MANAGER 3000

INTERFACE MANUAL C0224122-11-15-EN

For software versions HG06

Replaces C0224122-05-12-EN

The information contained in this document may be modified without prior notice. No part of this document may be reproduced and/or disclosed to third parties or competitors.

November 2015

EN

C0224122-11-15-EN

2

Contents

1. USABILITY .................................................................................................................................................................................... 3

2. INTERFACING WITH THE BMS (MODBUS)................................................................................................................................. 4

2.1 Components required .............................................................................................................. 4 2.2 Installing the serial interface card ............................................................................................ 4 2.3 Setting supervisor parameters.................................................................................................. 5 2.4 Setting up the supervisor network ............................................................................................ 5 2.5 Interface database (software releases HG06 and higher) ........................................................... 6

3. INTERFACING WITH THE LONWORKS SYSTEM (ECHELON) ................................................................................................. 10

3.1 Components required ............................................................................................................ 10 3.2 Installing the serial interface card to the LONWORKS system ................................................... 10 3.3 Setting supervisor parameters................................................................................................ 11 3.4 Setting up the supervisor network .......................................................................................... 11 3.5 LONWORKS interface database (software releases HG04 and higher) ....................................... 11 3.6 Meaning of variables ............................................................................................................. 12

4. INTERFACING WITH THE BACNET SYSTEM ........................................................................................................................... 13

4.1 Components required ............................................................................................................ 13 4.2 Installing the serial interface card to the BACNET system ........................................................ 13 4.3 Setting supervisor parameters................................................................................................ 14 4.4 Setting up the supervisor network .......................................................................................... 14 4.5 Meaning of variables ............................................................................................................. 14

5. ANNEXES ................................................................................................................................................................................... 15

5.1 AWG (American Wire Gauge) conversion table ........................................................................ 15

C0224122-11-15-EN

3

1. Usability

This document exclusively refers to systems managed by the Manager 3000 electronic controller running on HG06 software. This version uses software release EA12r00 or higher in the I/O module. Information on the version of the software installed in the I/O module is shown in the “Configuration Test” screen which can be accessed as shown below.

Press [MENU] on the main screen of the display to access the user password-protected main menu.

Enter the user password. Confirm with “OK”.

Press this button to access manufacturer password-protected manufacturer menu.

Press “UP” and “DOWN” to scroll the list of available functions and press “Configuration Test”.

The “Configuration Test” screen displays any system configuration errors and information on the version and release

of the software installed on the I/O module (EA application).

In the example, I97 indicates that the code identifying the installed software is equal to 501, where 5 indicates the fifth letter of the alphabet “E” and 01 the first letter of the alphabet “A”, while I98 indicates software version 04, release 00 of the software installed. Press "Back" to return to the submenu.

The manufacturer menu is also used to access the other screens required to interface the Manager 3000 with the BMS. The electronic controller may only be installed and programmed by adequately trained technical staff.

C0224122-11-15-EN

4

2. Interfacing with the BMS (MODBUS)

2.1 Components required

Serial interface card PCOS004850.

Gateway inside the Manager 3000 panel, if requested by the customer.

2.2 Installing the serial interface card

The operations required to install and connect the components for interfacing the Manager3000 electronic controller with the BMS are shown below. The card must not be powered during these operations.

Remove the “Serial Card” cover of the gateway

Fit the BMS serial interface card (if not present) into the slot.

Put back the cover.

C0224122-11-15-EN

5

2.3 Setting supervisor parameters

To communicate with BMS, set the dedicated parameters via display (Manufacturer Menu - System Configuration) as shown below.

