Medical Gas Console Outlet
Genstar Technologies Company, Inc. 4525 Edison Avenue, Chino, CA 91710 T. 909.606.2726 F.909.606.6485 www.genstartech.com
MEDICAL GAS CONSOLE OUTLETOHMEDA® COMPATIBLE 180o TUBING
Features
•AcceptsOhmeda®,Chemetron®orPuritan-Bennett®
quickconnectandDISSgasspecificadapters
•Indexedtopreventinterchangeabilityofgasservices•100%hydrostaticallytested•ComplieswithNFPA99andCGAG-4.1standards
Medicalgasoutlet(s)shallbemanufacturedbyGenstarTechnologiesCo.,Inc.(GENTEC®).Consoleoutletshallbedesignedforconcealedpipinginstallationandavailableforgasservicesindicated.
Outletsshallbedeliveredtothecustomerinagasspecificlatchvalveassembly,andamatchinggasspecificlatchvalveassembly,bothcleanedforoxygenuseandinsealedpackages.Optionaltrimplatescanbeprovidedtotrimeachoutletassemblyandallowlatchvalvetobeindividuallyremovedforservicing.
ThelatchvalveassemblyshallbeOhmeda,ChemetronorPuritan-Bennettquickconnectcompatible,orhaveCompressedGasAssociation(CGA)DiameterIndexSafetySystem(DISS)threadedconnector,andacceptonlycorrespondinggasspecifictypeadapters.Eachlatchvalveassemblyshallbecolor-codedforeaseofgasidentificationpertheappropriatestandards(USorISO).Latchvalveassembliesshallhavegasspecificpinindexingcorrespondingtotherough-inassemblytopreventinterchangeabilityofgasservices.Outletscanbeeasilyconvertedfromoneadaptertypetoanotherbyreplacingthelatchvalveassemblywithanotherofthesamegasservice.
Universalrough-inassemblyshallincludearough-inplate(16ga.)withgasinlettubingsilverbrazedat180degreestotheoutletbody.Inlettubingshallbetype“K”copper,1/2”O.D.(12.7mm),andextend6-1/2inches(165mm).
Rough-inassemblyshallacceptonlythespecifiedgasservicebyuseofindexes.Adustplugshallbeprovidedtoprotectrough-inassemblyfromcontaminationduringhandlingandinstallation.
Rough-inassembliesshallacceptanylatchvalveassemblyofthesamegasservice.Thelatchvalveassemblyshallbeinterchangeable,allowingconversionfromoneconnectionstyletoanotherwithoutshuttingdownthemedicalgaspipingsystem.
Allpositivepressuregasoutletsshallhaveaprimaryandsecondarycheckvalve,wherethesecondaryvalveintherough-inassemblyallowsservicingofthelatchvalveassemblywithouthavingtodisruptgasservicetotheoutlet.
Allassembliesshallbe100%testedforleaks,manufacturedtocomplywiththelatesteditionofNFPA99,andULListed.
Specifications