mcs-touchscreens . mcs-touch-7 front back new for 2015 high resolution (1280 x 800) lcd display...
TRANSCRIPT
MCS-TOUCHSCREENSwww.mcscontrols.com
MCS-TOUCH-7MCS-TOUCH-7FRONT
BACK
NEW FOR 2015
High Resolution (1280 x 800)
LCD Display with LED Backlighting
MCS-TOUCH-15.4MCS-TOUCH-15.4FRONT
BACK
ON-SCREEN KEYPAD
MCS-CONNECT and MCS-GRAPHICS providesboth graphics and service mode
The MCS-TOUCH-7 and TOUCH-15.4 are new touchscreen interfaces designed to simplify user access with the MCS-Magnum and MCS-MicroMag utilizing MCS-Connect to provide both graphics and service mode access to technicians.
Information and graphics on the MCS-TOUCH-7 and MCS-TOUCH-15.4 are shown on a high resolution (1280x800) LCD display with LED backlighting, which will guarantee long-life operation.
The MCS-TOUCH-7 and 15.4 are suitable for installation for both indoor and outdoor applications. Utilizing a gasket for an environment seal provides the unit with a NEMA 4 rating.
MCS-TOUCHSCREEN
MOTHERBOARD - FRONT
MICRO
SD Slot
1 USB Port
On-the-Go
2 - USB
Ports 2.0Ethernet
Port
3 - RS 485
Communication Ports
+12 V DC
Power Input
1 GB DDR3
Memory
RTC
Battery
5 wire connection15.4 Touchscreen
Serial
Console
PortMCS-TOUCHSCREEN
MOTHERBOARD - BACK
4 GB EMMCFlash Memory
7in LCD connector
mPCIeExpansion slot
15.4IN LCD Connector
800 MHZ i.MX6 ARM Micro
4 wire connection7in Touchscreen
INCLUDED COMPONENTSINCLUDED COMPONENTS
12 VDC - 50W Single Output Power Supply for Touchscreen Resistant to short circuiting, overloading and over voltageOperating temperature up to 700C
Ethernet Crossover Cable5ft CAT 5e Crossover Patch CordOrange
DESKTOP WITH COMPANY DESKTOP WITH COMPANY GRAPHICGRAPHIC
SETTING UP THE NETWORKSETTING UP THE NETWORK
Click the key shown and the network manager will appear as shown in this screen shot
Click Options to set Static & Dynamic IP address
Editing Wired Connection – Editing Wired Connection – Static AddressStatic Address
Click IP4 Settings
to change Network Settings
Static IP, Netmask & Static IP, Netmask & Gateway AddressGateway Address
Enter Static IP, Netmask &
Gateway Address
Set to Manual for Static IP or Auto DHCP for Dynamic
Click to save
Click Add to add a Static IP
MCS-CONNECT SCREENMCS-CONNECT SCREEN
Click to display the MCS-CONNECT main screen
Click Setup to move to the MCS-CONNECT
setup screen
MCS-PC CONNECT Setup ScreenMCS-PC CONNECT Setup Screen
Local COM PortChoose 1 to 4
Click to save
COM PORTS:RS485 1 = 1RS485 2 = 2RS485 3 = 3
USB-RS485 = 4
OPENING THE ON-SCREEN OPENING THE ON-SCREEN TOUCH KEYBOARDTOUCH KEYBOARD
Click this key to see on-screen Keyboard
DIRECTORY FOR MCS FOLDERSDIRECTORY FOR MCS FOLDERS
Click this key to see MCS Folders
Autostart boot config file runs in background to start MCS-CONNECT
BOOT CONFIG FILE STARTING BOOT CONFIG FILE STARTING MCS CONNECTMCS CONNECT
File shows MCS-TOUCHSCREEN Boot Config file starting MCS-CONNECT
GETTING TO THE MICRO CONTROL GETTING TO THE MICRO CONTROL WEBSITE SOFTWARE PAGEWEBSITE SOFTWARE PAGE
Click this key to go to the MCS website for software updates
The MCS-TOUCH-7 and 15 makes it easy for the user to manage more complex installation diagrams, without losing the overall view of the installation, as well as ensuring that the pages can be browsed in a fast and straightforward manner.
Photos below and on the next page are actual screen shots using MCS-CONNECT and MCS-GRAPHICS.
MCS GRAPHICSMCS GRAPHICS
The MCS-TOUCH-7 and 15.4 can connect to up to 60 MCS Controllers at once and supports RS485 or Ethernet networking.
MCS-TOUCH – CONNECTION MCS-TOUCH – CONNECTION RS-485 TO ONE MCS-MAGNUMRS-485 TO ONE MCS-MAGNUM
MCS-TOUCH – CONNECTION MCS-TOUCH – CONNECTION ETHERNET TO ONE MCS-MAGNUMETHERNET TO ONE MCS-MAGNUM
MCS-TOUCH – CONNECTION MCS-TOUCH – CONNECTION ETHERNET TO MULTIPLE MCS-MAGNUMSETHERNET TO MULTIPLE MCS-MAGNUMS
For additional information please visit our website www.mcscontrols.com
Or call MCS at 239-694-0089