mci pwp pump panel cat001 - tlp...

6
PWP Series Part Winding Pump Control Panel Motor Controls PWP series starter consists of two across-the-line-starters and a timer. The first starter is used to connect one winding of the motor across the line. The starting current from one winding will be about 50% of the starting current if both windings were connected. The starting torque is correspondingly 50%. The PW series panel comes standard with a flanged circuit breaker or fusible disconnect, in a NEMA 3R UL listed enclosure. NEMA type 3R steel enclosure with powder coating finish Full gasket hinged door with provision for padlocks UL listed and suitable for use as service equipment Heavy duty flange fusible or circuit breaker disconnect switch NEMA rated part winding motor starters Solid state overload relay with selectable trip class that provides phase loss and phase unbalance protection Transition timing relay adjustable 0.05 seconds interval. Factory set at 1.0 seconds Hand-Off-Auto selector switch Start push button switch Door mounted overload reset push button Fuses ordered separately; 3 required The part-winding starter reduces inrush current by using two different sets of windings in the motor. Therefore, part-winding starters can only be used with motors having stator windings divided into two equal parts with the terminals of each part available for external connection. 1-800-735-1097 | Fax: 972-247-8991 | www.motorcontrols.com FEATURES

Upload: dangthuan

Post on 15-Mar-2019

218 views

Category:

Documents


0 download

TRANSCRIPT

PWP Series Part Winding Pump Control Panel

Motor Controls PWP series starter consists of two across-the-line-starters and a timer. The first starter is used to connect one winding of the motor across the line. The starting current from one winding will be about 50% of the starting current if both windings were connected. The starting torque is correspondingly 50%. The PW series panel comes standard with a flanged circuit breaker or fusible disconnect, in a NEMA 3R UL listed enclosure.

• NEMA type 3R steel enclosure with powder coating finish • Full gasket hinged door with provision for padlocks • UL listed and suitable for use as service equipment • Heavy duty flange fusible or circuit breaker disconnect switch • NEMA rated part winding motor starters • Solid state overload relay with selectable trip class that provides phase loss

and phase unbalance protection • Transition timing relay adjustable 0.05 seconds interval. Factory set at 1.0

seconds • Hand-Off-Auto selector switch • Start push button switch • Door mounted overload reset push button • Fuses ordered separately; 3 required

The part-winding starter reduces inrush current by using two different sets of windings in the motor. Therefore, part-winding starters can only be used with motors having stator windings divided into two equal parts with the terminals of each part available for external connection.

1-800-735-1097 | Fax: 972-247-8991 | www.motorcontrols.com

FEATURES

Catalog number explanation

1-800-735-1097 | Fax: 972-247-8991 | www.motorcontrols.com

Circuit Breaker Type- Solid State Overload

PLEASE NOTE: Motor Logic SSOLR are designed to protect 50/60 hertz three-phase AC motors from overload, phase

Fusible Disconnect Type- Solid State Overload

MCI Part Number

Max. HP

Input Volts

NEMA Starter

Max Amps

Fused Disc. Size

OL Range

Enclosure Size H x W x D

Wt. Lbs.

List Price

PWP21FD 10 1 27 30 9-27 34" x 16" x 7" 55 $ 3,090

PWP22FD 25 2 45 60 15-45 34" x 16" x 7" 95 $ 3,560

PWP23FD 50 230 3 90 100 30-90 45" x 16" x 9" 140 $ 4,550

PWP24FD 75 4 135 200 45-135 45" x 16" x 9" 200 $ 6,550

PWP25FD 150 5 270 400 90-270 58" x 24" x 10" 480 $ 17,460

PWP41FD 15 1 27 30 9-27 34" x 16" x 7" 55 $ 3,090

PWP42FD 40 2 45 60 15-45 34" x 16" x 7" 95 $ 3,560

PWP43FD 75 460 3 90 100 30-90 45" x 16" x 9" 140 $ 4,550

PWP44FD 150 4 135 200 45-135 45" x 16" x 9" 200 $ 6,550

PWP45FD 350 5 270 400 90-270 58" x 24" x 10" 480 $ 17,460 Fuses ordered separately

MCI Part Number

Max. HP

Input Volts

NEMA Starter

Max Amps

Circuit Breaker

SizeOL

RangeEnclosure Size

H x W x DWt. Lbs.

List Price

PWP21CB 10 1 27 30 9-27 34" x 16" x 7" 55 $ 3,490

PWP22CB 25 2 45 50 15-45 34" x 16" x 7" 95 $ 3,950

PWP23CB 50 230 3 90 100 30-90 45" x 16" x 9" 140 $ 4,880

PWP24CB 75 4 135 150 45-135 45" x 16" x 9" 200 $ 7,580

PWP25CB 150 5 270 400 90-270 58" x 24" x 10" 480 $ 17,920

PWP41CB 15 1 27 30 9-27 34" x 16" x 7" 55 $ 3,490

PWP42CB 40 2 45 50 15-45 34" x 16" x 7" 95 $ 3,950

PWP43CB 75 460 3 90 100 30-90 45" x 16" x 9" 140 $ 4,880

PWP44CB 150 4 135 150 45-135 45" x 16" x 9" 200 $ 7,580

PWP45CB 350 5 270 400 90-270 58" x 24" x 10" 480 $ 17,920

1-800-735-1097 | Fax: 972-247-8991 | www.motorcontrols.com

Panel Schematics

1-800-735-1097 | Fax: 972-247-8991 | www.motorcontrols.com

Panel Sizes

NEMA Pump Panel

PUMP PANEL ENCLOSURE DIMENSIONS

Height Width Depth Size A (IN.) B (IN.) C (IN.)

1 & 2 34 16 7.00

3 & 4 45 16 9.00 5 58 24 10.00

1-800-735-1097 | Fax: 972-247-8991 | www.motorcontrols.com