Model JM4

Magnetostrictive Level Transmitter

HART® Installation and Operating Manual

Software v1.x

Page 2: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

2 ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter

Read this Manual Before InstallingThis manual provides information on the Jupiter® magnetostrictive transmitter. It is important that all instructions are read carefully and followed in sequence. Detailed instructions are included in the Installation section of this manual.

Conventions Used in this ManualCertain conventions are used in this manual to convey specific types of information. General technical material, support data, and safety information are presented in narrative form. The following styles are used for notes, cautions, and warnings.

NotesNotes contain information that augments or clarifies an operating step. Notes do not normally contain actions. They follow the procedural steps to which they refer.

CautionsCautions alert the technician to special conditions that could injure personnel, damage equipment, or reduce a component’s mechanical integrity. Cautions are also used to alert the technician to unsafe practices or the need for special protective equipment or specific materials. In this manual, a caution box indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.

WarningsWarnings identify potentially dangerous situations or serious hazards. In this manual, a warning indicates an imminently hazardous situation which, if not avoided, could result in serious injury or death.

Safety MessagesFollow all standard industry procedures for servicing electrical equipment when working with or around high voltage. Always shut off the power supply before touching any components.

WARNING! Explosion hazard. Do not connect or disconnect designs rated Explosion proof or Non-incendive unless power has been switched off and/or the area is known to be non-hazardous.

Low Voltage DirectiveFor use in Installation Category II, Pollution Degree 2. If equipment is used in a manner not specified by the man-ufacturer, protection provided by the equipment may be impaired.

Notice of Trademark, Copyright, and LimitationsOrion & Orion logotype, Magnetrol & Magnetrol logotype, and Jupiter are registered trademarks of Magnetrol International.Copyright © 2019 Magnetrol International. All rights reserved.Performance specifications are effective with date of issue and are subject to change without notice. Magnetrol reserves the right to make changes to the product described in this manual at any time without notice. Magnetrol makes no warranty with respect to the accuracy of the information in this manual.

WarrantyAll Magnetrol/Orion electronic level and flow controls are warranted free of defects in materials or workmanship for eighteen months from the date of original factory shipment.If returned within the warranty period; and, upon factory inspection of the control, the cause of the claim is determined to be covered under the warranty; then, Magnetrol/Orion will repair or replace the control at no cost to the purchaser (or owner) other than transportation.Magnetrol/Orion shall not be liable for misapplication, labor claims, direct or consequential damage or expense arising from the installation or use of equipment. There are no other warranties expressed or implied, except special written warranties covering some Magnetrol/Orion products.

Quality AssuranceThe quality assurance system in place at Magnetrol guar-antees the highest level of quality throughout the com-pany. Magnetrol is committed to providing full customer satisfaction both in quality products and quality service. Magnetrol’s quality assurance system is registered to ISO 9001 affirming its commitment to known international quality standards providing the strongest assurance of product/service quality available.

Page 3: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter 3

Jupiter® JM4 Magnetostrictive Transmitter

1.0 Installation1.1 Installation Prep . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

1.1.1 Factory Mounting & Pre-configuration . . . . 41.1.2 Unpacking . . . . . . . . . . . . . . . . . . . . . . . . . . 41.1.3 Electrostatic Discharge Handling . . . . . . . . . 41.1.4 Site Preparation (Power Supply) . . . . . . . . . . 51.1.5 Equipment and Tools . . . . . . . . . . . . . . . . . . 51.1.6 Mounting Transmitter Head . . . . . . . . . . . . 51.1.7 Remote Mount Transmitter Head . . . . . . . . 61.1.8 Hi-Temp Configurations and Temp Limits . 6

1.2 Mounting for External Mount . . . . . . . . . . . . . . . . . 61.2.1 Available Configurations . . . . . . . . . . . . . . . 61.2.2 Securing the Transmitter to the MLI . . . . . . 71.2.3 Installation on Atlas vs. Aurora . . . . . . . . . . . 81.2.4 Insulation . . . . . . . . . . . . . . . . . . . . . . . . . . . 81.2.5 Vibration Kit . . . . . . . . . . . . . . . . . . . . . . . . 8

1.3 Mounting for Direct Insertion . . . . . . . . . . . . . . . . . 91.3.1 Available Configurations . . . . . . . . . . . . . . . 91.3.2 Float Installation . . . . . . . . . . . . . . . . . . . . . 91.3.3 Centering Disc . . . . . . . . . . . . . . . . . . . . . . 10

1.4 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101.4.1 General Purpose or Non-Incendive (Cl I, Div. 2) . . . . . . . . . . . 101.4.2 Intrinsically Safe . . . . . . . . . . . . . . . . . . . . . 111.4.3 Explosion Proof . . . . . . . . . . . . . . . . . . . . . 11

1.5 Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121.5.1 Bench Configuration . . . . . . . . . . . . . . . . . 121.5.2 Menu Navigation and Data Entry . . . . . . . 12

1.5.2.1 Navigating the Menu . . . . . . . . . . . . . . . 131.5.2.2 Data Selection . . . . . . . . . . . . . . . . . . . . . 131.5.2.3 Entering Numeric Data Using Digit Entry 131.5.2.4 Entering Numeric Data Using Increment/Decrement . . . . . . . . . . . . . . 141.5.2.5 Entering Character Data . . . . . . . . . . . . 14

1.5.3 Password Protection . . . . . . . . . . . . . . . . . . 141.5.4 Model JM4 Menu: Step-By-Step Procedure 151.5.5 Auto-Configuration/Reset New Probe Diagnostic . . . . . . . . . . . . . . . . . . . . 171.5.6 Model JM4 Configuration Menu – Device Setup . . . . . . . . . . . . . . . . . 18

1.6 Configuration using HART®. . . . . . . . . . . . . . . . . . 231.6.1 Connections . . . . . . . . . . . . . . . . . . . . . . . . 23

1.6.2 HART Communicator Display . . . . . . . . . 231.6.3 HART Revision Table . . . . . . . . . . . . . . . . . 231.6.4 HART Menu – Model JM4 . . . . . . . . . . . . 231.6.5 HART Menu Items . . . . . . . . . . . . . . . . . . 27

2.0 Reference Information2.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 382.2 Theory of Operation . . . . . . . . . . . . . . . . . . . . . . . . 382.3 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

2.3.1 Diagnostics (Namur NE 107) . . . . . . . . . . 392.3.2 Troubleshooting Table . . . . . . . . . . . . . . . . 412.3.3 Status Messages . . . . . . . . . . . . . . . . . . . . . 422.3.4 Diagnostic Help . . . . . . . . . . . . . . . . . . . . . 43

2.4 Configuration Information . . . . . . . . . . . . . . . . . . . 442.4.1 Volumetric Capability . . . . . . . . . . . . . . . . 44

2.4.1.1 Configuration Using Built-In Vessel Types . . . . . . . . . . . . . . . . . . . . . 442.4.1.2 Configuration Using Custom Table . . . . . . . . . . . . . . . . . . . 46

2.4.2 Reset Function . . . . . . . . . . . . . . . . . . . . . . 472.4.3 Additional Diagnostic/Troubleshooting Capabilities . . . . . . . . . . . . . . . . . . . . . . . . . 47

2.4.3.1 Event History . . . . . . . . . . . . . . . . . . . . 472.4.3.2 Context-sensitive Help . . . . . . . . . . . . . 472.4.3.3 Trend Data . . . . . . . . . . . . . . . . . . . . . . 47

2.5 Agency Approvals . . . . . . . . . . . . . . . . . . . . . . . . . . 482.5.1 Agency Specifications – FM/CSA Intrinsically Safe Installation . . . . . . . . . . . . . . . . . . . . . 502.5.2 Agency Specifications – FM/CSA Intrinsically Safe Foundation fieldbus™ Installation . . . . 51

2.6 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 522.6.1 Functional/Physical . . . . . . . . . . . . . . . . . . 522.6.2 Probe Selection Guide . . . . . . . . . . . . . . . . 532.6.3 Probe Specifications . . . . . . . . . . . . . . . . . . 532.6.4 Physical Specifications - Transmitter . . . . . . 542.6.5 Power Supply Requirements . . . . . . . . . . . . 56

2.6.5.1 Safe Operating Area . . . . . . . . . . . . . . . 562.6.5.2 Terminal Voltage . . . . . . . . . . . . . . . . . . 56

2.7 Model Number. . . . . . . . . . . . . . . . . . . . . . . . . . . . 572.8 Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63

2.8.1 Replacement Parts . . . . . . . . . . . . . . . . . . . 63Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64

Table of Contents

Page 4: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

4 ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter

CAUTIONSENSITIVE ELECTRONIC DEVICES

DO NOT SHIP OR STORE NEAR STRONGELECTROSTATIC, ELECTROMAGNETIC, OR

RADIOACTIVE FIELDS

1.0 Installation

Caution: Ifequipmentisusedinamannernotspecifiedbyman-ufacturer,protectionprovidedbyequipmentmaybeimpaired

This section provides detailed procedures for properly installing, wiring, configuring and, if needed, troubleshooting the Jupiter magnetostrictive level transmitter.

In most cases, externally mounted units will be shipped from the factory attached to the Orion Instruments magnetic level indicator.

1.1 Installation Prep

1.1.1 FactoryMounting&Pre-configuration

All Jupiter Model JM4 transmitters sold with Orion Instruments® magnetic level indicators (MLIs) are shipped pre-mounted and pre-configured. The span for 4-20 mA and HART or Foundation fieldbus™ is set to the span of the process connec-tions on the MLI. For instructions on how to re-configure the transmitter, see Section 1.5 Configuration.

1.1.2 Unpacking

Unpack the instrument carefully. Inspect all units for damage. Report any concealed damage to carrier within 24 hours. Check the contents against the packing slip and purchase order. Check and record the serial number for future reference when ordering parts.

Caution: Do not discard the shipping container until all parts are accounted for and inspected.

1.1.3 Electrostatic Discharge Handling

Magnetrol/Orion’s electronic instruments are manufactured to the highest quality standards. These instruments use electronic components that may be damaged by static electricity present in most work environments.

The following steps are recommended to reduce the risk of com-ponent failure due to electrostatic discharge.

• Ship and store circuit boards in anti-static bags. If an antistatic bag is not available, wrap the board in aluminum foil. Do not place boards on foam packing materials.

• Use a grounding wrist strap when installing and removing circuit boards. A grounded workstation is recommended.

• Handle circuit boards only by the edges. Do not touch compo-nents or connector pins.

Page 5: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter 5

• Make sure that all electrical connections are completely made and none are partial or floating. Ground all equipment to a reli-able earth ground.

1.1.4 Site Preparation (Power Supply)

Each Jupiter magnetostrictive transmitter is built to match the specifications required within the defined model number. Wiring terminations will need to be made and the configuration will need to be accomplished.

Ensure that the power to be supplied to the instrument is the same voltage (24 VDC) as ordered with the instrument, and that the wiring between the power supply and the Jupiter transmitter is correct for the type of installation.

NOTE: Applying incorrect voltage will damage the unit.

When installing the Jupiter transmitter in a general purpose or hazardous area, all local, state, and federal regulations and guidelines must be observed. See Wiring, Section 1.4.

1.1.5 Equipment and Tools

To attach a Jupiter transmitter to an existing MLI or direct inser-tion model, you may need the following tools:

• 5⁄16" Nut-Driver (for tightening the mounting clamps).

• Screwdriver and assorted hand tools for making conduit and electrical connections.

• Tape measure or ruler if configuring via Set 4 mA and Set 20 mA display screens.

• Digital multimeter or DVM to troubleshoot supply voltage problems.

• 2.5 mm Allen key to tighten transmitter to probe connection.

1.1.6 Mounting Transmitter Head

To attach the JM4 transmitter head to the probe, place the female transmitter connection (Figure 1-2) over the male probe connection (Figure 1-3), and rotate until the pins slide into place. Use a 2.5 mm Allen key to hand tighten set screw (Fig-ure 1-1) to secure the transmitter head in place. Once secured, rotate display until its in the desired position. If transmitter head rotation is not desired, tighten the rotation screw, also with a 2.5 mm Allen key.

Caution: In case of potential head space constraints, ensure that an extra 1.5 inches is available in addition to the height ofthetransmitterhead(andflange,whereapplicable).This extra space is required for attaching or removing the transmitterheadwhennecessary.

NOTE: For dimensions, see Section 2.6.4.

Fig. 1-2 Transmitter Head Connection From Below

Fig. 1-3 Probe Connection From Above

Fig. 1-1 Side Views of Transmitter Head

Locking Set Screw Thread

Locking Set Screw

Rotation Set Screw

Page 6: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

6 ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter

1.1.7 Remote Mount Transmitter Head

For applications with possible clearance or transmitter accessibil-ity issues, the JM4 is available with a remote mount transmitter head. This transmitter head comes with a 3 or 12 ft (0.91 or 3.66 m) heavily shielded cable and can be mounted onto nearby objects.

NOTE: Not available for Explosion proof units.

1.1.8 Hi-TempConfigurationsandTempLimits

The hi-temp JM4 transmitter is capable of operating in pro-cess temperatures between -50 and +800 °F (-46 to +427 °C). Keep in mind that the hi-temp JM4 has a neck extending 91⁄4" (23.5 cm) from the probe to the transmitter head (as opposed to 51⁄4" or 13.3 cm for the standard JM4), so height restrictions should be considered before installing.

1.2 Mounting for External Mount

1.2.1 AvailableConfigurations

The externally mounted Jupiter Model JM4 transmitter is available with a variety of configurations and mounting options. These include (in order from left to right in Figure 1-4) top-mount, top-mount offset, bottom-mount offset. All of these configurations are available with one or two magnetic floats (two floats are necessary to measure total AND interface level).

Page 7: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter 7

1.2.2 SecuringtheTransmittertotheMLI

Each externally mounted JM4 transmitter is provided with a set of clamps (two or more, depending on probe length) for secur-ing to the MLI chamber. If the JM4 was ordered with an Orion MLI, then it will come pre-mounted, but if the transmitter was ordered separately, then it can be secured using the following steps.

1. Place the Jupiter transmitter and mounting clamps in a convenient location.

2. Position the Jupiter transmitter on the side of the MLI where it will be attached. Mark the location and the exact area where the clamps will be attached to hold the Jupiter in place. The probe should extend above and below the process connections to ensure full coverage of the desired measuring span.

3. Attach the lower clamp and tighten so that it remains in place, but loose enough so that there is still room to place the guide tab from the Jupiter between the inside of the clamp and the outer diameter of the MLI chamber.

Fig. 1-4a Top Mount

Fig. 1-4b Top Mount Offset

Fig. 1-4c Bottom Mount

Page 8: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

8 ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter

4. The upper clamp will need to be open to a large enough diam-eter to be able to mount to the MLI as well as the probe. The upper clamp should be positioned just above the 3/4” NPT threads.

5. Mount the Jupiter guide pin in the lower clamp and tighten. If necessary, use strapping tape to temporarily hold in place on the MLI.

6. Position the upper clamp to attach the unit to the MLI and tighten.

7. Discard any tape temporarily holding the Jupiter to the MLI.

1.2.3 InstallationonAtlasvs.Aurora

When mounting the Jupiter model JM4 transmitter onto the outside of an MLI, float proximity must be taken into account. For an Orion Atlas MLI, the distance between the float and the chamber wall is the same all around the chamber, so the trans-mitter could be placed anywhere. However, for an Aurora MLI, the chamber is divided into two sections: the float section and the magnetostrictive probe/gas-bypass section (Figure 1-5a). Because of this, the transmitter must specifically placed as close to the float section as possible, to ensure proper signal strength.

