MENTOR SOFTWARE OVERVIEW 

Page 2: Mentor 12 Software Overview - 1964978058.rsc.cdn77.org1964978058.rsc.cdn77.org/wp-content/uploads/2015/12/Mentor-12... · FAULT Three‐state Fault ... Playback and processing of

 

©EuroSMC, S.A. November 2014 

  

 

      MENTOR 12     SOFTWARE ELEMENTS 

MEN

TOR 12 

ROOTS 

OVER

CURREN

ROOTS 

DISTA

NCE 

ROOTS 

DIFFEREN

TIAL 

ROOTS VOLTAGE 

ROOTS 

FREQ

UEN

CY 

SOFTWARE/MODULES  FUNCTIONALITY 

FULL DIRECT CONTROL  Powerful, fast and easy manual testing, no PC needed             

CONFIGURATION CONTROL  Easy control of all Power source combinations, Binary I/O configurations, visual connection guide             

ASSISTED CONTROL  NEW!   On screen direct regulation of complex magnitudes: Impedance, Fault, Power (P,Q,S, Power Factor), Sequences (Symmetrical components), Vline and Homopolar Voltage,  Open Delta. Also available in State Sequencer. 

           

VECTOR VIEW  NEW!   Full control at your fingertips of individual or grouped phasors, with module and angle lock functions.             

TEST FUNCTIONS  The most complete Built‐in Test functions, with on‐screen graphic configuration, to carry out typical test for protection relays and protection schemes. 

           

FAULT  Three‐state Fault function, pre‐fault, fault and post‐fault configuration             

RAMPS  Single or double Ramps, upward or downward, of any MENTOR parameter             

PULSE RAMP  Pulse ramping with preset condition state, of any output parameter             

BINARY SEARCH  Effective search of trip values through adaptive pulses             

STATE SEQUENCER  A simple programmable multi‐step tool to test protection schemes and logical sequences.             

STATE SEQUENCER WITH ASSISTED CONTROL 

NEW!   The Assisted Control is now available in the State Sequencer, allowing the programming of complex magnitudes sequences.             

FAULT PLAYBACK (COMTRADE)  Playback and processing of COMTRADE files and similar, for transient fault analysis and relays reaction             

RESULTS MANAGER  Results and Test saving in USB pendrive, semi‐automatic routines tests collection. Test Reporting in PC with Mentor Report Viewer.             

REMOTE CONTROL Local mode or remote control, through serial or Ethernet connection             

BATTERY SIMULATOR Auxiliary DC supply setting for relay powering             

HARMONICS New control to select the desired Harmonic content and angle in each channel             

METER & MEASURING  Testing of transducers, counters, measuring devices, analogue and binary measurement             

LOGGER  On‐screen event list, automatic recording for all events, such as sources switching and I/O status change.             

SMART TEST TOOLS*1 

Importing RIO files and ROOTS test, execution of tests with no need of PC, just a USB pendrive, and storage of results             

IEC‐61850 – GOOSE *2 

Testing with GOOSE according to IEC 61850, with configuration tool and no need of PC             

POWER SAVING TRIMMER  Energy saving system with auto‐adjustment to load and  regulation of working cycle              

INTERNET UPGRADING & MAINTENANCE 

All MENTOR elements can be upgraded via internet, update and diagnostics             

CAPE TEST FILES CONVERTER  SS1 CAPE converter and execution of this network simulation program files             

BINARY I/O MONITOR & CONFIGURATION 

On‐screen display of all binary I/O status and flexible configuration              FREE LIFETIME UPDATES*3  EuroSMC free unlimited updates, new releases and modules             DEVICES CONFIGURATION,  DEVICES MANAGEMENT & TEST LIST 

Data settings and Devices template configuration. Several Test Modules added to every device, each module with its specific relay´s settings, protective elements and Test List. Easy Device Management and search of devices with a quick classification tool. 

           

AUTOMATIC REPORTING & REPORT CONFIGURATION 

Immediate reporting in PDF format, or XML, with selection of data to display. NEW!   Now available the report export to Word editable RTF format. 

           DATABASE MANAGEMENT  Administration of Databases of Devices with relay definitions, test values, test 

routines, results and reports. Databases can be exported to XML.            

RIO FILES IMPORT  Direct import of RIO files , relay definitions and settings             

Page 3: Mentor 12 Software Overview - 1964978058.rsc.cdn77.org1964978058.rsc.cdn77.org/wp-content/uploads/2015/12/Mentor-12... · FAULT Three‐state Fault ... Playback and processing of

 

©EuroSMC, S.A. November 2014 

     

 

 

          MENTOR 12                    SOFTWARE ELEMENTS (Cont’d) 

MEN

TOR 12 

ROOTS 

OVER

CURREN

ROOTS 

DISTA

NCE 

ROOTS 

DIFFEREN

TIAL 

ROOTS VOLTAGE 

ROOTS 

FREQ

UEN

CY 

SOFTWARE/MODULES  FUNCTIONALITY 

AUTOMATIC IMPORT OF RELAY SETTINGS TOOL 

NEW! Tool to automate the import of variables/settings and/or update existing ones, from a text file, using Pattern recognition and Templates. Source file can be generated by the Relay software, or from the Engineering file issued to adjust the device settings 

           

DATA SETTINGS PANEL  NEW!  Besides the edition of the data associated with the device (Formulas, Custom and Default Variables) included in previous versions,  this new Data Settings window includes a tree classification system, displayed to the user´s convenience 

           

GENERAL REPORT  NEW! Tool to select and combine the different reports of executed tests in different modules, in a single General Report, for the selected device. 

           CHARACTERISTICS EDITOR & TEMPLATES 

Powerful Graphic Editor for protective areas and curves of Elements, with pre‐defined templates 

           FORMULAS   

User‐programmable test engine in Visual Basic.Net language.Function definition window 

           FAULT CALCULATION & SEQUENTIAL TEST EXECUTION 

Accurate fault calculation and Test Assessment for the specified settings in every test point sequence. 

           CLICK SEQUENCE   Automatic sequential injection of test points, with pre‐fault, Fault and Post‐

Fault conditions, and assessing of results.            

PICK UP/DROP OUT   Finding of the pickup and dropout values of the active elements in the relay under test 

         RECLOSE   Verification of the relays reclose function, with any number of reclosing cycles       COLD LOAD   Evaluation of protection devices that support the cold load function       SOTF (Switch On To Fault)   Performance of the relay during a SOTF condition       I2/I1 RATIO   Generation of faults to evaluate relays with this function       CB FAILURE   CB failure scheme evaluation        FUSE FAIL   Test elements behavior during the Fuse Fail condition       SELECTIVE OVERCURRENT LOGIC  Verify the correct logic behavior of the protective devices on signal reception 

with forward faults and reverse faults      

RESET TIME   Testing of reset timing function       DISTANCE SEARCH   Impedance element evaluation to find the boundary values of distance zones in 

selected directions.      

DISTANCE VERIFICATION   Impedance element evaluation without zone geometry       EVOLVING FAULT   Evaluation of relay´s behavior under evolving fault conditions during a single‐

phase recloses cycle.      

TRIP ON RECLOSE   Test to evaluate the relay´s trip acceleration function during a reclose cycle.       ZONE 1 EXTENSION TEST  Evaluation of the relay when this clearing‐fault function is active       LOSS OF LOAD   Test module to evaluate LOL function in diverse circumstances (also called 

Remote End Opened)      

LOAD ENCROACHMENT   Module to verify the proper operation of a distance relay under heavy load conditions. 

     DIFFERENTIAL VERIFICATION   Test to check the consistence between the protected device, the relay settings, 

the Differential module's setup, and connections.        

DIFFERENTIAL SEARCH  Test to find the boundary trip values which corresponds with the characteristic of the relay 

       DIFF. HARMONICS RESTRAINT  Evaluates the response of the relay to the harmonic content variation in 

measured current signals        

SET OF DIFFERENTIAL MODULES   Differential 87C Classic; Differential 87T Transformer; Differential 87GM Generator / Motor; Differential Bar 87B  

       

SET OF VOLTAGE MODULES  Single Phase and 3‐Phase Voltages Modules to test the operation of protective devices with functions 27, 47 and 59 

         PICK UP/DROP OUT FREQUENCY  Test to search for pickup and drop out values of the active frequency elements         

Page 4: Mentor 12 Software Overview - 1964978058.rsc.cdn77.org1964978058.rsc.cdn77.org/wp-content/uploads/2015/12/Mentor-12... · FAULT Three‐state Fault ... Playback and processing of

 

©EuroSMC, S.A. November 2014 

     

 

*1 ‐ Smart Test Tools – optional license 

*2 ‐ Optional Plug & Play board needed. 

*3 ‐ ROOTS can be ordered with the license/s activated for one, several or all Protection Modules, or also including free rights for future         modules.  

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

       MENTOR 12                    SOFTWARE ELEMENTS (Cont’d) 

MEN

TOR 12 

ROOTS 

OVER

CURREN

ROOTS 

DISTA

NCE 

ROOTS 

DIFFEREN

TIAL 

ROOTS VOLTAGE 

ROOTS 

FREQ

UEN

CY 

SOFTWARE/MODULES  FUNCTIONALITY 

VOLTAGE INHIBIT FREQUENCY  Searching of the minimum voltage value that prevents the frequency elements to operate when the measured voltage is below the setting. 

           CLICK SEQUENCE DF/DT  Generation of test points list, each one being a frequency ramp, to evaluate the 

trip setting of df/dt element            

PICK UP DF/DT  This test allows searching for pickup values of active df/dt elements in the device with the desired accuracy. 

           VOLTAGE INHIBIT DF/DT  Test for searching the inhibition voltage of df/dt elements, through frequency 

ramps.            

