mechanically attached tpo · the installation of any mule-hide roof system is in a coastal area or...
TRANSCRIPT
Mule-Hide Products Co., Inc. 05-1110
MECHANICALLY ATTACHED TPO
07 54 00/MUL Revision Date: September 2018
TABLE OF CONTENTS PART 1 GENERAL Page
1.01 Description .................................................................. 1 1.02 Quality Assurance ....................................................... 2 1.03 Submittals .................................................................... 2 1.04 Product Delivery, Storage and Handling ...................... 3 1.05 Job Conditions ............................................................. 4 1.06 Warranties ................................................................... 7
PART 2 PRODUCTS
2.01 General ........................................................................ 9 2.02 Roofing Membrane ...................................................... 9 2.03 Accessory Materials .................................................... 10 2.04 Related Materials By Others ........................................ 13 2.05 Precautions ................................................................. 16
PART 3 EXECUTION
3.01 General ........................................................................ 17 3.02 Substrate Conditions ................................................... 17 3.03 Preparation Of Existing Substrate ............................... 20 3.04 Vapor Retarder ............................................................ 21 3.05 Wood Nailers ............................................................... 22 3.06 Insulation Installation ................................................... 23 3.07 Membrane Installation ................................................. 24 3.08 Sheet Attachment ........................................................ 25 3.09 Welding of Lap Areas .................................................. 31 3.10 Additional Membrane Securement (Base Attachment) 33 3.11 Flashing Installation ..................................................... 35 3.12 Drains, Expansion Joints, Pitch Pans .......................... 38 3.13 Walkway Installation .................................................... 39 3.14 Temporary Tie-Ins ....................................................... 40
ATTACHMENTS AweroWeb Supplement ..........................................................41
PLEASE CONSULT THE MULE-HIDE WEBSITE FOR THE MOST CURRENT INFORMATION AT WWW.MULEHIDE.COM
MULE-HIDE PRODUCTS CO., INC Page 1 05-1111
MECHANICALLY ATTACHED TPO SYSTEM SPECIFICATION Revision Date: September 2018 PART 1 - GENERAL 1.01 Description
A. Scope:
1. Furnish and install a Mechanically Attached TPO Roofing Membrane with flashings and accessories necessary to comprise a roofing system. The Mule-Hide TPO products and accessories shall be installed in strict compliance with current specifications and drawings as published by Mule-Hide Products Co., Inc. (“Mule-Hide”).
2. The Mule-Hide Mechanically Attached TPO (Thermoplastic
Polyolefin) Membrane Roof System utilizes a 45-mil (.045 inch), 60-mil (.060 inch) or 80-mil (.080 inch) thick reinforced TPO sheet. The TPO membrane is mechanically attached to the roof deck with 2.4” Seam Plates and approved Mule-Hide Fasteners. Adjoining sheets are overlapped a minimum of 5-1/2 inches and welded with a robotic welder. The field membrane is secured at all changes in plane greater than 2” per foot. Note: All membrane thicknesses listed in this specification are nominal thicknesses.
B. Related Work:
The work includes, but is not necessarily limited to the installation of:
1. Vapor Retarder (where specified) 2. Wood Blocking (Nailers) 3. Insulation 4. Slip Sheet (where required) 5. Fasteners 6. Roof Membrane 7. Roof Membrane Flashings 8. Metal Flashings 9. Adhesives 10. Sealants 11. Walkways
MULE-HIDE PRODUCTS CO., INC Page 2 05-1111
System Specifications MECHANICALLY ATTACHED TPO Revision Date: September 2018
Note: Mule-Hide recommends adherence to industry standards
(SMACNA) for the installation of any metalwork. 1.02 Quality Assurance
A. The Mule-Hide Mechanically Attached TPO Membrane Roofing System shall be installed by an independent roofing contractor eligible (Warranty Eligible) to apply for Mule-Hide “system warranties” when Standard System or Premium System Warranties are requested.
B. There shall be no deviations from this specification or the Mule-
Hide Products Co., Inc. ("Mule-Hide") standard details without prior written approval from Mule-Hide's Warranty Department
C. Upon completion of the installation according to the terms and
conditions stated in this specification and in accordance to the information given in the Warranty Application and Pre-Job survey form and any additional approvals which might have been given by Mule-Hide, an authorized representative of Mule-Hide may perform an on-site inspection of the roof to verify that all installation and material requirements have been met.
Note: Inspections are only conducted on projects where a "System Warranty" is requested. Inspections are not conducted on projects not requiring a Mule-Hide System Warranty or when only a "Roofing Membrane Limited Warranty” is requested. The sole purpose of an inspection by a Mule-Hide Representative is not to be a final inspection for the benefit of the Building Owner/Owner’s Representative. It is for the benefit of Mule-Hide to determine if a warranty may be offered for the project.
D. Mule-Hide reserves the right to reject any roof system and refuse to
issue any warranty on roofs which do not comply with Mule-Hide's specifications or current policies.
1.03 Submittals
A. Prior to the time of bidding, the roofing contractor shall submit to the Owner or Owner's representative the following items:
1. Copies of Mule-Hide specifications and published product
data. 2. Samples of each material to be used in the roof system. 3. Specimen copy of Mule-Hide Products Co. warranty
MULE-HIDE PRODUCTS CO., INC Page 3 05-1111
System Specifications MECHANICALLY ATTACHED TPO Revision Date: September 2018
4. Dimensioned shop drawings to include an outline of the roof
and appropriate details for flashings and terminations. 5. Certification from insulation, roofing and accessory
components manufacturers that all materials supplied comply with identified ASTM and industry standards.
6. Verification that system specifications meet all identified code and insurance requirements including but not limited to the following:
a. Factory Mutual Research Laboratories Norwood, MA b. Underwriters Laboratories
Northbrook, IL
Note: It is the Building Owner/Owner’s Representative’s responsibility to determine what submittals are required for the project.
B. Submit to Mule-Hide, prior to the job start, a Heat-Weld System
Warranty Application to be reviewed by the Mule-Hide Warranty Department to determine the acceptability of the project based on the information provided.
1. The Heat-Weld System Warranty Application (“Warranty
Application”) must be completely filled out and should be accompanied with a copy of the written roof specification (if available). Also included should be any requests for deviations to Mule-Hide’s standard published specification and details.
2. A roof drawing shall be submitted with the Warranty
Application indicating all dimensions and locations of all penetrations.
1.04 Product Delivery, Storage and Handling
A. All products delivered to the job site shall be in their original unopened containers or wrappings and clearly labeled with the manufacturer's name, product identification and date of manufacture.
B. Protect all materials from damage during transit, storage and delivery to the job site. Place all materials on pallets and protect from moisture.
C. Store all materials in a dry, clean area protected from the elements.
MULE-HIDE PRODUCTS CO., INC Page 4 05-1111
System Specifications MECHANICALLY ATTACHED TPO Revision Date: September 2018
All rolls of membrane shall be stored flat on pallets.
D. All adhesive and caulking shall be stored at temperatures between
60oF and 80oF. Materials exposed to lower temperatures affect the workability and performance of the product. Products shall be restored to the above temperature prior to use.
E. All flammable materials shall be stored in a cool, dry area away
from open flames and sparks. Follow precautions outlined on containers or supplied by the material manufacturer/supplier.
F. All materials determined as being damaged (confirmed by Mule-
Hide) due to improper storage on the job site are to be replaced with new materials
1.05 Job Conditions
A. This specification shall not be considered applicable without the appropriate additional specifications approved by Mule-Hide if it should be determined that any of the following conditions exist:
1. The installation of any Mule-Hide Roof System is in a coastal
area or high wind zone. 2. If the Mule-Hide Roof System should exceed the structural
load conditions as determined by an architect or Engineer. 3. When chemical or hazardous materials are discharged onto
the Mule-Hide Roof System.
B. Mule-Hide TPO roofing materials may be installed in temperatures below 40° F but only after consultation with the Mule-Hide Technical Department as special precautions or procedures may be necessary. The performance of the materials, installation costs and production rates may be affected.
C. The General Contractor or the building owner shall be responsible for providing adequate surfaces and structures to receive the insulation, Mule-Hide Roof System and related sheet metal necessary for the successful completion of the project.
D. Only as much new roofing as can be made watertight each day
shall be installed each day. This includes all flashing work. E. All substrates to receive new insulation, membrane or flashing shall
be thoroughly dry. Should surface moisture occur, the contractor
MULE-HIDE PRODUCTS CO., INC Page 5 05-1111
System Specifications MECHANICALLY ATTACHED TPO Revision Date: September 2018
shall provide adequate equipment to dry the substrate prior to application of new materials.
F. Prior to and during application, all dirt, debris and dust shall be
removed from surfaces to be roofed for both new and reroofing substrates.
G. On all projects where the Mechanically Attached TPO system is
specified, it is the responsibility of the independent roofing contractor to have the owner or owner's representative verify the condition of the deck or substrate and to confirm the roof deck can withstand the additional load.
H. Precautions shall be taken to prevent wind blow-off or wind damage
during the course of the roofing application. This may necessitate additional securement of temporary construction, materials and equipment.
I. The contractor shall verify and ensure that all roof drain lines are
unblocked before starting work. Any blockages found shall be reported to the owner's representative and Mule-Hide's Warranty Department in writing.
J. Temporary waterstops shall be installed at the end of each day's
work. Temporary waterstops shall be removed at the start of the next day's work and disposed of properly. Waterstops shall be compatible with all materials.
K. Do not install the Mule-Hide TPO Roofing Membrane in direct
contact with any product containing coal tar pitch, creosote or penta-based materials. Consult the Mule-Hide Technical Service Department for special installation requirements.
L. Do not allow contaminants such as petroleum, grease, acid,
solvents, vegetable or mineral oil, animal oil, animal fat, etc. or direct steam venting to come into direct contact with the Mule-Hide TPO Roofing Membrane. Contact the Mule-Hide Technical Service Department for recommendations if such conditions exist.
M. The contractor shall follow and comply with all safety regulations as
recommended by OSHA. N. All work shall be scheduled and executed without exposing interior
building areas to the effects of inclement weather. The existing building and its contents shall be protected against all risks.
