Proceeding 2. After connecting the device and checking all measuring voltage for their correct connec-

tion, an operating voltage of (e. g. 24 VDC) must be applied. The LED "Operation" lights up. 3. After applying the measuring quantities the device indicates the various measuring value

which can be checked with a measuring instrument. 4. By simultaneously depressing the two buttons "Digit↑" and "Cursor→" you reach the enter-

and test mode. Please enter now the operating data according to the setting ranges men-tioned below, using the configuration masks (Sealing function "OFF").

up to version 1.9xx 5. a) Sealing function not required (simultaneous depression of the buttons "Digit↑" and

"Cursor→ " → Activation of the Automatic mode). b) Sealing function required (for further details of the proceedings please refer to the ex-

planations of the masks).

Coding ON

Sealing function

Input: Select "ON" and confirm with button "Select".

Code no. 000 Code? ?????

Enter code

Input: button "Select".

Incorrect entry [Next: Select]

Incorrect code

Input: button "Select".

Code no. 000 Break? NO

Break seal

Input: Select "YES" and confirm with button "Select.

Code no. 001 New code: ?????

Enter new code

Input: Enter new code number and confirm with button "Select".

Page 47: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

© Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 MFR 11 Manual 37140 Page 47/63

from v 2.0xx 5. Enter code number

Enter code number XXXX

Enter code number 0..9.999

On accessing the configuration mode, a code number to identify the various users is requested first. The indicated number XXXX is a random number and is confirmed with the button "Select" . If the random number is confirmed with "Select" without any modification, the code level of the device remains unchanged. In order to change the code level and to set up new code words for the users, two four-digit code numbers (0000..9999) are available. For the user level "External person" no assignment is necessary, since generally, the user has no access to the configuration level (pro-tected by the encoding).

6. After entering and checking the parameters of the device, you get back to the automatic

mode by simultaneously depressing the two buttons "Digit↑" and "Cursor→/Test" .

Page 48: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page48/63 37140

6 Appendix

6.1 Interface telegram

Number Content (words) Unit Remark 3964 MOD bus CAN bus Profibus

00 01 1 (02, 03) MUX=1, 1 0 Telegram call sign "302" Telegram type 02 03 2 (04, 05) MUX=1, 2 1 Voltage L12 V 04 05 3 (06, 07) MUX=1, 3 2 Voltage L23 V 06 07 4 (08, 09) MUX=2, 1 3 Voltage L31 V 08 09 5 (10, 11) MUX=2, 2 4 Voltage L1N V 10 11 6 (12, 13) MUX=2, 3 5 Voltage L2N V 12 13 7 (14, 15) MUX=3, 1 6 Voltage L3N V 14 15 8 (16, 17) MUX=3, 2 7 Frequency L12 Hz × 100 16 17 9 (18, 19) MUX=3, 3 8 Current L1 A Internal 18 19 10 (20, 21) MUX=4, 1 9 Current L2 A Internal 20 21 11 (22, 23) MUX=4, 2 10 Current L3 A Internal 22 23 12 (24, 25) MUX=4, 3 11 power factor cos phi dim.less × 100 Internal 24 25 13 (26, 27) MUX=5, 1 12 Active power kW Internal 26 27 14 (28, 29) MUX=5, 2 13 Reactive power kvar Internal 28 29 15 (30, 31) MUX=5, 3 14 Bus bar voltage L12 V Option Yc 30 31 16 (32, 33) MUX=6, 1 15 Bus bar frequency L12 Hz × 100 Option Yc

32 17 (34) MUX=6, 2 16 Exponent dim.los UGN 33 17 (35) MUX=6, 2 16 dim.los IGN 34 18 (36) MUX=6, 3 17 Exponent dim.los PGN/QGN 35 18 (37) MUX=6, 3 17 dim.los USS

36 37 19 (38, 39) MUX=7, 1 18 Generator active energy kWh High Word 38 39 20 (40, 41) MUX=7, 2 19 Low Word 40 41 21 (42, 43) MUX=7, 3 20 Internal alarm6 Bit 15 = 1 \

Bit 14 = 0 / Overfrequency level 2 Bit 13 = 1 \

Bit 12 = 0 / Underfrequency, level 2 Bit 11 = 1 \

Bit 10 = 0 / Overvoltage, level 2 Bit 9 = 1 \

Bit 8 = 0 / Overvoltage, level 2 Bit 7 = 1 \

Bit 6 = 0 / Internal

Bit 5 = 1 \ Bit 4 = 0 / Internal

Note (example Bit 15/14):

Bit 3 = 1 \ Bit 2 = 0 / Internal

0/1 = protective device not tripped1/0 = protection has tripped

Bit 1 = 1 \ Bit 0 = 0 / Internal

42 43 22 (44, 45) MUX=8, 1 21 Internal alarm6 Bit 15 = 1 \ Bit 14 = 0 / Overfrequency level 1