Par Description Value

P053 Superv. protocol 2 Protocol: Modbus / Standard

P054 Superv. speed 3

Communication speed: from 1200 baud to 19200 baud (0:1200 - 1:2400 - 2:4800 -

3:9600 - 4:19200)

P055 Superv. address 11 GATEWAY ID: from 001 to 200

IMPORTANT: to allow the parameter changes to be saved to the system, after making the changes perform the “Send

I/O module parameters” procedure (Manufacturer Menu – Send I/O module parameters), first making sure the system is OFF. Other non-modifiable supervisor connection settings:

Protocol Configuration

ModBus Data bits: 8

Parity: none

Stop bits: 2

Start Address: 1

2.4 Setting up the supervisor network

The supervisor network must be set up as shown below:

Tx/Rx -Tx/Rx +GND

Gateway

R=120

Scheda interfacciamento seriale

BMS

SCHERMO

Diagram showing a possible BMS supervision network layout

Take great care when installing the serial line. This is an RS485 serial line, based on a balanced differential communication line with a characteristic impedance of 120 ohm. The maximum length of the connection depends on the Baud-rate, background electrical noise, and the type and quality of the cable. Operation is generally guaranteed up to 1000 m. Use a twisted and shielded AWG 20/22 cable for the RS 485 serial line. The serial connection is made with a single cable running from the BMS to the gateway. The serial cable must be kept separate from the power cables. The shield of the connection cable must be earthed in just one point.

