Engr. Eduard MercadoElectrical Design Team
MERALCO Standards:Electrical Design
![Page 2: MERALCO Standards · or power fuse elbow arrester padmounted transformer ct meter to customer’s main secondary circuit breaker cable termination underground primary cables incoming](https://reader033.vdocuments.us/reader033/viewer/2022051511/601a207eaf8bdc2d8471b3ad/html5/thumbnails/2.jpg)
Electrical Design Standards
![Page 3: MERALCO Standards · or power fuse elbow arrester padmounted transformer ct meter to customer’s main secondary circuit breaker cable termination underground primary cables incoming](https://reader033.vdocuments.us/reader033/viewer/2022051511/601a207eaf8bdc2d8471b3ad/html5/thumbnails/3.jpg)
SERVICE VOLTAGES
• SECONDARY METERED - 240 V, 400 V, 460 V • PRIMARY METERING -34.5 kV, 13.8 kV (portions
of Cavite & Bulacan), 115 kV (Subtransmission)
FACILITIES
1. OVERHEAD• POLE MOUNTED TRANSFORMERS• PADMOUNT TRANSFORMERS• VAULT TYPE DT
2. UNDERGROUND• PADMOUNT TRANSFORMERS• VAULT TYPE DT
![Page 4: MERALCO Standards · or power fuse elbow arrester padmounted transformer ct meter to customer’s main secondary circuit breaker cable termination underground primary cables incoming](https://reader033.vdocuments.us/reader033/viewer/2022051511/601a207eaf8bdc2d8471b3ad/html5/thumbnails/4.jpg)
SURGE ARRESTER
FUSE CUTOUT OR POWER FUSE
ELBOWARRESTER
PADMOUNTED TRANSFORMER
CT
METER
TO CUSTOMER’S MAIN SECONDARY CIRCUIT BREAKER
CABLE TERMINATION
UNDERGROUND PRIMARY CABLES
INCOMING OVERHEAD LINE
TERMINAL POLE
EPMC
Single Line Diagram
OVERHEAD LINE FEEDING A TRANSFORMER VAULT
TRANSFORMER VAULT TO BE CONSTRUCTED BY THE APPLICANT/CUSTOMER BASED ON MERALCO STANDARD
ALL CIVIL WORKS, i.e., CONCRETE-ENCASED PVC DUCTS & FITTINGS, TO BE PROVIDED AND INSTALLED BY THE APPLICANT/CUSTOMER
SECONDARY CABLES
![Page 5: MERALCO Standards · or power fuse elbow arrester padmounted transformer ct meter to customer’s main secondary circuit breaker cable termination underground primary cables incoming](https://reader033.vdocuments.us/reader033/viewer/2022051511/601a207eaf8bdc2d8471b3ad/html5/thumbnails/5.jpg)
Single Line Diagram
ELBOWARRESTER
PADMOUNTED TRANSFORMER
CT
METER
UNDERGROUND PRIMARY CABLES
UNDERGROUND FEEDER
PADMOUNTED SWITCHGEAR
EPMC
UNDERGROUND LINE FEEDING A TRANSFORMER VAULT
ALL CIVIL WORKS, i.e., CONCRETE-ENCASED PVC DUCTS & FITTINGS, TO BE PROVIDED AND INSTALLED BY THE APPLICANT/CUSTOMER
TRANSFORMER VAULT TO BE CONSTRUCTED BY THE APPLICANT/CUSTOMER BASED ON MERALCO STANDARD
SECONDARY CABLES
TO CUSTOMER’S MAIN SECONDARY CIRCUIT BREAKER
![Page 6: MERALCO Standards · or power fuse elbow arrester padmounted transformer ct meter to customer’s main secondary circuit breaker cable termination underground primary cables incoming](https://reader033.vdocuments.us/reader033/viewer/2022051511/601a207eaf8bdc2d8471b3ad/html5/thumbnails/6.jpg)
34.5 kV
OH Line
Vault
Type
DT's
(SEE
NOTE)
Single Line Diagram - 2 Banks
w/ 4-Way Junction
LoadLoad
Transformer
Vault
Elbow
Arrester
Lightning
ArresterFuse Cut-Out
or Power Fuse
4-Way Loadbreak
Junction, 200A
PRIMARY
SECONDARY