CLICK SEQUENCE VOLT/HZ  Evaluation of trip times for the series of test points selected in the V/Hz characteristic 

           PICK UP/DROP OUT VOLT/HZ  Search for pickup and drop out values of active V/Hz elements in the device 

with the desired accuracy. It is performed by injecting consecutive faults            

Page 5: Mentor 12 Software Overview - 1964978058.rsc.cdn77.org1964978058.rsc.cdn77.org/wp-content/uploads/2015/12/Mentor-12... · FAULT Three‐state Fault ... Playback and processing of

 

©EuroSMC, S.A. November 2014 

 

 

 

    MMEENNTTOORR  1122    ‐‐  SSOOFFTTWWAARREE  EELLEEMMEENNTTSS   FULL DIRECT CONTROL  The MENTOR 12  is  the most advanced  three‐phase relay  test set available  for  type and  field testing of electromechanical and digital protections of any kind, providing the most complete and straightforward Manual Control of the market. The MENTOR 12  is controlled via a touch screen panel and a rotary selector. An external mouse, monitor and keyboard can also be used if desired.   The MENTOR  12’s  intuitive  interface  is  organized  to  complete  the  job  safely  and accurately  in  the  shortest  possible  time.  Locating  the  necessary  controls  and  the relevant  test  information  will  take  just  a  few  seconds  to  the  untrained  expert. Adjusting a  few values and testing a handful of trip points  in the relay  is a snap, at the reach of your fingertip.   The optimized Control Panel refers to the control of the equipment in local mode for total control over all its functions: 

Power  source  controls: Current  source/ Voltage  source, Amplitude, phase angle,  low  level  outputs,  harmonic  content,  channel  selection,  on/off activation, channel combination, frequency control. New Vector View. 

Measurement  display:  multifunction  timer,  countdown  timer,  analogue input  measurement,  binary  input  pulse  counter  and  frequency measurement. 

Function keys: channel selection, memory and dynamic fault shortcuts 

Battery simulator: Auxiliary DC supply setting for relay powering 

I/O  states:    monitoring  of  power  sources,  binary  inputs,  binary  outputs activation/status. 

On‐screen access to Alarms reports 

Output Power trimmer: Energy saving system with auto‐adjustment to load and regulation of working cycle. 

Fine/coarse tuning. 

Real‐time representation of power vectors. Direct regulation in Vector View. 

Timer operation/trip setup and preferences, binary I/O setting. 

Event  Logger,  with  event  description  and  time  of  the  event.  Automatic recording for all events, such as sources switching and I/O states. 

External measurement, for testing of transducers, meters and sensors. 

Hardware configuration and maintenance, with internet upgrading capacity. 

Results Manager, and storage of results. 

STT: Importing RIO files and ROOTS test, execution of tests with no need of PC, just a USB pendrive. 

Advanced built‐in Test Functions: Fault, Ramp, Double Ramps, Pulse Ramps, Binary Search, State Sequencer, Fault Playback (COMTRADE) 

New  Assisted  Control  for  complex magnitudes:  Impedance,  Fault,  Power, Sequences, Vline and Homopolar Voltage, Open Delta. 

The MENTOR  12’s  standard  equipment  build  up  one  of  the most  advanced  basic configurations available on  the market  for quick,  simple and easy  testing,  for both commissioning and maintenance, without the need of any PC. One of  the biggest advantages of  the MENTOR 12  is  the "plug & play" modularity. New amplifiers connected by the user are automatically recognized and added to all the test and configuration screens by the MENTOR 12, with no software adjustment.  

 

Page 6: Mentor 12 Software Overview - 1964978058.rsc.cdn77.org1964978058.rsc.cdn77.org/wp-content/uploads/2015/12/Mentor-12... · FAULT Three‐state Fault ... Playback and processing of

 

©EuroSMC, S.A. November 2014 

 

 

 

 

 

CONFIGURATION CONTROL 

One of  the greatest advantages of  the MENTOR 12  is  its modular design. You  can start with a basic 6‐channel unit and add more channels later on. The plug and play technology makes adding or replacing channels an easy operation, with no need to return  the unit  to  the  factory. Depending on  the  device  being  tested,  the default hardware configuration can be quickly changed at any time:  Power Outputs Configuration: Easy control of all Power sources configurations. Regardless the number of amplifiers in your MENTOR 12, you can also combine them in  series  and  in  parallel  to  attain  greater  voltage  and  current  levels.  The  output configuration screen displays a menu with all the possible combinations and a visual guide to help the user at connecting the relay. There  is no need to calculate partial current, voltage or phase angle values as the MENTOR 12 manages and shows each group of combined channels as if it were a single “virtual “one.  Furthermore, each voltage amplifier  can be  switched  to current mode by a  simple touch  on  the  configuration  screen.  This  feature  allows,  for  example,  to  convert  a MENTOR 12 3v3i (3 voltage + 3 current channels) to a six‐current test set when the need for testing three‐phase differential relay arises. Low  Level  Outputs  and  superimposed  harmonics  for  every  source  can  also  be activated in this control.  Binary  Input Configuration: The MENTOR 12 has 12  (Logic) Binary  Inputs grouped together  in 6  isolated pairs,  in order  to be able  to detect  the behavior of  the  logic outputs of the relay or protection scheme that is being tested. The Binary Inputs can be configured to detect both Dry Contact operation signals, or Wet Contacts, that is, a signal with voltage applied to them (1.5 or 15V threshold up to 400V pk ac or dc). Each Binary Input can be programmed to be active High or Active Low (NO, NC)  Binary Output Configuration: There are 8 Binary (Logic) Outputs in the MENTOR 12, in  order  to  be  able  to  program  their  behavior  so  the  action  of  devices  in  the protection scheme that is being tested can be simulated. Each Binary Output can be configured as: Relay /Open Collector, and NO/NC mode.  Default Configuration: many other settings can be easily adjusted such as working with  primary  or  secondary  values,  debounce  and  glitch  time  sensitivity  of  binary inputs,  angle  notation  and  direction,  default  frequency,  default  values  for  voltage and current sources, seconds/cycles, language selection and GPS info (if GPS board is installed in the unit)  TEST FUNCTIONS 

The most complete Built‐in Test  functions, with on‐screen graphic configuration, to carry  out  typical  test  for  protection  relays  and  protection  schemes.  These  tests allows  determining  the  state  of  the  relay  and  obtaining  readings  and  results  of different relay parameters under different test conditions, configured by the user.  A  Logger  is  available  for  all  functions,  to  carry  out  an  in‐depth  study  of  the performance of the relay tested throughout the function. The  test  configuration  is  similar  to all of  them, making  the MENTOR 12 extremely easy to use, since controls are shared by the functions. The TRIP processing can also be configured in any of them, by combining the twelve available binary inputs in OR or AND  logic. Prefault,  fault and postfault states of  the binary outputs and outputs test signals sources are defined through an intuitive graphical interface.  

Page 7: Mentor 12 Software Overview - 1964978058.rsc.cdn77.org1964978058.rsc.cdn77.org/wp-content/uploads/2015/12/Mentor-12... · FAULT Three‐state Fault ... Playback and processing of

 

©EuroSMC, S.A. November 2014 

   

 

 

Fault  function:  this  three‐state  function allows  the user  to set a complete simple fault and execute the prefault, fault and postfault values, including duration of the states,  logic  I/O  states,  and  trip  conditions.  The  fault  execution  displays  the progress timeline and test results in graphical and numeric mode, including the trip time and end function time.  

Ramp  function:  Single  and Double  Ramps,  upward  or  downward  ramps,  of  any output  parameter  on  the MENTOR  12  can  be  programmed  and  executed.  The automatic ramps are generally used to systematically determine the trip level of a protection  relay  with  respect  to  the  parameter  that  is  varied.  Ramp  function operation is provided for finding limiting values, such as pick‐up and drop‐off. The linear  ramp  is  the  best  way  of  handling  parameters  such  as  the  Phase  Angle, Voltage  and  Frequency,  especially  the  latter,  as  the  real  performance  of  these parameters can be reproduced with great precision.   The  flexibility  of  this  module  allows  two  synchronized  simultaneous  ramps  of different  variables,  each  one  applied  to  different  types  of  output  quantities,  for example,  one  ramp  moving  the  Voltage  and  the    other  moving  the  Current (Impedance ramp).  Simultaneous  ramps,  even  of  different  parameters,  can  be  applied  to  the  same selected output source,  for example one  ramp moving  the voltage and  the other moving  the  frequency at  the  same  time on  the  same output  source,  in  this  case voltage ( V/Hz variation ramp).  After  ramp  and  trip  conditions  are  set,  the  test  progress  is  displayed  in  an oscillographic  fashion,  with  electrical  values  evolving  along  the  ramp  and  trip events being stamped on the timeline as they take place. Relay trip time, trip value and duration of the test are displayed, and test repetition can also be performed if desired, or with different conditions. At the end of a test, user can type a name and a  brief  description  and  save  it  for  future  use.  Since  storage  takes  place  on removable USB pendrives, the capacity  is unlimited, and  it also provides a way to create a collection of automatic test routines.  

Pulse Ramp function:  It  is a way of carrying out a Fault ramp, each state with  its pre‐fault and  its  fault. The basic difference with  respect  to  the Ramp  function  is that  instead  of  continuously  increasing  the magnitude,  a  preset  condition  state occurs between consecutive pulses.  This  function  is  preferably  used when  instantaneous  or  defined  time  values  are sought in Overcurrent elements, as it enables to inject a high current value during a specified  time and  return  to  low  current  conditions or even non‐existing  current conditions  between  each  programmed  pulse,  thus  eliminating  the  possibility  of damaging the relay tested.  It is also very useful to verify trip setting values in protection zones, as we can enter the zone  for a defined time and exit  it without causing the other slower zones to trip.  The selectivity that is achieved with this function when selecting the trip elements, makes  it  very  interesting  to  use  when  testing  trip  outputs  of  relays  that  have different protection functions assigned to them at the same time, thus avoiding the need to change the configuration of the relay being tested. The information about the  number  of  steps  (increases)  and  the  total  duration  of  the  function  (in milliseconds)  appears  automatically  calculated  in  the  screen,  as  in  the  ramp function.  

Page 8: Mentor 12 Software Overview - 1964978058.rsc.cdn77.org1964978058.rsc.cdn77.org/wp-content/uploads/2015/12/Mentor-12... · FAULT Three‐state Fault ... Playback and processing of

 

©EuroSMC, S.A. November 2014 

     

Binary  Search  function, unlike  the  ramps,  the Binary  Search does  not  use  a  fixed increase value, as it adapts to different values to make an effective search. Ramp and Pulse Ramp are excellent  to verify  the accuracy of a  trip value within some known margins. The Binary Search function is designed to cover the circumstance when you do not know the trip value or even, to verify a known trip value carrying out the test in a different way.  

An initial search point is defined in this function as well as an end point that may be separated  from the  initial one as much as we want as well as a maximum  function Precision or Resolution. After defining the limits, the function will give a first pulse at half the value of the range defined by the initial and end values. If it detects a trip it drops to half the difference between the  last applied value and previous.  If  it does not detect a trip it increases to half the difference that it dropped previously, and so on and so forth. This is a very quick and accurate way of searching for trip values. Other difference between a Binary Search and the previous Ramps  is that only one trip  is detected  in  the Ramps  (going up or down until  this occurs) whereas  in  the Binary Search multiple trips occur for the relay tested, which must be considered.  