1.2.4 Insulation

For personnel and equipment protection, high-temperature insu-lation is available with JM4 transmitters. Insulation pads provide protection for the transmitter only, whereas insulation blankets cover the entire chamber, which can help protect personnel from elevated temperatures.

To install a JM4 with an insulation pad, first secure pad to the chamber, then secure the transmitter over the pad (Figure 1-6a). To install a JM4 with an insulation blanket, secure the blanket over the chamber, then be sure to place the transmitter in the smaller of the two grooves, leaving the larger groove for visual indication (Figure 1-6b).

1.2.5 Vibration Kit

For applications in which vibration is an issue, the Jupiter model JM4 is available with a vibration absorption kit.

Fig. 1-5a Aurora® Cross-section

Fig. 1-5b Atlas™ Cross-section

Fig. 1-6a Insulation Pad

Fig. 1-6b Insulation Blanket

Page 9: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter 9

1.3.2 FloatInstallation

Use caution when handling probes to ensure probe is not bent during installation. A bend in the probe may prevent float from traveling freely up and down the probe.

1. Verify float will pass through vessel opening, if not, it will be necessary to attach the float after the probe is installed.

2. Carefully insert probe into vessel and thread or bolt to the mating connection as appropriate.

3. The float is held on the probe by a C-clip inserted into a groove machined into the tip of the probe. The float is at-tached or removed by removing and reinserting the C-clip. To ensure proper float orientation, the float is marked “UP”.

NOTE: Whenplacingfloatsonprobe,makesurethesidemarked“UP”isfacingup.Iftherearetwofloats,makesurethetotallevelfloat(thelighterfloat)isontop,andtheinterfacefloat(theheavierfloat)isonthebottom.

1.3 Mounting for Direct Insertion

1.3.1 AvailableConfigurations

The direct insertion version of the JM4 transmitter has several available configurations as well. As with external-mount, direc-tion insertion JM4 is available with one or two floats. JM4 can be installed in external chambers or into the main vessel. It is also available with a centering disc and/or stilling well to keep the probe in position.

Fig. 1-7a. Direct Insertion, Two Floats

Fig. 1-7b. Direct Insertion, One Float

Page 10: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

10 ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter

1.3.3 Centering Disc

All Jupiter model JM4 transmitters that come with a stilling well are also provided with a centering disc to prevent the probe from making contact with the stilling well.

1.4 Wiring

Caution: HART version of the JUPITER Model JM4 transmitter operate at voltages of 11-28.6 VDC, while FOUNDATION fieldbusversionsoperateat9-17.5VDC.Highervoltageswill damage the transmitter.

Wiring connections between the power supply and the Jupiter Model JM4 transmitter should be made using 18-22 AWG shielded twisted pair instrument cable. Connections are made to the terminal strip and the ground connections within the top enclosure compartment.

The directions for wiring the Jupiter transmitter depend on the applications:

• General Purpose or Non-Incendive (Cl I, Div. 2)

• Intrinsically Safe

• Explosion Proof

WARNING! Explosion hazard. Do not connect or disconnect designs rated Explosion proof or Non-incendive unless power has been switched off and/or the area is known to be non-hazardous.

1.4.1 GeneralPurposeorNon-Incendive(ClI,Div.2)

A general purpose installation does not have flammable media present.

Areas rated Non-Incendive (Cl I, Div. 2) have flammable media present only under abnormal conditions.

No special electrical connections are required.

Caution: Ifflammablemediaiscontainedinthevessel,thetrans-mitter must be installed per Class I, Div 1 standards of areaclassification.

To install General Purpose or Non-Incendive wiring:

1. Remove the cover from the wiring compartment of the trans-mitter. Install the conduit plug in the unused opening and use PTFE tape/sealant to ensure a liquid-tight connection.

2. Install a conduit fitting and pull the supply wires.

3. Connect shield to an earth ground at power supply.

4. Connect an earth ground wire to the nearest green ground screw (not shown in illustration).

5. Connect the positive supply wire to the (+) terminal and the negative supply wire to the (-) terminal.

Red(+)

(+)(-)

Black(-)

Fig. 1-8 Wiring Diagram

Page 11: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter 11

6. Replace and tighten the cover to the transmitter wiring compart-ment before applying power.

1.4.2 IntrinsicallySafe

An Intrinsically Safe (IS) installation potentially has flammable media present. An approved IS barrier must be installed in the non-hazardous (safe) area to limit the available energy out to the hazardous area. See Agency Specifications Section 2.5.1.

To install Intrinsically Safe wiring:

1. Ensure that the IS barrier is properly installed in the safe area (refer to local plant or facility procedures). Complete the wir-ing from the power supply to the barrier and from the barrier to the JM4 transmitter.

2. Remove the cover from the wiring compartment of the trans-mitter. Install the conduit plug in the unused opening and use PTFE tape/sealant to ensure a liquid-tight connection.

3. Install a conduit fitting and pull the supply wires.

4. Connect shield to an earth ground at power supply.

5. Connect an earth ground wire to the nearest green ground screw (not shown in illustration).

6. Connect the positive supply wire to the (+) terminal and the negative supply wire to the (-) terminal.

7. Replace and tighten the cover to the wiring compartment of the transmitter before applying power.

1.4.3 ExplosionProof

Explosion Proof (also referred to as XP or flameproof ) is another method of designing equipment for installation into hazardous areas. A hazardous location is an area in which flammable gases or vapors are (or may be) present in the air in quantities suffi-cient to produce explosive or ignitable mixtures

The wiring for the transmitter must be contained in Explosion Proof conduit extending into the safe area.

• Due to the specialized design of the JM4 transmitter, no Explo-sion Proof conduit fitting (EY seal) is required within 18" of the transmitter.

• An Explosion Proof conduit fitting (EY seal) is required between the hazardous and safe areas.

To install Explosion Proof transmitter:

1. Install Explosion Proof conduit from the safe area to the conduit connection of the JM4 transmitter (refer to the local plant or facility procedures).

2. Remove the cover from the wiring compartment of the transmitter.

3. Connect shield to an earth ground at the power supply.

Page 12: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

12 ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter

4. Connect an Earth ground wire to the nearest green ground screw per local electrical code (not shown in illustration).

5. Connect the positive supply wire to the (+) terminal and the negative supply wire to the (-) terminal.

6. Replace and tighten the cover to the wiring compartment of the transmitter before applying power.

1.5 Configuration

Although the Jupiter Model JM4 transmitter can be delivered pre-configured from the factory, it can also be easily reconfigured in the shop or at the installation using the local LCD/Keypad, HART communicator, or PACTware/DTM. Bench configura-tion provides a convenient and efficient way to set up the trans-mitter before going to the tank site to complete the installation.

Before configuring any transmitter, collect all operating parame-ters information.

Apply power to the transmitter and follow the step-by-step pro-cedures below for the menu-driven transmitter display. See Menu Navigation and Data Entry Section 1.5.2

Information on configuring the transmitter using a HART com-municator is given in Section 1.6.

1.5.1 BenchConfiguration

The Jupiter Model JM4 transmitter can be easily configured at a test bench by connecting a standard 24 VDC power supply di-rectly to the transmitter terminals as shown in the accompanying diagram. An optional digital multimeter is shown in the event that mA current measurements are desired.

NOTE: Current measurements taken at these test points are an ap-proximate value. Accurate current readings should be taken withthedigitalmultimeterdirectlyinserieswiththeloop.

NOTE:WhenusingaHARTcommunicatorforconfiguration,amini-mum250-ohmlineloadresistanceisrequired.RefertoyourHART communicator manual for additional information.

NOTE:Thetransmittercanbeconfiguredwithouttheprobe.Pleasedisregard the “No Probe” diagnostic indicator that will appear.

1.5.2 Menu Navigation and Data Entry

The four push buttons offer various forms of functionality for navigation and data entry.

The Model JM4 user interface is hierarchical in nature, best de-scribed as a tree structure. Each level in the tree contains one or more items. Items are either menu labels or parameter names.

• Menu labels are presented in all capital letters

• Parameters are capital words

Power Supply24 VDC

TestCurrent Meter

(-)negative

(-)positive

+

-

-

+

Fig. 1-9 G.P./I.S./Explosion Proof Model

Page 13: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter 13

1.5.2.1 Navigating the Menu

UP moves to the previous item in the menu branch.

DOWN moves to the next item in the menu branch.

BACK moves back one level to the previous (higher) branch item.

ENTER enters into the lower level branch or switches to the en-try mode. Holding the ENTER down on any highlighted menu name or parameter will show help text for the item.

1.5.2.2 Data Selection

This method is used for selecting configuration data from a specific list.

UP and DOWN to navigate the menu and highlight the item of interest.

ENTER allows modification of that selection.

UP and DOWN to choose new data selection.

ENTER to confirm selection.

Use BACK (Escape) key at any time to abort the procedure and escape to previous branch item.

1.5.2.3EnteringNumericDataUsingDigitEntry

This method is used to input numeric data, e.g., Probe Length, set 4mA and set 20mA.

Push Button KeystrokeAction

UpMoves up to the next highest digit (0,1,2,3,....,9 or decimalpoint).Ifhelddownthedigitsscrolluntilthepush button is released.

DownMoves down to the next lowest digit (0,1,2,3,....,9 or decimalpoint).Ifhelddownthedigitsscrolluntilthepush button is released.

Back

Moves the cursor to the left and deletes a digit. If thecursorisalreadyattheleftmostposition,thenthescreenisexitedwithoutchangingthepreviouslysaved value.

EnterMoves the cursor to the right. If the cursor is located at a blank character position, the new value is saved.

All numeric values are left-justified, and new values are entered from left to right. A decimal point can be entered after the first digit is entered, such that .9 is entered as 0.9.

Some configuration parameters can have a negative value. In this case, the leftmost position is reversed for the sign (either “-” for a negative value, or “+” for a positive value).

Fig 1-10 Home Screen

UP DOWN BACK ENTER

Jupiter® Model JM4

Level

in

PV%

OK58.7

Page 14: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

14 ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter

1.5.2.4 Entering Numeric Data Using Increment/Decrement

Use this method to input the following data into parameters such as Damping and Failure Alarm.

Push Button KeystrokeAction

Up

Incrementsthedisplayedvalue.Ifhelddownthedigits scroll until the push button is released.Depending on which screen is being revised, the incrementamountmayincreasebyafactorof10after the value has been incremented 10 times.

Down

Decrementsthedisplayedvalue.Ifhelddownthedigits scroll until the push button is released.Depending on which screen is being revised, the decrementamountmayincreasebyafactorof10after the value has been decremented 10 times.

BackReturns to the previous menu without changing the originalvalue,whichisimmediatelyredisplayed.

EnterAcceptsthedisplayedvalueandreturnstotheprevious menu.

1.5.2.5 Entering Character Data

This method is used for parameters requiring alphanumeric char-acter entry, such as for entering tags, etc.

General Menu Notes:

Push Button KeystrokeAction

UpMovestothepreviouscharacter(Z...Y...X...W).Ifheld down, the characters scroll until the push button is released.

DownMovestothenextitemcharacter(A...B...C...D).Ifheld down, the characters scroll until the push button is released.

BackMoves the cursor back to the left. If the cursor is alreadyattheleftmostposition,thenthescreenisexited without changing the original tag characters.

EnterMoves the cursor forward to the right. If the cursor is at the rightmost position, then the new tag is saved.

1.5.3 Password Protection

The Jupiter Model JM4 transmitter has three levels of pass-word protection to restrict access to certain portions of the menu structure that affect the operation of the system. The user password can be changed to any numerical value up to 59999. When the transmitter is programmed for password protection, a password is required whenever configuration values are changed.

User Password

The User Password allows the customer to limit access to the basic configuration parameters.

Page 15: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter 15

The default User Password installed in the transmitter at the factory is 0. With a password of 0, the transmitter is no longer password protected, and any value in the basic user menus can be adjusted without entering a confirming password.

NOTE: If a User Password is not known or has been misplaced, the menu item New Password in the DEVICE SETUP/AD-VANCEDCONFIGmenudisplaysanencryptedvaluerepre-senting the present password. Contact Technical Support with thisencryptedpasswordtoretrievetheoriginalUserPass-word.

Advanced Password

Certain portions of the menu structure that contain more advanced parameters are further protected by an Advanced Password.

This password will be provided when necessary, by Factory technical support.

Factory Password

Calibration-related and other factory settings are further protected by a Factory Password.

1.5.4 Model JM4 Menu: Step-By-Step Procedure

The following tables provide a complete explanation of the soft-ware menus displayed by the JM4 transmitter. The menu layout is similar between the local Keypad/LCD interface, the DD, and the DTM.

Use these tables as a step-by-step guide to configure the trans-mitter based on the desired measurement type from the follow-ing selections:

• Level Only

• Interface Only

• Interface & Level

• Level & Volume

HOME SCREEN

The Home Screen consists of a “slide show” sequence of Mea-sured Values screens which are rotated at 2-second intervals. Each Home Measured Value screen can present up to four infor-mation items:

• HART® Tag

• Measured Value Label, Numerical Value, Units

• Status Will be displayed as text or optionally with

NAMUR NE 107 symbol

• Primary Value Bar Graph (shown in %)

Fig 1-11 Home Screen

UP DOWN BACK ENTER

Jupiter® Model JM4

Level

in

PV%

OK58.7

Page 16: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

16 ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter

The Home Screen presentation can be customized by viewing or hiding some of these items. See DISPLAY CONFIG under the DEVICE SETUP menu in Section 1.6.4 HART Menu - Model JM4.

Figure 1-9 is an example of a Home Screen for a Model JM4 configured for a Level Only application.

MAIN MENU

Pressing any key on the Home Screen will present the Main Menu, consisting of three basic menu labels shown in all capital letters.

• DEVICE SETUP

• DIAGNOSTICS

• MEASURED VALUES

As shown, the reverse video represents a cursor identifying the selected item, which will appear in reverse video on the LCD. The actions of the keys at this point are:

Push Button KeystrokeAction

Up Noaction,asthecursorisalreadyatthefirstiteminthe MAIN MENU

Down Moves the cursor to DIAGNOSTICS

Back Moves back to HOME SCREEN, the level above MAIN MENU

Enter Presents the selected item, DEVICE SETUP

NOTES: 1. Items and parameters that are shown in lower level menus willdependontheMeasurementTypechosen.Thosepa-rametersnotapplicabletothepresentMeasurementTypewill be hidden.

2.HoldingdowntheEnterkeywhenthecursorishighlightedover a parameter or menu will provide additional information about that item.

DEVICE SETUP

Choosing DEVICE SETUP from the MAIN MENU will result in an LCD presentation as shown at left.

The small down arrow shown at the right hand side of the screen is the indication that more items are available below and can be accessed by pressing the DOWN key.

Section 1.6.4 shows the entire tree menu for the Model JM4 DEVICE SETUP Menu.

MEASURED VALUES

Allows the user to scroll through all of the available measured values for the measurement type chosen.

