management training jumeirah beach residence sector 3 presented by november 15 th 2006

43
Management training Management training Jumeirah beach residence Jumeirah beach residence sector 3 sector 3 Presented by November 15 th 2006

Upload: anna-marsh

Post on 17-Dec-2015

216 views

Category:

Documents


0 download

TRANSCRIPT

Management trainingManagement training

Jumeirah beach residenceJumeirah beach residencesector 3sector 3

Presented by

November 15th 2006

Jumeirah beach residenceSector over view

Located between sector 1 and Al Fattan hotel

Jumeirah beach residenceJumeirah beach residencesector 3sector 3

7 towers ranging from 30 floors high to 52 floors high

5 level podium out of which 3 levels are car parkingMEP plant rooms in basement, mid-level(s) and roof.

Mechanical systems involvedMechanical systems involvedHVACHVAC

• Air conditioning system• Toilet extract system• Kitchen extract system• Refuse extract system• Lobby relief and stair well

pressuristaion system• Car park ventilation system

Mechanical systems involvedMechanical systems involvedPlumbingPlumbing

• Domestic cold water system• Hot water system

Mechanical systems involvedMechanical systems involvedDrainageDrainage

• Soil waste and vent systems• Rain water systems

Mechanical systems involvedMechanical systems involvedFire protectionFire protection

• Wet riser• Sprinkler protection• FM 200 system• Carbon di oxide system• Pre action system

Air conditioning systemAir conditioning system• Fresh air system• Standalone fan coil units• Common area fan coil units• Dx system for MDF rooms in grade

level

Fresh air systemFresh air system

Pre filtersBag filtersHeat wheelCooling coilSupply and extract fans

FAHU with heat recovery wheelFAHU with heat recovery wheel

Heat wheel

Heat wheel recovers energy from cold toilet exhaustAnd pre cool the fresh air intake

Fresh air systemFresh air system

FAHU are located in plant rooms.

Fresh air intake through sand trap louvers

Fresh air supply to apartments and lobbies

Fan coil unitsFan coil units

Fan coil units are provided with filters, cooling coil and fanAir distribution with ducting and grilles and diffusers

Fan coil unitsFan coil units

Thermostat are providedwith temperatureand speed control.

Dx systemDx system

MDF rooms in the gradelevel have been provided with DX system

Units are provided onduty/standby basis

Chilled water systemChilled water system

Energy transfer stations are located in the basement level

Each tower has its own ETS and two dedicated stations for podium.

Chilled water systemChilled water systemTertiaryTertiary

Tertiary heat exchangers and chilled water pumps are located in midlevelPlant rooms.

Chilled water systemChilled water system

View of chilled water pumps

Chilled water systemChilled water system

View of Energy transfer station (heat exchanger)

Toilet extract systemToilet extract system

Fans part of FAHU

Ducting system with ceiling mounted diffusers in toilets

Operation of the fan will be in tandem with FAHU

Kitchen extract systemKitchen extract system

Centrifugal fans located in the plant rooms

Centralised ducting and extract from diffusers mounted in kitchen

Air is passed thru carbon filter assembly (odour removal unit) prior toDischarge to atmosphere.

Kitchen extract systemKitchen extract system

A view of KitchenExtract fan

Refuse extract systemRefuse extract system

Ceiling mounted diffusers in every garbage collection room

Centralised ducting

Fans are located at plant rooms.

Stairwell pressurisationStairwell pressurisationand Lobby relief fansand Lobby relief fans

Both the stair wells will bePressurised in the event ofFire to avoid smoke ingress.

Stairwell pressurisationStairwell pressurisationand Lobby relief fansand Lobby relief fans

Lobby relief fans will ensureThat lobbies are not overPressurised.

Motorised dampers are installedAt every level which will openIn the event of fire

Car park ventilation systemCar park ventilation system

Covers all the three parking levels

View of the exhaust fan riser

Car park ventilation systemCar park ventilation system

View of fresh air intake plenum

Car park ventilation systemCar park ventilation system

Jet fans are locatedThroughout the parkingAreas.

Car park ventilation systemCar park ventilation system

Axial fans are locatedIn fan rooms withMotorised dampersAnd sound attenuators

Water supply system

DEWA incoming supply willBe stored in the basementRCC tank

Transfer pumps feed the mid-Level and roof tanks

Gravity feed to apartments

Penthouse and Loft apartmentsWill be having boosted waterSupply

Tenant water meters are locatedIn mechanical room at each level

Water supply systemWater supply system

GRP tank in thePlant room

Water supply systemWater supply system

A view of tenant waterMeter arrangement

Water supply systemWater supply system

View of PRV stationFor water supplysystem

Hot water systemHot water system

Decentralized system

Each apartment will haveOne dedicated water heater.

Drainage systemDrainage system

Drainage systemDrainage system• Soil waste and vent systems• FIC’s located at grade level close to

perimeter wall inside the sector• Grease traps have been provided for

retail kitchen waste system.• Sump pumps have been provided for

basement drainage.

Rain water systemRain water system• Roof drains have been provided at

roof and terrace levels• Balcony drains have been installed in

all balconies• Collection and discharge through

dedicated rain water stacks

Fire protection systemFire protection system

One dedicated fire tank in the basement serving entire sector

Fire pumps are on duty and Stand by basis

Ring main at the basement

Podium areas are divided into 7 fire zones

Fire protection systemFire protection system

PRV stations have been located various levels

Each floor has been provided with 2 fire hose reels and 2Landing valves.

All areas are sprinkler protected.

A view of fire protectionBranch off at typical floor

Fire protection systemFire protection system

A view of PRVstation

Special fire protection systemsSpecial fire protection systems

• MDF rooms have been protected by FM200 system

Special fire protection systemSpecial fire protection system

LV rooms and generatorrooms have been protectedby CO2 System.

Building management systemBuilding management system

Fully integrated BMS has been provided covering all the towersAnd podium common areas.

Main system with computer and printers are located in theSector control room

DDC’s are installed in all plant rooms.

Remote monitoring and controlling of entire HVAC systemis possible

Supplier: Honeywell

Management trainingManagement training

Thank You

Any questions?