manual for pms

Upload: jon-lopez

Post on 02-Jun-2018

228 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/11/2019 Manual for Pms

    1/76

    MANUAL FOR PMS

  • 8/11/2019 Manual for Pms

    2/76

    Zhejiang Xinya Electric Development Co.,Ltd

    Tableofcontents

    1. SystemDescription....................................................................................................................................4

    2. Hardwarespecification..............................................................................................................................6

    2.1 PLC(SIMATICS7200Programmablecontroller)...............................................................................6

    2.1.1 TechnicalSpecifications..............................................................................................................6

    2.1.2CPU

    specifications

    ............................................................................................................................

    7

    2.1.2 Digitalexpansionmodulesspecifications.................................................................................12

    2.1.3 Analogexpansionmodulesspecifications................................................................................18

    2.2 Synchronizer.....................................................................................................................................20

    2.2.1 Description............................................................................................................................20

    2.2.2Technicalspecifications:.................................................................................................................21

    2.2.3Selfmonitoring:..............................................................................................................................21

    2.2.4Settingandindication.....................................................................................................................22

    2.2.5Connectiondiagram.......................................................................................................................22

    2.3

    Transducers (YOKOGAWA)...........................................................................................................

    24

    3. PMS functions........................................................................................................................................29

    3.1Dieselgeneratormanuallycontrol........................................................................................................29

    3.1.1Dieselgeneratormanuallystart&ACBclosuretodeadbus.........................................................29

    3.1.2Dieselgeneratormanuallystart&synchro....................................................................................29

    3.1.3Dieselgenertormanuallyloadshift&ACBopen,Enginestop......................................................30

    3.2Dieselgeneratorsemiautocontrol.......................................................................................................30

    3.2.1Dieselautomaticallystart&ACBclosuretodeadbus...................................................................30

  • 8/11/2019 Manual for Pms

    3/76

    Zhejiang Xinya Electric Development Co.,Ltd

    3.4.3ShaftgeneratorautomaticallyloadshifttoD/G&deexcite. ....................................................32

    3.5.After

    subarea

    power

    supply,

    manually

    synchro

    by

    bus

    tie

    breaker

    ....................................................

    33

    3.5.1Aftersubareapowersupplydividually,manuallysynchrobySDBT1bustiebreaker...................33

    3.5.2Aftersubareapowersupply,manuallysynchrobySDBT2bustiebreaker...................................33

    3.5.3Aftersubareapowersupply,manuallysynchrobyDDBTbustiebreaker.....................................33

    3.6.Aftersubareapowersupply,semiautosynchrobybustiebreaker..................................................33

    3.6.1Aftersubareapowersupply,semiautosynchrobySDBT1bustiebreaker..................................33

    3.6.2Aftersubareapowersupply,semiautosynchrobySDBT2bustiebreaker..................................33

    3.6.3Aftersubareapowersupply,semiautosynchrobyDDBTbustiebreaker...................................33

    3.7Generatorautomaticallycontrol...........................................................................................................34

    3.7.1

    One

    shaft

    generator

    power

    supply,

    Generator

    ACB

    abnormal

    trip

    and

    blackout

    .........................

    34

    3.7.2Onedieselgeneratorsupplypower,GeneratorACBabnormaltripandblackout........................34

    3.7.3Oneshaftgeneratorsupplypower,busbarabnormal...................................................................35

    3.7.4Onedieselgeneratorsupplypower,busbarabnormal..................................................................35

    3.7.5Dieselgeneratorautomaticallyloadshift&ACBopen,Enginestopduetolightload..................36

    3.7.6Gen.

    Eng.

    automatically

    start

    &

    synchro

    due

    to

    heavy

    load

    ..........................................................

    36

    3.7.7Pretripnonessentialconsumer.....................................................................................................36

    3.7.8Heavyconsumerstartrequest.......................................................................................................36

    3.7.9 Dynamic positioning DP2..............................................................................................................38

    4.PMSwiringdiagrams...................................................................................................................................38

  • 8/11/2019 Manual for Pms

    4/76

    Zhejiang Xinya Electric Development Co.,Ltd

    1. System Description

    This power management system (PMS) is performed by a computerized generator

    automatic control functionsPLC CONTROL SYSTEM: generator voltage monitoring,

    bus voltage and frequency monitoring, generator synchronizing (Paralleling), load sharing

    control and load shift control.

    The PMS has the following features:

    The PMS is an extremely easy to us and highly reliable total system.

    ThePMSis composed of the one touch screen and PLC, Synchronizer, transducer. And

    each device are installed in switchboard under common section.ThePMSis responsible for overall management of the generating plant.

    It has an automatic synchronizing/automatic load sharing function, automatic generator

    start and changeover commands, and power management functions.

