Page 1: ME 414: Project #1

ME 414: Project #1

Design Team Members: Andy CashKyle BredehoeftAlan KoersBrent Miller

Presentation Date: May 5, 2006

Page 2: ME 414: Project #1

Project Definition

NASA Requests a quote: To design a heating and ventilation system for an

arctic research facility located at the North Pole. Contains four researchers Inside temperature to be maintained at 25 °C Outside temperature is a constant -40 °C No cooling system needed for obvious reasons

Page 3: ME 414: Project #1

Design Constraints

Ducts formed from rubber coated sheet metal: Sheet Size: 70” x 90” Relative roughness: 2mm

Outside Walls 12” thick Inside Walls 8” Register location is fixed

Register Size: 6” x 16” Occupants Require 8 liters of fresh air per

minute

Page 4: ME 414: Project #1

Resistance Network

Page 5: ME 414: Project #1

Room #1 Heat Loss & Cost

Page 6: ME 414: Project #1

Room #1 Mass Flow Rate

Page 7: ME 414: Project #1

Fresh Air Heating

Page 8: ME 414: Project #1

Heat Generation fromBuilding Occupants

Page 9: ME 414: Project #1

Flowmaster Room Model

Return

Register

Junction

Piping

Page 10: ME 414: Project #1

Flowmaster Model

Page 11: ME 414: Project #1

Flowmaster Results

Room Number

Calculated Flow Rate

(m^3/s)

Flowmaster Flow Rate

(m^3/s)

Difference (m^3/s)

1 0.028 0.0077 0.02032 0.029 0.0117 0.01733 0.0185 0.0187 0.00024 0.0219 0.0181 0.00395 0.0244 0.0193 0.0051

Page 12: ME 414: Project #1

Housing Layout

Room 1Room 2

Room 3

Room 4

Room 5

Page 13: ME 414: Project #1

Solid Model Duct RoutingFRESH AIR OUTLET

FRESH AIR INLET

Page 14: ME 414: Project #1

Duct Routing Close-up

Page 15: ME 414: Project #1

Duct Work System

Page 16: ME 414: Project #1

Building Front Section View

Page 17: ME 414: Project #1

Material & Labor Costs

Material Costs

Sheet Width (in.) 70

Sheet Length (in.) 90

   

Total material area needed (in2) 169,748

Total Number of Sheets 27

Cost per Sheet $250.00

Material Cost $6,736.03

   

   

Labor Costs

Shearing Cost $1,347.21

Bend Forming $4,300.00

Branch Forming $1,000.00

Register Hookups $400.00

   

Total Material and Labor Cost: $13,783.24

Page 18: ME 414: Project #1

800 CFM Fan Curve

Page 19: ME 414: Project #1

800 CFM Fan Results

Page 20: ME 414: Project #1

Fresh Air Inlet Results

Page 21: ME 414: Project #1

800 CFM Pressure Distribution

Page 22: ME 414: Project #1

800 CFM Pressure Distribution

Page 23: ME 414: Project #1

800 CFM Velocity Distribution

Room Air Velocity Below Comfort Threshold of 0.15 m/s

Page 24: ME 414: Project #1

800 CFM Flow Trajectory

Page 25: ME 414: Project #1

800 CFM Flow Trajectory

Page 26: ME 414: Project #1

800 CFM Pressure Dropand Air Changes per Hour

Page 27: ME 414: Project #1

Blower Comparison

Blower Capacity

Volume

Flow m3/s ACHMass Flow kg/s

System Heat Loss Mass Flow Requirement

Maximum Velocity m/s

System dp inches of water

Fresh Air Inlet Mass

Flow m3/s

Fresh Air Outlet Mass

Flow m3/s

Fresh Air Volume Rate

Required m3/s

800 CFM 0.37 2.60 0.45 0.14 6.65 0.33 0.007 -0.007 0.031200 CFM 0.55 3.90 0.66 0.14 11.00 0.83 0.01 -0.01 0.032000 CFM 7.70 55.00 16.60 0.14 372.00 662.00 x.xx x.xx 0.03

Note:•2000 CFM Blower vel_max exceeds 100 m/s •Fresh Air Delivery Insufficient

Page 28: ME 414: Project #1

Blower Operation Cost/Month

Page 29: ME 414: Project #1

Monthly Heating Requirements & Costs

Note:•Total Bldg Q=14,651 BTU/hr •Basement not heated

Room Number Q insulated (Btu/hr) Cost ($/month) Heat Addition of Scientist (Btu/hr) 599121 2853 112.52 Cost savings from heat of scientist ($/month) 23.632 3692 145.61 Fresh Air Heating (Btu/hr) 2557.023 2299 90.68 Cost of fresh air heating ($/month) 100.844 2719 107.225 3088 121.78

Total Cost : 577.81

Operating Costs ($/month): 655.023 Month Cost: 1965.06

Page 30: ME 414: Project #1

Risk Assessment and Contingency

Event of Furnace or Blower Failure

1) Gather at Central Bldg Location

2) Start Generator and Resistance heater

Like

lihood

ImpactHigh Low

Low

Hig

h

Page 31: ME 414: Project #1

Risk Assessment and Contingency

Fresh Air VentilationSystem Frost or Other Blockage

1) Remove Blockage

2) Insure Safe Oxygen Levels

Like

lihood

ImpactHigh Low

Low

Hig

h

Page 32: ME 414: Project #1

Cost Summary

Cost Item Cost

Material and Labor $13,783.24Heating $1,965.06Blower Operation $145.14

$15,893.44 Total

Page 33: ME 414: Project #1

Questions

Special Thanks to: Billy Holland Professor Toksoy