MULE-HIDE PRODUCTS CO., INC Page 6 05-1111
System Specifications MECHANICALLY ATTACHED TPO Revision Date: September 2018
O. Arrange work sequence to avoid use of newly constructed roofing
for storage, walking surfaces and equipment movement. Contractor shall provide all necessary protection and barriers to segregate the work areas and prevent damage to adjacent areas. If excessive traffic over newly installed membrane is necessary, contractor shall provide plywood or polyester felt protection to prevent damage. All damaged materials shall be replaced with new materials.
P. All existing roofing materials to be removed for construction shall be
immediately removed from the construction site to a dumping area authorized to receive such debris. Any hazardous materials such as asbestos or materials containing asbestos fibers shall be removed and disposed of in accordance with applicable City, State and Federal requirements.
Q. Any unusual or concealed condition discovered during the course
of the work is to be reported to the owner and Mule-Hide immediately in writing. Work is to be halted until the owner has responded with a solution to the problems.
R. All local building codes and requirements should be followed where
applicable. It is the roofing contractor's sole responsibility to determine and ensure that the roofing system selected complies with all local codes and requirements.
S. Both interior and exterior building areas affected by construction
shall be cleaned up and any damaged areas shall be repaired to the owner's satisfaction.
T. Certain project conditions may require modifications to this
specification. Contact the Mule-Hide Warranty Department if any of the following conditions exist:
1. Roof heights greater than 60 feet. 2. Geographical location in a 100 mph or greater wind zone,
per the ANSI 100 year mean recurrence interval wind isotach.
3. Location with a D exposure as determined in ANSI A58.1
U. When using heat-welding equipment, always review the equipment
manufacturer’s instructions, precautions and warnings.
V. Consideration should be given in the project design to problems
MULE-HIDE PRODUCTS CO., INC Page 7 05-1111
System Specifications MECHANICALLY ATTACHED TPO Revision Date: September 2018
that can precipitate from the smooth surface characteristic of the Mule-Hide TPO membrane
W. On all reroofing projects and for all lightweight deck systems,
pullout tests shall be performed by the independent roofing contractor, fastener manufacturer or owner's representative to verify the condition of the deck or substrate and to confirm system design pullout values. A minimum of 10 pullout tests for areas up to 500 squares, thereafter 2 tests per 100 squares is considered sufficient. Tests should be taken approximately 60% in perimeters and 40% from field areas. Additional tests shall be performed in areas where the integrity of the deck is questionable. A written report of pullout test results shall be submitted to Mule-Hide's Warranty Department for review.
X. Mechanically attached systems are not allowed over Oriented
Strand Board (OSB) decks without prior approval by the Mule-Hide Technical Department. Mule-Hide will not issue system warranties on “As-Built” projects where Mule-Hide did not grant approval prior to the start of the work
1.06 Warranties All Mule-Hide warranties are available for commercial projects. A Roofing Membrane Limited Warranty for a maximum of 10 years is available for residential projects.
A. Mule-Hide's Roofing Membrane Limited Warranty Mule-Hide offers a 10, 15, or 20-year Roofing Membrane Limited
Warranty ("Warranty") for a charge. The Warranty covers only the Mule-Hide TPO membrane (or portion thereof) determined by Mule-Hide to be defective and resulting in roof leaks. This Warranty does not cover workmanship or other components not supplied by Mule-Hide. Mule-Hide does not perform inspections of the installation before issuing the Roofing Membrane Limited Warranty. A Mule-Hide Warranty Application and the appropriate fee must be submitted to Mule-Hide to obtain this warranty. Proof of purchase may be required.
Note: Projects requesting a 20-year Roofing Membrane Limited
Warranty require the use of a minimum 60-mil thick TPO membrane and shall incorporate additional design enhancements as outlined in the 20-year Design Enhancements for TPO Mechanically Attached Roofing System Specification. Mule-Hide
MULE-HIDE PRODUCTS CO., INC Page 8 05-1111
System Specifications MECHANICALLY ATTACHED TPO Revision Date: September 2018
recommends that Warranty Applications be submitted for review prior to bidding the project.
B. Mule-Hide's Standard System Warranty Mule-Hide offers a 10, 15, or 20-year Standard System Warranty
("Standard") for commercial projects for a charge. The Standard warranty is a "No Dollar Limit", labor and material warranty that covers the Mule-Hide labeled membrane and other components supplied by Mule-Hide installed by a Mule-Hide Warranty Eligible Applicator. The Standard warranty does not cover insulation or its attachment system. Metal flashing components not supplied by Mule-Hide are not covered under this warranty. A Mule-Hide Warranty Eligible Applicator must submit a Warranty Application and the appropriate fee to Mule-Hide. Standard warranties require inspections by a Mule-Hide representative.
Note: Projects requesting a 20-year Standard System Warranty
require the use of a minimum 60-mil thick TPO membrane and shall incorporate additional design enhancements as outlined in the 20-year Design Enhancements for TPO Mechanically Attached Roofing System Specification. Mule-Hide recommends that Warranty Applications be submitted for review prior to bidding the project.
C. Mule-Hide Premium System Warranty Mule-Hide offers a 10, 15, or 20-year Premium System Warranty
("Premium") for commercial projects for a charge. The Premium warranty is a "No Dollar Limit", labor and material warranty that covers the Mule-Hide labeled membrane, insulation, other components supplied by Mule-Hide and approved products (such as insulation adhesive or other pre-approved accessories) installed by a Mule-Hide Warranty Eligible Applicator. A Mule-Hide Warranty Eligible Applicator must submit a Warranty Application and the appropriate fee to Mule-Hide. Premium warranties require inspections by a Mule-Hide representative.
Note: Projects requesting a 20-year Premium Warranty require the
use of a minimum 60-mil thick TPO membrane and shall incorporate additional design enhancements as outlined in the 20-year Design Enhancements for TPO Mechanically Attached Roofing System Specification. Mule-Hide recommends that Warranty Applications be submitted for review prior to bidding the project.
MULE-HIDE PRODUCTS CO., INC Page 9 05-1111
System Specifications MECHANICALLY ATTACHED TPO Revision Date: September 2018
D. Metal flashing products supplied by Mule-Hide (Mule-Hide Metal
Accessories) and installed by a Mule-Hide Warranty Eligible Applicator will be covered under a Standard or Premium System warranty.
E. Standard and Premium System warranties are not available for
residential projects. F. TPO tie-ins to built-up (BUR) or any other type of roof system are
not covered by Mule-Hide warranties. G. Contact Mule-Hide for other extended warranties that may be
available.
H. Terms and Conditions of Warranties
Mule-Hide's obligations under the Roofing Membrane Limited Warranty, the Standard System Warranty, and the Premium System Warranty are limited to the specific terms and conditions of the respective Warranties. Sample copies of the Mule-Hide Warranties are available from Mule-Hide upon request.
PART 2 - PRODUCTS 2.01 General
A. The components of the Mechanically Attached Mule-Hide TPO Membrane Roof System are to be products manufactured or supplied by Mule-Hide Products Co., Inc.
B. Components other than those supplied or manufactured by Mule-
Hide may be submitted for review and acceptance by Mule-Hide's Warranty Department. Mule-Hide's acceptance of any other product is based solely on chemical compatibility and published performance data provided by the component manufacturer. Other components may be considered on a job-by-job basis and must be approved in writing by Mule-Hide's Warranty Department. Mule-Hide offers no warranty or guarantee for the performance or suitability of any component not supplied or manufactured by Mule-Hide.
2.02 Roofing Membrane The Mule-Hide Reinforced TPO-c Membrane is available in 45 mils (.045 inch), 60 mils (.060 inch), or 80 mils (.080 inch) thick. The Mule-Hide TPO-c membrane is a polyester scrim reinforced thermoplastic polyolefin roofing
MULE-HIDE PRODUCTS CO., INC Page 10 05-1111
System Specifications MECHANICALLY ATTACHED TPO Revision Date: September 2018
membrane that meets and exceeds the requirements of ASTM D6878 Standard Specification for Thermoplastic Polyolefin Based Sheet Roofing. Refer to the Product Data Sheets for physical properties and additional information. 2.03 Accessory Materials
The following Mule-Hide materials must be used to install Mule-Hide Roof Systems. Mule-Hide will not warrant any application where another manufacturer's product is substituted for a Mule-Hide product. All products listed below are physically and chemically compatible with each other.
A. Mule-Hide TPO Bonding Adhesive - A solvent-based rubberized adhesive used for bonding Mule-Hide TPO-c Membrane to various vertical substrates and insulation boards. Mule-Hide TPO Bonding Adhesive is a two-surface contact adhesive that is applied to both the underside of the membrane and substrate surface. This product may be used with TPO field membrane and flashing membrane. Adhesive is compatible with polyisocyanurate, wood fiberboard insulations, fiberglass-faced gypsum panels, concrete, masonry, metal and wood surfaces.
B. Mule-Hide Low VOC Bonding Adhesive - A high strength solvent-
based contact adhesive that allows bonding of TPO membrane to various porous and non-porous substrates. It is specially formulated using a blend of VOC exempt and non-exempt solvents to meet the < 250 g/l VOC content requirements of the OTC Model Rule for Single Ply Roofing Adhesives.
C. Mule-Hide Low VOC Bonding Adhesive - 1168 – A high strength
solvent-based contact adhesive that allows bonding of TPO membrane to various porous and non-porous substrates. It is specially formulated using a blend of VOC exempt and non-exempt solvents to meet the < 250 g/l VOC content requirements of the OTC Model Rule for Single Ply Roofing Adhesives. This product COMPLIES with the following California counties’ VOC regulations: Alameda, Contra Costa, El Dorado, Los Angeles, Marin, Napa, Orange, Riverside, Sacramento, San Bernardino, San Diego, San Francisco, San Mateo, Santa Clara, Solano, Sonoma, and Tehama.