    It is used to automate plants with unattended machinery rooms and performs efficient

    power management for super-rationalization plants.

    System design based on two principles; manual control should override automatic

    controlandcontrol system should be isolated or separated from safety and protective

    systems, so that the safety of the ship's electric power system and the ship herself will

    be secured even if the worst happens to the control system.

    The PMScontrols generating plant centralized so that extremely high level of power

    supply reliability is achieved.

  • 8/11/2019 Manual for Pms

    5/76

    Zhejiang Xinya Electric Development Co.,Ltd

    Hardware configuration: SIMATIC S7200 ,Synchronizer,transducer,LCD(SIMATIC HMI Smart 700 IE)

    PMS1:

    CPU

    MODULE

    6ES7 226

    I/O

    MODULE

    6ES7223

    I/O

    MODULE

    6ES7223

    AI

    MODULE

    6ES7231

    AI

    MODULE

    6ES7231

    SIMATIC S7200 series:

    CPU: 6ES7226 24VDC 24 inputs/16 outputs Qty:1

    I/O: 6ES7223 24VDC 32 inputs/32 outputs Qty: 2

    AI: 6ES7231 4 inputs Qty: 2

    Transducers

    Power transducer: Qty: 2

    Voltage transducer: Qty:2

    Frequency transducer: Qty:2

    PMS2:

    CPU

    MODULE

    6ES7 226

    I/O

    MODULE

    6ES7223

    I/O

    MODULE

    6ES7223

    AI

    MODULE

    6ES7231

    AI

    MODULE

    6ES7231

    SIMATIC S7200 series:

    CPU: 6ES7226 24VDC 24 inputs/16 outputs Qty:1

    I/O: 6ES7223 24VDC 32 inputs/32 outputs Qty: 2

    AI: 6ES7231 4 inputs Qty: 2

    Transducers

    Power transducer: Qty: 3

    Voltage transducer: Qty:3

    Frequency transducer: Qty:2

    Paralleling and transducer

    Synchronizer: Qty:1

  • 8/11/2019 Manual for Pms

    6/76

  • 8/11/2019 Manual for Pms

    7/76

    Zhejiang Xinya Electric Development Co.,Ltd

    2.1.2 CPU specifications

  • 8/11/2019 Manual for Pms

    8/76

    Zhejiang Xinya Electric Development Co.,Ltd

  • 8/11/2019 Manual for Pms

    9/76

    Zhejiang Xinya Electric Development Co.,Ltd

  • 8/11/2019 Manual for Pms

    10/76

    Zhejiang Xinya Electric Development Co.,Ltd

  • 8/11/2019 Manual for Pms

    11/76

    Zhejiang Xinya Electric Development Co.,Ltd

  • 8/11/2019 Manual for Pms

    12/76

    Zhejiang Xinya Electric Development Co.,Ltd

    2.1.2 Digital expansion modules specifications

  • 8/11/2019 Manual for Pms

    13/76

    Zhejiang Xinya Electric Development Co.,Ltd

  • 8/11/2019 Manual for Pms

    14/76

    Zhejiang Xinya Electric Development Co.,Ltd

  • 8/11/2019 Manual for Pms

    15/76

    Zhejiang Xinya Electric Development Co.,Ltd

  • 8/11/2019 Manual for Pms

    16/76

    Zhejiang Xinya Electric Development Co.,Ltd

  • 8/11/2019 Manual for Pms

    17/76

    Zhejiang Xinya Electric Development Co.,Ltd

  • 8/11/2019 Manual for Pms

    18/76

    Zhejiang Xinya Electric Development Co.,Ltd

    2.1.3 Analog expansion modules specifications

  • 8/11/2019 Manual for Pms

    19/76

    Zhejiang Xinya Electric Development Co.,Ltd

  • 8/11/2019 Manual for Pms

    20/76

    Zhejiang Xinya Electric Development Co.,Ltd

  • 8/11/2019 Manual for Pms

    21/76

    Zhejiang Xinya Electric Development Co.,Ltd

    The synchroniser measures the busbar and generator voltages and frequencies and

    compares these, plus compares their phase angles. It controls the generator frequency,

    till it matches the busbar frequency. In order to determine phase accordance between the

    generator and the busbar, the synchroniser calculates a phase angle advance based on

    the circuit breaker closing time and the slip frequency. When the phase difference is

    within this olerance the synchroniser transmits a closing signal for the generator

    circuit breaker allowing time for this to close.

