M5 Hardware Quick Reference RS2 Technologies, LLC - 400 Fisher Street, Suite G - Munster, IN 46321 - (877) 682-3532 - Fax (219) 836-9102 www.rs2tech.com Revised: 12/2016

Upload: others

Post on 27-Dec-2019

5 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: M5 Hardware Quick Reference · 1. Set S1 - Configuration DIP Switch DIPs 1 & 2 ON 2. Set S1 - Configuration DIP Switch DIPs 3 & 4 OFF 3. Apply power to the M5-IC LEDs 1 & 2 and LEDs

M5 Hardware Quick Reference

RS2 Technologies, LLC - 400 Fisher Street, Suite G - Munster, IN 46321 - (877) 682-3532 - Fax (219) 836-9102www.rs2tech.com Revised: 12/2016

Page 2: M5 Hardware Quick Reference · 1. Set S1 - Configuration DIP Switch DIPs 1 & 2 ON 2. Set S1 - Configuration DIP Switch DIPs 3 & 4 OFF 3. Apply power to the M5-IC LEDs 1 & 2 and LEDs

M5-Enclosure 3

M5-Backplane 4

M5-IC 5

M5-COM 7

MODEL PAGE

© 2016 RS2 Technologies, LLC. - All rights reserved.

M5-8RP 13

M5-20IN 15

Table Of Contents

M5-2RP 9

M5-2SRP 11

M5-16DO 17

M5-16DOR 19

WIU-4 27

WIU-2 25

4033-BGN 26

M2000 Base 23

M5-MUX8 21

Page 3: M5 Hardware Quick Reference · 1. Set S1 - Configuration DIP Switch DIPs 1 & 2 ON 2. Set S1 - Configuration DIP Switch DIPs 3 & 4 OFF 3. Apply power to the M5-IC LEDs 1 & 2 and LEDs

TOC M5 Enclosure Quick Reference

RS2 Technologies, LLC - 400 Fisher Street, Suite G - Munster, IN 46321 - (877) 682-3532 - Fax (219) 836-9102www.rs2tech.com Revised: 10/2013

Page 4: M5 Hardware Quick Reference · 1. Set S1 - Configuration DIP Switch DIPs 1 & 2 ON 2. Set S1 - Configuration DIP Switch DIPs 3 & 4 OFF 3. Apply power to the M5-IC LEDs 1 & 2 and LEDs

TOC M5 Backplane Quick Reference

RS2 Technologies, LLC - 400 Fisher Street, Suite G - Munster, IN 46321 - (877) 682-3532 - Fax (219) 836-9102www.rs2tech.com

J2

J3

J4

J5

J6

J7

J1

Slo

t – J

7M

5-IC

/ M5-C

OM

Only

Slo

t – J

6D

o N

ot U

se

Slo

t – J

52R

P / 2

SR

P / 8

RP

20IN

/ 16D

O / 1

6D

OR

Slo

t – J

42R

P / 2

SR

P / 8

RP

20IN

/ 16D

O / 1

6D

OR

Slo

t – J

32R

P / 2

SR

P / 8

RP

20IN

/ 16D

O / 1

6D

OR

Slo

t – J

22R

P / 2

SR

P / 8

RP

20IN

/ 16D

O / 1

6D

OR

Slo

t – J

12R

P / 2

SR

P / 8

RP

20IN

/ 16D

O / 1

6D

OR

Revised: 10/2013

Page 5: M5 Hardware Quick Reference · 1. Set S1 - Configuration DIP Switch DIPs 1 & 2 ON 2. Set S1 - Configuration DIP Switch DIPs 3 & 4 OFF 3. Apply power to the M5-IC LEDs 1 & 2 and LEDs

TOC Detail

RS2 Technologies, LLC - 400 Fisher Street, Suite G - Munster, IN 46321 - (877) 682-3532 - Fax (219) 836-9102www.rs2tech.com

J6

J6 – M5 Backplane Connector

(Slot 7)

TB1TM

PR

PF

LT

GN

D

VIN

VIN

GN

D

GN

D

VIN TB2

Po

we

r Inp

ut 2

(12

Vd

c@

3A

Min

.)

Po

we

r Inp

ut 1

(12

Vd

c@

3A

Min

.)

Po

we

r Inp

ut 3

(12

Vd

c@

3A

Min

.)

TR

+

TR

-

GN

D

RS

-48

5 B

us

(2 w

ire O

NLY

! - Fig

ure

2)

REMOVE FOR

SERVICE

S2 - R

eset S

witc

h(E

xp

lana

tion

2)

S1 - C

on

figura

tion

Dip

Sw

itch

(Exp

lana

tion

1)

OFF

ON

S11234

S2234 16 5

J4

J7

Tam

per In

pu

t – (F

igu

re 1

)

Po

wer F

au

lt – (F

igu

re 1

)

Battery Bypass Sleeve(Explanation 3)

Memory Backup Battery(Explanation 3)

J1 –

Prim

ary

Eth

ern

et

Hos

t Ch

an

ne

l(E

xp

lana

tion

1)