D. Mule-Hide Aqua Base 120 – A water base adhesive used to bond
Mule-Hide TPO-c membrane to various vertical substrates and insulation boards. Aqua Base 120 is applied as a two-sided contact adhesive when used with standard (non-fleece back) TPO membranes, or as a single-side, wet lay-in adhesive when used with Mule-Hide Fleece Back TPO membrane.
MULE-HIDE PRODUCTS CO., INC Page 11 05-1111
System Specifications MECHANICALLY ATTACHED TPO Revision Date: September 2018
E. Mule-Hide TPO Primer - A high-solids-content, clear (translucent
color), polymer-based splice primer used to prepare TPO membrane for improved adhesion to pressure-sensitive TPO accessories such as: RUSS Strips, TPO Pressure Sensitive Cover Strips, Uncured Flashing Tapes and Cured Cover Tapes. Mule-Hide TPO Primer is required to prepare TPO membrane surfaces prior to the application of any pressure sensitive Mule-Hide accessories.
F. Mule-Hide Low VOC Primer - a solvent-based product designed to
prepare TPO membrane for improved adhesion to pressure-sensitive TPO accessories such as: RUSS Strips, TPO Pressure Sensitive Cover Strips, Uncured Flashing Tapes and Cured Cover Tapes. This Low-VOC product is ideal for use in states where VOC content is a concern.
G. Mule-Hide TPO Flashing - a non-reinforced, .060-inch thick material
primarily used to seal details where field fabrication is necessary, such as drain details, pipe flashings, pitch pocket flashings, seaming joints of the Mule-Hide TPO Coated Metal, and any place where reinforced membrane is not practical.
H. Mule-Hide TPO Universal Corners - .060-inch thick pre-molded,
non-reinforced TPO material. They are uniform in shape and size and provide water tightness at corners formed by TPO coated metal and flashing membrane. They provide a neat, finished look to building corners, curbs and parapet flashings with no cutting or stretching required. Universal Corners are available in white only.
I. Mule-Hide TPO Outside Corners – are pre-molded and are used for
flashing outside corners on a variety of details. Installation is fast and easy with no cutting or stretching required. TPO Outside Corners are available in white, gray, and tan.
J. Mule-Hide TPO Inside Corners – are pre-molded and are used for
flashing inside corners on a variety of details. Installation is fast and easy with no cutting or stretching required. TPO Inside Corners are available in white, gray, and tan.
K. Mule-Hide Weathered Membrane Cleaner - Used to clean in-
service TPO-c membrane prior to the welding process. This cleaner helps to loosen and remove dirt and other contaminants from the surface of the TPO-c membranes and leaves a suitable surface for welding or the subsequent application of TPO Primer.
MULE-HIDE PRODUCTS CO., INC Page 12 05-1111
System Specifications MECHANICALLY ATTACHED TPO Revision Date: September 2018
L. Mule-Hide TPO Pipe Seal - An injection molded, pre-formed
flashing for pipes made of Mule-Hide non-reinforced TPO material. They are designed to add ease to the installation process while offering increased watertight security and improved aesthetics. TPO Pipe Seals are designed as an economical flashing for single pipe penetrations on Mule-Hide TPO-c Membrane roof systems. The TPO Pipe Seals can be used wherever the TPO Pipe Seals may be slipped over the top of the pipe.
M. Mule-Hide TPO T-Joint Cover - 60-mil non-reinforced flashing cut
into a 4.5” diameter circle used to seal step-offs at splice intersections. Installation is mandatory on all 60-mil and 80-mil TPO systems and on all jobs warranted longer than 15 years.
N. Mule-Hide TPO Coated Metal – 24-gauge, galvanized steel to
which is laminated 35 mils (.035" thick) of Mule-Hide non-reinforced TPO Membrane used for flashing and edge metal detailing.
O. Mule-Hide All-Purpose Bar ("A-P Bar") - an extruded aluminum bar,
50 mils (.050") thick, used to terminate adhered reinforced membrane vertical flashings in certain constructions. Mule-Hide A-P Bar may also be used to anchor the field sheet at the base of vertical angle changes.
P. Membrane Fasteners and Discs - Mule-Hide offers a variety of
membrane fasteners and discs to meet specific job conditions and substrates.
Q. Mule-Hide Thermoplastic Pourable Sealant - a one-component
thermoplastic sealant for use in pitch pockets. R. Mule-Hide TPO .045 Reinforced 6” X 100’ – used for stripping-in
TPO Coated Metal and as cover strips over TPO Coated Metal joints.
S. Mule-Hide TPO Cut Edge Sealant – A solvent-based liquid sealant
used to seal the cut edge of the Mule-Hide TPO Membrane. T. Mule-Hide TPO Walkway Rolls – a 1/8-inch thick embossed TPO
membrane available in rolls (34" x 50’) having a herringbone traction surface. Walkway Rolls are trimmed in safety yellow along the length of the sheet to better define the walkway area. Walkway Rolls may be welded directly to the TPO roofing membrane. The yellow edges are smooth without safety lugs to allow for easier welding. Walkway Rolls are available in White and Gray colors.
MULE-HIDE PRODUCTS CO., INC Page 13 05-1111
System Specifications MECHANICALLY ATTACHED TPO Revision Date: September 2018
U. Mule-Hide Insulation - Mule-Hide Poly ISO polyisocyanurate
insulation (flat or tapered) is a closed-cell polyisocyanurate foam core laminated to heavy, black (non-asphaltic) glass fiber reinforced felt facers.
V. Mule-Hide HP Protective Mat - A nominal 6.0-ounce per square
yard (140 grams per square meter) UV resistant polypropylene needle punched fabric. It can be used above the membrane as a slipsheet for protection from damage by materials placed on top of the membrane or below the membrane as a slipsheet over smooth surfaced BUR or Modified Bitumen roofing systems when recovering with a Mule-Hide Mechanically Attached TPO Roofing System.
2.04 Related Materials By Others
A. Wood Nailers
1. Nailers shall be #2 or better lumber. Creosote and asphaltic preservatives are not acceptable. Pressure treated lumber is not required on new construction unless specified by the architect.
2. Wood nailers shall conform to Factory Mutual's Loss
Prevention Data Sheet 1-49. 3. Wood nailers shall be installed as specified on the project
drawings and shall be of a height sufficient to match the thickness of the insulation being used.
B. Vapor Retarders
1. Vapor retarders shall meet specified codes and insurance
requirements. 2. Vapor retarders shall be compatible with insulation and other
accessories. 3. The use and placement of a vapor retarder should be
determined by an architect or engineer. Mule-Hide does not require the use of vapor retarders. However, Mule-Hide recommends that a vapor retarder be considered when both of two conditions are anticipated:
a. The outside average January temperature is below
40°F, and
MULE-HIDE PRODUCTS CO., INC Page 14 05-1111
System Specifications MECHANICALLY ATTACHED TPO Revision Date: September 2018
b. The expected interior winter relative humidity is 45% or greater.
4. Mule-Hide must be contacted for buildings that are
refrigerated (freezers or cold storage) or have a high interior humidity such as, but not limited to, swimming pools, produce storage or locker rooms.
C. Insulation
1. Insulation shall be installed as a protection layer over the
existing substrate or to obtain a desired thermal value. 2. Insulation shall be compatible with the Mule-Hide TPO
Membranes, Mule-Hide Adhesives, Mule-Hide TPO Flashings and other Mule-Hide Accessories.
3. The following insulation boards are acceptable for use with a
mechanically attached roofing system when a standard warranty is requested:
a. Polyisocyanurate insulations having non-asphaltic
facers (foil facers are not acceptable) meeting the physical property requirements of Fed. Spec HH-I-1972 and having a minimum compressive resistance of 18 psi. Thickness minimum is 1.0" or greater as required by insulation manufacturer to span steel deck flutes.
b. High Density Wood Fiberboard - may be used as an
overlay over other insulations. 1/2-inch thick is the minimum requirement when used as an overlay. Mule-Hide requires a minimum 1-inch thick board when installing directly over steel decks. Wood and concrete decks require a minimum 1/2-inch thick board. Minimum thicknesses and attachment rates will vary with wind requirements and deck types.
c. Expanded Polystyrene. Density of boards must be
1.0 PCF certified minimum and meeting ASTM C578, Type II physical properties. Minimum thickness shall be 1.0 inch. When installing directly over a steel deck the minimum thickness shall be as required by insulation manufacturer to span flutes. Check local building codes as a layer of gypsum board may be
MULE-HIDE PRODUCTS CO., INC Page 15 05-1111
System Specifications MECHANICALLY ATTACHED TPO Revision Date: September 2018
required under the EPS insulation (on steel decks) or on top for fire ratings.
d. Extruded polystyrene meeting ASTM C578, Types IV,
VI or VII physical properties. Minimum thickness shall be as required by insulation manufacturer to span steel deck flutes. Check local building codes as a layer of gypsum board may be required under the extruded insulation (on steel decks) or on top for fire ratings.
e. Perlite Insulation – Perlite is not an acceptable
insulation. Perlite may only be used as a fill insulation under an approved insulation. The TPO membrane cannot be adhered directly to perlite insulation.
f. Dens Deck, Dens Deck Prim, or Securock - A
minimum 1/4" thick layer of Dens Deck, Dens Deck Prime or Securock may be used as an overlay over an approved insulation.
g. State and local building codes should be reviewed
regarding the installation of expanded or extruded polystyrene insulation directly over a steel deck.
4. Insulation manufacturer shall provide its recommendations for use and attachment to the owner with a copy sent to Mule-Hide’s Warranty Department. In addition, the insulation manufacturer shall provide a copy of their specific warranty conditions.
5. Mule-Hide Premium Warranties require the use of the Mule-
Hide labeled insulation or insulation by an approved Mule-Hide manufacturer. Use of other insulations may disqualify the project for consideration of the issuance of a Premium warranty. Contact the Mule-Hide Technical Service Department for specific requirements.
D. UL and FM Approved Assemblies
Contact Mule-Hide Technical Department for proper insulated assemblies when projects require compliance with UL or FM requirements. The components may change with the slope, deck type and classification requested.