    2.2.2 Technical specifications:

    Supply volt. (Un): 400VAC/450VAC20%

    (MAX. 3.5VA)

    Meas. voltage: 400VAC/450VAC

    (

  • 8/11/2019 Manual for Pms

    22/76

    Zhejiang Xinya Electric Development Co.,Ltd

    2.2.4 Setting and indication

    MARKED SETTING OF RANGE

    TN Control pulse length 25~500ms

    XP Proportional band 0.25~2.5HZ

    FRE Slip frequency 0.1~0.5HZ

    VOLTAGE Acceptable voltage difference 2~12%of UBB

    BREAKER Breaker closure time 20~200ms

    MARKED LEDs Light

    UG Generator voltageGreen,

    when value is within the

    acceptable range

    Switched off, if outside this range

    UBB Busbar voltage

    f Frequency difference

    U Voltage difference

    SG Increase speed (frequency)

    Yellow,

    when relay is activatedSG Decrease speed (frequency)

    SYNC Synchronising

    2.2.5 Connection diagram

    1 3 8 9 10

    24 26 29 30 33 34 35 36 39

    XY09-SYN

    X1 X2

    L1 L2BB

    L1 L2

    RELAY TO

    CIRCUIT BREAKER

    AUX SUPPLY

    L1

    L2

    L3

    ~ ~

    SYNC

    BB

    L1

    L2

    L3

    G G

    GENERATOR

    U INH f

    40 41

    17 18

    38

    SG

    SPEED

    +Sta -

  • 8/11/2019 Manual for Pms

    23/76

    Zhejiang Xinya Electric Development Co.,Ltd

    Terminal no. Description/action

    13

    X1/X2Input for supply voltage

    8,9,10 Relay contact for circuit breaker. On time 400 ms

    17,18

    Sta

    Status output, activated (closed) when the supply voltage is

    connected and the unit is working correctly

    24, 26

    BB/L1 BB/L2Input for busbar voltage measurement.This input becomes

    active when the voltage level exceeds 80% of nominal voltage

    29, 31

    G/L1 G/L2

    Input for generator voltage measurement. When the voltagelevel on this input exceeds 60% of nominal voltage, the

    XY09-SYN is activated and the regulator outputs (SG) become

    active. Note that with an auxiliary contact on the generator

    circuit breaker this function can be used for resetting of the

    XY09-SYN after synchronisation and hereby deactivation of

    the SG outputs. This function allows the supply voltage to be

    connected at any time

    34,("INH")

    May be connected to a potential-free N/O contact. When thiscontact is activated, the XY09-SYN will not transmit a closing

    signal (terminals 9 and 10), but the SYNC LED will be lit

    when the sync. pulse is transmitted. This function can be

    used for testing purposes.

    35, ("") Common earth terminal for the above input/output

    38, 39 Relay

    contacts "SG" Relay contact for increase of the speed

    40, 41 Relay

    contacts "SG"Relay contact for decrease of the speed

    NOTE:

    Relay contacts

    Relays (SG) should always be connected via external aux.

    relays when a DC pilot motor is applied. A transient

    suppressor should always beconnected across the relay coil

    of the external relays

  • 8/11/2019 Manual for Pms

    24/76

    Zhejiang Xinya Electric Development Co.,Ltd

    2.3Transducers (YOKOGAWA)

    2.3.1 Technical specifications

  • 8/11/2019 Manual for Pms

    25/76

    Zhejiang Xinya Electric Development Co.,Ltd

  • 8/11/2019 Manual for Pms

    26/76

    Zhejiang Xinya Electric Development Co.,Ltd

    2.4LCD (SIMATIC HMI Smart 700 IE)

  • 8/11/2019 Manual for Pms

    27/76

    Zhejiang Xinya Electric Development Co.,Ltd

  • 8/11/2019 Manual for Pms

    28/76

    Zhejiang Xinya Electric Development Co.,Ltd

  • 8/11/2019 Manual for Pms

    29/76

    Zhejiang Xinya Electric Development Co.,Ltd

    3. PMS functions

    3.1 Diesel generator manually control

    3.1.1 Diesel generator manually start & ACB closure to dead busThe following describes, as an example, steps to place DG1 onto a dead bus.

    Turn the DG1s mode select switch on the No.1 diesel generator panel to MANU position,

    check the preparation for starting the generator engine has been made satisfactory(the

    READY TO START indicator lamp is turned on).

    Press the ENGINE START pushbutton on the No.1 diesel generator to start gensets, as the

    diesel engine accelerates to synchronous speed, the generator voltage will build up and the

    RUNNING indicator lamp on the No.1 diesel generator panel will be turned on.

    Check if the required generator voltage and frequency is reached with the voltmeter and

    frequency meter for No.1 diesel generator panel, operating theVOLTMETER SELECT

    switch on the No.1 diesel generator panel is set to each phasetophase position. If the

    generator voltage is other than specified, adjust it with the manual voltage regulator controls.

