MANUFACTURERS’
PERSPECTIVE
09/01/2015 NEW DELHI 1
MINISTRY OF HEAVY INDUSTRIES & PUBLIC ENTERPRISES NOTIFIES
ELECTRICAL TRANSFORMERS (QUALITY CONTROL ORDER,2014)
DT. 27.01.2014
MANDATES BIS LICENSING FOR DT’S UPTO & INCLUDING 100 KVAAS PER IS 1180:1989AS PER IS 1180:1989
SUPERSEDED BY
ELECTRICAL TRANSFORMERS (QUALITY CONTROL)
AMENDMENT ORDER, 2014 DT.14TH NOV 2014.
MANDATES BIS LICENSING FOR DT’S UPTO & INCLUDING
2500 KVA AS PER IS 1180:2014(PARTI)
09/01/2015 NEW DELHI 2
ELECTRICAL TRANSFORMERS (QUALITY CONTROL)
AMENDMENT ORDER, 2014 DT. 14TH NOV 2014.
THE ENFORCMENT OF THIS ORDER SHOULD BE POSTPONED BY ATLEAST SIX MONTHSFOR THE FOLLOWING REASONS:
GUIDELINES FOR CERTIFICATION OF OUTDOOR TYPE DISTRIBUTION
TRANSFORMERS AS PER IS 1180 WERE ISSUED ONLY ON 27TH NOV. 2014TRANSFORMERS AS PER IS 1180 WERE ISSUED ONLY ON 27TH NOV. 2014
SCHEME OF TESTING AND INSPECTION FOR IS 1180:2014 WAS MADE AVAILABLE VERYLATE AND STILL REQUIRES MANY CLARIFICATIONS ESPECIALLY TATKAL LICENSING.
REGIONAL OFFICES TOO ARE STILL NOT CLEAR ON THE GUIDELINES ISSUED & HAVEDIFFERENT OPINIONS ON THE RANGE & QUANTITIES OF SAMPLES DRAWL ETC. FORTESTING AT THE FIRST INSTANCE.
APPLICATIONS OF MOST MANUFACTURERS WHO HAD APPLIED EARLIER FORCERTIFICATION HAVE BEEN CLOSED & RETURNED OWING TO BIS 1180 QUALITY CONTROLORDER AMENDMENT.
09/01/2015 NEW DELHI 3
THRUST AREAS NEEDING ATTENTION OF REGULATORS & STAKE HOLDERS BEFORE
ENFORCING ELECTRICAL TRANSFORMERS QUALITY CONTROL ORDER, 2014
UTILITIES/DISCOMS HAVE DIFFERENT SPECS. FOR MANUFACTURE OF TRANFORMERS WRT
1. BASIC INSULATION LEVELS
2. ENERGY EFFICIENCY LEVELS 1,2 OR 3
3. FLUX DENSITIES, CURRENT DENSITIES ,
4. NO OF COILS PER LIMB,
5. TYPE OF CONDUCTOR VIZ DPC OR SE
6. TYPE OF INSULATING MATERIAL VIZ. KRAFT PAPER/EPOXY DOTTED KRAFT ETC.
7. WEIGHTS OF CORE/COIL/OIL AND SO ON AND ON
8. TEMEPERATURE RISE OF OIL/WINDINGSCONTD……….
09/01/2015 NEW DELHI 4
THRUST AREAS NEEDING ATTENTION OF REGULATORS & STAKE HOLDERS BEFORE
ENFORCING ELECTRICAL TRANSFORMERS QUALITY CONTROL ORDER,2014
9 COOLING METHODS, DESIGN & PLACEMENT OF RADIATORS
10 ELLIPTICAL TUBES, ROUND TUBES,PSR,CORRUGATED
11 SHAPE OF TANK-RECTANGULAR, ELLIPTICAL OR ROUND
12 PLACEMENT OF BUSHINGS TOP, SIDE ETC.12 PLACEMENT OF BUSHINGS TOP, SIDE ETC.
13 THICKNESS OF TANK SHEET ETC.
14 DIFFERENT COMPONENT LOSSES EVEN FOR STAR RATINGS
VIDE (CL.BI) GUIDELINES FOR CERTIFICATION AS PER IS 1180 CIRCULATED VIDE
REF. NO. CMDI(BD)/IS 1180 DT. 27.11.2014, ANY CHANGE IN ANY OF ABOVE
PARAMETERS WOULD TANTAMOUNT TO CHANGE OF DESIGN OF TRANSFORMER
AND THIS WOULD REQUIRE TYPE TESTING AGAIN.