Bit 13 = 1 \ Bit 12 = 0 / Underfrequency level 1

Bit 11 = 1 \ Bit 10 = 0 / Overvoltage, level 1

Bit 9 = 1 \ Bit 8 = 0 / Undervoltage, level 1

Bit 7 = 1 \ Bit 6 = 0 / Internal

Bit 5 = 1 \ Bit 4 = 0 / Tripping df/dt

Note (example Bit 15/14):

Bit 3 = 1 \ Bit 2 = 0 / Asymmetry (voltage)

0/1 = protection has not tripped 1/0 = protection has tripped

Bit 1 = 1 \ Bit 0 = 0 / Vector shift

Page 49: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

© Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 MFR 11 Manual 37140 Page 49/63

Number Content (words) Unit Remark

3964 MOD bus CAN bus Profibus

44 45 23 (46, 47) MUX=8, 2 22 Internal alarm6 Bit 15 = 1 \ Bit 14 = 0 / Internal

Bit 13 = 1 \ Bit 12 = 0 / Internal

Bit 11 = 1 \ Bit 10 = 0 / Internal

Bit 9 = 1 \ Bit 8 = 0 / Internal

Bit 7 = 1 \ Bit 6 = 0 / Internal

Bit 5 = 1 \ Bit 4 = 0 / Internal

Note (example Bit 15/14):

Bit 3 = 1 \ Bit 2 = 0 / Internal

0/1 = protection has not tripped 1/0 = protection has tripped

Bit 1 = 1 \ Bit 0 = 0 / Interface error

46 47 24 (48, 49) MUX=8, 3 23 Internal alarm6 Bit 15 = 1 \ Bit 14 = 0 / Internal

Bit 13 = 1 \ Bit 12 = 0 / Internal

Bit 11 = 1 \ Bit 10 = 0 / Internal

Bit 9 = 1 \ Bit 8 = 0 / Internal

Bit 7 = 1 \ Bit 6 = 0 / Internal

Bit 5 = 1 \ Bit 4 = 0 / Internal

Note (example Bit 15/14):

Bit 3 = 1 \ Bit 2 = 0 / Internal

0/1 = protection has not tripped 1/0 = protection has tripped

Bit 1 = 1 \ Bit 0 = 0 / Internal

48 49 25 (50, 51) MUX=9, 1 24 Internal alarm6 Bit 15 = 1 \ Bit 14 = 0 / Internal

Bit 13 = 1 \ Bit 12 = 0 / Internal

Bit 11 = 1 \ Bit 10 = 0 / Internal

Bit 9 = 1 \ Bit 8 = 0 / Internal

Bit 7 = 1 \ Bit 6 = 0 / Internal

Bit 5 = 1 \ Bit 4 = 0 / Internal

Note (example Bit 15/14):

Bit 3 = 1 \ Bit 2 = 0 / Zero voltage

0/1 = protection has not tripped 1/0 = protection has tripped

Bit 1 = 1 \ Bit 0 = 0 / Internal

Page 50: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page50/63 37140

Number Content (words) Unit Remark

3964 MOD bus CAN bus Profibus

50 51 26 (52, 53) MUX=9, 2 25 Internal alarm6 Bit 15 = 1 \ Bit 14 = 0 / line-to-ground fault Ue, level 1

Bit 13 = 1 \ Bit 12 = 0 / Internal

Bit 11 = 1 \ Bit 10 = 0 / Internal

Bit 9 = 1 \ Bit 8 = 0 / Internal

Bit 7 = 1 \ Bit 6 = 0 / Internal

Bit 5 = 1 \ Bit 4 = 0 / line-to-ground fault Ue, level 2

Note (example Bit 15/14):

Bit 3 = 1 \ Bit 2 = 0 / Internal

0/1 = protection has not tripped 1/0 = protection has tripped

Bit 1 = 1 \ Bit 0 = 0 / Internal

6.1.1 Description of the data format

NOTE

The value is calculated from the measured value and the exponent!

Voltage 0..9.999 without sign measured in [V]

Frequency measured in [Hz × 100]

a.) Example

UG12 = 103, Exponent = 2 103 ⋅ 102 [V] = 1.030 [V] = 10.3 kV fGN = 5230 5.230 [Hz ⋅ 100] = 52,30 [Hz] = 52.3 Hz

b.) Bit change at tripping of a protective device

If one of the protective devices has responded, the corresponding bits are changed (-example: Bit 15/14 = overfrequency level 2) from not tripped (= 0/1) to tripped (= 1/0).

Page 51: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

© Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 MFR 11 Manual 37140 Page 51/63

6.1.2 Frame date for the interfaces

a.) Frame data for the procedure 3964 (TTY, RS232, RS485)

Data Length of characters...... 8 Bit Stop bit .......................... 1 Bit Parity bit ........................ 1 Bit with even parity Release condition .......... Corresponds to the status log. "1" (20 mA bei TTY) Data format ................... 16 Bit binary values Transmitting rate ........... 9.600 Baud. Other baud rates on request. The records are

transferred cyclically. Flow Interpreter RK 512 see Siemens documentation for procedure 3964.

b.) Frame data for hardware handshaking RTS/CTS (RS232, RS422)

Data Length of characters 8 Bit Stop bit .......................... 1 Bit Parity bit ........................ 1 Bit with even parity Data format ................... 16 Bit binary values Transmitting rate ........... 9.600 Baud. Other baud rates on request. The records are

transferred cyclically.