    If the frequency is higher than the rated value, turn the GOVERNORcontrol switch to

    LOWER position to decrease the generator frequency and adjust it to the rated value. Ifthe frequency is lower than the rated value, adjust it to the rated value by setting the

    GOVERNORcontrol switch to RAISE position.

    Check the bus voltage and frequency by the double voltage and frequency meters on the

    synchro panel, and the meters indicate zero. On confirmation of this, presss the ACB

    CONTROL pushbutton on the No.1 diesel generator panel or synchro panel to CLOSE to

    place No.1 diesel generator onto a dead bus C.

    3.1.2 Diesel generator manually start & synchro

    The following describes, as an example, steps to place No.2 diesel generator onto a live bus

    served by No.1 diesel generator.

    Turn the DG2s mode select switch on the No.1 diesel generator panel to MANU position,

    check the preparation for starting the generator engine has been made satisfactory(the

    READY TO START indicator lamp is turned on), press the ENGINE START pushbutton onthe No.2 diesel generator to start gensets, as the diesel engine accelerates to synchronous

    speed, the generator voltage will build up and the RUNNING indicator lamp on the No.2

    diesel generator panel will be turned on.

    Compare the incoming generator voltage with the bus voltage by charging the switch and

  • 8/11/2019 Manual for Pms

    30/76

    Zhejiang Xinya Electric Development Co.,Ltd

    generator ACB to occur at the exact instant of synchronism. Press the ACB CLOSE

    pushbutton to closeNo.2 diesel generator a little prior to the synchronism.

    When two generators are on line, you must operate theirGOVERNORcontrol switchessimultaneously to RAISE (frequency up) or to LOWER (frequency down),

    operation of only one switch transfers load from one generator to the other rather than

    changing the frequency.

    3.1.3 Diesel genertor manually load shift & ACB open, Engine stop

    a. The following describes, as an example, the case where No.1 diesel generator is removed

    from the bus when DG1 and DG2 are on line. Adjust the DG1s GOVERNOR control switch to

    LOWER and DG2s to RAISE.

    This lightens the kW load on No.1 diesel generator and increases the kW load on No.2 diesel

    generator i.e., load on No.1 diesel generator is shifted to No.2 diesel generator.

    When the load on No.1 diesel generator is reduced to about 5% of its rated kW output(check

    the power meter), press the ACB OPEN pushbutton to remove No.1 diesel generator from

    the bus.Then, adjust the bus frequency to the rated value as necessary by operating DG2s

    GOVERNORcontrol switch toLOWERor toRAISE.

    Press the ENGINE STOP pushbutton to stop DG1 manually.

    b. The following describes, as an example, the case where No.1 diesel generator is removed

    from the bus when DG1 and SG1 are on line in short time. Adjust the DG1s GOVERNOR

    control switch to LOWER.

    When the load on No.1 diesel generator is reduced to about 5% of its rated kW output(check

    the power meter), press the ACB OPEN pushbutton to remove No.1 diesel generator from

    the bus.

    Press the ENGINE STOP pushbutton to stop DG1 manually.

    3.2 Diesel generator semiauto control

    3.2.1 Diesel automatically start & ACB closure to dead busThe following describes, as an example, steps to place DG1 onto a dead bus.

    Turn the DG1s mode select switch on the No.1 diesel generator panel to AUTO position,

    check the preparation for starting the generator engine has been made satisfactory(the

    READY TO START indicator lamp is turned on).

  • 8/11/2019 Manual for Pms

    31/76

    Zhejiang Xinya Electric Development Co.,Ltd

    While the No.1 diesel generator supply the power to the main bus, turn the MODE

    SELECT switch to AUTO position on the NO.2 diesel generator panel, confirm No.2

    diesel generator is remote and ready, Press the AUTO START/SYNCHRO pushbuttonon the No.2 diesel generator panel to start the diesel engine, at the same time, the DG2

    AUTO START/SYN indicator lamp is turned on , after the No.2 diesel generator running.

    While voltage establish to rated value, and busbar is alive, PMS gives automatic synchro

    command, while meets synchro condition, synchronizer gives automatic close command,

    then generator supplies power to busbar in parallel, load sharing automatically, at the

    same time, the DG2 AUTO START/SYN indicator lamp is turned off.. If start fail/voltage

    not established/ACB nonclose/auto synchro fail, PMS gives alarm.

    3.2.3 Diesel generator automatically load shift & ACB open, Engine stop

    The following describes, as an example, the case where No.1 diesel generator is removed

    when DG1 and DG2 are in parallel operation.

