MCCBs and trip-free switches16 A to 1600 A

Page 2: MCCB

MCCBs and trip-free switches16 to 1600 AEasy mounting and safetyThe new range of MCCBs provides safe and easy solutions for low voltage electrical circuits protection.The state of the art circuit breakers offers both designers and installers wide range of features and bene-fits.Special attention has been given to ergonomics, especially with the integration of these devices in theTP&N and panelboard.

Your benefits:

• Easy to install

• Quick, easy and safety mounting of accessories

• Wide range of rated current ratings and breaking capacities

• Calibrated at 50 Deg centigrade

• Trip-free switches

Technical data :

• Comply with IEC 60947-2

• 6 frame sizes: x160, x250, h250, h630, h1000, h1600

• Breaking capacity: 18, 25, 40, 50, 65, 70 kA

• Thermal magnetic and electronic trip units

• 1 pole to 4 poles

• Current limiting type

• Complete range of accessories

• International certification and approvals

Page 3: MCCB

Electronic trip unit (LSI)Is permitting total selectivity andgenerator protection.

Breaking capacity18 to 70kA, Icu 415V AC, coversall applications.

Easy mounting of auxiliariesEasy opening of secondarycover, clip-on type auxiliaries.

1

2

3

Design by HagerIn harmony with Hager enclosures and modular products.

4

Integrated padlockingfacilityNice solution for maintenance.

Complete range of accessoriesRotary handles, padlocks, motors, terminal covers.

Flexible connectionCollar terminals, front and rear connections, straight connections, spreaders ...

5

6

7

Visibility of auxiliariesfittedIndicates type of auxiliary mounted in breaker.

8

Experttips

Page 4: MCCB

H3 add-on blocks16 to 1600 AEasy mounting and safetyDesigned to complete the MCCBs and trip-free switches range, the residual current add-on blocks feature:

- performance: high immunity A type for standard versions, adjustable product ...- Safety: default current gradually displayed, class II...- Ease of use: drawer system, system avoids the omission of terminal tightening, Quickconnect ...

Your benefits:

• Easy to install

• Safety to use

• Time saving

• Design matches with modular protection devices

Technical data :

• 3 frame sizes: x160, x250, h630

• Double isolation class II

• Type A reinforced immunity

• Fixed 300mA version for x160

• Sensitivity and time delay settings

Page 5: MCCB

Connectionsfor the information report via QuickConnect terminals: fast and long term quality connections.

A and HI type are standardHigh detection performance product:- detects sinusoidal alternating

currents and residual pulsatingcurrents

- is protected against nuisancetripping caused by transient voltages

1

2

3

Drawer system formounting on x160Quick and safe to mount, thanksto the system avoiding the terminal tightening omission.

Safe connection MCCB /add-on block- Class II: terminal cover avoid

direct contacts.

Pre-mounted connectionscrewsSimplified implementation of theadd-on blocks:- time saving- avoid part loosing.

4

5

6

High performanceGradual display of the defaultcurrent allows preventive actionbefore tripping.

Experttips

Page 6: MCCB

6 Technical modifications reserved

MCCBs : technical characteristics

Frame x160 x250Product Switch MCCB Switch MCCBReference HCA HDA HHA HNA HCB HNBNumber of poles [No.] 3-4 3-4 3-4 3-4 3-4Electrical characteristicsRated current In [A] 160 250Current rated range [A] 125-160 16-125 (1P), 16-160 (2,3,4P) 250 100-250Rated service voltage, (AC) Ue [V] 220-440 220-440Frequency f [Hz] 50/60 50/60Rated insulation voltage Ui [V] 800 800Rated impulse withstand voltage Uimp [kV] 8 8Rated ultimate short-circuit breaking capacity, (Icu)

(AC) 50-60 Hz 220/230 V Icu [kA] - 25 35 85 - - 85

(AC) 50-60 Hz 380/415 V Icu [kA] - 18 25 40 - - 40(AC) 50-60 Hz 480/500/525 V Icu [kA] - - - - - - -(AC) 50-60 Hz 660/690 V Icu [kA] - - - - - - -(DC) 250 V - 2 poles in series Icu [kA] - 10 10 10 - - 9

Rated service short-circuit breaking capacity, (Ics)(AC) 50-60 Hz 220/230 V Ics [kA] - 25 25 40 - - 40

(AC) 50-60 Hz 380/415 V Ics [kA] - 18 20 20 - - 20(AC) 50-60 Hz 480/500/525 V Ics [kA] -(AC) 50-60 Hz 660/690 V Ics [kA] - - -(DC) 250 V - 2 poles in series Ics [kA] - 5 5 5 - - 5

Rated short-circuit making capacity Icm [kA] 2,8 - - - 9 - -Rated short-time withstand current for 1s Icw [kA] 2 - - - 3 - -Category of use (EN 60947-2) - A - ACalibration temperature - 50°C - 50°CDerating 40°C - 100% - 100%

50°C - 100% - 100%55°C - 95% - 94%60°C - 93% - 91%65°C - 90% - 88%

Suitability for isolation ok okElectric endurance in number of cycles 10000 10000Mechanical endurance in number of operations 20000 20000Operating temperature -25 to +70°C -25 to +70°CStorage temperature -35 to +70°C -35 to +70°CPower loss (at In for 3P) [W] 39 60Reference standard IEC 60947-3 IEC 60947-2 IEC 60947-3 IEC 60947-2Releases: switch ok - ok -Releases: TM (thermomagnetic) - ok - okT fixed, M fixed - ok - okT adjustable, M fixed - ok - -T adjustable, M adjustable - - - okThermal adjustment value - 0,63 to 1 x In - 0,63 to 1 x InMagnetic adjustment value - - - 6-8-10-13 x In (200A)

5-7-9-11 In (250A)Releases: LSI (electronic) - - - -Long delay - - - -Short delay - - - -

Time delay - - - -TerminationsStandard terminal type cage lugsMaximum terminal capacity 95 mm2 185 mm2 (cage)Terminal width mm - 25Terminal shields ok okCage terminal integrated okExtended connections ok okRear connections no okDimensionsHeight mm 130 165Width 1P mm - 25 - -

2P mm - 50 - -3P mm 75 1054P mm 100 140

Depth mm 68 68Weight 1P kg - 0,29 - -

2P kg - 0,48 - -3P kg 0,715 1,34P kg 0,95 1,6

Page 7: MCCB

7Technical modifications reserved

h250 LSI h400 h630 h1000 h1600MCCB MCCB Switch MCCB Switch MCCB Switch MCCBHNC HEC HHD HND HCD HND HED HCE HNE HEE HCF HNF HEF3-4 3-4 3-4 3-4 3-4

250 400 630 1000 160040-125-250 250-400 400-630 250-630-400 800-1000 1250-1600220-690 220-690 220-690 220-690 220-69050/60 50/60 50/60 50/60 50/60800 800 800 800 8008 8 8 8 8

85 100 35 85 - 85 100 - 85 (800A)75 (1000A)

100 - 100 100

50 70 25 50 - 50 70 - 50 70 - 50 7025 45 10 30 - 30 30 - 30 30 - 45 657,5 20 7,5 20 - 20 20 - 20 20 - 25 45- - 25 40 - - - - - - -

85 100 35 85 - 85 85 - 85 (800A)75 (1000A)

100 (800A)75 (1000A)

- 75 75

25 70 25 50 - 50 50 - 50 50 - 50 5010 45 10 30 - 30 30 - 30 30 - 45 507,5 15 7,5 15 - 15 15 - 20 20 - 25 34- - 25 40 - - - - - - -- - - 9 - - 20 - - 45 - -- - - 5 (0,3s) - - 10 (0,3s) - - 20 (0,3s) - -A A - B (250A) - A (630A) - B (800A) - A (1000A) - B40°C 50°C - 40°C - 40°C - 40°C100% 100% - 100% - 100% - 100%95% 100% - 100% - 100% - 100%90% 95% - 95% - 95% - 95%80% 92% - 90% - 90% - 90%80% 89% - 80% - 80% - 80%ok ok ok ok ok10000 4500 4500 4500 450030000 15000 15000 15000 15000-25 to +70°C -25 to +70°C -25 to +70°C -25 to +70°C -25 to +70°C-35 to +70°C -35 to +70°C -35 to +70°C -35 to +70°C -35 to +70°C75 75 150 150 170IEC 60947-2 IEC 60947-2 IEC 60947-3 IEC 60947-2 IEC 60947-3 IEC 60947-2 IEC 60947-3 IEC 60947-2- - ok - ok - ok -- ok - - -- - - - -- - - - -- ok - - -- 0,63 to 1 x In - - -- 6-8-10-12 x In - - -

- - - ok - ok - ok0,4 to 1 x Ir - - 0,4 to 1 x Ir - 0,4 to 1 x Ir - 0,4 to 1 x In2,5 to 10 x Ir - - 2,5 to 10 x Ir (250A)

2,5 to 8 x Ir (630A)- 2,5 to 10 x Ir (800A)

2,5 to 8 x Ir (1000A)- 2,5 to 10 x Ir

0,1 - 0,2s - - 0,1 - 0,2s - 0,1 - 0,2s - 0,1 - 0,2s

lugs lugs lugs lugs lugs120 mm2 (cage) 240 mm2 (cage) - - -25 30 30 45 45ok ok ok ok okok ok - - -ok ok integrated integrated integratedok ok ok ok ok

165 260 260 273/433 370/570- - - - -- - - - -105 140 140 210 210140 185 185 280 28097 97 97 99,5 140- - - - -- - - - -2,5 4,2 4,3 11 273,3 5,6 5,7 14,8 31

Page 8: MCCB

MCCBs : technical characteristics

8 Technical modifications reserved

Number of poles

Tripping access

Standards CEI/EN 60947-2 appendix B

Electrical characteristics

Mx rated current (40°) In A In

Rated service voltage Ue V AC (50/60Hz) Ue

Mechanical characteristics

Top and bottom supply

For tripping, no additional external electrical sources

Possible operating with 2 active phases

Settings

Sensitivity IΔn IΔn (A)

Time delay Δt Δt (s)

Max. opening time ms

Delay add-on block is not possible if IΔn = 30mA

Selective product

Mechanical test button

Isolating test without cable removal

Electrical test button

Reset button

Sealable setting button

Isolation level signaling by led 25 and 50%

In runnig signalisation by led

Residual default signaling contact

Signaling contact 50% Idn

Anti-transient type AC

Pulsating current type A

High immunity type HI

-25°C

Accessories and connection

Steel terminal cage (x3/x4)

Connexion by lugs

Extended connexions (x4)

Spreaders (x4)

Terminal covers (3P/4P)

Interphase barriers (x3)

Rigid cables connection capacity mm²

Flexible cables connection capacity mm² (with terminal)

Tightening torque Nm

Copper bar (width) in mm

Mounting

Clips on DIN rail

Fixed on mounting plate

Fixation type

Mounting by customer

Dimensions and weight

Dimensions (LxHxP) in mm L

Side mounted 4P H

D

Weight 3P

4P

Add-on blocks

x160 x160 x250 h630

Product

Frame

3, 4

mechanical

ok

125A

240-415V

ok

ok

ok

300mA

inst.

10

/

no

ok

ok

ok

ok

no

no

no

ok

no

ok

ok

yes

ok

ok (included)

no

ok

ok

no

ok

4 - 95

4 - 70

6

no

ok

no

side

ok

100

165

95

1,4

1,55

3, 4

mechanical

ok

125 - 160A

240-415V

ok

ok

ok

0.03, 0.1, 0.3, 1,

3, 6A

inst., 0.06, 0.15,

0.3, 0.5, 1

10

ok

ok

ok

ok

ok

ok

ok

ok

ok

ok

ok

ok

ok

yes

ok

ok (included)

no

ok

ok

no

ok

4 - 95

4 - 70

6

no

ok

no

side

ok

100

165

95

1,4

1,55

4

mechanical

ok

160 - 250A

240-415V

ok

ok

ok

0.03, 0.1, 0.3, 1,

3, 6A

inst., 0.06, 0.15,

0.3, 0.5, 1

10

ok

ok

ok

ok

ok

ok

ok

ok

ok

ok

ok

ok

ok

yes

ok

accessories

ok

ok

ok

ok

ok

35-185

35-150

12

25

no

ok

bottom

ok

140

107,5

85

/

1,2

4

mechanical

ok

400A - 500A

240-415V

ok

ok

ok

0.03, 0.1, 0.3, 1,

3, 6A

inst., 0.06, 0.15,

0.3, 0.5, 1

10

ok

ok

ok

ok

ok

ok

ok

ok

ok

ok

ok

ok

ok

yes

ok

accessories

ok

ok

ok

ok

ok

35-240

35-185

22

30

no

ok

bottom

ok

184

133

110

/

2,4

Page 9: MCCB

9Technical modifications reserved

MCCBs : references guide

Serie HDx HHx HNx HNx HExPole Trip unit In A 18kA 25kA 40kA 50kA 65kA - 70kA

x160

3P

TM fix/fix

16 HDA016L HHA016L20 HDA020L HHA020L25 HDA025L HHA025L32 HDA032L HHA032L40 HDA040L HHA040L50 HDA050L HHA050L63 HDA063L HHA063L80 HDA080L HHA080L100 HDA100L HHA100L125 HDA125L HHA125L160 HDA160L HHA160L

TM adj/fix

16-20-25 HHA025H HNA025H25-32-40 HHA040H HNA040H40-50-63 HHA063H HNA063H50-63-80 HHA080H HNA080H63-80-100 HHA100H HNA100H80-100-125 HHA125H HNA125H100-125-160 HHA160H HNA160H

4P100%

TM fix/fix

16 HDA017L20 HDA021L25 HDA026L32 HDA033L40 HDA041L50 HDA051L63 HDA064L80 HDA081L100 HDA101L125 HDA126L160 HDA161L

TM adj/fix

16-20-25 HHA026H HNA026H25-32-40 HHA041H HNA041H40-50-63 HHA064H HNA064H50-63-80 HHA081H HNA081H63-80-100 HHA101H HNA101H80-100-125 HHA126H HNA126H100-125-160 HHA161H HNA161H

x250

3P

TM fix/fix

100 HNB100H125 HNB125H160 HNB160H200 HNB200H250 HNB250H

TM adj/adj

63-80-100 HNB100U80-100-125 HNB125U100-125-160 HNB160U125-160-200 HNB200U160-200-250 HNB250U

4P 0% - 4P50%

HNB102HHNB127HHNB162HHNB202HHNB252H

4P 0% - 4P100%

TM adj/adj

63-80-100 HNB101H80-100-125 HNB126H100-125-160 HNB161H125-160-200 HNB201H160-200-250 HNB251H

h250

3P LSI16-40 HNC040H HEC040H50-125 HNC125H HEC125H100-250 HNC250H HEC250H

4P 0% LSI16-40 HNC041H HEC041H50-125 HNC126H HEC126H100-250 HNC251H HEC251H

h400 - h630

3P LSI100-250 HND250H HED250H160-400 HND400H HED400H250-630 HND630U HED630H

4P 0% - 50%- 100%

LSI100-250 HND251H HED251H160-400 HND401H HED401H250-630 HND631H HED631H

h10003P LSI

800 HNE800H HEE800U1000 HNE970H HEE970U

4P 0% - 50%- 100%

LSI800 HNE801H HEE801H1000 HNE971H HEE971H

h16003P LSI

1250 HNF980H HEF980H1600 HNF990H HEF990H

4P 0% - 50%- 100%

LSI1250 HNF981H HEF981H1600 HNF991H HEF991H

Page 10: MCCB

Trip-free switches and add-on blocks for MCCBsreferences guide

10 Technical modifications reserved

Serie x160 x250 h630 h1000 h1600

Product Version Poles In A

Trip-free switches

3 poles125 HCA125H

160 HCA160H

4 poles125 HCA126H

160 HCA161H

3 poles250 HCB250H

4 poles250 HCB251H

3 poles400 HCD400H

630 HCD630H

4 poles400 HCD401H

630 HCD631H

3 poles800 HCE800H

1000 HCE970H

4 poles800 HCE801H

1000 HCE971H

3 poles1250 HCF980H

1600 HCF990H

4 poles1250 HCF981H

1600 HCF991H

Add-on blocks

Side mounted

3 poles

125 fixed HBA127H

125 adjustable HBA125H

160 adjustable HBA160H

4 poles

125 fixed HBA128H

125 adjustable HBA126H

160 adjustable HBA161H

Bottom mounted 4 poles

160 adjustable HBB161H

250 adjustable HBB251H

400 adjustable HBD401H

500 adjustable HBD631H

Page 11: MCCB

Switches and accessories for MCCBsreferences guide

11Technical modifications reserved

Switches and accessoriesProducts Version pole In A / Ue V x160 x250 h250 h400-h630 h1000 h1600

Auxiliaries

Shunt trip release 3/4P

24V DC HXA001H HXC001H

48V DC HXA002H HXC002H

100-120V AC HXA003H HXC003H

200-240V AC HXA004H HXC004H

380-450V AC HXA005H HXC005H

Undervoltage release 3/4P

24V DC HXA011H HXC011H HXE011H

100-120V AC HXA013H HXC013H HXE013H

200-240V AC HXA014H HXC014H HXE014H

380-450V AC HXA015H HXC015H HXE015H

Delayed undervoltage release

3P 24V DCHXA051H HXC051H

HXC051HHXE051H HXF051H

4P 24V DC HXD051H

3P 110-120V ACHXA053H HXC053H

HXC053HHXE053H HXF053H

4P 110-120V AC HXD053H

3P 220-240V ACHXA054H HXC054H

HXC054HHXE054H HXF054H

4P 220-240V AC HXD054H

3P 380-415V ACHXA055H HXC055H

HXC055HHXE055H HXF055H

4P 380-415V AC HXD055H

Auxiliary contact 3/4P 1NO+1NC HXA021H HXC021H

Alarm contact 3/4P 1NO+1NC HXA024H HXC024H

Auxiliary contact - low level 3/4P 1NO+1NC HXA025H HXC025H

Alarm contact - low level 3/4P 1NO+1NC HXA026H HXC026H

Direct rotary handle HXA030H HXB030H HXC030H HXD030H HXE030H HXF030H

Extended rotary handle HXA031H HXB031H HXC031H HXD031H HXE031H HXF031H

Padlock HXA039H HXC039H HXD039H HXF039H

Motor operator 3/4P24V DC - HXB040H HXC040H HXD040H HXE040H HXF040H

220V AC - HXB042H HXC042H HXD042H HXE042H HXF042H

Interlocking wire type 3/4P - HXB065H HXC065H HXD065H HXE065H -

Connections

Collar terminal - copper

3P included - HYC003HHYD003H(250-400A)

- -

4P included - HYC004HHYD004H(250-400A)

- -

Collar terminal - aluminium3P HYA005H HYB001H - HYD005H - -

4P HYA006H HYB002H - HYD006H - -

Collar terminal multiple - aluminium3P - - - HYD007H HYE007H (to 800) -

4P - - - HYD008H HYE008H (to 800) -

Extended straight connection3/4P HYA013H HYB010H HYC010H

HYD010H(250-400A)HYD013H(630A integrated)

included(except 630A)

included

Extended spreader connection

3P HYA014H HYB011H HYC011H

HYD011H(250-400A)HYD014H(630A)