CERTIFICATION & LICENSING ONCE GIVEN FOR THE HIGHEST RATING & ENERGY
EFFICIENCY LEVEL SHOULD BE PERMANENT & NOT SUBJECT TO CHANGE DUE TO
CHANGE IN ANY OF ABOVE PARAMETERS09/01/2015 NEW DELHI 5
THRUST AREAS NEEDING ATTENTION OF REGULATORS & STAKE HOLDERS BEFORE
ENFORCING ELECTRICAL TRANSFORMERS QUALITY CONTROL ORDER,2014
THERE HAS TO BE STANDARDISATION OF SPECIFICATIONS BY THE
REGULATORS & OTHER STAKE HOLDERS:
1. ONE UNIFORM SPECIFICATION DRAFTED JOINTLY BY BIS/REC/BEE WITH1. ONE UNIFORM SPECIFICATION DRAFTED JOINTLY BY BIS/REC/BEE WITH
CEA AS NODAL AGENCY TO BE ADOPTED.
2. MANDATE FOR ALL STAKE HOLDERS TO FOLLOW IN TOTO FOR TENDERING,
MANUFACTURE, INSPECTION & ACCEPTANCE.
3. RECOMMENDATIONS BY CONSULTANT ABPS ON QUALITATIVE
IMPROVEMENT IN MANUFACTURING PRACTICES OF DISTRIBUTION
TRANSFORMERS AND BEST O & M PRACTICES FOR UTILITIES AT THE BEHEST
OF MOP JOINTLY BY ITMA & BEE IS YET TO BE IMPLEMENTED.
09/01/2015 NEW DELHI 6
ELECTRICAL TRANSFORMERS (QUALITY CONTROL) AMENDMENT ORDER
2014 DT.14TH NOV 2014 – PROCEDURES FOR APPLYING:
APPLICATIONS SHOULD BE ACCEPTED ONLINE WITH USER FRIENDLY WEB PORTAL FOR UPLOADING DATA WITH SPECIFIC DROP DOWN MENUS.
• APPLICATION FORMS SHOULD HAVE MINIMUM REQUIRED FIELDS NECESSARY FOR REGISTRATION, CERTIFICATION & LICENSING. EXTRA FIELDS SHOULD BE DONE AWAY WITH AND MINIMUM DETAILS SOUGHT.
• AFTER PERUSAL OF THE APPLICATION IF ANY FURTHER CLARIFICATION IS REQUIRED THEN ONLY SUCH SPECIFIC QUERIES MAY BE RAISED AND DETAILS SOUGHT FROM THE APPLICANT INSTEAD OF CLOSING THE APPLICATION & RETURNING THE WHOLE FILE ALONG WITH FEES & FOR RESUBMISSION OF COMPLETE FRESH APPLICATION.
09/01/2015 NEW DELHI 7
ELECTRICAL TRANSFORMERS (QUALITY CONTROL) AMENDMENT ORDER
2014 DT.14TH NOV 2014 – GRANT OF LICENCE CLARIFICATIONS
BIS HAS BEEN KIND ENOUGH IN CLARIFYING COUPLE OF POINTS VIDE THEIR EMAIL DT 02 JAN 2015. BUT STILL THERE ARE FEW POINTS WHICH NEED CLARIFICATION
IN THE DETAILED STEP BY STEP PROCEDURE FOR GETTING BIS LICENCE
POINT NO. 2 & 3 MENTIONS THAT “THE APPLICANT WILL HAVE TO GET HIS PRODUCT TESTED IN ANY BIS RECOGNIZED LABORATORY AS PER RELEVANT STANDARDS AND THEN APPLY TO BIS FOR LICENCE”. THIS CLEARLY MEANS THAT MANUFACTURER HAS TO GET THE TYPE TESTS DONE BEFORE APPLYING FOR BIS LICENCE.