    The MODE SELECTswitch on the each diesel generator panel is set to AUTO

    position .Press the LOAD SHIFT pushbutton on the No.1 diesel generator panel, at the same

    time, the LOAD SHIFT indicator lamp is turned on, PMS gives automatic load transfer

    command, adjust the No.1 diesel generator speed automatically, while the No.1 diesel

    generator power is less than 5% rated power, PMS gives automatic open command, the

    No.1 diesel generator disconnects, at the same time, the LOAD SHIFT indicator lamp is

    turned off. After 3 minutes (adjustable), No.1 diesel generator stops automatically, at the

    same time, the LOAD SHIFT indicator lamp is turned on , then the engine stopped, at

    the same time the LOAD SHIFT indicator lamp is turned off.

    Note: if the load on the generator to remain on line is expected to reach 90% or more if its

    rated kW output as a result of automatic laod shift control operation the pushbutton

    LOAD SHIFT has no effect.

    3.3 Shaft generator manually control3.3.1 Shaft generator manually excite & ACB closure to dead bus

    The following describes, as an example, steps to place SG1 onto a dead bus.

    Turn the MODE SELECT switch on the No.1 shaft generator panel to MANU position,

    confirm the main engine is constant speed, namely in shaft generator mode. Turn the select

  • 8/11/2019 Manual for Pms

    32/76

    Zhejiang Xinya Electric Development Co.,Ltd

    predefine gensets(SG1), adjust DGs speed and voltage manually, look over meter and

    synchronoscope, while meets synchro condition, press the ACB CLOSE pushbutton on the

    No.1 shaft generator panel or Synchro panel for SG2 , then generator supplies power tobusbar in parallel. If need subarea power supply, open the relevant bustie breaker.

    3.3.3 Shaft generator manually load shift & deexcite

    The following describes, as an example, the case where No.1 shaft generator is removed from

    the bus when SG1 and DG are on line in short time. Adjust the DGs GOVERNOR control

    switch to RAISE.

    Turn the MODE SELECT switch on the No.1 shaft generator panel to MANU position, adjust

    the D/Gs governor switch to RAISE, check DG1s power meter, while the DG1s power is less

    than 5% rated power, press ACB OPEN pushbutton on the No.1 shaft generator panel or

    synchro panel, the ACB disconnected, then turn the select switch of EXCITATION to OFF

    position, the SG1 deexcited.

    3.4 Shaft generator semiauto control

    3.4.1 Shaft generator automatically excite & ACB closure to dead busThe following describes, as an example, steps to place SG1 onto a dead bus.

    Turn the MODE SELECT switch on the No.1 shaft generator panel to AUTO position,

    confirm the main engine is constant speed, namely in shaft generator mode, press AUTO

    EXCITE & ACB CLOSE illuminated pushbutton on the No.1 shaft generator panel to start SG,

    after generator is running, while voltage establish to rated value, PMS automatically closes

    generator breaker, then generator supplies power to bus A. If start fail/voltage not .

    3.4.2 Shaft generator automatically excite & synchro momently

    The following describes, as an example, steps to place No.1 shaft generator onto a live bus

    served by diesel generator.

    Turn the MODE SELECT switch on the No.1 shaft generator panel to AUTO position,

    confirm the main engine is constant speed, namely in shaft generator mode, press AUTO

    EXCITE & ACB CLOSE illuminated pushbutton on the No.1 shaft generator panel to start SG,after generator is running, while voltage establish to rated value, if SG and DG run in parallel ,

    PMS adjust speed for DG and output automatic synchro command, while meets synchro

    condition, synchronizer output automatic close command, then generator supplies power to

    busbar in parallel, then manually control: a. subarea power supply ,b. load shift and stop DG. If

    Zh ji Xi El i D l C L d

  • 8/11/2019 Manual for Pms

    33/76

    Zhejiang Xinya Electric Development Co.,Ltd

    3.5 . After subarea power supply, manually synchro by bus tie breaker

    3.5.1 After subarea power supply dividually, manually synchro by SDBT1 bus tie breaker

    When bus C and bus A subarea power supply, Turnthe synchro select switch on synhcro panelto SDBT1, adjust the GOVERNOR switch for DG manually, check voltage , frequency meter

    and synchronoscope, let SG s speed quicker. While meets synchro condition, press ACB

    CLOSE pushbutton on synchro panel for SDBT1, then generator supplies power to busbar in

    parallel, then load shift manually.

    3.5.2 After subarea power supply, manually synchro by SDBT2 bus tie breaker

    When bus D and bus B subarea power supply, Turnthe synchro select switch on synhcro panel

    to SDBT2, adjust the GOVERNOR switch for DG manually, check voltage , frequency meter

    and synchronoscope, let SG s speed quicker. While meets synchro condition, press ACB

    CLOSE pushbutton on synchro panel for SDBT2 , then generator supplies power to busbar in

    parallel, then load shift manually.

