Mains controller
Installation and operating guide
8/9/2019 Manual - Mains Controller (50035400_A)
http://slidepdf.com/reader/full/manual-mains-controller-50035400a 2/11
astralTM mains controllers are available in 1 and 2 gangversions and are suitable for flush or surface mounting inBS wall boxes with a minimum internal depth of 35mm andshould be mounted in dry indoor locations only.
A mains controller can provide on/off control over switchesand in addition on/off and dimming control over dimmers tooperate together as a group. Alternatively it can be used to
control a scene where the user configured light levels arerecalled to set a required lighting mood.
Up to 64 different switches and dimmers maybe controlled byeach mains controller. A 2 gang mains controller can control 2groups or scenes.
The mains controller also allows activation of the astralsystem HOLIDAY MODE feature and a system ALL-OFF functionvia its default functionality.
The mains controller also incorporates command statusindicators giving visual indication and confirmation thatany commands to other switches and dimmers have beensuccessfully received. There is also a night locator feature tohelp find the controller in the dark.
Always follow the manufacturer’s advice when using powertools, steps, ladders etc. and wear appropriate protectiveequipment such as safety goggles when drilling holes. Beforedrilling holes in walls, check for hidden electricity cables andwater pipes, and use a cable/pipe locater if in doubt.
DANGER 230 VOLTS
Always disconnect the electricity supply before commencingany work on the installation of devices.
This device should be installed by a competent personor a qualified electrician in accordance with the device’sinstallation instructions and the appropriate current nationalwiring regulations.
It is essential that all connections are made as instructed, thatcables are not stressed and that terminals are fully tightened.
The mains supply to this device must be protected by a 10Atype B or type C MCB.
MAINS CONTROLLER INSTALLATION AND OPERATING GUIDE 2
IntroductionMAINS CONTROLLER INSTALLATION AND OPERATING GUIDE 3
Safety
GROUP CONTROL AND DIMMING
When turning on a group, dimmers
will turn on at the light level they
were set to before they were
turned off.
The light levels of all dimmers in a
group will align to the same level
after any dimming operation ends.
SCENE CONTROL AND DIMMING
When turning on dimmers in a
scene they will always go to their
programmed light level for the
scene.
Dimming of all dimmers in a scene
will maintain any difference in light
level after dimming stops. The light
levels will not align.
8/9/2019 Manual - Mains Controller (50035400_A)
http://slidepdf.com/reader/full/manual-mains-controller-50035400a 3/11
Program button
and indicator
Operation button
and status indicator
Operation button
and status indicator
Operation buttons
and status indicators
Program button
and indicator
Inc/Asc Exc/Dis
MAINS CONTROLLER INSTALLATION AND OPERATING GUIDE 4
Operation
Each channel of the mains
controller is capable of controlling
a group or scene containing up
to 64 other switches or dimmers.
However the product cannot
control more than 64 other
switches and dimmers in total.
2 GANG PRODUCTS
A 2 gang mains controller has2 sets of operation buttons and
status indicators, one for each
channel.MODULE WITH
FASCIA REMOVED
Short press ON / SET SCENE
Long press DIM UP
Fascia release clip
Short press OFF
Long press DIM DOWN
Inc/Asc Exc/Dis
1 2
Each channel button on the mains
controller includes a command
status that illuminates after each
operation as follows:
FLASH RED 1 TIME
Device not included in the system
FLASH GREEN 3 TIMES
Command received by all target switches and dimmers
FLASH RED 3 TIMES
Command not received by all target switches and dimmers
BLUE LOW INTENSITYNight locator feature, visible in low light conditions
SWITCHES BETWEEN HIGH AND LOW LEVEL BLUE EVERY SECOND
Holiday mode active
MAINS CONTROLLER INSTALLATION AND OPERATING GUIDE 5
Status indicators
8/9/2019 Manual - Mains Controller (50035400_A)
http://slidepdf.com/reader/full/manual-mains-controller-50035400a 4/11
The default functionality will
be over-ridden as soon as any
association is created on
channel 1 of the product.
To restore the default functionality,
delete all associations on
channel 1, (see pages 14 - 15).
ACTIVATING HOLIDAY MODE
To activate holiday mode press
and hold down the bottom button
on channel 1 for over 1 second.
DE-ACTIVATING HOLIDAY MODE
Holiday mode is cancelled either
by a short press the bottom part
of the rocker on channel 1 or by
operating any switch or dimmer in
the system.
ALL-OFF
The system ALL-OFF command is
activated by a long press of the
top part of the rocker on channel 1.
MAINS CONTROLLER INSTALLATION AND OPERATING GUIDE 6
Holiday mode
Holiday mode is an occupation
simulation feature built into the
astralTM lighting control system
products.
When holiday mode is activated,
astralTM switches and dimmers
will automatically simulate their
operation over the previous 24
hour period. This will continue untilholiday mode is cancelled.