![Page 7: MERALCO Standards · or power fuse elbow arrester padmounted transformer ct meter to customer’s main secondary circuit breaker cable termination underground primary cables incoming](https://reader033.vdocuments.us/reader033/viewer/2022051511/601a207eaf8bdc2d8471b3ad/html5/thumbnails/7.jpg)
4-WAY / 4-POINT JUNCTION
![Page 8: MERALCO Standards · or power fuse elbow arrester padmounted transformer ct meter to customer’s main secondary circuit breaker cable termination underground primary cables incoming](https://reader033.vdocuments.us/reader033/viewer/2022051511/601a207eaf8bdc2d8471b3ad/html5/thumbnails/8.jpg)
Transformers for Vault Installation
Three-phase, 34.5 GrdY/20 kV or 13.2 GrdY/7.62 kV
Available in either 240Y/139-V secondary (75-1000 kVA) or 480Y/277-V secondary (500-2000 kVA)
416Y/240 V secondary (500-1000 kVA)
Meralco-Supplied Padmounted Transformers
![Page 9: MERALCO Standards · or power fuse elbow arrester padmounted transformer ct meter to customer’s main secondary circuit breaker cable termination underground primary cables incoming](https://reader033.vdocuments.us/reader033/viewer/2022051511/601a207eaf8bdc2d8471b3ad/html5/thumbnails/9.jpg)
Transformers for Vault Installation
Deadfront primary
Less flammable liquid filled
Completely self-protected with fuses
Provided with loop sectionalizing switch
Meralco-Supplied Padmounted Transformers
![Page 10: MERALCO Standards · or power fuse elbow arrester padmounted transformer ct meter to customer’s main secondary circuit breaker cable termination underground primary cables incoming](https://reader033.vdocuments.us/reader033/viewer/2022051511/601a207eaf8bdc2d8471b3ad/html5/thumbnails/10.jpg)
Transformers for Vault Installation
Single-phase, 34.5 GrdY/20 kV or 13.2 GrdY/7.62 kV
Available in either 139/277-V secondary or 240/120-V secondary
Available in 167 – 333 kVA
Meralco-Supplied Deadfront Distribution Transformer
![Page 11: MERALCO Standards · or power fuse elbow arrester padmounted transformer ct meter to customer’s main secondary circuit breaker cable termination underground primary cables incoming](https://reader033.vdocuments.us/reader033/viewer/2022051511/601a207eaf8bdc2d8471b3ad/html5/thumbnails/11.jpg)
Transformers for Vault Installation
Deadfront primary
Less flammable liquid filled
Provided with standard DT accessories
Round tank construction
Meralco-Supplied Deadfront Distribution Transformer
![Page 12: MERALCO Standards · or power fuse elbow arrester padmounted transformer ct meter to customer’s main secondary circuit breaker cable termination underground primary cables incoming](https://reader033.vdocuments.us/reader033/viewer/2022051511/601a207eaf8bdc2d8471b3ad/html5/thumbnails/12.jpg)
Standard Vault
Location
![Page 13: MERALCO Standards · or power fuse elbow arrester padmounted transformer ct meter to customer’s main secondary circuit breaker cable termination underground primary cables incoming](https://reader033.vdocuments.us/reader033/viewer/2022051511/601a207eaf8bdc2d8471b3ad/html5/thumbnails/13.jpg)
PREFERRED VAULT LOCATION:
• PREFERRED VAULT LOCATION SHALL BE ON THE GROUND FLOOR
• SECOND FLOOR MAY BE ALLOWED (FOR VAULT TYPE DT’s AND PADMOUNTED XF WITH HOISTING FACILITIES)
• FIRST BASEMENT MAY BE ALLOWED FOR BUILDINGS WITH MULTIPLE BASEMENT