Normal LED Function

LED 1 Off-Line / On-Line and Battery Status

Off-Line: 1 second cycle, 200 ms ON / 800 ms OFF

On-Line: flash cycle of 800 ms ON / 200 ms OFF

Double Flash: Battery Low

LED 2 Host Communicat ion Activity

LED 3 M5 Backplane Communication Activity

LED 4 RS-485 Bus Communication Activity

LED 5 Unassigned

LED 6 Unassigned

J1 –

Prim

ary

Eth

ern

et H

ost

(Exp

lana

tion

1)

Ye

llow

LE

D10

Mb/s

: OF

F10

0M

b/s

: ON

Gre

en L

ED

No L

ink: O

FF

Lin

k: ON

Eth

ern

et A

ctiv

ity: F

lash

ing

J7 - B

acku

p M

icro

-100

Eth

ern

et H

ost C

han

nel

Mechanical Specifications

Dimensions 3.5" (88.9mm) W x 10.25" (260.35mm) L

Temperature -55ºC to +85ºC, storage

0ºC to +70ºC, operat ing

Humidity 5% to 95% RHNC

M5-IC Quick Reference

J4 – Termination(Figure 2)

Revised: 10/2013

Page 6: M5 Hardware Quick Reference · 1. Set S1 - Configuration DIP Switch DIPs 1 & 2 ON 2. Set S1 - Configuration DIP Switch DIPs 3 & 4 OFF 3. Apply power to the M5-IC LEDs 1 & 2 and LEDs

OviewTOC

Explanation 3: Memory Backup Battery

If the M5-IC should experience a complete power loss, the 3 volt lithium memory backup battery provides power to the onboard memory which conta ins the card file, activity transactions and system configuration data. The M5-IC will reta in a ll database information during a power failure for up to 60 days. For optimum reliability, the memory backup battery should be replaced yearly using only a type BR2325, BR2330, or CR2330 lithium battery or equivalent.

NOTE: When setting up or servicing the M5-IC, it is recommended to leave the battery bypass sleeve in p lace until all system testing is completed. By keeping the battery bypass sleeve in between the battery and the '+' post, you can be certain that the memory is being completely flushed during power cycles. Upon completion, be certain to remove the battery bypass sleeve and store it within the enclosure for future use.

Figure 2: RS-485 Sub-Panel Bus Termination

The M5-IC has one 2 wire RS-485 sub-panel bus. The bus needs to be terminated at both the beginning and ending points.

J4 is the termination jumper for the RS-485 Sub-Panel Bus.

TB

2

TR+

TR-

GND

J4

Dra

in W

ire

Sh

ield

Pressing the S2 - Reset Switch will cause the M5-IC to reset.

This process will NOT erase the system configuration and cardholder databases.

Explanation 2: S2 - Reset Switch

Explanation 1: S1 – Configuration DIP Switch & Primary 10/100 Ethernet Host Channel

Bulk Erasing The System Configuration And Cardholder Databases

1. Set S1 - Configuration DIP Switch DIPs 1 & 2 ON

2. Set S1 - Configuration DIP Switch DIPs 3 & 4 OFF

3. Apply power to the M5-IC

LEDs 1 & 2 and LEDs 3 & 4 flash al ternate ly at a .5 second rate

4. With in 10 seconds, switch S1 - Configuration DIP Switch DIP 1 OFF

LED 2 flashes at a 2 second rate as memory is being erased

WARNING! DO NOT CYCLE POWERErasing memory takes approximately 60 seconds to complete.

LEDs 1 & 4 flash for 10 seconds after the memory has been erased, then the M5-IC reboots

5. The M5-IC is now ready to be configured as needed

Configuring Primary 10/100 Ethernet Host Channel

For DHCP Enabled Networks

1. Set all S1 - Configuration DIP Switch DIPs OFF

2. Apply power to the M5-IC

3. Make note of the MAC address located on the side of the RJ45 jack

4. Run Access It! Universal

5. Create a new Channel

Channel Enabled: X

Protocol Type: SCP

Channel Type: IP Server

6. Create a new SCP

General Tab

Model: M5-IC

Device Installed: X

SCP Time Zone: <Set accordingly>

Initialization String: <Leave blank>

Address: 0

SIO Port Speed

Port 1: 38400

Port 2: 38400

Comm Tab

Channel: <Set to the newly created channel>

TCP/IP Settings

IP Address: <MACxxxxxxxxxxxx>

If the MAC address from step 3 was 00-0F-E5-00-03-4B then the IP Address field must beentered as the Host Name of MAC000FE500034B.

Port Number: 3001

Encryption Settings: None

NOTE: If unable to resolve the Host Name to an IP Address, contact your loca l network administra tor.

