maximizing hydronic system design part iiicleaverbrooks.com/reference-center/resource-library...•...
TRANSCRIPT
MAXIMIZING HYDRONIC SYSTEM DESIGN
– PART III
Presented by Cleaver Brooks’ Steve Connor
& DCEs’ David Grassl
June 21, 2017
TODAY’S TOPICS
• Dispelling common myths about condensing boilers
• Supply water temperature
• System Delta T
• Hot water reset
• System pumping choices and implementation strategies
• System piping choices and myths
• The REAL factors affecting efficiency
• Key points to know when designing new and retrofit condensing hot
water systems
• Summary of the Three Part Series
• Q&A
2
David Grassl
President, Dynamic Consulting Engineers
3
MYTH #1 –
NEED TO MAINTAIN 180°F HWS
TEMPERATURE
• Logic with 180°F Hot Water Supply
• Flue Gas Temperatures
• Examples:
• AHU heating coils
• VAV box reheat coils
• Miscellaneous terminal equipment
• New Design Paradigm:
• As low of HWS as possible (reduces HWR)
• Wide delta T
• Evaluate existing conditions
4
5
MYTH #1 –
NEED TO MAINTAIN 180°F HWS
TEMPERATURE
• Logic with 180°F Hot Water Supply
• Flue Gas Temperatures
• Examples:
• AHU heating coils
• VAV box reheat coils
• Miscellaneous terminal equipment
• New Design Paradigm:
• As low of HWS as possible (reduces HWR)
• Wide delta T
• Evaluate existing conditions
MYTH #2 –
NEED TO MAINTAIN A 20°F ΔT
• Logic with 20°F ΔT
• Heat Transfer Ability
• More flow
• Higher hot water return temperature
• New Design Paradigm:
• Increase ΔT as allowed by boiler
• Reduces flow rates, pump sizes, and piping
• Increased time in condensing mode
6
MYTH #2 –
NEED TO MAINTAIN A 20°F ΔT
• Logic with 20°F ΔT
• Heat Transfer Ability
• More flow
• Higher hot water return temperature
• New Design Paradigm:
• Increase ΔT as allowed by boiler
• Reduces flow rates, pump sizes, and piping
• Increased time in condensing mode
7
MYTH #3 –
HOT WATER RESET DOESN’T WORK
• Logic with Constant HWS
• New Design Paradigm:
• Aggressive HWS reset
• Less energy to heat to lower HWS
• More time in condensing mode
8
MYTH #3 –
HOT WATER RESET DOESN’T WORK
• Logic with Constant HWS
• New Design Paradigm:
• Aggressive HWS reset
• Less energy to heat to lower HWS
• More time in condensing mode
9
MYTH #4 –
VARIABLE FLOW PRIMARY IS TOO
COMPLICATED
• Logic with Primary-Secondary
• System Consists of Control Valves
• Desire for Flow Measurement
• New Design Paradigm:
• Fewer pumps
• Energy management
• Less pumping energy
• Reduce/eliminate mixing
10
• System Requirements:
• Boiler isolation control valve
• Two-way coil control valves
• Minimum flow protection
• Minimum flow bypass control valve
• Three-way control valves
MYTH #4 –
VARIABLE FLOW PRIMARY IS TOO
COMPLICATED
11
• System Requirements:
• Boiler isolation control valve
• Two-way coil control valves
• Minimum flow protection
• Minimum flow bypass control valve
• Three-way control valves
MYTH #4 –
VARIABLE FLOW PRIMARY IS TOO
COMPLICATED
12
MYTH #5 –
HOT WATER SUPPLY & CONDENSING
EFFICIENCIES
• Logic with hot water supply temperature and & efficiencies
• Boiler Flue Gas Temperatures
• Counterflow Arrangement
• New Design Paradigm:
• Reduce hot water return temperature
• Multiple boilers at part-load
• Increased system efficiency
13
• Boiler Efficiencies are Dictated By:
• Hot water return temperatures
• Boiler Firing Rates
MYTH #5 –
HOT WATER SUPPLY & CONDENSING
EFFICIENCIES
14