SCREEN

Serial interface board

C0224122-11-15-EN

6

2.5 Interface database (software releases HG06 and higher)

Register/Coil Modbus protocol

Protocol address: - Standard - Bacnet

Type Flow Description

40001 000 A NOT MANAGED

40002 001 A OUT Unit 1 evaporator inlet temperature

40003 002 A OUT Unit 1 evaporator outlet temperature

40004 003 A OUT Unit 1 recovery inlet temperature

40005 004 A OUT Unit 1 recovery outlet temperature

40006 005 A OUT Unit 2 evaporator inlet temperature

40007 006 A OUT Unit 2 evaporator outlet temperature

40008 007 A OUT Unit 2 recovery inlet temperature

40009 008 A OUT Unit 2 recovery outlet temperature

40010 009 A OUT Unit 3 evaporator inlet temperature

40011 010 A OUT Unit 3 evaporator outlet temperature

40012 011 A OUT Unit 3 recovery inlet temperature

40013 012 A OUT Unit 3 recovery outlet temperature

40014 013 A OUT Unit 4 evaporator inlet temperature

40015 014 A OUT Unit 4 evaporator outlet temperature

40016 015 A OUT Unit 4 recovery inlet temperature

40017 016 A OUT Unit 4 recovery outlet temperature

40018 017 A OUT Unit 5 evaporator inlet temperature

40019 018 A OUT Unit 5 evaporator outlet temperature

40020 019 A OUT Unit 5 recovery inlet temperature

40021 020 A OUT Unit 5 recovery outlet temperature

40022 021 A OUT Unit 6 evaporator inlet temperature

40023 022 A OUT Unit 6 evaporator outlet temperature

40024 023 A OUT Unit 6 recovery inlet temperature

40025 024 A OUT Unit 6 recovery outlet temperature

40026 025 A OUT Unit 7 evaporator inlet temperature

40027 026 A OUT Unit 7 evaporator outlet temperature

40028 027 A OUT Unit 7 recovery inlet temperature

40029 028 A OUT Unit 7 recovery outlet temperature

40030 029 A OUT Unit 8 evaporator inlet temperature

40031 030 A OUT Unit 8 evaporator outlet temperature

40032 031 A OUT Unit 8 recovery inlet temperature

40033 032 A OUT Unit 8 recovery outlet temperature

40034 033 A OUT Unit 1 condenser inlet temperature

40035 034 A OUT Unit 1 condenser outlet temperature

40036 035 A OUT Unit 2 condenser inlet temperature

40037 036 A OUT Unit 2 condenser outlet temperature

40038 037 A OUT Unit 3 condenser inlet temperature

40039 038 A OUT Unit 3 condenser outlet temperature

40040 039 A OUT Unit 4 condenser inlet temperature

40041 040 A OUT Unit 4 condenser outlet temperature

40042 041 A OUT Unit 5 condenser inlet temperature

40043 042 A OUT Unit 5 condenser outlet temperature

40044 043 A OUT Unit 6 condenser inlet temperature

40045 044 A OUT Unit 6 condenser outlet temperature

40046 045 A OUT Unit 7 condenser inlet temperature

40047 046 A OUT Unit 7 condenser outlet temperature

40048 047 A OUT Unit 8 condenser inlet temperature

40049 048 A OUT Unit 8 condenser outlet temperature

40091 090 A OUT Cold/hot circuit inlet temperature

40092 091 A OUT Cold/hot circuit outlet temperature

40093 092 A OUT Recovery circuit inlet temperature

40094 093 A OUT Recovery outlet circuit temperature

40095 094 A IN / OUT Cold temperature setpoint

C0224122-11-15-EN

7

Register/Coil Modbus protocol

Protocol address: - Standard - Bacnet

Type Flow Description

40096 095 A IN / OUT Cold temperature adjustment band

40097 096 A IN / OUT Hot temperature setpoint

40098 097 A IN / OUT Hot temperature adjustment band

40099 098 A IN / OUT Recovery temperature setpoint

40100 099 A IN / OUT Recovery temperature adjustment band

40101 100 A OUT Cold/hot active temperature setpoint

40102 101 A OUT Recovery temperature active setpoint

40103 102 A OUT External air temperature

001 000 B NOT MANAGED

002 001 B OUT Unit 1 offline (0: unit online – 1: unit offline)

003 002 B OUT Unit 2 offline (0: unit online – 1: unit offline)

004 003 B OUT Unit 3 offline (0: unit online – 1: unit offline)

005 004 B OUT Unit 4 offline (0: unit online – 1: unit offline)

006 005 B OUT Unit 5 offline (0: unit online – 1: unit offline)

007 006 B OUT Unit 6 offline (0: unit online – 1: unit offline)

008 007 B OUT Unit 7 offline (0: unit online – 1: unit offline)

009 008 B OUT Unit 8 offline (0: unit online – 1: unit offline)

091 090 B IN / OUT System on/off command (0: system off – 1: system on)

095 094 B IN / OUT Unit 1 enable (0: unit disabled – 1: unit enabled)

096 095 B IN / OUT Unit 2 enable (0: unit disabled – 1: unit enabled)

097 096 B IN / OUT Unit 3 enable (0: unit disabled – 1: unit enabled)

098 097 B IN / OUT Unit 4 enable (0: unit disabled – 1: unit enabled)

099 098 B IN / OUT Unit 5 enable (0: unit disabled – 1: unit enabled)

100 099 B IN / OUT Unit 6 enable (0: unit disabled – 1: unit enabled)

101 100 B IN / OUT Unit 7 enable (0: unit disabled – 1: unit enabled)

102 101 B IN / OUT Unit 8 enable (0: unit disabled – 1: unit enabled)

103 102 B IN / OUT Demand Limit command from supervision (0: command inactive – 1: command active)