MAIN MENUDEVICE SETUPDIAGNOSTICSMEASURED VALUES

Hold down Enter keyfor help

Fig. 1-12. Main Menu

Page 17: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter 17

1.5.5 Auto-Configuration/ResetNewProbeDiagnostic

Each JM4 probe has its own set of configuration parameters stored inside. With these parameters, it is possible to auto-configure the transmitter using the following steps.

1. Connect the new probe to the transmitter.

2. The home screen will display a “Device Failure: New Probe” message in alternating video on the screen.

3. Pressing any key will bring the user directly to the “Clear New Probe Diagnostic” line in the Device Setup\Advanced Config\Probe Params menu.

NOTE: Clear New Probe Diagnostic will replace current settings withthoseneededtoproperlyusethenewlyattachedprobe.Beforeexecuting,considersavingafilecontainingyourcurrentBasicConfig,I/OConfig,andLocalDisplayConfigsettingsforreferenceusingtheDTMoraHARTcommunicator.

4. Press the Enter key to initiate the clearing process.

NOTE: Afterrunningthediagnostic,checkPV,measurementtype,and 4 and 20 mA set points to be sure these parameters are appropriatelysetfortheapplication.

Page 18: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

18 ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter

1.5.6 ModelJM4ConfigurationMenu–DeviceSetup

*OnlyavailablewhenMeasurementType=Volume&Level **NotavailablewhenMeasurementType=InterfaceOnly ***OnlyavailablewhenMeasurementType=InterfaceOnlyorInterface&Level ****OnlyAvailablewhenMeasurementType=Interface&Level

Identity

Basic ConfigVolume ConfigLocal Display ConfigAdvanced ConfigFactory Config

Measurement Type:Level OnlyInterface OnlyInterface & LevelVolume & Level

System Units:

Level Offset:-50 ft to 50 ft(-15 m to 15 m)

Probe Properties

Probe Model (read only)S/N (read only)Configuration (read only)Probe Type (read only)Probe Length (read only)Temperature Rating (read only)Vibration Rating (read only)

Level UnitsInchesFeet MillimetersCentimetersMeters

Distance UnitsInchesFeet MillimetersCentimetersMeters

Interface Level Units***InchesFeet MillimetersCentimetersMeters

Upper Thickness Units****InchesFeet MillimetersCentimetersMeters

Device Setup

Main Menu

Home Screen

Product Name (read only)Orion S/N (read only)DIGITAL BOARD (read only)ANALOG BOARD (read only)[Physical Dev Tag] (read only)[Device Address][Date Code] (read only)

Volume Units*Cubic FeetCubic InchesGallonsMillilitersLiters

Fill Rate Units*Cubic Ft/SecondCubic Ft/MinuteCubic Ft/HourGallons/SecondGallons/MinuteGallons/HourLiters/SecondLiters/MinuteLiters/Hour

Temperature UnitsFahrenheitCelsius

Page 19: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter 19

*OnlyavailablewhenMeasurementType=Volume&Level **NotavailablewhenMeasurementType=InterfaceOnly ***OnlyavailablewhenMeasurementType=InterfaceOnlyorInterface&Level ****OnlyAvailablewhenMeasurementType=Interface&Level

1.5.6 ModelJM4ConfigurationMenu–DeviceSetup

IdentityBasic ConfigVolume Config*

I/O ConfigLocal Display ConfigAdvanced ConfigFactory Config

Vessel Type:RectangularHorizontal/FlatHorizontal/EllipseHorizontal/SphericalSphericalVertical/FlatVertical/EllipseVertical/SphericalVertical/ConicalCustom Table

Primary Variable

4 mA Set Pt (LRV):-52 to +102 feet (-15.8 m to +31.1 m )([Upr] Level**, Ifc Level***)0 to 50 feet (Upr Thickness)0 to 9999999 cf (Volme*)

20 mA Set Pt (URV):-52 to +102 feet (-15.8 m to +31.1 m) ([Upr] Level**, Ifc Level***)0 to 50 feet (Upr Thickness)0 to 9999999 cf (Volme*)

Failure Alarm:22 mA3.6 mAHold

Damping:0 to 10 seconds

Device Setup

Main Menu

Home Screen

Vessel Dimensions:RadiusEllipse DepthConical HeightWidthLength

Custom Table Setup:Custom Table Type:LinearSpline

Level Input Source:KeypadSensor

CUSTOM TABLE VALUES:Up to 30 Pairs ofLevel/Volume Data

Page 20: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

20 ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter

1.5.6 ModelJM4ConfigurationMenu–DeviceSetup

IdentityBasic ConfigVolume ConfigI/O ConfigLocal Display Config

Advanced ConfigFactory Config

Language:EnglishFrançaisDeutschEspañolРусскийPortuguês

Status Symbol:HideView

Long Tag:HideView

PV Bar Graph:Hide View

Measured Values Upr Level**:HideView

Ifc Level***:Hide View

Upr Thickness:HideView

Distance:HideView

Volume*:Hide View

Fill Rate*:Hide View

Device Setup

Main Menu

Home Screen

Upr Echo Strength**:Hide View

Ifc Echo Strength***:HideView

% Output:HideView

Analog Output:HideView

Elec Temp:HideView

*OnlyavailablewhenMeasurementType=Volume&Level **NotavailablewhenMeasurementType=InterfaceOnly ***OnlyavailablewhenMeasurementType=InterfaceOnlyorInterface&Level ****OnlyAvailablewhenMeasurementType=Interface&Level

Page 21: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter 21

1.5.6 ModelJM4ConfigurationMenu–DeviceSetup

Sensitivity (read only)Reset New Probe DiagnosticLvl Thresh Mode (read only)Lvl Thresh Value (read only)Upr Lvl Polarity (read only)

IdentityBasic ConfigVolume ConfigI/O ConfigLocal Display ConfigAdvanced Config

Factory Config

Blocking Distance:0 to 50 feet(0 m to 15 m)

Minimum Separation:0 to 28 inches(0 cm to 71 cm)

Zero Offset:-50 to 50 feet(-15 m to 15 m)

Level Trim:-2 to 2 feet(-0.6 m to 0.6 m)

Failure Alarm Delay:0 to 5 sec

Sensitivity:0 to 255

Theshold Settings

Analog Output

New User Password:0 to 599999

Reset Parameters

CONFIG CHANGED

Probe Properties

Lvl Thresh Mode:Auto LargestFixed ValueSloped

Lvl Sloped Start Value:17 to 239

Lvl Thresh Value:0 to 87

Upr Lvl Polarity:NegativePositive

Poll Address:0 to 63

Analog Output Mode:Disabled (Fixed)Enabled (PV)

Fixed Loop Current:400 to 2000

Adjust Analog Output:Adjust 4mAAdjust 20mA

4mA Trim Value (read only)20mA Trim Value (read only)Fdbk 4mA Trim Value (read only)Fdbk 20mA Trim Value (read only)

Device Setup

Main Menu

Home Screen

Indicator Mode:EnabledDisabled

Reset Config Changed

Page 22: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

22 ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter

1.5.6 ModelJM4ConfigurationMenu–DeviceSetup

IdentityBasic ConfigVolume ConfigI/O ConfigLocal Display ConfigAdvanced ConfigFactory Config

Elec Temp Offset:-60 to +60º C

NAPValue:0 to 59999

Factory Reset

Factory Calib

Probe Properties

Conv Factor0 to 32767

Scale Offset-3.28 to 3.28 ft (-1 m to 1 m)

Drive+ Counts0 to 20

Wait Counts0 to 20

Drive- Counts0 to 20

Probe Conv Factor (read only)Probe Scale Offset (read only)Drive+ Counts (read only)Wait Counts (read only)Drive- Counts (read only)Calibration Date (read only)Calibration Location (read only)

Device Setup

Main Menu

Home Screen

Page 23: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter 23

1.6 ConfigurationusingHART

A HART (Highway Addressable Remote Transducer) remote unit, such as a HART communicator, can be used to provide a communication link to the Jupiter Model JM4 transmitter. When connected to the control loop, the same system measure-ment readings shown on the transmitter are also shown on the communicator. The communicator can also be used to config-ure the transmitter. The HART communicator may need to be updated to include the Jupiter Model JM4 software (Device Descriptions). Refer to your HART Communicator Manual for update instructions.

1.6.1 Connections

A HART communicator can be operated from a remote loca-tion by connecting it to a remote junction or by connecting it directly to the terminal block in the wiring compartment of the Jupiter transmitter.

HART uses the Bell 202 frequency shift keying technique of high-frequency digital signals. It operates on the 4–20 mA loop and requires 250 Ω load resistance. A typical connection be-tween a communicator and the Jupiter transmitter is shown in Figure 1-10.

1.6.2 HART Communicator Display

A typical communicator display is an 8-line by 21-character LCD. When connected, the top line of each menu displays the model (Model JM4) and its tag number or address. For detailed operating information, refer to the instruction manual provided with the HART communicator.

1.6.3 HART Revision TableModel JM4 1.xHART Version HCF Release Date CompatiblewithJM4SoftwareDev Rev 1, DD Rev 1 May 2014 Version 1.0 and later

1.6.4 HARTMenu–ModelJM4

The Jupiter transmitter HART menu trees are shown in the fol-lowing pages. Open the menu by pressing the alphanumeric key 4, then Device Setup, to display the second-level menu.

Junction

- +

PowerSupply

RL >250Ω

CurrentMeter

JunctionRoomDisplay

Fig. 1-12. Placement of Portable HART Communicator in Communication Loop

Page 24: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

24 ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter

1.6.4 HARTMenu–ModelJM4 NOTE: Numbered menu boxes below correspond to numbered tables on Section 1.6.5.

1 PV2 PV Analog Output3 PV % Output4 Device Setup5 Setup Wizard6 Diagnostics7 Measured Values

1 Enter Password2 Tag3 Long Tag4 Descriptor5 Final asmbly num6 Date7 Message8 Date/Time/Initials9 Factory Identity

1 Identity

2 Basic Config

3 Volume Config4 I/O Config5 Local Display Config6 Advanced Config7 Factory Config

1 Manufacturer2 Product Name3 Orion S/N4 Main Hardware Rev.5 Main Firmware Rev.6 CoP Hardware Rev.7 CoP Firmware Rev.8 Cfg chng count9 Device ID10 Universal Revision11 Fld dev rev12 Software rev13 Num req preams

1 Enter Password2 Measurement Type3 System Units4 Level Offset5 Basic Config Diagram6 Probe Properties

1 Level2 Upr Level3 Ifc Level4 Upr Thickness5 Volume6 Fill Rate7 Distance 8 % Output9 Analog Output10 Echo Strength11 Upr Echo Strength12 Ifc Echo Strength13 Temperature

1 Enter Password2 Vessel Type3 Vessel Dimensions4 Custom Table Setup5 Vessel Diagram

1 Probe Model2 S/N3 Configuration4 Probe Type5 Probe Length6 Temperature Rating7 Vibration Rating

1

2 3

4

5

6

7

26

Page 25: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter 25

1.6.4 HARTMenu–ModelJM4 NOTE: Numbered menu boxes below correspond to numbered tables on Section 1.6.5.

1 PV2 PV Analog Output3 PV % Output4 Device Setup5 Setup Wizard6 Diagnostics7 Measured Values

1 Identity2 Basic Config3 Volume Config4 I/O Config

5 Local Display Config

6 Advanced Config

7 Factory Config

1 Enter Password2 PV is3 PV 4 mA Set Point4 PV 20 mA Set Point5 PV Failure Alarm6 Damping7 I/O Config Diagram8 Variable Selection9 Graph Ranges10 Probe Properties

1 Enter Password2 Language3 Status Symbol4 Long Tag5 PV Bar Graph6 Display Setup Diagram7 Measured Values

1 Enter Password2 Blocking Distance3 Minimum Distance4 Level Trim5 Ifc Level Trim6 Failure Alarm Delay7 Sensitivity8 Adv Config Diagram9 Threshold Settings10 Analog Output11 New User Password12 Reset Parameters13 Probe Properties 1 Minimum Separation

2 Sensitivity3 Reset New Probe Diagnostic4 Lvl Thresh Mode 5 Lvl Thresh Value6 Upr Lvl Polarity7 Ifc Lvl Thresh Mode8 Ifc Lvl Thresh Value9 Ifc Lvl Polarity

1 Enter Password2 Elec Temp Offset3 NAP Value4 Factory Reset5 Factory Param 16 Factory Param 27 Factory Param 38 Factory Param 49 Factory Calib10 Probe Properties 1 Probe Conv Factor

2 Probe Scale Offset3 Drive+ Counts4 Wait Counts5 Drive- Counts6 Calibration Date7 Calibration Location

1 Lvl Thresh Mode2 Lvl Thresh Value3 Ifc Lvl Thresh Mode4 Ifc Lvl Thresh Value5 Upr Lvl Polarity6 Ifc Lvl Polarity

8

10

12

13

14

9

11

Page 26: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

26 ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter

1 PV2 PV Analog Output3 PV % Output4 Device Setup5 Setup Wizard6 Diagnostics7 Measured Values

1 Present Status

2 Event History

3 Advanced Diagnostics

4 Echo Curves

5 Echo History

6 Trend Data

1 Level Ticks2 Echo Strength3 Ifc Ticks4 Ifc Echo Strength5 Lvl Noise/Threshold6 Lvl Noise Location7 Ifc Noise/Threshold8 Ifc Noise Location9 Distance10 Fdbk Current

1 Event Log2 Refresh History3 Reset History4 Set Clock

1 Present Temperature2 Max Temperature3 Min Temperature4 Reset Max/Min Temp

1 Internal Values2 Elec Temperatures3 Transmitter Tests

1 Echo Graph2 Curve 13 Curve 24 Refresh Graph5 Zoom6 Echo History Log7 Refresh History8 History Setup9 Delete History10 Set Clock

1 Enter Password2 Sensitivity3 Blocking Distance4 Upr Lvl Polarity5 Ifc Lvl Polarity6 Lvl Thresh Mode7 Lvl Thresh Value8 Ifc Lvl Thresh Mode9 Ifc Lvl Thresh Value

1 Echo Graph2 Curve 13 Curve 24 Refresh Graph5 Zoom6 Save Ref Echo Curve7 Parameters

1 Trend Data2 Level3 Ifc Level4 Upr Thickness5 Echo Strength6 Ifc Echo Strength7 Analog Output8 % Output9 Data Log Setup

1 Echo History Mode2 Event Triggers3 Time Triggers4 Set Clock5 Enter Password

1 Trending Variables2 Time Setup3 Set Clock4 Enter Password

1.6.4 HARTMenu–ModelJM4 NOTE: Numbered menu boxes below correspond to numbered tables on Section 1.6.5.

15

16

17

18

19

20

21

22

23

24

25

Page 27: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter 27

1.6.5 HARTMenuItems 1

Display Description

1 PV

Digital representation that tracks the Analog Output Number 1, under normal operating modes.

Level of material on the probe.(Whenininterfacemode,thisvaluecorrespondstotheleveloftheuppersurface.)

2 PV Analog Output

Digital representation that tracks the Analog Output Number 1, under normal operating modes.

Analog Output Value: Value that tracks the Digital Value representation, under normal operating modes

3 PV % Output

Digital representation that tracks the Analog Output Number 1, under normal operating modes.

Analog Output Value: Value that tracks the Digital Value representation, under normal operating modes

4 Device Setup Setofmenustoallowfullconfigurationofthetransmitter.5 Setup Wizard

6 Diagnostics Menu showing Diagnostic information.

7 Measured ValuesAread-onlyscreenthatpresentsthevariousoutputvaluesthatcanbedisplayed.(AvailableoptionswilldependonMeasurementType.)