• Boiler Efficiencies are Dictated By:
• Hot water return temperatures
• Boiler Firing Rates
MYTH #5 –
HOT WATER SUPPLY & CONDENSING
EFFICIENCIES
15
MYTH #6 –
CONDENSING BOILERS REQUIRE
ADDITIONAL WORK
• Logic with Condensing Boilers
• Robust Heat Exchanger & Venting
• Condensate Production & Treatment
• New Design Paradigm:
• SS heat exchanger – minimal maintenance
• SS category IV venting
• Condensate occurs naturally
16
MYTH #6 –
CONDENSING BOILERS REQUIRE
ADDITIONAL WORK
• Logic with Condensing Boilers
• Robust Heat Exchanger & Venting
• Condensate Production & Treatment
• New Design Paradigm:
• SS heat exchanger – minimal maintenance
• SS category IV venting
• Condensate occurs naturally
17
CONDENSING BOILERS
& RETROFITS –
COMMON ITEMS IN ALL RETROFITS
• Type of Boilers
• System mass
• Piping & pumping configuration
• Building Loads
• Temperatures required
• Minimum & maximum design loads
• Dual temperature applications
• Hot Water Supply & Return Temperatures
• Temperature Control Valves
• Two-way vs. Three-way valves
18
• Pumps
• Reuse or replace
• VFD or constant speed
• Condensate Treatment
• Venting & Combustion Air
• Gas Pressures
• System Controls
• Pump control
• Hot water reset
• Boiler management
CONDENSING BOILERS
& RETROFITS –
COMMON ITEMS IN ALL RETROFITS
19
CONDENSING BOILERS
& RETROFITS –
RETROFIT #1
20
• Small, simple building
• Single non-condensing boiler
CONDENSING BOILERS
& RETROFITS –
RETROFIT #1
21
• Replace boiler with condensing boiler
• Evaluate HWS temperature required
CONDENSING BOILERS
& RETROFITS –
RETROFIT #2
22
• Medium sized building
• Multiple parallel boilers
CONDENSING BOILERS
& RETROFITS –
RETROFIT #2
23
• Replace boilers with condensing boilers
• Variable primary flow conversion
CONDENSING BOILERS
& RETROFITS –
RETROFIT #3
24
• Large building
• Multiple parallel boilers
CONDENSING BOILERS
& RETROFITS –
RETROFIT #3A
25
• Keep an existing boiler –add condensing boilers
• Maintain P-S pumping
CONDENSING BOILERS
& RETROFITS –
RETROFIT #3B
26
• Keep an existing boiler –add condensing boilers
• Variable flow primary conversion for condensing boilers
CONDENSING BOILERS
& RETROFITS –
RETROFIT #3C
27
Solutions
• Larger-capacity condensing
boilers
• Condensing control strategy
• Outdoor air resetSystem pump
110ºF
110ºF
150ºF
150ºF
VSD
SUMMARIZING THE
THREE PART SERIES…
28
Boiler Efficiency Improves Dramatically
with Condensing
Counter-flow
Heat Exchanger
Cold water return inlet
temperature introduced
near the optimum flue gas temperatures with counter flue
gas flow as water rises in opposite direction
Effective Heating Surface to
promote condensing
EFFICIENT CONDENSING
BOILER INCLUDES…
29
BURNER WITH CONSISTENT
FUEL/AIR RATIO CONTROL
30
Boiler Efficiency Improves Dramatically
with Condensing
Condensing Efficiency Drivers:
• Low return temperatures
• Effective heat exchanger
• Burner with effective fuel/air ratio
control
DEW POINT CHANGES WITH
EXCESS AIR AND RETURN WATER
TEMPERATURE
Flue Gas Dew point moves left (lower) based on
rise in Excess Air
31
BOILER MASS MAKES
A DIFFERENCE…
High Mass
Low Mass
32
PRIMARY/SECONDARY SYSTEM
PRIMARY SECONDARY
33
VARIABLE FLOW PRIMARY SYSTEM
34
• Movement toward larger ΔT’s
• Reduce pumping flow
• Reduce piping sizes, pumps, & accessories both in size and number required
• Decrease hot water return to the boiler
• Greatly increases efficiency!