State Sequencer function: The State Sequencer is a very flexible test module to test protection  schemes,  since  it  allows  programming  a  sequence  of  all  the  outputs available on  the MENTOR, analog or binary, as you desire,  in a  logical sequence of states. The transition from one state to another can be configured either by elapsed time, by any combination of the binary  inputs trigger, by both things or by manual initiation.  The  State Sequencer is used to test protection functions that are closely connected to  times and actions dependent on each other, such as reclosing cycles, protection schemes  with  segregated  or  selective  trips,  sending  orders  and  signals  to  other protections, communication schemes, etc…  To use this function it is important to study the data contained in the Logger in detail as  well  as  their  correlation  with  the  changes  in  state,  depending  on  what  the protection or scheme tested are expected to do under the injected conditions. Within one state, all configured test signals (voltage and current outputs) of the test device can be set independently in amplitude, phase, and frequency.  

Fault  Playback:  This  function  allows  the  playback  of  COMTRADE  fault  description files, both binary and ASCII, according to  IEEE STD C37.111‐1999. This  is very useful to  analyze  the  protection´s  behavior  against  a  previously  recorded  fault,  or  a simulated fault (from network simulation programs), reproducing this transient faults recordings at a specific sampling frequency.  In this function, the MENTOR internal amplifiers radically change its normal perfectly sinusoidal wave reproduction, to play sample by sample the registered wave  in the COMTRADE  file, with a 3 Khz bandwidth. The MENTOR 12  includes  this  feature as standard, and a PC is not needed.  COMTRADE files can be directly read from a USB pendrive, plug  it  into the unit and press Playback. User can assign each in the recording to specific current and voltage channels  for  the playback, select  the section  to be played – all  the record or some cycles before and after  the  trigger –  and analyze  the  response of  the  relay at  the binary  inputs  in  the MENTOR 12. User  can edit and discard  the unneeded  signal’s sections or adjust the best transformation ratio for the playback.  If the GPS option  is  installed,  it  is possible  to synchronize the  file playback through this external time reference.  This makes  it possible to check  if the relay´s reaction differs between the recording and  its behavior during playback, and also  to analyze how other protection device operates under the same conditions.  

Page 9: Mentor 12 Software Overview - 1964978058.rsc.cdn77.org1964978058.rsc.cdn77.org/wp-content/uploads/2015/12/Mentor-12... · FAULT Three‐state Fault ... Playback and processing of

 

©EuroSMC, S.A. November 2014 

      Results  Manager:  The  Results  Manager  allows  saving  both  the  test  results  and configuration of Advanced  test  functions, so  that  they can be  repeated as desired. Results are saved in a USB pendrive. The  system  can  save  as  many  tests  as  needed  in  Report  files,  being  a  way  to automate tests for specific relays. The reports can be displayed on the PC, exported and/or printed, using the Report Viewer for Windows, which is included as standard in every MENTOR. After any advanced function test, we can add the results to any existing report, with a new name for this test and a description. The test  is recorded with date and time and  the  function  type.  The  saved  collection  of  user‐defined  and  customized  test routines will provide a valuable asset of  ready‐to‐use  test  tools  for each  relay  type and  protective  function.  The  user  only  needs  to  choose  one  from  the  list  in  the Results Manager and press Execute.   Internet upgrading and Maintenance: the MENTOR 12 will never become obsolete because  all  its  functional  elements  are  completely  programmable.  The  user  can upgrade  its  software  over  the  internet  and  install plug‐and‐play hardware options with  no  external  assistance.  All  hardware  and  software  configurations  can  be updated by internet. The user enjoys free updates and upgrades of new features and new modules made by EuroSMC. MentorUpdate module automatically updates the unit through direct connection of the MENTOR  unit  to  internet. Other  option  is  to  update  the  unit  through  a  USB pendrive, which previously have loaded the update files, downloaded via a computer connected to the Internet from our servers, using the program MentorSynch. VNC Remote Control Server  is a tool which allows remote control of MENTOR from any external computer connected in the corporate network or a computer connected to  the  Internet.  It  is very useful  to allow  remote  control of  the unit, especially  for checking and diagnosis of the unit operation by our service specialists.  Meter & Measuring: Measurement  configuration  section  to  configure  the  settings for analog and binary measurement. This  functionality, specifically designed  to  test transducers with analog output  in VDC or mA DC or counters with analog or digital output by pulses, makes the conversion from the magnitude measured at the  input (V, mA, Pulses) to the units that are assumed to be the nominal ones of the element to be  tested  (V, A, KVA, Kw, Kvar, Kw,  time, etc) entering  the  ratio between both. Optical  scanning  heads  for  capturing  pulses  emitted  by  the  energy meters  (non‐visible infrared LED and visible) are optional accessories available. The multifunction display in the main control panel shows the values measured in the analog input and binary input in real time.  Binary  I/O Monitor: The MENTOR 12  is permanently monitoring  the Binary  Inputs states,  and  reflecting  any  change  at  both  the  screens  of  test  results  and  in  the Logger; furthermore, the user can also monitor on‐screen any status change of all the Binary  Inputs at any  time, which  facilitate  testing and verifying  the  relay´s  reaction during the test execution.   Similarly,  Binary  Outputs  status  is  displayed  on  the  screen,  monitoring  the  pre‐programmed activity of them at any of the functions; besides that, the user can also activate  or  deactivate  manually  any  of  the  Binary  Outputs,  if  required  by  the simulated protection scheme, from the Binary Outputs control on the main screen.  Battery Simulator:   The MENTOR 12 has a built‐in battery simulator up to 250 Vdc, which must be used to supply the relays being tested and which require an auxiliary power supply. The Battery Simulator control is available in all the accessible function screens.  

Page 10: Mentor 12 Software Overview - 1964978058.rsc.cdn77.org1964978058.rsc.cdn77.org/wp-content/uploads/2015/12/Mentor-12... · FAULT Three‐state Fault ... Playback and processing of

 

©EuroSMC, S.A. November 2014 

 

    Timer Settings: Timer start and stop conditions can be quickly adjusted to the test needs. The timer can be programmed to start by the status changes  in the Power Outputs, by  the action of a Binary  Input combination, or by  the status change of any Binary Output. Timer stops by the trip action at the Binary  Input  logic, which setting  is  straightforward  selected.  After  the  stop  of  the  timer,  voltage  and/or current  outputs  can  be  immediately  switched  off  or  delayed  to  simulate  switch time.  A  countdown  timer  can  also  be  programmed  to  stop  the  outputs  or  to  load  the previous state with the desired time in milliseconds.  Logger: Automatic recording available in MENTOR 12, where any event is registered, such as the activation of the outputs, and changes at the binary inputs and outputs. The events listing are displayed with the time recorded for each, to correctly analyze the performance of the relay.   Harmonics:  set of  controls  to easily  regulate different harmonics  contents  in  the voltage and/or current channels. The control allows selecting the desired Harmonic (2  to  33  in  60 Hz  base  frequency  and  2 to  40  in  50 HZ  base  frequency)  for  the channel  group.  On  each  channel  it  is  possible  to  regulate  both  the  harmonic content  in  percentage  and  the  angle  where  it  is  going  to  be  inserted  into  the fundamental waveform.  The possibility  to work with  the  two parameters makes possible to generate with the desired Crest Factor (also called Form Factor), which is  important mainly  in  testing old electromechanical and electronic analog  relays, which are sensitive  to  this parameter.  In  this way  the user does not need  to  run pieces  of  external  software  or  make  any  kind  of  calculations  to  be  able  to determine the exact pickup or blocking values of the restraining harmonic elements in differential and ground  relays, by  just using  the  regulating control as with any other parameter in the MENTOR 12.  Cape Test files converter: Now all the EuroSMC's MENTOR 12 users may convert the Cape SS1  files  into a file directly  readable  from a USB pendrive by  the MENTOR 12 test set, and perform  the  test  in  few seconds by using  the EuroSMC's CAPE SS1  to MENTOR converter software,  which  allow  the  user  to  directly  download  the sequence values  into  the States Sequencer and perform  the  test  immediately. The States  Sequencer may  be  triggered  either manually  or  through the GPS  or  IRIG‐B time synchronized options available for the MENTOR 12 unit, making an ideal tool for End‐to‐End testing. The Cape software  is a popular program for network simulation and  shorcircuit  analysis,  which  allow  the  user  to  calculate  the  fault  values  in  a network point and make possible to obtain a file which contains all the  information of  the prefault,  fault and post  fault values and the duration of each state.  It  is also possible to obtain a full states sequence corresponding to a reclosing cycle.  IEC‐61850–  GOOSE  module:  MENTOR  12  is  IEC‐61850  compatible.  The option MENTOR IEC 61850 is a GOOSE Messages Interface Board which consists in a plug & play electronic board that installs into the Control Bus of any MENTOR 12 unit  just  by  sliding  it  inside.  The  configuration  software  tool  is  included  in  the MENTOR  12  internal  software,  avoiding  the  use  of  an  external  computer,  and allows to subscribe/publish the GOOSE messages. This option works through the RJ‐45 connector, which connects with the IEC‐61850 bus and use the information contained in the GOOSE messages as logic inputs and also  it  is able  to broadcast GOOSE messages  that acts as  logic outputs, exactly  in the same way  that  the current MENTOR 12 electrical  I/O works, but avoiding the wiring of the I/O to the relay inputs and outputs. The IEC 61850 option can be installed in any existing or future MENTOR 12.    