![Page 14: MERALCO Standards · or power fuse elbow arrester padmounted transformer ct meter to customer’s main secondary circuit breaker cable termination underground primary cables incoming](https://reader033.vdocuments.us/reader033/viewer/2022051511/601a207eaf8bdc2d8471b3ad/html5/thumbnails/14.jpg)
• THE VAULT SHALL BE LOCATED ON PERIMETER OF THE BUILDING
• ADJACENT TO STREET/ROADWAY ACCESSIBLE TO MERALCO TRUCKS AND CRANE TRUCK
MINIMUM ROAD WIDTH : 6.5 METERS
PREFERRED VAULT LOCATION:
![Page 15: MERALCO Standards · or power fuse elbow arrester padmounted transformer ct meter to customer’s main secondary circuit breaker cable termination underground primary cables incoming](https://reader033.vdocuments.us/reader033/viewer/2022051511/601a207eaf8bdc2d8471b3ad/html5/thumbnails/15.jpg)
Standard Vault
Specifications/Requirements
![Page 16: MERALCO Standards · or power fuse elbow arrester padmounted transformer ct meter to customer’s main secondary circuit breaker cable termination underground primary cables incoming](https://reader033.vdocuments.us/reader033/viewer/2022051511/601a207eaf8bdc2d8471b3ad/html5/thumbnails/16.jpg)
STANDARD SPECIFICATION/REQUIREMENTS:
• WALLS AND ROOF SHALL BE MADE OF REINFORCED CONCRETE NOT LESS THAN 150MM
• THERE SHALL BE NO OPENING FROM THE VAULT TO ANY PART OF THE BUILDING INTERIOR
• 150 MM DOORSILL IS REQUIRED FOR LIQUID CONFINEMENT
• PROVISION FOR ADEQUATE AND PERMANENT VENTILATION (EXHAUST FAN-TEMP CONTROLLED RATED ¾ HP, 71 CuM/Min (2500 CFM))
• CLEAR HEADROOM SHALL NOT BE LESS THAN 4M FROM THE BOTTOM OF THE I-BEAM TO MAINTAIN A 30°SLING ANGLE FROM THE VERTICAL (HOISTING FACILITY)
![Page 17: MERALCO Standards · or power fuse elbow arrester padmounted transformer ct meter to customer’s main secondary circuit breaker cable termination underground primary cables incoming](https://reader033.vdocuments.us/reader033/viewer/2022051511/601a207eaf8bdc2d8471b3ad/html5/thumbnails/17.jpg)
• DUCTS (PRIMARY AND SECONDARY) – 110 MM DIAMETER, THICK WALLED, RED ORANGE COLOR, UNPLASTICIZED POLYVINYL CHLORIDE (UPVC) IN ACCORDANCE WITH PNS 14. IT SHOULD BE ENCASED IN CONCRETE
• PROVISION OF PERSONNEL ACCESS DOORWAY DIRECTLY ACCESSIBLE FROM OUTSIDE OF THE BUILDING
STANDARD SPECIFICATION/REQUIREMENTS:
![Page 18: MERALCO Standards · or power fuse elbow arrester padmounted transformer ct meter to customer’s main secondary circuit breaker cable termination underground primary cables incoming](https://reader033.vdocuments.us/reader033/viewer/2022051511/601a207eaf8bdc2d8471b3ad/html5/thumbnails/18.jpg)
Customer Vault Layouts
for
Transformers (pdt & vt)
![Page 19: MERALCO Standards · or power fuse elbow arrester padmounted transformer ct meter to customer’s main secondary circuit breaker cable termination underground primary cables incoming](https://reader033.vdocuments.us/reader033/viewer/2022051511/601a207eaf8bdc2d8471b3ad/html5/thumbnails/19.jpg)
MINIMUM DIMENSION
PADMOUNT TRANSFORMER IN VAULT
LOCATION 1-BANK 2-BANKS
Ground Floor(W) 5m X (D) 4m
X (H) 3m(W) 8m X (D) 4m
X (H) 3m
2nd Floor(W) 5m X (D) 6m
X (H) 4m*(W) 8m X (D) 6m
X (H) 4m*
1st Basement(W) 5m X (D) 6m
X (H) 3m(W) 8m X (D) 6m
X (H) 3m
NOTES: [1] W = Width; D = Depth; H = Height (Headroom)
EXCEPTION: For 2nd floor transformer vault with a hatchway, the depth requirement is 8m.