40129 000 I NOT MANAGED

40130 001 I OUT Unit 1 cold/hot demand percentage

40131 002 I OUT Unit 1 cold/hot active percentage

40132 003 I OUT Unit 1 recovery demand percentage

40133 004 I OUT Unit 1 recovery active percentage

40134 005 I OUT Unit 2 cold/hot demand percentage

40135 006 I OUT Unit 2 cold/hot active percentage

40136 007 I OUT Unit 2 recovery demand percentage

40137 008 I OUT Unit 2 recovery active percentage

40138 009 I OUT Unit 3 cold/hot demand percentage

40139 010 I OUT Unit 3 cold/hot active percentage

40140 011 I OUT Unit 3 recovery demand percentage

40141 012 I OUT Unit 3 recovery active percentage

40142 013 I OUT Unit 4 cold/hot demand percentage

40143 014 I OUT Unit 4 cold/hot active percentage

40144 015 I OUT Unit 4 recovery demand percentage

40145 016 I OUT Unit 4 recovery active percentage

40146 017 I OUT Unit 5 cold/hot demand percentage

40147 018 I OUT Unit 5 cold/hot active percentage

40148 019 I OUT Unit 5 recovery demand percentage

40149 020 I OUT Unit 5 recovery active percentage

40150 021 I OUT Unit 6 cold/hot demand percentage

40151 022 I OUT Unit 6 cold/hot active percentage

40152 023 I OUT Unit 6 recovery demand percentage

40153 024 I OUT Unit 6 recovery active percentage

40154 025 I OUT Unit 7 cold/hot demand percentage

40155 026 I OUT Unit 7 cold/hot active percentage

40156 027 I OUT Unit 7 recovery demand percentage

C0224122-11-15-EN

8

Register/Coil Modbus protocol

Protocol address: - Standard - Bacnet

Type Flow Description

40157 028 I OUT Unit 7 recovery active percentage

40158 029 I OUT Unit 8 cold/hot demand percentage

40159 030 I OUT Unit 8 cold/hot active percentage

40160 031 I OUT Unit 8 recovery demand percentage

40161 032 I OUT Unit 8 recovery active percentage

40162 033 I OUT

Unit 1 status W3000: (0:ON from keyboard - 1:ON from digital input - 2:ON from time bands - 3:ON from supervisor - 4:OFF from alarm - 5:OFF from supervisor - 6:OFF from time bands - 7:OFF from digital input - 8:OFF from keyboard - 9: OFF from deselect compressors 10:OFF) CVM300/3000 (0:Idle – 1:ON – 2:Configuration – 3:Off 4:OFF – 5:OFF from digital input in progress – 6: OFF from digital input – 7: OFF from supervisor in progress – 8: OFF from supervisor)

40163 034 I OUT Unit 2 status (see unit 1 status)

40164 035 I OUT Unit 3 status (see unit 1 status)

40165 036 I OUT Unit 4 status (see unit 1 status)

40166 037 I OUT Unit 5 status (see unit 1 status)

40167 038 I OUT Unit 6 status (see unit 1 status)

40168 039 I OUT Unit 7 status (see unit 1 status)

40169 040 I OUT Unit 8 status (see unit 1 status)

40170 041 I OUT Unit 1 alarm code active

40171 042 I OUT Unit 2 alarm code active

40172 043 I OUT Unit 3 alarm code active

40173 044 I OUT Unit 4 alarm code active

40174 045 I OUT Unit 5 alarm code active

40175 046 I OUT Unit 6 alarm code active

40176 047 I OUT Unit 7 alarm code active

40177 048 I OUT Unit 8 alarm code active

40178 049 I OUT Pump speed percentage with unit 1 cold/hot circuit inverter

40179 050 I OUT Pump speed percentage with unit 2 cold/hot circuit inverter

40180 051 I OUT Pump speed percentage with unit 3 cold/hot circuit inverter

40181 052 I OUT Pump speed percentage with unit 4 cold/hot circuit inverter

40182 053 I OUT Pump speed percentage with unit 5 cold/hot circuit inverter

40183 054 I OUT Pump speed percentage with unit 6 cold/hot circuit inverter

40184 055 I OUT Pump speed percentage with unit 7 cold/hot circuit inverter

40185 056 I OUT Pump speed percentage with unit 8 cold/hot circuit inverter

40186 057 I OUT Unit 1 cold/hot available percentage

40187 058 I OUT Unit 1 recovery available percentage

40188 059 I OUT Unit 2 cold/hot available percentage

40189 060 I OUT Unit 2 recovery available percentage

40190 061 I OUT Unit 3 cold/hot available percentage

40191 062 I OUT Unit 3 recovery available percentage

40192 063 I OUT Unit 4 cold/hot available percentage

40193 064 I OUT Unit 4 recovery available percentage

40194 065 I OUT Unit 5 cold/hot available percentage

40195 066 I OUT Unit 5 recovery available percentage

40196 067 I OUT Unit 6 cold/hot available percentage

40197 068 I OUT Unit 6 recovery available percentage

40198 069 I OUT Unit 7 cold/hot available percentage

40199 070 I OUT Unit 7 recovery available percentage

40200 071 I OUT Unit 8 cold/hot available percentage

40201 072 I OUT Unit 8 recovery available percentage

40202 073 I OUT Pump speed percentage with unit 1 recovery circuit inverter

40203 074 I OUT Pump speed percentage with unit 2 recovery circuit inverter

40204 075 I OUT Pump speed percentage with unit 3 recovery circuit inverter

40205 076 I OUT Pump speed percentage with unit 4 recovery circuit inverter

40206 077 I OUT Pump speed percentage with unit 5 recovery circuit inverter

40207 078 I OUT Pump speed percentage with unit 6 recovery circuit inverter

40208 079 I OUT Pump speed percentage with unit 7 recovery circuit inverter

C0224122-11-15-EN

9

Register/Coil Modbus protocol

Protocol address: - Standard - Bacnet

Type Flow Description

40209 080 I OUT Pump speed percentage with unit 8 recovery circuit inverter

40229 100 I OUT System status (0:system ON - 4:system OFF from alarm - 7:system OFF from contact - 8: system OFF)