Page 11: Mentor 12 Software Overview - 1964978058.rsc.cdn77.org1964978058.rsc.cdn77.org/wp-content/uploads/2015/12/Mentor-12... · FAULT Three‐state Fault ... Playback and processing of

 

©EuroSMC, S.A. November 2014 

      MENTOR‐GPS/IRIG‐B:  Certain  kind  of  test  requires  the  setup  of  two  or  more MENTOR  12  units  (or  one MENTOR  12  and  other  test  set)  separated  on  different locations  and  synchronized  with  each  other.  In  this  case  a  very  high  precision reference  clock  is necessary,  in order  to obtain  the  required  timing  to  trigger  the state sequencer or the reproduction of Fault playback (COMTRADE files) on separate units.  The  MENTOR  12  equipment  allows  for  this  synchronism  by  the  use  of  two alternatives of very precise time reference inputs: GPS and IRIG/B. Any of these two options  can  be  chosen.  It  requires  the  installation  of  the  corresponding  Printed Circuit Board.  The GPS signal  is broadcasted via satellite, and can thus be received at any place of the terrestrial globe. On the contrary, the utilization of an IRIG/B signal requires the presence of a  local setup that generates this signal and transmits  it via cable to the MENTOR 12. The precision in time measurement of either two technologies is very high, allowing the  MENTOR  12  to  trigger  pre‐programmed  sequences  with  precision  of microseconds.   GPS and  IRIG/B boards are plug & play; once  the hardware has been detected and the signal is received, the unit is in disposition to initiate a state sequence or execute a COMTRADE  file  in a previously defined  instant with a precision of microseconds. User  can  upgrade  the  MENTOR  12  with  these  optional  boards  at  any  time  by themselves, without needing to send back the unit to factory.  Smart Test Tools (STT): This optional functionality can be enabled at any time with the  optional  software  Smart  Test  Tools,  for  automatic  stand‐alone  testing  of distance elements. Among the advanced test features provided by this component, the  possibility  of  executing  ROOTS‐originated  test  files  is  possibly  the  most outstanding, because  it avoids  the connections and preparation overhead usually associated to an external computer.  Any number of relay entries, each one containing a batch of different tests, can be stored from ROOTS onto a USB removable memory and then read and executed by the MENTOR 12.  It  is also possible  to modify  the  test  settings and even  the  test points before running the pre‐defined tests. The  results are automatically appended  to each  test point and  saved back  into a new  file  in  the  USB memory.  Later  on,  ROOTS  will  retrieve  the  complete  test records from the USB and will associate them all to the corresponding relays in the original database, for future reference and/or immediate reporting.  Another  useful  feature  in  STT  is  the  RIO  file  import.  This  can  save  the  time  of defining your relay's operation characteristic. Once a RIO  file has been read  from your USB removable drive onto the STT, the user only needs to enter the values of as many points to test or, even easier, add test points by just touching at different spots on the displayed characteristic's graphics. STT effectively  leverages the outstanding power of ROOTS by allowing you to put your  test plan  inside your pocket, execute  it with no manual  intervention and no external  computer on  the  field,  and produce  as many  reports  as  you need once back in your desk.      

Page 12: Mentor 12 Software Overview - 1964978058.rsc.cdn77.org1964978058.rsc.cdn77.org/wp-content/uploads/2015/12/Mentor-12... · FAULT Three‐state Fault ... Playback and processing of

 

©EuroSMC, S.A. November 2014 

   

 

                                MMEENNTTOORR  NNEEWW  SSOOFFTTWWAARREE  MMOODDUULLEESS                     NNEEWW!!  ((22001155))  

 

Vector View: Full control at your fingertips of individual or grouped phasors, with module  and  angle  lock  functions.  It  offers  an  alternative way  of  regulating  the amplitude  and  phase  angle  of  the  channels.  Instead  of modifying  the  numerical fields, you can touch and drag  its representative vectors on the screen whilst you observe  the  values  that  each  channel  takes.  To  prevent  it  from  changing  the module of a vector whilst it is dragging it circularly, you can activate the Lock level button.  If  you wish  to  vary  the  amplitude without modifying  the  angle,  you  can activate the Phase lock button.  

Assisted  Control:  On  screen  direct  regulation  of  complex  magnitudes (Impedance,  Fault,  Power,  Sequences,  Homopolar,  Open  Delta);  The  Assisted Control It is also available to be selected when programming sequences in the State Sequencer Test Function.  Instead of setting voltage, current or angle arbitrarily in each channel to configure a specific electrical situation, the Assisted Control incorporates a powerful algorithm that calculates those magnitudes whilst you set a single‐phase, phase by phase or three‐phase test directly in terms of:  

Fault Impedance: in Cartesian format (R‐X) or polar format (Module‐Angle).          It includes options and settings of Ground Compensation Factor. 

Fault Voltage, Current and Angle, for any of the Fault loop (single‐phase,        two‐phase, three‐phase)  

Power disturbance: Single‐phase and 3‐phase modality for Active/Reactive,        or Apparent/Power factor  

Symmetric components: Voltage settings: module and angle for  

o Positive or direct sequence  o Negative or reverse sequence  o   Zero or homopolar sequence  

Current settings: module and angle for  o Positive or direct sequence  o Negative or reverse sequence  o Zero or homopolar sequence  

Line Voltages (AB, BC, CA) and Zero Sequence Voltage. 

Open delta, AB and AC voltage vectors and Zero Sequence Voltage.  When a parameter  is  set  in any of  the  tabs under Assisted Control, all  the other tabs and even the normal Direct Control view are re‐calculated in agreement with the new value. Consequently, the electrical situation is always unique and common to all the tabs, and it can also be seen in terms of voltage, current and angle just by pressing the Assisted control button again to return to the Direct control. The Lock button permits re‐setting parameters without modifying the output. When pressed again, the output instantaneously takes on the new parameters entered.  

Summary window: This small square area  in the upper right‐hand corner of the Direct  control  screen  normally  offers  a  simplified  vector  representation  of  the values set  in  the output channels.  If you briefly  touch  it,  its content changes  to a summary of the impedance, power values, etc., which corresponds to the electrical situation  currently  set  in  the  different  tabs  of  the  Assisted  control.  This  view provides  an  aid  to  the  regulation  whilst  working  in  Direct  control,  and  is  also available when configuring State 1 and State 2. 

  

Page 13: Mentor 12 Software Overview - 1964978058.rsc.cdn77.org1964978058.rsc.cdn77.org/wp-content/uploads/2015/12/Mentor-12... · FAULT Three‐state Fault ... Playback and processing of

 

©EuroSMC, S.A. November 2014 

  

  

  

    RROOOOTTSS  ‐‐  RREELLAAYY  TTEESSTTIINNGG  SSOOFFTTWWAARREE                                            

  ROOTS (Relay Object‐Oriented Test System) provides the best solution to the testing of  today’s multifunctional  IEDs by performing accurate  fault calculation,  sequential test execution, and reporting automatically.  A ROOT is an optional product for PC‐operation of EuroSMC’s MENTOR 12 and TRES relay test sets.  ROOTS is developed using the latest Microsoft .NET® technology and is available for 32‐bit and 64‐bit Windows XP, or later platforms.  ROOTS  implements  a  friendly,  intuitive  interface,  for  the  quick  and  accurate configuration of all equipment  features, device  settings,  test modules,  test  results, reports,  and  the  permanent  storage  in  a  database.  Test  routines  and  report definitions  are  saved  according  to  a  simple  hierarchy  that  is  flexible  and  easy  to understand. The user can create any number of test databases and each database is organized  by  Devices  (IED);  several  Test Modules  can  be  added  to  every  Device, protection‐specific modules, such as Distance or Overcurrent, or RIO  files modules. Each module contains a test kit with test routines (click sequence, search, reclosing, breaker  failure,  etc)  that  can  be  used  right  off‐the‐box  or  quickly  and  easily customized to the user’s needs. In summary, substation/s overall test procedures can easily be built, can be repeated for maintenance testing, and also used as templates for similar substations with minimum adjustments, which saves considerable time.   The best solution to the testing of today’s multifunctional IEDs.  Spans  the  testing  from  the  relay  to  its  interactions with  the whole protection 

scheme.   Accurate fault calculation and sequential test execution.  Automatic, customized and exportable Reporting. Now, New General Report.  Roots  storage  files  are  self‐contained  databases:  relay  data,  characteristics, 

custom formulas, test routines and report definitions.  Database  management  functions  for  the  import/export  of  devices,  test 

definitions and results between databases. Databases can be exported to XML.   Devices Classification tool, for easy and quick  localization of the devices  in the 

database.  Ability  of  using  formulas  instead  of  fixed  values  when  entering  test  values, 

settings, options or other data.  Direct  import  of  RIO  relay  description  files  supplied  by  a  number  of  relay 

manufacturers (SIEMENS, ABB, etc)  Intuitive  graphical  zone  and  elements  Characteristics  Editor, with  pre‐defined 

Templates.  Modular architecture, different optimized test modules for each protection.  Modular Pricing, ROOTS can be purchased with one or more functional modules, 

providing a price‐optimized solution.  Free updates, No other product  in  its class offers free  lifetime updates and the 

possibility of being upgraded (in software and in hardware) by the user himself.  New  Import  Settings  Tool,  automate  the  import  of  settings  and/or  update 

existing ones, from a text file.  New  Data  Settings  Panel,  edition  of  the  data  associated  with  the  device 

(Formulas, Custom and Default Variables) and a classification system of settings.  

Test  procedures  defined within  ROOTS  can  be  directly  executed  on  a  connected EuroSMC test set. For a MENTOR 12 equipped with the Smart Test Tools module, the test procedures can also be transferred from ROOTS to an USB pendrive that can be read and executed by the MENTOR 12 with no need of an external computer.  New MENTOR 12 users are entitled to test 100% functional ROOTS and Smart Test Tools during a free trial period before deciding to purchase a permanent license.  

Page 14: Mentor 12 Software Overview - 1964978058.rsc.cdn77.org1964978058.rsc.cdn77.org/wp-content/uploads/2015/12/Mentor-12... · FAULT Three‐state Fault ... Playback and processing of

 

©EuroSMC, S.A. November 2014 

 

 

 

  

    RROOOOTTSS  ‐‐  DDEEVVIICCEESS  MMAANNAAGGEEMMEENNTT                                                                                          NNEEWW!!  ((22001155))  

  Data  Settings  Panel:  the  design  of  ROOTS  software  provides  a  universal,  vendor‐independent  approach  and  templates of  settings  (and/or  also  templates of devices with  an structured protection modules and  tests  lists) can be personalized  for each  relay  type. Each cell  in  the  Data  Settings  Panel  can  be  labeled  according  to  the  names  used  by  the  relay manufacturer  for  each  setting,  as  found  in  the  relay's  documentation,  in  the  relay management software or in the data entry sheet distilled by the protections department.  It can includes underlying user‐defined Formulas that save a lot of time and errors when some settings in a particular relay type can be calculated from a reduced set of data. The Device Template Edition  is an  integral part of ROOTS, allowing the user to modify  just a few settings for similar relay types, to be re‐executed and re‐saved along with the new results at any time.  The  Settings  Editor  includes  Functions  (written  in  VisualBasic.Net),  Custom  Variables  and Default Variables  (such as Nominal Frequency, Main CT and VT data). Functions and Custom Variables are associated with each device under test. It is provided a tree classification system, displayed to the user´s convenience, with nodes that can be relocated to any position  in the tree.  The  management  of  settings  provides  a  quick  way  to  locate  and  make  visible  the concrete settings required. ROOTS  focus  on making  the  data  entry  an  easy  process,  rather  than  eliminating  the  test 

operator's crucial involvement in verifying the integrity and veracity of the test information. 

