Match & NetPro 19 inch Rackmount Product Presentation. Product Management August 2004. Contents. Range Match/NetPro 19” shared features Line Interactive versus On Line Technology Match 19” Topology Unique Selling Points Key Features Applications NetPro 19” Topology - PowerPoint PPT PresentationTRANSCRIPT
Match & NetPro 19 inch Rackmount Product PresentationProduct ManagementAugust 2004
Match/NetPro 19inch Sales PresentationProduct Management
August 4th, 2004
Range
Match/NetPro 19” shared features
Line Interactive versus On Line Technology
Match 19” Topology
Unique Selling Points
Key FeaturesApplications
NetPro 19”TopologyUnique Selling PointsKey FeaturesApplications
Accessories
Contents
Match/NetPro 19inch Sales PresentationProduct Management
August 4th, 2004
“Even a moment’s disruption can have devastating effects on power sensitive customers such as internet service providers, data centres, wireless telecommunications networks, on line traders, computer chip manufacturers and medical research centres. For these customers, power disruptions can result in data corruption, burned circuit boards, component damage, file corruption and lost customers.” - “Electrical Power Interruption Cost Estimates for Individual Industries, Sectors and US Economy” February 2002, US Dept of Energy, Office of Power Technologies
“The system and its data can become corrupt as a result of power failure…a UPS can protect the system if power is lost. A UPS usually provides…temporary power which may be enough to permit a graceful shutdown” - Special Publication 800-34 Contingency Planning Guide for Information Technology Systems, National Institute of Standards and
Technology, June 2002
Match/NetPro 19inch Sales PresentationProduct Management
August 4th, 2004
Models available include
Range
Match
700VA
1000VA
1500VA
2200VA
3000VA
NetPro
600VA
1000VA
1500VA
2000VA
3000VA
Match/NetPro 19inch Sales PresentationProduct Management
August 4th, 2004
Manual service bypass box
SNMP plug-in card
Relay plug-in card
DC connector kit for external batteries
Match
Matching battery cabinet for
2200VA (36V/14Ah)
3000VA (48V/14Ah)
NetPro
Matching battery cabinet for
1000VA (36V/14-28Ah)
2000VA (72V/14Ah)
3000VA (108V/7Ah)
Range
Match/NetPro 19inch Sales PresentationProduct Management
August 4th, 2004
Match 19inch
Easy to use DC connector and plug (2.2 and 3kVA) Simple installation
Allows for more battery support time
Match/NetPro 19inch Sales PresentationProduct Management
August 4th, 2004
NetPro 19inch
Easy to use DC connector and plug (1, 2 and 3kVA) Simple installation
Allows for more battery support time
Match/NetPro 19inch Sales PresentationProduct Management
August 4th, 2004
Match and NetPro 19inch
More outlets and 16A inlet (Match/NetPro 3000) Greater flexibility for the user
More individual loads can be supported
Match/NetPro 19inch Sales PresentationProduct Management
August 4th, 2004
Match and NetPro 19inch
Front accessible battery drawers User replaceable batteries
Safe and easy installation and removal
Match/NetPro 19inch Sales PresentationProduct Management
August 4th, 2004
Excellently engineered for maximum cooling Prolongs battery and UPS
life
Match and NetPro 19inch
Match/NetPro 19inch Sales PresentationProduct Management
August 4th, 2004
Line Interactive versus On Line Technology
Lower cost than on-line UPS
Higher efficiency than on line UPS, lower direct cost to run
Total mains conditioning – always creating a new sinewave
No break in supply to the load in a mains failure
Stable output voltage (NetPro - +/- 1%)
Lower level of mains conditioning
Break in the power when transferring from mains to inverter
Wide output voltage window (Match = +10/-17%)
More components, typically lower MTBF and efficiency
More components, higher cost
Disadvantages OL
Disadvantages LI
Advantages LI
Advantages OL
Match/NetPro 19inch Sales PresentationProduct Management
August 4th, 2004
UPS Input Voltage
LI Output
Status:
OL OutputStatus:
on battery boost normal buck battery buck normal boost battery
on battery on mains batt mains batt
Line Interactive & On Line Output Voltage
Match 19 inch Rackmount
Match/NetPro 19inch Sales PresentationProduct Management
August 4th, 2004
Control Inverter
Boost
Buck
Normal
Battery
SafetyRelay
IN
OUT
Line Interactive
Topology
AVR relay
Match/NetPro 19inch Sales PresentationProduct Management
August 4th, 2004
A Line Interactive UPS provides:
Battery back up and voltage stabilisationAs well as providing back up power from the battery when the mains fails, the UPS filters the mains during normal operation, regulating the incoming voltage
Cost effective UPS protection Lower price compared to on line double conversion UPS
Topology
Match/NetPro 19inch Sales PresentationProduct Management
August 4th, 2004