WHETHER THIS PRE TESTING OF TRANSFORMERS BEFORE APPLYING HAS TO BE DONE ON ALL THE SIZES OR THE LARGEST SIZE
09/01/2015 NEW DELHI 8
ELECTRICAL TRANSFORMERS (QUALITY CONTROL) AMENDMENT ORDER 2014
DT.14TH NOV 2014 – GRANT OF LICENCE CLARIFICATIONS
WHEREAS IN POINT NO. 5 (V) IT STATES THAT REQUISITE SAMPLE WILL BE DRAWN FOR INDEPENDENT TESTING IN BIS LAB WHICH MEANS THAT THE SAMPLE HAS TO BE TYPE TESTED AGAIN AFTER THE FACTORY INSPECTION BY BIS OFFICERS.
IS RE TESTING OF SAMPLE IN BIS LAB COMPULSORY BEFORE GRANT OF LICENCE?
TATKAL SCHEME
IN CASE IF SOMEONE APPLIES FOR TATKAL SCHEME AND HAS THE TYPE TESTS REPORTS AVAILABLE WITH HIM FOR THE SAID SIZE, HE SHOULD BE GRANTED BIS LICENCE ON THE IMMEDIATE BASIS AFTER ASSESSING THE MANUFACTURING FACILITIES WITHOUT GOING INTO ANY FURTHER TESTING ETC.
09/01/2015 NEW DELHI 9
MUCH BEFORE THIS ELECTRICAL TRANSFORMERS QUALITY
CONTROL ORDER WAS NOTIFIED: TRANSFORMERS WERE BEING
PROCURED BY DISCOMS CONFORMING TO IS 1180/2026 &
BUREAU OF ENERGY EFFICIENCY (BEE) INTRODUCED THE STAR
LABELLING PROGRAMME FOR MANUFACTURE OF ENERGYLABELLING PROGRAMME FOR MANUFACTURE OF ENERGY
EFFICIENT TRANSFORMERS WITH IS 1180 AS THE BASE.
• DISTRIBUTION TRANSFORMERS PRESENTLY UPTO 200 KVA ARE
SUBJECT TO BEE STAR LABELLING AND IT IS MANDATED BY CEA
GAZETTE TO MANUFACTURE/ PROCURE DISTRIBUTION
TRANSFORMERS WITH LOSSES EQUAL TO OR BETTER THAN
THREE STAR RATINGS.(LEVEL 1 OF BIS 1180:2014)
09/01/2015 NEW DELHI 10
FOR REDUCING MULTIPLE TESTING TIME & COST
TO THE MANUFACTURERS WHO ARE FROM THE MSME SECTOR
& MAINLY SME ‘S WITH LIMITED RESOURCES
BIS LICENCING SHOULD BE ALIGNED WITH BIS LICENCING SHOULD BE ALIGNED WITH
BEE TESTING & REGISTRATION
PROVISION SHOULD BE MADE FOR AUTOMATIC GRANTING OF
BIS LICENCE ON THE BASIS OF BEE REGISTRATION FOR THE
RATINGS ALREADY REGISTERED WITH BEE FOR STAR LABELLING
UPTO 200 KVA AS OF NOW
09/01/2015 NEW DELHI 11
ITMA MEMBERS ASSURE THIS AUGUST GATHERING THAT:-
WE ARE MANUFACTURING TRANSFORMERS CONFORMING TO INTERNATIONALSTANDARDS IN EFFICIENCY & RELIABILITY & ARE ADOPTING BESTMANUFACTURING PRACTICES & EXERCISING STRICT QUALITY CONTROL.MANUFACTURING PRACTICES & EXERCISING STRICT QUALITY CONTROL.
WE ARE COMMITTED TO USING PRIME MATERIAL BE IT CRGO OR ANY OTHERFOR PRODUCING HIGH EFFICIENCY TRANSFORMERS.
WE APPRECIATE THAT THE ELECTRICAL TRANSFORMERS QUALITY CONTROLORDER , 2014 WILL BE BENEFICIAL FOR ALL STAKE HOLDERS., HOWEVER IT ISOUR HUMBLE REQUEST THAT THE WHOLE PROCESS OF CERTIFICATION ANDLICENSING BE STREAMLINED IN THE WAKE OF OUR SUBMISSIONS EXPLAINEDEARLIER FOR EASIER & FLAWLESS IMPLEMENTATION.