Automatic  Import  of  Relay  Settings:  New  Tool  to  automate  the  import  of 

variables/settings and/or update existing ones, from a Text file, using Pattern recognition and Templates. The source  file can be generated by  the Relay software, or  from  the Engineering file issued to adjust the device settings. It is divided in four submenus: 

Import data:  It allows  to select  the Text data  file, choose  the  template and  import the settings automatically. 

Template manager: Allows  the  construction or modification of  the  templates  that are used to import the settings. It includes a Mapped Table of the Variables found in the file by the selected Patterns, to be linked with ROOTS variables. a template for a specific  file  type  is  stored  in Roots and allows  reuse  it at any  time  to  import data from a  similar  file  type  (from  similar  relay  types  that have  the  same  file of export settings) 

Pattern manager: It facilitates the creation, testing and modification of patterns used by  templates. The Patterns are used  in  the analysis of  the  files  in order  to capture the required data, through Regular Expressions. The patterns can be produced by an advanced  user  or  required  to  EuroSMC.  The  design  allows  reuse  each  pattern implemented in several templates in order to economize efforts. 

Options manager: options for the interpretation of data files. 

 This New Tool for Automatic Import of Settings provides: 

A quicker and more automated solution than the manual data entry process. 

More guaranteed results in comparison with the RIO files import. The import of RIO files that contain relay settings provide a method to prepare the test quickly. ROOTS also includes the direct import of RIO files. However, the user has no direct way to ensure  that  the  settings  (blindly)  imported  via  the  RIO  file  into  the  test  system exactly  describe  the  functionality  planned  for  the  tested  relay  in  a  particular protective  scheme  (unless  the  RIO  file  has  been  accountably  issued  by    the protections engineer); in other words, generally speaking, a successful test based on a RIO  file  just confirms  the relay's operation and measurement accuracy, but only guarantees that the relay and the test system share the same settings. 

Test  the  device  with  the  CORRECT  settings,  those  settings  provided  by  the protection dpt. or when any change is made by them, delivered by any format that at the end can be exported in a text file. 

Provides full independence from the relay and test set manufacturers. 

Allows  the  customer  to  seamlessly  implement  their  own  engineering  procedures across  the entire quality assurance cycle,  from  the system design down  to  the  in‐field testing routine. 

 

Page 15: Mentor 12 Software Overview - 1964978058.rsc.cdn77.org1964978058.rsc.cdn77.org/wp-content/uploads/2015/12/Mentor-12... · FAULT Three‐state Fault ... Playback and processing of

 

©EuroSMC, S.A. November 2014 

Database

DeviceTemplate

Device 1 Device 2 Device 3 Device N

Device

DATA SETTINGS 

FunctionsCustomVariables

Default Variables

TEST MODULES 

ROOTS Module

Distance Overcurrent

Differential Voltage, etc.

RIO 

 

  

  

  

    RROOOOTTSS  ‐‐  DDEEVVIICCEESS  MMAANNAAGGEEMMEENNTT                                                                                      NNEEWW!!  ((22001155))  

  Databases  and Devices  Panel:  ROOTS  database  files may  include  as many  devices  as 

required and the user can create any number of test databases.  Each  database  is  organized  by  Devices, with  its  specific  device  definition,  relay  settings, protection modules, characteristics, test routines, test results, reports and report definitions.  Each Device can be assigned: 

Functions:  They  can  be  used  in  formulas  to  define  any  test  value  based  on  the device's settings.  

Custom variables: provide a practical data input method when the users wants to define  the  test parameters based on  the  relay  settings. An unlimited number of user‐created variables can be defined for a device and used in the test modules.  

Default variables:  A number of default variables is automatically defined by Roots for each newly created device.  

Test  Modules:  The  Modules  (Distance,  Overcurrent,  Differential,  Voltage, Frequency,  etc)  are  configurable  for  each  device  separately  depending  on  the characteristics of the device under test. Several test modules of the same type are allowed  at  the  same  device.  It  contains  all  the  test  settings,  test characteristics/Elements and test results for a variety of protection‐ and scheme‐oriented set of pre‐configured tests.  

The Device Panel shows a list of devices stored in the database in use.   Devices  can be classified/reordered by any  column, or group  them by  the user  criteria by simply dragging the column heading  to  the  top of  the  table, as a  tree structure. Each new column  dragged  will  be  part  of  the  grouping  of  information.  This  makes  easier  the organization  and  finding  of  concrete  devices,  mainly  when  a  big  number  of  those  are included in the database, as well as facilitates the creation of test plans for different devices that  can  be  repeated  for  maintenance  testing  as  templates  for  the  same  or  several substations.  The  Device  Panel  allows  creating,  editing,  duplicating,  and  export/import  the  devices to/from XML  format  (and also  to export  to Mentor STT  file, which  is also XML). Using  the “import  device”  tools  allows  having  an  unchanged  database  of many  test  templates  for different devices, to open a “new database”, and  import the specific device (or devices) to that new database without changing the original template.  For every device  the user  can edit  the  identification  fields  as  required,  adding new  fields (that can help to locate a particular device within the database) and also write in the Notes tab  the  additional  information  about  the  device  tested,  general  checks  or  notes  to  the operator, etc.  

Report Configuration:  Upon completion of a test, a report is automatically generated, in 

PDF or HTML file. Now, it is also available the report export to Word editable RTF format. The user can choose the sections that must be  included  in the test report by means of the Report Configuration tool included.  User can also select the image/logo to display on each page of the report.  

General Report: New Tool to select and combine the different reports of executed tests in 

different modules,  in a single General Report,  for  the selected device. The  list of executed Tests are shown grouped by the module column, and can also be ordered by module type, creation  date,  etc,  and  filtered  with  similar  columns  dragging  action  that  in  the  device classification.   User can select which reports wish to combine in a single General Report, or to select all of them.    

 

Page 16: Mentor 12 Software Overview - 1964978058.rsc.cdn77.org1964978058.rsc.cdn77.org/wp-content/uploads/2015/12/Mentor-12... · FAULT Three‐state Fault ... Playback and processing of

 

©EuroSMC, S.A. November 2014 

  

  

      

RROOOOTTSS  ‐‐  OOVVEERRCCUURRRREENNTT  MMOODDUULLEE             The Overcurrent test module is used to automatically test the performance of protective devices that  implement  any  combination  of  the  50,  50N,  51,  51N,  67,  67N,  46  and  49  protection functions.  It also  includes  tests of operating  values, and  the external  scheme  tests  related  to these protective functions.   The module's functionality is distributed in the following sections:  Technical  data:  general  parameters  that  affect  all  the  tests  contained  in  the  Overcurrent module, such as: work with primary values, elements used  for phase‐ground  faults, ground CT data,  sensitive  ground  CT  data,  Current,  time  and  angle  tolerances,  directional  settings, grounding characteristics and transformer connection. Element  list:  the  test  module  supports  any  number  of  phase,  neutral,  negative  sequence, ground and sensitive ground elements. Different element characteristics can be selected, added and  activated  in  the  Element  List,  and  different  settings  can  be  adjusted  for  each  one.  A Graphical  View  of  the  Relay  curve  is  available  for  Non  Directional  and  Directional  Relays (Forward Curve, Reverse Curve and Operation/No Operation zone view)  Characteristics Template: access to the edition of the different inverse time characteristics that Roots  contain.  Groups  of  pre‐defined  Characteristics  are  available  depending  on  specific equations (IEC, IEEE, ANSI, U.S.), user‐defined formulas, and curves in tabular form. Each one can be edited through modification of the associated variables. The user can also easily create new curves from scratch. Test  List: Multiple  tests  can  be  selected  and  attached  to  the  device  under  test  from  a wide choice of test types including scheme‐oriented tests like reclosing or CB failure: Click Sequence, Pick up/drop out, Reclose, Cold Load, SOTF (Switch On To Fault),  I2/I1 Ratio, Breaker Fail, Fuse Failure, SOL (Selective OC Logic), Reset Time Test Screen: with flexible access and configuration of the various test elements: ‐ Test Settings (prefault, fault and postfault) ‐ Test  Points:  table  of  test  points  for  each  Fault  type  loop with  the  set  values. With  several methods  to  define  and  insert  test  points, individually,  interactively  clicked  right  onto  the characteristic’s  drawing  or  a  number  of  time‐saving  tools  can  be  used  to  automatically generate series of test points, supporting separate or multiple fault loops selection (A‐N, B‐N, C‐N, A‐B, ABC, etc)  

‐ Test Result Assessment, automatic and manual. ‐ Test Graph of  the protection  element:  For directional  relays,  the  graph  shows  three  views, time curve for forward and backward faults, and an angular view, indicating the operating area by colors. 

‐ Phasor Graph: allow to view the phasor diagram of every point being tested. ‐ Hardware  Settings:  map  the  MENTOR  12    I/O  and  power  connections  to  the  relay, configuration of operating options  in MENTOR 12  for Binary  I/O  (Relay/Open Collector, NO, NC, Dry/Voltage) 

‐ Report and Report Configuration: automatic report generation with user selection of data to be  shown. The  report  can  be  produced  in  PDF  format  or  other  data  interchange  like  XML. Reports are saved along with the results in the database. 

‐ Test execution: automatic sequential injection of test settings for every test point, comparing the operating time measurement with the allowable current and time tolerances  in technical data, assessing the result as correct or incorrect and printing it both in the test point table and the  test  graph.  The  test  sequence  can  be  stopped  at  any  time  by  the  operator,  and  then resumed from the first non‐tested point. The user may also decide to reset the tested points and restart the entire test from the beginning, or to repeat the test only for a selection of the points in the list without affecting the other points. 

          

Page 17: Mentor 12 Software Overview - 1964978058.rsc.cdn77.org1964978058.rsc.cdn77.org/wp-content/uploads/2015/12/Mentor-12... · FAULT Three‐state Fault ... Playback and processing of

 

©EuroSMC, S.A. November 2014 

            

Click Sequence: this shot test offers the easiest way to check the relay’s settings against the geometrical representation of its protective characteristic, through the running of a sequence of test points. 

Pick  up/drop  out:  test  for  finding  the  pickup  and  dropout  values  of  the  active  protection elements in the relay under test. 