- -

4P HYA015H HYB012H -

HYD012H(250-400A)HYD015H(630A)

- -

Interphase barrier 3/4Pshort HYA019H - - - -

long HYB019H included included included included

Terminal cover for extended straight connections

3P HYA021H HYB021HHYC021H (LSI)HYG021H (TM)

HYD021H HYE021H -

4P HYA022H HYB022HHYC022H (LSI)HYG022H (TM)

HYD022H HYE022H -

Terminal cover large for spreader connection

3P HYA023H HYB023H - HYD023H - -

4P HYA024H HYB024H - HYD024H - -

Terminal cover short for rear connections

3P HYA025H HYB025H HYC025H (LSI) HYD025H HYE025H -

4P HYA026H HYB026H HYC026H (LSI) HYD026H HYE026H -

Terminal cover for collar terminal

3P HYA027H HYB027H HYC027H HYD027H - -

4P HYA028H HYB028H HYC028H HYD028H - -

Rear connections

3P - HYB031H HYC031H (LSI)

HYD031H(250-400A)HYD033H(630A)

HYE031H (630-800A)HYE033H (1000A)

-

4P - HYB032H HYC032H (LSI)

HYD032H(250-400A)HYD034H (630A)

HYE032H (630-800A)HYE034H (1000A)

-

DIN rail adaptor 3/4P HYA033H - - - - -

Connecting kit (0,75mm2) 3/4P HYA035H

Rail Din raiser 3/4P HYA036H - - - - -

Compact lugs 16mm2 D:8,5 3/4P HYA086H - - - - -

Compact lugs 25mm2 D:8,5 3/4P HYA087H - - - - -

Compact lugs 35mm2 D:8,5 3/4P HYA088H - - - -

Compact lugs 50mm2 D:8,5 3/4P HYA089H - - - -

Compact lugs 70mm2 D:8,5 3/4P HYA090H - - - -

Compact lugs 95mm2 D:8,5 3/4P HYA091H - - - -

Compact lugs 120mm2 D:8,5 3/4P - HYB092H - - - -

Compact lugs 120mm2 D:10 3/4P - - - HYD093H - -

Compact lugs 150mm2 D:8,5 3/4P - HYB094H - - - -

Compact lugs 150mm2 D:10,5 3/4P - - - HYD095H - -

Compact lugs 185mm2 D:10,5 3/4P - - - HYD096H - -

Compact lugs 185mm2 D:12,8 3/4P - - - HYD097H* - -

Compact lugs 240mm2 D:12,8 3/4P - - - HYD098H* - -

* with spreaders

Page 12: MCCB

12 Technical modifications reserved

MCCBs and trip-free switches x160

Designation In

Moulded case circuit breakersx160Thermal magnetic trip unit, 2 ver-sions:- L version: fixed thermal and

fixed magnetic- H version: adjustable thermal

and fixed magnetic

3P and 4P Mechanical test button, lockable

Cat. ref.

3P 4P

MCCBs x160 18kAbreaking capacityIcs : 18 kA(400/415 V AC)

fixed thermal1x Infixed magnetic> 10 x In

16A20A25A32A40A50A63A80A100A125A160A

HDA016LHDA020LHDA025LHDA032LHDA040LHDA050LHDA063LHDA080LHDA100LHDA125LHDA160L

HDA017LHDA021LHDA026LHDA033LHDA041LHDA051LHDA064LHDA081LHDA101LHDA126LHDA161L

MCCBs x160 25kAbreaking capacityIcs : 20 kA(400/415 V AC)adjustable thermal0,63 - 0,8 - 1 x Infixed magnetic> 10 x In

16-20-25A25-32-40A40-50-63A50-63-80A63-80-100A80-100-125A100-125-160A

HHA025HHHA040HHHA063HHHA080HHHA100HHHA125HHHA160H

HHA026HHHA041HHHA064HHHA081HHHA101HHHA126HHHA161H

settings, integrated padlocking handle Ø 4mm.

Connection capacity95 mm2 rigid cables70 mm2 flexible cablescollar terminals

Comply with IEC 60 947-2.

Trip-free switchesAllows tripping at distance usinga voltmetrical trip unit (optional)AC 22/23A.

Comply with IEC 60 947-3.

HDA125L

HDA161H

Page 13: MCCB

MCCBs and trip-free switches x160

13Technical modifications reserved

Designation In Cat. ref.

3P 4P

MCCBs x160 40kAbreaking capacityIcs : 20 kA(400/415 V AC)

adjustable thermal0,63 - 0,8 - 1 x Infixed magnetic> 10 x In

16-20-25A25-32-40A40-50-63A50-63-80A63-80-100A80-100-125A100-125-160A

HNA025HHNA040HHNA063HHNA080HHNA100HHNA125HHNA160H

HNA026HHNA041HHNA064HHNA081HHNA101HHNA126HHNA161H

Trip-free switches x160suitable for AC22A / AC 23A

Ue: 415 V ACIcw (1s): 2 kA

125A160A

HCA125HHCA160H

HCA126HHCA161H

Add-on blocks l n 300 mA fixed sensitivityinstantaneous tripping

sensitivity lΔnadjustable: 0,03 - 0,1 - 0,3 -1 - 3 - 6Aadjustable tripping:- instantaneous- time delay 0,06 - 1 sec.

125 A

125A160A

HBA128H

HBA126HHBA161H

HBA127H

HBA125HHBA160H

Add-on blocks for x160 devicesThese devices are intended to befixed on the right side of the devices.

Type A and HIFor fault component pulsating current.HI (High Immunity):the products with “reinforced immunity” reduce the unexpected tripping when theyprotect equipment generating

disturbances (micro-processing,electronic ballast...)Fixed version: 300 mA sensitivityand instantaneous tripping

Adjustable version: adjustable sensitivity and tripping.

Test button for differential func-tioning check.Mechanical test button

LED or at distance signal for tripping or advance warning

(25-50% I n).

Assembly and disassembly facilitated by the drawer assembly system. The terminalcover is dependent of the add-on block.

Connection capacity95 mm2 rigid cables70 mm2 flexible cables

Comply with IEC 60 947-2annexe B.

HNA125H

HBA161H

Page 14: MCCB

HXA021H HXA024H

14 Technical modifications reserved

Accessories for MCCBs and trip-free switches x160

Designation Characteristics

Indication contacts- 1 changeover switch (ON/OFF):indicates the position of theMCCB is “open” or “close”.- 1 changeover alarm contact:indicates MCCB tripping.

Coil connectionConnection capacity:0,75I flexible or rigid cablesOptional connection cables.The cable capacity of the terminals is 0,5 to 1,25 mm2.

Auxiliary contactsAXAL

1 changeover contact (ON/OFF)250 V AC / 3A125 V DC / 0,4A1 NO + 1 NC

1 changeover alarm contact250 V AC / 3A125 V DC / 0,4A1 NO + 1 NC

Low level contact (ON/OFF)125 V AC1 NO + 1 NC

Low level alarm contact125 V AC1 NO + 1 NC

HXA021H

HXA024H

HXA025H

HXA026H

Shunt tripsSH

24 V DC

48 V DC

100 - 120 V AC

200 - 240 V AC

380 - 450 V AC

HXA001H

HXA002H

HXA003H

HXA004H

HXA005H

Undervoltage releasesUV

24 V DC

100 - 120 V AC

200 - 240 V AC

380 - 450 V AC

HXA011H

HXA013H

HXA014H

HXA015H

Cat. ref.

Shunt tripRemotes tripping of MCCBs or trip-free switches.Operating voltage: 0,7 to 1,1 xUn

Under voltage releaseAllows the tripping of MCCBs or trip-free switches when voltagelevel drop between 35 and 70%of Un. Pick up voltage 0,85 x Un

Direct rotary handle- padlockable- equipped with front cover and handle- fixing without any additionalscrew.

Extended rotary handle- IP 55- supplied complete with shaftand handle.

Delayed undervoltage releasesDUVR

24 V DC

110 - 120 V AC

220 - 240 V AC

380 - 450 V AC

HXA051H

HXA053H

HXA054H

HXA055H

HXA014H

HXA004H

Page 15: MCCB

Accessories for MCCBs and trip-free switches x160

15Technical modifications reserved

Designation Characteristics Cat. ref.

3P 4P

Extended connections set of 4 straightconnections

set of 3 or 4 spreaderconnections

HYA013H

HYA015H

HYA013H

HYA014H

Direct rotary handle padlockable handlemax Ø 6 mm

Extended rotary handle padlockable handlemax Ø 8 mm

Padlock to mount on MCCB forhandle lockingfor 3 padlockmax Ø 8 mm

HXA030H

HXA031H

HXA039H

Collar terminals set of 3 or 4 terminals foraluminium conductor

HYA006HHYA005H

HXA030H

HXA031H

HYA006H

HYA015H

Page 16: MCCB

Accessories for MCCBs and trip-free switches x160

16 Technical modifications reserved

Interphase barriers set of 3, height: 50 mm

set of 3, height: 97 mm

HYA019H

HYB019H

HYA019H

HYB019H

Terminal covers for extended straight connections

for extended spreader connections

for collar terminal

HYA022H

HYA024H

HYA028H

HYA021H

HYA023H

HYA027H

Din rail adaptor HYA033HHYA033H

Ring lugs compact lugs 16 mm2 Ø8,5

compact lugs 25 mm2 Ø8,5

compact lugs 35 mm2 Ø8,5

compact lugs 50 mm2 Ø8,5

compact lugs 70 mm2 Ø8,5

compact lugs 95 mm2 Ø8,5

HYA086H

HYA087H

HYA088H

HYA089H

HYA090H

HYA091H

Connecting kit HYA035HHYA035H0,75 mm2

set of 3 x 2 wireslength: 1,30m

Designation Characteristics Cat. ref.

3P 4P

HYA019H

HYA023H

HYA027H

Page 17: MCCB

MCCBs, trip-free switchesx160

17Technical modifications reserved

MCCBs

Magnetic and thermal settings

220/240V ACIEC 60 947-2

380/415V ACIEC 60 947-2

HDA Icu 25 kA 18 kA

Ics 25 kA 18 kA

HHA Icu 35 kA 25 kA

Ics 25 kA 20 kA

HNA Icu 85 kA 40 kA

Ics 30 kA 20 kA

PUSH TO TRIP

TRIP

6

Thermal adjustment from 0,63 to 1 x In

� �

�In 15 - 50 A 63 - 80 A 100 - 125 A 160 A

Imag 600 A 1000 A 1500 A 1600 A

Magnetic adjustment fixed > 10 x In

Page 18: MCCB

18 Technical modifications reserved

MCCBs, trip-free switchesx160

Tripping curve

MCCB x160

Déclenchement à froid

Déclenchement à chaud(courant nominal)

25 A32

A63 A

100

A, 4

0 A

80 A

160

A12

5 A

, 50

A

0.01

0.1

1

10

100

1000

100101xIn

Tem

ps d

e dé

clen

chem

ent (

s)

0.001

10000

Thermal constraint curve (Let-through energy)

MCCB x160

25A32A

40A50A63A80A

100A125A160A

I2 t (x

10 A

s)

62

101

102

103

104

101 10210,1

Current limiting curve (Let-through pick current)

MCCB x160

125 A

0,8

0,5

0,3

0,25

0,7

0,9

32 A25 A

40 A50 A63 A80 A

100 A

160 A

0.1

1

10

100

1001010,1Icc (kA)

Ip (k

A)

Hot start (rated current)

Cold start

Trip

pin

g tim

e (s

)

Page 19: MCCB

One line titleMCCBs, trip-free switchesx160

MCCB x160

Dimensions

11 96,1

6815

45130

25 25

A25

114

111

A(mm)

B(mm)

C(mm)

1P 24,8 25 111

2P 49,5 25 111

3P 74,5 25 111

4P 99,5 25 111

Terminal covers for extended straight connections

A(mm)

B(mm)

C(mm)

1P 24,4 50 60,5

2P 49,5 50 60,5

3P 74,5 50 60,5

4P 99,5 50 60,5

230

A C

B

Terminal cover for extended spreader connections

A(mm)

B(mm)

C(mm)

3P 106,5 50 60,5

4P 141,5 50 60,5

60,5A

B

Page 20: MCCB

20 Technical modifications reserved

MCCBs, trip-free switchesx160

min. 6 mm2 max. 70 mm2

min. 6 mm2 max. 95 mm2

6 6 Nm

Connection

Connection with end lugs

16maxi

55

L

Interphase barriers

PUSH TO TRIP

L(mm)

HYA019H 50

HYB019H 97

4

Terminals fo aluminium conductor

min. 35 mm2 max. 95 mm2

6 10 Nm5

Page 21: MCCB

21Technical modifications reserved

MCCBs, trip-free switchesx160

Extended straight connections

12,7

17,6

Ø 8,3

122122

87

16,8 1026,8

3P

4P

35 3535

12,7

203

mm

54

17,6

Ø 8,3

122122

87

16,8 1026,8

3P

4P

PUSH TO TRIP

17

PUSH TO TRIP

Ø 8

6 Nm

6 Nm

Extended spreader connections

Direct rotary handle

48,5127

53,745

101,

8

(3 P) 74,5(4 P) 99,5

12

112

45

101,

8

8,5

200

(3 P) 74,5(4 P) 99,5

Extended rotary handle

Page 22: MCCB

22 Technical modifications reserved

MCCBs, trip-free switchesx160

AX AL SH / UV

UVAL

AX

t e 3 P

4 P

Auxiliaries

Auxiliaries for MCCBs and trip-free switches

PUSH TO TRIP

Mounting combination for auxiliaries and releases

AXAuxiliary contact

ALAlarm contact

SHShunt trip

UVUndervoltage release

TRIP

DUVRDelayedundervoltagerelease

Page 23: MCCB

23Technical modifications reserved

Add-on blockx160

Characteristics

Reset button : Signals add-on block tripping and must be acknowledged before switching on the installation.

Test button for differential functioning : Allows to check the electrical operating of the MCCB / Add-on block association.

Mechanical test button : Allows to check the mechanical operating of the MCCB / Add-on blockassociation.

LED signaling default current level in the installation:25% (orange) and 50% (red) IΔn; green light to signal correct operating.

Remote tripping and advanced warning (50% IΔn) signaling thanks tothese contacts:

Add-on block operatingEarth leakage current (IΔn) and delay (Δt) setting

When associated with MCCB, the add-on block provides an earth faultprotection and protects against electrical shocks by direct or indirectcontacts.

The add-on blocks are protected against nuisance tripping caused bytransient voltages. It’s able to detect sinusoidal alternating currents andresidual pulsating direct currents ( A type ). It also avoids miss tripping (HI type - High Immunity).

N L1 L2 L3

N L1 L2 L3

incoming

outgoing

test button

CA

50%

electronic

ON

125A250A

V

1

V

2

63

10,30,1

0,03

I n (A)

10,5

0,30,150,06

Inst.

t (s)

103

10,30,1

0,03

10,5

0,30,150,06

Inst.

I n (A)

t (s)

5

2

S (Δ

t)

A (IΔn)

0,03 0,1 0,3 1 3 6

Inst. OK OK OK OK OK OK

0,06 no OK OK OK OK OK

0,15 no OK OK OK OK OK

0,3 no OK OK OK OK OK

0,5 no OK OK OK OK OK

1 no OK OK OK OK OK

Page 24: MCCB

24 Technical modifications reserved

Add-on blockx160

Add-on block mounting

Dimensions

Exclusive drawer assembly system allows quick mounting and makesMCCB and add-on block association a complete monoblock unit.

Reinforced insulation connexion (class II)

System avoids the omission of terminal tightening

TRIP

OFF

37

25 25

A

165

B

3P 4P

A (mm) 100 100

B (mm) 174,5 199,5

PUSH TO TRIP

4

3

6 Nm

PUSH TO TRIP

5

� �

� �

Page 25: MCCB

25Technical modifications reserved

Page 26: MCCB

26 Technical modifications reserved

MCCBs and trip-free switches x250

Designation In

Moulded case circuit breakers x250, adjustable thermal and magnetic

3P and 4PMechanical test button,lockable settings,integrated padlocking handle Ø 4mm.Comply with IEC 60 947-2.

Connection:Directly on copper cable terminal, with end lug max. width: 25 mmConnection capacity: 185 mm2

rigid cables

Cat. ref.

3P 4P

MCCBs x250 40kA 100A

125A

160A

200A

250A

HNB100H

HNB125H

HNB160H

HNB200H

HNB250H

HNB101H

HNB126H

HNB161H

HNB201H

HNB251H

Trip-free switches x250 250A HCB250H HCB251H

Designation

breaking capacityIcu : 40 kA(400/415 V AC)Ics: 20 kA

adjustable thermal0,63 - 0,8 - 1x Inadjustable magnetic6 - 8 - 10 - 13 x In (100 - 200A)5 - 7 - 9 - 11 x In (250A)

3P, 3 trip units4P,neutral setting: 0 or 100%

capacity suitable forAC 22/23A

Icw (1s): 3 kA

Type A and HIfor fault component dc pulsating current and the products with “reinforced immunity”.Adjustable sensitivity and tripping.Test button for differential functioning check.Mechanical test buttonLED or at distance signal for tripping or advance warning (25 - 50% IΔn).

Comply with IEC 60 947-2 annexe B

Add-on blocks 160A

250A

-

-

HBB161H

HBB251H

adjustable sensitivity IΔn:0,03 - 0,1 - 0,3 - 1 - 3 - 6A

adjustable tripping:- instantaneous- time delay:0,06 - 0,15 - 0,3 - 0,5 - 1 sec

Comply with IEC 60 947-2.Collar terminals

Trip-free switchesAllows tripping at distance usinga voltmetrical trip unit (optional)Complies with IEC 60 947-3AC 22/23A

Add-on blocks for x250 devicesThese devices are intended to befixed at the bottom of the devices.

HNB100H

HBB251H

Page 27: MCCB

27Technical modifications reserved

Accessories for MCCBs and trip-free switches x250

1 changeover contact250 V AC / 3A125 V DC / 0,4A1 NO + 1 NC

1 changeover alarm contact250 V AC / 3A125 V DC / 0,4A1 NO + 1 NC

low level contact (ON/OFF)125 V AC1 NO + 1 NC

low level alarm contact125 V AC1 NO + 1 NC

HXA021H HXA024H

Designation Characteristics

Indication contacts- 1 changeover switch (ON/OFF):indicates the position of theMCCB is “open” or “closed”.- 1 changeover alarm contact:indicates MCCB tripping.

Coil connectionConnection capacity:0,75 mm2 flexible or rigid cablesOptional connection cables.The cable capacity of the terminals is 0,5 to 1,25 mm2.