40230 101 I OUT System alarm code active

40232 103 I OUT Cold/hot circuit demand percentage

40233 104 I OUT Cold/hot circuit active percentage

40234 105 I OUT Recovery circuit demand percentage

40235 106 I OUT Recovery circuit active percentage

40236 107 I IN / OUT

System operating mode (1:cold only - 2:cold+rec - 3:recovery ony- 4:hot - 5:hot+rec)

40237 108 I IN / OUT Cold capacity limit percentage

40238 109 I IN / OUT Hot capacity limit percentage

40239 110 I IN / OUT Recovery capacity limit percentage

Table 2.5.a: Interface database

GATEWAY Address: This is the ID of the Manager3000 inside the BMS network. The value can be set from 1 to 200. Variable address: This is the supervision variable address in the electronic control unit. When using the addresses with the ModBus protocol, add 128 for whole variables. (e.g.: “System operating mode” address 107 -> Modbus address 235 [128+107]) Type: B: Boolean variable (Coil for the Modbus protocol) I: Whole variable (Register for the Modbus protocol) A: Analogue variable (Register for the Modbus protocol) Flow: OUT: Read-only variable for the BMS IN / OUT: Read/write variable for the BMS Analogue variables are expressed with a decimal number (e.g.: 12.0 bar -> 120; 33.8°C -> 338). If a probe is in an alarm condition a value equal to -99.9 is sent. If a probe or a parameter is not configured a value equal to -88.8 is sent.

Analogue variables, whole and digital with address 0 are considered as incorrect and throw the “ILLEGAL DATA

ADDRESS” error code.

All the addresses not indicated in the database must not be used.

C0224122-11-15-EN

10

3. Interfacing with the LONWORKS system (Echelon)

3.1 Components required

The components required to interface the system fitted with the Manager3000 electronic controller to the LONWORKS system are described below.

Serial interface card to the LONWORKS system.

Gateway inside the Manager 3000 panel if requested by the customer.

3.2 Installing the serial interface card to the LONWORKS system

The operations required to install and connect the components for interfacing the Manager3000 electronic controller with the LONWORKS system are shown below. The card must not be powered during these operations.

Remove the “Serial Card” cover of the gateway

Fit the LONWORKS system serial interface card (if not present) into the slot.

Put back the cover.

C0224122-11-15-EN

11

3.3 Setting supervisor parameters

To communicate with the LONWORKS system, set the dedicated parameters via display (Manufacturer Menu - System Configuration) as shown below.

Par Description Value

P053 Superv. protocol 3 Protocol: LonWorks

P054 Superv. speed (*) 2 Communication speed: 4800 baud

P055 Superv. address 01 GATEWAY ID: 001

(*) Speed of communication between GATEWAY and LONWORKS interface board. N.B.: the speed of communication towards the external BMS is always 78 kbps.

IMPORTANT: to allow the parameter changes to be saved to the system, after making the changes perform the “Send

I/O module parameters” procedure (Manufacturer Menu – Send I/O module parameters), first making sure the system is OFF.

3.4 Setting up the supervisor network

The supervisor network is set up by LONWORKS staff. The .NXE file and the .XIF file for configuring the card must be requested from CLIMAVENETA by the technicians setting up the network. The card is programmed by the technician developing the integration.