Reclose:  This  test  allows  the  verification of  the  relays  reclose  function with  any number of reclosing cycles,  through  the generation of reclosing sequences, and any combination of  the elements settings for each reclosing cycle.  

Cold Load: test to evaluate the performance of protection devices that support the cold load function, through the generation of the necessary states, testing the capacity of the device to vary its normal overcurrent settings during the cold load period. 

SOTF  (Switch  On  To  Fault):  test  to  evaluate  the  performance  of  the  relay  during  a  SOTF condition. The user interface is designed so that the user can vary the position of the fault and the moment on which it happen. It also allows analyzing the behavior of the function related with  the  Recloser  and  the  temporary  acceleration  of  the  overcurrent  protection  elements during the SOTF action time. 

I2/I1 Ratio: This test allows the user to evaluate the performance of those relays that generate alarms or  trips when a certain  level  is  reached by controlling  this  relationship. The user can generate faults with the I2/I1 ratio desired and evaluate the performance of the alarms and/or associated trips.  

Breaker Failure: test to evaluate the behavior of the CB failure protection function. The user easily adjusts the desired conditions of the breaker failure settings (stage 1 and stage 2) and the software automatically generates the necessary states to perform the CB Failure Scheme, in  different  situations  such  as  CB  Failure  Delay,  CB  Failure minimum  phase  current  or  CB Failure minimum ground current. 

Fuse Fail:  test  to evaluate  the different detection methods and performance of  the modern relays  in front of the  lack of secondary voltages  in the relay  input, being the typical case the fuse blow up or trips of MCBs that protects the VT secondaries, and  its capacity to changing their protection  function to non voltage‐dependent through the  logic  implemented, and test the elements behavior during the Fuse Fail condition. 

SOL  (Selective Overcurrent  Logic)  test  to  verify  the  correct  logic behavior of  the protective devices  on  signal  reception with  forward  faults  and  reverse  faults,  and  the  capacity  of  the protective device to selectively operate or change adjustments depending on signals received that are activated by request of other located devices in one direction or another. 

Reset Time:  this test allows checking the operation of the reset times used by mean of setting different  test conditions.  Induction electromechanical  relays have  inherent  reset  time delay. When a static or digital relays need to be coordinated with an upstream electromechanical, is convenient to use reset timings to ensure coordination. Another situation where reset delays are used is to reduce the clearance time in intermittent faults situations.  

     

                   

Page 18: Mentor 12 Software Overview - 1964978058.rsc.cdn77.org1964978058.rsc.cdn77.org/wp-content/uploads/2015/12/Mentor-12... · FAULT Three‐state Fault ... Playback and processing of

 

©EuroSMC, S.A. November 2014 

    

  

    RROOOOTTSS  ‐‐  DDIISSTTAANNCCEE  MMOODDUULLEE   Distance test module is used to test all functions related to protection function IEEE number 21. It includes not only the tripping characteristic tests but also external scheme tests related to this protection function.  The module's functionality is distributed in the following sections: Technical data: general parameters  that affect all  the  tests contained  in  the Distance module, such  as:  Line  data  (line  impedance,  line  angle,  ground  compensation  factor),  Impedance  and Time Tolerance (both absolute and as a percentage), Transformer connection, and performance parameters of the specific distance relay model Distance Zones: Zones defined in the relay are listed grouped by single‐phase, phase‐to‐phase or three‐phase characteristics, which the user can activate, edit and adjust the operating time for each  zone.  Also,  as  standard  key  feature  in  ROOTS,  the  direct  import  of  RIO  files with  relay characteristics and settings, reduces the data entry process to minor modifications.  Graphical Characteristic Editor: ROOTS features an  intuitive and powerful  interactive graphical editor  for geometrical definitions of protective characteristics and  impedance zones. Lines and curves can be drawn in free hand mode and/or adjusted using numerical values and coordinates. The  user  can  use  MHO,  Lens  and  Tomato  characteristics  shapes  or  create  a  customized characteristic as complex as desired.  Test  List: Multiple  tests  can  be  attached  to  the module  from  a  wide  choice  of  test  types, including  scheme‐oriented  tests:  Click  Sequence,  Search,  Verification  Test,  Reclose,  Evolving Fault,  Switch On  To  Fault,  Trip  on  Reclose,  Zone  1  extension,  Loss  of  Load,  CB  Failure,  Fuse Failure, Load Encroachment. Test Screen: with flexible access and configuration of the different test elements: ‐ Test models:  fault  simulation models  of  constant  test  current,  constant  test  voltage,  and constant impedance source. 

‐ Test Settings (prefault, fault and postfault) ‐ Test  Points:  table  of  test  points  for  each  Fault  type  loop with  the  set  values. With  several methods to define and insert test points, by individual coordinates, by clicking on the graph or with automatic generation of test points, supporting separate or multiple loop plane selection  (A‐N, B‐N, C‐N, A‐B, ABC, etc). With the Smart sweep function, test points are automatically set at the tolerance boundaries at each side of each zone, and with the Insert Sweep function test points  are  created  along  impedance  directions,  according  to  the  sweep  angle  and  reach defined. The calculated  fault parameters are displayed  for each point. Test points  list can be listed or made visible by any parameter criteria. 

‐ Test Result Assessment, automatic and manual. ‐ Test Graph of the protection element: show the characteristics of the active zones in the relay, for each selected fault type (single phase fault, phase to phase and three phase fault), and the length and angle of the protected line. 

‐ Phasor Graph: allow to view the phasor diagram of every point and injection values per phase and its angles. 

‐ Hardware Settings: map  the  test set    I/O and connections  to  the  relay, and configuration of operating options in the test set for Binary I/O (Relay/Open Collector, NO, NC, Dry/Voltage) 

‐ Report and Report Configuration: automatic report generation with user selection of data to be  shown. The  report  can  be  produced  in  PDF  format  or  other  data  interchange  like  XML. Reports are saved along with the results in the devices database. 

‐ Test execution: The entire  test  sequence will be  injected and operation  time  results will be obtained for each test point. The trip time at each test point is compared with the theoretical value  calculated  taking  into  account  the  tolerances  for  impedance  and  the  preset  time specified in the settings, qualifying the result as Successful or Failed on the table of test points, and  in  the  subsequent  test  report.  If,  at  the  end  of  a  test,  the  user wants  to  repeat  the execution of some test points, without affecting the others, he just select the test points to be redone and re‐test them. 

‐ Test notes and message to the operator, to show at start test, is also available.   

                                                        

 

Page 19: Mentor 12 Software Overview - 1964978058.rsc.cdn77.org1964978058.rsc.cdn77.org/wp-content/uploads/2015/12/Mentor-12... · FAULT Three‐state Fault ... Playback and processing of

 

©EuroSMC, S.A. November 2014 

 

 

 

 

Click Sequence: this shot test offers the easiest way to check the relay’s settings against the geometrical representation of its protective characteristic, through the running of a sequence of test points. 

Search Test: test to find the boundary values of distance zones  in selected directions. Search will in fact test the relay's accuracy. User can select the type of ramp to be used in the search, pulse ramp or binary search, and its resolution and search interval. Search lines can be easily added by  clicking on  the graph or by an automatic  sweep. Once all  search  lines have been created, test points are automatically generated in the intersections with the zone boundaries, only for the marked zones. 

Verification  Test:  Impedance  element  evaluation  without  zone  geometry.  The  process  is similar to a Click sequence test, but no zone graphs are drawn. As in the rest of tests, several methods are available  to define  the  test points, as well as  the  choice  to place  them  in  the various fault loops available. 

Reclose Test: Verification of the relays reclose function, with any number of reclosing cycles. The user  interface allows  the  creation of  logical  sequences, effectively  simulating  successful reclose cycles and / or  the  lockout of  the reclosing element  (by CB  failure, by  time, manual, etc) In addition, special reclose settings commonly found in modern numerical relays can also be  tested. Failed states are highlighted at  the end of  the  test  for easier  identification of  the cause of  failure. The States Handler  tool allows viewing and editing  the states generated by the program to test the sequence. 

Evolving  Fault  Test:  Evaluation  of  relay´s  behavior  under  evolving  fault  conditions  during  a single‐phase recloses cycle. The program automatically generates a default sequence of states to perform  the  test. The  sequence  can  then be executed  right away or  fine‐tuned with  the States  handler  in  order  to match  specific  test  requirements.  Events  resulting  from  the  test sequence can also be viewed in alphanumeric and graphical form with the Log viewer. 

SOTF (Switch On To Fault): This test module provides an easy method to evaluate the relay's performance  in  a  SOTF  situation  by  allowing  trying  various  fault  locations  and  occurrence times. The operation of  the  reclose  function and  the acceleration algorithms  is also  tested. With a  simple  setup of general  test  conditions made by  the user  (fault  loop,  fault  location, fault  at  CB  close  or  after  the  SOTF  time),  the  program  automatically  generates  a  default sequence of states to perform the test. 

Trip on Reclose: Test to evaluate the relay´s trip acceleration function during a reclose cycle. It also  includes  the option  to verify  the protection's  return  to normal operation after  the TOR Action Time has elapsed. 

Zone 1 Extension Test: Evaluation of the relay performance when this clearing‐fault function is active, under various fault types and locations, as well as for diverse operation behavior by the remote protection. The test fault can be simulated at various locations on the protected line or at the nearest section of an adjacent line. 

Loss  of  Load:  This  test  module  allows  the  evaluation  of  the  LOL  function  in  diverse circumstances. The Loss of Load function, also called Remote End Opened (REO), is commonly used in link lines with CBs at both ends, and basically consists of detecting the tripping of the opposite CB after a short circuit has occurred very close to it. Three LOL characteristics may be tested, with the corresponding choice of fault locations. 

CB  Failure:  Test  to  evaluate  the  CB  failure  protection  scheme.  Based  on  a  simple  setup  of general  test  conditions made  by  the  user,  the  program  automatically  generates  a  default sequence of states to perform the test. The sequence can then be executed right away or fine‐tuned with the States handler. Upon execution, the test sequence  is transmitted to the state sequencer in the test set, where the relay's reaction is collected and re‐transmitted back to the program for final assessment. 

Fuse  Failure  Test:  This  test module  has  been  designed  to  allow  the  testing  of  the  various features and settings in the Fuse Failure function implemented in digital relays. 

Load Encroachment test: This module provides test options to verify the proper operation of a distance  relay under heavy  load conditions. The  relay should operate  if and only  if a  fault  is simulated in maximum load scenery. 