Auxiliary contactsAXAL

HXA021H

HXA024H

HXA025H

HXA026H

Shunt tripsSH

24 V DC

48 V DC

100 - 120 V AC

200 - 240 V AC

380 - 450 V AC

HXA001H

HXA002H

HXA003H

HXA004H

HXA005H

Undervoltage releasesUV

24 V DC

100 - 120 V AC

200 - 240 V AC

380 - 450 V AC

HXA011H

HXA013H

HXA014H

HXA015H

Cat. ref.

Shunt tripRemotes tripping of MCCBs ortrip-free switches.Operating voltage: 0,7 to 1,1 x Un

Under voltage releaseAllows the tripping of MCCBs ortrip-free switches when voltagelevel drop between 35 and 70%of Un. Pick up voltage 0,85 x Un

Direct rotary handle- padlockable- equipped with front cover and handle- fixing without any additionalscrew.

Extended rotary handle- IP 55- supplied complete with shaftand handle.

Delayed undervoltage releasesDUVR

24 V DC

110 - 120 V AC

220 - 240 V AC

380 - 450 V AC

HXA051H

HXA053H

HXA054H

HXA055H

HXA014H

HXA004H

Page 28: MCCB

Accessories for MCCBs and trip-free switches x250

28 Technical modifications reserved

Direct rotary handles padlockable handlemax Ø 6 mm

HXB030H

Extended rotary handles padlockable handlemax Ø 8 mm

HXB031H

Padlocks to mount on MCCBs for handlelockingfor 3 padlockmax Ø 8 mm

HXA039H

Motor operators 24 V DC230 - 240V AC

HXB040HHXB042H

Designation Characteristics Cat. ref.

3P 4P

Interlocking wire type HXB065HHXB065H

HYB010H

Page 29: MCCB

Accessories for MCCBs and trip-free switches x250

29Technical modifications reserved

Designation Characteristics Cat. ref.

3P 4P

Collar terminals 4 aluminium / copper conductors150 mm2 rigid cables120 mm2 flexible cables

HYB002HHYB001H

Extended connections

set of 4 pieces forstraight connections

spreader connections

HYB010H

HYB012H

HYB010H

HYB011H

Interphase barriers

set of 3,height: 97 mm

HYB019HHYB019H

Terminal covers for extended straight connections

for extended spreader connections

for rear connections

for collar terminals

HYB022H

HYB024H

HYB026H

HYB028H

HYB021H

HYB023H

HYB025H

HYB027H

HYB002H

HYB012H

HYB022H

HYB024H

Page 30: MCCB

30 Technical modifications reserved

Accessories for MCCBs and trip-free switches x250

Ring lugs compact lugs 35 mm2 Ø8,5

compact lugs 50 mm2 Ø8,5

compact lugs 70 mm2 Ø8,5

compact lugs 95 mm2 Ø8,5

compact lugs 120 mm2 Ø8,5

compact lugs 150 mm2 Ø8,5

HYA088H

HYA089H

HYA090H

HYA091H

HYB092H

HYB094H

Rear connections HYB032HHYB031Hset of 3 or 4 pieces

Connecting kit HYA035HHYA035H0,75 mm2

set of 3 x 2 wireslength: 1,30m

Designation Characteristics Cat. ref.

3P 4P

HYB031H

Page 31: MCCB

31Technical modifications reserved

MCCBs, trip-free switchesx250

MCCBs

Magnetic and thermal settings

220/240V ACIEC 60 947-2

380/415V ACIEC 60 947-2

HNB Icu 85 kA 40 kA

Ics 40 kA 20 kA

PUSH TO TRIP

Thermal adjustment from 0,63 to 1 x In

Magnetic adjustment from 6 to 13 x In (100 - 200A)from 5 to 11 x In (250A)

PUSH TO TRIP

6

TRIP5

8

1013l i (xIn)

6

l r (xIn)0,63

0,8

1

� �

58

1013

%0

100%

l i (xIn)xIn / Ii

l r (xIn)0,63

0,8

1

6

6

100 - 200A 250A

Ir (x In) � 0,63 - 0,8 - 1 x In

Ii (x In) � 6 - 8 - 10 - 13 x In 5 - 7 - 9 - 11 x In

x In/Ii �0 - 100%

0 - 60%

� � �

Page 32: MCCB

MCCBs, trip-free switchesx250

32 Technical modifications reserved

Tripping curve

MCCB x250

0.01

0.1

1

10

100

1000

100101xIn

Tem

ps d

e dé

clen

chem

ent (

s)

Déclenchement à froid

Déclenchement à chaud(courant nominal)

0.001

10000

Thermal constraint curve (Let-through energy)

MCCB x250

106

104

105

107

108

109

102 103 104 105

I2 t (x

10 A

s)

62

100 A

250 A

Current limiting curve (Let-through pick current)

MCCB x250

0.1

1

10

100

Ip (k

A)

1001010,1Icc (kA)

0,8

0,5

0,3

0,25

0,7

0,9

Hot start (rated current)

Cold start

Trip

pin

g tim

e (s

)

Page 33: MCCB

MCCBs, trip-free switchesx250

33Technical modifications reserved

Dimensions

MCCB x250

PUSH TO TRIP

96

6822

45165

35

35

35

105 (3 P)140 (4 P)

144

126

A(mm)

B(mm)

C(mm)

3P 104,5 35 126

4P 139,5 35 126

A(mm)

B(mm)

C(mm)

3P 105 54,5 64

4P 140 54,5 64

PUSH TO TRIP

CA

B

Terminal covers for extended straight connections

Page 34: MCCB

34 Technical modifications reserved

MCCBs, trip-free switchesx250

Accessories

Terminal cover for extended spreader connections

Terminal cover for rear connections

A(mm)

B(mm)

C(mm)

3P 105 28,5 64

4P 140 28,5 64

Terminal covers for collar terminals

PUSH TO TRIP

CA

B A(mm)

B(mm)

C(mm)

3P 105 5 64

4P 140 5 64

CA

B

A(mm)

B(mm)

C(mm)

3P 147,5 54,5 64

4P 196 54,5 64

PUSH TO TRIP

64A

B

Page 35: MCCB

MCCBs, trip-free switchesx250

35Technical modifications reserved

Connection

Extended straight and spreader connections

29,5

226

Ø 11

128

35 3535

3P

4P

93

29,5

23

11,5

11,5

52,5

226

Ø 11

Ø 8,5

168

50 5050

3P

4P

120

23

48,5

13,5 35

36,5

48,5

PUSH TO TRIP

23Ø 11

PUSH TO TRIP

23

Rear connections

3P

4P

3535 35

144

mm

1111

5716

92

5 12 Nm65 12 Nm6

Page 36: MCCB

MCCBs, trip-free switchesx250

36 Technical modifications reserved

6H 5540.a

20 maxi.

Connection with end lugs

Ø 8

25

25 mmMax.

25 mmmax.

9 mmmax.

min. 35 mm2 max. 150 mm2

min. 35 mm2 max. 185 mm2

5 35 mm2 to 50 mm2 = 25 Nm60 mm2 to 185 mm2 = 25 Nm

Connection by collar

8

Interphase barriers

97

55 55

5 12 Nm6

Page 37: MCCB

37Technical modifications reserved

MCCBs, trip-free switchesx250

Accessories

Rotary handle

PUSH TO TRIPPUSH TO TRIP

12

107,5

45

101,

8

8,5

200

(3 P) 105(4 P) 140

Motor operator

90 90

150

165

Rated operating voltage24V DC ok

230-240V AC ok

Operating current (A)24V DC 18

230-240V AC 4

Starting current (A)24V DC 26

230-240V AC 8

Operating method direct drive

Operating time (s)

ON 0,1

OFF 0,1

RESET 0,1

Operating switch rating 100V, 0.1A, opening voltage 44V, current 4mA

Power supply required 300 VA minimum

Dielectric properties24V DC 1000 V AC

230-240V AC 1500 V AC

Extended rotary handle

PUSH TO TRIPPUSH TO TRIP

48,5

53,745

101,

8

A 116

Page 38: MCCB

38 Technical modifications reserved

MCCBs, trip-free switchesx250

AX SH / UVALAX

UVAL

AX

t e 3 P

4 P

DUVRDelayedundervoltagerelease

Auxiliaries

Auxiliaries for MCCBs and trip-free switches

PUSH TO TRIP

6

TRIP

Mounting combination for auxiliaries and releases

AXAuxiliary contact

ALAlarm contact

SHShunt trip

UVUndervoltage release

Page 39: MCCB

Add-on blocksx250

39Technical modifications reserved

Add-on block operatingEarth leakage current (IΔn) and delay (Δt) setting

63

10,30,1

0,03

I n (A)

10,5

0,30,150,06

Inst.

t (s)

103

10,30,1

0,03

10,5

0,30,150,06

Inst.

I n (A)

t (s)

5

2N L1 L2 L3

N L1 L2 L3

incoming

outgoing

test button

CA

50%

electronic

ON

125A250A

V

1

V

2

Characteristics

Reset button : Signals add-on block tripping and must be acknowledged before switching on the installation.

Test button for differential operating : Allows to check the electrical operating of the MCCB / Add-on block association.

Mechanical test button : Allows to check the mechanical operating of the MCCB / Add-on blockassociation.

LED signaling default current level in the installation:25% (orange) and 50% (red) IΔn; green light to signal correct operating.

Remote tripping and advanced warning (50% IΔn) signaling thanks tothese contacts:

When associated with MCCB, the add-on block provides an earth faultprotection and protects against electrical shocks by direct or indirectcontacts.

The add-on blocks are protected against nuisance tripping caused bytransient voltages. It’s able to detect sinusoidal alternating currents andresidual pulsating direct currents ( A type ). It also avoids miss tripping (HI type - High Immunity).

S (Δ

t)

A (IΔn)

0,03 0,1 0,3 1 3 6

Inst. OK OK OK OK OK OK

0,06 no OK OK OK OK OK

0,15 no OK OK OK OK OK

0,3 no OK OK OK OK OK

0,5 no OK OK OK OK OK

1 no OK OK OK OK OK

Page 40: MCCB

40 Technical modifications reserved

Add-on blocksx250

Add-on block mounting

Dimensions

ON ON

5 m

m

68

45

105

35 35 3593,2

10,5

139,5

270

45

9670

70

104,

512

6

35

6

PUSH TO TRIP

PUSH TO TRIP

PUSH TO TRIP

12 Nm

Page 41: MCCB

41Technical modifications reserved

MCCBs h250

Designation In

Moulded case circuit breakers h250 Mechanical test button,lockable settings,

Cat. ref.

3P 4P

Characteristics

Electronic trip unit LSI:Long delay (thermal equivalent) adjustable: Ir = 0.4 to 1 x Inshort delay (magnetic equivalent) adjustable: 2.5 to 10 x Irtime delay: 0,1 - 0,2 s3P & 4PMechanical test button,sealable settings,

Not for use in TPN and panelboards.

Connection:Directly on copper cable termi-nal, with end lug max. width: 25 mm

Comply with IEC 60 947-2.

MCCBs h250 70kALSI

16-40A

50-125A

100-250A

HEC040H

HEC125H

HEC250H

HEC041H

HEC126H

HEC251H

breaking capacityIcu : 70 kA (400/415 V AC)Ics: 70 kA

adjustable thermalIr = 0.4 to 1 x Inadjustable magnetic2.5 to 10 x Ir

3P, 3 trip units & 4P, 3 trip units

MCCBs h250 50kALSI

16-40A

50-125A

100-250A

HNC040H

HNC125H

HNC250H

HNC041H

HNC126H

HNC251H

breaking capacityIcu : 50 kA (400/415 V AC)Ics: 25 kA

adjustable thermalIr = 0.4 to 1 x Inadjustable magnetic2.5 to 10 x Ir

3P, 3 trip units & 4P, 3 trip units

HEC250H

Page 42: MCCB

Accessories for MCCBs h250

42 Technical modifications reserved

Designation Characteristics

Indication contacts- 1 changeover switch (ON/OFF):indicates the position of theMCCB is “open” or “close”.- 1 changeover alarm contact:indicates MCCB tripping.

Coil connectionConnection capacity:0,75 mm2 flexible or rigid cablesOptional connection cables.The cable capacity of the terminals is 0,5 to 1,25 mm2.

Shunt trips SH

24 V DC48 V DC100 - 120 V AC200 - 240 V AC380 - 450 V AC

HXC001HHXC002HHXC003HHXC004HHXC005H

Undervoltage releasesUV

24 V DC100 - 120 V AC200 - 240 V AC380 - 450 V AC

HXC011HHXC013HHXC014HHXC015H

Cat. ref.

Shunt tripRemotes tripping of MCCBs ortrip-free switches.Operating voltage: 0,7 to 1,1 xUn

Under voltage releaseAllows the tripping of MCCBs ortrip-free switches when voltagelevel drop between 35 and 70%of Un. Pick up voltage 0,85 x Un

Direct rotary handle- padlockable- equipped with front cover and handle- fixing without any additionalscrew.

Extended rotary handle- IP 55- supplied complete with shaftand handle.

Delayed undervoltage releasesDUVR

24 V DC110 - 120 V AC200 - 240 V AC380 - 450 V AC

HXC051HHXC053HHXC054HHXC055H

HXC021H HXC024H

Auxiliary contactsAXAL

1 changeover contact (ON/OFF)250 V AC / 3A125 V DC / 0,4A1 NO + 1 NC

1 changeover alarm contact250 V AC / 3A125 V DC / 0,4A1 NO + 1 NC

Low level contact (ON/OFF)125 V AC1 NO + 1 NC

Low level alarm contact125 V AC1 NO + 1 NC

HXC021H

HXC024H

HXA025H

HXA026H

HXC004H

HXC014H

Page 43: MCCB

43Technical modifications reserved

Accessories for MCCBs h250

Direct rotary handles padlockable handleØ 5 - 8 mm2 max

HXC030H

Extended rotary handles padlockable handleØ 5 - 8 mm2 max

HXC031H

Designation Characteristics Cat. ref.

Padlocks to mount on MCCBs forhandle lockingfor 3 padlockmax Ø 5 mm

HXC039H

Motor operators 24 V DC230-240 V AC

HXC040HHXC042H

Interlocking wire type HXC065H

HXC039H

Page 44: MCCB

Accessories for MCCBs h250

44 Technical modifications reserved

Collar terminals copper HYC004H

Extended connections

spreader connections

straight connections

-

HYC010H

Terminal covers for extended straight connections(LSI only)

for extended straight connections(TM only)

for rear connections

for collar terminals

HYC022H

HYG022H

HYC026H

HYC028H

Rear connections HYC032H

Designation In Cat. ref.

3P 4P

Characteristics

HYC003H

HYC011H

HYC010H

HYC021H

HYG021H

HYC025H

HYC027H

HYC031H

Connecting kit HYA035HHYA035H0,75 mm2

set of 3 x 2 wireslength: 1,30m

HYC004H

HYC011H

HYC22H

HYC031H

Page 45: MCCB

45Technical modifications reserved

MCCBs h250

MCCBs

Magnetic and thermal settings

10

6 8

1

0,630,8

Ir (x In) Ii (x In)

220/240 VAC(kA)

380/415 VAC (kA)

660/690 VAC(kA)

HNCIcu 85 50 7,5

Icu 85 25 7,5

HECIcu 100 70 20

Icu 100 70 15

Thermal adjustment from 0,63 to 1 x In

Magnetic adjustment from 6 to 10 x In (250A)from 6 to 13 x In (160 and 200A)from 6 to 12 x In (32, 63, 100 and 125A)

Characteristics (*) Use

Electronic trip unit setting (LSI)

0,4

0,5

0,8

0,63 1

0,950,9

1

2

4

3

6

7

5

CharacteristicsIr (A)

PICK UP

1 2

xInIR (A)

8

9

L - Long delay - protection against overloads: Ir and tr settings

S - Short delay - protection against short circuits: Isd and tsd set-tings

I - Instantaneous - max. instantaneous threshold (< 10 ms) in case ofshort circuit: 2,5 to 10 x Ir.

3 P 4 P

pos. 1

pos. 2 and 3

pos. 4 and 5

pos. 1, 4 and 7

pos. 2, 5 and 8

pos. 3, 6 and 9

Generator protection

Standard protection

Motor protection

LSI

In A

3P 4P

Long Time Delay Short Time Delay Inst Long Time Delay Short Time Delay Inst Protection

Ir (x In) tr (s) isd (xlr) tsd (s) li (xlr) Ir (x In) tr (s) isd (xlr) tsd (s) li (xlr) Neutral

Ir (x In)

0,4 OK OK

0,5 OK OK

0,63 OK OK

0,8 OK OK

0,9 OK OK

0,95 OK OK

1 OK OK

Characteristics

1 11s at 2 xlr 2,5 0,1 14(max12 x In)

11 s at 2 xlr 2,5 0,1 14(max10 x In)

no

2 21s at 2 xlr 21 s at 2 xlr 5

3 5 7,5 s at 6 xlr 10 0,2

4 5 s at 6 xlr 10 11 s at 2 xlr 2,5 0,1 50%

5 7,5 s at 6 xlr 0,2 21 s at 2 xlr 10

6 7,5 s at 6 xlr 2,5 0,2

7 11 s at 6 xIr 2,5 0,1 100%

8 21 s at 2 xIr 5

9 21 s at 2 xIr 10 0,2

1

2

T

x Ir I

Ir ajustable

Page 46: MCCB

MCCBs h250

46 Technical modifications reserved

MCCB h250 3P LSI

0.01

0.1

1

10

100

1000

10000

Tem

ps d

e dé

clen

chem

ent (

s)

100001000100%Ir

5

4

5

32

1

1, 2, 3, 4

LTD pick-up current

Characteristics

Standard

No. 1

LTD Tr (s) 11

STD Isd

tsd

li

x Ir

(s)

x Ir

200 % x Ir 600 % x Ir

INST

0,1

14 (max 13 x In)

2,5

2

21

0,1

2,5

3

21

0,1

5

4

5

0,1

10

5

7,5

0,2

10

Ir x In 10,950,90,80,630,50,4

Trip

pin

g tim

e (s

)

Page 47: MCCB

MCCBs h250

47Technical modifications reserved

MCCB h250 4P LSI

0.01

0.1

1

10

100

1000

10000

Tem

ps d

e dé

clen

chem

ent (

s)

100001000100

1, 4, 7

2, 5, 83, 6, 9

%Ir

LTD pick-up current

Characteristics No. 987654321

Tr (s) 7,5 s

600% x Ir

21 s11 s7,5 s21 s11 s7,5 s21 s11 sLTD

Isd x Ir

(s)

x Ir

200 % x Ir600% x Ir200 % x Ir600% x Ir200 % x Ir

0,2

STD

INST

Neutral protection

0,10,20,10,20,1

14 (max 13 x In)

no 0,5 1

1052,51052,51052,5

Ir x In 10,950,90,80,630,50,4

Trip

pin

g tim

e (s

)

Page 48: MCCB

48 Technical modifications reserved

MCCBs h250

Thermal constraint curve (Let-through energy)

MCCB h250

102 103 104 105

106

104

105

107

108

109

I2 t (x

10 A

s)

62

Current limiting curve (Let-through peak current)

MCCB h250

0.1

1

10

100

Ip (k

A)

1001010,1Icc (kA)

0,8

0,5

0,3

0,25

0,7

0,9

HNC... upto 50kAHEC... upto 70kA

HNC... upto 50kAHEC... upto 70kA

Page 49: MCCB

MCCBs h250

49Technical modifications reserved

Dimensions

MCCBs

A(mm)

3P 105

4P 140

A(mm)

3P 105

4P 140

Accessories

Terminal covers for extended straight connections

Terminal cover for rear connections

A(mm)

3P 105

4P 140

PUSH TO TRIP

A

35 35

165

144

9645 10

2

125,5

55

89A

275

7,5 96A

170

Page 50: MCCB

MCCBs h250

50 Technical modifications reserved

Connection

Extended straight and spreader connections

2323

29,5 Ø

11

P

120

48,5 48,5

Connection with end lugs

Ø 8

22

Connection by collar

20max.