ACTIVATING HOLIDAY MODE
Holiday mode can only be activated
using the default functionality on
channel 1 on an astralTM mains or
battery controller.
CANCELLING HOLIDAY MODE
Holiday mode can be cancelled
using either the default functionality
on channel 1 of a mains or battery
controller or by operating any
astralTM switch or dimmer.
System ALL-OFF
Long press
System ALL-OFF
Long press
Holiday mode
Long press ON
Short press OFF
Holiday mode
Long press ON
Short press OFF
MAINS CONTROLLER INSTALLATION AND OPERATING GUIDE 7
Mains controller default functionality
1 2
1
8/9/2019 Manual - Mains Controller (50035400_A)
http://slidepdf.com/reader/full/manual-mains-controller-50035400a 5/11
The mains controller is suitable for
use with astralTM dimmer fascias
only. Only fit a 1 gang fascia to a
1 gang mains controller and a 2
gang fascia to a 2 gang mains
controller.
FITTING THE FASCIA
Holding the fascia at a slight angle
to the module, locate the 2 hooks
on the back of the fascia into the
holes on the top of the module.
Gently push the fascia up and then
push home along the bottom edge
until the clip snaps home securing
the fascia in position.
REMOVING THE FASCIA
Press the release clip in the bottom
edge to the module and carefully
release the fascia at the bottom edge.
Pull the fascia downwards to
disengage the 2 hooks before fully
removing the fascia.
N 2 1L
N
L
Supply
MAINS CONTROLLER INSTALLATION AND OPERATING GUIDE 8
Fitting and removing fasciasMAINS CONTROLLER INSTALLATION AND OPERATING GUIDE 9
Installation
1 Strip back the outer cable sheath
and trim the inner cables to
length. Carefully strip the inner
cable insulation to expose 8mm
of wire.
2 Connect the Live and Neutral
cables to the switch as shown in
the diagram:
Live = brown Neutral = blue
NOTE Some countries and
existing installations may also
use the following cable colours:
Live = red
Neutral = black
3 Any earth wires must be suitably
terminated and fitted with
yellow/green insulating sleeving.
4 Carefully push the wired unit into
the back box, ensuring cables are
not trapped or pinched.
5 Secure the device to the wall box
using the fixing screws provided.
NOTE Do not over tighten the
fixing screws as this may cause
damage or distortion to the
device that could impair normal
operation or fitting the fascia.
DO NOT USE ELECTRIC SCREWDRIVERS
OR POWER TOOLS
220-240V
50Hz
IMPORTANT The mains supply must
be protected by a 10A class B or
C MCB.
8/9/2019 Manual - Mains Controller (50035400_A)
http://slidepdf.com/reader/full/manual-mains-controller-50035400a 6/11
To add the mains controller into
an existing system please refer
to your system programming
guide for instructions on ‘adding a
product to an existing system’.
S y s te m p rog ra
m m i ng g u ide
To install the entire system for
the first time, follow the astralTM
quick start guide.
MAINS CONTROLLER INSTALLATION AND OPERATING GUIDE 10
Programming the controller into a new systemMAINS CONTROLLER INSTALLATION AND OPERATING GUIDE 11
Programming the controller into an existing system
Q u i c k s ta r t g u i
de
8/9/2019 Manual - Mains Controller (50035400_A)
http://slidepdf.com/reader/full/manual-mains-controller-50035400a 7/11
STEP 3
CONFIGURE THE MAINS CONTROLLER
FOR GROUP OR SCENE CONTROL
The mains controller is factory-set
to control a group. To control a
scene it must first be put it into
scene control mode.
NOTE Any associations must be
deleted from the controller beforeyou will be allowed to change
control modes (see page 14 - 15).
1 Hold down the Inc/Asc button on
the controller for 8 seconds until
the indicator starts flashing yellow
and then release the button.
2 The indicator will flash 3 times to
show the new control mode:
Green = Group control
Red = Scene control
If necessary repeat until the
required control mode is achieved.
STEP 4
ASSOCIATE WITH SWITCHES AND
DIMMERS TO CREATE GROUPS AND
SCENES
1 Refer to your system
programming guide for
association.
2 When you need to select the
mains controller, press theappropriate channel operation
button on the front of the mains
controller.
3 The status indicator will flash
green 3 times if the association
has been successful.
THERE ARE 4 STEPS TO ADDING
THE MAINS CONTROLLER TO AN
EXISTING SYSTEM
Step 1 Inclusion
Step 2 Replication
Step 3 Configuration
Step 4 Association
STEP 1
INCLUDE THE MAINS CONTROLLER INTO
THE SYSTEM
1 Refer to your system
programming guide for inclusion.
2 When you need to select the
mains controller to include it into
the system press any button on
the front.
