    Molded Case Circuit Breakers(MCCB) UL 489Provide branch and feeder circuit protection inindustrial control panels

    UL 489

    Up to 600 amps

    65kA @ 240 VAC interrupting rating

    G-frame size 15 to 100 amps

    F-frame size 100 to 225 amps

    K-frame size 250 to 400 amps

    L-frame size 400 to 600 amps

    UL 98 Rated Disconnect SwitchesHeavy-duty fusible and non-fusible disconnects meeting all therequirements of the UL 98 standard. Can be used as a motordisconnecting means to meet NEC 430.109 and meets NEC430.111 as a motor controller.

    SIRCO series

    Non-fusible rotary disconnect

    switches

    Makes/breaks loads up to

    800 amps

    Front operated

    Visible blade contacts

    Line-side shrouding comes

    standard with switch

    FUSERBLOC series

    Fusible rotary disconnect switches

    Makes/breaks loads up to 200 amps

    Front operated

    Uses Class CC and Class J fuses

    Line side shrouding comes

    standard with switch

    Touch-safe fuse covers standard

    with switch

    Circuit

    Motor feeder shortcircuit and ground

    fault protection

    Motordisconnecting

    means(NEC 430.101-

    430.113)

    Motor branch-circuit short

    circuit protection(NEC 430.51-

    430.58)

    Motor controller(NEC 430.81-

    430.91)

    Motor overloadprotection (NEC430.21-430.44)

    OSHA

    Lockout/tagoutdisconnect

    (NEC 430.81-430.91)

    Circuit Protection SelectionMolded Case

    Circuit Breakers(MCCB) UL 489

    CurrentLimitingFusesUL 248

    RotaryDisconnectSwitches

    UL 98

    Manual MotorStarters(MMS)UL 508

    LoadSwitchesUL 508

    SupplementaryProtectorsUL 1077

    GeneralFusesUL 248

    page 28-4 page 28-73 page 28-30 page 16-26 page 28-53

    Short circuit andground fault protectionfor feeder and branchcircuits

    YES YES YES NO NO NO NO

    Motor disconnectingmeans(NEC 430.101-430.113)

    YES YES YES NO NO

    Motor branch-circuitshort circuit protection(NEC 430.51-430.58)

    YES YES YES NO NO NO NO

    Motor controller(NEC 430.81-430.91) YES YES YES NO NO NO NO

    Motor overloadprotection(NEC 430.21-430.44)

    YES YES YES YES NO NO NO

    OSHA Lockout/tagoutdisconnect(NEC 430.81-430.91)

    YES YES YES YES YES NO NO

    Which type of Circuit Protection are you looking for?

    starting at

    $167.25begin on

    page 28-4

    Circuit Protection 1 - 8 0 0 - 6 3 3 - 0 4 0 5282

    starting at

    $57.00begin on

    page 28-30

    MAIN

    CIRCUIT

    MOTOR

    CIRCUIT

    UL

    508

    U

    L

    98

    Motor

    Supply

  • 8/9/2019 Mccbselection.pdf b.big

    2/3

    Protection

    SupplementaryProtection Selection

    SupplementaryProtectors

    UL 1077

    GeneralFuses

    UL 248-14

    page 28-21 page 28-76

    YES YES

    Anywhere

    branch

    circuit,

    overcurrent

    protection is

    already provided

    or not neededPLCI/O ContactorCoils Relays

    ControlTransformer

    UL 508 Rated Load SwitchesThe SD series of load switches are usedfor making and breaking equipmentloads. These switches can be used as amotor controller meeting NEC 430,Part VII. Typical applications include localmotor isolation.

    SD Series

    35mm DIN rail mountable or

    direct mountable

    Loads from 16 to 125 amps

    IP20 degree of protection

    FusesThe Edison Fuse products are industry-standard fuses thatare designed using the highest quality materials and manu-facturing methods. All Edison fuses can be directly crossreferenced and used as replacements for other name-brandfuses such as Littelfuse, Ferraz, Siemens, and many more.

    starting at

    $8.50begin on

    page 28-21

    SupplementaryProtectors UL1077Supplementary protectors are UL 1077

    recognized and are used in applicationswhere branch circuit protection is notrequired or is already provided

    WMS Series

    DIN rail mountable

    Full line of auxiliary switches, alarm switches and

    padlock lockout accessories

    B trip curve 6 to 60 amps

    C trip curve 0.5 to 60 amps

    D trip curve 0.5 to 40 amps

    starting at

    $1.25begin on

    page 28-59

    Circuit Protectionw w w . a u t o m a t i o n d i r e c t . c o m / c i r c u i t _ p r o t e c t i o n 283

    PLCOverview

    DL05/06PLC

    DL105PLC

    DL205PLC

    DL305PLC

    DL405PLC

    Field I/O

    Software

    C-moreHMIs

    Other HMI

    AC Drives

    Motors

    Steppers/Servos

    MotorControls

    ProximitySensors

    PhotoSensors

    LimitSwitches

    Encoders

    CurrentSensors

    PushbuttonLights

    Process

    Relays/Timers

    Comm.