Procedure If the transmitter is ready for data transmission, it signals this to the receiver by put-ting its control wire RTS in the "ON"-status. The prerequisite of this is that no data are received (CTS = "OFF"). The receiver registers this status and signals its readiness for reception by the "ON"-status of its RTS-wire. The transmitter can then begin transmitting when it detects this "ON" status on its CTS line. As soon as the receiver withdraws its RTS signal (RTS = "OFF"), the transmitter interrupts its transmission and waits until the receiver is ready to receive again. Both, the initialization conflict (both subscribers setting the RTS wire simultaneously) and the Time-Out (one sub-scriber waiting in vain for response), have to be considered.

c.) Frame data for the MOD bus RTU slave

Parameter Transmission protocol ................................................................. MOD bus RTU slave Hardware............................................................................................ interface RS485 transmitting rate............................................................................................adjustable Slave address...............................................................................................adjustable Parity ............................................................................................................adjustable With one order, a maximum of 10 words can be read or. 4 words can be written . MOD-bus function codes 03, 04, 06 and 16 are supported.

Page 52: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page52/63 37140

d.) Frame data for the CAN bus

Parameter transmission protocol................................................................................... CAN (CiA) Hardware....................................................................................................... CAN-Bus transmitting rate............................................................................................adjustable particularity......................................................................................Bt0 = 03, Bt1 = 1C Every 200 ms a data telegram of 8 bytes is cyclically transmitted, which is configured as follows (all word formats are high Byte / low Byte):

Transmitting data ID .......................Basic-ID transmission + CAN-number Byte 1 .................Multiplexor [1..9] Byte 2 .................always 221 Byte 3/4 ..............1. data word (see table no. 1), multiplexed (MUX = 1, 1) Byte 5/6 ..............2. data word (see table no. 2), multiplexed (MUX = 1, 2) Byte 7/8 ..............3. data word (see table no. 3), multiplexed (MUX = 1, 3) Byte 9/10 ............4. data word (see table no. 4), multiplexed (MUX = 2, 1) Byte 11/12 ..........5. data word (see table no. 5), multiplexed (MUX = 2, 2) etc.

Control data Option Sb ID .......................Basic-ID control + CAN-number A data telegram of 7 Bytes is expected, which is configured as follows (all word for-mats in high Byte / low Byte): Byte 1 .................Multiplexor Byte 2/3 ..............1. data word (see table no. 1), multiplexed (MUX = 1, 1) Byte 4/5 ..............2. data word (see table no. 2), multiplexed (MUX = 1, 2) Byte 6/7 ..............3. data word (see table no. 3), multiplexed (MUX = 1, 3) etc.

Configuration data Option Sf ID ....................... ID configuration (standard value: 831)

General IDs must not be assigned twice within the system. This applies to all devices linked to the bus system. Also, all IDs adjusted at the device must have different values. Procedure for basic-ID-transmission All devices available for the bus system are assigned the same "Basic-ID Transmis-sion". This way, the information types are grouped. Example: The same basis–ID transmission = 800 is set.

Due to the different device numbers, the individual IDs can be assigned. Device number 1: ID = 801 Device number 2: ID = 802 etc. Procedure for basis-ID-control The same procedure applies to the basis-ID control. (Standard value 224)

Page 53: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

© Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 MFR 11 Manual 37140 Page 53/63

e.) Frame data for Profibus DP

Reception range Byte 0 and following ................................................Telegram according to description Example: No. 1 - Byte 0/1 = telegram call sign "302"

No. 2 - Byte 2/3 = voltage L12 No. 3 - Byte 4/5 = voltage L23 No. 4 - Byte 6/7 = voltage L31 etc. Byte 185 ....... The bit 0 becomes unstable every 2.5 seconds. This may be used as a

control to check if the interface is still working properly.

Wiring diagram

2001-06-13 Datenkopplung.skf

A

B

External devicePLC

According to the specifications,the SPS has to be possibly ter-minated with a resistor too. The Leon00d9.gsd has tobe used.

A-Line

B-Line

Stream

GND

RTS

+5 V

Prof

i bus

DP

X3

X6

X4

X5

X2

X1

220 Ohm

390 Ohm

390 Ohm

Unit of Leonhard-Reglerbau GmbHe.g. MFR 1, MFR 2, TÜG 4, etc.