19 Nm

1 2

min. 35 mm2 max. 120 mm2

min. 35 mm2 max. 120 mm2

5 19 Nm

5 12,7 Nm6

5 12,7 Nm6

Page 51: MCCB

51Technical modifications reserved

MCCBs h250

Rear connections

3P

4P

3535 35

611,8 Nm

Accessories

Direct rotary handle

C

102

C(mm)

3P 105

4P 140

144

1010

5615

91

193

72

97

102

Page 52: MCCB

52 Technical modifications reserved

MCCBs h250

101,

8

(3 P) 105(4 P) 140

Extended rotary handle

155

20590

Motor operator

Rated operating voltage24V DC ok230-240V AC ok

Operating current (A)24V DC 18230-240V AC 4

Starting current (A)24V DC 26230-240V AC 8

Operating method direct drive

Operating time (s)ON 0,1OFF 0,1RESET 0,1

Operating switch rating 100V, 0.1A, opening voltage 44V, current 4mA

Power supply required 300 VA minimum

Dielectric properties24V DC 1000 V AC230-240V AC 1500 V AC

171

70

21,5

358

19,544

Page 53: MCCB

53Technical modifications reserved

MCCBs h250

Auxiliaries

Auxiliaries for MCCBs and trip-free switches

TRIP

6

21

AL SH / UVAX

HXC 024 HHXC 026 H

AL

AX

HXC 021 HHXC 025 H

SH

UV

DUVR

3 P4 P

AXAuxiliary contact

ALAlarm contact

SHShunt trip

UVUndervoltagerelease

DUVRDelayed undervoltagerelease

Mounting combination for auxiliaries and releases

Page 54: MCCB

54 Technical modifications reserved

MCCBs and trip-free switches h400-h630

Designation In

Moulded case circuit breakersh400, h630

Electronic trip unit LSI:- long delay ( thermal equivalent) adjustable: Ir = 0.4 to 1 x In- short delay (magnetic equiva-lent) adjustable: 2.5 to 10 x Ir (400A)2.5 to 8 x Ir (630A)- time delay: 0,1 - 0,2 s3P & 4P (adjustable neutral 0 -50% - 100%).Mechanical test button,lockable settings

Cat. ref.

3P 4P

MCCBs h630 50kALSI

250A

400A

630A

HND250H

HND400H

HND630H

HND251H

HND401H

HND631H

Characteristics

breaking capacityIcu : 50 kA (400/415 V AC)Ics: 50 kA

MCCBs h630 70kALSI

250A

400A

630A

HED250H

HED400H

HED630H

HED251H

HED401H

HED631H

breaking capacityIcu : 70 kA (400/415 V AC)Ics: 50 kA

Trip-free switches 400A

630A

HCD400H

HCD630H

HCD401H

HCD631H

suitable for AC 22A / AC 23A Ue: 415 V ACIcw (0,3s) = 5kA

Connection:Directly on copper cable terminal, with end lug max. width: 30 mm

Comply with IEC 60 947-2.

Trip-free switchesAllows tripping at distance usinga voltmetrical trip unit (optional)

Comply with IEC 60 947-3.AC 23A / DC 22A

Add-on blocksFor h630 (LSI) devicesThese devices are intended to befixed at the bottom of the devices.

Fixed version: 300mA sensitivity and instantaneoustrippingAdjustable version: sensitivityfrom 30mA to 6A, tripping from instantaneous to 1s delay.Test button for differential functioning check.Mechanical test button.LED or remote signal for trippingor advance warning (25-50% l n).Type A (for fault component DCpulsating current) and HI (reinforced immunity against unexpected tripping).

Comply with IEC 60 947-2.

Add-on blocks(only for h630)

400A

500A

-

-

HBD401H

HBD631H

adjustable sensitivity l n:0,03 - 0,1 - 0,3 - 1 - 3 - 6Aadjustable trippinginstantaneoustime delay: 0,06s - 0,15s - 0,3s - 0,5s - 1s

HBD401H

HND630H

Page 55: MCCB

HXC021H HXC024H

55Technical modifications reserved

Designation Characteristics

Indication contacts- 1 changeover switch (ON/OFF):indicates the position of theMCCB is “open” or “close”.- 1 changeover alarm contact:indicates MCCB tripping.

Coil connectionConnection capacity:0,75mm2 flexible or rigid cablesOptional connection cables.The cable capacity of the terminals is 0,5 to 1,25 mm2.

Auxiliary contactsAXAL

1 changeover contact250 V AC / 3A125 V DC / 0,4A1 NO + 1 NC

1 changeover alarm contact 250 V AC / 3A125 V DC / 0,4A1 NO + 1 NC

low level contact (ON/OFF)125 V AC1 NO + 1 NC

low level alarm contact125 V AC1 NO + 1 NC

HXC021H

HXC024H

HXC025H

HXC026H

Shunt tripsSH

24 V DC48 V DC100 - 120 V AC200 - 240 V AC380 - 450 V AC

HXC001HHXC002HHXC003HHXC004HHXC005H

Undervoltage releasesUV

24 V DC100 - 120 V AC200 - 240 V AC380 - 450 V AC

HXC011HHXC013HHXC014HHXC015H

Cat. ref.

Shunt tripRemotes tripping of MCCBs or trip-free switches.Operating voltage: 0,7 to 1,1 xUn

Under voltage releaseAllows the tripping of MCCBs or trip-free switches when voltagelevel drop between 35 and 70%of Un. Pick up voltage 0,85 x Un

Direct rotary handle- padlockable- equipped with front cover and handle- fixing without any additionalscrew.

Extended rotary handle- IP 55- supplied complete with shaftand handle.

Delayed undervoltage releasesDUVR

24 V DC100 - 120 V AC200 - 240 V AC380 - 450 V AC

HXD051HHXD053HHXD054HHXD055H

Characteristics Cat. ref.3P 4PHXC051HHXC053HHXC054HHXC055H

Accessories for MCCBs and trip-free switches h400-h630

HXC004H

HXC014H

Page 56: MCCB

Accessories for MCCBs and trip-free switches h400-h630

56 Technical modifications reserved

Direct rotary handle padlockable handlemax Ø 6 mm

HXD030H

Extended rotary handle padlockable handlemax Ø 8 mm

HXD031H

Padlock to mount on MCCBs forhandle lockingfor 3 padlockØ 5 - 8 mm2 max

HXD039H

Designation Characteristics Cat. ref.

HXD030H

HXD039H

Interlocking wire type HXD065HHXD065H

Motor operators 24-48 V DC100-240 V AC

HXD040HHXD042H

HXD040HHXD042H

HXD042H

Page 57: MCCB

Accessories for MCCBs and trip-free switches h400-h630

57Technical modifications reserved

Designation Characteristics Cat. ref.

3P 4P

Collar terminals set of 3 or 4 terminals forcopper conductors 240mm2

set of 3 or 4 terminals foraluminium conductors 1 x 35 - 240 mm2

set of 3 or 4 terminals formultiple aluminium conductors 2 x 35 - 240 mm2

HYD004H

HYD006H

HYD008H

HYD003H

HYD005H

HYD007H

Extended connections set of 4 pieces forstraight connections

spreader connections

HYD010HHYD013H

HYD012HHYD015H

HYD010HHYD013H

HYD011HHYD014H

Terminal covers for extended straight connectionsfor extended spreader connectionsfor rear connectionsfor collar terminals

HYD022HHYD024HHYD026HHYD028H

HYD021HHYD023HHYD025HHYD027H

In

250 - 400A

250 - 400 -630A

250 - 400 -630A

250 - 400A630A

250 - 400A630A

HYD003H

HYD006H

HYD008H

HYD015H

HYD022H

HYD010H

Page 58: MCCB

58 Technical modifications reserved

Accessories for MCCBs and trip-free switches h400-h630

Ring lugs compact lugs 120 mm2 Ø10

compact lugs 150 mm2 Ø10,5

compact lugs 185 mm2 Ø10,5

compact lugs 185 mm2 Ø12,8suitable with spreader

compact lugs 240 mm2 Ø12,8suitable with spreader

HYD093H

HYD095H

HYD096H

HYD097H

HYD098H

Designation Characteristics Cat. ref.

Rear connections HYD032HHYD034H

HYD031HHYD033H

250 - 400A630A

Connecting kit HYA035HHYA035H0,75 mm2

set of 3 x 2 wireslength: 1,30m

HYD033H

Designation Characteristics Cat. ref.

3P 4P

In

Page 59: MCCB

59Technical modifications reserved

MCCBs, trip-free switchesh400 - h630

MCCBs

Settings

Magnetic and thermal settings

TM 400 A

126

8 10

10,63

0,8

Ir (x In) Ii (x In)

B

A

220/240 V AC(kA)

380/415 V AC (kA)

660/690 V AC (kA)

H400/H630HND

Icu 85 50 20

Ics 85 50 15

H630HED

Icu 100 70 20

Ics 85 50 15

H630HCD

Icm _ 9 _

Icw _ 5 kA-0,3 s _

Thermal adjustment from 0,63 to 1 x In

Magnetic adjustment from 6 to 12 x In

Page 60: MCCB

MCCBs, trip-free switchesh400 - h630

60 Technical modifications reserved

4

2.5 5 10 14

0.1S0.2S

5,6,7

76

5

31,2

4

3

12

T

x Ir I

Ir ajustable

Electronic trip unit setting (LSI)

LSI250/400/630 A 1 B2

3

1

0,4

0,5

0,8

0,63 0,95

0,90,85

1

2

4

3

6

7

5

CharacteristicsIr (A)

TEST INPICK UP

ON 1xIR

OFF 0,5xIR

NP

Neutral settings:

� Long delay current Ir setting

� Other curve characteristics setting (tr, Isd, tsd)

� Neutral protection against overloads setting

L - Long delay - protection against overloads: Ir and trsettings

S - Short delay - protection against short circuits: Isdand tsd settings

I - Instantaneous - max. instantaneous threshold (< 10ms) in case of short circuit: 2,5 to 10 x Ir (250 - 400A)and 2,5 to 8 x Ir (630A).

(*) Characteristic 1 : use for generators protection.Characteristic 2 to 4 - standard protection : options allow coordination optimisation with other products. Characteristic 5 to 7 - motor protection: use positions according to motor starting characteristics.

LSI

In A

250 A / 400 A 630 A

Long Time Delay Short TimeDelay

Inst Long Time Delay Short Time Delay

Inst

Ir (x In) tr (s) isd (xlr) tsd (s) li (xlr) Ir (x In) tr (s) isd (xlr) tsd (s) li (xlr)

�Ir (x In)

0,4 OK OK

0,5 OK OK

0,63 OK OK

0,8 OK OK

0,85 _ OK

0,9 OK OK

0,95 OK OK

1 OK OK

�Characteristics

1 11s at 2 xlr 2,5 0,1 14(max13 xIn)

11s at 2 xlr 2,5 0,1 14(max10 xIn)

2 21s at 2 xlr 21s at 2 xlr

3 5 5

4 5 s at 6 xlr 10 5 s at 6 xlr 8

5 10 s at 6 xlr 0,2 10 s at 6 xlr 0,2

6 19 s at 6 xlr 16 s at 6 xlr

7 29 s at 6 xlr _ _ _

��Neutral

protection

0%50%100%

Page 61: MCCB

MCCBs, trip-free switchesh400 - h630

61Technical modifications reserved

0.01

0.1

1

10

100

1000

10000

Tem

ps d

e dé

clen

chem

ent (

s)

100001000100%Ir

3

1, 2, 3, 4

5, 6

1 24

5 67

Electronic trip unit setting (LSI)

MCCB h630 LSI (250A and 400A)

IR (A)

LTD Pick-up current IR xIn 0,4 0,5 0,63 0,8 0,9 0,95 1

Characteristics No. 1 2 3 4 5 6 7

Standard LTD tR (s) 11 21 21 5 10 19 29

200% x I R 600% x I R

STD Isd xIR 2,5 5 10

tsd (s) 0,1 0,2

INST Ii xIR 14 (max : 13 x In)

Optional N IN xIn 0 - 0,5 - 1

tN (s) tN=tR

Trip

pin

g tim

e (s

)

Tripping curve

MCCB h630 LSI (250A and 400A)

Page 62: MCCB

62 Technical modifications reserved

MCCBs, trip-free switchesh400 - h630

Electronic trip unit setting (LSI)

MCCB h630 LSI (630A electronic)

IR (A)

LTD Pick-up current IR xIn 0,4 0,5 0,63 0,8 0,85 0,9 0,95 1

Characteristics No. 1 2 3 4 5 6

Standard LTD tR (s) 11 21 21 5 10 16

200% x I R 600% x I R

STD Isd xIR 2,5 5 8

tsd (s) 0,1 0,2

INST Ii xIR 14 (max : 13 x In)

Optional N IN xIn 0 - 0,5 - 1

tN (s) tN=tR

0.01

0.1

1

10

100

1000

10000

Tem

ps d

e dé

clen

chem

ent (

s)

100001000100

3

1, 2, 3, 4

5, 6

1 2 4 56

%Ir

Trip

pin

g tim

e (s

)

Tripping curve

MCCB h630 LSI (630A electronic)

Page 63: MCCB

MCCBs, trip-free switchesh400 - h630

63Technical modifications reserved

Thermal constraint curve (Let-through energy)

MCCB h400 TM (400A)

I2 t (x

A s

)2

107

106

105

104

103

108

104103102101 105

HHD... upto 25kAHND... upto 50kA

MCCB h630LSI (250A and 400A)

I2 t (x

10 A

s)

62

0,1

1

101

102

101 10210,1

I2 t (x

10 A

s)

62

0,1

1

101

102

101 10210,1

MCCB h630 LSI (630A)

HND... upto 50kAHED... upto 70kA

HND... upto 50kAHED... upto 70kA

(kA)

(kA) (kA)

Page 64: MCCB

64 Technical modifications reserved

MCCBs, trip-free switchesh400 - h630

Current limiting curve (Let-through peak current)

MCCB h630 LSI (250A and 400A)MCCB h400 TM

0.1

1

10

100

Ip (k

A)

1001010,1Icc (kA)

0,8

0,5

0,3

0,25

0,7

0,9

0.1

1

10

100

Ip (k

A)

1001010,1Icc (kA)

0,8

0,5

0,3

0,25

0,7

0,9

MCCB h630 LSI (630A)

HND... upto 50kAHED... upto 70kA

HHD... upto 25kAHND... upto 50kAHED... upto 70kA

Page 65: MCCB

MCCBs, trip-free switchesh400 - h630

65Technical modifications reserved

Dimensions

MCCBs

145

97

90260

45 45

A

228

A(mm)

B(mm)

C(mm)

3P 140 45 214

4P 185 45 214

Terminal covers for extended straight connections

B48

0

A DC

A(mm)

B(mm)

C(mm)

D(mm)

3P 140 85 97 94,5

4P 185 85 97 94,5

Terminal covers for extended spreader connectionsB

CA

A(mm)

B(mm)

C(mm)

3P 180 110 97

4P 240 114 98

Terminal covers for rear connections and collar terminal

CA

B' B

D

A(mm)

B(mm)

B’(mm)

C(mm)

D(mm)

3P 140 3 4,5 97 93

4P 185 3 4,5 97 93

Page 66: MCCB

MCCBs, trip-free switchesh400 - h630

66 Technical modifications reserved

Connection

Cable connection (h400 TM 250 - 400A, h630 LSI 250 - 400A)

13

7,0-9,5 Nm

25 maxi.

Extended straight and spreader connections

3P

60

349

Ø14

148

4P

30

30

60 60

60 60

208

4P

163

30

30 45 Ø 14

30

4545 45

228

1515

3P

4P 55 (250-400A)

45 (630A)

15

115 (250-400 A)95 (630 A)

5 22,5 Nm8

7,0 - 9,5 Nm

max. 240 mm2

5 25 Nm8

Rear connections

Page 67: MCCB

67Technical modifications reserved

MCCBs, trip-free switchesh400 - h630

Connection with end lugs

M 10 30max.

12max.

1 2

5 22,5 Nm8

Accessories

Direct rotary handle

140 200103

241,

5

140

127

180,5

x+46,5

27

19,5x44

125

Extended rotary handle

244

139,5

160

Motor operator

Rated operating voltage

24-48V DC ok

100-240V AC ok

Operating current (A)

24-48V DC 4,3

100-240V AC 0,9

Starting current (A)

24-48V DC 9,8

100-240V AC 3,8

Operating method spring charging

Operating time (s)

ON 0,1

OFF 1,5

RESET 1,5

Operating switch rating

100V, 0.1A, opening voltage 48V, current 1mA

Power supply required

300 VA minimum

Dielectric properties

24-48V DC 1000 V AC

100-240V AC 1500 V AC

220

123

Page 68: MCCB

MCCBs, trip-free switchesh400 - h630

68 Technical modifications reserved

Auxiliaries

Auxiliaries for MCCBs and free tripping switches

6

TRIP

AL SH / UVAX

t e

X

L

SH

UV

DUVR

6

AXAuxiliary contact

ALAlarm contact

SHShunt trip

UVUndervoltagerelease

DUVRDelayedundervoltagerelease

Mounting combination for auxiliaries and releases

Page 69: MCCB

69Technical modifications reserved

Add-on block h630

63

10,30,1

0,03

I n (A)

10,5

0,30,150,06

Inst.

t (s)

103

10,30,1

0,03

10,5

0,30,150,06

Inst.

I n (A)

t (s)

5

2N L1 L2 L3

N L1 L2 L3

incoming

outgoing

test button

CA

50%

electronic

ON

125A250A

V

1

V

2

Add-on block operatingEarth leakage current (IΔn) and delay (Δt) setting

S (Δ

t)

A (IΔn)

0,03 0,1 0,3 1 3 6

Inst. OK OK OK OK OK OK

0,06 no OK OK OK OK OK

0,15 no OK OK OK OK OK

0,3 no OK OK OK OK OK

0,5 no OK OK OK OK OK

1 no OK OK OK OK OK

Characteristics

Reset button :

Signals add-on block tripping and must be acknowledged before switching on the installation.

Test button for differential functioning : Allows to check the electrical operating of the MCCB / Add-on block association.