09/01/2015 NEW DELHI 12
THIS TRANSFORMERS QUALITY CONTROL ORDER ORDER IS FOR ENSURING
QUALITY,RELIABILITY & DURABILITY, BUT RELIABILITY & DURABILITY OF
DISTRIBUTION TRANSFORMERS DEPENDS NOT ONLY ON QUALITY
MANUFACTURE BUT ON MANY FACTORS POST MANUFACTURING, VIZ:
• TRANSPORTATION & STORAGE• TRANSPORTATION & STORAGE
• INSTALLATION & COMMISSIONING
• OPERATION & MAINTENANCE.
NEXT FEW SLIDES SHOW THAT INSTALLATION , OPERATION AND
MAINTENANCE PROCEDURES BEING EMPLOYED ARE NOT AS PER BIS
CODES & WHICH IF NOT CHECKED WILL MAKE ALL EFFORTS OF ELECTRICAL
TRANSFORMERS QUALITY CONTROL ORDER FUTILE
09/01/2015 NEW DELHI 13
BIS CODES FOR INSTALLATION & MAINTENANCE NOT FOLLOWED
09/01/2015 NEW DELHI 14
BIS CODES FOR INSTALLATION & MAINTENANCE NOT FOLLOWED.
BRANCHES FOULING WITH HT CONNECTIONS
09/01/2015 NEW DELHI 15
BIS CODES FOR INSTALLATION & MAINTENANCE NOT FOLLOWED.
JUMBLED WIRES
09/01/2015 NEW DELHI 16
BIS CODES FOR INSTALLATION & MAITENANCE NOT FOLLOWED .
HT < WIRES CRISS CROSSING
09/01/2015 NEW DELHI 17
BIS CODES FOR INSTALLATION & MAITENANCE NOT FOLLOWED.
LOOSE CONNECTIONS CAUSING HEATING
09/01/2015 NEW DELHI 18
BIS CODES FOR INSTALLATION & MAITENANCE NOT FOLLOWED.
HUGE SIZE OF WIRE FOR HT FUSE
09/01/2015 NEW DELHI 19
BIS CODES FOR INSTALLATION & MAITENANCE NOT FOLLOWED.
OIL LEVEL NOT MAINTAINED
09/01/2015 NEW DELHI 20
• WHOLE SYSTEM SHOULD CONTRIBUTE TO QUALITY
CONTROL AND AS SUCH THE BIS CODES IS 10028 (PART II)
& (PART III) FOR INSTALLATION & MAINTENANCE OF
TRANSFORMERS SHOULD BE IMPLEMENTED & GOING TRANSFORMERS SHOULD BE IMPLEMENTED & GOING
FURTHER MAY BE SUBJECTED TO CERTIFICATION BY BIS.
• WHY SHOULD ONLY MANUFACTURERS OF SMALL
TRANSFORMERS AND WHO ARE MOSTLY FROM THE SME
SECTOR BE SINGLED OUT AND BEAR THE COST OF QUALITY
ASSURANCE FOR FACTORS BEYOND THEIR SCOPE .
09/01/2015 NEW DELHI 21
FOR TOTAL QUALITY MANAGEMENT MINISTRY OF HEAVY
INDUSTRIES & ENTERPRISES SHOULD EXTEND THIS QUALITY
CONTROL ORDER TO ALL SIZES & RATINGS OF TRANSFORMERS
INCLUDING POWER TRANSFORMERS.INCLUDING POWER TRANSFORMERS.
IMPORTS OF ALL RATINGS AND TYPES OF TRANSFORMERS
SHOULD ALSO BE SUBJECTED TO SOME BIS QUALITY CONTROL
ORDER OTHERWISE THE INDIAN SOIL WILL BE FLOODED WITH
SUBSTANDARD TRANSFORMERS AT THE COST OF THE INDIAN
TRANSFORMER MANUFACTURERS.
09/01/2015 NEW DELHI 22
TOGETHER LETS WORK FOR
ENERGY EFFICIENT , RELIABLE & DURABLE
TRANSFORMERS