6.2 Accuracy

Measuring quantity Indication Accuracy1 Range Remark

Frequency fL1, fL2, fL3 40.0..80.0 Hz 0.05 Hz 40.0..80.0 Hz

Voltage UL1, UL2, UL3, UL12, UL23, UL31 0..520 V / 0..65 kV 1 % 0..520 V / 0..65 kV Adjustable transformer ratio

Reference conditions for the recorded quantities 1 The indications apply to the following reference conditions: - Input voltage = sinusoidal rated voltage - Input current = sinusoidal rated current - Frequency = rated frequency ± 2 % - Supply voltage = rated voltage ± 2 % - Power factor ϕ = 1 - Ambient temperature = 23 °C ± 2 K - Warm-up period = 20 minutes.

Page 54: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page54/63 37140

6.3 Technical data

Environment variables - Power supply (Uaux) ...............................................................24 Vdc (18..32 Vdc) - Optional power pack (option N, Uaux) .........................75..265 Vac or 90..300 Vdc - Power consumption .................................................. max. 10 W (10 VA or 10 W) - Ambient temperature ...........................................................................-20..70 °C - Ambient humidity ..............................................................95 %, non-condensing

Measuring inputs • Voltage (Umeas)

- Measuring voltages...................[1] 69/120 Vac, [4] 230/400 Vac, [6] 398/690 Vac - Measuring voltages (UL)................................[1] max. 150 Vac, [4] max. 300 Vac - Accuracy................................................................................................... Class 1 - Linear measuring range up to .................................................................1.3 × UN - Input resistance ............................................................... [1] 0.21 MΩ, [4] 0.7 MΩ - Max. power consumption per path ........................................................... 0.15 W

• Frequency - Measuring frequency ..................................................... 50/60 Hz (40.0..80.0 Hz)

Discrete inputs - Metallically separated - Input range (UCont, digital input) ........................................................... 18..250 Vac/dc - Input resistance ..............................................................................approx. 68 kΩ

Potential-free outputs - Potential free

- Contact material........................................................................................ AgCdO - General purpose (GP) (UCont, relay output) ................................... 2.00 Aac@250 Vac 2.00 Adc@24 Vdc / 0.36 Adc@125 Vdc / 0.18 Adc@250 Vdc - Pilot duty (PD) (UCont, relay output) ......................................................................B300 1.00 Adc@24 Vdc / 0.22 Adc@125 Vdc / 0.10 Adc@250 Vdc

Interface - Metallically isolated

- Version .................................................................................................... variable

Analog outputs - for actual value output freely scalable .................................metallically separated - Resolution....................................................................................................12 Bit - Output ±0/4..20 mA.....................................................................max. load 400 Ω - Output ±0..10 Vdc..........................................................internal resistance ≤1 kΩ

Housing - Type ...............................................................................APRANORM DIN 43700

- Dimensions.............................................................................. 96 × 72 × 130 mm - Front cutout .......................................................................................91 × 67 mm - Connection .................................................................................. screw terminals depending on plug connector 1.5 mm² or 2.5 mm² use 60/75 °C copper wire only use class 1 wire only or equivalent - Weight .......................................................... depending on model, approx. 800 g

Protection - Protection system ........................................................................................ IP 21

- Front ......................................................................................... insulating surface - Disturbance test (CE) ......................tested according to applicable EN guidelines - Type approvals .........................................................................UL and cUL listed

Ordinary Locations, File No.: E212970

Page 55: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

© Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 MFR 11 Manual 37140 Page 55/63

6.4 Dimensions

Housing Type APRANORM DIN 43 700 Dimensions 96 × 72 × 130 mm Front cutout 91 × 67 mm Connection screw terminals depending on plug connector 1.5 mm² or 2.5 mm² Protection system IP 21 Weight depending on model, approx. 800 g

6150

8087 40

1

2003-01-31 | MFR 1 Dimensions r1ww-0503-ab.skf

70 75

45

16

32 17

50130

96

8

90

130

72 65

2735

6150

40

1

70 75

45

16

32 17

X5X1OptionS

OptionA6/A8

Back view withconnecting terminals

Bottom view

Back plate mountingoptionally

Front view

alte

rnat

ive

Configuration plug

Configuration plug

Configuration plug

Configuration plug

Page 56: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page56/63 37140

6.5 Wiring diagram

6.5.1 Package models su

perv

ised

sys

tem

Subject to technical modifications.

78

CB

3

Relay 2

Relay 1

2003-03-24 | MFR 11 Wiring Diagram r13ww-1303-ap.skf

1211

109

1316

1514

SC

56

7071

721

24

3

Measuring voltage L1

not measured

Blocking of watchdog function/remote acknowledgement

Synchronizing voltage L2

Synchronizing voltage L1

Synchronizing voltage L3

Measuring voltagethree-wire orfour-wire system Measuring voltage L2

Measuring voltage L3

(Measuring voltage N)

Relay 8

MFR

11

(Mul

ti Fu

nctio

n R

elay

)

Relay 3(SC: Synch-check)

Measuring voltage: 100 V AC or 400 V AC

The socket for the PC parameterization is situatedon the side of the unit. This is where the DPChas to be plugged in.