Mechanical test button : Allows to check the mechanical operating of the MCCB / Add-on blockassociation.

LED signaling default current level in the installation:25% (orange) and 50% (red) IΔn; green light to signal correct operating.

Remote tripping and advanced warning (50% IΔn) signaling thanks tothese contacts:

When associated with MCCB, the add-on block provides an earth faultprotection and protects against electrical shocks by direct or indirectcontacts.

The add-on blocks are protected against nuisance tripping caused bytransient voltages. It’s able to detect sinusoidal alternating currents andresidual pulsating direct currents ( A type ). It also avoids miss tripping (HI type - High Immunity).

Page 70: MCCB

Add-on block h630

70 Technical modifications reserved

5 m

m

ON ON

Add-on block mounting

Dimensions

97

45

45 45 45120,5

16

185

119,

5

8 22,5 Nm

� �

Association / Compatibility

250 - 400A 630A x 0,8

HBD401H400A

HBD631H500A(Ie: 630A x 0,8)

Page 71: MCCB

MCCBs and trip-free switches h1000

71Technical modifications reserved

Designation In

Moulded case circuit breakersh1000Electronic trip unit LSI:- long delay (thermal equivalent) adjustable:Ir= 0,4 to 1 x In- short delay (magnetic equivalent) adjustable: 2,5 to 10 x Ir (630-800A) and 2,5 to 8 x Ir (1000A)- time delay: 0,1-0,2 s

Cat. ref.

3P 4P

MCCBs h1000 50kALSI

800A

1000A

HNE800H

HNE970H

HNE801H

HNE971H

MCCBs h1000 70kALSI

800A

1000A

HEE800H

HEE970H

HEE801H

HEE971H

Designation

breaking capacityIcu : 50 kA (400/415 V AC)Ics: 50 kA

breaking capacityIcu : 70 kA (400/415 V AC)Ics: 50 kA

Trip-free switches 800A

1000A

HCE800H

HCE970H

HCE801H

HCE971H

suitable for AC 22A / AC 23AUe : 415 V ACIcw (0,3 s) = 10 kA

3P & 4P (adjustable neutral 0 - 50% - 100%).Mechanical test button,lockable settings.

Connection:Directly on copper cable terminal, with end lug max. width: 50 mm

Comply with IEC 60 947-2.

Trip-free switchesAllows tripping at distance usinga voltmetrical trip unit (optional)

Comply with IEC 60 947-3.AC 23A / DC 22A

HNE970H

Page 72: MCCB

Accessories for MCCBs and trip-free switches h1000

72 Technical modifications reserved

Designation Characteristics

Indication contacts- 1 changeover switch (ON/OFF):indicates the position of theMCCB is “open” or “close”.- 1 changeover alarm contact:indicates MCCB tripping.

Coil connectionConnection capacity:0,75mm2 flexible or rigid cablesOptional connection cables.

Cat. ref.

The cable capacity of the terminals is 0,5 to 1,25 mm2.

Shunt tripRemotes tripping of MCCBs or trip-free switches.Operating voltage: 0,7 to 1,1 x Un

Under voltage releaseAllows the tripping of MCCBs or

trip-free switches when voltagelevel drop between 35 and 70%of Un. Pick up voltage 0,85 x Un

Shunt trips SH

24 V DC48 V DC100 - 120 V AC200 - 240 V AC380 - 450 V AC

HXC001HHXC002HHXC003HHXC004HHXC005H

Undervoltage releasesUV

24 V DC100 - 120 V AC200 - 240 V AC380 - 450 V AC

HXC011HHXC013HHXC014HHXC015H

HXC021H HXC024H

Auxiliary contactsAXAL

1 changeover contact (ON/OFF)250 V AC / 3A125 V DC / 0,4A1 NO + 1 NC

1 changeover alarm contact250 V AC / 3A125 V DC / 0,4A1 NO + 1 NC

Low level contact (ON/OFF)125 V AC1 NO + 1 NC

Low level alarm contact125 V AC1 NO + 1 NC

HXC021H

HXC024H

HXA025H

HXA026H

HXC004H

HXC014H

Page 73: MCCB

Accessories for MCCBs and trip-free switches h1000

73Technical modifications reserved

Designation Characteristics

Direct rotary handle- padlockable- equipped with front cover and handle- fixing without any additionalscrew.

Cat. ref.

3P 4P

Terminal covers for extended connections

for rear connections

HYE022H

HYE026H

HYE021H

HYE025H

In

Extended rotary handle- IP 55- supplied complete with shaftand handle.

Delayed undervoltage releasesDUVR

24 V DC

110 - 120 V AC

220 - 240 V AC

380 - 415 V AC

HXE051H

HXE053H

HXE054H

HXE055H

HXE051H

HXE053H

HXE054H

HXE055H

Collar terminals set of 3 or 4 terminals forconductors 4 x 35 - 240 mm2

HYE008HHYE007H630-800A

Connecting kits HYA035HHYA035H0,75 mm2

set of 3 x 2 wireslength: 1,30m

Rear connections HYE032H

HYE034H

HYE031H

HYE033H

630-800A

1000A

HYE031H

Page 74: MCCB

Accessories for MCCBs and trip-free switches h1000

74 Technical modifications reserved

Interlocking wire type HXE065H

Direct rotary handles padlockable handle HXE030H

Extended rotary handles padlockable handle HXE031H

Padlocks to mount on MCCB forhandle lockingfor 3 padlockmax Ø 8 mm

HXD039H

Motor operators 24 - 48V DC

100 - 240V AC

HXE040H

HXE042H

Designation Characteristics Cat. ref.

HXD039H

Page 75: MCCB

MCCBs, trip-free switchesh1000

75Technical modifications reserved

MCCBs

Electronic trip unit settings (LSI)

1

0,4

0,5

0,8

0,63 0,95

0,90,85

1

2

4

3

6

7

5

CharacteristicsIr (A)

TEST INPICK UP

ON 1xIR

OFF 0,5xIR

NP

1 2

3

220/240 V AC(kA)

380/415 V AC (kA)

660/690 V AC (kA)

HNEIcu 85 (630-800A), 75 (1000A) 50 20

Ics 85 (630-800A), 75 (1000A) 50 20

HEEIcu 100 70 20

Ics 100 (630-800A), 75 (1000A) 50 20

HCEIcm _ 17 _

Icw _ 10 kA-0,3 s _

L - Long delay - protection against overloads: Ir and tr settings

S - Short delay - protection against short circuits: Isd and tsd set-tings

I - Instantaneous - max. instantaneous threshold (< 10 ms) in case ofshort circuit: 2,5 to 10 x Ir (630-800A) and 2,5 to 8 x Ir (1000A).

1

2

4

5,6,7

76

5

31,2

4

3

12

T

x Ir I

Ir ajustable

0,2S0,1S

2,5 5 10 14

LSI

In A

630-800 A 1000 A

Long Time Delay Short TimeDelay

Inst Long Time Delay Short TimeDelay

Inst

Ir (x In) tr (s) isd (xlr) tsd (s) li (xlr) Ir (x In) tr (s) isd (xlr) tsd (s) li (xlr)

Ir (x In)

0,4 OK OK

0,5 OK OK

0,63 OK OK

0,8 OK OK

0,9 OK OK

0,95 OK OK

1 OK OK

Characteristics*

1 11s at 2 xlr 2,5 0,1 14(max12 xIn)

11s at 2 xlr 2,5 0,1 14(max10 xIn)

2 21s at 2 xlr 21s at 2 xlr

3 5 5

4 5 s at 6 xlr 10 5 s at 6 xlr 8

5 10 s at 6 xlr 0,2 10 s at 6 xlr 0,2

6 19 s at 6 xlr 16 s at 6 xlr

7 29 s at 6 xlr _ _ _

��

Neutral protection

0%50%100%

(*) Characteristic 1 : use for generators protection.Characteristic 2 to 4 - standard protection : options allow coordination optimisation with other products. Characteristic 5 to 7 - motor protection: use positions according to motor starting characteristics.

Page 76: MCCB

MCCBs, trip-free switchesh1000

76 Technical modifications reserved

Tripping curve

MCCB h1000 LSI (630-800A)

Electronic trip unit setting (LSI)

MCCBs 630-800A electronic

IR (A)

LTD Pick-up current IR xIn 0,4 0,5 0,63 0,8 0,9 0,95 1

Characteristics No. 1 2 3 4 5 6 7

Standard LTD tR (s) 11 21 21 5 10 19 29

200% x I R 600% x I R

STD Isd xIR 2,5 5 10

tsd (s) 0,1 0,2

INST Ii xIR 14 (max : 12 x In)

Optional NP IN xIR 0,5 or 1 or NON (IN x 105% NT, IN x 120% T)

tN (s) IN=tR

Page 77: MCCB

MCCBs, trip-free switchesh1000

77Technical modifications reserved

Tripping curve

MCCB h1000 LSI (1000A)

Electronic trip unit setting (LSI)MCCBs 1000A electronic

IR (A)

LTD Pick-up current IR xIn 0,4 0,5 0,63 0,8 0,9 0,95 1

Characteristics No. 1 2 3 4 5 6

Standard LTD tR (s) 11 21 21 5 10 16

200% x I R 600% x I R

STD Isd xIR 2,5 5 8

tsd (s) 0,1 0,2

INST Ii xIR 14 (max : 10 x In)

Optional NP IN xIn 0,8

tN (s) IN=tR

Page 78: MCCB

MCCBs, trip-free switchesh1000

78 Technical modifications reserved

Thermal constraint curve (Let-through energy)

MCCB h1000

Current limiting curve (Let-through peak current)

MCCB h1000

Page 79: MCCB

MCCBs, trip-free switchesh1000

79Technical modifications reserved

Dimensions

MCCBs

145

99,535 10

90433

40 70

273

403

331

B

A

243

Terminal covers for extended straight connections

A(mm)

B(mm)

C(mm)

3P 215 130 99,5

4P 285 130 99,5

A(mm)

B(mm)

D(mm)

3P 210 180 243

4P 280 250 243

A C

534

B

Page 80: MCCB

80 Technical modifications reserved

MCCBs, trip-free switchesh1000

Connection

Extended straight connections

40

36 Ø13

1

Direct cable connection on terminalCopper with conductor max. width: 50 mm

2

CA

B A(mm)

B(mm)

C(mm)

3P 210 14 101

4P 280 18 99

Terminal covers for rear connections

5 65,7 Nm19

Page 81: MCCB

MCCBs, trip-free switchesh1000

81Technical modifications reserved

Connection with end lugs

1 2

Rear connections

90°

58

122

121258

12

243

288

(100

0 A

)28

5 (8

00 A

)

20 36

Ø 13

601010

6010

1000 A

800 A

1000A:vertical only.

630-800A:vertical or horizontalposition.

Page 82: MCCB

MCCBs, trip-free switchesh1000

82 Technical modifications reserved

Accessories

Direct rotary handle

120

127

115

120

127

Extended rotary handle

115140

160

Motor operator

Rated operating voltage

24-48V DC ok

100-240VAC ok

Operating method spring charging

Power supply required 300 VA minimum

Dielectric properties

24-48V DC 1000 V AC

100-240VAC 1500 V AC

115 213

113,5

200

103

115

125

180,5

92

27

322

19,5

45

Page 83: MCCB

83Technical modifications reserved

MCCBs, trip-free switchesh1000

Auxiliaries

Auxiliaries for MCCBs and free tripping switches

TRIP

6

1

2

Mounting combination for auxiliaries and releases

AL SH / UVAX

HXC 024 HHXC 026 H

L

X

HXC 021 HHXC 025 H

SH

UV

DUVR

3 P4 P

AXAuxiliary contact

AL Alarm contact

SHShunt trip

UVUndervoltagerelease

DUVRDelayedundervoltagerelease

Page 84: MCCB

MCCBs and trip-free switches h1600

84 Technical modifications reserved

Designation In

Moulded case circuit breakers h1600, selection and protectionElectronic trip unit LSI- Long delay (thermal equivalent) adjustable: Ir = 0,4 to 1 x In- short delay (magnetic equiva-lent) adjustable: 2,5 to 10 x Ir- time delay: 0,1-0,2 s3 pole, 3 trip units,

Cat. ref.

3P 4P

MCCBs h1600 50kALSI

1250A

1600A

HNF980H

HNF990H

HNF981H

HNF991H

MCCBs h1600 70kALSI

1250A

1600A

HEF980H

HEF990H

HEF981H

HEF991H

Designation

breaking capacityIcu : 50 kA (400/415 V AC)Ics: 50 kA

breaking capacityIcu : 70 kA (400/415 V AC)Ics: 50 kA

Trip-free switches 1250A

1600A

HCF980H

HCF990H

HCF981H

HCF991H

suitable for AC 22A / AC 23AUe : 415 V ACIcw (0,3 s) = 20 kA

4 pole, 4 trip units,adjustable neutral 0 - 50% -100%

Mechanical test button,lockable settings.

Connection:Directly on copper cable termi-nal, with end lug max. width: 60 mm

Comply with IEC 60 947-2.

Trip-free switchesAllows tripping at distance usinga voltmetrical trip unit (optional)

Comply with IEC 60 947-3.AC 23A / DC 22A

HNF990H

Page 85: MCCB

85Technical modifications reserved

Accessories for MCCBs and trip-free switches h1600

Designation Characteristics

Indication contacts- 1 changeover switch (ON/OFF):indicates the position of theMCCB is “open” or “close”.- 1 changeover alarm contact:indicates MCCB tripping.

Coil connectionConnection capacity:0,75mm2 flexible or rigid cablesOptional connection cables.The cable capacity of the terminals is 0,5 to 1,25 mm2.

Cat. ref.

Shunt tripRemotes tripping of MCCBs or trip-free switches.Operating voltage: 0,7 to 1,1 x Un

Under voltage releaseAllows the tripping of MCCBs or trip-free switches when voltagelevel drop between 35 and 70%of Un. Pick up voltage 0,85 x Un

Direct rotary handle- padlockable- equipped with front cover and handle- fixing without any additionalscrew.

Extended rotary handle- IP 55- supplied complete with shaftand handle.

Rear connection: included

Shunt trips SH

24 V DC48 V DC100 - 120 V AC200 - 240 V AC380 - 450 V AC

HXC001HHXC002HHXC003HHXC004HHXC005H

Undervoltage releasesUV

24 V DC100 - 120 V AC200 - 240 V AC380 - 450 V AC

HXC011HHXC013HHXC014HHXC015H

HXC021H HXC024H

Auxiliary contactsAXAL

1 changeover contact (ON/OFF)250 V AC / 3A125 V DC / 0,4A1 NO + 1 NC

1 changeover alarm contact250 V AC / 3A125 V DC / 0,4A1 NO + 1 NC

Low level contact (ON/OFF)125 V AC1 NO + 1 NC

Low level alarm contact125 V AC1 NO + 1 NC

HXC021H

HXC024H

HXA025H

HXA026H

HXC004H

HXC014H

Page 86: MCCB

Headline 1Headline 2

86 Technical modifications reserved

Undervoltage releasesUV

24 V DC110 - 120 V AC220 - 240 V AC380 - 415 V AC

HXE011HHXE013HHXE014HHXE015H

Direct rotary handle padlockable handle, max Ø 8 mm HXF030H

Extended rotary handle padlockable handle, max Ø 8 mm HXF031H

Padlock to mount on MCCB forhandle lockingfor 3 padlockmax Ø 8 mm

HXF039H

Motor operators 24 V DC200 - 230 V AC

HXF040HHXF042H

Page 87: MCCB

Headline 1Headline 2

87Technical modifications reserved

Interphase barriers 3/4 P HYF019H

Delayed undervoltage releasesDUVR

24 V DC110 - 120 V AC220 - 240 V AC380 - 415 V AC

HXF051HHXF053HHXF054HHXF055H

Connection kit HYA035H0,75 mm2

set of 3 x 2 wireslength: 1,30m

Page 88: MCCB

MCCBs, trip-free switchesh1600

88 Technical modifications reserved

MCCBs

Electronic trip unit settings (LSI)

220/240 V AC(kA)

380/415 V AC (kA)

660/690 V AC (kA)

HNFIcu 100 50 25

Ics 75 50 25

HEFIcu 100 70 45

Ics 75 50 34

HCFIcm 45 kA

Icw 20 kA-0,3 s

L - Long delay - protection against overloads: Ir and tr settings

S - Short delay - protection against short circuits: Isd and tsd settings

I - Instantaneous - max. instantaneous threshold (< 10 ms) in case of shortcircuit: 2,5 to 10 x Ir.

Ir(A)�

Im�

N

LSI 0,4 - 1In

2,5 -10 Ir

0%50%100 %

LSI

In A

1250 - 1600 A

Long Time Delay Short Time Delay Inst

Ir (x In) tr (s) isd (xlr) tsd (s) li (xlr)

Ir (x In)

0,4 OK

0,5 OK

0,63 OK

0,8 OK

0,9 OK

0,95 OK

1 OK

Characteristics*

1 11s at 2 xlr 2,5 0,1 14 (max 12 xIn)2 21s at 2 xlr

3 5

4 5 s at 6 xlr 10

5 10 s at 6 xlr 0,2

6 19 s at 6 xlr

7 29 s at 6 xlr

��

Neutral protection

0%50%100%

(*) Characteristic 1 : use for generators protection.Characteristic 2 to 4 - standard protection : options allow coordination optimisation with other products. Characteristic 5 to 7 - motor protection: use positions according to motor starting characteristics.

