MALS-14 R134 ECU Testing. GySgt Ward SNCOIC 990. CWO5 Art LeBlanc AVO. History. Initial Delivery started in May 2008 Current on hand 55 units R134A ECU Failures (19) 2 bad compressors 2 bad indoor blowers 2 leaking Freon from high side - PowerPoint PPT PresentationTRANSCRIPT
![Page 1: MALS-14 R134 ECU Testing](https://reader030.vdocuments.us/reader030/viewer/2022033018/56815c36550346895dca2185/html5/thumbnails/1.jpg)
MALS-14R134 ECU Testing
CWO5 Art LeBlancAVO
GySgt WardSNCOIC 990
![Page 2: MALS-14 R134 ECU Testing](https://reader030.vdocuments.us/reader030/viewer/2022033018/56815c36550346895dca2185/html5/thumbnails/2.jpg)
• Initial Delivery started in May 2008• Current on hand 55 units• R134A ECU Failures (19)• 2 bad compressors• 2 bad indoor blowers• 2 leaking Freon from high side• 9 outdoor fans contacting outdoor coil/Bracket • 2 outdoor fan motors failed• 1 bad transformer• 1 bad main contactor
History
![Page 3: MALS-14 R134 ECU Testing](https://reader030.vdocuments.us/reader030/viewer/2022033018/56815c36550346895dca2185/html5/thumbnails/3.jpg)
ECU Physical Differences
64% Increase in RPM
![Page 4: MALS-14 R134 ECU Testing](https://reader030.vdocuments.us/reader030/viewer/2022033018/56815c36550346895dca2185/html5/thumbnails/4.jpg)
Investigation/Bulletin History• SEB 1034 was released in July 2010 requiring
a one time inspection of the indoor fan motor.• Checking for presence of flat point set screws vice knurled cup point set screws.
![Page 5: MALS-14 R134 ECU Testing](https://reader030.vdocuments.us/reader030/viewer/2022033018/56815c36550346895dca2185/html5/thumbnails/5.jpg)
• SEB 1047 was released in October 2010 directing an inspection to ensure proper placement of the outdoor fan motor IRT the fan bracket, requiring a distance of 2 ¼” from fan motor to fan mounting
assembly.
Investigation/Bulletin History
![Page 6: MALS-14 R134 ECU Testing](https://reader030.vdocuments.us/reader030/viewer/2022033018/56815c36550346895dca2185/html5/thumbnails/6.jpg)
• Snowbird conducted an E.I. in Dec 2010 on MALS-14 asset that met the requirement of SEB 1047 but still suffered failure of the outdoor fan.
Investigation/Bulletin History
![Page 7: MALS-14 R134 ECU Testing](https://reader030.vdocuments.us/reader030/viewer/2022033018/56815c36550346895dca2185/html5/thumbnails/7.jpg)
Solution• After extensive research by Snowbird, two prototypes
were released for testing trials in Jan. 2011.• Units were delivered and installed @ MALS-14.
Heavier duty bracket
Steel, heavier duty fan
![Page 8: MALS-14 R134 ECU Testing](https://reader030.vdocuments.us/reader030/viewer/2022033018/56815c36550346895dca2185/html5/thumbnails/8.jpg)
Results• One unit has ran with no problems for almost
180 days +.• One unit suffered a outdoor lower fan motor loss
after approximately 110 days.– LCdr Davis, Snowbird, & MF Program Office
traveled to Ch Pt to install new Fan Motor. No problems since…
![Page 9: MALS-14 R134 ECU Testing](https://reader030.vdocuments.us/reader030/viewer/2022033018/56815c36550346895dca2185/html5/thumbnails/9.jpg)
• 2 Catastrophic outdoor fan failures (20 June 2011)
Recent Events & Comments
![Page 10: MALS-14 R134 ECU Testing](https://reader030.vdocuments.us/reader030/viewer/2022033018/56815c36550346895dca2185/html5/thumbnails/10.jpg)
• 1 outdoor fan motor failed (shorted to case) on 22 June 2011
Recent Events & Comments
![Page 11: MALS-14 R134 ECU Testing](https://reader030.vdocuments.us/reader030/viewer/2022033018/56815c36550346895dca2185/html5/thumbnails/11.jpg)
• Wire routing
Recent Events & Comments
![Page 12: MALS-14 R134 ECU Testing](https://reader030.vdocuments.us/reader030/viewer/2022033018/56815c36550346895dca2185/html5/thumbnails/12.jpg)
• Manufactured with sealant used through bulkhead and on motor
Recent Events & Comments
![Page 13: MALS-14 R134 ECU Testing](https://reader030.vdocuments.us/reader030/viewer/2022033018/56815c36550346895dca2185/html5/thumbnails/13.jpg)
QUESTIONS ?