G59

/ G

59N

all

all /

NU /

G59N

0 Vdc

24 VdcPackage NU/G59N: 75..265 Vac + 90..300 Vdc

2721

2019

2226

2524

2328

3231

3029

all

Relay 4

Relay 5

Relay 6

Relay 7

Page 57: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

© Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 MFR 11 Manual 37140 Page 57/63

6.5.2 Optional models, 100 Vac and 400 Vac

Stan

dard

Stan

dard

IvYc

Measuring voltage L1

supe

rvis

ed s

yste

m

Subject to technical modifications.

not measured

715

78

670

CB

7270

7172

1

Displacement voltage uevia e-n-winding or

zero-point transformer

Blocking of watchdog function/remote acknowledgement

0 Vdc

24 VdcOption N: 75..265 Vac + 90..300 Vdc

Synchronizing voltage L2

Synchronizing voltage L1

Synchronizing voltage L3

Measuring voltagethree-wire orfour-wire system

3

24

3

Measuring voltage L2

Measuring voltage L3

(Measuring voltage N)

Relay 4

Relay 5

Relay 6

Relay 8(Option Yc + R: Synchro-Check)

Relay 7

+/- 10 VAnalog output 2 52

Poss

ible

com

bina

tions

: A1

/A2/

A3/A

4+S.

., A6

, A8,

S..

+/- 10 V

MFR

11

(> v

ersi

on 3

.0xx

; 100

/400

V m

odel

) A1

Relay 2

Relay 1

Relay 3(Option Yc: Synchro-Check)

Stan

dard

Analog output 1Common 1 + 2

2003-03-24 | MFR 11 Wiring Diagram r13ww-1303-ap.skf

1211

109

5051

0

1316

1514

+/- 20 mA

+/- 20 mA

+/- 20 mA

+/- 10 V

+/- 10 V

+/- 20 mA

+/- 20 mA

+/- 10 V

+/- 10 V

+/- 10 V

+/- 10 V

+/- 20 mA

Interface

RS232, RS422, RS485TTY, MOD bus slaveCAN bus, Profi bus DP

A6 Analog output 5

A2

A8 A4A6 A3

A8

Analog output 3

Analog output 2

Analog output 1

Analog output 4Analog output 3Common 3 + 4

Analog output 4

Analog output 8Analog output 7

Analog output 6Analog output 5Common 5 + 6

Common 7 + 8

S..

S..A.

., S.

.

Analog output 6

Alte

rnat

ivel

y

55530

5254

5550

5153

54

0

0

0

Alte

rnat

ivel

y

0

8182

8381

8283

8485

86

0

00

0

X1X2

X384

8687

X4X5

0

X6

Measuring voltage: 100 V AC or 400 V AC

The socket for the PC parameterization is situatedon the side of the unit. This is where the DPChas to be plugged in.

R

2721

2019

2226

2524

2328

3231

3029

Page 58: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page58/63 37140

6.5.3 Optional models, 690 Vac

Stan

dard

Stan

dard

supe

rvis

ed s

yste

m

Subject to technical modifications.

78

CB

0 Vdc

24 VdcOption N: 75..265 Vac + 90..300 Vdc

3

Relay 4

Relay 5

Relay 6

Relay 7

+/- 10 VAnalog output 2 52

Poss

ible

com

bina

tions

: A1

/A2/

A3/A

4+S.

., A6

, A8,

S..

+/- 10 V

A1

Relay 2

Relay 1

Stan

dard

Analog output 1Common 1 + 2

2003-03-24 | MFR 11 Wiring Diagram r13ww-1303-ap.skf

1211

109

5051

0

1316

1514

+/- 20 mA

+/- 20 mA

+/- 20 mA

+/- 10 V

+/- 10 V

+/- 20 mA

+/- 20 mA

+/- 10 V

+/- 10 V

+/- 10 V

+/- 10 V

+/- 20 mA

Interface

RS232, RS422, RS485TTY, MOD bus slaveCAN bus, Profi bus DP

A6 Analog output 5

A2

A8 A4A6 A3

A8

Analog output 3

Analog output 2

Analog output 1

Analog output 4Analog output 3Common 3 + 4

Analog output 4

Analog output 8Analog output 7

Analog output 6Analog output 5Common 5 + 6

Common 7 + 8

S..

S..A.

., S.

.

Analog output 6

Alte

rnat

ivel

y

55530

5254

5550

5153

54

0

0

0

Alte

rnat

ivel

y

0

8182

8381

8283

8485

86

0

00

0

X1X2

X384

8687

X4X5

0

X6

Relay 8

65 Measuring voltage L3

(Measuring voltage N)

1

Measuring voltagethree-wire orfour-wire system

24

3

Measuring voltage L1

Measuring voltage L2

Relay 3

Measuring voltage: 690 V AC

The socket for the PC parameterization is situatedon the side of the unit. This is where the DPChas to be plugged in.

