MANUAL S, J & DState of Idaho Division of Building Safety
![Page 3: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/3.jpg)
Overview:
When Why & What?
Submittal Procedures
Plan Review Requirements
Inspection Requirements Summary
![Page 4: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/4.jpg)
January 1, 2019
Manual S, J & D review for NEW RESIDENTIAL HVAC permits prior
to HVAC Inspection
Inspectors will verify residential equipment installations in accordance with the “APPROVED” Manual S, J & D report
![Page 5: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/5.jpg)
2012 IRC Part V - Mechanical
•Equipment Sizing: heating and cooling equipment and appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating and cooling calculation methodologies
M1401.3
•Duct Design: duct systems serving heating, cooling and ventilation equipment shall be installed in accordance with provisions of Chapter 16 and ACCA Manual D or other approved methods
M1601.1
![Page 6: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/6.jpg)
Manual S – Equipment Selection• Design Conditions• Equipment Capacities• Static Pressures• Load Sensible Heat Ratio
Manual J – Heating & Cooling Load Calculations• Building Construction: component construction, orientation, insulation etc.• Mechanical Ventilation & Infiltration• Occupants & Appliances• Equipment & Duct Locations
Manual D – Air Distribution System• Room by Room CFM Delivery• Static Pressures & Total Effective Lengths• Mechanical Ventilation Design• Return Air Paths
![Page 7: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/7.jpg)
ACCA Approved Software Programs
AdtekAcculoads
Avenir MJ8 Editions
CarmelsoftHVAC
Cool CalcElite HVAC
Spec Pro
Wrightsoft
![Page 8: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/8.jpg)
SUBMITTAL PROCEDURES
![Page 9: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/9.jpg)
New Residential HVAC Process
New Permit
• Apply for a New Residential HVAC Permit• Email Notification from DBS to Permit Holder of Manual S, J & D
Requirement
Plan Review
• Permit Holder emails Manual S, J & D to DBS• Manual S, J & D Review Conducted• Review Correspondence: Email & eTrakit
Inspection
• Inspection may be scheduled after Manual S, J & D report is APPROVED• HVAC Inspector will have the APPROVED report through DBS Software
![Page 10: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/10.jpg)
Email Notification After Permit Issuance
![Page 12: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/12.jpg)
Review Procedures
• Allow approximately 10 business days to complete review
Report Received
• Review Fee Assessed to HVAC Permit of $25
Review Conducted • Approved – ok to
schedule inspection• Corrections
Required – fix & resubmit
Correspondence Sent
![Page 13: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/13.jpg)
Review Status Notification
Sent to the Permit Holder
EmailSearch for Permit
Plan review status, report & comments
eTrakit
![Page 14: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/14.jpg)
Status Notification via Email
![Page 15: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/15.jpg)
Status Notification: Look up on eTrakit
![Page 16: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/16.jpg)
![Page 17: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/17.jpg)
![Page 18: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/18.jpg)
All fees assessed must be paid prior to Final HVAC
inspection
Review Fee: eTrakit
![Page 19: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/19.jpg)
Resubmittals: Corrections OR Changes
Corrections Required• Notification by DBS• Make revisions• Email revised report to
DBS
Re-review Conducted• Review fee re-assessed of
$25 toward HVAC permit
Correspondence Sent• Approved – “ok” to
schedule inspection• Corrections Required – fix
& resubmit
![Page 20: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/20.jpg)
Reminders…
New Residential ONLY: “Approved” Manual S, J & D•Prior to scheduling an HVAC Inspection
HVAC Inspector will verify Installation vs. Report •Hard copies not required on the jobsite•Mechanical installation must match design
Review Fee Paid prior to the Final HVAC Inspection
![Page 21: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/21.jpg)
REVIEW REQUIREMENTS
State of Idaho
![Page 22: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/22.jpg)
Plan Review Requirements
Design Conditions
Equipment Selection
Load Calculations
House Mechanical Design
![Page 23: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/23.jpg)
Design Conditions
Design conditions can be found in ACCA
Manual J8 or ASHRAE
![Page 24: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/24.jpg)
Equipment Selection
AHRI DataAHRI Data
![Page 25: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/25.jpg)
Use OEMs: Performance Data Specifications
![Page 26: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/26.jpg)
![Page 27: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/27.jpg)
![Page 28: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/28.jpg)
AHRI Data
Heating Output Capacity Needs Adjusted
![Page 29: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/29.jpg)
Calculate Design Capacities
■ EXAMPLE: Gas Furnace
• Equipment is NOT 100% efficient
• Equipment Data Specification Sheets are required to calculation equipment outputs for Design Conditions
![Page 30: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/30.jpg)
Load Calculations
![Page 31: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/31.jpg)
Can Equipment Accommodate the Loads?