2

Display Description1 Identity Aread-onlyscreenthatdisplaysbasicmanufacturer’sinformationaboutthetransmitter.2 Basic Config Amenuthatallowsforbasicconfigurationofthetransmitter.

3 Volume ConfigAmenuthatallowsforentryofknowntankshapesorcustomtablesforvolumetricoutput.ThismenucontainsvarioustankshapesforeasyconfigurationforthoseapplicationsrequiringVolu-metric output.

4 I/O ConfigAllowsforconfigurationofthe4/20mAAnalogOutput,whichincludestheloweranduppersetpoints, Damping, and Failure Alarms.

5 Local Display Config

Allows for customized presentation of information on the graphic LCD. The LCD can be con-figuredtodisplayuptotwoMeasuredVariables,alongwithaTag,BarGraph,andNE107symbols.

6 Advanced ConfigAllowsformoreadvancedconfigurationandtroubleshooting.(AdvancedPasswordmayberequiredforaccesstoparameters.)Contact Technical Support.

7 Factory ConfigAllowsviewingofFactoryParameters.Theseparametersareprotectedbyafactorypasswordandarenotintendedtobeadjustedinthefield.

*For‘Volume&Level’MeasurementTypeonly.

Page 28: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

28 ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter

1.6.5 HARTMenuItems(cont.) 3

Display Description

1 Enter Password

2 Tag

TextthatisassociatedwiththeFieldDeviceinstallation.Thistextcanbeusedbytheuserinanyway.ArecommendeduseisasauniquelabeltoaplantthatcorrelatestoaFieldDevicelabel,aplantdrawing,oronaControlSystem.Thisvariableisalsousedasatypeofdatalinklayeraddresshandle.

3 Long TagFunctionsexactlylikeTagexceptthesizeislarger(maximumof32ISOLatin1characters).

4 DescriptorTextthatisassociatedwiththeFieldDevice.Thistextcanbeusedbytheuserinanyway.Thereisnospecificrecommendeduse.

5 Final asmbly numNumberthatisusedforidentificationpurposes,andisassociatedwiththeoverallFieldDevice.

6 DateGregoriancalendardatethatisstoredintheFieldDevice.Thisdatecanbeusedbytheuserinanyway.Thereisnospecificrecommendeduse.

7 MessageTextthatisassociatedwiththeFieldDevice.Thistextcanbeusedbytheuserinanyway.Thereisnospecificrecommendeduse.

8 Date/Time/Initials Whenandbywhomcalibrationwasperformed.

9 Factory IdentityAread-onlyscreenthatdisplaysdetailedmanufacturer’sinformationaboutthetransmitter,suchas Serial Number and hardware/software revisions.

4

Display Description

1 ManufacturerReferencesaspecificmanufacturer,whichisusuallyacompanyname,thatisresponsibleforthe manufacture of this Field Device.

2 Product NameTransmitter Trade Name.

3 Orion S/NSerial number of the electronics contained in this transmitter.

4 Main Hardware Rev.This revision corresponds to the electronics that are used in the Field Device.

5 Main Firmware Rev.ThisrevisioncorrespondstothesoftwareorfirmwarethatisembeddedintheMainProcessorof the Field Device.

6 CoP Hardware Rev.This revision corresponds to the electronics that are used in the Field Device.

7 CoP Firmware Rev.ThisrevisioncorrespondstothesoftwareorfirmwarethatisembeddedintheCoProcessorofthe Field Device.

8 Cfg chng counIndicatesthenumberoftimesthedevice’sconfigurationorcalibrationhasbeenchangedbyahost application or from a local operator interface.

9 Device IDUniquelyidentifiestheFieldDevicewhencombinedwiththeManufacturerIdentificationandDeviceType.Therefore,thisvariablecannotbemodifiedbytheHostuser.

10 Universal RevisionRevision of the Universal Device Description, to which the Field Device conforms.

11 Fld dev revRevisionoftheFieldDeviceSpecificDeviceDescription,towhichtheFieldDeviceconforms.

12 Software revThisrevisioncorrespondstothefirmwarethatisembeddedintheFieldDevice.

13 Num req preamNumberofPreamblesrequiredfromtheHostrequestbytheFieldDevice.

Page 29: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter 29

1.6.5 HARTMenuItems(cont.) 5

Display Description1 Enter Password

2 Measurement TypeThe desired measurement mode of operation. (SelectionofMeasurementTypemaybeconstrainedbytheProbeModel.)

3 System UnitsAmenuthatallowsforsettingthemeasurementunitsusedbythetransmitter.

4 Level OffsetDesired level reading when liquid surface is at the tip of the probe.(Rangeis-50feet[-15meters]to+50feet[15meters])

5 Basic Config Diagram

6 Probe Properties Displaysprobeconfigurationparameters.

6

Display Description

1 Probe ModelTypeofprobeconnectedtothetransmitter,asshownbytheprobemodelnumberonthename-plate. Refer to the I/O Manual for additional information regarding different Probe Models.

2 S/NSerial number of the probe connected to this transmitter.

3 ConfigurationProbeconfigurationwithsensorlocation.

4 Probe TypeTypeofprobeconnectedtothetransmitter.

5 Probe LengthDistancefromprobereferencepointtoendofprobe.Upto35feet(10.7meters)maximumdepending on Probe Model. (Probe reference point is bottom of NPT Threads, top of BSP Threads,orflangefacefordirectinsertion,orendofprobeheadassemblyforexternalmount.)

6 Temperature RatingTemperature rating of the probe.

7 Vibration RatingVibration rating of the probe.

7

Display Description

1 Enter Password

2 Vessel Type* Shapeofvessel.(UsedwhenMeasurementType=Volume)

3

Radius* Radiusofthecylindrical/sphericalportionofthevessel

LengthHorizontallengthoftherectangularvesselorofthecylindricalportionofavesselwithellipticalor spherical ends.

Width Horizontal width of the rectangular vessel.4 Custom Table AllowsforCustomVolumeStrappingTableentry.5 Vessel Diagram

Page 30: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

30 ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter

1.6.5 HARTMenuItems(cont.) 8

Display Description1 Enter Password

2 PV isAnindexlocationthatindicateswhichFieldDevicedynamicvariablehasbeenmappedintothePrimaryVariabledynamicvariable.

3 PV 4 mA Set Point Enter 4 mA point in level units4 PV 20 mA Set Point Enter 20 mA point in level units

5 PV Failure Alarm

Digital representation that tracks the Analog Output Number 1, under normal operating modes.

DefineshowtheAnalogOutputwillrespondwhentheFieldDevicedetectsthattheAnalogOutputmaynotbetrackingtheassociatedFieldDeviceVariable.NOTE-TheDigitalValuerepresentationmaynotbedeterminate.

6 DampingAdampingfactor(0-10seconds)maybeaddedtosmooththeoutputintheeventofturbu-lence.

7 I/O Config Diagram

8 Variable SelectionAllowsforselectionoftheSecondaryVariable(SV),TertiaryVariable(TV),andQuaternaryVariable(QV).Theanalog4/20mAoutputwillfollowthePV.

9 Graph Ranges DefinesthelimitsoftheverticalaxesinDD/DTMgraphs.

10 Probe Properties

- Lvl 4mA Set Point DefinestheoperationalendpointfromwhichtheAnalogValueandthe0%pointofthePer-centRangearederived.Inaddition,theLowerRangeValuedefinesanoperationalendpointfrom which the alarms associated with the Analog Value and the alarms associated with the Digital Value representation are derived.

- Ifc 4mA Set Point*

- Thk 4mA Set Point*

- Vol 4mA Set Point**

- Lvl 20mA Set Point DefinestheoperationalendpointfromwhichtheAnalogValueandthe100%pointofthePer-centRangearederived.Inaddition,theUpperRangeValuedefinesanoperationalendpointfrom which the alarms associated with the Analog Value and the alarms associated with the Digital Value representation are derived.

- Ifc 20mA Set Point*

- Thk 4mA Set Point*

- Vol 20mA Set Point**

*For‘Interface&Level’MeasurementTypeOnly **For‘Volume&Level’MeasurementTypeonly.

Page 31: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter 31

1.6.5 HARTMenuItems(cont.) 9

Display Description

1 Enter Password

2 Language EnableschoiceoflanguagetobedisplayedontheLCD.3 Status Symbol EnablesNE107StatussymboltobedisplayedonHomeScreen.4 Long Tag EnablesLongTagtobedisplayedontheHomeScreen.

5 PV Bar GraphEnablesabargraph(displayingthePrimaryVariableinpercent)tobedisplayedontheHomeScreen.

6 Display Setup Diagram

7 Measured ValuesAread-onlyscreenthatpresentsthevariousoutputvaluesthatcanbedisplayed.(AvailableoutputswilldependonMeasurementType).

- Upr Level

Aread-onlyscreenthatpresentsthevariousoutputvaluesthatcanbedisplayed.(AvailableoutputswilldependonMeasurementType).

- Ifc Level

- Upr Thickness

- Distance

- Volume

- Fill Rate

- Upr Echo Strength

- Ifc Echo Strength

- % Output

- Analog Output

- Elec Temp

Page 32: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

32 ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter

1.6.5 HARTMenuItems(cont.) 10

Display Description1 Enter Password

2 Blocking DistanceDistance below the reference point within which level is ignored.(Operationisundefinedwhentheliquidleveliswithintheblockingdistance.)

3 Level Trim An offset value to be used to force the transmitter to output the exact Level or Distance. This shouldonlybeusedafterallparametershavebeenenteredcorrectly,andithasbeencon-firmedthatthetransmitteristrackingthecorrectlevel.4 Ifc Level Trim

5 Failure Alarm DelayDelaythatcanbeaddedtoloopfailurecondition.Thisdelaycanbeusedtoignorenuisance,shorttermalarms.Initialsettingofthisdelayshouldbeshort,e.g.,1-2seconds.

6 Sensitivity

PresentSensitivity(gain)oftheinstrument.Defaultsettingdependsonthevalueintheprobememoryandissuitableformostinstalla-tions. RefertoI&Omanualbeforeadjusting.

7 Adv Config Diagram

8 Threshold Settings

Allowsforconfigurationofthevariousthresholdsettings.AutomaticThresholdisusedtodetectthestrongestsignalontheprobeandshouldonlybeusedwhenitisensuredthatonlyonemediumispresent.FixedThresholdisusedtodetectthefirstvalidsignalontheprobeandshouldbeusedincaseswherestratificationcanoccur.Forexample,applicationswherewater bottoms can occur.

9 Analog Output

Certainparametersarepasswordprotectedtolimitaccessbytheuser.ParametersthatshouldneverbechangedbytheuserareprotectedwiththeFactorypassword.Someparam-eters,intendedforfielduse,thatmaybechangedinspecial,controlledsituationsrequiretheAdvanced password.

10 New User Password Change password that is required to access user parameters.

11 Reset ParametersResetthedevicetofactorycalibratedsettings.If using a HART host, disconnect and then reconnect the host after performing the reset.

12 Probe Properties Displaysprobeconfigurationparameters.

11

Display DescriptionLvl Thresh Mode Selects the signal threshold control for measuring the upper level pulse.

Defaultsettingdependsonthevalueintheprobememoryandissuitableformostinstalla-tions.RefertoI&Omanualbeforeadjusting.

Lvl Thresh Value

Ifc Lvl Thresh Mode

Ifc Lvl Thresh Value

Upr Lvl PolaritySelectsthepolarityformeasuringtheupperlevelpulse.Typicallysettomatchthepolarityofthefirstportionofthesine-wavesignalofadirectinsertionfloat,orthefirstportionoftheM-shaped signal of an external mount probe.

Ifc Lvl Polarity

Page 33: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter 33

1.6.5 HARTMenuItems(cont.) 12

Display Description

1 Minimum SeparationMinimumdistancethatcanbeachievedbetweenthemagnetsonadjacentfloatswhenthefloatsaretouchingeachother.

2 SensitivityPresentSensitivity(gain)oftheinstrument.Defaultsettingdependsonthevalueintheprobememoryandissuitableformostinstallations.RefertoI&Omanualbeforeadjusting.

3 Reset New Probe Diagnostic

Clearsthediagnosticthatindicatesanewprobehasbeenattached.Updatesthememoryinthe transmitter to match the probe.

4 Lvl Thresh Mode Selects the signal threshold control for measuring the upper level pulse.Defaultsettingdependsonthevalueintheprobememoryandissuitableformostinstallations.RefertoI&Omanualbeforeadjusting.5 Lvl Thresh Value

6 Upr Lvl PolaritySelectsthepolarityformeasuringtheupperlevelpulse.Typicallysettomatchthepolarityofthefirstportionofthesine-wavesignalofadirectinsertionfloat,orthefirstportionoftheM-shaped signal of an external mount probe.

7 Ifc Lvl Thresh Mode Selects the signal threshold control for measuring the upper level pulse.Defaultsettingdependsonthevalueintheprobememoryandissuitableformostinstallations.RefertoI&Omanualbeforeadjusting.8 Ifc Lvl Thresh

Value

9 Ifc Lvl PolaritySelectsthepolarityformeasuringtheupperlevelpulse.Typicallysettomatchthepolarityofthefirstportionofthesine-wavesignalofadirectinsertionfloat,orthefirstportionoftheM-shaped signal of an external mount probe.

13

Display Description1 Enter Password

2 Elec Temp OffsetPCB temperature calibration value.RefertoI&Omanualbeforeadjusting.

3 NAP Value Advanced Password used for advanced troubleshooting.

4 Factory ResetResetthedevicetofactorydefaultsettings.If using a HART host, disconnect and then reconnect the host after performing the reset.

5 Factory Param 1 Factoryparameter.Displayedfordiagnosticpurposesonly.6 Factory Param 2

7 Factory Param 3

8 Factory Param 4

9 Factory Calib Read-OnlyMenushowingFactoryCalibrationParameters.10 Probe Properties Displaysprobeconfigurationparameters.

14

Display Description1 Probe Conv Factor Factoryparameter.Displayedfordiagnosticpurposesonly.2 Probe Scale Offset

3 Drive+ Counts

4 Wait Counts

5 Drive- Counts

6 Calibration Date Date on which the probe was calibrated.

7 Calibration Location

Location where the probe was calibrated.

Page 34: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

34 ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter

1.6.5 HARTMenuItems(cont.) 15

Display Description1 Present Status ShowsthePresentStatus(health)ofthetransmitter.2 Event History Thehistoryofthe10mostrecentdiagnosticevents.

3 Advanced Diagnostics

Menu containing Advanced Diagnostic parameters.

4 Echo Curves AllowsconfigurationoftheEchoCurveoption.

5 Echo HistoryAllowsconfigurationoftheEchoHistoryOption.SavinganEchoCurveunderafaultconditionis important for accurate troubleshooting.

6 Trend Data Graphdisplayingreal-timetrenddata.

16

Display Description1 Event Log Allows for viewing of the 10 most recent diagnostic indicators.

2 Refresh HistoryDisplaysahistoryofmostrecentdiagnosticevents.Foreachevent,thetimewhentheeventoccurredandthedurationoftheeventareshown.Thetableofhistoryeventsdisplaysthemostrecenteventatthetopwithsuccessivelyprecedingeventsindescendingorder.