MFR

117

0 (>

ver

sion

3.0

xx; 6

90 V

mod

el)

R

2721

2019

2226

2524

2328

3231

3029

Page 59: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

© Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 MFR 11 Manual 37140 Page 59/63

7 List of parameters

MFR 11 - Multi Function Relay List of parameters Version ____________________________________________________

Project ____________________________________________________

Device number ________________________________ Date _________

Option Parameter Line 1 - Text - Line 2

Adjustment range 100/400/690 V

Standard- setting

Customer settings

SPRACHE/LANGUAGE German/English German g e g e Coding (seal) ON/OFF OFF on off on off

BASIC SETTINGS Yc Volt.-Measuring p-n / p-to-p Phase-neutral n p n p

.. Volt.transformer secondary 50..120/50..480 V 100/400 V

.. Volt.transformer primary 0.10..65.00 kV 0.40 kV

.. Volt.transformer sec. 50..120/50..480 V 100/400 V

.. Volt.transformer prim. 0.10..65.00 kV 0.40 kV

.. Volt.transformer sec. 50..120/50..480 V 100/400 V

.. Volt.transformer prim. 0.10..65.00 kV 0.40 kV

.. Nominal voltage 5..125/10..480 V 100/400 V Yc Nomin. Frequency 40.0..70.0 Hz 50.0 Hz

CONFIGURATION OF THE PROTECTIVE DEVICES Volt.-Monitoring for Phase-neutral /

Phase to phase Phase-neutral n p n p

Yc Synchronization functions ON/OFF ON on off on off .. Synchronization df max. 0.02..0.49 Hz 0.18 Hz .. Synchronization df min. 0.00..-0.49 Hz 0.10 Hz .. Synchronization dU max. 0.1..15.0 % 6.0 % .. Synchronization Time pulse 50.. 250 ms 200 ms

Yc Circuit breaker Pick-up t. 40.. 300 ms 80 ms U Overvoltage Monitoring ON/OFF ON on off on off .. ..

Overvoltage 1 V (ph-ph) > (Phase-N) >

20..130/20..520/20..900 V 10..75/10..300/20..900 V

110/440/769 V 64/254/444 V

.. Overvoltage 1 Delay 0.02..99.98 s 0.10s

..

.. Overvoltage 2 V (ph-ph) > (Phase-N) >

20..190/20..520/20..900 V 10..75/10..300/20..900 V

120/480/839 V 64/254/485 V

.. Overvoltage 2 Delay 0.02..99.98 s 0.04s

.. Overvoltage Hysteresis 0..99 V 1/4/8 V

.. Undervoltage Monitoring ON/OFF OFF on off on off

.. Undervoltage 1 V(ph-ph) < 20..130/20..520/20..900 V 90/360/629 V

.. (Phase-N) < 10..75/10..300/20..900 V 51/207/363 V

.. Undervoltage 1 Delay 0.02..99.98 s 0.10s

.. Undervoltage 2 V(ph-ph) < 20..190/20..520/20..900 V 80/320/559 V

.. (Phase-N) < 10..75/10..300/20..900 V 46/184/323 V

.. Undervoltage 2 Delay 0.02..99.98 s 0.04s U Undervoltage Hysteresis 0..99 V 1/4/8 V

Un Zero-voltage Monitoring ON/OFF ON on off on off .. Zero-voltage V(ph-ph) 3..130/12..520/20..900 V 8/32/55 V .. (Phase-N) 2..75/6..300/20..900 V 4/18/31 V .. Zero-voltage Delay 0.02..99.98 s 0.25s

Un Zero-voltage Hysteresis 0..99 V 1/4/8 V U Asymmetry- Monitoring ON/OFF ON on off on off .. Asymmetry release v. 0..99 V 10/40/69 V .. Asymmetry Delay 0.02..99.98 s 2.00s .. Asymmetry Hysteresis 0..99 V 1/4/6 V .. Overfrequency- Monitoring ON/OFF ON on off on off .. Overfrequency 1 f > 40,0..80,0 Hz 50.20 Hz .. Overfrequency 1 Delay 0.02..99.98 s 0.10s .. Overfrequency 2 f > 40.0..80.0 Hz 51.00 Hz .. Overfrequency 2 Delay 0.02..99.98 s 0.04s .. Overfrequency Hysteres. 0.01..9.99 Hz 0.05 Hz .. Underfrequency- Monitoring ON/OFF ON on off on off .. Underfrequency 1 f > 30.0..80.0 Hz 49.80 Hz .. Underfrequency 1 Delay 0.02..99.98 s 0.1s .. Underfrequency 2 f > 30.0..80.0 Hz 49.00 Hz .. Underfrequency 2 Delay 0.02..99.98 s 0.04s U Underfrequency Hysteres. 0.01..9.99 Hz 0.05 Hz

Page 60: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page60/63 37140

Option Parameter

Line 1 - Text - Line 2 Adjustment range 100/400/690 V

Standard- setting

Customer settings

CONFIGURATION OF THE PROTECTIVE DEVICES

V Phase shift monitoring ON/OFF ON on off on off .. ..