E. Sheet Metal
MULE-HIDE PRODUCTS CO., INC Page 16 05-1111
System Specifications MECHANICALLY ATTACHED TPO Revision Date: September 2018
1. Metal flashing products supplied by Mule-Hide (Mule-Hide Metal Accessories) and installed by a Mule-Hide Warranty Eligible Applicator will be covered under a Standard or Premium System warranty.
2. TPO Coated Metal and non-coated metal components such
as gravel stops, drip aprons, counterflashings, copings, etc., should be fabricated and installed in accordance ES-1 recommendations and requirements.
3. Sheet metal components supplied by others are not covered
by the Mule-Hide warranties. Contact Mule-Hide’s Technical Department for specific requirements.
F. Insulation Adhesive
1. Mule-Hide Helix® Low-Rise Adhesive. Refer to the
specifications and Helix Product Data Sheet for acceptable insulations, substrates, and bead spacing.
2.05 Precautions
A. Consult Material Safety Data Sheets and container labels for specific safety instructions prior to use.
B. Avoid breathing vapors of solvents, cleaners, primers, sealants and
adhesives. Use with adequate ventilation. Avoid prolonged contact of solvents, sealants, cleaners, primers and adhesives with skin. Solvent resistant rubber gloves should always be worn during use.
C. Do not use Mule-Hide TPO roofing products near fire or flame. Do
not use open flames for drying of surfaces, sealants or adhesives. Do not smoke near flammable products.
D. Do not use oil-based paint on Mule-Hide TPO Coated Metal or
membrane. Contact Mule-Hide's Technical Department for recommendations.
E. Do not allow muriatic acid (masonry cleaner) to come in direct
contact with the Mule-Hide TPO Membrane or accessory products. F. Do not allow Mule-Hide TPO membranes or accessories to come
into direct contact with steam or vents that produce temperatures in excess of 160°F (71°C).
MULE-HIDE PRODUCTS CO., INC Page 17 05-1111
System Specifications MECHANICALLY ATTACHED TPO Revision Date: September 2018
G. The Mule-Hide TPO Roof System may be installed in cold weather
provided the adhesives are stored at room temperature until just prior to use and used within 2 hours. Adhesives left in the cold must be returned to room temperature prior to use.
H. Cover Tapes may lose tack when exposed to temperatures below
40° F. for extended periods of time. A heat gun may be used to warm the product. Only apply heat to the TPO side. Be careful not to overheat. Hot boxes are the preferred method to warm tapes.
I. In colder temperatures when the ambient temperature is near the
dew point, condensation may form on the tape primer and adhesive as the solvents flash off. If condensation occurs, discontinue the application and allow the surface to dry. Do not attempt to dry the surface with heat guns or torches. When weather permits apply a new coat of product.
Part 3 - EXECUTION 3.01 General
A. When installing a Mechanically Attached Mule-Hide Reinforced TPO Membrane Roofing System in cooler weather, it is recommended that liquids such as solvents, sealants, etc., be stored at warmer temperatures (60°F or more but not exceeding 80°F) until just prior to use in order to facilitate the installation.
3.02 Substrate Conditions
The following general conditions apply to the substrate that will receive a Mechanically Attached Mule-Hide TPO Membrane Roofing System for both new construction and reroof applications:
A. The roof deck must be structurally sound to provide proper
securement for mechanical fasteners. Areas showing a loss of integrity due to corrosion, rotting, warping, concrete spalling, etc., must be repaired or replaced prior to installing the roofing system.
B. It is the responsibility of the roofing contractor to perform test cuts
at each roof area prior to reroofing. The condition of the substrate must be suitable to receive a Mechanically Attached Mule-Hide TPO Roofing System. Wet insulation must be removed and replaced. See Single Ply Roofing Institute's guidelines for determining wet insulation.
C. Contact the material manufacturer when the substrate is exposed
MULE-HIDE PRODUCTS CO., INC Page 18 05-1111
System Specifications MECHANICALLY ATTACHED TPO Revision Date: September 2018
to excessively high humidity and/or a corrosive environment. Special fasteners (i.e.- stainless steel) or details may be required.
D. A determination must be made regarding the presence or absence
of coal tar pitch within the existing roof assembly when considering a recover of the old roof system. The presence of coal tar pitch requires the use of a 6-mil poly slipsheet under the insulation unless the coal tar pitch is 10 years or older and is separated from the Mule-Hide TPO membrane by a layer of insulation a minimum of 1-1/2" thick having a minimum "R" value of 5.0. All joints must be butted tightly together or have joints completely taped to prevent volatiles from damaging roof membrane.
E. It is acceptable to install a Mechanically Attached Mule-Hide TPO
Membrane Roofing System over the following deck substrates in new construction, provided that an acceptable insulation is installed over the substrate as needed:
1. Structural Metal Deck (22 gauge minimum) shall conform to
recommendations outlined in Factory Mutual's Loss Prevention Data Sheet 1-28 (requires insulation). Contact Mule-Hide's Warranty Department for attachment requirements for decks less than 22-gauge in thickness. All FM testing is based on attachment to a 22-gauge steel deck.
2. Structural concrete and pre-cast, pre-stressed concrete
(2,500 psi. minimum) shall be cured and dry to industry standards and surface shall be smooth and free of moisture or frost. All sharp ridges or other projections above the surface shall be removed before roofing. An approved insulation board is recommended. Minimum deck thickness shall be 2 inches with 3 inches preferred due to possible spalling damage that may occur to the underside of the deck when using fasteners for insulation and membrane attachment. Insulation may be attached with Type III or IV hot asphalt, approved adhesive or approved fasteners.
3. Lightweight Insulating Concrete Fill and Metal Form work
(minimum 24 gauge metal form work) - the roof deck shall be cured and dry to the deck manufacturer's and/or industry standards and shall be smooth and free of ridges and depressions. All necessary venting as recommended by the roof deck manufacturer shall be accomplished. These decks may be acceptable to receive a Mechanically Attached Mule-Hide TPO Membrane Roofing System after pullout tests have been completed and appropriate fasteners have been
MULE-HIDE PRODUCTS CO., INC Page 19 05-1111
System Specifications MECHANICALLY ATTACHED TPO Revision Date: September 2018
selected. Attachment must be through the insulating concrete into the steel or concrete deck. Insulation board is required. Vapor barriers may be required when installing insulation over new decks.
4. Wood Plank (1" minimum) shall conform to Factory Mutual's
requirements for Class 1 impregnated decks (insulation is required). FM approved wood decks are a minimum, nominal 2-inch thick, tongue and groove planks.
5. Plywood (15/32" minimum) shall be exterior grade (minimum
CDX grade). A layer of an approved insulation is required for reroof applications. On new construction, while insulation board is recommended, fastening directly to the plywood deck is acceptable if the decking is secured with screws or back-out resistant fasteners. Decks attached with common or cement coated nails or staples shall be covered with an approved insulation.
Mechanically attached systems are not allowed over Oriented Strand Board (OSB) decks without prior approval by the Mule-Hide Technical Department. Mule-Hide will not issue system warranties on “As-Built” projects where Mule-Hide did not grant approval prior to the start of the work
6. Cementitious Wood Fiber Decks - Certain cementitious
wood fiber decks may be acceptable to receive a Mechanically Attached Mule-Hide TPO Membrane Roofing System after pullout tests have been completed and appropriate fasteners have been selected. This deck type requires an acceptable insulation.
7. Gypsum Concrete Deck - shall be cured and dry to
manufacturers' and/or industry standards. The surface of the deck shall be smooth and free from ridges and depressions. Certain gypsum concrete decks may be acceptable to receive a Mechanically Attached Mule-Hide TPO Membrane Roofing System after pullout tests have been completed and appropriate fasteners have been selected. This deck type requires an acceptable insulation.
F. For reroofing projects having plywood decks, a minimum of one
layer of an approved insulation is required after the tear-off has been completed.
G. Mule-Hide recommends that all roof surfaces have a positive slope
MULE-HIDE PRODUCTS CO., INC Page 20 05-1111
System Specifications MECHANICALLY ATTACHED TPO Revision Date: September 2018
to provide adequate drainage. There should not be any ponding water 48 hours after a rainfall.
3.03 Preparation of Existing Substrate
A. General
1. To prevent delays or interruptions, coordinate work with other trades or suppliers to ensure that components to be incorporated into the Mechanically Attached Mule-Hide TPO Membrane Roofing System are available as the work progresses. Examine substrates to which the roofing materials are to be applied to ensure that their condition is satisfactory for the Mule-Hide TPO Membrane Roofing System application.
2. Do not permit voids greater than 1/4" wide in the substrate. Concrete substrates shall be cured and free of laitance and curing compounds. Substrates for roofing materials shall be dry and free of oil, dirt, grease, sharp edges and debris. Inspect substrates and correct defects before application of roofing membrane.
3. Specifier or roofing contractor shall determine the condition of the existing roof deck and roofing system. Areas with deteriorated decking, wet insulation or other failed materials shall have those affected materials removed and replaced. Make sure all decking is securely fastened. The roofing contractor has the final responsibility to ensure an acceptable deck is provided to receive the new roof system.
4. Large blisters shall be cut and patched to provide a reasonably level substrate surface.
5. On recover projects, tear off all existing base flashings, cant
strips and projection flashings down to the substrate. The flashing substrate shall be dry and free of oil, dirt, grease, sharp edges and debris.
6. Gravel over existing nailers must be totally removed prior to
installing new nailers and flashings. Verify that the existing nailers are in good condition and securely anchored to the roof decks.
7. When an additional thickness of insulation is being added,
new nailers must be added to match the height of the new
MULE-HIDE PRODUCTS CO., INC Page 21 05-1111
System Specifications MECHANICALLY ATTACHED TPO Revision Date: September 2018
insulation. Nailers must be securely anchored to the roof deck per Section 3.05 of this specification.
8. All roof surfaces shall be free of ponded water, ice, or snow.
Significant ponding that remains after a period of 48 hours should be eliminated by either installing tapered insulation to create positive drainage of the roof surface or by installing new drains in the low areas where the ponding remains. Positive drainage shall also eliminate the possibility of excessive live loads caused by ponding water that could cause structural damage or failure.