Configuring Primary 10/100 Ethernet Host Channel

For A Stat ic IP Address

1. Set S1 - Configuration DIP Switch DIP 2 ON

2. Set S1 - Configuration DIP Switch DIPs 1, 3 & 4 OFF

3. Apply power to the M5-IC

4. Manually configure a computer to 192.168.0.100

5. Using a crossover cable, connect computer to M5-IC

6. Open a web browser and go to 192.168.0.251

7. Set S1 - Configuration DIP Switch DIP 1 ON

8. Click on Click Here to Login

9. Click on Continue to this website (not recommended).

10. Enter a Username of admin

11. Enter a Password of password

12. Click Network from the left hand menu

13. Select Use Static IP configuration:

IP Address: <Set accordingly>

Subnet Mask: <Set accordingly>

Default Gateway: <Set accordingly>

14. Click OK

15. Click Apply Setting from the left hand menu

16. Click Apply, Reboot button

17. Wait 60 seconds for M5-IC to reboot

18. Remove power from the M5-IC

19. Set all S1 - Configuration DIP Switch DIPs OFF

20. Remove crossover cable and connect to network

21. Apply power to the M5-IC

22. Run Access It! Universal

23. Create a new Channel

Channel Enabled: X

Protocol Type: SCP

Channel Type: IP Server

24. Create a new SCP

General Tab

Model: M5-IC

Device Installed: X

SCP Time Zone: <Set accordingly>

Initialization String: <Leave blank>

Address: 0

SIO Port Speed

Port 1: 38400

Port 2: 38400

Comm Tab

Channel: <Set to the newly created channel>

TCP/IP Settings

IP Address: <Set accordingly>

Port Number: 3001

Encryption Settings: None

Figure 1: Cabinet Tamper and Power Fault Wiring

TMPR

PFLT

GND

TB

1

© 2016 RS2 Technologies, LLC. - All rights reserved.M5-IC Details

Page 7: M5 Hardware Quick Reference · 1. Set S1 - Configuration DIP Switch DIPs 1 & 2 ON 2. Set S1 - Configuration DIP Switch DIPs 3 & 4 OFF 3. Apply power to the M5-IC LEDs 1 & 2 and LEDs

TOC Detail

RS2 Technologies, LLC - 400 Fisher Street, Suite G - Munster, IN 46321 - (877) 682-3532 - Fax (219) 836-9102www.rs2tech.com

M5-COM Quick Reference

Mechanical Specifications

Dimensions 3.5" (88.9mm) W x 10.25" (260.35mm) L

Temperature -55ºC to +85ºC, storage

0ºC to +70ºC, operat ing

Humidity 5% to 95% RHNC

J1

J1 – M5 Backplane Connector

(Slot 7)

TB1 TB2

GN

D

VIN

VIN

GN

D

GN

D

VIN

TR

+

TR

-

GN

D

No

t Co

nn

ec

ted

(Expla

natio

n 1

)

Po

wer In

put 3

(12

Vd

c@

3A

Min

. - Fig

ure

2)

Po

wer In

put 2

(12

Vd

c@

3A

Min

. - Fig

ure

2)

Po

wer In

put 1

(12

Vd

c@

3A

Min

. - Fig

ure

2)

RS

-485 B

us

(2 w

ire O

NLY

! - Fig

ure

1)

Revised: 10/2013

Page 8: M5 Hardware Quick Reference · 1. Set S1 - Configuration DIP Switch DIPs 1 & 2 ON 2. Set S1 - Configuration DIP Switch DIPs 3 & 4 OFF 3. Apply power to the M5-IC LEDs 1 & 2 and LEDs

OviewTOC

Explanation 1: Cabinet Tamper / Power Fault Wiring

The M5-IC board has two dedicated inputs for cabinet tamper (TMPR) and UPS fault monitoring (PFLT). The M5-COM board insta lled in downstream M5 enclosures does not have dedicated inputs.

There are several options to wire tamper and power fault switches in downstream M5 enclosure(s):

1. Tamper and power fault switches can be wired in series from the first M5 enclosure to downstream M5 enclosures. Wiring from the fi rst M5 enclosure to downstream M5 enclosure(s) should be in conduit and inaccessible.

With this option the user cannot determine which M5 enclosure is reporting the a larm.

2. Tamper and power fault switches can be wired to avai lable M5-20IN board inputs.

3. Tamper and power fault switches can be wired to avai lable reader port inputs.

The sensor inputs on the M5-20IN, M5-2RP, and M5-2SRP boards are configured as unsupervised, normal ly closed contacts. Refer to the specific I/O insta llation manual for wiring details.

Figure 2: Power Input Wiring

Power is passed through to the back plane to power the I/O modules of the M5 enclosure. A larger power supply may be required depending on the system configuration. Three pairs of power connections in parallel are available. If needed, the other two pair can supply power to o ther I/O boards.

TB

1

TMPR

PFLT

GND

VIN

VIN

GND

GND

VIN

– Ground (12Vdc return)

+ +12Vdc12Vdc

Power Supply

3A Min.

18AWG Min.

Figure 1: RS-485 Bus Termination

The M5-COM communicates to upstream and downstream M5 enclosures. TB2 is wired to TB2 of the M5-IC board and other downstream M5-COM boards. This interface allows multi-drop communication on a single bus up to 4,000 feet (1,200m). Use shielded twisted pair (min. 24AWG) cable with 120 ohm impedance.

When located at the end of the RS-485 bus, a separate 120 ohm resistor must be instal led across TR+ and TR- (see below).