REDUCE FLOW RATES,
REDUCE PIPING AND PUMP SIZE
35
• Hot Water Supply Temperature Reset
• Return temperature
• Outdoor reset
• Pump Control with VFD
• Delta P
• Delta T
SYSTEM CONTROL STRATEGIES
36
BUFFER TANK RATIONALE:
• Stores excess energy
• Prevents boiler cycling (Low mass)
• Allows for better temperature control
• Assists in system efficiency
Not required in High system mass applications
37
BUFFER TANKS
Tank Sizing Calculations
1. Minimum Boiler Cycle Time
2. Minimum Boiler Output
3. Minimum System Load
4. Temperature Differential in Tank
38
CONDENSING BOILERS –
VENTING
Flue Stack Temperatures &
Materials:
• Condensing boilers:
• Flue gases are generally less than
200°F
• Stainless steel, polypropylene, or
CPVC
• Highly recommend stainless steel
(could always operate in non-
condensing mode)
• Non-condensing boilers:
• Flue gases are approximately 250°F to
350°F
• Aluminum, galvanized, carbon or
stainless steel
• Consult the boiler manufacturer prior to
choosing the stack material
39
NON-TRADITIONAL SYSTEMS
WITH CONDENSING BOILER
Low grade heating is a perfect application for
condensing boilers:
• Water source heat pumps
• Geothermal
• Radiant systems
• Ceiling panels
• In-floor heating
• Snow melt
• Pool heating
• Series loop
40
CONDENSING BOILER
WITH DUAL RETURN
41
• Accepts hot water return from two
sources
• Eliminates mixing high hot water return
with low hot water return
• Promotes condensing that would
otherwise be lost
THE HYBRID SYSTEM
42
DISPELLING THE SIX
MAJOR MYTHS
43
MYTH #1
MUST HAVE 180 DEGREE F
SUPPLY WATER
• True of legacy systems, not condensing
boilers
• Some VAV box and finned radiation can
still be used @ lower temps.
• Some may require more or larger coils
• Check for air side Delta P and coil output
for the space.
• Reduce supply water temperature as
much as possible!
44
MYTH #2
MUST HAVE A 20 DEGREE
DELTA T
• Needed to protect non-condensing boilers
• Higher Delta T, LOWER FLOW
• Low mass boilers normally 20 – 30 degree Delta T
• High mass are tolerant of LOW FLOW, HIGHER
Delta T
• Lower returns increase efficiency
• Impacts pump sizing, pipe sizing, accessories size,
LOWERING COSTS
45
MYTH #3
HOT WATER RESET
• Required to meet ASHRAE 90.1
• Reducing Supply also reduces Return
temperature
• With condensing boilers aggressive setback
possible
• Especially high mass boilers!
46
MYTH #4
VFP IS MORE COMPLICATED
THAN P/S PIPING
• LOGIC: P/S assures proper
flow through the boiler
• VFP has one set of pumps =
Simpler
• VFP has less pump
horsepower, less piping and
accessories; lower operating
and install cost
• Most valves and meters
required for P/S are same for
VFP
• Exception are boiler isolation
valves.
47
MYTH #5
MUST REDUCE SUPPLY TEMP.
FOR HIGH EFFICIENCY
• On the right track, but not always
helpful when condensing
• Reduce from 180 to 160 with 20 degree
DT…Yipes! Not condensing!!
• What’s key is return temp at or below
flue gas dew point temp and excess air
levels
• Condensing boilers most efficient at
lower firing rates
48
MYTH #6
HIGHER MAINTENANCE WITH
CONDENSING BOILERS
• LOGIC: Condensation causes inordinate corrosion
problems
• Actually the heat exchanger is designed for this
• So are the venting materials
• If properly sized for load, less cycling, less problems
• Exception: Condensate neutralization; monitored
and replaced
49
RETROFITTING
CONDENSING BOILERS
• Boiler and system mass decision
• Buffer tank required?
• Low mass boilers will require P/S, high
mass VFP
• Flow is critical with low mass!
• Building load, max and min affects boiler
sizing and turndown
• Dual return opportunity?
50
• Fan coil sizing and building efficiency
enhancements?
• If converting to VFP, two way control valves in
system allow for variable flow
• VFD capability on pumps
• Venting for condensing boilers must be Category
IV.
• Masonry chimney needs liner
• Gas pressure requirements
• Boiler and system control strategy. A combination
of the boiler mfr. and the building control people.
RETROFITTING
CONDENSING BOILERS
51
THAT’S IT FOR THE SUMMARY!
52