A Line Interactive UPS provides:
Small break in powerDuring the switch from mains to battery, there is a small loss of power to the load (typically 2-4ms, not affecting most computer type loads)
Medium degree of protection When compared to on line (double conversion) UPS
Topology
Match/NetPro 19inch Sales PresentationProduct Management
August 4th, 2004
Excellent high voltage protection The Match UPS will protect itself and the
supported load up to 350V AC. Most UPS will damage themselves or the load if the inout voltage exceeds 300V
Low ‘green’ power consumption Compared to other line interactive UPS, the
power consumption is extremely low during normal operation
Unique Selling Points
Match/NetPro 19inch Sales PresentationProduct Management
August 4th, 2004
Optimised sinewave output The output waveform is sinusoidal with a linear load, and with a crest load is slightly flattened. This avoids high current peaks on the electronics and the battery, and still provides high efficiency
This is the optimal solution between sinewave and stepwave UPS outputs. Stepwave UPS may cause some electronic equipment to malfunction
Unique Selling Points
Match/NetPro 19inch Sales PresentationProduct Management
August 4th, 2004
Additional USPs, Match 2200 & 3000 Extremely wide input voltage window
At 165-275V (500-1500VA) and 140-305V (2200 & 3000VA), the output voltage is limited to 190-254V. This minimises the need for battery use, extending battery life
Battery charging even at 140VAC Even in poor mains conditions there is a fast recovery of battery power, increasing up time and battery life
High battery recharge current
When additional battery packs are connected, the charger current automatically increases to 10A, ensuring much faster recharge time
Match/NetPro 19inch Sales PresentationProduct Management
August 4th, 2004
Deep battery calibration testThe actual battery capacity can be tested and calibrated. This ensures the predicted runtime stays accurate throughout the life of the UPS
Load dependent end of dischargeIf the discharge time is shorter, batteries may be discharged deeper. This feature ensures maximum runtime is given at any load level, without the risk of damaging the battery during longer power failures
Additional USPs, Match 2200 & 3000
Match/NetPro 19inch Sales PresentationProduct Management
August 4th, 2004
Automatic voltage regulationThe buck and boost function minimises battery operation, increasing the battery life. With an input voltage window of 165-275V, the output voltage is limited to 190-254V
Crest factor input acceptance 6:1The Match is especially suited for computer loads, and no oversizing is necessary
Key Features
Match/NetPro 19inch Sales PresentationProduct Management
August 4th, 2004
Battery start (cold start)Allows the UPS to be switched on without mains power, for mobile applications or to perform a quick action during a mains failure
Extended communicationRS232, SNMP and contact interface communication (plug in options)
Key Features
Match/NetPro 19inch Sales PresentationProduct Management
August 4th, 2004
Automatic monthly battery testing
Charger off at end of discharge period
Automatic boost charge
2 hours battery recharge time
The UPS keeps running in normal operation over the test, rather than switching to battery. If the battery is damaged or empty, the load is still supported
Lowest battery temperature during mains operation
Prevents battery depletion beyond recharge capability
Safe battery test
Alerts the user that the batteries need to be replaced
For areas with poor mains, ensures a faster recharge time than with float charge only
On battery at less than 5% load, the UPS performs an automatic shutdown to protect the battery. This function can be disabled
Means that loads even in very poor mains areas can be supported more than once during a shift
The electronic design of the UPS means the battery temperature is very low, increasing battery life
No load shutdown
Key Features – Superior Battery Management
Match/NetPro 19inch Sales PresentationProduct Management
August 4th, 2004
PCs
Servers
Workstations
Hubs, switches and routers
Cash register systems (EPOS)
Fax, modem, ISDN adaptors
Applications
NetPro 19 inch Rackmount
Match/NetPro 19inch Sales PresentationProduct Management
August 4th, 2004
Topology
On Line Double Conversion
Rectifier Inverter
Battery
SafetyRelay
IN OUT
AutomaticBypass
Match/NetPro 19inch Sales PresentationProduct Management
August 4th, 2004
Voltage and frequency independenceAs well as providing back up power when the mains fails, the UPS filters the mains during normal operation, stabilising the incoming voltage and frequency and generating a new, clean output to the load
Highest level of protection Greater protection when compared to off line and line interactive UPS