       

Page 20: Mentor 12 Software Overview - 1964978058.rsc.cdn77.org1964978058.rsc.cdn77.org/wp-content/uploads/2015/12/Mentor-12... · FAULT Three‐state Fault ... Playback and processing of

 

©EuroSMC, S.A. November 2014 

     

    RROOOOTTSS  ‐‐  DDIIFFFFEERREENNTTIIAALL  MMOODDUULLEE  

The set of differential test modules is used to test the operation of protective devices that  implement  the  IEEE  function 87 and  includes  the  following modules  to  test  the operation values and also the trip blocking by the harmonic restrain: 

Classic  Differential  87C:  Module  used  to  check  the  operation  of  conventional differential relays (usually electromechanical or static). Transformer  Differential  87T:  Designed  for  testing  numerical  relays  for  differential protection of transformers.  Generator/Motor  Differential  87GM:  Designed  for  testing  rotating  machines differential relays.  Busbar Differential 87B: Designed for testing busbar differential relays. 

CLASSIC DIFFERENTIAL 87C: The module's functionality is distributed in the following sections: Technical  Data:  section  to  set  up  the  general  parameters  associated  with  the  data  of  the protected object, the characteristics of the protective device and the applied settings: number of windings, tap settings, restraint current calculation, current and time tolerances. Differential  Operating  Characteristic:  section  for  configuration  of  the  characteristic  and  the operating  times  of  the  relay,  as well  as  defining  the  parameters  for  the  harmonics  restrain. ROOTS  allows  to  edit  in  a  very  simple way  the  relay  characteristic,  either  by  implementing various types of predefined characteristics,  or by custom design. In tests designed for harmonic restrain  in differential  relays, ROOTS allows  to add a certain component of a harmonic  to  the fundamental frequency value. Although the common practice is to work with the 2nd harmonic (Inrush Blocking) and 3 ° or 5 ° (Blocking by over excitation), harmonics from the second to the eighth can be manipulated. Test  List: Multiple  tests  can  be  attached  to  the module  from  the  test  types:  click  sequence, search, and harmonic restraint. Click Sequence Test: in Test Values window the user can define the test points for each phase, to be  inserted  in several ways, by coordinates values, clicking on the graph or by Smart Sweep insertion of multiple  test points evenly distributed  at  the  limits of  the  tolerance  zone,  in  the selected  fault  loops.  In  the  graph  the operating  characteristic of  the  relay  is  shown with  the zones of tolerance in the Idiff/Ibias plane. The evaluation of the test points, either trip or no trip, will be done according to its position above or below the characteristic of the relay, or within the tolerance zone, and the different relay behavior in each case. Search  Test:  This  test  allows  finding  the  boundary  trip  values  which  corresponds  with  the characteristic of  the  relay.  It's actually a confirmation of  the accuracy of  the  relay. The  test  is done by injecting consecutive faults by means of pulse ramps that are coming into the searched zone. The search  for a point stops when the protection trips and then starts the search of the next point. There  is a window to display the wiring of the analog current channels.  In the text setting window the user can establish common parameters for all selected test points, such as the search type, search resolution and interval, and the windings to test. Harmonics Restraint Test: The harmonic restraint test evaluates the response of the relay to the harmonic content variation in measured current signals. Current is injected through one or more phases in a previously selected winding, where it is possible to indicate the phases which contain harmonics  or  not.  The  reaction  of  the  relay  is  evaluated  according  to  the  adjusted  set parameters. The test points are defined  in the harmonic restraint characteristic with the zones of  tolerance, where  the  differential  current  is  drawn  over  the  harmonic  content  of  the  test current. For simulating different  inrush conditions, the  initial phase shift between fundamental and harmonics can be specified. An automatically generated relay connection scheme is shown before the test is executed.    

       

Page 21: Mentor 12 Software Overview - 1964978058.rsc.cdn77.org1964978058.rsc.cdn77.org/wp-content/uploads/2015/12/Mentor-12... · FAULT Three‐state Fault ... Playback and processing of

 

©EuroSMC, S.A. November 2014 

      

TRANSFORMER DIFFERENTIAL 87T: Designed  for  testing numerical  relays  for differential protection of transformers. The module's functionality is distributed in the following sections: 

 Technical Data: an extensive modeling of the protected device and the relay data gathers all the data  for  the  calculations  required  to  facilitate  testing,  suitable  for  transformer  differential schemes with up to 3‐windings and up to nine currents to be injected. The automatic calculation of  the  test currents eliminates  the most  time consuming and error‐prone manual tasks. Testing the correct operation of the relay becomes simple, time saving, and cost efficient. Adjustments for each winding are available such as: transformer windings, winding connection, CT currents, CT connection and polarity, grounded in zone winding, etc. The Relay Data  gathers  all  the  data defining  the operation of  the protective  relay:  reference current, restraint current calculation, phase reference winding, maximum  test current, current and time tolerances, remove zero sequence settings, etc. Differential Operating Characteristic: section to configure the characteristic and  the operating times of the relay, as well as defining the parameters for the harmonics restrain. Similar section to the Differential Classic module. It includes single slopes, double continuous and discontinuous slopes and user‐defined curves, with easy programming of pickup thresholds, slope of segments, change points and offset. As in the rest of ROOTS modules, the test solution provides evaluation and assessment of results against nominal characteristics and tolerances, and the results report is generated automatically, including the characteristic diagrams. Test List: Multiple  tests can be attached  to  the module  from  the  test  types: verification, click sequence, search, and harmonic restraint. Verification Test:  The  verification  test has  the main purpose of  verifying  the  correspondence between  the equipment  to protect,  the  settings of protective equipment, differential module settings, and wiring connections, i.e. to verify that the protection is stable for faults outside the protected zone. The executed test consists of a simulation of  load conditions or external faults and checks the behavior of the protection. For these test conditions  it  is verified that the relay does  not  trigger  (at  least  for  differential  protection).  It  may  optionally  be  verified  the correspondence between values of restrain current and differential current measured with the values injected according to the test settings. Click  Sequence Test:  This  test  allows  checking  the operation  characteristic  of  the differential relay verifying its ability to discriminate between faults inside and outside the protected area. It is composed by a sequence of points defined by the user in the test window. Each test point has a  pre‐fault,  Fault  and  Post‐fault  condition.  The  execution  of  the  test  involves  injecting sequentially the three conditions in each test point, determine if a trip has been issued, and if so evaluate  the  operating  times.  The  time  obtained  in  each  test  point  is  compared  with  the theoretical value calculated taking into account the current and time tolerances pre‐established, qualifying the result as correct or  incorrect and printing  it both  in the test point table and the test  graph.  As  in  the  rest  of  ROOTS  modules,  the  test  solution  provides  evaluation  and assessment of  results against nominal  characteristics and  tolerances, and  the  results  report  is generated automatically, including the characteristic diagrams. Search Test: test for finding the boundary values of the characteristic of the relay. It is actually supposed to confirm the accuracy of the relay, so the choice of the size of the increments is very important.  It  is performed by  injecting consecutive  faults  that will enter  in  the searched area. The user can establish common parameters for all selected test points, such as the Location of the Fault,  if voltage signals are  to be applied, search  type, search  resolution and  interval, and available trigger type. Harmonic Restraint Test: The harmonic restrain test evaluates the response of the relay to the harmonic content variation in measured current signals. It consists in injecting current in one or more phases of previously selected windings, where the presence or no presence of harmonics can  be  indicated.  The  blocking  function  of  the  relay  is  evaluated  according  to  the  adjusted parameters against the inrush currents and the over excitation.  

.

Page 22: Mentor 12 Software Overview - 1964978058.rsc.cdn77.org1964978058.rsc.cdn77.org/wp-content/uploads/2015/12/Mentor-12... · FAULT Three‐state Fault ... Playback and processing of

 

©EuroSMC, S.A. November 2014 

  

GENERATOR/MOTOR  DIFFERENTIAL  87GM:  Designed  for  testing  rotating  machines differential relays. The module's functionality is distributed in the following sections: 

 Technical  Data:  the  setting  of  Generator/Engine  Data  gather  all  relevant  data  from  the protected machine and from the current transformers used by the differential protection. Reference current, Ibias calculation, and time and current tolerances are set in the relay data, in a similar way to rest of ROOTS differential modules. Operating Characteristic: ROOTS  allows editing of  the  relay  characteristic  in  a  simple way by choosing from a set of predefined types or by custom building one when necessary. Test List: Multiple  tests can be attached  to  the module  from  the  test  types: verification, click sequence and search. Verification Test: The Verification test provides a method to check the consistence between the protected device, the relay settings, the Differential module's setup, and the test connections.  This  test  simulates  load  conditions  and/or  external  faults under which  the  relay's differential element  should  not  operate.  If  the  relay  features  a  measurements  display,  the  user  can optionally  compare  the  values measured  for  the  restrain  and  differential  currents  with  the quantities generated by ROOTS. The assessment of each test point consists of verifying that the differential element did not operate and that the quantities measured by the relay fall inside the tolerance threshold set. Click Sequence Test:   The Click Sequence allows the user to verify the accuracy of the relay at determining  if  a  fault  falls  inside  or  outside  the  protected  zone.  This  test  generates  test sequences from test points defined by the user in the test window. Each test point will include pre‐fault, fault and post‐fault stages. All test points defined within the test share the same pre‐ and post‐fault conditions.   The execution of  the  test  involves  injecting  the  three conditions at each  test point  sequentially, determine  if operation has occurred and evaluate  the operation time compared to the theoretical time in the relay's characteristic. Search Test: This tool provides a method to locate the boundaries of the relay's characteristic. A series of consecutive faults  is  injected that gradually enter the searched zone. The search for a point  is  stopped  when  the  relay  operates,  and  the  process  is  resumed  for  the  next  point searched. This method reveals the actual accuracy of the relay.  