Phase shift mon. Phase-neutral / Phase to phase

Phase-neutral n p n p

.. Phase-jump value (One phase) 2..90 ° 30° V Phase-jump value (3-phase) 2..90 ° 8° D df/dt- Monitoring ON/OFF ON n p n p .. df/dt Release > 1.0..9.9 Hz/s 2,5 Hz/s D df/dt Delay T= 0.1..9.9 s 0.1s Iv Earth fault Ue monitoring ON/OFF ON n p n p .. Earth fault Ue> Release 3..100 % 10 % .. Earth fault Ue> Delay 0.02..99.98 s 0.1s .. Earth fault Ue>> Release 3..100 % 15 % .. Earth fault Ue>> Delay 0.02..99.98 s 2.5s

CONFIGURATION OF INFORMATION External Clearing ON/OFF ON on off on off Auto-clearing Relays ON/OFF ON on off on off

U Release delay Overvolt. 0.02..99.98 s 0.10s U Release delay Und.volt. 0.02..99.98 s 0.10s U Release delay Asymmetry 0.02..99.98 s 0.10s

Un Release delay Zerovolt. 0.02..99.98 s 0.10s U Release delay Overfreq. 0.02..99.98 s 0.10s U Release delay Underfrq. 0.02..99.98 s 0.10s V Release delay Phase jmp 0.02..99.98 s 0.10s D Release delay df/dt 0.02..99.98 s 0.20s Iv Release delay Earth.Ue 0.02..99.98 s 0.10s

Auto-clearing Display ON/OFF ON on off on off Clearing display after 1..99 s 01S

CONFIGURATION OF THE RELAYS Change relay- allocation? YES/NO YES Y N Y N

Yc Funct. relay 12 (R=releases) R/A RA Funct. relay 123 (R=releases) R/A RAA

R Funct. relay 45 ((R=releases) R/A AA R Funct. relay 678 (R=releases) R/A AAA

R+Yc Funct. relay 67 (R=releases) R/A AA U Overvoltage 1 to relay 0..3/8 0002 U Overvoltage 2 to relay 0..3/8 0002 U Undervoltage 1 to relay 0..3/8 0002 U Undervoltage 2 to relay 0..3/8 0002

Un Zero-voltage to relay 0..3/8 0002 U Asymmetry to relay 0..3/8 0002 U Overfrequency 1 to relay 0..3/8 0003 U Overfrequency 2 to relay 0..3/8 0003 U Underfrequency 1 to relay 0..3/8 0003 U Underfrequency 2 to relay 0..3/8 0003 V Phase shift to relay 0..3/8 0003 D df/dt to relay 0..3/8 0003 Iv Earth fault Ue> to relay 0..3/8 0003 Iv Earth fault Ue>> to relay 0..3/8 0003

Collect response to relay 0..3/8 0

Page 61: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

© Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 MFR 11 Manual 37140 Page 61/63

Option Parameter

Line 1 - Text - Line 2 Adjustment range 100/400/690 V

Standard- setting

Customer settings

ANALOG OUTPUTCONFIGURATION

A2/3/6 A1/4/8

..

..

Analog. output 1 OFF 0..10 V

-10..+10 V

-10..+10 V OFF 0..10 -/+10

OFF 0..10 -/+10

..

..

..

..

OFF 0 .. 20 mA 4 .. 20 mA

-20 .. +20 mA

-20 .. +20 mA OFF 0..20 4..20 -/+20

OFF 0..20 4..20 -/+20

.. Analog. output 1 U L1-L2

..

.. Analog. output 0/-10 V 0/4/-20 mA

0 V

A2/3/6 A1/4/8

Analog. output 10 V 20 mA

see list at the end of this list of parameters 400 V

A3/6 A4/8

..

..

Analog. output 2 OFF 0..10 V

-10..+10 V

-10..+10 V OFF 0..10 -/+10

OFF 0..10 -/+10

..

..

..

..

OFF 0 .. 20 mA 4 .. 20 mA

-20 .. +20 mA

-20 .. +20 mA OFF 0..20 4..20 -/+20

OFF 0..20 4..20 -/+20

.. Analog. output 2 U L2-L3

..

.. Analog. output 0/-10 V 0/4/-20 mA

0 V

A3/6 A4/8

Analog. output 10 V 20 mA

see list at the end of this list of parameters 400 V

A3/6 A4/8

..

..

Analog. output 3 OFF 0..10 V

-10..+10 V

-10..+10 V OFF 0..10 -/+10

OFF 0..10 -/+10

..

..

..

..

OFF 0 .. 20 mA 4 .. 20 mA

-20 .. +20 mA

-20 .. +20 mA OFF 0..20 4..20 -/+20

OFF 0..20 4..20 -/+20

.. Analog. output 3 U L3-L1

..

.. Analog. output 0/-10 V 0/4/-20 mA

0 V

A3/6 A4/8

Analog. output 10 V 20 mA

see list at the end of this list of parameters 400 V

A4/6/8 .. ..

Analog. output 4 OFF 0..10 V

-10..+10 V

-10..+10 V OFF 0..10 -/+10

OFF 0..10 -/+10

..

..

..

..