True On Line Double Conversion provides:
Topology
Match/NetPro 19inch Sales PresentationProduct Management
August 4th, 2004
No UPS inrush current Inrush currents result in voltage dips on the
mains, which can disturb other users or even blow the fuse of the distribution board
No load inrush current When the UPS is switched on, the bypass is
disabled for a short time. This avoids high inrush currents from the load passing through the bypass
Unique Selling Points
Match/NetPro 19inch Sales PresentationProduct Management
August 4th, 2004
Deep battery calibration testThe actual battery capacity can be tested and calibrated. This ensures the predicted runtime stays accurate throughout the life of the UPS
Load dependent end of dischargeIf the discharge time is shorter, batteries may be discharged deeper. This feature ensures maximum runtime is given at any load level, without the risk of damaging the battery during lengthy mains failures
Unique Selling Points
Match/NetPro 19inch Sales PresentationProduct Management
August 4th, 2004
Wide AC input voltage windowMinimises the need for battery operation, extending the battery life
Crest factor handling of 6:1Well suited for computer loads, with no need for oversizing
Power factor one inputMaximum power with minimum current, meaning less mains distortion and no risk of feeding disturbances back to the mains
Key Features
Match/NetPro 19inch Sales PresentationProduct Management
August 4th, 2004
Automatic bypass switchIn the event of an overload on the UPS, there is a no break transfer to mains so the load is continuously supported
Extended communicationRS232, SNMP and contact interface communication
Bypass operation enable/disableIf it’s not desirable to transfer the load to bypass (if there is unstable bypass voltage or frequency) this feature can be disabled
Key Features
Match/NetPro 19inch Sales PresentationProduct Management
August 4th, 2004
Automatic monthly battery testing
Charger off at end of discharge period
Automatic boost charge
1.5 hour battery recharge time
Measures the actual value of the battery
Temperature compensated battery charging
Prevents battery depletion beyond recharge capability
Deep battery calibration test
Alerts the user that the batteries need to be replaced
For areas with poor mains, ensures a faster recharge time than with float charge only
Protects the battery whilst still ensuring maximum autonomy can be provided to even small loadsOn battery at less than 5% load, the UPS performs an automatic shutdown to protect the battery. This function can be disabled
Means that loads even in very poor mains areas can be supported more than once during a shift
Prevents over- or under-charging of the battery, increasing the battery life
No load shutdown
Load dependent end of discharge
Key Features – Superior Battery Management
Match/NetPro 19inch Sales PresentationProduct Management
August 4th, 2004
Additional Key Features 2000-4000VALiquid crystal display
Immediately visible information on input voltage, load level, remaining autonomy time, status and alarm settings
Adjustable frequency tracking rangeThe UPS can be optimised for use with a generator
Programmable outlets (3 & 4kVA)Allows the user to switch off less critical loads during a power failure, to provide maximum uptime for more critical loads
Match/NetPro 19inch Sales PresentationProduct Management
August 4th, 2004
Rackmount servers for internet
Local/Wide area networks
Cad/Cam stations
Telecom clusters
Telecommunication equipment
Any mission critical application
Applications
Accessories
Match/NetPro 19inch Sales PresentationProduct Management
August 4th, 2004
Accessories SNMP Card Presents UPS information across a network via: SNMP Agent (one or more NMS can monitor,
manage and control the UPS) Web Server (UPS data in HTML format, so standard internet browser can be used to monitor UPS) Easy installation through RS232 slot SNMP box also available
Network Protection Software CD packed with UPS free of charge, with intelligent communication cable. Simple installation Virtually invisible operation under normal conditions Provides a graceful shutdown of load after a lengthy mains failure Supports all major operating systems DataShield supplied for JAVA supported operating systems
Match/NetPro 19inch Sales PresentationProduct Management
August 4th, 2004
Accessories Relay Interface Card Easily installed into CardConnect slot at rear of UPS Provides 4 potential free contacts for:
Mains failure
General alarm
Battery low
Bypass active
and a 9 pole Sub-D connector
Manual Service Bypass Contains a manual bypass switch Allows for maintenance or testing of UPS with no interference to the protected load Pluggable as standard, but can be hardwired using the internal terminal strip