7

0,4

0,5

0,8

0,63 1

0,950,9

1

2

4

3

65

CharacteristicsIr (A)

TEST INPICK UPOFF

ON

Page 89: MCCB

MCCBs, trip-free switchesh1600

89Technical modifications reserved

Tripping curve

MCCB h1600 LSI

2

1

3

4

5

6

7

5,6,7

1,2,3,4

time

80 90 100

125

200

250

500

600

700

800

900

1000

1500

2500

3000

4000

5000

6000

2000

7000

8000

150

[%]

4

2

15040

30

20

108654

3

2

15040

30

20

3

108

654

3

2

10.8

0.60.50.4

0.3

0.2

0.10.08

0.060.050.04

0.03

0.02

0.01

0.005

hour

min

ute

seco

nd

IR

Electronic trip unit setting (LSI)

MCCBs 1250A and 1600A electronic

IR (A)

LTD Pick-up current IR xIn 0,4 0,5 0,63 0,8 0,9 0,95 1

Characteristics No. 1 2 3 4 5 6 7

Standard LTD tR (s) 11 21 21 5 10 19 29

200% x I R 600% x I R

STD Isd xIR 2,5 5 10

tsd (s) 0,1 0,2

INST Ii xIR 14 (max : 12 x In)

Optional NP IN xIR 0,5 or 1 or NON (IN x 105% NT, IN x 120% T)

tN (s) IN=tR

Page 90: MCCB

MCCBs, trip-free switchesh1600

90 Technical modifications reserved

Thermal constraint curve (Let-through energy)

MCCB h1600

I2 t (x

10 A

s)

62

109

1010

104 105

108

107

103102

Current limiting curve (Let-through peak current)MCCB h1600

Max. Let-through peak current 3�TYPE h1600

1000

100

10

1

0.1

Max

. Let

-thr

ough

pea

k cu

rren

t (k

A)

001011 1000

Prospective short-circuit current in RMS sym. (kA)

HNE…up to 50kAHEE…up to 70kA

HNF... upto 50kAHEF... upto 70kA

Page 91: MCCB

MCCBs, trip-free switchesh1600

91Technical modifications reserved

Dimensions

MCCBs

191

140

95570

44,5 46 2070

370

541

476

11

BA

A(mm)

B(mm)

3P 210 185

4P 280 255

Connection

Connection with end lugs

65 Nm

1 2

5 65,7 Nm19

Page 92: MCCB

MCCBs, trip-free switchesh1600

92 Technical modifications reserved

115140

165

268

136

257 45

125

115140

322

19,5

27

165

210

173,

5

Motor operator

Rated operating voltage

24V DC ok

200-230V AC ok

Operating current (A) 200-230V AC 1

Starting current (A) 200-230V AC 3,2

Operating method spring charging

Operating time (s)

ON 0,06

OFF 3

RESET 3

Power supply required 300 VA minimum

Dielectric properties24V DC 500 V AC

200-230V AC 1500 V AC

260,5

130

Accessories

Direct rotary handle Extended rotary handle

Page 93: MCCB

93Technical modifications reserved

MCCBs, trip-free switchesh1600

Auxiliaries

Auxiliaries for MCCBs and free tripping switches

TRIP

1

Mounting combination for auxiliaries and releases

AL

SH / UV

AX

HXC 024 HHXC 026 H

AL

AX

HXC 021 HHXC 025 H

SH

UV

DUVR

3 P4 P

AXAuxiliary contact

ALAlarm contact

SHShunt trip

UVUndervoltagerelease

DUVRDelayedundervoltagerelease

Page 94: MCCB

94 Technical modifications reserved

Cascading according to CEI 60947-2MCCBs x160, x250, h250, h630, h1000, h1600

Upstream

x160 TM x250 TM h250 TM

HDA HHA HNA HHB HNB HHG HNG

18 kA 25 kA 40 kA 25 kA 40 kA 25 kA 50 kA

Dow

nstr

eam

x160 TM

HDA 18 kA - 25 kA 40 kA 25 kA 40 kA 25 kA 50 kA

HHA 25 kA - 30 kA 40 kA 30 kA 40 kA 25 kA 50 kA

HNA 40 kA - - 40 kA - 40 kA - 50 kA

x250 TMHHB 25 kA - - - 25 kA 40 kA 25 kA 50 kA

HNB 40 kA - - - - 40 kA - 50 kA

h250 TM

HHG 25 kA - - - - 40 kA 25 kA 50 kA

HNG 50 kA - - - - - - 50 kA

HEG 65 kA - - - - - - -

h250 LSIHNC 50 kA - - - - - - -

HEC 70 kA - - - - - - -

h400 TMHHD 25 kA - - - - - - -

HND 50 kA - - - - - - -

h630 LSIHND 50 kA - - - - - - -

HED 70 kA - - - - - - -

h1000 LSIHNE 50 kA - - - - - - -

HEE 70 kA - - - - - - -

h1600 LSIHNF 50 kA - - - - - - -

HEF 70 kA - - - - - - -

Upstream

x160 TM x250 TM h250 TM

HDA HHA HNA HHB HNB HHG HNG

25 kA 35 kA 85 kA 35 kA 85 kA 35 kA 85 kA

Dow

nstr

eam

x160 TM

HDA 25 kA - 35 kA 85 kA 35 kA 85 kA 35 kA 85 kA

HHA 35 kA - 50 kA 85 kA 50 kA 85 kA 35 kA 85 kA

HNA 85 kA - - 85 kA - 85 kA - 85 kA

x250 TMHHB 35 kA - - - 35 kA 85 kA 35 kA 85 kA

HNB 85 kA - - - - 85 kA - 85 kA

h250 TM

HHG 35 kA - - - - 85 kA 35 kA 85 kA

HNG 85 kA - - - - - - 85 kA

HEG 85 kA - - - - - - -

h250 LSIHNC 85 kA - - - - - - -

HEC 100 kA - - - - - - -

h400 TMHHD 35 kA - - - - - - -

HND 85 kA - - - - - - -

h630 LSIHND 85 kA - - - - - - -

HED 100 kA - - - - - - -

h1000 LSIHNE 85 kA - - - - - - -

HEE 100 kA - - - - - - -

h1600 LSIHNF 85 kA - - - - - - -

HEF 100 kA - - - - - - -

Cascading values in kA according to CEI 947-2 Network : 3 phases + neutral 380V - 415V AC

Cascading values in kA according to CEI 947-2 Network : 3 phases + neutral 220V - 240V AC

Page 95: MCCB

95Technical modifications reserved

h250 LSI h400 TM h630 LSI h1000 LSI h1600 LSI

HEG HNC HEC HHD HND HND HED HNE HEE HNF HEF

65 kA 50 kA 70 kA 25 kA 50 kA 50 kA 70 kA 50 kA 70 kA 50 kA 70 kA

65 kA 50 kA 40 kA 25 kA 30 kA 30 kA 40 kA 30 kA 40 kA 30 kA 40 kA

65 kA 50 kA 70 kA 25 kA 50 kA 50 kA 50 kA 50 kA 50 kA 50 kA 50 kA

65 kA 50 kA 70 kA 25 kA 50 kA 50 kA 70 kA 50 kA 70 kA 50 kA 50 kA

65 kA 50 kA 70 kA 25 kA 50 kA 50 kA 50 kA 50 kA 50 kA 50 kA 50 kA

65 kA 50 kA 70 kA 25 kA 50 kA 50 kA 70 kA 50 kA 70 kA 50 kA 50 kA

65 kA 50 kA 70 kA 25 kA 50 kA 50 kA 50 kA 50 kA 50 kA 25 kA 25 kA

65 kA 50 kA 70 kA - 50 kA 50 kA 70 kA 50 kA 70 kA 50 kA 70 kA

65 kA - 70 kA - - - 70 kA - 70 kA - 70 kA

- 50 kA 70 kA - 50 kA 50 kA 70 kA 50 kA 70 kA 50 kA 70 kA

- - 70 kA - - - 70 kA - 70 kA - 70 kA

- - 70 kA 25 kA 50 kA 50 kA 50 kA 50 kA 70 kA 25 kA 25 kA

- - - - 50 kA 50 kA 70 kA 50 kA 70 kA 50 kA 70 kA

- - - - - 50 kA 70 kA 50 kA 70 kA 50 kA 70 kA

- - - - - - 70 kA - 70 kA - 70 kA

- - - - - - - 50 kA 70 kA 50 kA 70 kA

- - - - - - - - 70 kA - 70 kA

- - - - - - - - - 50 kA 70 kA

- - - - - - - - - - 70 kA

h250 LSI h400 TM h630 LSI h1000 LSI h1600 LSI

HEG HNC HEC HHD HND HND HED HNE HEE HNF HEF

85 kA 85 kA 100 kA 35 kA 85 kA 85 kA 100 kA 85 kA 100 kA 85 kA 100 kA

85 kA 50 kA 85 kA 35 kA 85 kA 50 kA 85 kA 50 kA 85 kA 50 kA 85 kA

85 kA 85 kA 100 kA 35 kA 85 kA 85 kA 85 kA 85 kA 85 kA 85 kA 85 kA

85 kA 85 kA 100 kA 35 kA 85 kA 85 kA 100 kA 85 kA 100 kA 85 kA 100 kA

85 kA 85 kA 100 kA 35 kA 85 kA 85 kA 85 kA 85 kA 85 kA 85 kA 85 kA

85 kA 85 kA 100 kA 35 kA 85 kA 85 kA 100 kA 85 kA 100 kA 85 kA 100 kA

85 kA 85 kA 100 kA 35 kA 85 kA 85 kA 85 kA 85 kA 85 kA 85 kA 85 kA

85 kA 85 kA 100 kA - 85 kA 85 kA 100 kA 85 kA 100 kA 85 kA 100 kA

85 kA 85 kA 100 kA - - - 100 kA - 100 kA - 100 kA

- 85 kA 100 kA - 85 kA 85 kA 100 kA 85 kA 100 kA 85 kA 100 kA

- - 100 kA - - - 100 kA - 100 kA - 100 kA

- - 100 kA 35 kA 85 kA 85 kA 100 kA 85 kA 100 kA 85 kA 100 kA

- - - - 85 kA 85 kA 100 kA 85 kA 100 kA 85 kA 100 kA

- - - - - 85 kA 100 kA 85 kA 100 kA 85 kA 100 kA

- - - - - - 100 kA - 100 kA - 100 kA

- - - - - - - 85 kA 100 kA 85 kA 100 kA

- - - - - - - - 100 kA - 100 kA

- - - - - - - - - 85 kA 100 kA

- - - - - - - - - - 100 kA

Page 96: MCCB

96 Technical modifications reserved

Cascading MCCBs / MCBs

Rangex160 TM x250 TM h250 TM

HDA HHA HNA HHB HNB HHG

Breaking capacity IEC 60898 / 61009-1 - - - - - -

Breaking capacity IEC 60947-2 25 KA 35 kA 85 kA 35 kA 85 kA 35 kA

Curve - - - - - -

Ax8xx 4,5 kA 6 kA B, C 10 kA 10 kA 10 kA 10 kA 10 kA 7,5 kA

Ax9xx 6 kA 10 kA B, C 15 kA 15 kA 15 kA 15 kA 15 kA 12,5 kA

AC1xx, AD1xx, AE1xx, AF1xx, ACx1xx,ADx1xx, AEx1xx

6 kA - B, C 25 kA 30 kA 50 kA 30 kA 40 kA 30 kA

10 kA - B, C - 35 kA 85 kA 35 kA 50 kA 35 kA

MV, MW 3 kA 10 kA B, C 20 kA 20 kA 30 kA 20 kA 20 kA 20 kA

MU, MT, MV 6 kA 20 kA B, C 25 kA 30 kA 50 kA 30 kA 40 kA 30 kA

NB, NC, ND 10 kA 30 kA B, C, D - 35 kA 85 kA 35 kA 50 kA 35 kA

MHN, MJN 4,5 kA 6 kA B, C 10 kA 10 kA 10 kA 10 kA 10 kA 7,5 kA

MLN 6 kA 7,5 kA B, C 15 kA 15 kA 15 kA 10 kA 10 kA 10 kA

MBN, MCN 6 kA - B, C 25 kA 30 kA 50 kA 30 kA 40 kA 30 kA

MB, MC, NGN 6 kA 20 kA B, C, D 25 kA 30 kA 50 kA 30 kA 40 kA 30 kA

NBN, NCN, NDN 10 kA 30 kA B, C, D - 35 kA 85 kA 35 kA 50 kA 35 kA

NQN, NRN, NSN

- 50 kA B, C, D - - 85 kA - 85 kA -

- 40 kA B, C, D - - 85 kA - 70 kA -

- 30 kA B, C, D - 35 kA 85 kA 35 kA 50 kA 35 kA

MMN 2xx, MMN 3xx - 50 kA magn. - - 85 kA - 85 kA -

MMN 2xx, MMN 3xx - 40 kA magn. - - 85 kA - 70 kA -

HLE, HLF, HLS - 20 kA B, C 25 kA 30 kA 50 kA 30 kA 40 kA 30 kA

HMB, HMC, HMD - 30 kA B, C, D - 35 kA 85 kA 35 kA 60 kA 35 kA

HMJ, HMK - 60 kA B, C - - 85 kA - 85 kA -

HMX - 100 kA C - - - - - -

Rangex160 TM x250 TM h250 TM

HDA HHA HNA HHB HNB HHG

Breaking capacity IEC 60898 - - - - - -

Breaking capacity IEC 60947-2 18 KA 25 kA 40 kA 25 kA 40 kA 25 kA

Curve - - - - - -

MV, MW 3 kA 4,5 kA B, C 10 kA 10 kA 15 kA 10 kA 10 kA 10 kA

MU, MT, MV 6 kA 10 kA B, C 18 kA 20 kA 30 kA 20 kA 20 kA 20 kA

NB, NC, ND 10 kA 15 kA B, C, D 18 kA 25 kA 40 kA 25 kA 30 kA 25 kA

MVN, MWN 3 kA - B, C 10 kA 10 kA 15 kA 10 kA 10 kA 10 kA

MBN, MCN 6 kA - B, C 18 kA 20 kA 30 kA 20 kA 20 kA 20 kA

MB, MC, NGN 6 kA 10 kA B, C, D 18 kA 25 kA 30 kA 20 kA 25 kA 25 kA

NBN, NCN, NDN 10 kA 15 kA B, C, D 18 kA 25 kA 40 kA 25 kA 30 kA 25 kA

NQN, NRN, NSN

- 25 kA B, C, D - 25 kA 40 kA 25 kA 40 kA 25 kA

- 20 kA B, C, D - 25 kA 40 kA 25 kA 35 kA 25 kA

- 15 kA B, C, D 18 kA 25 kA 40 kA 25 kA 30 kA 25 kA

MMN 2xx, MMN 3xx - 25 kA magn. - 25 kA 40 kA 25 kA 40 kA 25 kA

MMN 2xx, MMN 3xx - 30 kA magn. - 25 kA 40 kA 25 kA 35 kA 25 kA

HLE, HLF, HLS 10 kA 10 kA B, C 18 kA 20 kA 30 kA 20 kA 25 kA 20 kA

HMB, HMC, HMD 15 kA 15 kA B, C, D 18 kA 25 kA 40 kA 25 kA 30 kA 25 kA

HMJ, HMK - 30 kA B, C - - 40 kA - 40 kA -

HMX - 50 kA C - - - - - -

Cascading MCCBs / MCBs 1PP+N / 2PP 230V - 240 V IEC 947-2

Cascading MCCBs / MCBs 1PP 230V - 240 V 2PP / 3PP / 3PP+N / 4PP 400 - 415 V IEC 947-2

Page 97: MCCB

97Technical modifications reserved

h250 LSI h400 LSI h630 LSI h1000 LSI h1600 LSI

HNG HEG HNC HEC HHD HND HND HED HNE HEE HNF HEF

- - - - - - - - - - - -

85 kA 85 kA 85 kA 100 kA 35 kA 85 kA 85 kA 100 kA 85 kA 100 kA 100 kA 100 kA

- - - - - - - - - - - -

7,5 kA 7,5 kA 10 kA 7,5 kA 10 kA 10 kA 6 kA 6 kA 6 kA 6 kA 6 kA 6 kA

12,5 kA 12,5 kA 15 kA 12,5 kA 15 kA 15 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA

40 kA 40 kA 40 kA 40 kA 25 kA 30 kA 30 kA 30 kA 20 kA 20 kA 20 kA 20 kA

50 kA 50 kA 50 kA 50 kA 35 kA 40 kA 40 kA 40 kA 30 kA 30 kA 30 kA 30 kA

20 kA 20 kA 20 kA 20 kA 15 kA 15 kA 15 kA 15 kA 10 kA 10 kA 10 kA 10 kA

40 kA 40 kA 40 kA 40 kA 25 kA 30 kA 30 kA 30 kA 20 kA 20 kA 20 kA 20 kA

50 kA 50 kA 50 kA 50 kA 35 kA 40 kA 40 kA 40 kA 30 kA 30 kA 30 kA 30 kA

7,5 kA 7,5 kA 10 kA 7,5 kA 10 kA 10 kA 6 kA 6 kA 6 kA 6 kA 6 kA 6 kA

10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 7,5 kA 7,5 kA 7,5 kA 7,5 kA 7,5 kA 7,5 kA

40 kA 40 kA 40 kA 40 kA 25 kA 30 kA 30 kA 30 kA 20 kA 20 kA 20 kA 20 kA

40 kA 40 kA 40 kA 40 kA 25 kA 30 kA 30 kA 30 kA 20 kA 20 kA 20 kA 20 kA

50 kA 50 kA 50 kA 50 kA 35 kA 40 kA 40 kA 40 kA 30 kA 30 kA 30 kA 30 kA

85 kA 85 kA 85 kA 85 kA - 65 kA 65 kA 65 kA 50 kA 50 kA 50 kA 50 kA

70 kA 70 kA 70 kA 70 kA - 50 kA 50 kA 50 kA 40 kA 40 kA 40 kA 40 kA

50 kA 50 kA 50 kA 50 kA 35 kA 40 kA 40 kA 40 kA 30 kA 30 kA 30 kA 30 kA

85 kA 85 kA 85 kA 85 kA - 65 kA 65 kA 65 kA 50 kA 50 kA 50 kA 50 kA

70 kA 70 kA 70 kA 70 kA - 50 kA 50 kA 50 kA 40 kA 40 kA 40 kA 40 kA

40 kA 40 kA 40 kA 40 kA 25 kA 30 kA 30 kA 30 kA 30 kA 30 kA 20 kA 20 kA

60 kA 60 kA 60 kA 60 kA 35 kA 40 kA 40 kA 40 kA 40 kA 40 kA 30 kA 30 kA

85 kA 85 kA 85 kA 85 kA - 85 kA 85 kA 85 kA 85 kA 85 kA 60 kA 60 kA

- - - - - - - 100 kA - 100 kA 100 kA 100 kA

h250 LSI h400 LSI h630 LSI h1000 LSI h1600 LSI

HNG HEG HNC HEC HHD HND HND HED HNE HEE HNF HEF

- - - - - - - - - - - -

50 kA 65 kA 50 kA 70 kA 25 kA 50 kA 50 kA 70 kA 50 kA 70 kA 50 kA 70 kA

- - - - - - - - - - - -

10 kA 10 kA 10 kA 10 kA 6 kA 6 kA 6 kA 6 kA 4,5 kA 4,5 kA 4,5 kA 4,5 kA

20 kA 20 kA 20 kA 20 kA 15 kA 15 kA 15 kA 15 kA 10 kA 10 kA 10 kA 10 kA

30 kA 30 kA 30 kA 30 kA 20 kA 20 kA 20 kA 20 kA 20 kA 20 kA 15 kA 15 kA

10 kA 10 kA 10 kA 10 kA 6 kA 6 kA 6 kA 6 kA 4,5 kA 4,5 kA 4,5 kA 4,5 kA

20 kA 20 kA 20 kA 20 kA 15 kA 15 kA 15 kA 15 kA 10 kA 10 kA 10 kA 10 kA

20 kA 20 kA 25 kA 20 kA 20 kA 20 kA 20 kA 20 kA 10 kA 10 kA 10 kA 10 kA

30 kA 30 kA 30 kA 30 kA 20 kA 20 kA 20 kA 20 kA 20 kA 20 kA 15 kA 15 kA

40 kA 40 kA 40 kA 40 kA 25 kA 40 kA 40 kA 40 kA 30 kA 30 kA 25 kA 25 kA

35 kA 35 kA 35 kA 35 kA 25 kA 25 kA 25 kA 25 kA 25 kA 25 kA 20 kA 20 kA

30 kA 30 kA 30 kA 30 kA 20 kA 20 kA 20 kA 20 kA 20 kA 20 kA 15 kA 15 kA

40 kA 40 kA 40 kA 40 kA 25 kA 40 kA 40 kA 40 kA 30 kA 30 kA 25 kA 25 kA

35 kA 35 kA 35 kA 35 kA 25 kA 25 kA 25 kA 25 kA 25 kA 25 kA 20 kA 20 kA

25 kA 25 kA 25 kA 25 kA 15 kA 15 kA 15 kA 15 kA 15 kA 15 kA 10 kA 10 kA

30 kA 30 kA 30 kA 30 kA 20 kA 20 kA 20 kA 20 kA 20 kA 20 kA 15 kA 15 kA

50 kA 50 kA 50 kA 50 kA - 50 kA 50 kA 50 kA 50 kA 50 kA 35 kA 35 kA

50 kA 50 kA 50 kA 50 kA - 50 kA 50 kA 50 kA 50 kA 50 kA 50 kA 50 kA

Page 98: MCCB

98 Technical modifications reserved

Selectivity chart

Limits (kA)