3 Reset History ClearsentriesinStatusHistoryandresetstheruntimetozero.4 Set Clock Sets the Real-Time Clock in the device.

17

Display Description1 Internal Values Shows detailed transmitter performance-related parameters.2 Elec Temperatures ThismenudisplaystheMaximum,Minimum,andPresenttemperaturesoftheelectronics.3 Transmitters Tests Menu containing various tests to determine the functioning of the device.

18

Display Description

1 Level TicksRelative location of level signal.Displayedfordiagnosticpurposesonly.

2 Echo StrengthRelative amplitude of the level signal.Displayedfordiagnosticpurposesonly.

3 Ifc TicksRelative location of the interface level signal.Displayedfordiagnosticpurposesonly.

4 Ifc Echo StrengthRelative amplitude of the interface level signal.Displayedfordiagnosticpurposesonly.

5 Lvl Noise/Threshold Amplitude of the largest noise signal in percent of the level threshold.

6 Lvl Noise LocationLocation on the probe where greatest upper level noise has occurred.Location is relative to the lower probe end.

7 Ifc Noise/Threshold Amplitude of the largest noise signal in percent of the interface threshold.

8 Ifc Noise LocationLocation on the probe where greatest interface level noise has occurred.Location is relative to the lower probe end.

9 Distance Distance from the sensor reference point to the upper surface level.10 Fdbk Current Factoryparameter.Displayedfordiagnosticpurposesonly.

Page 35: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter 35

1.6.5 HARTMenuItems(cont.) 19

Display Description1 Present Temperature Present temperature measured in the electronics compartment.2 Max Temperature Maximum temperature measured in the electronics compartment.3 Min Temperature Minimum temperature measured in the electronics compartment.

4 Reset Max Min TempReset the maximum and minimum temperatures measured in the electronics compartment to the present temperature.

20

Display Description1 Echo Graph

2 Curve 1 Selecttheprimarycurvetodisplay.3 Curve 2 Selectthesecondarycurvetodisplay.4 Refresh Graph Click to refresh Echo Curve.5 Zoom AllowsusertozoominandoutofaspecificportionoftheEchoCurve.

6 Save Ref Echo CurveMethod to save a reference echo curve in the device. The reference echo curve will be re-taineduntilover-writtenbyanewreferenceechocurve.

7 Parameters

21

Display Description1 Enter Password

2 SensitivityPresentSensitivity(gain)oftheinstrument.Defaultsettingdependsonthevalueintheprobememoryandissuitableformostinstallations.RefertoI&Omanualbeforeadjusting.

3 Blocking DistanceDistance below the reference point within which level is ignored.(Operationisundefinedwhentheliquidleveliswithintheblockingdistance.)

4 Upr Lvl PolaritySelectsthepolarityformeasuringtheupperlevelpulse.Typicallysettomatchthepolarityofthefirstportionofthesine-wavesignalofadirectinsertionfloat,orthefirstportionoftheM-shaped signal of an external mount probe.

5 Ifc Lvl PolaritySelectsthepolarityformeasuringtheinterfacelevelpulse.Typicallysettomatchthepolarityofthefirstportionofthesine-wavesignalofadirectinsertionfloat,orthefirstportionoftheM-shaped signal of an external mount probe.

6 Lvl Thresh ModeSelects the signal threshold control for measuring the upper level pulse.Defaultsettingdependsonthevalueintheprobememoryandissuitableformostinstallations.RefertoI&Omanualbeforeadjusting.

7 Lvl Thresh ValueRelative setting of the threshold for detecting level.Defaultsettingdependsonthevalueintheprobememoryandissuitableformostinstallations.RefertoI&Omanualbeforeadjusting.

8 Ifc Lvl Thresh ModeSelects signal threshold control for measuring liquid-liquid interface level.Defaultsettingdependsonthevalueintheprobememoryandissuitableformostinstallations.RefertoI&Omanualbeforeadjusting.

9 If Lvl Thresh ValueRelative setting of the threshold for detecting interface level.Defaultsettingdependsonthevalueintheprobememoryandissuitableformostinstallations.RefertoI&Omanualbeforeadjusting.

Page 36: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

36 ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter

1.6.5 HARTMenuItems(cont.) 22

Display Description1 Echo Graph

2 Curve 1 Selecttheprimarycurvetodisplay.3 Curve 2 Selectthesecondarycurvetodisplay.4 Refresh Graph Click to refresh Echo Curve.5 Zoom AllowsusertozoominandoutofaspecificportionoftheEchoCurve.6 Echo History Log Listing of echo curves saved in the device.

7 Refresh History Methodtore-readtheechohistorysummary.

8 History Setup Menuforsettinguptheautomaticechohistorycapturefeatureofthedevice.

9 Delete History AllowstheHistoryinformationtobeclearedandreset.10 Set Clock Sets the Real-Time Clock in the device.

23

Display Description1 Echo History Mode Selection to save echo curves based on time intervals or selected diagnostic events.

2 Event TriggersListing of diagnostic indicators that can be selected to trigger an automatic saving of an echo curve.

3 Time Triggers Listing of parameters to control time-based automatic saving of echo curves.4 Set Clock Sets the Real-Time Clock in the device.5 Enter Password

24

Display Description1 Trend Data Graphdisplayingreal-timetrenddata.

2 LevelLevel of material on the probe.(Whenininterfacemode,thisvaluecorrespondstotheleveloftheuppersurface.)

3 Ifc LevelLevel of liquid-liquid interface.(Whennointerfaceispresent,thisvaluecorrespondstothelevelofproductinthevessel.)

4 Upr Thickness Thicknessoftheupperliquidlayer.

5 Echo StrengthRelative strength of the level signal being detected.(Whenintheinterfacemode,thisvaluecorrespondstothestrengthoftheupperlevelsignal.)

6 Ifc Echo Strength Relative strength of the interface level signal.

7 Analog OutputAllowsforconfigurationofthe4/20mAAnalogOutput,whichincludesthePollAddress,AnalogOutput Mode, and trimming of the loop.

8 % Output PercentofOutputofthePrimaryVariableandAnalogOutput1Current.9 Data Log Setup Menucontainingparameterstosetupthedevice’sinternaldatalogfeature.

Page 37: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter 37

1.6.5 HARTMenuItems(cont.) 25

Display Description

1 Trending VariablesListing of Device Variables that can be selected to be saved in the internal data log feature of the device.

2 Time Setup A menu that allows the user to set the time span and sample interval for the Data Log.3 Set Clock Sets the Real-Time Clock in the device.4 Enter Password

26

Display Description

1 LevelLevel of material on the probe.(Whenininterfacemode,thisvaluecorrespondstotheleveloftheuppersurface.)

2 Upr Level

3 Ifc LevelLevel of liquid-liquid interface.(Whennointerfaceispresent,thisvaluecorrespondstothelevelofproductinthevessel.)

4 Upr Thickness Thicknessoftheupperliquidlayer.5 Volume Volume of product in the vessel.6 Fill Rate Fill rate of the liquid in the vessel.7 Distance Distance from the sensor reference point to the upper surface level.8 % Output PercentofOutputofthePrimaryVariableandAnalogOutput1Current.9 Analog Output Value that tracks the Digital Value representation, under normal operating modes

10 Echo StrengthRelative strength of the level signal being detected.(Whenintheinterfacemode,thisvaluecorrespondstothestrengthoftheupperlevelsignal.)

11 Upr Echo Strength

12 Ifc Echo Strength Relative strength of the interface level signal.13 Temperature The present temperature of the electronics.

Page 38: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

38 ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter

2.0 ReferenceInformation

This section presents an overview of the operation of the Jupiter magnetostrictive transmitter, information on troubleshooting common problems, listing of agency approvals, lists of replace-ment and recommended spare parts, and detailed functional, performance and physical specifications for the instrument.

2.1 Description

The Jupiter is a two-wire, 24 VDC level transmitter based on the concept of magnetostrictive level measurement technology.

The Jupiter electronics are housed in an ergonomic housing of two tandem compartments angled at a 45° angle for ease of wiring and configuration.

2.2 Theory of Operation

Magnetostrictive level sensors are based on “time-of-flight” technology.

Permanent magnets contained within a float device tracks the process liquid as it changes level. The Jupiter probe is fixed with-in close proximity to this magnetic field. A short current pulse is then applied to a specially designed wire alloy contained within the probe. The interaction of the current pulse and magnetic field causes distortion in a small section of the wire alloy. This in turn creates a vibratory disturbance which begins to travel through the wire at a very constant rate of speed. The distur-bance is later detected via a sensing device at the transmitter end of the probe and sent to the electronics unit where it is filtered and amplified.

Extremely accurate level measurement can thus be obtained precisely measuring the elapsed time between the current pulse (start), and the returned pulse (stop). The Jupiter electronics module processes these signals, and then performs various math-ematical operations in order to provide the user with an analog and/or digital representation of the liquid level.

2.3 Troubleshooting

The JUPITER Model JM4 transmitter is designed and engi-neered for trouble-free operation over a wide range of operating conditions. The transmitter continuously runs a series of inter-nal self-tests and displays helpful messages on the large graphic liquid crystal display (LCD) when attention is required.

The combination of these internal tests and diagnostics messages offer a valuable proactive method of troubleshooting. The device not only tells the user what wrong, but also, and more impor-tantly, offers suggestions on how to solve the problem.

All of this information can be obtained directly from the trans-mitter on the LCD, or remotely by using a HART communica-tor or PACTware and the JUPITER Model JM4 DTM.

Page 39: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter 39

PACTwareTM PC Program

The JUPITER Model JM4 offers the ability to perform more advanced diagnostics such as Trending and Echo Curve analysis using a PACTware DTM. This is a powerful troubleshooting tool that can aid in the resolution of any diagnostic indicators that may appear.

2.3.1 Diagnostics (Namur NE 107)

The JUPITER Model JM4 transmitter includes an exhaustive list of Diagnostic Indicators which follow the NAMUR NE 107 guidelines.

NAMUR is an international user association of automation technology in process industries, whose goal is to promote the interest of the process industry by pooling experiences among its member companies. In doing so, this group promotes interna-tional standards for devices, systems, and technologies.

The objective of NAMUR NE 107 was essentially to make maintenance more efficient by standardizing diagnostics in-formation from field devices. This was initially integrated via Foundation fieldbus, but the concept applies regardless of the communication protocol.

According to the NAMUR NE107 recommendation, “Self Monitoring and Diagnosis of Field Devices,” fieldbus diagnostic results should be reliable and viewed in the context of a given application. The document recommends categorizing internal diagnostics into four standard status signals:

• Failure

• Function Check

• Out of Specification

• Maintenance required

These categories are shown by both symbols and colors, depend-ing on the display capability.

In essence, this approach ensures that the right diagnostic information is available to the right person-at the right time. In addition, it allows diagnostics to be applied, as most appropriate, for a particular plant application (such as process control engi-neering or asset management maintenance). Customer specific mapping of diagnostics to these categories allows for flexible configuration depending on the user’s requirements.

From an external Model JM4 transmitter perspective, diagnos-tic information includes measurement of process conditions, in addition to detection of internal device or system anomalies.

Fig. 2-1. Namur NE 107 Status Signals - Symbols

Page 40: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

40 ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter

As mentioned above, the indicators can be assignable (via the a DTM or host system) by the user to any (or none) of the NAMUR recommended Status Signal categories: Failure, Func-tion Check, Out of Specification, and Maintenance Required.

The Foundation fieldbus transmitter version of the Model JM4 was implemented according to the Field Diagnostics Profile, which is consistent with the objectives of NE 107.

In the Foundation fieldbus version, diagnostic indicators can be mapped to multiple categories, an example is shown in the diagram at left.

In this example, “Calibration Required” is mapped to both the Out of Specification and Maintenance Required status signals, and the diagnostic indicator named “High Temperature” is mapped to none of the signals.

Indicators that are mapped to the Failure category will normally result in a current loop alarm output. The alarm state for HART transmitters is configurable as high (22 mA), Low (3.6 mA), or Hold (last value).

Users will not have the ability to unassign certain indicators from the Failure signal category as the Model JM4 user interfac-es will prohibit or reject such re-assignment entries). This is to ensure that current loop alarms are asserted in situations where the device is not able to provide measurements due to critical failures. (For example, if the alarm selection has not been set to Hold, or a fixed current mode is in effect.)

A default mapping of all diagnostic indicators will be applied initially, and can be re-applied through use of a reset function.

Refer to the table below for a complete listing of the Model JM4 diagnostic indicators, along with their explanations, default cate-gories, and recommended remedies.

NOTES: 1. The remedies shown in this table can also be seen on the transmitterLCDbyviewingthepresentstatusscreenwhenthe device is in a diagnostic condition.

2. Those indicators showing failure as the default result in an alarm condition.

Analog Output Error

Failure

FunctionCheck

OutofSpecification

MaintenanceRequired

DiagnosticIndicators

CalibrationRequired

High Temperature

Echo LostDry

Probe

Fig. 2-2 Namur NE 107 Status Signals - Venn Diagram

Page 41: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter 41

2.3.2 Troubleshooting Table

Problem SolutionBlankdisplay EnsurelocalKeypad/LCDisproperlyinstalled.

Removepowerandreapplypowertotheunit.

Check to see if LED on module is illuminated.

Check voltage at terminal board.

Ifjumperisinplaceunderdisplay,removejumper.Transmitterdoesnottracklevel(ExternalMount)

(DirectInsertion)

Check echo curve for noise preventing tracking of level.

Remove transmitter and probe from piping column and test with re-alignment magnet. Run magnet from bottom to top of probe.

Check zero and span calibration. If no change in output, consultthefactory.

Floatinsidethelevelgaugeismovingslowlyornotatall. Ensure that the magnetic level indicator is plumb.

Theprocessfluidbeingmeasuredmaybetooviscousandheattracingmayberequiredtomakethematerialmorefluid.

Thespecificgravityoftheprocessfluidandfloatweightmayneedtobereverified.

Theliquidbeingmeasuredmaycontainmagneticparticlescollectingonthemagneticsectionofthefloatcausing drag. If this happens magnetic trap assemblies canbepurchasedfromthefactory.

Visualinspectionofthefloatmayberequiredtoseeifthefloathascollapsed.

LEVEL,%OUTPUT,andLOOPvaluesareallinaccurate.

Wipe probe with external magnet.

Confirmconfigurationsettings.

Consultfactory.LEVEL,%OUTPUT,andLOOPvaluesfluctuate. Check echo curve for noise levels that could be affecting

level reading.

Turbulence, increase damping factor until readings stabilize.

Levelreadingondisplayiscorrect,butloopvalueisstuck at 4 mA.

Set poll address to zero.

Page 42: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

42 ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter

2.3.3 Status Messages

Display Message BriefDescription SolutionNo Probe No probe connected to

transmitterCheckprobeconnectiontotransmitter,ConsultFactory

New Probe Probememorycontentsdisagree with EEPROM image

OnDisplay,goto‘ResetNewProbe’andenterpassword.

Analog Board Error No response from co-processor, or clock error

ConsultFactory.

ProbeMemoryError Memorydeviceinprobeisunresponsive

ConsultFactory.

No Float Detected Echo curve does not rise above threshold

Run echo curve. If a visible peak exists, increase gain/sensitivity.Ifthereisnopeak,visuallyinspectprobetoconfirmpresenceoffloat.Iffloatstillnotdetected,consultfactory.