9. When removing an existing roof during reroofing, remove
only that amount of roofing and flashing that can be made watertight with new Mule-Hide TPO materials in a one-day period or prior to the onset of inclement weather.
10. Recovering over a gravel surfaced BUR systems require the
installation of an acceptable insulation. Loose gravel must be removed. All lead pipe and drain flashings shall be removed.
11. Smooth Surfaced BUR and smooth Modified Bitumen roofing
systems shall require the installation of an acceptable insulation or slipsheet. All lead pipe and drain flashings shall be removed. Single-ply membranes such as EPDM, Hypalon, PVC or CPA must have all existing flashings removed, the field sheet must be cut up into sections no larger than 10' by 10' and an acceptable layer of insulation shall be installed over the existing field membrane.
12. Polyurethane Foam roofing systems ("PUF") are not
acceptable for recover applications. The PUF system must be completely removed and new insulation installed prior to the installation of the new TPO Roofing System.
13. If a Mule-Hide Premium warranty is requested, the existing
roof system must be removed to the deck prior to the installation of the new roofing system or a moisture survey by an independent third party must be taken, all wet areas removed and a copy of the survey submitted to Mule-Hide with the warranty application.
3.04 Vapor Retarder Installation (where specified)
A. Specific climatic and job conditions may require the use of a vapor
MULE-HIDE PRODUCTS CO., INC Page 22 05-1111
System Specifications MECHANICALLY ATTACHED TPO Revision Date: September 2018
retarder. It is the sole responsibility of the design professional to determine the need for a vapor retarder, and its type and location in the roofing system. A vapor retarder may often act as an "air barrier" which may have a positive effect in reducing internal air pressure. Vapor retarders should be strongly considered for buildings subject to high internal air pressures such as airplane hangars and buildings with many loading bays such as warehouse facilities.
B. The National Roofing Contractor's Association recommends the
installation of vapor retarders when interior relative humidity is 45% or greater and the outside mean average January temperature is below 40°F.
C. Install a vapor retarder over a suitable substrate with all side and
end laps and all penetrations sealed in accordance with the manufacturer's instructions. The vapor retarder may be loosely laid or adhered with the manufacturer's recommended adhesive. In reroofing where the existing built-up roof is to remain, the built-up roof may be an adequate vapor retarder as long as all splits or tears are repaired in order to provide a total barrier to vapor penetration.
3.05 Wood Nailers
A. Wood nailers are required at all roof perimeter edges where metal
edging and gutter systems are specified or where indicated in Mule-Hide’s published Standard TPO Details.
B. Nailers shall be firmly anchored to the decks at a maximum 2'-0"
o.c. and shall resist a pullout force of 200 lbs./linear foot in any direction. A 1/2" vent space shall be provided between adjacent lengths of nailers. Fasteners shall be installed within 6 inches of each end. Spacing and fastener embedment shall conform to Factory Mutual Loss Prevention Data Sheet 1-49.
C. Height of nailers shall match the surface level of the insulation and
roof membrane. The width of the wood nailer shall extend beyond the metal flange to prevent damage to the membrane.
D. All woodwork to be reused shall resist a minimum force of 200
lbs/linear foot in any direction and shall be free of rot. E. Wood nailers with creosote and asphaltic preservatives are not
acceptable. Pressure treated lumber is not required on new construction unless specified by the architect.
MULE-HIDE PRODUCTS CO., INC Page 23 05-1111
System Specifications MECHANICALLY ATTACHED TPO Revision Date: September 2018
3.06 Insulation Installation
A. Mule-Hide accepted roof insulations shall be installed in accordance with Mule-Hide specifications.
B. Mule-Hide accepted roof insulations shall be secured to the roof
deck in accordance with Mule-Hide's requirements utilizing Mule-Hide fasteners or approved compatible fasteners. An approved low-rise foam adhesive for each layer may be substituted for mechanically fastening through the top layer.
C. All roof insulation shall be neatly cut to fit around all penetrations
and projections with a maximum allowable gap of 1/4-inch. D. Open joints shall be repaired with like insulation material. E. Insulation shall be feathered or tapered to provide a minimum sump
area of 36" x 36" where possible at all drains. Crickets and saddles may be installed beneath the specified insulation where possible. Crickets and saddles made from non-compatible insulations materials must be overlaid with an acceptable insulation or underlayment.
F. Install no more roof insulation in one day than can be covered with
the Mule-Hide TPO Membrane or when the onset of inclement weather is anticipated.
G. Insulation installed over steel decks shall be checked so that no
edges are left unsupported along the flutes. All insulations shall be of sufficient thickness and density to prevent breakage under normal roof construction traffic.
H. When installing insulation, the end joints of each row of insulation
shall be offset against the previous row. When more than one layer of insulation is to be used, succeeding layers are to be laid staggered in relation to the previous layer of insulation and all joints shall be offset.
I. When a Mule-Hide Premium Warranty is requested, only Mule-Hide
labeled insulation may be used unless written approval is obtained, prior to job bid, for an alternative insulation.
J. Insulation other than Mule-Hide labeled insulation must be an FM
approved insulation and acceptable to Mule-Hide for use under the Mule-Hide Mechanically Attached Roofing System. Refer to the
MULE-HIDE PRODUCTS CO., INC Page 24 05-1111
System Specifications MECHANICALLY ATTACHED TPO Revision Date: September 2018
insulation manufacturers guidelines for the appropriate type, size and thickness of the insulation needed for use over the respective substrate and under the Mule-Hide Mechanically Attached Roofing System.
K. Mule-Hide's minimum attachment rates shall be as follows:
2' by 4' boards shall be 2 per board 4' by 4' boards shall be 4 per board 4' by 8' boards shall be 6 per board (for boards up to 2" thick) 4' by 8' boards shall be 5 per board (for boards 2” thick or
greater) Contact Mule-Hide’s Technical Department for FM approvals and
required attachment rates that are determined by deck type, insulation brand, type and thickness. When using multiple layers of insulation or more than one type of insulation, the number of fasteners required per board is determined by the top layer of insulation.
L. If a slipsheet is to be installed, the roof membrane shall be installed
immediately after the slipsheet to prevent any displacement. The slipsheet should be overlapped a minimum of 4 inches on each edge. Plates and fasteners may be necessary to anchor the slipsheet when installing in windy conditions. Sufficient fasteners should be used to ensure the slipsheets lay flat under the roof membrane.
3.07 Membrane Installation
A. General - Unroll the Mule-Hide TPO Membrane and position without stretching. Allow the membrane to relax at least 15 minutes when the temperature is above 60°F, or 30 minutes when the temperature is below 60°F, prior to installation. Inspect and remove any damaged membrane.
B. Membrane must run perpendicular to the direction of steel
deck flutes and orientation of wood decks where possible. C. All membrane overlaps shall be installed to facilitate the flow of
water. Seams shall be shingled or run parallel to the flow of water. Backwater seams are not permitted.
D. Lap sheets a minimum of 5-1/2 inches for In-Lap Fastening, leaving
space for a continuous, minimum 2” weld beyond the outside edge of the fasteners and discs. Membrane overlaps shall be shingled
MULE-HIDE PRODUCTS CO., INC Page 25 05-1111
System Specifications MECHANICALLY ATTACHED TPO Revision Date: September 2018
with the flow of water or parallel to the flow of water. End laps shall be overlapped a minimum of 3 inches.
E. The roofing contractor shall check all welded seams for continuity
and integrity using a cotter pin puller or other suitable blunt object. The contractor shall make sample test seams each day prior to welding field seams. The contractor shall, using scrap material, run at least two test seams, each a minimum of 2' long. Each test seam shall be used to determine adequate seam strength and to ensure the equipment has warmed up, is operating properly and proper settings have been determined. This should be done each time the equipment is turned on after a cool down period.
3.08 Sheet Attachment
A. Perimeter Enhancements
1. When installing the Mechanically Attached Mule-Hide TPO Roofing system, fastening enhancements must be installed at the perimeters and completed with Mule-Hide approved fastening systems at the predetermined spacing. The Perimeter Enhancements are dependent on building height, wind zone location, and warranty duration. See Technical Bulletin TPO-MA02-2006 for required enhancements.
Perimeter areas shall be determined by one of the following
methods:
a. Mule-Hide Technical Bulletin TPO-MA-02-2006
b. For Factory Mutual insured buildings, follow guidelines in FM's Loss Prevention Data Sheet 1-29. Perimeter area for all exterior roof edges/parapet walls is calculated by taking 40% of the roof height or 10% of the lesser plan dimension, whichever is less. The calculated distance is the area into the field of the roof, from the exterior edge/wall, which shall be included in the enhanced fastening area, rounding off to the next full enhancement dimension as needed. Contact Mule-Hide Warranty Department for fastener spacing for compliance with FM 1-60 and 1-90 requirements.
c. Parapet walls of a height of 8 feet or greater do not
require Perimeter Enhancements.
MULE-HIDE PRODUCTS CO., INC Page 26 05-1111
System Specifications MECHANICALLY ATTACHED TPO Revision Date: September 2018
d. Parapets, walls and expansion joints separating
adjoining roofs of the same elevation or roofs that are at a higher elevation than the roof being installed are considered interior walls and do not require Perimeter Enhancements. Sheet Mule-Hide Details # MHT-UN-108A and MHT-UN-108B
e. Roof edges and parapet walls separating other roofs
areas that are at a lower elevation than the roof being installed are considered exterior edges/parapets when the difference in elevation is three feet or more and shall require the installation of Perimeter Enhancements. Sheet Mule-Hide Details # MHT-UN-108A and MHT-UN-108B
f. For roofs of heights of 70 feet or greater and located
in wind zones higher than 80 mph or for projects requesting enhanced wind speed warranties, Mule-Hide requires that FM guidelines be followed when determining the extent of the perimeter enhancements.