    3.5.3 After subarea power supply, manually synchro by DDBT bus tie breakerWhen bus BD and bus AC supply power dividually. Turnthe SYN SELECT switch to DDBT,

    adjust GOVERNOR switch for DG manually, check voltage, frequency meter and

    synchronoscope. While meets synchro condition, press ACB CLOSE pushbutton on synchro

    panel for DDBT, then generator supplies power to busbar in parallel, then load shift manually.

    3.6 . After subarea power supply, semiauto synchro by bus tie breaker

    3.6.1 After subarea power supply, semiauto synchro by SDBT1 bus tie breaker

    When bus C and bus A supply power dividually. Turnthe MODE SELECT switch on each

    generator panel to AUTO position, press AUTO SYNCHRO illuminated pushbutton on

    synchro panel for SDBT1, PMS output automatic synchro command and then SDBT1 bus tie

    breaker synchro close, then generators supplies power to busbar in parallel, then load shift

    manually.

    3.6.2 After subarea power supply, semiauto synchro by SDBT2 bus tie breaker

    When bus D and bus B supply power dividually. Turnthe MODE SELECT switch to AUTO

    position, press AUTO SYNCHRO illuminated pushbutton on synchro panel for SDBT2, PMS

    output automatic synchro command and then SDBT2 bus tie breaker synchro close, then

    Zh ji Xi El t i D l t C Ltd

  • 8/11/2019 Manual for Pms

    34/76

    Zhejiang Xinya Electric Development Co.,Ltd

    3.7 Generator automatically control

    3.7.1 One shaft generator power supply, Generator ACB abnormal trip and blackout (The

    MODE SELECT switch on each generator panel is set to AUTO position)A: Standby SG automatically excite and ACB closeure on the dead bus

    a. While the No.1 shaft generator supply the power to busbar, the SG1 ACB abnormal trip

    and blackout, if SG2 in shaft generator mode, the SG2 auto excite, while voltage establish to

    rated value, PMS output automatic close command, then the SG2 ACB close and supplies

    power to bus B and SDBT2 bus tie breaker automatic close; If voltage not established/ACB

    non close, then PMS gives alarm. If busbar continued to short circuit, power supply is

    interrupt.

    b. While the No.2 shaft generator supply the power to busbar, the SG2 ACB abnormal trip

    and blackout, if SG1 in shaft generator mode, the SG1 auto excite, while voltage establish to

    rated value, PMS output automatic close command, then the SG1 ACB close and supplies

    power to bus B and SDBT1 bus tie breaker automatic close; If voltage not established/ACB

    non close, then PMS gives alarm. If busbar continued to short circuit, power supply is

    interrupt.

    B: 1ststandby DG (DG1,DG2 or DG3) automatically start and ACB closure to the dead bus

    While One shaft generator supply the power to busbar, SG ACB abnormal trip and blackout, if

    the other SG is not in SG mode or excite fail, the 1 ststandby DG automatically start, after 1st

    standby DG is running, while voltage establish to rated value, PMS gives automatic close

    command, then ACB close and 1ststandby DG supplies power to busbar. If start fail/voltage

    not established/ACB non close, then PMS gives alarm. If busbar continued to short circuit,

    power supply is interrupt.

    C: 2ndstandby DG (DG1,DG2 or DG3) automatically start and ACB closure to the dead bus

    SG ACB abnormal trip and blackout, if the other SG is not in SG mode or excite fail, and 1 st

    standby DG failure to supply, the 2ndstandby DG automatically dittoes 1ststandby DG.

    3.7.2 One diesel generator supply power, Generator ACB abnormal trip and blackout (The

    MODE SELECT switch on each generator panel is set to AUTO position)

    A: 1stStandby DG automatically start , ACB closure to the dead bus

    a. DG ACB trip and blackout, the 1st standby DG automatically start, after 1st standby DG is

    Zhejiang Xinya Electric Development Co Ltd

  • 8/11/2019 Manual for Pms

    35/76

    Zhejiang Xinya Electric Development Co.,Ltd

    busbar, the relevant bustie breaker automatically close. If voltage not established/ACB non

    close, then PMS output alarm. If busbar continued to short circuit, power supply is interrupt.

    C: 2ndstandby SG (SG1or DG2) automatically excite , ACB closure to the dead bus

    DG ACB trip and blackout, if the other DG are not ready or start fail, and 1 ststandby SG failure

    to supply, the 2ndstandby SG automatically dittoes 1ststandby SG.