ConfigConflict MeasurementTypeandPrimaryVariableselectionparameters are inconsistent

ConfirmmeasurementtypematchesPV.GoodExamples:

1. MT=LevelOnly,PV=TotalLevel2. MT=Level&IFC,PV=IFC

High Volume Alarm Level exceeds highest level in strapping table or top of vessel bymorethan5%

Confirmspansetpointsareatdesiredvalues.Run echo curve. Check for noise at top of probe. If top mount or direct insertion unit, increase deadband/blocking distance

Extra Float Detected Echo curve rises above threshold additional instance from expected number

CheckMeasurementtype;Runechocurvetocheckforextrapeaks;DecreaseGain/SensitivitySettings;Swipeprobewithpocketmagnettoeliminatepossibilityofresidualmagnetism;ConsultFactory.

2nd Float Missing Echo curve rises above thresholdonlyonce

CheckMeasurementtype;Runechocurve;IncreaseGain/SensitivitySettings;Verifytwofloatsarepresent.ConsultFactory.

High Elec Temp Present electronics temperature above maximum

Take measures to cool transmitter head. Consider installing sunshade.

Low Elec Temp Present electronics temperature below minimum

Take measure to warm transmitter head. Consider installing heat tracing.

AdjustAnalogOut Loop trim parameters are at default values

Perform Trim Loop Current Check via HART Communication

LowSupplyVoltage Powersupplyvoltageinadequate to prevent brownout or reset

Checksupplyvoltage.

Weak Upr Echo Strengthofechofromfloatatgas-liquid interface less than allowable minimum

Runechocurve.IncreaseGain/SensitivitySettings.ConsultFactory.

Weak Ifc Echo Strengthofechofromfloatatliquid-liquid interface less than allowable minimum

Runechocurve.IncreaseGain/SensitivitySettings;Consult Factory.

High Noise/Lvl Threshold

Strength of baseline noise too near upper level threshold

Check echo curve for noise levels. EchoRejectionmayberequired,ConsultFactory,Swipeprobewithpocketmagnettoeliminatepossibilityofresidualmagnetism

High Noise/Ifc Threshold

Strength of baseline noise too near interface level threshold

Check echo curve for noise levels.EchoRejectionmayberequired,ConsultFactory,Swipeprobewithpocketmagnettoeliminatepossibilityofresidualmagnetism

Page 43: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter 43

2.3.4 Diagnostic Help

Selecting DIAGNOSTICS from the MAIN MENU presents a list of five ITEMS from the top level of the DIAGNOSTICS tree.

When Present Status is highlighted, the highest MAGNETROL priority active diagnostic indicator (numerically lowest in Table 3.3.3) is displayed on the bottom LCD line, which is “OK” as shown at left. Pressing the ENTER key moves the active diagnostic indicator to the top line outdented and presents in the lower area of the LCD a brief explanation of and possible remedies for the indicated condition. A blank line separates the explanation from the remedies. Additional active diagnostic indicators, if any, appear with their explanations in descending priority order. Each additional active indicator name-explanation pair is separated by a blank line from the one above.

If the explanation and remedy text (and additional name expla-nation pairs) exceeds the available space, a appears in the right-most column of the last line indicating more text below. In this situation, the DN key scrolls text up one line at a time. Similarly, while text exists above the upper line of the text field, a appears in the rightmost column of the top (text) line. In this situation, the UP key scrolls the text down one line at a time. Otherwise the DN and UP keys are inoperative. In all cases the ENT or DEL key reverts to the previous screen.

When the transmitter is operating normally and the highlight cursor is positioned on Present Status, the bottom LCD line displays “OK” because no diagnostic indicators are active.

EVENT HISTORY – This menu displays the parameters related to diagnostic event logging.

ADVANCED DIAGNOSTICS – This menu displays parame-ters related to some of the advanced diagnostics available within the Model JM4.

INTERNAL VALUES – Displays read-only internal param-eters.

ELEC TEMPERATURES – Displays temperature informa-tion as measured in the potted module in degrees F or C.

TRANSMITTER TESTS – Allows the user to manually set the output current to a constant value. This is a method for the user to verify operation of the other equipment in the loop.

ECHO CURVES – This menu allows the user to display the live Echo Curve and Echo Rejection on the LCD.

DIAGNOSTICSPresent StatusEVENT HISTORYADVANCED DIAGNOSTICSECHO CURVESECHO HISTORYOK

DEVICE FAILURE

No Probe

Fig. 2-3 Diagnostics Menu

Fig. 2-4 Status Message - No Probe

Page 44: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

44 ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter

2.4 ConfigurationInformation

2.4.1 Volumetric Capability

Selecting Measurement Type = Volume and Level allows the Model JM4 transmitter to measure volume as the Primary Mea-sured Value.

2.4.1.1 ConfigurationUsingBuilt-InVesselTypes

The following table provides an explanation of each of the Sys-tem Configuration parameters required for volume applications that use one of the nine Vessel Types.

ConfigurationParameter Explanation

Volume Units AselectionofGallons(factorydefaultVolumeUnit),Milliliters,Liters,CubicFeet,or Cubic Inches, is provided.

Vessel Type

SelecteitherVertical/Flat(factorydefaultVesselType),Vertical/Elliptical,Vertical/Spherical, Vertical/Conical, Custom Table, Rectangular, Horizontal/Flat, Horizontal/Elliptical, Horizontal/Spherical, or Spherical.

Note:VesselDimsisthenextscreenonlyifaspecificVesselTypewasselected.IfCustomTablewasselected.Refertopage46toselecttheCustTableTypeandCust Table Vals.

Vessel Dims See the vessel drawings on the following page for relevant measuring areas.Radius UsedforallVesselTypeswiththeexceptionofRectangular.

Ellipse Depth Used for Horizontal and Vertical/Elliptical vessels.Conical Height Used for Vertical/Conical vessels.

Width Used for Rectangular vessels.Length Used for Rectangular and Horizontal vessels.

Page 45: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter 45

Horizontal/Spherical

Horizontal/Elliptical

Horizontal/Flat

Vertical/Elliptical

Vertical/Flat Vertical/Conical

Rectangular

Vertical/Spherical

Spherical

Vessel Types

Page 46: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

46 ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter

2.4.1.2 ConfigurationUsingCustomTable

If none of the nine Vessel Types shown can be used, a Custom Table can be created. A maximum of 30 points can be used to establish the level to volume relationship. The following table provides an explanation of each of the System Configuration parameters for volume applications where a Custom Table is needed.

ConfigurationParameter Explanation (Custom Volumetric Table)

Volume Units A selection of Gallons(factorydefaultVolumeUnit),Milliliters,Liters,CubicFeet, or CubicInches, is provided.

Vessel Type Select Custom Table if none of the nine Vessel Types can be used.

Cust Table TypeThe Custom Table points can be a Linear(straightlinebetweenadjacentpoints)or Spline(canbeacurvedlinebetweenpoints)relationship.Seebelowdrawingfor more information.

Cust Table Vals

A maximum of 30 points can be used in building the Custom Table. Each pair of valueswillhavealevel(height)intheunitschosenintheLevel Units screen, and the associated volume for that level point. The values must be monotonic, i.e. each pair of values must be greater than the previous level/volume pair. The last pair of values should have the highest level value and volume value associated with the level in the vessel.

Linear SPLINE

TransitionPoint

Use where walls are not perpendicular to base.

Concentrate at least two points at the beginning (P1) and end(P9);andthreepointsateithersideoftransitionpoints

P1

P1

P2

P2P3

P4

P5P6P7

P8P9

Page 47: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter 47

2.4.2 Reset Function

A parameter labeled “Reset Parameter” is located at the end of the DEVICE SETUP/ADVANCED CONFIG menu. In the event a user gets confused during configuration or advanced troubleshooting, this parameter gives the user the ability to reset the Model JM4 transmitter configuration.

Unique to the Model JM4 transmitter is the ability for Orion In-struments to fully “pre-configure” devices to customer requests. For that reason, the Reset function will return the device back to the state at which it left the factory.

It is recommended that Orion Instruments Technical Support be contacted as the Advanced User password will be required for this reset.

2.4.3 AdditionalDiagnostic/TroubleshootingCapabilities

2.4.3.1 EventHistory

As a means for improved troubleshooting capability, a record of significant diagnostic events is stored with time and date stamps. A real time on board clock (which must be set by the operator), will maintain the current time.

2.4.3.2 Context-sensitive Help

Descriptive information relevant to the highlighted parameter in the menu will be accessible via the local display and remote host interfaces. This will most often be a parameter-related screen, but could also be information about menus, actions (for example, Loop [Analog Output] Test, resets of various types), diagnostic indicators, etc.

For example: Dielectric Range — Selects the range bounding the dielectric constant of the medium in vessel. For interface measurement mode, it selects the range bounding the dielectric constant of the lower liquid medium. Some ranges may not be selectable depending on the probe model.

2.4.3.3 Trend Data

Another new feature to the Model JM4 is the ability to log several measured values (selectable from any of the primary, sec-ondary, or supplemental measured values) at a configurable rate (for example, once every five minutes) for a period ranging from several hours to a number of days (depending on the configured sample rate and number of values to be recorded). The data will be stored in nonvolatile memory in the transmitter with date and time information for subsequent retrieval and visualization using the associated Model JM4 DTM.

Page 48: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

48 ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter

2.5 AgencyApprovals

These units are in compliance with the EMC directive 2004/108/EC, the PED directive 97/23/EC and the ATEX directive 2014/34/EU.

Explosion Proof US/Canada:FM16US0357X/FM16CA0168XClass I, Div 1, Group B, C and D, T4 Ta = -40°C to +70°C Type 4X, IP67

Flame Proof:Flameproof US/ Canada:Class I, Zone 0/1, AEx db IIB + H2 T1…T6 Ga/Gb (US)Class I, Zone 0/1, Ex db IIB + H2 T1…T6 Ga/GB (Canada) Ta = - 40 C to +70 C IP 67ATEX FM14ATEX0059X:II 1/2G Ex db IIB+H2 T6…T1 Ga/GbTa=-40°C to +70°CIP67IEC- IEC Ex FMG14.0028XEx db IIB+H2 T6…T1 Ga/GbTa=-40°C to +70°CIP67

Non- IncendiveUS/Canada:FM16US0357X/FM16CA0168XU.S. - Class I, II, III, Division 2, Group A, B, C, D, E, F, G, T4, Ta = -40°C to 70°C CANADA – Class I, Division 2, Group A,B,C,D T4, Ta = -40°C to 70°C Class I, Zone 2 AEx nA IIC T4 Gc Ta = -15°C to 70°C Class I, Zone 2 Ex nA IIC T4 Gc Ta = -15°C to +70°C Type 4X, IP67 ATEX FM14ATEX0060X: II 3 G Ex nA IIC T4 Gc Ta = -15°C to +70°C IP67 IEC – IECEx FMG 14.00028X: Ex nA IIC T4 Gc Ta = -15°C to + 70°C IP67

Intrinsically Safe US/Canada:FM16US0357X/FM16CA0168X Class I, II, III, Div 1, Group A, B, C, D, E, F, G, T4,Class I, Zone 0 AEx ia IIC T4 Ga Class I, Zone 0 Ex ia IIC T4 Ga Ta =-40°C to + 70°C Type 4X, IP67 ATEX – FM14ATEX0059X: II 1 G Ex ia IIC T4 Ga Ta = -40°C to +70°C IP67 IEC – IECEx FMG 14.0028X: Ex ia IIC T4 Ga Ta = -40°C to +70°C IP67

Dust Ignition Proof US/Canada:FM16US0357X/FM16CA0168X Class II, III, Division 1, Group E, F and G, T4 Ta = 5°C to +70°C Type 4X, IP67US/Canada Zone Ratings as follows:Zone 21, AEx tb IIIC T86C…T120C Ta= -15 C to +70 C Db (US)Zone 21, Ex tb IIIC T85C…T120C Ta = -15 C to +70 C Db (Canada)Type 4X, IP67ATEX – FM14ATEX0059X: II 2 D Ex tb IIIC T85°C … T120°C DbTa = -15°C to +70°C IP67 IEC – IECEx FMG 14.0028X: Ex tb IIIC T85°C … T120°C Ta = -15°C to +70°C IP67

The following approval standards are applicable: NEMA 250:2003, ANSI/IEC 60529:2004, C22.2 No. 94:2001, C22.2 No. 157:2012, C22.2 No. 213:2012, C22.2 No. 1010.1:2009, EN60079-0:2018, EN60079-1:2014, EN60079-11:2012, EN60079-26:2015, EN60079-15:2010, IEC60079-1:2014 IEC60079-11:2011, FM3600:2018, FM3610:2018, FM3611:2018, FM3615:2018, FM3616:2018, FM3810:2018, ANSI/ISA UL60079-0:2014, ANSI/ISA 60079-1:2009, ANSI/ISA 60079-11:2014, ANSI/ISA 60079-15:2013, ANSI/ISA 60079-26:2017, C22.2 No. 0.4:2017, C22.2 No. 0.5:2016, C22.2 No. 30:2016, CAN/CSA 60079-0:2015, CAN/CSA 60079-1:2016, CAN/CSA 60079-11:2014, CAN/CSA 60079-15:2016, C22.2 No. 60529:2016, EN 60079-0:2018, EN 60079-26:2015, EN 60079-31:2014, EN 60529:1991+A1:2000+A2:2013, IEC 60079-0:2017, IEC 60079-15:2017, IEC 60079-31:2013

Page 49: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter 49

JM4 Material Properties of Probe Partition Well

Material StandardMinimum Wall

Thickness inch (mm)

Tensile Strength Minimum (ksi)

Yield Strength Minimum (ksi)

Stainless Steel ASTM A276 .057 (1.46) 75 30

Hastelloy C-276 ASTM B574 .057 (1.46) 100 41

Monel 400 ASTM B164 .057 (1.46) 70 25

Temperature ranges are tabulated in section 2.6.2.

SPECIALCONDITIONSOFUSE:

1. The enclosure contains aluminum and is considered to present a potential risk of ignition by impact or friction. Care must be taken during installation and use to prevent impact or friction.

2. To maintain the T4 temperature code care shall be taken to ensure the enclosure temperature does not exceed +70 °C (+158 °F).

3. The risk of electrostatic discharge shall be minimized at installation, following the direction given in the instruction.

4. For installation with ambient temperature of +70 °C (+158 °F), refer to the manufacturer’s instructions for guidance on proper selection of conductors.

5. Provisions shall be made to provide transient overvoltage protection to a level not to exceed 119 Vdc.

6. WARNING – Explosion Hazard do not disconnect equipment when flammable or combustible atmosphere is present

7. When equipment is used in explosive dust atmospheres, the end user shall take precautions so that the thermal effects of the process temperature shall limit the equipment enclosure and probe surface temperatures to not exceed the required installation location temperature and shall be between T85 °C (185 °F) and T120 °C (248 °F).

8. For the Ex db rated Jupiter JM4, consult the manufacturer for dimensional information on the flameproof joints for repair.

9. All unused device openings must be closed using a suitably certified plug.

10. Temperature codes for the ratings Ex db IIB+H2, are defined by the following table:

Maximum Process Temperature

Temperature Class

From 0°C to 70°C T6

From 71°C to 90°C T5

From 91°C to 125°C T4

From 126°C to 190°C T3

From 191°C to 290°C T2

From 291°C to 440°C T1

NOTES:

1. For Explosion-proof installations the I.S. ground terminal shall be connected to appropriate intrinsically safe ground in accordance with the Canadian Electrical code (CEC) or the national electrical code (NEC). For intrinsically safe installations the I.S. ground terminal does not require grounding.