Drain Wire

Shield

TB2

TR

+

TR

-

GN

D

120

End of Bus – 120 Ohm TerminationMiddle of Bus – No Termination

Drain Wire

Shield

TB2

TR

+

TR

-

GN

D

© 2016 RS2 Technologies, LLC. - All rights reserved.M5-COM Details

Page 9: M5 Hardware Quick Reference · 1. Set S1 - Configuration DIP Switch DIPs 1 & 2 ON 2. Set S1 - Configuration DIP Switch DIPs 3 & 4 OFF 3. Apply power to the M5-IC LEDs 1 & 2 and LEDs

TOC DetailM5-2RP Quick Reference

RS2 Technologies, LLC - 400 Fisher Street, Suite G - Munster, IN 46321 - (877) 682-3532 - Fax (219) 836-9102www.rs2tech.com

Mechanical Specifications

Dimensions 3.5" (88.9mm) W x 10.25" (260.35mm) L

Temperature -55ºC to +85ºC, storage

0ºC to +70ºC, operat ing

Humidity 5% to 95% RHNC

TB1TB2

J6

J6 – M5 Backplane Connector

(Slots 1-5)

TB3TB4

NCCNO

RLY 1

NCCNO

RLY 3

NCCNO

RLY 2

NCCNO

RLY 4

NCCNO

RLY 6

NCCNO

RLY 5

J5

+5

V

+12

V

RLY 4RLY 5RLY 6 RLY 1RLY 2RLY 3

12

34

57

68

OFF ONS1

S1 - Address Dip Switch (Table 1)

Start at address 0

Each SIO address in the bus must be unique

Set switches prior to powering up

1234

Normal LED Function

LED 1 Heartbeat / On-Line Status

Off-Line: 1 second cycle, 200 ms ON / 800 ms OFF

On-Line Non-encrypted: flash cycle of 800 ms ON / 200 ms OFF

On-Line Encrypted: 4 flash cycles in 700 ms ON / 300 ms OFF

Waiting firmware download: flash cycle of 100 ms ON / 100 ms OFF

LED 2 SIO Communication Port Status

LED 3 Reader Port 1 Act ivity

LED 4 Reader Port 2 Activity

J5 – Reader Voltage Selector+5V = 5Vdc@300mA per reader port

+12V = 12Vdc@300mA per reader port

Reader Port 1

Clock/Data, Wiegand, F/2F, and Supervised F/2F

DIS

P

LE

D

GN

D

VO

WD

1

DC

+

WD

0

RE

X+

DC

-N

U

RE

X-

CL

K D

0

DIS

P

LE

D

GN

D

VO

WD

1

DC

+

WD

0

RE

X+

DC

-N

U

RE

X-

CL

K D

0

Doo

r Strik

e 1

(2A

@30

Va

c/d

c –

Exp

. 3)

Aux

iliary

Ou

tput 2

(2A

@30

Va

c/d

c –

Exp

. 3)

Aux

iliary

Ou

tput 3

(2A

@30

Va

c/d

c –

Exp

. 3)

Doo

r Strik

e 2

(2A

@30

Va

c/d

c –

Exp

. 3)

Aux

iliary

Ou

tput 5

(2A

@30

Va

c/d

c –

Exp

. 3)

Aux

iliary

Ou

tput 6

(2A

@30

Va

c/d

c –

Exp

. 3)

Reader Port 2

Clock/Data, Wiegand, F/2F, and Supervised F/2FR

ead

er 1

(Exp

lana

tion

s 1

& 2

)

Read

er 2

(Exp

lana

tion

s 1

& 2

)

Revised: 5/2014

Page 10: M5 Hardware Quick Reference · 1. Set S1 - Configuration DIP Switch DIPs 1 & 2 ON 2. Set S1 - Configuration DIP Switch DIPs 3 & 4 OFF 3. Apply power to the M5-IC LEDs 1 & 2 and LEDs

OviewTOC

Explanation 2: Reader Input Wiring Configurations

Door contact and request to exit may be configured in one of four ways:

1. Unsupervised Wired to the M5-2RP (Figure 1)

2. Unsupervised Wired to the F/2F Reader (Figure 2)

3. Supervised Wired to the F/2F Reader (Figure 3)

4. Wired to a M/R-J Box, WIU-2, or 4033-BGN (Not pictured)DISP

LED

GND

VO

WD1

DC+

WD0

REX+

DC-NU

REX-CLK D0

Request to Exit Switch

Normally Open

Contact

Door Contact

Switch Normally

Closed Contact

Figure 1 Figure 2

Door Contact Switch

Normally Closed

Contact

Request to Exit Switch

Normally Open

Contact

Figure 3

1K, 1%

1K, 1%

Door Contact Switch

Normally Closed

Contact

1K, 1%

1K, 1%

Request to Exit Switch

Normally Open

Contact

Table 1: S1 - Address Dip Switch

Address 1 2 3 4 5 6 7 8

0 Off Off Off Off Off On On Off

1 On Off Off Off Off On On Off

2 Off On Off Off Off On On Off

3 On On Off Off Off On On Off

4 Off Off On Off Off On On Off

5 On Off On Off Off On On Off

6 Off On On Off Off On On Off

7 On On On Off Off On On Off

8 Off Off Off On Off On On Off

9 On Off Off On Off On On Off

10 Off On Off On Off On On Off

11 On On Off On Off On On Off

12 Off Off On On Off On On Off

13 On Off On On Off On On Off

14 Off On On On Off On On Off

15 On On On On Off On On Off

16 Off Off Off Off On On On Off

17 On Off Off Off On On On Off

18 Off On Off Off On On On Off

19 On On Off Off On On On Off

20 Off Off On Off On On On Off

21 On Off On Off On On On Off

22 Off On On Off On On On Off

23 On On On Off On On On Off

24 Off Off Off On On On On Off

25 On Off Off On On On On Off

26 Off On Off On On On On Off

27 On On Off On On On On Off

28 Off Off On On On On On Off

29 On Off On On On On On Off

30 Off On On On On On On Off

31 On On On On On On On Off

Explanation 1: Reader Wiring

Magnetic Stripe Reader

+5Vdc /+12Vdc

Ground

Door DO(Reader LED)

Data 1

DISP

LED

GND

VO

WD1

WD0

REX+

TB1 or TB3

Supervised F/2F Reader

+5Vdc /+12Vdc

Ground

Door DO(Reader LED)

Data 1

Display DO

ToDisplay DO

DISP

LED

GND

VO

WD1

WD0

REX+

TB1 or TB3

Wiegand or Unsupervised F/2F Reader

+5Vdc /+12Vdc

Ground

Door DO(Reader LED)

Data 1

DISP

LED

GND

VO

WD1

WD0

REX+

TB1 or TB3

Explanation 3: Output Wiring Configurations

Use one of the two methods of transient clamping below to protect relay contacts and reduce EMI emissions . Protect against accidental overloads by wiring in an inline fuse to the common side of the re lay.

DC Source – Suppression Diode SelectionDiode Current Rating > 1x Strike CurrentDiode Break Down Voltage: 4x Strike Voltage12Vdc or 24Vdc Str ike, Diode 1N4002 (100V / 1A) Typical

DC Source – External Relay

DC

External Relay

Fuse

Load

Suppression Diode

To Reader s Green LED InputBlocking Diode

1N5817 Or

Equivalent

Suppression Diode

DATA

LED

GND

12V

RE

AD

ER

DC Source – Internal Relay

NC

CN

ORL

Y 1

or 4

DC

Fuse

Load

Suppression Diode

AC Source – Suppression MOV Selection

Clamp Voltage > 1.5x Vac RMS24Vac Str ike, Panasonic ERZ-C07DK470 Typical

AC Source – External Relay

External Relay

Suppression MOV AC

DISP

LED

GND

VOFuse

Load

To Reader s Green LED InputBlocking Diode

1N5817 Or

Equivalent

Suppression Diode

AC Source – Internal Relay

NC

CN

ORL

Y 1

or 4

ACSuppression MOV

Fuse

Load

4033-BGNWIU-2

© 2016 RS2 Technologies, LLC. - All rights reserved.M5-2RP Details

Page 11: M5 Hardware Quick Reference · 1. Set S1 - Configuration DIP Switch DIPs 1 & 2 ON 2. Set S1 - Configuration DIP Switch DIPs 3 & 4 OFF 3. Apply power to the M5-IC LEDs 1 & 2 and LEDs

TOC DetailM5-2SRP Quick Reference

RS2 Technologies, LLC - 400 Fisher Street, Suite G - Munster, IN 46321 - (877) 682-3532 - Fax (219) 836-9102www.rs2tech.com

Mechanical Specifications

Dimensions 3.5" (88.9mm) W x 10.25" (260.35mm) L

Temperature -55ºC to +85ºC, storage

0ºC to +70ºC, operat ing

Humidity 5% to 95% RHNC

TB1TB2

J6

J6 – M5 Backplane Connector

(Slots 1-5)

TB3TB4

NCCNO

RLY 1

NCCNO

RLY 3

NCCNO

RLY 2

NCCNO

RLY 4

NCCNO

RLY 6

NCCNO

RLY 5

J5

+5

V

+12

V

RLY 4RLY 5RLY 6 RLY 1RLY 2RLY 3

12

34

57

68

OFF ONS1

S1 - Address Dip Switch (Table 1)

Start at address 0

Each SIO address in the bus must be unique

Set switches prior to powering up

1234

Normal LED Function

LED 1 Heartbeat / On-Line Status

Off-Line: 1 second cycle, 200 ms ON / 800 ms OFF

On-Line Non-encrypted: flash cycle of 800 ms ON / 200 ms OFF

On-Line Encrypted: 4 flash cycles in 700 ms ON / 300 ms OFF

Waiting firmware download: flash cycle of 100 ms ON / 100 ms OFF

LED 2 SIO Communication Port Status

LED 3 Reader Port 1 Act ivity

LED 4 Reader Port 2 Activity

J5 – Reader Voltage Selector+5V = 5Vdc@300mA per reader port

+12V = 12Vdc@300mA per reader port

Reader Port 1

Clock/Data, Wiegand, F/2F, and Supervised F/2F

DIS

P

LE

D

GN

D

VO

WD

1

DC

+

WD

0

RE

X+

DC

-N

U

RE

X-

CL

K D

0

DIS

P

LE

D

GN

D

VO

WD

1

DC

+

WD

0

RE

X+

DC

-N

U

RE

X-

CL

K D

0

Doo

r Strik

e 1

(2A

@30

Va

c/d

c –

Exp

. 3)