    TBs &Wiring

    Power

    CircuitProtection

    Enclosures

    Appendix

    Part Index

    starting at

    $20.00begin on

    page 28-53

    CONTROLCIRCUIT

    for 5-pack

  • 8/9/2019 Mccbselection.pdf b.big

    3/3

    Circuit Protection 1 - 8 0 0 - 6 3 3 - 0 4 0 5284

    Molded Case Circuit Breakers

    Molded Case Circuit Breakers Part Numbering System

    Made by Eaton Electric Inc.,

    Manufacturer of Cutler-Hammer Products

    Note: These parts available for sale to North American locations only.

    ABBPrice/Part NumberCircuit Breakers

    AutomationDirectPrice/Part Number

    Square DPrice/Part Number

    All prices are U.S. published prices. AutomationDirect prices are from October 2007 Price List. Square D pricesare from http://www.squared.com 7/20/07. ABB prices are from http://www.abb-control.com 7/20/07.

    9,360

    20

    $459S1N100TL

    17,328

    18

    $616FAL34100

    9,424

    22

    $167G3P-100

    100A BreakerPanelArea(mm2)

    IckA@ 480/277VAC

    List Price

    17,850

    25

    $1,131S3N225TW

    23,142

    25

    $1,733KAL36225

    15,808

    35

    $384F3P-225

    225A BreakerPanelArea(mm2)

    IckA@ 480/277VAC

    List Price

    CHECK OUT OUR PRICES

    OverviewDesigned to provide branch and feedercircuit protection in industrial controlpanels, this line of Molded Case CircuitBreakers supplies protection againstoverload in conductors and short circuitin connected equipment such as motors.They are UL listed for installation in UL508 control panels. Their small size, inrelation to standard circuit breakers orother comparable devices, saves panelspace. Four frame sizes and all standardaccessories are available.

    Listings UL 489 MCCB, File: E7819

    Field-installed accessories:

    UL file E64983

    CSA 22.2 No.5, File: 43556 IEC 157-1

    NEMA Standards Pub. No. AB1-1993

    Features UL489 listed performance for branch

    circuit overcurrent protection and

    disconnecting means

    Patented contact conductor designs

    featuring high-speed blow-open

    action, providing superior performance

    when high level fault currents produce

    extra-ordinary electromechanical forces

    Advanced arc extinguishing technology

    Toggle handle provides three positions

    (on/off/tripped) along with visual

    indicators

    Manufactured in ISO 9000 certified

    facilities

    HACR (heating, air conditioning and

    refrigeration) rated

    G-Frame and F-Frame breakers are

    suitable for reverse feed

    K-Frame and L-Frame breakers include3-pole adjustable magnetic trip.

    G 3P - 020 - AUX

    Molded Case Circuit Breaker Series (by frame size)

    G: 15 to 100 Amp F: 60 to 225 Amp

    K: 250 to 400 Amp L: 400 to 600 Amp

    Accessory Description Code

    AUX: auxiliary contact UVAC: undervoltage release

    STAC: shunt trip AC

    STDC: shunt trip DC

    Amp Rating

    3 Pole

    UVDC: undervoltage release

    Molded Case Circuit Breakers Technical Specifications

    Circuit Breaker

    Type

    AmpereRating at

    40C

    No.

    Poles

    Volts Typeof

    Trip*

    FederalSpecification

    W-C-375b

    UL 489 Interrupting Ratings(rms Symmetrical Amperes) (kA)

    AC DC Volts AC (50/60 Hz) Volts DC240 480 600 250**

    G-Frame 15 -100 3 480 250 N.I.T.U 13b 65 22 10

    F-Frame 60 - 225 3 480 250 N.I.T.U 22a 65 35 18 10

    K-Frame 250 - 400 3 600 250 I.T.U 23a 65 35 25 10

    L-Frame 400 - 600 3 600 250 I.T.U 23a 65 35 25 22

    *Note: N.I.T.U denotes non-interchangeable trip unit. I.T.U denotes interchangeable trip unit.

    **Note: Two poles of 3-pole circuit breaker

    http://www.automationdirect.com/pn/S1N100TLhttp://www.automationdirect.com/pn/FAL34100http://www.automationdirect.com/pn/G3P-100http://www.automationdirect.com/pn/S3N225TWhttp://www.automationdirect.com/pn/KAL36225http://www.automationdirect.com/pn/F3P-225http://www.automationdirect.com/pn/F3P-225http://www.automationdirect.com/pn/G3P-100http://www.automationdirect.com/pn/KAL36225http://www.automationdirect.com/pn/S3N225TWhttp://www.automationdirect.com/pn/FAL34100http://www.automationdirect.com/pn/S1N100TL