2. Manufacturer’s installation instructions supplied with the protective barrier and the CEC or the NEC must be followed when installing this equipment. Barrier must be certified for Canadian & U.S. installation.

3. Control equipment connected to protective barriers must not use or generate more than 250 VDC or VRMS.

4. Agency approved dust tight seals must be used when transmitter is installed in Class II & III environments.

5. For supply connections, use wire suitable for the operating temperature.

6. Agency approved barriers with linear output characteristics must be used.

Page 50: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

50 ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter

"SEE NOTE 2"

2

C

C

JUPITER JM4-51XX-XXX

+-

TB1

J1

CURRENT LOOP

2.5.1 AgencySpecifications–FM/CSAIntrinsicallySafeInstallation

Page 51: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter 51

:

FOR PROPER INSTALLATION REFERENCE ALL APPLICABLE NOTES FROM PAGE 2 - 99-5074-001Ui (Vmax) = 24V

Ii (Imax) = 280mAPi = 1.93W orAny approved termination on withR = 90 ... 100C = 0 ... 2.2µF

Any FM/CSA ApprovedIntrinsically SafeAssociated Apparatus withParameters suitable for theFISCO Concept.

CR

Any FM ApprovedIntrinsically SafeAssociated Apparatus with EntityParameters suitable for theFISCO Concept.

Ui (Vmax) = 17.5VIi (Imax) = 380 mAPi = 5.32 WCi = 440pF Li = 2.7µHLeakage current < 50µA

Ui (Vmax) = 17.5VIi (Imax) = 380 mAPi = 5.32 WCi = 440pF Li = 2.7µHLeakage current < 50µA

2.5.2 AgencySpecifications–FM/CSAIntrinsicallySafeFoundationfieldbusTMInstallation

Page 52: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

52 ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter

2.6 Specifications

2.6.1 Functional/Physical System Design Measurement Principle Magnetostriction-based mechanical response signalInput Measured Variable Level,responsesignaltimeofflight

Span 6inchesto400inches(15cmto999cm)

Output Type 4to20mAwithHART:3.8mAto20.5mAuseable(perNAMURNE43)

FoundationfieldbusTM:H1(ITKVer.6.1.1) Resolution Analog: 0.003 mADigitalDisplay: 1 mm Loop Resistance 591 ohms @ 24 VDC and 22 mA Diagnostic Alarm Selectable: 3.6 mA, 22 mA (meets requirements of NAMUR NE 43), or HOLD last output Damping Adjustable0-10secondsUserInterface Keypad 4-buttonmenu-drivendataentry

Display Graphicliquidcrystaldisplaywithviewableechocurve Digital Communication HART Version 7 —with Field Communicator, Foundationfieldbus™,

DTM (PACTware™),AMS,FDT,EDDL Menu Languages Transmitter LCD: English, French, German, Spanish, Russian, Portuguese

HART DD: English, French, German, Spanish, Russian, Chinese, PortugueseFoundationfieldbusTMHostSystem:English

Power (attransmitterterminals) HART:GeneralPurpose(Weatherproof)/IntrinsicallySafe/Explosion-proof:16 to 36 VDC11VDCminimumundercertainconditions(refertoSection2.6.5)Foundationfieldbus™: FISCO 9 to 17.5 VDCFISCO,FNICO,ExplosionProof,GeneralPurpose(WeatherProof):9to32VDC

Housing Material IP67/diecastaluminumA413(<0.6%copper);optional316stainlesssteel Net/Gross Weight Aluminum:4.5lbs.(2.0kg)

StainlessSteel:10.0lbs.(4.50kg) Overall Dimensions TransmitterHead:H8.34”(212mm)xW4.03”(102mm)xD7.56”(192mm) CableEntry 1⁄2”NPTorM20 SIL2Hardware(SafetyIntegrityLevel) SafeFailureFraction=93.1%forSingleFloatversion,

91.9%forDualFloatversion(HARTonly)(FullFMEDAreportavailableuponrequest)

Performance Linearity 0.030in.(.8mm)or0.01%ofprobelength,whicheverisgreater Accuracy ±0.01%fullscaleor±0.05in(1.3mm),whicheverisgreater Resolution .014”(.4mm) Repeatability ±0.005%offullspanor0.014in,whicheverisgreater Response Time 1 second Initialization Time Less than 10 seconds Ambient Temperature Effect Approx.±0.02%ofprobelength/degreeC Execution Time 15msec(30msecPID,SignalCharacterizerBlock) Calibration Points Upto5-pointcalibration(uponrequest)

Page 53: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter 53

2.6 Specifications(continued)

Foundation fieldbus™

ITK Version 6.1.1 H1 Device Class Link Master (LAS)—selectable ON/OFF  H1 Profile Class 31PS, 32L Function Blocks (6) Al, (2) Transducer, (1) Resource, (1) Arithmetic, (1) Input Selector,

(1) Signal Characterizer, (2) PID, (1) Integrator Quiescent Current 15 mA Execution Time 15 msec (30 msec PID, Signal Characterizer Block)Environment Ambient Temperature Range Transmitter: -40°F to +158°F (-40°C to +70°C)

Display: -5°F to +158°F (-20°C to +70°C) Storage Temperature -50°F to +185°F (-46°C to +85°C) Process Pressure (Direct Insertion) Vacuum to 3000 psig (207bar) Humidity 0 to 99%, non-condensing Electromagnetic Compatibility Meets CE requirement (EN 61326) and NAMUR NE 21 Surge Protection Meets CE EN 61326 (1000V)

Shock/Vibration ANSI/ISA-S71.03 Class SA1 (Shock); ANSI/ISA-S71.03 Class VC2 (Vibration)

Process Conditions Process Temperature External Mount: -320°F to +850°F (-196°C to +450°C) Direct Insertion: -320°F to +800°F (-196°C to +425°C) Process Pressure Direct Insertion: Vacuum to 3000 psig (207 bar)

2.6.2 Probe Selection Guide

JM4 Probe Temperature Range Pressure Range (Direct Insertion)Standard -50 to 450 °F (-46 to 232 °C) Vacuum to 3000 psig (207 bar)High Temperature -50 to 800 °F (-46 to 427 °C) Vacuum to 3000 psig (207 bar)Cryogenic -320 to 158 °F (-196 to 70 °C) Vacuum to 3000 psig (207 bar)

2.6.3 Probe Specifications Probe Diameter 0.625 inches (1.59 cm)

Process Connection3⁄4" NPT, 2" NPT, 1" BSP, 2" BSPANSI or DIN Flanges

Materials

Standard: 316 SS, nickel, Teflon®, brass, silicone

High Temperature: 316 SS, ceramic, brass, nickel, mica

Cryogenic: 316 SS, silicone, nickel, Teflon®, brass

Page 54: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

54 ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter

2.6.4 PhysicalSpecifications-Transmitter

inches [mm]

10.04255.1

45°

3.3986

4.18106.2

3.7795.9

3.96100.7

8.35212.1

5.09129.4

Transmitter Head

16.92429.7

20.92531.3

16.92429.7

DirectInsertion.75 NPT

DirectInsertion.75NPT,HighTemp&Cryo

DirectInsertion1" BSP

16.92429.7

DirectInsertion2" BSP

17.17436

DirectInsertion2" NPT

Page 55: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter 55

2.6.4 PhysicalSpecifications-Transmitter

inches [mm]

18.92480.5

22.92582.1

DirectInsertionFlange

DirectInsertionFlang,HighTemp&Cryo

16.42417

15.16385.1

20.23513.9

External Top Mount External Top MountOffset

External Top MountOffset,Cryo

20.42518.6

External Top MountHigh Temp & Cryo

7.84199.112.63

320.7

11.39289.417.06

433.4

External Bottom MountOffset

External Bottom MountOffset,Cryo

Page 56: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

56 ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter

2.6.5 Power Supply Requirements

2.6.5.1 Safe Operating Area

2.5.5.2 Terminal Voltage

Operational Mode Current Consumption Vmin Vmax

HART

General Purpose 4mA20mA

16.25V11V

36V36V

IntrinsicallySafe 4mA20mA

16.25V11V

28.6V28.6V

Explosion Proof 4mA20mA

16.25V11V

36V36V

Fixed Current-Solar Power Operation (PV transmitter via HART)General Purpose 10mA 1 11V 36V

IntrinsicallySafe 10mA 1 11V 28.6V

HART Multi-Drop Mode (Fixed Current)Standard 4mA 1 16.25V 36V

IntrinsicallySafe1 4mA 1 16.25V 28.6V

FOUNDATIONfieldbusSupply/TerminalVoltage 9V to 17.5V 9V to 17.5V 9V to 17.5V

1 Start-up current 12mA minimum.

0

Vsupply (Loop Supply Voltage)

Typical HART4-20 mA

Opera�ng AreaDigital Solar Mode

Safe Opera�ng Area

16.25 V

591 Ω

1136 Ω

360 Ω

24 V18.9 V 36 V

LoopR

Page 57: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter 57

J M 4 5

1 2 3 | BASIC MODEL NUMBERJM4 Jupiter 4th Generation Magnetostrictive Level Transmitter

4 | POWER5 24 VDC Two-Wire

5 | SIGNAL OUTPUT1 4-20 mA with HART®

2 Foundationfieldbus™ Communications

6 | SAFETY OPTIONS0 None requiredforFOUNDATIONfieldbus™

1 SIL 2 Hardware SEE NOTE 1

7 | ACCESSORIES/MOUNTING0 NoDigitalDisplayandKeypad-Integral1 NoDigitalDisplayandKeypad-Remote36"(0.91m) SEE NOTE 2

2 NoDigitalDisplayandKeypad-Remote144"(3.6m) SEE NOTE 2

A DigitalDisplayandKeypad-IntegralB DigitalDisplayandKeypad-Remote36"(0.91m) SEE NOTE 2

C DigitalDisplayandKeypad-Remote144"(3.6m) SEE NOTE 2

8 | AREA CLASSIFICATION0 GeneralPurpose,Weatherproof(IP67)1 IntrinsicallySafe/FISCO(cFMus)3 Explosion-Proof/FNICO(cFMus)A IntrinsicallySafe(ATEX&IEC)B Flame-Proof(ATEX&IEC)C Exn(ATEX&IEC)D DustEx(ATEX&IEC)

9 | HOUSING1 Aluminum, Dual-Component2 316 SS, Dual-Component

10 | CONDUIT CONNECTION0 1⁄2" NPT1 M202 1⁄2" NPT with Sunshade3 M20 with Sunshade

1 32 4 5 6 7 8 9 10

2.7 Model NumberTransmitter

1 3rdPartyFMEDAreportavailable2 Remote-mount transmitter not available

with XP / Flame Proof approvals

NOTES:

Page 58: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

58 ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter

21 32 4 5 6 7 8 9 10 11 12 13 14 15

1 | TECHNOLOGY2 Jupiter Magnetostrictive Probes - Model JM4

2 | MEASUREMENT SYSTEMA English Probe length to be provided in inches

C Metric Probe length to be provided in centimeters

3 | CONFIGURATIONE STANDARD Top Mount

suitable for process temperatures -40 to +500 °F

(-40 to +260 °C)F STANDARD Top Mount Offset

H STANDARD Bottom Mount Offset

K HIGH-TEMP Top Mountsuitable for process temperatures

+501 to +850 °F(+261 to +454 °C)

L HIGH-TEMP Top Mount Offset

M HIGH-TEMP Bottom Mount Offset

R CRYOGENIC Top Mountsuitable for process temperatures

-320 to +150 °F (-196 to +66 °C)

S CRYOGENIC Top Mount Offset

T CRYOGENIC Bottom Mount Offset

4 5 | MOUNTING SIDE

0 0 Left-side MLI Mount0 1 Right-side MLI Mount

6 | PROBE MATERIAL OF CONSTRUCTION

A Powder-Coated Aluminum Sensor Enclosure with 316 SS Probe SEE NOTE 1

1 316 SS Sensor Enclosure with 316 SS Probe

7 | PROBE OPTIONS AND HAZARDOUS LOCATION APPROVALS

Model NumberExternal Mount Probe

00 0

1AvailableonlywithDigit3,OptionsF,H,L,M

Standard Probe

F ATEX&IECFlameproofapprovalonly

N Allotherapprovals(XP,IS,NI)

Vibration Resistant Probe SEE NOTE 2

G ATEX&IECFlameproofapprovalonly

V Allotherapprovals(XP,IS,NI)2AvailableonlywithDigit3,OptionsF,H,L,M

Page 59: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter 59

21 32 4 5 6 7 8 9 10 11 12 13 14 15

8 | CHAMBER SIZE (FOR MOUNTING HARDWARE)

0 No mounting clamps required.

Select from these options if chamber DOES NOT contain high-temp insulation1 2" (or if digit 20 of MLI model code is 1, 2, or 7)2 21⁄2" (or if digit 20 of MLI model code is 3, 4, 5, or 6)3 3" (or if digit 20 of MLI model code is A, B, C, or D)4 4" (or if digit 20 of MLI model code is E, F, G, H, or J)5 3⁄4" (for Atlas Top Mount Configuration only)

Select from these options if chamber DOES contain high-temp insulationE 2" (or if digit 20 of MLI model code is 1, 2, or 7)F 21⁄2" (or if digit 20 of MLI model code is 3, 4, 5, or 6)G 3" (or if digit 20 of MLI model code is A, B, C, or D)H 4" (or if digit 20 of MLI model code is E, F, G, H, or J)J 3⁄4" (for Atlas Top Mount Configuration only)

00 0

Model Number ContinuedExternal Mount Probe

10 | LEVEL/INTERFACE MEASUREMENT PREFERENCE1 Measure Only the Total Liquid Level2 Measure Only the Interface Level3 Measure Both Total and Interface Level

13 14 15 | PROBE LENGTH – max. 400" (999 cm)

X X XExample: 87 inches = 087 Code 2 must be “A”

Example: 120 centimeters = 120 Code 2 must be “C”

Note: Maximum Probe Length = 400 inches (999 cm) (limited to 192 inches (487 cm) when digit 3 = K, L or M)

Page 60: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

60 ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter

21 32 4 5 6 7 8 9 10 11 12 13 14 15

1 | TECHNOLOGY2 Jupiter Magnetostrictive Probes - Model JM4

2 | MEASUREMENT SYSTEMA English Probe length to be provided in inches

C Metric Probe length to be provided in centimeters

3 | CONFIGURATION1 Standard | process temperatures between -40 to +500 °F (-40 to +260 °C)

2 High-Temperature SEE NOTE 1 | process temperatures between +501 to +800 °F (+261 to +425 °C)

8 Cryogenic |process temperatures between -320 to +150 °F (-196 to +66 °C)

4 & 5|PROCESSCONNECTIONSIZE&TYPEThreaded

11 3⁄4" NPT41 2" NPT

ASME Flanges43 2" 150# Raised Face44 2" 300# Raised Face45 2" 600# Raised Face47 2" 900/1500# Raised Face53 3" 150# Raised Face54 3" 300# Raised Face55 3" 600# Raised Face

EN 1092-1 FlangesCB DN40:PN16/25/40TypeACC DN40:PN63/100TypeB2DA DN 50 : PN 16 Type ADB DN 50 : PN 25/40 Type ADD DN 50 : PN 63 Type B2DE DN 50 : PN 100 Type B2EA DN 80 : PN 16 Type AEB DN 80 : PN 25/40 Type A

22 1" BSP42 2" BSP

56 3" 900# Raised Face57 3" 1500# Raised Face63 4" 150# Raised Face64 4" 300# Raised Face65 4" 600# Raised Face66 4" 900# Raised Face67 4" 1500# Raised Face

ED DN80:PN63TypeB2EE DN80:PN100TypeB2FA DN100:PN16TypeAFB DN 100 : PN 25/40 Type AFD DN 100 : PN 63 Type B2FE DN 100 : PN 100 Type B2FF DN 100 : PN 160 Type B2FG DN 100 : PN 250 Type B2

6 | MATERIAL OF CONSTRUCTION

A 316 SSB HastelloyC276C Monel 400L 316SSw/Teflon-ScoatingonprobetubingandfloatSEE NOTE 2

P 316SSw/PFAcoatingonprobetubingandfloatSEE NOTE 2

Model NumberDirect Insertion Probe

1Probelengthsupto192inches(488cm).Consultfactoryforlongerlengths.