3 If the mains controller is included
successfully all indicators on the
mains controller will flash green
3 times.
STEP 2
REPLICATE THE ROUTING TABLE TO ALL
CONTROLLERS
After the controller is included
into the system you must update
the routing table in all system
controllers.
1 Refer to your system
programming guide for replication.
2 Put the mains controller into
replicate receive mode, press the
Inc/Asc button for 2 seconds until
the indicator illuminates yellow.
3 The indicator will flash yellow
while the routing table is updated
and then turn green for 4 seconds
if replication has been successful.
Inc/Asc Exc/Dis
MAINS CONTROLLER INSTALLATION AND OPERATING GUIDE
Programming the controller into an existing system 13
8/9/2019 Manual - Mains Controller (50035400_A)
http://slidepdf.com/reader/full/manual-mains-controller-50035400a 8/11
DISASSOCIATION
Allows you to remove a switch
or dimmer from a group or scene
controlled from the mains controller.
1 Refer to your system manual and
put the primary controller into
disassociate mode.
2 When you need to select the
mains controller, press theappropriate operation button on
the front.
3 The status indicator will flash
green 3 times if the association
has been successfully removed.
DELETING A COMPLETE GROUP/SCENE
ON THE MAINS CONTROLLER
1 Remove the decorative fascia.
2 Hold down the Exc/Dis button
for 8 seconds until the indicator
illuminates green and then release
the button.
3 While the Exc/Dis indicator is
illuminated green, press and
release the channel operation
button on the mains controller
that controls the group or scene
to be deleted.
4 The Exc/Dis and selected channel
status indicator will flash green 10
times while the selected group or
scene is deleted.
MAINS CONTROLLER INSTALLATION AND OPERATING GUIDE
Other programming functions
EXCLUDING THE MAINS CONTROLLER
FROM THE SYSTEM
1 Remove the decorative fascia.
2 Refer to your system
programming guide and put the
primary controller into exclude
mode.
3 Press the Exc/Dis button on the
mains controller twice within
1 second.
4 If the mains controller is excluded
successfully all indicators will
flash red 3 times.
MAINS CONTROLLER NVM RESET
WARNING Use NVM Reset with
extreme caution and only prior
to resetting all products and
completely rebuilding the network.
1 Remove the decorative fascia.
2 Hold down the Exc/Dis button
for 15 seconds until the indicator
illuminates red. Release the
button and the indicator will start
flashing red.
3 While the indicator is flashing red
press Exc/Dis for 2 seconds until
the indicator turns green and then
release the button.
4 All indicators will flash red 10
times while the mains controller
is reset and factory settings are
restored.
15
Inc/Asc
Inc/Asc
Inc/Asc
Inc/Asc
8/9/2019 Manual - Mains Controller (50035400_A)
http://slidepdf.com/reader/full/manual-mains-controller-50035400a 9/11
FASCIA DOES NOT FIT THE CONTROLLER
• Incorrect fascia being fitted.
You can only fit a 1 gang dimmer
fascia to a 1 gang mains controller
module and a 2 gang fascia to
a 2 gang module. You cannot fit
switch fascias to mains controller
modules.
CONTROLLER DOES NOT OPERATE
• No power to product.
Check other devices on the same
circuit are receiving power.
Check connections and wiring.
• Fuse or MCB blown.
Check and rectify fault before
replacing fuse or resetting the
MCB.
STATUS INDICATORS FLASH YELLOW
ONCE WHEN CONTROLLER IS OPERATED
• The controller has not yet been
included into a network.
CANNOT ADD THE DEVICE TO A SYSTEM
• The controller is already part
of another system. Reset the
controller first using the exclusion
process before trying again.
CANNOT ADD A SWITCH OR DIMMER TO
A GROUP/SCENE CONTROLLED BY THE
CONTROLLER
• Too many switches and dimmersalready associated. You can only
control 64 other switches or
dimmers.
CANNOT SWITCH BETWEEN GROUP AND
SCENE CONTROL
• The controller still has an
association on one or more
channels and controls another
switch or dimmer. Delete all
groups/scenes first and then
change control mode.
CANNOT ACTIVATE HOLIDAY MODE
FROM CHANNEL 1
• There is an association on
channel 1 to another switch or
dimmer. Delete all associations
on channel 1 to restore the
controllers default functionality
to channel 1.
MAINS CONTROLLER INSTALLATION AND OPERATING GUIDE 16
Troubleshooting
Suitable for flush or surface mounted
in dry interior locations only.