2. Methods for Perimeter Enhancements
Perimeter Enhancements can be formed by using individual 4’ or 6’ wide sheets, by subdividing 8’, 10’, or 12’ wide field sheets using 10” wide Pressure-Sensitive RUSS strip, or by installing rows of seam fastening plates through the top of the membrane and patching with appropriate materials. a. Individual Perimeter Sheets Method
1. Position membrane along the perimeter of the
roof over the acceptable insulation/underlayment. a. 4’ perimeter sheets are used with 8’ field
sheets
b. 6’ perimeter sheets are used with 10’ and 12’ field shets
2. Over steel roof decks
a. All seams must run perpendicular to the
ribs of the deck. This requirement will
MULE-HIDE PRODUCTS CO., INC Page 27 05-1111
System Specifications MECHANICALLY ATTACHED TPO Revision Date: September 2018
necessitate that perimeter sheets on two sides of the roof (where the seams would be running parallel with the flutes of the deck) be turned so that the seams in the perimeter sheets run perpendicular to the deck flutes. See Detail MHT-FM-308B.
b. In lieu of changing the orientation of the
perimeter half sheets where the seams would normally run parallel to the deck flutes, the contractor can elect to install fastener row “fingers” as depicted in Detail MHT-FM-308A.
b. 10” RUSS Method
1. When field sheets are positioned parallel to
a roof perimeter, 10" wide Sure-Weld Pressure-Sensitive RUSS (with 3” wide tape each side) shall be placed approximately down the center of the 8‘, 10', or 12' wide TPO field membrane sheets. When a 10” RUSS divides a field sheet in half, two perimeter sheets are created.
2. Unroll and position the 10" wide TPO Pressure-
Sensitive RUSS over the insulation substrate where membrane securement is desired. Locate the RUSS with the fastener markings and tape facing upwards.
3. Position Mule-Hide Seam Plates at the same
spacing as the field sheets and secure with an appropriate fastener. Do not fasten plates over top of the release liner as this will cause the liner to tear when removed.
4. Remove any dirt or dust resulting from plate
installation. Any residual dust/dirt will be detrimental to the bond strength of the tape adhesive.
5. Position the TPO membrane and thoroughly
clean the underside of the TPO membrane using Weathered Membrane Cleaner if
MULE-HIDE PRODUCTS CO., INC Page 28 05-1111
System Specifications MECHANICALLY ATTACHED TPO Revision Date: September 2018
necessary. (The entire membrane surface where the tape is to contact must be clean. The adhesive on the TPO Pressure Sensitive RUSS will not adhere to dusted / dirty surfaces).
6. Using a Scotch Brite© Pad, apply TPO Primer
to the underside of the TPO membrane in a circular motion in the area that will come in contact with the two strips of 3” wide tape. The properly primed area will be uniform in color without streaks and free from globs or puddles.
7. Remove the release liner from the tape on the
TPO Pressure-Sensitive RUSS pulling it parallel to the roof deck.
8. Once the TPO Primer has dried to the touch
but is still tacky, roll the deck membrane onto the exposed tape and apply hand pressure to the seam area.
9. Roll the entire 10" width of the TPO Pressure-
Sensitive RUSS seam area with a 2" wide roller using positive pressure.
10. To achieve proper adhesion of the TPO
Pressure-Sensitive RUSS when job site temperatures fall below 40°F (5°C), heat the cleaned / primed area of the TPO membrane with a hot air gun as it is applied and pressed into the tape.
11. Over steel roof decks
a. When field membrane sheets extend perpendicular to the edge of the roof, position the 10" RUSS beneath the membrane along the center of each field sheet extending a distance equal to 0.4 times the building height to create perimeter enhancements.
CAUTION: 6" wide RUSS is only available with 3” wide tape on one side and therefore cannot be used to form perimeter sheets.
MULE-HIDE PRODUCTS CO., INC Page 29 05-1111
System Specifications MECHANICALLY ATTACHED TPO Revision Date: September 2018
c. Fastening Plates Method
1. In lieu of the RUSS securement method prior
to the installation of the field membrane, position a row of seam fastening plates down the center of the 8’, 10’, or 12’ wide field sheets after it has been placed in position. Secure plates with appropriate fastener and overlay plates with 6” wide Pressure-Sensitive TPO Cover Strip or 6” Reinforced TPO Cover Strip hot air welded to the field membrane.
2. On projects requesting warranties of 20 years
or more, the plates and fasteners must be overlaid with 6” Reinforced TPO Cover Strip and hot air welded to the field membrane. Cut Edge Sealant must be applied to all cut edges of the Reinforced TPO Cover Strip.
3. Over steel roof decks
a. When field membrane sheets extend
perpendicular to the edge of the roof, position the plates and fasteners on top of the membrane along the center of each field sheet extending a distance equal to 0.4 times the building height to create perimeter enhancements.
d. Building with Special Conditions:
Air pressurized buildings, canopies and buildings with large openings where the total wall openings exceed 10% of the total wall area on which the openings are located (such as airport hangars, warehouses and large maintenance facilities) will typically require additional perimeter enhancement. 1. Buildings with large
openings (Figure 1) - When any wall contains major openings with a combined area which exceeds 10% of the total wall area on which the
Figure 1
MULE-HIDE PRODUCTS CO., INC Page 30 05-1111
System Specifications MECHANICALLY ATTACHED TPO Revision Date: September 2018
openings are located, a minimum of four (4) perimeter sheets (centered over the opening) must be specified as shown. As an option to the above perimeter securement, an adhered membrane section may be used in lieu of the mechanically fastened membrane at large openings in accordance with the Mule-Hide Fully Adhered TPO Roof System Specification. NOTE: Depth of perimeter area shall not be less than 2.5 times the width of the opening. See Detail MHT-MA-103A.
2. Buildings with overhangs (Figure 2) – The membrane must be specified with perimeter sheets installed over the entire overhang area extending onto the main roof deck when at the same level. As an option, an adhered membrane section may be used in lieu of the mechanically fastened membrane at building overhangs in accordance with the Mule-Hide Fully Adhered TPO Roof System Specification. See Detail MHT-MA-103B.
B. Field Areas
a. Membrane should run perpendicular to the
direction of steel deck flutes and orientation of wood decks where possible.
b. All membrane overlaps shall be installed to facilitate
the flow of water. Seams shall be shingled or run parallel to the flow of water. Backwater seams are not permitted.
c. All membrane sheets are to be overlapped a
minimum of 5-1/2" to provide space for fastener and disc placement and for a continuous, minimum 2" wide weld.
Figure 2
MULE-HIDE PRODUCTS CO., INC Page 31 05-1111
System Specifications MECHANICALLY ATTACHED TPO Revision Date: September 2018
d. Do not run any seams through field drains or sumps.
Any seams running through drains shall be cut out and target patches (36” x 36”) shall be installed.
3.09 Welding of Lap Areas
A. General
1. Roofing membrane is to be hot air welded only. Seaming of "membrane to membrane" and "flashing/detail membrane to membrane" shall be by hot air welding only.
2. All surfaces to be welded shall be clean and dry.
B. Hot Air Welding
1. Machines for hot air welding are available from several
different sources. Each manufacturer's instructions for use shall be followed, as well as all local codes regarding electric grounding, supply and other related functions. Since most automatic welding machines require 218 to 230 volts, the use of a portable generator on the roof is recommended for greater flexibility. Mule-Hide requires the use of automatic welding machines for all field sheet seaming. Hand welding is only acceptable for flashings and those seams where the automatic welder cannot be used.
2. Hand-held welding equipment is also available to weld
membrane. After the preheated nozzle tip is applied in the overlap area and the material starts to soften, immediately follow with a silicone hand roller to press the heated membrane surfaces together with slow, even movements. Keep the roller within 1 inch of the nozzle tip. Angle the hot air tool so that the flowing air faces the roller. Seam strength may be tested when cool. For best results, testing seams 8 hours after hot air welding is recommended.
C. “T” Joint Covers
1. For 45-mil membrane and maximum warranty length of
15-years. Pay special attention to the “T” lap seams formed where the second perpendicular half-sheet overlaps the butt ends of the field sheets. To ensure proper seaming of the “T” joints the top layer of the Heat-Weld Membrane is creased a minimum of one inch into the lower layer of membrane by using a heat gun with a narrow or pencil tip
MULE-HIDE PRODUCTS CO., INC Page 32 05-1111
System Specifications MECHANICALLY ATTACHED TPO Revision Date: September 2018
nozzle and a rubber hand roller. By inserting a heat gun nozzle between the layers of the membrane, the membrane will soften and begin to flow allowing it to crease and seal completely after applying pressure with a hand roller to ensure adequate bonding of the softened material. After heat-sealing the “T” joint, Edge Sealant must be applied on all cut edges of reinforced membrane. See detail MHT-UN-105A
2. For membrane thickness greater than 45-mil or warranty
length greater than 15-years. Separate “T” joint patches are required over all “T” joints. See detail MHT-UN-105B
D. Seam Patches at Roof/Wall Transitions
1. Mule-Hide requires the installation of Non-Reinforced TPO Flashing Membrane patches over any seam that transitions from the horizontal to the vertical. These patches are to be constructed with Non-Reinforced TPO Flashing Membrane only and hot air welded. Refer to Mule-Hide Detail MHT-UN-105C.
E. Daily Welding Equipment Setup
1. The roofing contractor shall make sample test seams each
day prior to welding field seams. The contractor shall, using scrap material, run at least two test seams, each a minimum of 2 feet long. Each test seam shall be used to determine adequate seam strength and to ensure the equipment has warmed up, is operating properly and proper settings have been determined. This should be done each time the equipment is turned on after a cool down period.
F. Quality Control of Seams
1. After seaming, the seams are checked for integrity with a
probe. Any openings or "fishmouths" are to be repaired with a hand-held hot air tool fitted with a narrow nozzle tip and with a roller. Each day the contractor shall attempt to pull apart several sections of welded seams to test the quality of the welds. Should the welds be deficient, a more thorough examination of the work performed must be carried out and necessary repairs made.