![Page 32: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/32.jpg)
Can Equipment Accommodate the Loads?
![Page 33: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/33.jpg)
Insulation
Practical R-values
Construction Types are Realistic
![Page 34: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/34.jpg)
Window u-Factor & SHGC Ratings
SHGC Indicated
u-Factor Indicated
![Page 35: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/35.jpg)
Infiltration
Part IV Table 5A of the ACCA Manual J8 provides
definitions for the following envelope tightness: Tight, Semi-Tight, Average, Semi-
Loose, Loose
![Page 36: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/36.jpg)
Mechanical Ventilation Load
2012 IRC: Table M1507.3
![Page 37: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/37.jpg)
Occupant/Appliance Loads
Occupants = # of Bedrooms + 1 @ 230
BTUs per person
Appliance BTU Load up to Designer
![Page 38: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/38.jpg)
Duct Loads
Based on Duct Design Locations
![Page 39: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/39.jpg)
Solar Orientation
House Orientation MUST be indicated
![Page 40: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/40.jpg)
House Mechanical Design
![Page 41: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/41.jpg)
Method of Mechanical Ventilation
![Page 42: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/42.jpg)
Equipment Location
![Page 43: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/43.jpg)
Code Compliant Duct Design
Examples: M1601.6 – Forced air equipment serves
only the living space and does not condition the garage.
M1602.2 – Return air locations are code compliant.
M1602.2 – Return air sized not to pull more cfm than what is supplied to the
room or area.
![Page 44: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/44.jpg)
Return Air Paths
ACCA Manual D Section 4-9
![Page 45: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/45.jpg)
Duct Velocities
![Page 46: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/46.jpg)
Duct Velocities
![Page 47: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/47.jpg)
Static Pressures
![Page 48: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/48.jpg)
Review Requirements Document
![Page 49: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/49.jpg)
Questions?
![Page 50: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/50.jpg)
INSPECTION VERIFICATION
State of Idaho
![Page 51: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/51.jpg)
Inspection Phases
Rough Inspection•Inspector Verification•Items Requiring Design Change
Final Inspection•Inspector Verification•Items Requiring Design Change
![Page 52: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/52.jpg)
Equipment
Square Footage
Windows
Ceiling Heights
Floor Design Page
ROUGH INSPECTION
![Page 53: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/53.jpg)
Equipment (If Installed at Rough Inspection)
![Page 54: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/54.jpg)
(Incorrect) Square Footage
8198
![Page 55: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/55.jpg)
(Correct) Square Footage
8198
![Page 56: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/56.jpg)
(Incorrect) Window U-Values & Solar Heat Gain Coefficient
[SHGC]
![Page 57: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/57.jpg)
(Correct) Window U-Values & Solar Heat Gain Coefficient
[SHGC]
![Page 58: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/58.jpg)
(Incorrect) Ceiling Heights
![Page 59: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/59.jpg)
(Correct) Ceiling Heights
![Page 60: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/60.jpg)
Floor Design Pages
![Page 61: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/61.jpg)
(Incorrect) Solar Orientation
![Page 62: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/62.jpg)
(Correct) Solar Orientation
![Page 63: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/63.jpg)
Floor Plan/Design
![Page 64: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/64.jpg)
Window & Exterior Door Locations
![Page 65: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/65.jpg)
Supply & Return Air Terminations
![Page 66: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/66.jpg)
Mechanical Ventilation
![Page 67: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/67.jpg)
Equipment Location
![Page 68: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/68.jpg)
Equipment
Insulation
Floor Design Page
FINAL INSPECTION
![Page 69: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/69.jpg)
Equipment
![Page 70: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/70.jpg)
Insulation
![Page 71: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/71.jpg)
Solar Orientation
![Page 72: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/72.jpg)
Supply & Return Air Terminations
![Page 73: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/73.jpg)
Inspection Verification Document
![Page 74: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/74.jpg)
Questions?
![Page 75: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/75.jpg)
Conclusion: New Process 1/1/2019
New Residential HVAC Permit Issued
Manual S, J & D report submitted & Reviewed
Inspector Verifies Installation to the Approved
Manual S, J & D Report
![Page 76: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/76.jpg)
Conclusion: Reminders
New Residential HVAC Permits ONLY
Updated Email Address
eTrakit Software Providers
Review Fee $25
Inspector Verification
![Page 77: Manual s, j & d reports · appliances shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACC Manual J or other approved heating](https://reader034.vdocuments.us/reader034/viewer/2022051900/5feef72933368b73a87578e7/html5/thumbnails/77.jpg)
DBS does NOT provide training on Software Programs…
■ See your software provider for training updates and video tutorials