  • 8/12/2019 MD1-0-V-114-01-00004-C

    1/2

    APPROVED Approved without exception

    APPROVED WITH COMMENTS Approved Subject to Incorporation of comments

    RETURNED FOR CORRECTION Insufficient Information/ Detail

    Resubmit for Approval

    REJECTED Complete redesign required

    RECEIVED FOR INFORMATION Returned without comments

    RECEIVED FOR INFORMATION Returned with comments

    any obligations covered under contract

    Engineer:

    Discipline:

    Date:

    Note: Approval or comments does not relieve the Contractor of

    Pyry EnTWO(2) X 500MWMONG DUONG 1 THERMAL POWER PLANT

    avi anghorneSenior Mec Engineer5-Mar-13

  • 8/12/2019 MD1-0-V-114-01-00004-C

    2/2

    Pyry Comment Two(2) x 500MW Mong Duong 1 Thermal Power Plant Project

    Dwg. / Doc. Title Outline Drawing for HP-7Low Pressure FWH Dwg. / Doc. No. MD1-0-V-114-01-00004

    HDEC DT No. MD1-HDH-EVN-X-1036 Submitted Date 2012.11.02 Rev. BPyry TR No. 9A000323-002559 Received Date 2012.11.28New HDEC DT No. MD1-HDH-EVN-X-2233 Re-Submitted Date 2013.02.05 Rev. CStatus Received for Information Returned with Comments

    Page 1 / 1

    No. Pyry s Comments Contractors Reply / Action1 < Pyry s Comments on Rev.A>

    Please refer to general comments on MD1-0-V-114-01-00001.

    < Contractors Reply / Action on Rev.A>Reflected.

    < Contractors Reply / Action on Rev.B>Closed.

    2 < Pyry s Comments on Rev.A>

    Review the steam inlet nozzle material. Theskirt design temperature is 490 deg C.

    Closed.

    < Contractors Reply / Action on Rev.A>

    Reflected.Steam inlet material has been revised from

    A106-B to A335-P11.

    3 < Pyry s Comments on Rev.A>Clause 6.4.3 of the ERQ states that the HPHeaters shall be designed to withstand the boilerfeed water pump shut-off pressure. Pleaseconfirm this requirement is met in the heatercalculations.

    Closed.

    < Contractors Reply / Action on Rev.A>Boiler Feedwater Pump shut-off pressure is 300barg. BFP shut-off pressure has been reflectedas tube side design pressure of 300 barg.

    4 < Pyry s Comments on Rev.A> At the key plan, please correct location of HP-7FWH from Mezzanine floor to Operating floor.

    Noted the drawing is for Heater No. 7 .

    Closed.

    < Contractors Reply / Action on Rev.A>HP-6 FWH is on the HP heater floor. Pleasecheck the modified key plan.

    < Contractors Reply / Action on Rev.B>Reflected.

    5 < Pyry s Comments on Rev.A>Correct the nozzle bevel data table. It appearsto be a cut and paste from MD1-0-V-114-01-00001.

    Closed.

    < Contractors Reply / Action on Rev.A>Reflected.