MULE-HIDE PRODUCTS CO., INC Page 33 05-1111
System Specifications MECHANICALLY ATTACHED TPO Revision Date: September 2018
3.10 Additional Membrane Securement (Base Attachment)
A. Additional securement of the TPO membrane by mechanical attachment must be provided at the perimeter of each roof level, base of walls, curbs, skylights, expansion joints, tie-ins, interior walls, bottom of valleys and any angle changes that exceed inclines of 2:12 (2” rise in 12”) and various penetrations as shown in the Mule-Hide Standard Details. All securement must be either horizontally to the roof deck or vertically to the base of the various penetrations as shown in the Mule-Hide Standard Details.
B. The mechanical attachment of the membrane may be achieved by
the following methods:
1. 2.4” Seam Plate and appropriate fasteners a. The 2.4” Seam Plate and appropriate fasteners are
placed with the edge of the Seam Plate approximately ½” away from the angle change. Seam Plates may be placed either horizontally or vertically depending on the conditions encountered. Refer to the Mule-Hide TPO Standard Details for proper placement.
2. Mule-Hide All Purpose Bar
a. The Mule-Hide All Purpose Bar is a specially extruded
aluminum bar that has pre-punched holes 6 inches on center. Bar may be placed either horizontally or vertically depending on the detail followed. Refer to the Mule-Hide TPO Standard Details for the proper placement. Refer to Mule-Hide Detail # MHT-UN-330 for appropriate placement of the All Purpose Bar.
b. The maximum spacing of the fasteners shall not
exceed 12 inches on center. Adjoining bars should be spaced approximately ½ inch to 1 inch apart. All bars must be attached at the ends a maximum of 1 inch from the end of each bar. This may require pre-drilling additional holes. All cut bars shall be deburred.
c. Under no circumstances shall the All Purpose Bar be
stripped-in with TPO PS Cover Strip. TPO .045 Reinforced 6” X 100’ product may be used to strip-in the All Purpose Bar with a continuous, minimum of 1-1/2” (40 mm) wide weld.
MULE-HIDE PRODUCTS CO., INC Page 34 05-1111
System Specifications MECHANICALLY ATTACHED TPO Revision Date: September 2018
d. The All Purpose Bar must be installed a minimum of 3
inches to a maximum of 6 inches from inside and outside corners.
3. TPO PS RUSS attachment strip
a. The RUSS is a 6" wide reinforced strip of TPO
membrane that may be installed at the base of walls and curbs. Mule-Hide 2.4 inch Seam Plates are used to attach the RUSS horizontally with appropriate fasteners. Refer to Mule-Hide Detail # MHT-UN-305B for appropriate placement of the RUSS, plates and fasteners. The RUSS attachment strip is installed prior to the placement of the field sheet. The RUSS attachment strip is to be placed on horizontal surfaces only and not turned up the vertical.
b. Follow the standard procedures for cleaning, applying
primer and adhering the RUSS and field sheet. Only Mule-Hide TPO Primer or Low VOC Primer may be used to adhere the RUSS to the field sheet. Bonding Adhesive is not permitted for use with the RUSS attachment strips.
c. Spacing of the fasteners shall match the field sheet
spacing and shall not exceed 12 inches on center. Adjoining RUSS attachment strips shall be spaced a maximum of 1 inch apart. It is not required to overlap the RUSS.
d. For horizontal attachment, the RUSS attachment strip
must be placed a maximum of ½ inch from the base of the angle change extending out onto the horizontal surface (roof substrate). The 2.4 inch Seam Plate must be placed a minimum of ½ inch to a maximum of 1 inch from the exterior edge of the strip. Refer to Mule-Hide Detail # MHT-UN-305B. Installation of the plates must be a minimum of 6 inches to a maximum of 9 inches from the inside and outside corners.
4. Drip Apron and Gravel Stop
a. For drip aprons and gravel stops, the metal flange
shall extend a minimum of 3 inches onto the wood nailer. The wood nailer must be wider than the metal
MULE-HIDE PRODUCTS CO., INC Page 35 05-1111
System Specifications MECHANICALLY ATTACHED TPO Revision Date: September 2018
flange. Approved screw fasteners shall be installed a maximum of 6 inches on center and ½" to 3/4" from the inside edge of the metal flange. Ring shank nails spaced a maximum of 4" on center may also be used.
b. Drip aprons and gravel stops not made out of TPO
Coated Metal shall be primed with Mule-Hide’s TPO Primer or Low Voc Primer and stripped with Mule-Hide’s TPO PS Cover Strip. Cleaning the metal with a solvent such as toluene or xylene to remove oil film may be required prior to installing and priming with the TPO Primer. Refer to Mule-Hide detail # MHT-UN-106B.
3.11 Flashing Installation
A. TPO Membrane Flashings
1. All membrane flashings are to be installed concurrently with the roof membrane as the project progresses. Temporary flashings are not allowed without prior written approval from the Mule-Hide Warranty Department. Should any water penetrate the new roofing because of incomplete flashings, the affected areas shall be removed and replaced at the contractor's expense.
2. All surfaces to be fully adhered should be compatible, dry
and smooth with no excessive surface roughness.
3. On recover projects, tear off all existing base flashings, cant strips and projection flashings down to the substrate. If deteriorated substrate is uncovered, repairs must be made to provide a suitable substrate for the new TPO flashings.
B. TPO Bonding Adhesive, Low VOC Bonding Adhesive, and Low
VOC Bonding Adhesive - 1168 (solvent base)
1. Mix adhesive scraping the sides and bottom of the can (minimum 5 minutes is required) until adhesive is uniform in color. Consult product data sheet for adhesive instructions. a. Low VOC Bonding Adhesive and Low VOC Bonding
Adhesive – 1168 require mechanical stirring (electric drill), both initially and periodically during application.
b. Porous surfaces and substrates may require the application of a prime coat and second coat of Low
MULE-HIDE PRODUCTS CO., INC Page 36 05-1111
System Specifications MECHANICALLY ATTACHED TPO Revision Date: September 2018
VOC Bonding Adhesive and Low VOC Bonding Adhesive – 1168 to accomplish proper adhesion.
2. Using a plastic core, medium nap roller, apply a smooth even coat of TPO Bonding Adhesive to back side of membrane and substrate (no globs or puddles). A nine inch roller will easily fit into a 5-gallon adhesive container. Do not apply adhesive in area of seam laps.
3. Coverage rate to be approximately: 120 square feet per gallon for one surface (membrane or
substrate only) or 60 square feet per gallon per finished surface (membrane
and substrate)
4. Allow adhesive to dry to a ‘tacky’ state. Test adhesive by placing a knuckle into it and turning your wrist a one-quarter turn. Adhesive is ready to mate when it is tacky but does not string when knuckle is lifted.
5. Care must be taken to ensure proper drying. Avoid thin layers of adhesive which can result in over drying and improper adhesion.
6. Roll coated membrane onto substrate being careful to not
wrinkle the sheet or trap air bubbles. Once membrane is mated to the substrate, carefully roll the membrane with a 2-inch wide rubber hand roller to promote maximum positive contact between the membrane and the substrate.
7. TPO Membrane Flashings shall extend a minimum of 6
inches onto the field sheet and be adhered securely. There shall be a minimum of 2 inches between the front of the fastener plates and the edge of the sheet to allow for heat welding. All side laps are to overlap a minimum of 2 inches.
8. Areas of the flashings and membrane to be welded are
not to have TPO Bonding Adhesive applied to them. 9. Extended drying times can be expected during cool,
overcast, humid, shaded, or late day applications. The adhesive must be dry (but still tacky) before mating surfaces to avoid permanent blisters due to trapped solvents.
10. All flashings shall be extended a minimum of 8 inches above
roof membrane level and be terminated unless previously
MULE-HIDE PRODUCTS CO., INC Page 37 05-1111
System Specifications MECHANICALLY ATTACHED TPO Revision Date: September 2018
accepted by the owner or his representative and the Mule-Hide Technical Department. All flashings shall be hot air welded at their connections with the roofing membrane. Apply Cut Edge Sealant at all welded edges of cut membrane flashings. Refer to Mule-Hide TPO Standard Details for more information.
NOTE: After flashing is adhered in place, promote full
contact adhesion by going back over entire area with a 2-inch rubber hand roller.
C. Aqua Base 120 Bonding Adhesive
1. Mix adhesive scraping the sides and bottom of the can
(minimum 5 minutes is required) until adhesive is uniform in color. Consult product data sheet for adhesive instructions.
2. Using a 9” wide, ¼” or 3/8” nap roller, apply a smooth even
coat of Aqua Base 120 adhesive to back side of membrane and substrate (no globs or puddles). A nine inch roller will easily fit into a 5-gallon adhesive container. Do not apply adhesive in area of seam laps.
3. Coverage rate to be approximately: 120 square feet per gallon for one surface (membrane or
substrate only) or 60 square feet per gallon per finished surface (membrane
and substrate) 4. Allow adhesive to dry until it turns yellow and does not
transfer to a dry finger or pull away from the substrate. Aqua Base 120 adhesive will take a longer time to dry. Adhesive must remain tacky.
5. Mate surfaces together avoiding wrinkles. Immediately roll
the bonded area of the sheet with a 2-inch wide rubber hand roller to promote maximum positive contact between the membrane and the substrate. Overlap all adjacent flashing sheets a minimum of 2 inches.
6. Do not apply adhesive in area to be heat-welded. 7. Extended drying times can be expected during cool,
overcast, humid, shaded, or late day applications. The adhesive must be dry (but still tacky) before mating surfaces to avoid permanent blisters due to trapped moisture.
MULE-HIDE PRODUCTS CO., INC Page 38 05-1111
System Specifications MECHANICALLY ATTACHED TPO Revision Date: September 2018
8. TPO Membrane Flashings shall extend a minimum of 6
inches onto the field sheet and be adhered securely. There shall be a minimum of 2 inches between the front of the fastener plates and the edge of the sheet to allow for heat welding. All side laps are to overlap a minimum of 2 inches.
9. All flashings shall be extended a minimum of 8 inches above
roof membrane level and be terminated unless previously accepted by the owner or his representative and the Mule-Hide Technical Department. All flashings shall be hot air welded at their connections with the roofing membrane. Apply Cut Edge Sealant at all welded edges of cut membrane flashings. Refer to Mule-Hide TPO Standard Details for more information.