3.5 LONWORKS interface database (software releases HG04 and higher)

The reference database for systems using the LONWORKS networks is shown below:

Address Type Type NV Flow Description

000 A 105 NOT MANAGED

090 A 105 OUT Cold/hot circuit inlet temperature

091 A 105 OUT Cold/hot circuit outlet temperature

092 A 105 OUT Recovery circuit inlet temperature

093 A 105 OUT Recovery outlet circuit temperature

094 A 105 IN / OUT Cold temperature setpoint

095 A 105 IN / OUT Cold temperature adjustment band

096 A 105 IN / OUT Hot temperature setpoint

097 A 105 IN / OUT Hot temperature adjustment band

098 A 105 IN / OUT Recovery temperature setpoint

099 A 105 IN / OUT Recovery temperature adjustment band

100 A 105 OUT Cold/hot active temperature setpoint

101 A 105 OUT Recovery temperature active setpoint

000 B 95 NOT MANAGED

090 B 95 IN / OUT System on/off command (0: system off – 1: system on)

102 B 95 IN / OUT Demand Limit command from supervision (0: command inactive – 1: command active)

000 I 8 NOT MANAGED

033 I 8 OUT

Unit 1 status W3000: (0:ON from keyboard - 1:ON from digital input - 2:ON from time bands - 3:ON from supervisor - 4:OFF from alarm - 5:OFF from supervisor - 6:OFF from time bands - 7:OFF from digital input - 8:OFF from keyboard - 9: OFF from deselect compressors 10:OFF) CVM300/3000 (0:Idle – 1:ON – 2:Configuration – 3:Off 4:OFF – 5:OFF from digital input in progress – 6: OFF from digital input – 7: OFF from supervisor in progress – 8: OFF from supervisor)

034 I 8 OUT Unit 2 status (see unit 1 status)

C0224122-11-15-EN

12

Address Type Type NV Flow Description

035 I 8 OUT Unit 3 status (see unit 1 status)

036 I 8 OUT Unit 4 status (see unit 1 status)

037 I 8 OUT Unit 5 status (see unit 1 status)

038 I 8 OUT Unit 6 status (see unit 1 status)

039 I 8 OUT Unit 7 status (see unit 1 status)

040 I 8 OUT Unit 8 status (see unit 1 status)

041 I 8 OUT Unit 1 alarm code active

042 I 8 OUT Unit 2 alarm code active

043 I 8 OUT Unit 3 alarm code active

044 I 8 OUT Unit 4 alarm code active

045 I 8 OUT Unit 5 alarm code active

046 I 8 OUT Unit 6 alarm code active

047 I 8 OUT Unit 7 alarm code active

048 I 8 OUT Unit 8 alarm code active

100 I 8 OUT System status (0:system ON - 4:system OFF from alarm - 7:system OFF from contact - 8: system OFF)

101 I 8 OUT System alarm code active

103 I 8 OUT Cold/hot circuit demand percentage

104 I 8 OUT Cold/hot circuit active percentage

105 I 8 OUT Recovery circuit demand percentage

106 I 8 OUT Recovery circuit active percentage

107 I 8 IN / OUT System operating mode (1:cold only - 2:cold+rec - 3:recovery ony - 4:hot - 5:hot+rec)

108 I 8 IN / OUT Cold capacity limit percentage

109 I 8 IN / OUT Hot capacity limit percentage

110 I 8 IN / OUT Recovery capacity limit percentage

Table 3.5.a: Gateway/Lonworks System interface database.

3.6 Meaning of variables

Analogue variables are expressed with a decimal number (e.g.: 12.0bar -> 120; 33.8°C -> 338). If a probe is in an alarm condition a value equal to -99.9 is sent. If a probe or a parameter is not configured a value equal to -88.8 is sent.

C0224122-11-15-EN

13

4. Interfacing with the BACNET system

4.1 Components required

The components required to interface the system fitted with the Manager3000 electronic controller to the BACNET system are described below.

Serial interface card BACNET. As well as the BACNET MS/TP card (for RS485 network) the BACNET TCP/IP serial card (for Ethernet) is also available

Gateway inside the Manager 3000 panel if requested by the customer.

4.2 Installing the serial interface card to the BACNET system

The operations required to install and connect the components for interfacing the Manager3000 electronic controller with the BACNET system are shown below. The card must not be powered during these operations.

Remove the “Serial Card” cover of the gateway

Fit the BACNET system serial interface card (if not present) into the slot.