BUSBAR DIFFERENTIAL 87B: Designed  for testing busbar differential relays. The module's 

functionality is distributed in the following sections:  Technical  Data:  Up  to  6  feeders  connected  to  the  busbar  can  be  configured,  with  the corresponding  setting of  the CT data  for each  feeder. Directional blocking  technique used by some relay manufacturers can also be activated in this module. Operating Characteristic: ROOTS  allows editing of  the  relay  characteristic  in  a  simple way by choosing from a set of predefined types or by custom building one when necessary. Test List: Multiple  tests can be attached  to  the module  from  the  test  types: verification, click sequence, search and breaker fail. Verification Test: The Verification test provides a method to check the consistence between the protected device, the relay settings, the Differential module's setup, and the test connections. This  test  simulates  load  conditions  and/or  external  faults under which  the  relay's differential element should not operate. The user can also compare  the values measured  for  the  restrain and differential currents with the quantities generated by ROOTS. Click Sequence Test: The Click Sequence test allows the user to verify the accuracy of the relay at  determining  if  a  fault  falls  inside  or  outside  the  protected  zone.  This  test  generates  test sequences  from  test  points  defined  by  the  user  in  the  test window.  The  Smart  Sweep  tool automatically  inserts  test  points  over  the  tolerance  boundaries.  The  user may  set  the  Ibias values for the first and the last point, as well as the interval used between consecutive points. Search:  This  tool  provides  a method  to  locate  the  boundaries  of  the  relay's  characteristic. A series of consecutive faults is injected that gradually enter the searched zone. Breaker Fail: This test evaluates the behavior of the CB failure function in diverse circumstances that are easily configurable by  the user. Once  the  fault condition and  the CB  failure  function's parameters have been entered, ROOTS will generate a  sequence of  test  states automatically. When the Circuit Breaker Failure function is carried out by the busbar differential relay, it must be aware of any protective trip command issued to the managed circuit breakers.     

Page 23: Mentor 12 Software Overview - 1964978058.rsc.cdn77.org1964978058.rsc.cdn77.org/wp-content/uploads/2015/12/Mentor-12... · FAULT Three‐state Fault ... Playback and processing of

 

©EuroSMC, S.A. November 2014 

     

RROOOOTTSS  ‐‐  VVOOLLTTAAGGEE  MMOODDUULLEESS                                                                                                        NNEEWW!!  ((22001155))        

Set of Voltages Modules  to  test  the operation of protective devices with  functions 27,  47  and  59.  It  includes  the  following modules  to  test  the  operation  values  of voltage relays: Three‐phase Voltage Module:  used  to  check  the operation  of  three‐phase  voltage relay. Lets you check the elements acting on the values of phase to ground, phase to phase, positive sequence, negative sequence, neutral and residual.  Single‐Phase Voltage Module:  is used to check  the operation of voltage relays with only one measuring voltage. 

The module's functionality is distributed in the following sections:  Technical Data:  section  to  set  up  the  general  parameters  associated with  the  data  of  the protected object: Voltage input connection, residual voltage, working with primary values, and voltage and time tolerances. Elements: section for configuration of the characteristic and the operating times of the relay. 

It includes characteristic templates, which formulas can be also edited, and also allows for the 

introduction of a Custom  table of over and undervoltage and  time  curve points. The  relays 

may have independent adjustment for the following: 

Over voltage:  

Phase‐N Elements: Act against increasing of measured or calculated phase voltage.  

Phase‐phase elements: Act against increasing of measured or calculated line voltage.  

Sec (+) Elements: Act against increasing of calculated positive sequence voltage.  

Neutral elements: act against increasing of calculated neutral voltage.  

 Sec (‐) Elements: Act against an increase of calculated negative sequence voltage.  

Residual Elements: Act against an increase of measured residual voltage.  

Under voltage:  

Phase‐N Elements: Act against decreasing of measured or calculated phase voltage.  

Phase‐phase  elements:  Act  against  decreasing  of  measured  or  calculated  line 

voltage.  

Sec (+) Elements: Act against decreasing of calculated positive sequence voltage.  

 Test  List:  Click  Sequence  and  Pick  up/Drop  out  tests  can  be  attached  to  any  of  the  two modules. Click Sequence Test: in Test Values window the user can define the test points for each phase, to  be  inserted  in  several  ways,  by  coordinates  values  (the  value  of  the  test  voltage  or optionally in times the nominal voltage), clicking on the graph or by Smart Sweep insertion, in the selected fault loops. In the graph the operating characteristic of the relay is shown for V< and V> elements (under voltage and overvoltage). The working is similar to other shot tests in Roots.  In  the   click sequence  test you can select  the  type of  fault  that you want  to perform. ROOTS,  in  the  3‐phase  Voltage module,  allows  you  to  select  a  total  of  9  different  faults grouped  into  5  types:  single‐phase,  bi‐phase,  three‐phase,  negative  sequence  and  residual faults. Pick  Up/Drop  Out  test:    This  test  allows  finding  pickup  and  dropout  values  of  the  active elements  in  the  device with  the  desired  accuracy.  It  is  performed  by  injecting  consecutive faults  through  ramps  that  vary  the  quantities  of  interest  in  the  selected  interval, which  is selected in the Test Settings, as well as the resolution. The Pickup Search method allows you to select between pulses ramp or binary search.  In the test points  list you can see the ramping details for each test point.    

       

Page 24: Mentor 12 Software Overview - 1964978058.rsc.cdn77.org1964978058.rsc.cdn77.org/wp-content/uploads/2015/12/Mentor-12... · FAULT Three‐state Fault ... Playback and processing of

 

©EuroSMC, S.A. November 2014 

   

  

  

RROOOOTTSS  ‐‐  FFRREEQQUUEENNCCYY  MMOODDUULLEE                                                                                                    NNEEWW!!  ((22001155)) 

The  frequency  module  is  used  to  test  the  operation  of  protective  devices  with frequency dependent functions. This includes functions of frequency, under and over frequency, Hz/s element (rate of change of frequency), and V/Hz protection (overflux or overexcitation element) 

The module's functionality is distributed in the following sections: Technical  Data:  configuration  of  the  the  general  parameters:  Voltage  input  connection, voltage, time, frequency and  dF/dT tolerances. Elements: section for adjustment and configuration of the elements and the operating times available in the relay under tests. It includes elements for: 

o Frequency:  F<  under frequency                          F> over frequency   Includes parameters such as Starting Cycles Count, Inhibit Voltage, Pick up level,     Time Index, Reset Time, Reset Ratio. 

o dF/dT: includes similar parameters plus the Direction (if the elements operates with descending  frequency, ascending  frequency or both) and  the Supervising Frequency  (which  define  the  frequency  threshold  level  for  ascending  and descending elements) 

o Volt/Hz:  includes  a  Characteristic  Template  editor,  with  formulas  or  custom table of Volt/Hz and time values. 

 

Test List: the following tests can be attached to the module: Click Sequence Frequency Test: This test generates test sequences from test points defined by the  user  in  the  test  window.  Fault  Frequency  value  can  be  in  Hz  or  times  the  nominal frequency. The graph  includes  the active elements  in  the  relay  to be sensitive  the  test. This also includes frequency and V/Hz elements if exist and are active, unless the settings "Volt/Hz Elements disabled" is selected in the Test Settings. Pick Up/Drop Out Frequency test:   This test allows finding pickup and dropout values of the active  elements  in  the  device  with  the  desired  accuracy.  It  is  performed  by  injecting consecutive faults through ramps that vary the quantities of  interest  in the selected  interval, which is selected in the Test Settings, as well as the resolution.  Voltage Inhibit Frequency: allows searching for the inhibition voltage (minimum voltage value for  which  are  taken  as  valid  the  frequency  measurement  in  frequency  elements).  It  is performed by voltage ramps at a defined frequency. Click  Sequence dF/dT: Generation  of  test  points  list,  each  one  being  a  frequency  ramp,  to evaluate the trip setting of df/dt element. Frequency elements and Volt/Hz elements can be disabled if required. Pick Up/Drop Out dF/dT: searching of pickup and drop out values of active df/dt elements in the device with the desired accuracy. It is performed by injecting consecutive faults ramps that vary the quantities of df/dt in the selected interval until the operation or the limit range. Voltage  Inhibit dF/dT: Test  for  searching  the  inhibition  voltage  (minimum  voltage  value  for which are taken as valid measurement for df/dt elements). It is performed by frequency ramps at a defined df/dt value by varying the voltage on each one to reach the value of the operation or the limit of the range. Click Sequence Volt/Hz: with different modes of tests, it evaluates the trip times for the series of  test points  selected  in  the V/Hz  characteristic.  Frequency elements  can be disabled.  The fault points or overflux values, can be introduced in V/Hz or times the ratio nominal voltage/ nominal frequency. Pick  up/Drop Out  Volt/Hz:  Test  for  searching  pickup  and  drop  out  values  for  active  V/Hz elements  in  the  device with  the  desired  accuracy.  It  is  performed  by  injecting  consecutive faults ramps that vary the quantities of interest in the selected interval until the operation or the  limit  range.  As  in  similar  tests,  the  search  interval,  resolution, maximum Overflux  and disabling of other elements, are part of the test settings.     

Page 25: Mentor 12 Software Overview - 1964978058.rsc.cdn77.org1964978058.rsc.cdn77.org/wp-content/uploads/2015/12/Mentor-12... · FAULT Three‐state Fault ... Playback and processing of

EUROPEAN OFFICE EUROSMC S. A. 5840 POLIGONO INDUSTRIAL P-29, C/BURIL 69, 28400, COLLADO VILLALBA, MADRID, SPAIN TEL: +34 91 849 8980 [email protected] [email protected] USA OFFICE NORAMSMC INC. SOUTH MEMORIAL DRIVE - SUITE 208 TULSA – OK7 74145 - USA TEL: +1 918 622 5725 [email protected] LATIN AMERICA OFFICE EUROSMC S. A. CANTUARIAS 270, OF 604, MIRAFLORES, LIMA, PERU TEL: +51 96 81 600 96 [email protected] ASIAN OFFICE EUROSMC S. A. UNIT A, 15/F, CHARMHILL CENTRE, 50 HILLWOOD RD, TSIM SHA TSUI, KOWLOON, HONG KONG SAR TEL: +852 3590 2499 [email protected]

   

 

     

Test Equipment for Substation and Protection Relay Testing

► PRIMARY INJECTION TEST SETS

► MULTIFUNTIONAL PRIMARY TEST SYSTEM 

► SECONDARY INJECTION TEST SETS 

► UNIVERSAL RELAY TEST SYSTEM 

► SINGLE/3‐PHASE RELAY TESTING 

► AUTOMATION RELAY TESTING SOFTWARE 

► ELECTRICAL MEASUREMENT 

► CIRCUIT BREAKER ANALYZERS 

► PHASE ANGLE METERS 

► DIGITAL MICRO‐OHMETERS 

► IEC‐61850 GOOSE SNIFFER 

► TRANSFORMER MAINTENANCE 

► TRANSFORMER TEST EQUIPMENT 

► SUBSTATION TEST SETS 

► MCB TESTING 

w w w . s m c i n t . c o m