*[2] 4m vertical distance measured from the bottom of the I-beam to the floor is
required when hoisting the transformer
Requirements for Customer Vault
![Page 20: MERALCO Standards · or power fuse elbow arrester padmounted transformer ct meter to customer’s main secondary circuit breaker cable termination underground primary cables incoming](https://reader033.vdocuments.us/reader033/viewer/2022051511/601a207eaf8bdc2d8471b3ad/html5/thumbnails/20.jpg)
MINIMUM DIMENSION
DEADFRONT (VAULT TYPE) DISTRIBUTION TRANSFORMERS
NOTE: W = Width; D = Depth; H = Height (Headroom)
LOCATION 1-BANK 2-BANKS
Ground Floor(W) 5m X (D) 4m
x (H) 3m(W) 6m X (D) 6m
X (H) 3m
2nd Floor(W) 5m X (D) 4m
x (H) 3m(W) 6m X (D) 6m
X (H) 3m
1st Basement(W) 5m X (D) 4m
x (H) 3m(W) 6m X (D) 6m
X (H) 3m
Requirements for Customer Vault
![Page 21: MERALCO Standards · or power fuse elbow arrester padmounted transformer ct meter to customer’s main secondary circuit breaker cable termination underground primary cables incoming](https://reader033.vdocuments.us/reader033/viewer/2022051511/601a207eaf8bdc2d8471b3ad/html5/thumbnails/21.jpg)
PRIMARY METERING
![Page 22: MERALCO Standards · or power fuse elbow arrester padmounted transformer ct meter to customer’s main secondary circuit breaker cable termination underground primary cables incoming](https://reader033.vdocuments.us/reader033/viewer/2022051511/601a207eaf8bdc2d8471b3ad/html5/thumbnails/22.jpg)
SINGLE LINE DIAGRAM FOR PRIMARY METERING (OH)
![Page 23: MERALCO Standards · or power fuse elbow arrester padmounted transformer ct meter to customer’s main secondary circuit breaker cable termination underground primary cables incoming](https://reader033.vdocuments.us/reader033/viewer/2022051511/601a207eaf8bdc2d8471b3ad/html5/thumbnails/23.jpg)
SINGLE LINE DIAGRAM FOR PRIMARY METERING (UG)
![Page 24: MERALCO Standards · or power fuse elbow arrester padmounted transformer ct meter to customer’s main secondary circuit breaker cable termination underground primary cables incoming](https://reader033.vdocuments.us/reader033/viewer/2022051511/601a207eaf8bdc2d8471b3ad/html5/thumbnails/24.jpg)
TYPICAL PRIMARY METERING ARRANGEMENT
![Page 25: MERALCO Standards · or power fuse elbow arrester padmounted transformer ct meter to customer’s main secondary circuit breaker cable termination underground primary cables incoming](https://reader033.vdocuments.us/reader033/viewer/2022051511/601a207eaf8bdc2d8471b3ad/html5/thumbnails/25.jpg)
![Page 26: MERALCO Standards · or power fuse elbow arrester padmounted transformer ct meter to customer’s main secondary circuit breaker cable termination underground primary cables incoming](https://reader033.vdocuments.us/reader033/viewer/2022051511/601a207eaf8bdc2d8471b3ad/html5/thumbnails/26.jpg)
3 Way RMU with Metering Module
![Page 27: MERALCO Standards · or power fuse elbow arrester padmounted transformer ct meter to customer’s main secondary circuit breaker cable termination underground primary cables incoming](https://reader033.vdocuments.us/reader033/viewer/2022051511/601a207eaf8bdc2d8471b3ad/html5/thumbnails/27.jpg)
3 Way RMU with Metering Module
![Page 28: MERALCO Standards · or power fuse elbow arrester padmounted transformer ct meter to customer’s main secondary circuit breaker cable termination underground primary cables incoming](https://reader033.vdocuments.us/reader033/viewer/2022051511/601a207eaf8bdc2d8471b3ad/html5/thumbnails/28.jpg)
Thank you.