• Protection IP4x
• Wall box depth 35mm minimum
• Mains supply 220-240Vac / 50Hz
• Supply protection 10A MCB, type B or C
• Power consumption <1W
• Operating temperature 0°C to +45°C
MAINS CONTROLLER INSTALLATION AND OPERATING GUIDE 17
Specifications
RF OPERATING FREQUENCY
• Malaysia 868.1MHz
• UK/Singapore/UAE 868.4MHz
• Hong Kong 919.8MHz
Typical RF range 75m open field
The RF range quoted above is in
open field conditions. This rangewill be reduced when mounted in
a property by any walls and objects
between the transmitting and
receiving devices by an amount
dependant upon the number
of walls and their construction.
However, the effects of this will be
minimized by the mesh and routing
capabilities of the astral system.
8/9/2019 Manual - Mains Controller (50035400_A)
http://slidepdf.com/reader/full/manual-mains-controller-50035400a 10/11
MAINTENANCE AND DISPOSAL
The product may be cleaned with
a dry soft lint free cloth. Do not
use water or any abrasive, solvent
based or aerosol cleaners as this
may damage, discolour or affect the
finish and safety of the product.
At the end of their useful life the
packaging, product and whereapplicable batteries, should be
disposed of via a suitable recycling
centre. Do not dispose of with your
normal household waste. Do not
burn.
COMPATIBILITY
astralTM products are tested and
certified as Z-Wave® compliant and
are designed to work with other
manufacturers Z-Wave® compliant
and interoperable products.
Z-Wave® products of other types
and applications can be added to
the system and will act as repeaters
if they support this functionality.
This enables the system to grow
and expand to other application
areas as your needs develop.
This product is supplied preset to
Low Power Configuration Mode.
PRODUCT ADVICE
If you require advice on the astralTM
system please contact the technical
service helpline on
Singapore 1800 461 6333
Malaysia 1800 88 4507
Hong Kong 2953 6379
UK and Ireland 01268 563720email [email protected]
UAE (+971) 4 807320
MAINS CONTROLLER INSTALLATION AND OPERATING GUIDE
Additional information
GUARANTEE
MK Electric Limited undertakes to
replace or repair at its discretion
goods (excluding batteries) should
they become defective within
18 months solely as a result of
faulty materials and workmanship.
Understandably if the product has
not been installed, operated or
maintained in accordance with the
instructions, has not been used
appropriately or if any attempt has
been made to rectify, dismantle
or alter the product in any way the
guarantee will be invalidated.
The guarantee states MK Electric
Limited’s entire liability. It does not
extend to cover consequential loss
or damage or installation costs
arising from the defective product.
This guarantee does not restrict,
infringe or in any way affect the
normal statutory or other rights of
the consumer.
R&TTE DECLARATION
MK Electric Limited hereby declares
that this wirefree lighting control
product is in compliance with the
essential requirements and other
relevant provisions of the European
Radio and Telecommunications
Terminal Equipment (R&TTE)
directive, 1999/5/EC.
DESIGN OWNERSHIP
MK Electric Limited wishes to make
it clear that it owns all the original
designs of the products that it
manufactures (whether or not listed
in this leaflet) and that it will take all
necessary action in any part of the
world against any party found to be
manufacturing, distributing, selling
or otherwise dealing with any article
which infringes the Company’s
intellectual property in its own
products, or any other right of the
company.
MK is a registered trademark of
Novar ED&S
Zensys and Z-Wave is a registered
trademark of Zensys Ltd
Patents applied for and pending
Registered designs
19
8/9/2019 Manual - Mains Controller (50035400_A)
http://slidepdf.com/reader/full/manual-mains-controller-50035400a 11/11
50035400.001 Ed.A
MK Electric Ltd
The Arnold Centre, Paycocke Road, Basildon,
Essex SS14 3EA United Kingdom
MK Electric (Middle East)
Honeywell ME, FZE, P.O. Box 18530, Jebel All,
Dubai U.A.E.
MK Electric (Singapore) Pte Ltd
8 Pandan Crescent, UE Tech Park, #01-06
(LL4), Singapore 128464
MK Electric (Malaysia) Sdn Bhd
(Co. No. 39068-A). Komplek Perusahaan LTAT,
Jalan Pengapit 15/19, 40000 Shah Alam,
Selangor Darul Ehsan, Malaysia
MK Electric (China) Ltd
25/F, Honeywell Tower, Olympia Plaza,
255 King’s Road, North Point, Hong Kong
Telephone +44 (0)1268 563000
Fax +44 (0)1268 563404
Email [email protected]
Telephone (+971) 4 807 3200
Fax (+971) 4 881 5733
Telephone (+65) 6461 6333
Fax (+65) 6461 6336 / 6338
Telephone (+603) 5519 4507
Fax (+603) 5510 8867
Telephone (+852) 2331 9133
(+852) 2834 1988
Fax (+852) 2151 9465
www.mkelectric.co.uk
Novar ED&S Ltd (A Honeywell Company)
Arlington Business Park, Bracknell, Berkshire RG12 1EB UK
© Novar ED&S Limited 2008 All rights reserved