2IDoffloattobeenlargedtoaccommodatecoating

Page 61: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter 61

2 1 32 4 5 6 7 8 9 10 11 12 13 14 15

7 | PROBE OPTIONS AND HAZARDOUS LOCATION APPROVALSF ATEX&IECFlameproofapprovalonly

N Allotherapprovals(XP,IS,NI)

8 | INSTALLATION CONSIDERATIONSN Direct Insertion unit mounted in vessel without stilling well

C Direct Insertion unit mounted in chamber, bridle, or stilling well SEE NOTE 3

11 12|MAGNETICFLOAT(S)Seenextpageforourstandarddirectinsertionfloatofferings.Ifalistedfloatdoesnotmeetyourapplicationrequirements,consultfactoryforacustomdesign.

13 14 15 |PROBELENGTH–max.400"(999cm)

X X XExample: 87 inches = 087 Code 2 must be “A”

Example: 120 centimeters = 120 Code 2 must be “C”

0 Industrial GradeK ASME B31.1L ASME B31.3M ASMEB31.3&NACEMR0103/MR0175N IndustrialGrade&NACEMR0103/MR0175

9 | CONSTRUCTION CODE

10 | LEVEL/INTERFACE MEASUREMENT PREFERENCE1 MeasureOnlytheTotalLiquidLevel2 MeasureOnlytheInterfaceLevel3 Measure Both Total and Interface Level

Model Number ContinuedDirect Insertion Probe

3 Refer to sizing chart for chambers and stilling wells on page 16 of bulletin ORI-150.

Page 62: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

62 ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter

Model Number ContinuedDirect Insertion Probe — Float Selection

Minimum Liquid Specific Gravity

316/316L SS Titanium Hastelloy® CHygienic Service

316/316L SSSF1: 20 µin (0.51 µm)

Hygienic Service316/316L SS

SF4: 15 µin (0.38 µm)

≥ 0.86AA

2.0" (51 mm) dia.BA

2.0" (51 mm) dia.CA

1.85" (47 mm) dia.DA

2.0" (51 mm) dia.FA

2.0" (51 mm) dia.

≥ 0.83AA

2.0" (51 mm) dia.BA

2.0" (51 mm) dia.CB

2.25" (57 mm) dia.DA

2.0" (51 mm) dia.FA

2.0" (51 mm) dia.

≥ 0.7AB

2.3" (58 mm) dia.BA

2.0" (51 mm) dia.CB

2.25" (57 mm) dia.DB

2.3" (58 mm) dia.FB

2.3" (58 mm) dia.

≥ 0.68AB

2.3" (58 mm) dia.BB

2.25" (57 mm) dia.99

consult factoryDB

2.3" (58 mm) dia.FB

2.3" (58 mm) dia.

≥ 0.64AC

2.5" (64 mm) dia.BB

2.25" (57 mm) dia.99

consult factoryDC

2.5" (64 mm) dia.FC

2.5" (64 mm) dia.

≥ 0.5299

consult factory dia.BB

2.25"(57 mm) dia.99

consult factory99

consult factory99

consult factory

< 0.5299

consult factory99

consult factory99

consult factory99

consult factory99

consult factory

Minimum Liquid Specific Gravities

upper / lower316/316L SS Titanium Hastelloy® C

Hygienic Service316/316L SS

SF1: 20 µin (0.51 µin)

Hygienic Service316/316L SS

SF4: 15 µin (0.38 µin)sinks thru floats on MA

2.0" (51 mm) dia.NA

2.0" (51 mm) dia.PA

1.85" (47 mm) dia.QA

2.0" (51 mm) dia.RA

2.0" (51 mm) dia.≤ 0.89 / ≥ 1.00sinks thru floats on MB

2.0" (51 mm) dia.NB

2.0" (51 mm) dia.PB

1.85" (47 mm) dia.QB

2.0" (51 mm) dia.RB

2.0" (51 mm) dia.≤ 1.00 / ≥ 1.12

Code Total Interface

11 AA

MA12 AB

13 AC

21 AA

MB22 AB

23 AC

31 BA NA

Code Total Interface

32 BB NA

41 BANB

42 BB

51 CAPA

52 CB

61 CAPB

62 CB

When utilizing two floats to measure total and interface liquid levels, reference the chart on the left to determine the appropriate float code to insert into the Jupiter model number.

If the desired combination is not shown, consult your local sales representative or Orion to inquire about a custom float deisgn.

DirectInsertionTotalLevelFloat(uppermostliquidlayer)

DirectInsertionInterfaceLevelFloat(lowerormiddleliquidlayer)

TwoFloatsforTotalLevelandInterfaceMeasurement

11 12|MAGNETICFLOAT(S)

Page 63: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter 63

(1)ElectronicModuleDigit 5 Replacement Part

1 031-2856-0012 031-2856-002

(2)DisplayModuleDigit 5 Digit 7 Replacement Part

1,20,1,2 ------------

A,B,C 031-2850-001

(3)WiringPCBoardDigit 5 Replacement Part

1 030-9165-001

2 030-9166-002

Replacement Part(4)“O”-ring 012-2201-237(5)“O”-ring 012-2201-237

(6)HousingCoverDigits

7 8 9 Replacement Part

0,1,20,1,3,

A,B,C,D1 004-9225-0022 004-9225-003

A,B,C0,1,A 1 036-4413-005

3 1 036-4413-0010,1,3,A 2 036-4413-002

A,B,C B,C,D1 036-4413-0082 036-4413-009

(7)HousingCoverDigit 9 Replacement Part

1 004-9225-0022 004-9225-003

2.8 Parts

2.8.1 Replacement Parts

TB1

Current Loop

J1

J M 4Part Number: 5

1

2

3

4

5

6

7

+-

Page 64: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

64 ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter

Glossary

Accuracy The maximum positive and negative % devia-tion from the actual value over the total span.

ANSI American National Standards Institute.

CSA Canadian Standards Association Canadian, third party agency that qualifies the safety of electrical equip-ment.

Damping The mathematical averaging of a meter and/or output signal to stabilize the effects of a noisy process due to surface turbulence.

Default Values The main position of the menu structure that displays the primary measurement values of LEVEL, % OUTPUT, and LOOP. The transmitter returns to this position after 5 minutes of inactivity.

DVM/DMM Digital Volt Meter/Digital Multimeter.

Electromagnetic Energy The radiation that travels through space as electric and magnetic fields varying with position and time. Examples in increasing frequency: radio waves, microwave, infrared light, visible light, ultraviolet light, x-rays, gamma waves, and cosmic waves.

EM See Electromagnetic Energy.

EMI Electromagnetic Interference Electrical noise caused by electromagnetic fields that may affect electrical circuits, particularly low-power electronic devices.

EN European Normal Committee guidelines in EC coun-tries that take precedence over local, country guidelines.

Ergonomic A mechanism that considers human capabili-ty in its design or function.

Explosion-Proof Enclosure An enclosure designed to withstand an explosion of gas or vapor within it and pre-vent the explosion from spreading outside the enclosure.

Fault A defect or failure in a circuit. The current (mA) value unit defaults to 3.6, 22, or Hold when a diagnostic condition occurs.

Feedthrough A small, connecting cavity between the main housing compartments, carrying the cable that supplies the operating energy to the measurement circuitry and returns the output value proportional to level. This cavity is potted to maintain the environmental isolation between the two compartments.

FM Factory Mutual American, third party agency that qualifies the safety of electrical equipment.

FSK Frequency Shift Keying.

Ground An electrical connection to the Earth’s potential that is used as a reference for the system and electrical safety.

Grounded A state where no electrical potential exists be-tween the ground (green) connection on the transmitter and the Earth or system ground.

HART Highway Addressable Remote Transducer. Protocol that uses the Bell 202 frequency shift keying (FSK) method to superimpose low level frequencies (1200/2000 Hz) on top of the standard 4–20 mA loop to provide digital communi-cation.

HART ID See Poll Address.

Hazardous Area An area where flammable gases or vapors are or may be present in the air in quantities sufficient to produce explosive or ignitable mixtures.

IEC International Electrotechnical Commission Organiza-tion that sets international standards for electrical devices.

Increased Safety Designs and procedures that minimize sparks, arcs, and excessive temperatures in hazardous areas. Defined by the IEC as Zone 1 environments (Ex e).

Interface: Electrical A boundary between two related, electronic circuits.

Interface: Process A boundary between two or more im-miscible liquids.

Intrinsic Safety A design or installation approach that limits the amount of energy that enters a hazardous area to eliminate the potential of creating an ignition source.

Level The present reading of the height of material in a vessel.

Linearity The worst case error calculated as a deviation from a perfect straight line drawn between two calibration points.

Loop The present reading of the 4–20 mA current output.

Low Voltage Directive A European Community require-ment for electrical safety and related issues of devices using 50-1000 VDC or 75-1500 VAC.

Magnetic Level Indicator A magnetically coupled, liq-uid level indicator which isolates the process in a sealed non-magnetic piping column. Contrasting colored flags provide indication of level.

Page 65: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter 65

Magnetostrictive Utilizing the Wiedemann effect to create a mechanical torsion or twist in a ferromagnetic wire which occurs as a result of the interaction between an elec-trical pulse on the wire and a magnetic field from the float.

Measured Value The typical level measurement values used to track the level of a process: Level, % Output, and Loop.

Media The liquid material being measured by the level transmitter.

Multidrop The ability to install, wire, or communicate with multiple devices over one cable. Each device is given a unique address and ID.

Nonhazardous Area An area where no volatile mixtures of vapors/gas and oxygen will be found at any time. Also called General Purpose Area.

Non-incendive Equipment And wiring which in its nor-mal operating condition is incapable of igniting a specific hazardous atmosphere or hazardous dust layer.

Offset The distance from the bottom of the tank to the bottom of the probe.

Password A numerical value up to 59999 protects stored configuration data from unauthorized manipulation.

Percent (%) Output The present reading as a fraction of the 16mA scale (4–20mA).

Poll Address A number between 1 and 15 which sets an address or location of a device in a multi-drop loop.

Probe A waveguide that propagates an electromagnetic pulse from the top of the tank into the process fluid.

Probe Length Exact measurement from the bottom of the process thread connection to the very bottom of the probe.

Range A value related to probe length (factory setting).

Repeatability The maximum error between two or more output readings of the same point.

RFI Radio Frequency Interference Electrical noise that can have an adverse affect on electrical circuits, particularly low-power devices.

Span The difference between the upper and lower limits of the range.

Specific Gravity (SG) The ratio of the density of a mate-rial to the density of water at the same conditions.

Tst Loop Test Loop Built-in system capability to test/calibrate a loop (or separate loop device) by driving the transmitter output to a particular value.

Trim 4/Trim 20 Built-in system capability to fine tune the 4 mA and 20 mA points so the transmitter output corresponds exactly to user’s meter, DCS input, etc.

Two Wire An electrical instrument design that uses one set of wires to provide both the supply power and process measurement signal. The process measurement is achieved by varying the current of the loop. Also called Loop Pow-ered.

Units The engineering units used to measure level in the system. The choices are in (inches) and cm (centimeters).

Page 66: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

66 ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter

ASSUREDQUALITY&SERVICECOSTLESS

Service Policy

Owners of Magnetrol/Orion Instruments controls may request the return of a or any part of an in-strument for complete rebuilding or replacement. They will be rebuilt or replaced promptly. Instru-ments returned under our service policy must be returned by prepaid transportation.

Magnetrol/Orion will repair or replace the control at no cost to the purchaser (or owner) other than transportation if:

1. Returned within the warranty period; and

2. The factory inspection finds the cause of the claim to be covered under the warranty.

If the trouble is the result of conditions beyond our control; or, is NOT covered by the warran-ty, there will be charges for labor and the parts required to rebuild or replace the equipment.

In some cases it may be expedient to ship replace-ment parts; or, in extreme cases a complete new instrument, to replace the original equipment before it is returned. If this is desired, notify the factory of both the model and serial numbers of the instrument to be replaced. In such cases, credit for the materials returned will be determined on the basis of the applicability of our warranty.

No claims for misapplication, labor, direct or con-sequential damage will be allowed.

Return Material Procedure

So that we may efficiently process any materials that are returned, it is essential that a “Return Ma-terial Authorization” (RMA) number be obtained from the factory, prior to the material’s return. This is available through Magnetrol/Orion’s local representative or by contacting the factory. Please supply the following information:

1. Company Name

2. Description of Material

3. Serial Number

4. Reason for Return

5. Application

Any unit that was used in a process must be prop-erly cleaned in accordance with OSHA standards, before it is returned to the factory.

A Material Safety Data Sheet (MSDS) must ac-company material that was used in any media.

All shipments returned to the factory must be by prepaid transportation.

All replacements will be shipped F.O.B. factory.

Contact Technical Support: Toll free 866-55-ORION or [email protected]

Page 67: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

ORI-650 Jupiter® Model JM4 Magnetostrictive Transmitter 67

JUPITER® MODEL JM4 | MAGNETOSTRICTIVE LEVEL TRANSMITTERSee Application Data Sheet ORI-345

for Direct Insertion Configuration

Notes

Page 68: Magnetostrictive Level Transmitter€¦ · Model JM4 Magnetostrictive Level Transmitter HART® Installation and Operating Manual Software v1.x. 2 ®ORI-650 Jupiter Model JM4 Magnetostrictive

2105 Oak Villa Boulevard • Baton Rouge, Louisiana 70815 • 225-906-2343 • orioninstruments.com

Copyright © 2019 Magnetrol Interna�onal, Incorporated

Magnetrol&MagnetrollogotypeandOrionInstruments&OrionlogotypeareregisteredtrademarksofMagnetrolInternational,Incorporated.HART® is a registered trademark of the HART Communication FoundationPACTware™ is trademark of PACTware ConsortiumCSAlogotypeisaregisteredtrademarkofCanadianStandardsAssociationViton® is a registered trademarks of DuPont Performance Elastomers.Hastelloy®isaregisteredtrademarkofHaynesInternational,Inc.Monel®isaregisteredtrademarkofSpecialMetalsCorporation(FormerlyIncoAlloysInternational) Tri-Clamp® is a registered trademark of Ladish Co.