x160 TM18/25/40kA

x250 TM25/40kA

h250 TM25/50/65 kA

In 16A 20A 25A 32A 40A 50A 63A 80A 100A 125A 160A 100A 125A 160A 200A 250A 32A

MH

N

B c

urve

6A 1,6 1,7 1,8 2,1 2,6 3,4 4,6 T T T T T T T T T 2,9

10A 1,4 1,5 1,6 1,9 2,3 2,7 3,2 3,8 4,5 5,5 T 5,3 T T T T 2,5

16A - - 1,5 1,7 2 2,3 2,7 3,1 3,6 4,1 5,2 4,3 5,3 T T T 2,2

20A - - - 1,7 2 2,3 2,7 3,1 3,6 4,1 5,2 4,3 5,3 T T T 2,2

25A - - - - 1,9 2,1 2,3 2,6 2,8 3,2 4 3,3 4,1 5,4 T T 2

32A - - - - - 2,1 2,3 2,6 2,8 3,2 4 3,3 4,1 5,4 T T -

40A - - - - - - 1,6 1,9 2,1 2,4 3,1 2,5 3,1 4,2 T T -

MJN

, MLN

C c

urve

1A 1,5 1,6 1,8 2,3 2,9 4 T T T T T T T T T T 3

2A 1,5 1,6 1,8 2,3 2,9 4 T T T T T T T T T T 3

6A 1,3 1,4 1,6 1,9 2,3 2,9 3,9 5,5 T T T T T T T T 2,5

10A 1,1 1,2 1,4 1,7 2 2,4 2,8 3,4 4 4,9 T 4,6 T T T T 2,3

16A - - 1,2 1,5 1,8 2 2,3 2,7 3 3,6 4,6 3,6 4,6 T T T 1,9

20A - - - 1,5 1,8 2 2,3 2,7 3 3,6 4,6 3,6 4,6 T T T 1,9

25A - - - - 1,6 1,8 2 2,2 2,4 2,9 3,6 2,9 3,6 4,8 T T 1,8

32A - - - - - 1,8 2 2,2 2,4 2,9 3,6 2,9 3,6 4,8 T T -

40A - - - - - - 1,4 1,7 1,9 2,2 2,8 2,2 2,8 3,7 5,5 T -

MB

, MU

, MV

B c

urve

6A 1,4 1,5 1,6 1,9 2,3 3 4 5,5 6,7 8,6 T 7,8 T T T T 2,5

10A 1,2 1,3 1,4 1,7 2 2,4 2,8 3,4 4 4,9 6,4 4,7 6,2 8,6 T T 2,2

13A - 1,2 1,3 1,5 1,8 2,1 2,4 2,8 3,2 3,7 4,6 3,8 4,7 6,2 9,9 T 2

16A - - 1,3 0 1,8 2,1 2,4 2,8 3,2 3,7 4,6 3,8 4,7 6,2 9,9 T 2

20A - - - 0 1,8 2,1 2,4 2,8 3,2 3,7 4,6 3,8 4,7 6,2 9,9 T 2

25A - - - - 1,7 1,9 2,1 2,3 2,5 2,9 3,6 3 3,7 4,9 7,4 T 1,8

32A - - - - - 1,9 2,1 2,3 2,5 2,9 3,6 3 3,7 4,9 7,4 T -

40A - - - - - - 1,6 1,7 1,9 2,2 2,8 2,3 2,8 3,8 5,9 9,9 -

50A - - - - - - - 1,4 1,5 1,8 2,3 1,8 2,3 3,2 4,9 8,6 -

63A - - - - - - - - 1,5 1,5 1,8 1,4 1,8 2,4 4,2 7,7 -

MC

, MN

, MW

, MT

C c

urve

0,5A 1,3 1,4 1,6 2 2,5 3,5 5,6 8,8 T T T T T T T T 2,6

1A 1,3 1,4 1,6 2 2,5 3,5 5,6 8,8 T T T T T T T T 2,6

2A 1,3 1,4 1,6 2 2,5 3,5 5,6 8,8 T T T T T T T T 2,6

3A 1,1 1,2 1,4 1,7 2 2,5 3,4 4,8 5,8 6,8 8,5 6,8 8,6 T T T 2,2

4A 1,1 1,2 1,4 1,7 2 2,5 3,4 4,8 5,8 6,8 8,5 6,8 8,6 T T T 2,2

6A 1,1 1,2 1,4 1,7 2 2,5 3,4 4,8 5,8 6,8 8,5 6,8 8,6 T T T 2,2

10A - 1,1 1,25 1,5 1,8 2,1 2,5 3 3,5 4,3 5,6 4,1 5,4 7,6 T T 2

13A - 1 1,1 1,3 1,6 1,8 2,1 2,4 2,7 3,2 4,1 3,2 4,1 5,6 8,3 T 1,7

16A - - 1,1 1,3 1,6 1,8 2,1 2,4 2,7 3,2 4,1 3,2 4,1 5,6 8,3 T 1,7

20A - - - 1,3 1,6 1,8 2,1 2,4 2,7 3,2 4,1 3,2 4,1 5,6 8,3 T 1,7

25A - - - - 1,4 1,6 1,8 2 2,2 2,6 3,2 2,6 3,2 4,3 6,3 9,9 1,6

32A - - - - - 1,6 1,8 2 2,2 2,6 3,2 2,6 3,2 4,3 6,3 9,9 -

40A - - - - - - 1,3 1,5 1,7 2 2,5 2 2,5 3,4 5 8,5 -

50A - - - - - - - 1,1 1,5 1,5 2 1,5 1,9 2,7 4,2 7,3 -

63A - - - - - - - - 1,5 1,5 1,6 1,3 1,6 2,2 3,8 6,7 -

MB

N

B c

urve

6A 1,1 1,2 1,3 1,5 1,8 2,4 3,2 4,4 5,4 T T T T T T T 2

10A 0,95 1,05 1,2 1,4 1,6 1,9 2,2 2,7 3,2 3,9 5,1 3,8 5 T T T 1,6

13A - 0,95 1,05 1,2 1,4 1,7 1,9 2,2 2,6 3 3,7 3 3,8 5 T T 1,6

16A - - 1,05 1,2 1,4 1,7 1,9 2,2 2,6 3 3,7 3 3,8 5 T T 1,6

20A - - - 1,2 1,4 1,7 1,9 2,2 2,6 3 3,7 3 3,8 5 T T 1,6

25A - - - - 1,3 1,5 1,7 1,8 2 2,3 2,9 2,4 3 3,9 5,9 T 1,4

32A - - - - - 1,5 1,7 1,8 2 2,3 2,9 2,4 3 3,9 5,9 T -

40A - - - - - - 1,3 1,4 1,5 1,8 2,2 1,8 2,2 3 4,7 T -

50A - - - - - - - 1,1 1,5 1,5 1,8 1,4 1,8 2,6 3,9 T -

63A - - - - - - - - 1,5 1,5 1,6 1,3 1,625 2,1 3,4 T -

MC

N

C c

urve

0,5A 1,05 1,1 1,3 1,6 2 2,8 4,5 T T T T T T T T T 2,1

1A 1,05 1,1 1,3 1,6 2 2,8 4,5 T T T T T T T T T 2,1

2A 1,05 1,1 1,3 1,6 2 2,8 4,5 T T T T T T T T T 2,1

3A 0,9 1 1,1 1,4 1,6 2 2,7 3,8 4,6 5,4 T 5,4 T T T T 1,8

4A 0,9 1 1,1 1,4 1,6 2 2,7 3,8 4,6 5,4 T 5,4 T T T T 1,8

6A 0,9 1 1,1 1,4 1,6 2 2,7 3,8 4,6 5,4 T 5,4 T T T T 1,8

10A 0,8 0,9 1 1,2 1,4 1,7 2 2,4 2,8 3,4 4,5 3,3 4,3 T T T 1,6

13A - 0,8 0,9 1,05 1,3 1,5 1,7 1,9 2,1 2,6 3,3 2,6 3,3 4,5 T T 1,4

16A - - 0,9 1,05 1,3 1,5 1,7 1,9 2,1 2,6 3,3 2,6 3,3 4,5 T T 1,4

20A - - - 1,05 1,3 1,5 1,7 1,9 2,1 2,6 3,3 2,6 3,3 4,5 T T 1,4

25A - - - - 1,1 1,3 1,4 1,6 1,8 2,1 2,6 2,1 2,6 3,4 5 T 1,3

32A - - - - - 1,3 1,4 1,6 1,8 2,1 2,6 2,1 2,6 3,4 5 T -

40A - - - - - - 1,05 1,2 1,5 1,6 2 1,6 2 2,7 4 T -

50A - - - - - - - 1 1,5 1,5 1,7 1,3 1,625 2,2 3,4 5,8 -

63A - - - - - - - - 1,5 1,5 1,6 1,3 1,625 2,1 3 5,4 -

T = total selectivity. Each underlined value must be read as T when it is over the breaking capacity range of MCBs or RCBOs. All values are given with MCCB at the maximum setting.

Page 99: MCCB

99Technical modifications reserved

h250 LSI50/70 kA

h400 TM25/50 kA

h630 LSI50/70 kA

h1000 LSI50/70 kA

h1600 LSI50/70 kA

63A 100A 125A 160A 200A 250A 40A 125A 250A 250A 400A 250A 400A 630A 630A 800A 1000A 1250A 1600A

5,9 T T T T T 3,1 T T T T T T T T T T T T

4,1 5,9 T T T T 2,6 T T T T T T T T T T T T

3,5 4,7 5,8 T T T 2,4 5,3 T T T T T T T T T T T

3,5 4,7 5,8 T T T 2,4 5,3 T T T T T T T T T T T

3 3,7 4,6 6 T T 2,2 4,1 T T T T T T T T T T T

3 3,7 4,6 6 T T - 4,1 T T T T T T T T T T T

2,3 2,8 3,4 4,6 T T - 3,1 T T T T T T T T T T T

T T T T T T 3,3 T T T T T T T T T T T T

T T T T T T 3,3 T T T T T T T T T T T T

5 T T T T T 2,6 T T T T T T T T T T T T

3,6 5,2 T T T T 2,4 T T T T T T T T T T T T

2,9 3,9 5 T T T 2,1 4,6 T T T T T T T T T T T

2,9 3,9 5 T T T 2,1 4,6 T T T T T T T T T T T

2,4 3,2 4 5,3 T T 1,9 3,6 T T T T T T T T T T T

2,4 3,2 4 5,3 T T - 3,6 T T T T T T T T T T T

2,3 2,4 3,1 4,2 T T - 2,8 T T T T T T T T T T T

5,2 8,7 T T T T 2,7 T T T T T T T T T T T T

3,6 5,2 6,9 9,6 T T 2,3 6,2 T T T T T T T T T T T

3,1 4,2 5,2 6,9 T T 2,1 4,7 T T T T T T T T T T T

3,1 4,2 5,2 6,9 T T 2,1 4,7 T T T T T T T T T T T

3,1 4,2 5,2 6,9 T T 2,1 4,7 T T T T T T T T T T T

2,7 3,3 4,1 5,4 8,2 T 2 3,7 T T T T T T T T T T T

2,7 3,3 4,1 5,4 8,2 T - 3,7 T T T T T T T T T T T

2,1 2,5 3,1 4,2 6,5 T - 2,8 9,9 T T T T T T T T T T

1,7 2 2,5 3,5 5,4 9,6 - 2,3 8,6 T T T T T T T T T T

- 1,6 2 2,7 4,7 8,5 - 1,8 7,7 9,4 T T T T T T T T T

7,3 T T T T T 2,9 T T T T T T T T T T T T

7,3 T T T T T 2,9 T T T T T T T T T T T T

7,3 T T T T T 2,9 T T T T T T T T T T T T

4,4 7,5 9,5 T T T 2,3 8,6 T T T T T T T T T T T

4,4 7,5 9,5 T T T 2,3 8,6 T T T T T T T T T T T

4,4 7,5 9,5 T T T 2,3 8,6 T T T T T T T T T T T

3,2 4,6 6 8,4 T T 2,1 5,4 T T T T T T T T T T T

2,6 3,5 4,5 6,2 9,2 T 1,9 4,1 T T T T T T T T T T T

2,6 3,5 4,5 6,2 9,2 T 1,9 4,1 T T T T T T T T T T T

2,6 3,5 4,5 6,2 9,2 T 1,9 4,1 T T T T T T T T T T T

2,2 2,9 3,6 4,8 7 T 1,7 3,2 9,9 T T T T T T T T T T

2,2 2,9 3,6 4,8 7 T - 3,2 9,9 T T T T T T T T T T

2,1 2,2 2,8 3,8 5,6 9,4 - 2,5 8,5 T T T T T T T T T T

1,3 1,7 2,1 3 4,7 8,1 - 1,9 7,3 8,9 T T T T T T T T T

- 1,3 1,6 2,4 4,2 7,4 - 1,75 6,7 8,2 T T T T T T T T T

4,2 T T T T T 2,2 T T T T T T T T T T T T

2,9 4,2 5,5 T T T 1,8 5 T T T T T T T T T T T

2,5 3,4 4,2 5,5 T T 1,7 3,8 T T T T T T T T T T T

2,5 3,4 4,2 5,5 T T 1,7 3,8 T T T T T T T T T T T

2,5 3,4 4,2 5,5 T T 1,7 3,8 T T T T T T T T T T T

2,2 2,6 3,3 4,3 T T 1,6 3 T T T T T T T T T T T

2,2 2,6 3,3 4,3 T T - 3 T T T T T T T T T T T

1,7 2, 2,5 3,4 5,2 T - 2,2 T T T T T T T T T T T

1,4 1,6 2 2,8 4,3 T - 1,8 T T T T T T T T T T T

- 1,3 1,625 2,2 3,8 T - 1,75 T T T T T T T T T T T

5,8 T T T T T 2,3 T T T T T T T T T T T T

5,8 T T T T T 2,3 T T T T T T T T T T T T

5,8 T T T T T 2,3 T T T T T T T T T T T T

3,5 T T T T T 1,8 T T T T T T T T T T T T

3,5 T T T T T 1,8 T T T T T T T T T T T T

3,5 T T T T T 1,8 T T T T T T T T T T T T

2,6 3,7 4,8 T T T 1,7 4,3 T T T T T T T T T T T

2,1 2,8 3,6 5 T T 1,5 3,3 T T T T T T T T T T T

2,1 2,8 3,6 5 T T 1,5 3,3 T T T T T T T T T T T

2,1 2,8 3,6 5 T T 1,5 3,3 T T T T T T T T T T T

1,8 2,3 2,9 3,8 5,6 T 1,4 2,6 T T T T T T T T T T T

1,8 2,3 2,9 3,8 5,6 T - 2,6 T T T T T T T T T T T

1,7 1,8 2,2 3 4,5 T - 2 T T T T T T T T T T T

1 1,4 1,7 2,4 3,8 T - 1,75 5,8 T T T T T T T T T T

- 1,3 1,625 2,1 3,4 5,9 - 1,75 5,4 T T T T T T T T T T

Page 100: MCCB

100 Technical modifications reserved

Selectivity chart

Limits (kA)