Aux

iliary

Ou

tput 2

(2A

@30

Va

c/d

c –

Exp

. 3)

Aux

iliary

Ou

tput 3

(2A

@30

Va

c/d

c –

Exp

. 3)

Doo

r Strik

e 2

(2A

@30

Va

c/d

c –

Exp

. 3)

Aux

iliary

Ou

tput 5

(2A

@30

Va

c/d

c –

Exp

. 3)

Aux

iliary

Ou

tput 6

(2A

@30

Va

c/d

c –

Exp

. 3)

Reader Port 2

Clock/Data, Wiegand, F/2F, and Supervised F/2FR

ead

er 1

(Exp

lana

tion

s 1

& 2

)

Read

er 2

(Exp

lana

tion

s 1

& 2

)

Revised: 5/2014

Page 12: M5 Hardware Quick Reference · 1. Set S1 - Configuration DIP Switch DIPs 1 & 2 ON 2. Set S1 - Configuration DIP Switch DIPs 3 & 4 OFF 3. Apply power to the M5-IC LEDs 1 & 2 and LEDs

Explanation 1: Reader Wiring

Magnetic Stripe Reader

+5Vdc /+12Vdc

Ground

Door DO(Reader LED)

Data 1

DISP

LED

GND

VO

WD1

WD0

REX+

TB1 or TB3

Supervised F/2F Reader

+5Vdc /+12Vdc

Ground

Door DO(Reader LED)

Data 1

Display DO

ToDisplay DO

DISP

LED

GND

VO

WD1

WD0

REX+

TB1 or TB3

Wiegand or Unsupervised F/2F Reader

+5Vdc /+12Vdc

Ground

Door DO(Reader LED)

Data 1

DISP

LED

GND

VO

WD1

WD0

REX+

TB1 or TB3Table 1: S1 - Address Dip Switch

Address 1 2 3 4 5 6 7 8

0 Off Off Off Off Off On On Off

1 On Off Off Off Off On On Off

2 Off On Off Off Off On On Off

3 On On Off Off Off On On Off

4 Off Off On Off Off On On Off

5 On Off On Off Off On On Off

6 Off On On Off Off On On Off

7 On On On Off Off On On Off

8 Off Off Off On Off On On Off

9 On Off Off On Off On On Off

10 Off On Off On Off On On Off

11 On On Off On Off On On Off

12 Off Off On On Off On On Off

13 On Off On On Off On On Off

14 Off On On On Off On On Off

15 On On On On Off On On Off

16 Off Off Off Off On On On Off

17 On Off Off Off On On On Off

18 Off On Off Off On On On Off

19 On On Off Off On On On Off

20 Off Off On Off On On On Off

21 On Off On Off On On On Off

22 Off On On Off On On On Off

23 On On On Off On On On Off

24 Off Off Off On On On On Off

25 On Off Off On On On On Off

26 Off On Off On On On On Off

27 On On Off On On On On Off

28 Off Off On On On On On Off

29 On Off On On On On On Off

30 Off On On On On On On Off

31 On On On On On On On Off

Explanation 2: Reader Input Wiring ConfigurationsDoor contact and request to exit may be configured in one of five ways:

1. Supervised 1K/1K EOL Wired to the M5-2SRP (Figure 1)

2. Supervised 6.8K/18K EOL Wired to the M5-2SRP (Figure 2)

3. Unsupervised Wired to the F/2F Reader (Figure 3)

4. Supervised Wired to the F/2F Reader (Figure 4)

5. Wired to a M/R-J Box, WIU-2, or 4033-BGN (Not pictured)

DISP

LED

GND

VO

WD1

DC+

WD0

REX+

DC-NU

REX-CLK D0

1K, 1%

1K, 1%

Door Contact

Switch Normally

Closed Contact

Request

to Exit Switch

Normally Open

Contact

1K, 1%

1K, 1%

Figure 1 Figure 2

DISP

LED

GND

VO

WD1

DC+

WD0

REX+

DC-NU

REX-CLK D0

Door Contact

Switch Normally

Closed Contact

Request

to Exit Switch

Normally Open

Contact

18K, 5%

6.8K, 5%

18K, 5%

6.8K, 5%Door Contact Switch

Normally Closed

Contact

Request to Exit Switch

Normally Open

Contact

Figure 3

1K, 1%

1K, 1%

Door Contact Switch

Normally Closed

Contact

1K, 1%

1K, 1%

Request to Exit Switch

Normally Open

Contact

Figure 4

Explanation 3: Output Wiring Configurations

Use one of the two methods of transient clamping below to protect relay contacts and reduce EMI emissions . Protect against accidental overloads by wiring in an inline fuse to the common side of the re lay.