Put back the cover.

C0224122-11-15-EN

14

4.3 Setting supervisor parameters

To communicate with the BACNET system, set the dedicated parameters via display (Manufacturer Menu - System Configuration) as shown below.

Par Description Value

P053 Superv. protocol 5 Protocol: Bacnet

P054 Superv. speed (*) 4 Communication speed: 19200 baud

P055 Superv. address 01 GATEWAY ID: from 001 to 200

(*) Speed of communication between GATEWAY and BACNET interface board. N.B.: The speed of communication to the external BMS may be 9600-19200-36400-76800.

4.4 Setting up the supervisor network

The PICS (Protocol Implementation Conformance Statement) file for configuring the card must be requested from CLIMAVENETA by the technicians setting up the network. The card is programmed by the technician developing the integration. The supervisor network is set up by the technicians developing the BACNET interface. The interface database is shown in the paragraph relative to the Modbus interface

4.5 Meaning of variables

Analogue variables are expressed with a decimal number (e.g.: 12.0bar -> 120; 33.8°C -> 338) If a probe is in an alarm condition a value equal to -99.9 is sent. If a probe or a parameter is not configured a value equal to -88.8 is sent.

C0224122-11-15-EN

15

5. Annexes

5.1 AWG (American Wire Gauge) conversion table

Conversion: AWG number – diameter in mm – area in mm²

AWG n° Diam. mm Area mm² AWG n° Diam. mm Area mm²

1 7.350 42.400 16 1.290 1.310

2 6.540 33.600 17 1.150 1.040

3 5.830 26.700 18 1.024 0.823

4 5.190 21.200 19 0.912 0.653

5 4.620 16.800 20 0.812 0.519

6 4.110 13.300 21 0.723 0.412

7 3.670 10.600 22 0.644 0.325

8 3.260 8.350 23 0.573 0.259

9 2.910 6.620 24 0.511 0.205

10 2.590 5.270 25 0.455 0.163

11 2.300 4.150 26 0.405 0.128

12 2.050 3.310 27 0.361 0.102

13 1.830 2.630 28 0.321 0.080

14 1.630 2.080 29 0.286 0.065

15 1.450 1.650 30 0.255 0.050

Climaveneta S.p.A.

Via Sarson 57/c

36061 Bassano del Grappa (VI)

Italy

Tel +39 0424 509 500

Fax +39 0424 509 509

[email protected]

www.climaveneta.com

Climaveneta France

3, Village d’Entreprises

ZA de la Couronne des Prés

Avenue de la Mauldre

78680 Epône

France

Tel +33 (0)1 30 95 19 19

Fax +33 (0)1 30 95 18 18

[email protected]

www.climaveneta.fr

Climaveneta Deutschland GmbH

Lyrenstraße 13

44866 Bochum

Germany

Tel +49 2327-95428-0

Fax +49 2327-95428-99

[email protected]

www.climaveneta.de

Climaveneta España - Top Clima

Londres 67, 1° 4°

08036 Barcelona

Spain

Tel +34 934 195 600

Fax +34 934 195 602

[email protected]

www.climaveneta.com

Climaveneta Chat Union

Refrig. Equipment Co Ltd

88 Bai Yun Rd, Pudong Xinghuo

New dev. zone 201419 Shanghai

China

Tel 008 621 575 055 66

Fax 008 621 575 057 97

Climaveneta Polska Sp. z o.o.

Ul. Sienkiewicza 13A,

05-120 Legionowo,

Poland

Tel +48 22 766 34 55-57

Fax +48 22 784 39 09

[email protected]

www.climaveneta.pl

Climaveneta Climate Technologies (P) Ltd

#3487, 14th Main, HAL 2nd stage,

Indiranagar, Bangalore 560008

India

Tel:+91-80-42466900 - 949,

Fax: +91-80-25203540

[email protected]

Climaveneta Powermaster ltd

Unit 6, St Clare Business Parck

Holly Road – Hampton Hill

Middlesex – TW12 1PZ

U.K.

Tel: +44 (0) 20 8783 1008

Fax: +44 (0) 20 8783 1009

[email protected]

www.climaveneta.co.uk