x160 TM18/25/40kA

x250 TM25/40kA

h250 TM25/50/65 kA

In 16A 20A 25A 32A 40A 50A 63A 80A 100A 125A 160A 100A 125A 160A 200A 250A 32A

NQ

N, N

BN

B c

urve

6A 1,4 1,5 1,6 1,9 2,3 3 4 5,5 6,7 8,6 12 7,8 11 16 T T 2,5

10A 1,2 1,3 1,4 1,7 2 2,4 2,8 3,4 4 4,9 6,4 4,7 6,2 8,6 14 23 2,2

13A - 1,2 1,3 1,5 1,8 2,1 2,4 2,8 3,2 3,7 4,6 3,8 4,7 6,2 9,9 17 2

16A - - 1,3 1,5 1,8 2,1 2,4 2,8 3,2 3,7 4,6 3,8 4,7 6,2 9,9 17 2

20A - - - 1,5 1,8 2,1 2,4 2,8 3,2 3,7 4,6 3,8 4,7 6,2 9,9 17 2

25A - -- - - 1,7 1,9 2,1 2,3 2,5 2,9 3,6 3 3,7 4,9 7,4 13 1,8

32A - -- - - - 1,9 2,1 2,3 2,5 2,9 3,6 3 3,7 4,9 7,4 13 -

40A - - -- - - - 1,6 1,7 1,9 2,2 2,8 2,3 2,8 3,8 5,9 9,9 -

50A - - - - - - - 1,4 1,5 1,8 2,3 1,8 2,3 3,2 5,9 8,6 -

63A - - - - - - - - 1,5 1,5 1,8 1,4 1,8 2,4 4,2 7,7 -

NR

N, N

CN

C c

urve

0,5A 1,3 1,4 1,6 2 2,5 3,5 5,6 8,8 12 16 23 14 20 T T T 2,6

1A 1,3 1,4 1,6 2 2,5 3,5 5,6 8,8 12 16 23 14 20 T T T 2,6

2A 1,3 1,4 1,6 2 2,5 3,5 5,6 8,8 12 16 23 14 20 T T T 2,6

3A 1,1 1,2 1,4 1,7 2 2,5 3,4 4,8 5,8 6,8 8,5 6,8 8,6 12 17 T 2,2

4A 1,1 1,2 1,4 1,7 2 2,5 3,4 4,8 5,8 6,8 8,5 6,8 8,6 12 17 T 2,2

6A 1,1 1,2 1,4 1,7 2 2,5 3,4 4,8 5,8 6,8 8,5 6,8 8,6 12 17 T 2,2

10A 1 1,1 1,25 1,5 1,8 2,1 2,5 3 3,5 4,3 5,6 4,1 5,4 7,6 12 20 2

13A - 1 1,1 1,3 1,6 1,8 2,1 2,4 2,7 3,2 4,1 3,2 4,1 5,6 8,3 14 1,7

16A - - 1,1 1,3 1,6 1,8 2,1 2,4 2,7 3,2 4,1 3,2 4,1 5,6 8,3 14 1,7

20A - - - 1,3 1,6 1,8 2,1 2,4 2,7 3,2 4,1 3,2 4,1 5,6 8,3 14 1,7

25A - - - - 1,4 1,6 1,8 2 2,2 2,6 3,2 2,6 3,2 4,3 6,3 11 1,6

32A - - - - - 1,6 1,8 2 2,2 2,6 3,2 2,6 3,2 4,3 6,3 11 -

40A - - - - - - 1,3 1,5 1,7 2 2,5 2 2,5 3,4 5 8,5 -

50A - - - - - - - 1,1 1,5 1,5 2 1,5 1,9 2,7 4,2 7,3 -

63A - - - - - - - - 1,5 1,5 1,6 1,3 1,625 2,2 3,8 6,7 -

NG

N, N

SN

, ND

N

D c

urve

0,5A 1 1,1 1,3 1,6 2 3 4,5 7,4 10 13 18 12 16 24 T T 2,1

1A 1 1,1 1,3 1,6 2 3 4,5 7,4 10 13 18 12 16 24 T T 2,1

2A 1 1,1 1,3 1,6 2 3 4,5 7,4 10 13 18 12 16 24 T T 2,1

3A 0,9 1 1,1 1,3 1,6 2,1 2,7 3,8 4,7 5,7 7,3 5,5 7,2 9,9 14 23 1,7

4A 0,9 1 1,1 1,3 1,6 2,1 2,7 3,8 4,7 5,7 7,3 5,5 7,2 9,9 14 23 1,7

6A 0,9 1 1,1 1,3 1,6 2,1 2,7 3,8 4,7 5,7 7,3 5,5 7,2 9,9 14 23 1,7

10A - 0,9 1 1,2 1,4 1,7 2 2,4 2,8 3,4 4,4 3,3 4,3 5,9 8,6 14 1,6

13A - - 0,95 1,1 1,3 1,5 1,7 1,9 2,2 2,6 3,3 2,6 3,2 4,5 6,8 11 1,4

16A - - - 1,1 1,3 1,5 1,7 1,9 2,2 2,6 3,3 2,6 3,2 4,5 6,8 11 -

20A - - - - 1,3 1,5 1,7 1,9 2,2 2,6 3,3 2,6 3,2 4,5 6,8 11 -

25A - - - - - 1,2 1,4 1,6 1,8 2 2,5 2,1 2,5 3,4 5,3 8,6 -

32A - - - - - - 1,4 1,6 1,7 2 2,5 2,1 2,5 3,4 5,3 8,6 -

40A - - - - - - - 1,2 1,5 1,5 1,8 1,5 1,9 2,4 4,1 6,8 -

50A - - - - - - - - 1,5 1,5 1,6 - 1,9 2,4 4,1 6,8 -

63A - - - - - - - - - 1,5 1,6 - - 2,08 3,1 5,3 -

MM

N

0,63A 1,1 1,15 1,2 1,35 1,5 1,8 2,7 4,9 8 13 22 9 16 T T T 1,8

1,25A 1,1 1,15 1,2 1,35 1,5 1,8 2,7 4,9 8 13 22 9 16 T T T 1,8

1,6A 1 1,05 1,1 1,2 1,4 1,7 2,1 2,7 3,3 4,5 7 3,9 5,7 9,9 17 T 1,6

2,5A 1 1,05 1,1 1,2 1,4 1,7 2,1 2,7 3,3 4,5 7 3,9 5,7 9,9 17 T 1,6

4A - - 1 1,1 1,3 1,5 1,9 2,4 3 4,1 5,6 3,5 5,1 7,6 12 20 1,4

6,3A - - - - 1,3 1,5 1,9 2,4 3 4,1 5,6 3,5 5,1 7,6 12 20 -

10A - - - - - - 1,7 2,1 2,7 3,7 4,5 3,2 4,7 6,1 8,8 14 -

12,5A - - - - - - - 2,1 2,7 3,7 4,5 3,2 4,7 6,1 8,8 14 -

16A - - - - - - - - 2,5 3,3 4 - 4,1 5,4 7,8 13 -

20A - - - - - - - - - 3,3 4 - - 5,4 7,8 13 -

25A - - - - - - - - - - 4 - - - 7,8 13 -

HLE

,HM

B,

HM

J

B c

urve 80A - - - - - - - - - 7,8 8,6 - 6,9 7,7 8,8 11 -

100A - - - - - - - - - - 8,6 - - 7,7 8,8 11 -

125A - - - - - - - - - - - - - - 8,8 11 -

HLF

, HM

C, H

MK

, HM

X

C c

urve

10A 1,6 1,9 2,3 3 3,7 4,6 5,6 6,7 7,7 8,6 9,5 9 11 13 16 23 3,9

16A - - 2 2,6 3,2 4 4,9 5,9 6,9 7,8 8,6 8,1 9,9 12 15 21 3,4

20A - - - 2,1 2,7 3,4 4,3 5,2 6,2 7 7,8 7,3 8,8 11 14 20 2,7

25A - - - - 2,4 3,1 3,9 4,9 5,8 6,7 7,5 6,8 8,5 11 14 20 2,4

32A - - - - - 2,9 3,6 4,5 5,4 6,3 7,1 6,3 7,9 9,9 13 18 -

40A - - - - - - 3,3 4,2 5,1 6 6,8 5,9 7,6 9 12 17 -

50A - - - - - - - 3,9 4,8 5,7 6,5 5,6 7,2 8,6 11 16 -

63A - - - - - - - - 4,5 5,4 6,2 5,3 6,8 8,4 11 16 -

80A - - - - - - - - - 7,4 8,2 - 6,6 7,3 8,6 11 -

100A - - - - - - - - - - 8,2 - - 7,3 8,6 11 -

125A - - - - - - - - - - - - - - 8,6 11 -

HM

D

D c

urve 80A - - - - - - - - - - - - - - 8,9 12 -

100A - - - - - - - - - - - - - - - 10 -

125A - - - - - - - - - - - - - - - - -

T = total selectivity. Each underlined value must be read as T when it is over the breaking capacity range of MCBs or RCBOs. All values are given with MCCB at the maximum setting.

Page 101: MCCB

101Technical modifications reserved

h250 LSI50/70 kA

h400 TM25/50 kA

h630 LSI50/70 kA

h1000 LSI50/70 kA

h1600 LSI50/70 kA

63A 100A 125A 160A 200A 250A 40A 125A 250A 250A 400A 250A 400A 630A 630A 800A 1000A 1250A 1600A

5,2 8,7 12 18 T T 2,7 11 T T T T T T T T T T T

3,6 5,2 6,9 9,6 15 T 2,3 6,2 23 T T T T T T T T T T

3,1 4,2 5,2 6,9 11 19 2,1 4,7 17 21 T T T T T T T T T

3,1 4,2 5,2 6,9 11 19 2,1 4,7 17 21 T T T T T T T T T

3,1 4,2 5,2 6,9 11 19 2,1 4,7 17 21 T T T T T T T T T

2,7 3,3 4,1 5,4 8,2 14 2 3,7 13 15 T T T T T T T T T

2,7 3,3 4,1 5,4 8,2 14 - 3,7 13 15 T T T T T T T T T

2,1 2,5 3,1 4,2 6,5 11 - 2,8 9,9 12 T T T T T T T T T

1,7 2 2,5 3,5 5,4 9,6 - 2,3 8,6 11 T T T T T T T T T

- 1,6 2 2,7 4,7 8,5 - 1,8 7,7 9,4 T T T T T T T T T

7,3 16 22 T T T 2,9 20 T T T T T T T T T T T

7,3 16 22 T T T 2,9 20 T T T T T T T T T T T

7,3 16 22 T T T 2,9 20 T T T T T T T T T T T

4,4 7,5 9,5 13 19 T 2,3 8,6 T T T T T T T T T T T

4,4 7,5 9,5 13 19 T 2,3 8,6 T T T T T T T T T T T

4,4 7,5 9,5 13 19 T 2,3 8,6 T T T T T T T T T T T

3,2 4,6 6 8,4 13 22 2,1 5,4 20 24 T T T T T T T T T

2,6 3,5 4,5 6,2 9,2 16 1,9 4,1 14 18 T T T T T T T T T

2,6 3,5 4,5 6,2 9,2 16 1,9 4,1 14 18 T T T T T T T T T

2,6 3,5 4,5 6,2 9,2 16 1,9 4,1 14 18 T T T T T T T T T

2,2 2,9 3,6 4,8 7 12 1,7 3,2 11 13 T T T T T T T T T

2,2 2,9 3,6 4,8 7 12 - 3,2 11 13 T T T T T T T T T

2,1 2,2 2,8 3,8 5,6 9,4 - 2,5 8,5 10 T T T T T T T T T

1,3 1,7 2,1 3 4,7 8,1 - 1,9 7,3 8,9 24 T T T T T T T T

- 1,3 1,625 2,4 4,2 7,4 - 1,75 6,7 8,2 22 T T T T T T T T

5,9 13 18 T T T 2,3 16 T T T T T T T T T T T

5,9 13 18 T T T 2,3 16 T T T T T T T T T T T

5,9 13 18 T T T 2,3 16 T T T T T T T T T T T

3,5 6,1 8 11 16 T 1,9 7,2 23 T T T T T T T T T T

3,5 6,1 8 11 16 T 1,9 7,2 23 T T T T T T T T T T

3,5 6,1 8 11 16 T 1,9 7,2 23 T T T T T T T T T T

2,6 3,7 4,8 6,6 9,6 16 1,6 4,3 14 18 T T T T T T T T T

2,2 2,9 3,6 5 7,5 12 1,5 3,2 11 13 T T T T T T T T T

2,2 2,9 3,6 5 7,5 12 1,5 3,2 11 13 T T T T T T T T T

2,2 2,9 3,6 5 7,5 12 1,5 3,2 11 13 T T T T T T T T T

1,8 2,3 2,8 3,8 5,9 9,5 - 2,5 8,6 10 T T T T T T T T T

- 2,3 2,8 3,8 5,9 9,5 - 2,5 8,6 10 T T T T T T T T T

- 1,7 2,1 2,7 4,5 7,6 - 1,9 6,8 8,4 23 T T T T T T T T

- - 1,7 2,2 3,9 6,5 - 1,9 6,8 7,2 20 T T T T T T T T

- - - 2,08 3,4 5,9 - 1,75 5,3 6,5 18 T T T T T T T T

3,5 10 18 T T T 1,8 16 T T T T T T T T T T T

3,5 10 18 T T T 1,8 16 T T T T T T T T T T T

2,7 4,3 6,3 11 19 T 1,6 5,7 T T T T T T T T T T T

2,7 4,3 6,3 11 19 T 1,6 5,7 T T T T T T T T T T T

2,5 3,9 5,7 8,4 13 22 1,5 5,1 20 24 T T T T T T T T T

2,5 3,9 5,7 8,4 13 22 - 5,1 20 24 T T T T T T T T T

2,2 3,5 5,2 6,8 9,8 16 - 4,7 14 18 T T T T T T T T T

- 3,5 5,2 6,8 9,8 16 - 4,7 14 18 T T T T T T T T T

- 3,3 4,6 6 8,7 14 - 4,1 13 15 T T T T T T T T T

- - 4,6 6 8,7 14 - - 13 15 T T T T T T T T T

- - - 6 8,7 14 - - 13 15 T T T T T T T T T

- 7,7 8,5 9,8 12 16 - 6,9 11 18 T T T T T T T T T

- - 8,5 9,8 12 16 - - 11 18 T T T T T T T T T

- - - 9,8 12 16 - - 11 18 T T T T T T T T T

7,3 10 12 14 18 26 4,3 11 23 19 T T T T T T T T T

6,4 9 11 13 16 23 3,7 9,9 21 25 T T T T T T T T T

5,6 8,1 9,8 12 15 22 3,2 8,8 20 24 T T T T T T T T T

5,1 7,5 9,4 12 15 22 2,8 8,5 20 24 T T T T T T T T T

4,7 7 8,8 11 14 20 - 7,9 18 22 T T T T T T T T T

4,3 6,6 8,4 10 13 19 - 7,6 17 21 T T T T T T T T T

4 6,2 8 9,6 12 18 - 7,2 16 20 T T T T T T T T T

- 5,9 7,6 9,3 12 18 - 6,8 16 20 T T T T T T T T T

- 7,3 8,1 9,6 12 16 - 6,6 11 18 T T T T T T T T T

- - 8,1 9,6 12 16 - - 11 18 T T T T T T T T T

- - - 9,6 12 16 - - 11 18 T T T T T T T T T

- - - - 9,8 13 - - 12 14 T T T T T T T T T

- - - - - 11 - - 10 12 T T T T T T T T T

- - - - - - - - 8,7 10 T T T T T T T T T

Page 102: MCCB

102 Technical modifications reserved

Selectivity chart

Breaking capacity according to IEC 947-2. Network : 3 phasis + neutral 220/380 ~ 240/415 V ACnotes : “T” = total discrimination (up to the breaking capacity of the downstream device)

“-” = no discrimination

Icc (kA) Upstream x160 TM x250 TM h250 TM

Downstream (A) 16 - 50 63 80 100 125 160 100 125 160 200 250 32 63 100

x160 TM18/25/40 kA

16 - 2 2 2,9 2,9 3 2,15 2,9 4,1 5,6 5,4 - 1,2 2,15

20 - 2 2 2,9 2,9 3 2,15 2,9 4,1 5,6 5,4 - 1,2 2,15

25 - 2 2 2,9 2,9 3 2,15 2,9 4,1 5,6 5,4 - 1,2 2,15

32 - 1,8 1,8 2,6 2,6 2,7 2 2,6 3,6 5 4,8 - 1,15 2

40 - 1,6 1,6 2,35 2,35 2,4 1,8 2,35 3,3 4,3 4,2 - 1,1 1,8

50 - 1,6 1,6 2,35 2,35 2,4 1,8 2,35 3,15 4,25 4,15 - 1,1 1,8

63 - - - 2,15 2,15 2,2 1,7 2,15 3 4,05 3,9 - - 1,7

80 - - - 2,15 2,15 2,2 1,7 2,15 2,9 3,9 3,8 - - 1,7

100 - - - - - 2,1 - 1,95 2,75 3,7 3,6 - - -

125 - - - - - 2,1 - 1,95 2,65 3,5 3,4 - - -

160 - - - - - - - 1,95 2,6 3,45 3,35 - - -

x250 TM25/40 kA

100 - - - - - - - 1,95 2,5 3,15 3,3 - - -

125 - - - - - - - - 2,5 3,15 3,3 - - -

160 - - - - - - - - - 3,15 3,3 - - -

200 - - - - - - - - - - 3,3 - - -

250 - - - - - - - - - - - - - -

h250 TM25/50/65 kA

32 - - - - - - 1,55 1,95 2,5 3,15 3,3 - 1 1,55

63 - - - - - - 1,55 1,95 2,5 3,15 3,3 - - 1,55

100 - - - - - - - 1,95 2,5 3,15 3,3 - - -

125 - - - - - - - - 2,5 3,15 3,3 - - -

160 - - - - - - - - - 3,15 3,3 - - -

200 - - - - - - - - - - 3,3 - - -

250 - - - - - - - - - - 3,3 - - -

h250 LSI50/70 kA

40 - - - - - - 1,55 1,95 2,5 3,15 3,3 - 1 1,55

125 - - - - - - - - 2,5 3,15 3,3 - - -

250 - - - - - - - - - - - - - -

h400 TM25/50 kA

250 - - - - - - - - - - - - -

400 - - - - - - - - - - - - - -

h630 LSI50/70 kA

250 - - - - - - - - - - - - - -

400 - - - - - - - - - - - - - -

630 - - - - - - - - - - - - - -

h1000 LSI50/70 kA

630 - - - - - - - - - - - - - -

800 - - - - - - - - - - - - - -

1000 - - - - - - - - - - - - - -

h1600 LSI50/70 kA

1250 - - - - - - - - - - - - - -

1600 - - - - - - - - - - - - - -

Page 103: MCCB

103Technical modifications reserved

h250 LSI h400 TM h630 LSI h1000 LSI h1600 LSI

125 160 200 250 40 125 250 250 400 250 400 630 630 800 1000 1250 1600

2,9 4,1 5,6 5,4 - T T 6,5 13 T T T T T T T T

2,9 4,1 5,6 5,4 - T T 6,5 13 T T T T T T T T

2,9 4,1 5,6 5,4 - T T 6,5 13 T T T T T T T T

2,6 3,6 5 4,8 - T T 5,6 10,5 T T T T T T T T

2,35 3,3 4,3 4,2 - T T 4,95 9,2 T T T T T T T T

2,35 3,15 4,25 4,15 - T T 4,8 8,8 T T T T T T T T

2,15 3 4,05 3,9 - T T 4,6 8,3 T T T T T T T T

2,15 2,9 3,9 3,8 - T T 4,35 7,9 T T T T T T T T

1,95 2,75 3,7 3,6 - T T 4,15 7,5 T T T T T T T T

1,95 2,65 3,5 3,4 - T T 4 7 T T T T T T T T

1,95 2,6 3,45 3,35 - T T 3,9 6,6 T T T T T T T T

1,95 2,5 3,15 3 - T T 3,6 5,75 T T T T T T T T

- 2,5 3,15 3 - - T 3,6 5,75 T T T T T T T T

- - 3,15 3 - - T 3,6 5,75 T T T T T T T T

- - - 3 - - T 3,6 5,75 T T T T T T T T

- - - - - - T 3,6 5,75 T T T T T T T T

1,95 2,5 3,15 3 T T T 3,6 5,75 T T T T T T T T

1,95 2,5 3,15 3 - T T 3,6 5,75 T T T T T T T T

1,95 2,5 3,15 3 - T T 3,6 5,75 T T T T T T T T

- 2,5 3,15 3 - - T 3,6 5,75 T T T T T T T T

- - 3,15 3 - - T 3,6 5,75 T T T T T T T T

- - - - - - T 3,6 5,75 T T T T T T T T

- - - - - - T 3,6 5,75 T T T T T T T T

1,95 2,5 3,15 3 - 1,65 3,25 3,6 5,75 T T T T T T T T

- 2,5 3,15 3 - - 3,25 3,6 5,75 T T T T T T T T

- - - - - - - - 5,75 T T T T T T T T

- - - - - - 3,25 - 5,75 T T T T T T T T

- - - - - - - - - - T T T T T T T

- - - - - - - - 5,75 - 5,2 6,3 T T T T T

- - - - - - - - - - - 6,3 T T T T T

- - - - - - - - - - - - T T T T T

- - - - - - - - - - - - - 9,6 10 T T

- - - - - - - - - - - - - - 10 T T

- - - - - - - - - - - - - - - T T

- - - - - - - - - - - - - - - - 19,2

- - - - - - - - - - - - - - - - -

Page 104: MCCB

Hager Vertriebsgesellschaft mbH & Co. KGZum Gunterstal66440 Blieskastel

Telefon 06842 945-0Telefax 06842 945-7666www.hager.com

10NC0589