AC Source – Internal Relay

NC

CN

ORL

Y 1

or 4

ACSuppression MOV

Fuse

Load

AC Source – Suppression MOV Selection

Clamp Voltage > 1.5x Vac RMS24Vac Str ike, Panasonic ERZ-C07DK470 Typical

AC Source – External Relay

External Relay

Suppression MOV AC

DISP

LED

GND

VOFuse

Load

To Reader s Green LED InputBlocking Diode

1N5817 Or

Equivalent

Suppression Diode

DC Source – Internal Relay

NC

CN

ORL

Y 1

or 4

DC

Fuse

Load

Suppression Diode

DC Source – Suppression Diode SelectionDiode Current Rating > 1x Strike CurrentDiode Break Down Voltage: 4x Strike Voltage12Vdc or 24Vdc Str ike, Diode 1N4002 (100V / 1A) Typical

DC Source – External Relay

DC

External Relay

Fuse

Load

Suppression Diode

To Reader s Green LED InputBlocking Diode

1N5817 Or

Equivalent

Suppression Diode

DATA

LED

GND

12V

RE

AD

ER

OviewTOC

4033-BGNWIU-2

© 2016 RS2 Technologies, LLC. - All rights reserved.M5-2SRP Details

Page 13: M5 Hardware Quick Reference · 1. Set S1 - Configuration DIP Switch DIPs 1 & 2 ON 2. Set S1 - Configuration DIP Switch DIPs 3 & 4 OFF 3. Apply power to the M5-IC LEDs 1 & 2 and LEDs

J3

1

3

2J3 - M5-8RP Power Selector

(Explanation 1)

TOC DetailM5-8RP Quick Reference

RS2 Technologies, LLC - 400 Fisher Street, Suite G - Munster, IN 46321 - (877) 682-3532 - Fax (219) 836-9102www.rs2tech.com

Mechanical Specifications

Dimensions 3.5" (88.9mm) W x 10.25" (260.35mm) L

Temperature -55ºC to +85ºC, storage

0ºC to +70ºC, operat ing

Humidity 5% to 95% RHNC

12

34

57

68

OFF ONS1

234 1

TB1TB2

J2

S1 - Address Dip Switch (Table 1)

Start at address 0

Each SIO address in the bus must be unique

Set switches prior to powering up

Normal LED Function

LED 1 Heartbeat / On-Line Status

Off-Line: 1 second cycle, 200 ms ON / 800 ms OFF

On-Line Non-encrypted: flash cycle of 800 ms ON / 200 ms OFF

On-Line Encrypted: 4 flash cycles in 700 ms ON / 300 ms OFF

Waiting firmware download: flash cycle of 100 ms ON / 100 ms OFF

LED 2 SIO Communication Port Status

LED 3 OFF – N/A

LED 4 OFF – N/A

J2 – M5 Backplane Connector

(Slots 1-5)

TB3TB4

READER 8

DA

TA

LE

D

GN

D

12

V

READER 7

DA

TA

LE

D

GN

D

12

V

READER 6

DA

TA

LE

D

GN

D

12

V

READER 5

DA

TA

LE

D

GN

D

12

V

READER 4D

ATA

LE

D

GN

D

12

V

READER 3

DA

TA

LE

D

GN

D

12

V

READER 1

DA

TA

LE

D

GN

D

12

V

READER 2

DA

TA

LE

D

GN

D

12

V

Read

er P

ort 1

- 12

Vo

lt F/2

F O

nly

(Exp

lana

tion

s 2

& 4

)

Read

er P

ort 2

- 12

Vo

lt F/2

F O

nly

(Exp

lana

tion

s 2

& 4

)

Read

er P

ort 3

- 12

Vo

lt F/2

F O

nly

(Exp

lana

tion

s 2

& 4

)

Read

er P

ort 4

- 12

Vo

lt F/2

F O

nly

(Exp

lana

tion

s 2

& 4

)

Read

er P

ort 8

- 12

Vo

lt F/2

F O

nly

(Exp

lana

tion

s 2

& 4

)

Read

er P

ort 7

- 12

Vo

lt F/2

F O

nly

(Exp

lana

tion

s 1

, 2, &

4)

Read

er P

ort 6

- 12

Vo

lt F/2

F O

nly

(Exp

lana

tion

s 2

& 4

)

Read

er P

ort 5

- 12

Vo

lt F/2

F O

nly

(Exp

lana

tion

s 2

& 4

)

Revised: 5/2014

Page 14: M5 Hardware Quick Reference · 1. Set S1 - Configuration DIP Switch DIPs 1 & 2 ON 2. Set S1 - Configuration DIP Switch DIPs 3 & 4 OFF 3. Apply power to the M5-IC LEDs 1 & 2 and LEDs