    3.7.3 One shaft generator supply power, busbar abnormal (voltage high or low/frequency

    high or low) (The MODE SELECT switch on each generator panel is set to AUTO position)

    A: Standby SG automatically excite , ACB closure to the dead bus

    a. SG1 abnormal(voltage high or low/frequency high or low), if SG2 in SG mode, SG2

    automatically excite, after SG2 is running, while voltage establish to rated value, PMS first

    automatic open SG1 ACB, then automatic close SG2 ACB onto dead bus B, SDBT2 bus tie

    breaker auto close; If voltage not established/ACB non close, then PMS gives alarm.

    b. SG2 abnormal(voltage high or low/frequency high or low), if DG1 in SG mode, SG1

    automatically excite, after SG1 is running, while voltage establish to rated value, PMS firstautomatic open SG2 ACB, then automatic close SG1 ACB onto dead bus A, SDBT1 bus tie

    breaker auto close; If voltage not established/ACB non close, then PMS gives alarm.

    B: 1ststandby DG (DG1,DG2 or DG3) automatically start , ACB closure to the dead bus

    SG abnormal(voltage high or low/frequency high or low), if another SG is not in SG mode or

    excite fail, the 1ststandby DG automatically start, after 1ststandby DG is running, while voltage

    establish to rated value, PMS first automatic open abnormal SG ACB, then automatic close 1st

    standbyDG ACB onto dead bus. If start fail/voltage not established/ACB non close, then PMS

    output alarm.

    C: 2ndstandby DG (DG1,DG2 or DG3) automatically start , ACB closure to the dead bus

    SG abnormal(voltage high or low/frequency high or low), if another SG is not in SG mode or

    excite fail, and 1st

    standby DG failure to supply, the 2nd

    standby DG automatically dittoes 1st

    standby DG.

    3.7.4 One diesel generator supply power, busbar abnormal (voltage high or low/frequency

    high or low) (The MODE SELECT switch on each generator panel is set to AUTO position)

    Zhejiang Xinya Electric Development Co Ltd

  • 8/11/2019 Manual for Pms

    36/76

    Zhejiang Xinya Electric Development Co.,Ltd

    DG abnormal(voltage high or low/frequency high or low), if the other DG are not ready or

    start fail, the 1ststandby SG automatically excite, after 1ststandby SG is running, while voltage

    establish to rated value, PMS first automatic open abnormal DG ACB, then automatic close 1ststandby SG ACB onto dead bus, the relevant bustie breaker automatically close. If voltage not

    established/ACB non close, then PMS gives alarm.

    C: 2ndstandby SG (SG1or DG2) automatically excite , ACB closure to the dead bus

    DG abnormal(voltage high or low/frequency high or low), if the other DG are not ready or

    start fail, and the 1ststandby SG failure to supply, the 2ndstandby SG automatically dittoes 1st

    standby SG .

    3.7.5 Diesel generator automatically load shift & ACB open, Engine stop due to light load (The

    MODE SELECT switch on each generator panel is set to AUTO position)

    Two or more diesel generators run in parallel, load power is less than 60%(adjustable) rated

    power, the last closure generator automatic load shift, while the generator power is less than

    5% rated power, PMS output automatic open command, the last closure generatordisconnects, after 5 minutes(adjustable), Engine stops automatically.

    3.7.6 Gen. Eng. automatically start & synchro due to heavy load (The MODE SELECT switch

    on each generator panel is set to AUTO position)

    Diesel Generator supplies power to busbar, load power is more than 90%(adjustable) rated

    power, after 15 sec. (adjustable), the 1ststandby DG automatically start, after 1ststandby DG is

    running, while voltage establish to rated value, PMS output automatic synchro command,

    while meets synchro condition, synchronizer output automatic close command, then

    generators supplies power to busbar in parallel, load sharing automatically. If start

    fail/voltage not established/ACB non close/auto synchro fail, then PMS gives alarm. If 1 st

    standby generator failure to supply, the 2ndstandby generator automatically dittoes 1st

    standby generator.

    3.7.7 Pretrip nonessential consumer

    Generator over current [100%(adjustable) rated current], after 10 sec. (adjustable),PMS gives

    pretrip command to disconnect nonessential consumer.

    Zhejiang Xinya Electric Development Co.,Ltd

  • 8/11/2019 Manual for Pms

    37/76

    Zhejiang Xinya Electric Development Co.,Ltd

    then the PMS output permit start signal to bow thruster control box. if SDBT2 bus-tie breaker

    open fail or No.2 shaft generator ACB close fail, then PMS output alarm.

    c. When No.2 shaft generator supply power to the ship, bow thruster output start request to PMS, ifthe load90% rated power of one diesel generator, the 1st standby and 2nd standby diesel

    generator start automatically, after standby diesel generators are running, auto synchro after

    voltage being built, then two diesel generators and No.2 shaft generator run in parallel, then the

    No.2 shaft generator auto transfer the load to diesel generators, then the load shift finished, the

    SDBT2 bus-tie breaker automatically open, then the PMS output permit start signal to bow

    thruster control box. If the load

  • 8/11/2019 Manual for Pms

    38/76

    j g y p ,

    synchro after voltage being built, then two diesel generators run in parallel, then the PMS output

    permit start signal to retractable stern thruster control box.

    b. When one set shaft generator supply power to the ship, stern thruster output start request to PMS,the 1st standby and 2nd standby diesel generator start automatically, after standby diesel

    generators are running, auto synchro after voltage being built, then two diesel generators and

    shaft generator run in parallel, then the shaft generator auto transfer the load to diesel generators,

    then the load shift finished, the SDBT1 or SDBT2 bus-tie breaker automatically open, if the

    surplus power is enough (online generators rating power X 85%-load large motor rating

    power),then the PMS output permit start signal to stern thruster control box.