NOTE: After flashing is adhered in place, promote full
contact adhesion by going back over entire area with a 2-inch rubber hand roller.
10. All flashings shall be hot air welded at their connections with
the roofing membrane. All hand welds shall be a minimum of 1-1/2" wide.
11. All flashings shall be properly terminated according to Mule-
Hide's published Standard Details.
NOTE: When using Mule-Hide All-Purpose Bar under Counterflashing to terminate wall flashing or when coping is used, TPO Bonding Adhesive, Low VOC Bonding Adhesive, Low VOC Bonding Adhesive – 1168, or Aqua Base 120 Bonding Adhesive may be eliminated when flashing height is 12” - 18” or less, depending on the type of termination. Refer to Mule-Hide’s published Standard TPO Details for additional information.
3.12 Drains, Expansion Joints, Pitch Pans
A. Roof Drains
1. Prepare the surface around each drain to prevent any distortion, tenting, or bridging of the membrane. A smooth transition shall be provided from the roof surface to the surface of the drain bowl/clamping ring.
2. All existing roofing materials and metal flashings shall be
removed.
MULE-HIDE PRODUCTS CO., INC Page 39 05-1111
System Specifications MECHANICALLY ATTACHED TPO Revision Date: September 2018
3. Mule-Hide requires the application of one full tube of Water
Cut-Off Mastic per drain applied to the drain bowl, under the membrane, where the clamping ring will be seated. This will provide a continuous seal between the membrane and the drain bowl.
4. Do not run field seams through drains or sumps. If sheet
layout causes a seam to fall in line with a drain, a target patch (minimum 36” x 36”) shall be required.
B. Expansion Joints
1. Refer to Mule-Hide’s published Standard TPO Details for application methods for flashing expansion joints.
C. Pitch Pans
1. Install and flash pitch pans as indicated in Mule-Hide’s
published Standard TPO Details. All pitch pans shall be filled with Thermoplastic Pourable Sealant.
3.13 Walkway Installation Walkways should be provided in areas where routine rooftop maintenance occurs and in areas where regular rooftop traffic is expected. A. TPO Walkway Roll Installation
1. Install TPO Walkway Rolls over clean, dry surfaces.
2. Layout areas where TPO Walkway Rolls are to be installed
with most of the material being oriented so that it is placed between field seams with each adjacent and abutting section gapped a minimum of 6". Do not install walkway pads over seams.
3. Heat weld the perimeter of the properly positioned TPO
Walkway Roll. Check seams for any voids or inconsistencies that might prevent watertightness.
B. Precast Pavers
1. Install precast paver systems acceptable to Mule-Hide over one layer of 6 oz. HP Protection Mat. Contact Mule-Hide for other acceptable slipsheets.
MULE-HIDE PRODUCTS CO., INC Page 40 05-1111
System Specifications MECHANICALLY ATTACHED TPO Revision Date: September 2018
3.14 Temporary Tie-ins
A. Install temporary cutoffs around incomplete edges of roofing assembly at the end of each day's work and when work must be postponed due to inclement weather. Straighten the insulation line using pieces of insulation loosely laid, and seal the Mule-Hide TPO membrane to the deck or existing membrane. Use a heavy application of roof cement at least six inches in width overlaid with an embedded reinforcement on gravel surfaced roofs. Use polyurethane sealant, low rise foam adhesive, or pourable sealer to seal onto single plies, smooth BUR, or modified bitumen roofs. Remove the temporary seals completely when work resumes, cutting out the contaminated membrane. Remove all sealant, contaminated membrane, insulation fillers, etc. from the work area and properly dispose off-site.
End of Section
This specification represents the applicable information available at the time of its publication. Mule-Hide reserves the right to change this information at any time. Contact Mule-Hide or check the Mule-Hide website (www.mulehide.com) for the latest updates regarding changes or modifications to this specification.
Mule-Hide Products Co., Inc. Page 41 01-1226
SPECIFICATION SUPPLEMENT AeroWeb Adhesive
Revision Date: September 2018 This Specification Supplement is to be used as an additional adhesive option for Mule-Hide’s TPO, Fleece Back TPO, EPDM and Fleece Back PVC specifications. Part 1 General 1.01 Description Mule-Hide’s AeroWeb can be used to adhere Fleece Back TPO and PVC, standard TPO, and standard or White-on-Black EPDM membrane to vertical substrates. AeroWeb can also be used to install standard TPO, standard EPDM, and White-on-Black EPDM to horizontal surfaces. AeroWeb is not approved to adhere Fleece Back TPO FR membrane. Additionally AeroWeb can be used as a primer to enhance the bond between Mule-Hide’s F5 and various substrates, and priming unexposed asphalt prior to applying Helix Adhesive for insulation attachment. 1.04 Product Delivery, Storage, and Handling A. Deliver materials to the job site in original, unopened containers, with the
manufacturer's name, brand name and installation instructions. B. Store all materials in a dry, clean area protected from the elements, as per
manufacturer's recommendations. C. Store cylinders in protected, conditioned space with temperature maintained
above 70°F. Do not store cylinders in areas where temperatures reach 110°F or higher. Contents are flammable.
D. Store in accordance with local, state, and federal regulations. E. Keep cylinder valve open to maintain pressure in the hose and spray gun.
Periodically spray in a safe manner to help prevent possible clogging. Keep spray gun trigger locked when not in use. Flush gun and hose with UN-TACK for long-term storage beyond 30 days.
Part 3 Execution 3.03 Substrate Preparation A. Acceptable vertical substrates include: Mule-Hide Poly ISO roof insulation,
Poly ISO 1-HD, DensDeck® Prime, SECUROCK®, OSB, plywood, metal, residual asphalt, and clean concrete block. To improve adhesion and reduce the potential for asphalt bleed-through on vertical surfaces with residual asphalt, apply an initial “sealing” base coat of AeroWeb and allow to flash off properly; then, apply a secondary coating of AeroWeb to the vertical surface.
B. Acceptable horizontal substrates include: Acceptable substrates include: Mule-Hide Poly ISO roof insulation, Poly ISO 1-HD, DensDeck Prime, SECUROCK, OSB, and plywood.
Mule-Hide Products Co., Inc. Page 42 01-1226
Specification Supplement AeroWeb Adhesive
C. The surface, on or against which AeroWeb is to be applied, shall be clean, smooth, dry, free of films, sharp edges, loose and foreign materials, oil and grease. Depressions greater than ¼" (6 mm) should be feathered, using epoxy, mortar or other approved patching material. All sharp projections shall be removed by sweeping, blowing or vacuum cleaning.
D. All air intake ventilation equipment must be shut off and all ductwork openings and gaps in the deck/ substrate should be temporarily sealed during product application.
3.04 Installation A. General use instructions
1. Refer to the applicable Product Data Sheets and Safety Data Sheets for cautions and warnings.
2. Connect spray gun to hose and connect hose to cylinder. Use lithium grease or petroleum jelly on all fittings and be careful to avoid cross- threading. Open valve on cylinder to check fittings for leaks. Keep cylinder valve open to maintain pressure in the hose/spray gun when not in use.
3. AeroWeb can be applied at ambient temperature of 25°F and above. Propellant in cylinders must be kept above 70°F for the product to spray properly. Utilize heated drum bands, power- heated blanket, and hot boxes when necessary. Substrate shall be clean, dry, and free of debris and contaminants.
4. For applications taking place in ambient temperature below 70°F, store cylinders in heated space and move to project area during application. Cylinders must be kept warm on the jobsite. Dispense product from cylinder while it is still warm. When product in cylinder becomes too cold, it will begin to spit rather than spray. If this occurs, swap cold cylinder for warmer one and return cold cylinder to heated area. When changing cylinder, close the valve on the cylinder and depressurize the hose. Remove the hose and attach to the new cylinder. Open valve and do a test spray.
5. Apply AeroWeb in an even coat to substrate (refer to the drawing on the next page), keeping the spray tip approximately 12" (30.5 cm) away and perpendicular to the surface during spray. Avoid high thickness buildup.
C. AeroWeb Application rates (*approximate coverages): 1. 1-Sided Primer – 2,000-2,500 ft2* when used with Mule-Hide F5 Air and
Vapor Barrier or as a primer for Helix® 2. 2-Sided Adhesive - Walls – 1,000 ft2* 3. 2-Sided Adhesive - Field – 1,000 ft2*
B. Vertical application using AeroWeb Approved membranes are: Fleece Back TPO and PVC, standard TPO, and
standard or White-on-Black EPDM (There are no height restrictions when using AeroWeb for vertical applications if the appropriate membrane terminations are utilized.)
Mule-Hide Products Co., Inc. Page 43 01-1226
Specification Supplement AeroWeb Adhesive
1. Spray wall and back of the membrane, utilizing a 50% overlapping spray pattern.
2. Do not apply adhesive to splice areas. 3. Allow adhesive to become tacky but not overly dry; it should not transfer
to fingers when touched. 4. Mate membrane with the wall from the center of the sheet towards the
edges, smoothing by hand. 5. Broom the membrane with a soft-bristle broom. 6. Roll in with a hand roller.
C. Horizontal application using AeroWeb Approved membranes are: standard TPO, standard EPDM, and White-on-
Black EPDM 1. Application shall be continuous and uniform, avoiding globs or puddles. 2. Spray substrate and back of the membrane with enough overlap to
ensure 100% coverage (2"-3" of overlap). 3. Do not apply adhesive to splice areas. 4. Allow adhesive to become tacky but not overly dry; it should not transfer
to fingers when touched. 5. Roll the membrane onto the adhesive-coated substrate while avoiding
wrinkles. Immediately brush down the bonded portion of the sheet with a soft-bristle push broom, and then roll the membrane with a clean, dry roller to achieve maximum contact.
This specification supplement represents the applicable information available at time of publication. Mule-Hide reserves the right to change this information at any time. Contact Mule-Hide Products or visit our website at www.mulehide.com for the latest updates, changes, or modifications to this specification supplement.