OFF 0 .. 20 mA 4 .. 20 mA

-20 .. +20 mA

-20 .. +20 mA OFF 0..20 4..20 -/+20

OFF 0..20 4..20 -/+20

.. Analog. output 4 Frequency

..

.. Analog. output 0/-10 V 0/4/-20 mA

45.00 Hz

.. A4/6/8

Analog. output 10 V 20 mA

see list at the end of this list of parameters 55.00 Hz

Page 62: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page62/63 37140

Option Parameter

Line 1 - Text - Line 2 Adjustment range 100/400/690 V

Standard- setting

Customer settings

ANALOG OUTPUT CONFIGURATION

A6/8 .. ..

Analog. output 5 OFF 0..10 V

-10..+10 V

-10..+10 V OFF 0..10 -/+10

OFF 0..10 -/+10

..

..

..

..

OFF 0 .. 20 mA 4 .. 20 mA

-20 .. +20 mA

-20 .. +20 mA OFF 0..20 4..20 -/+20

OFF 0..20 4..20 -/+20

.. Analog. output 5 U L1-N

..

.. Analog. output 0/-10 V 0/4/-20 mA

0 V

.. A6/8

Analog. output 10 V 20 mA

see list at the end of this list of parameters 230 V

A6/8 .. ..

Analog. output 6 OFF 0..10 V

-10..+10 V

-10..+10 V OFF 0..10 -/+10

OFF 0..10 -/+10

..

..

..

..

OFF 0 .. 20 mA 4 .. 20 mA

-20 .. +20 mA

-20 .. +20 mA OFF 0..20 4..20 -/+20

OFF 0..20 4..20 -/+20

.. Analog. output 6 U L2-N

..

.. Analog. output 0/-10 V 0/4/-20 mA

0 V

A6/8 Analog. output 10 V 20 mA

see list at the end of this list of parameters 230 V

A8 .. ..

Analog. output 7 OFF 0..10 V

-10..+10 V

-10..+10 V OFF 0..10 -/+10

OFF 0..10 -/+10

..

..

..

..

OFF 0 .. 20 mA 4 .. 20 mA

-20 .. +20 mA

-20 .. +20 mA OFF 0..20 4..20 -/+20

OFF 0..20 4..20 -/+20

.. Analog. output 7 U l3-N

..

.. Analog. output 0/-10 V 0/4/-20 mA

0 V

.. A8

Analog. output 10 V 20 mA

see list at the end of this list of parameters 230 V

A8 .. ..

Analog. output 8 OFF 0..10 V

-10..+10 V

-10..+10 V OFF 0..10 -/+10

OFF 0..10 -/+10

..

..

..

..

OFF 0 .. 20 mA 4 .. 20 mA

-20 .. +20 mA

-20 .. +20 mA OFF 0..20 4..20 -/+20

OFF 0..20 4..20 -/+20

.. Analog. output 8 U L-L max value

..

.. Analog. output 0/-10 V 0/4/-20 mA

0 V

.. A8

Analog. output 10 V 20 mA

see list at the end of this list of parameters 400 V

INTERFACE CONFIGURATION S3964 Data block Rk512 (3964) 0..255 0 S3964 Data word Rk512 (3964) 0..255 0 SPRO Device number Profibus 0..126 1 SMOD Device number MOD-Bus 0..255 1

..

.. Baudrate 1.200 / 2.400 / 4.800 /

9.600 / 19.200 9.600

.. Parity none / even / odd none

.. Stopbits one/two one SMOD Delay to send MOD-Bus 0.2.. 50,0 ms 0,0 ms SCAN Device number CAN-Bus 1..8 1

.. Baudrate 125/250/500 kBaud 125 kBaud

.. Base-ID (send) 0..2.015 800

.. Base-ID (remote) 0..2.015 224 SCAN ID (parametriz.) 0..2.015 831

Sb Serial control ON/OFF ON E A E A .. Serial interface Monitoring ON/OFF ON E A E A .. Interface fault to relay 0..3/0..8 0003

Sb Inhibit via Interface ON/OFF ON E A E A

Page 63: MFR 11 - Protection Relay - Precision Controls · MFR 11 Manual © Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 Page2/63 37140 Table of Contents Page 1

© Woodward Governor Company Leonhard-Reglerbau GmbH, +49 (0) 711 789 54-0 MFR 11 Manual 37140 Page 63/63

7.1 List of the adjustment ranges for the analog outputs

Value Lower and upper setting value 0 V, -10 V

0 mA, 4 mA, -20 mA 10 V, 20 mA

U L1-N 0..65.000 V U L2-N 0..65.000 V U L3-N 0..65.000 V U L-N mean value 0..65.000 V U L-N Max value 0..65.000 V U L-N Min value 0..65.000 V U L1-L2 0..65.000 V U L2-L3 0..65.000 V U L3-L1 0..65.000 V U L-L mean value 0..65.000 V U L-L Max value 0..65.000 V U L-L Min value 0..65.000 V Frequency 40.0..80.0 Hz