    3.7.9 Dynamic positioning DP2 (The MODE SELECT switch on each generator panel is set to

    AUTO position)

    In the mode of dynamic positioning DP2, three diesel generators and two shaft generators (divided

    into 4 zones) are in charge of power supply.

    a. When No.1 diesel generator supply the power, press DP2on the WHC, then SDBT1, SDBT2

    and SSBT bus-tie breaker open automatically. If No.1,No.2 shaft generator were in shaft mode,automatically exciteauto close after voltage has been built; The standby generators starts

    automatically, auto synchro after has been built, and diesel generators run in parallel, while

    DDBT bus-tie breaker auto open and divided into A/B/C/D four zones to supply power, thruster

    breaker auto close, sending the permit start signal to thruster.

    b. When No.1 shaft generator supply the power press DP2on WHC, then SDBT2 and SSBT bus-

    tie breaker open automatically. If No.2 shaft generator was in shaft mode, automatically excite

    auto close after voltage has been built; auto start No.1,No.2 and No.3 diesel generator , auto

    synchro after voltage has been built. After the diesel generator and No.1 shaft generator parallel

    running , No.1 shaft generator auto load shift and SDBT1 bus-tie breaker auto open. After three

    diesel generators run in parallel, DDBT bus-tie breaker auto open and automatically divided into

    A/B/C/D four zones to supply power, as thruster breaker auto close, sending the permit start

    signal to thruster

    c. When No.2 shaft generator supply the power press DP2on WHC, then SDBT1 and SSBT bus-tie breaker open automatically. If No.1 shaft generator was in shaft mode, automatically excite

    auto close after voltage has been built; auto start No.1,No.2 and No.3 diesel generator , auto

    synchro after has been built. After the diesel generators and No.2 shaft generator parallel running ,

    No.2 shaft generator auto load shift and SDBT2 bus-tie breaker auto open. After three diesel

  • 8/11/2019 Manual for Pms

    39/76

  • 8/11/2019 Manual for Pms

    40/76

  • 8/11/2019 Manual for Pms

    41/76

  • 8/11/2019 Manual for Pms

    42/76

  • 8/11/2019 Manual for Pms

    43/76

  • 8/11/2019 Manual for Pms

    44/76

  • 8/11/2019 Manual for Pms

    45/76

  • 8/11/2019 Manual for Pms

    46/76

  • 8/11/2019 Manual for Pms

    47/76

  • 8/11/2019 Manual for Pms

    48/76

  • 8/11/2019 Manual for Pms

    49/76

  • 8/11/2019 Manual for Pms

    50/76

  • 8/11/2019 Manual for Pms

    51/76

  • 8/11/2019 Manual for Pms

    52/76

  • 8/11/2019 Manual for Pms

    53/76

  • 8/11/2019 Manual for Pms

    54/76

  • 8/11/2019 Manual for Pms

    55/76

  • 8/11/2019 Manual for Pms

    56/76

  • 8/11/2019 Manual for Pms

    57/76

  • 8/11/2019 Manual for Pms

    58/76

  • 8/11/2019 Manual for Pms

    59/76

  • 8/11/2019 Manual for Pms

    60/76

  • 8/11/2019 Manual for Pms

    61/76

  • 8/11/2019 Manual for Pms

    62/76

  • 8/11/2019 Manual for Pms

    63/76

  • 8/11/2019 Manual for Pms

    64/76

  • 8/11/2019 Manual for Pms

    65/76

  • 8/11/2019 Manual for Pms

    66/76

  • 8/11/2019 Manual for Pms

    67/76

  • 8/11/2019 Manual for Pms

    68/76

  • 8/11/2019 Manual for Pms

    69/76

  • 8/11/2019 Manual for Pms

    70/76

  • 8/11/2019 Manual for Pms

    71/76

  • 8/11/2019 Manual for Pms

    72/76

  • 8/11/2019 Manual for Pms

    73/76

  • 8/11/2019 Manual for Pms

    74/76

  • 8/11/2019 Manual for Pms

    75/76

  • 8/11/2019 Manual for Pms

    76/76