Table 1: S1 - Address Dip Switch

Address 1 2 3 4 5 6 7 8

0 Off Off Off Off Off On On Off

1 On Off Off Off Off On On Off

2 Off On Off Off Off On On Off

3 On On Off Off Off On On Off

4 Off Off On Off Off On On Off

5 On Off On Off Off On On Off

6 Off On On Off Off On On Off

7 On On On Off Off On On Off

8 Off Off Off On Off On On Off

9 On Off Off On Off On On Off

10 Off On Off On Off On On Off

11 On On Off On Off On On Off

12 Off Off On On Off On On Off

13 On Off On On Off On On Off

14 Off On On On Off On On Off

15 On On On On Off On On Off

16 Off Off Off Off On On On Off

17 On Off Off Off On On On Off

18 Off On Off Off On On On Off

19 On On Off Off On On On Off

20 Off Off On Off On On On Off

21 On Off On Off On On On Off

22 Off On On Off On On On Off

23 On On On Off On On On Off

24 Off Off Off On On On On Off

25 On Off Off On On On On Off

26 Off On Off On On On On Off

27 On On Off On On On On Off

28 Off Off On On On On On Off

29 On Off On On On On On Off

30 Off On On On On On On Off

31 On On On On On On On Off

Explanation 2: Reader Wiring

Supervised F/2F Reader

RE

AD

ER

DATA

LED

GND

12V+12Vdc

Ground

Door DO(Reader LED)

Data 1

Explanation 3: Reader Input Wiring Configurations

Door contact and request to exit may be configured in one of three ways:

1. Unsupervised Wired to the F/2F Reader (Figure 2)

2. Supervised Wired to the F/2F Reader (Figure 3)

3. Wired to a M/R-J Box, WIU-2, or 4033-BGN (Not pictured)

Figure 2

Door Contact Switch

Normally Closed

Contact

Request to Exit Switch

Normally Open

Contact

Figure 3

1K, 1%

1K, 1%

Door Contact Switch

Normally Closed

Contact

1K, 1%

1K, 1%

Request to Exit Switch

Normally Open

Contact

Explanation 1: J3 M5-8RP Power Selector & Reader Port 7

Two M5-8RP Installed Within The Same M5 Enclosure

J3 must be set to 2 & 3 (first board)

J3 must be set to 1 & 2 (second board)

Additional power is required (Figure 1)

The 12V output on reader port 7 of the second M5-8RP is not current limited

1

3

2

J3 (second board)J3 (fi rst board)

1

3

2

One M5-8RP Installed Within The M5 Enclosure

J3 must be set to 2 & 3

No additional power is required

J3

1

3

2

Figure 1

TB1VIN

VIN

GN

D

GN

D

VIN

M5-IC or M5-COM

TB4

READER 7

DA

TA

LE

D

GN

D

12

V

Second M5-8RP

Gro

un

d

+1

2V

dc

Gro

un

d

+1

2V

dc

Explanation 4: Output Wiring Configurations

Use one of the two methods of transient clamping below to protect relay contacts and reduce EMI emissions. Locate the protection ci rcui t as close to the load as possible (12 inches [30cm] recommended). The circuit s effectiveness decreases the further away it is.

Protect against accidental overloads by wiring in an inline fuse to the common side of the relay.

Important! The external relay's coil current must be restricted to 40mA. The 5 volt relay coil resistance must be 125 ohms. The 12 volt relay coil resistance must be 300 ohms.

Access It! Universal v4 and newer allows mapping a reader port to an output on a separate sub-panel which is connected to the same M5-IC.

DC Source – Suppression Diode SelectionDiode Current Rating > 1x Strike CurrentDiode Break Down Voltage: 4x Strike Voltage12Vdc or 24Vdc Str ike, Diode 1N4002 (100V / 1A) Typical

DC Source – External Relay

DC

External Relay

Fuse

Load

Suppression Diode

To Reader s Green LED InputBlocking Diode

1N5817 Or

Equivalent

Suppression Diode

DATA

LED

GND

12V

RE

AD

ER

AC Source – Suppression MOV Selection

Clamp Voltage > 1.5x Vac RMS24Vac Str ike, Panasonic ERZ-C07DK470 Typical

AC Source – External Relay

External Relay

Suppression MOV AC

Fuse

Load

To Reader s Green LED InputBlocking Diode

1N5817 Or

Equivalent

Suppression Diode

DATA

LED

GND

12V

RE

AD

ER

OviewTOC

4033-BGNWIU-2

© 2016 RS2 Technologies, LLC. - All rights reserved.M5-8RP Details

Page 15: M5 Hardware Quick Reference · 1. Set S1 - Configuration DIP Switch DIPs 1 & 2 ON 2. Set S1 - Configuration DIP Switch DIPs 3 & 4 OFF 3. Apply power to the M5-IC LEDs 1 & 2 and LEDs

12

34

57

68

TOC Detail

RS2 Technologies, LLC - 400 Fisher Street, Suite G - Munster, IN 46321 - (877) 682-3532 - Fax (219) 836-9102www.rs2tech.com

M5-20IN Quick Reference

Mechanical Specifications

Dimensions 3.5" (88.9mm) W x 10.25" (260.35mm) L

Temperature -55ºC to +85ºC, storage

0ºC to +70ºC, operat ing

Humidity 5% to 95% RHNC

ON OFFS1 J1

J1 – M5 Backplane Connector

(Slots 1-5)

IN16IN20 IN19 IN18 IN17 IN11IN15 IN14 IN13 IN12 IN6IN10 IN9 IN8 IN7 IN1IN5 IN4 IN3 IN2

B4 B3 B2 B1 A1A2A3A4

Processor ASIO Address is Defined by S1

Example: S1 is set to address 10

Processor A = Address 10

Processor BSIO Address is Defined by S1 + 1

Example: S1 is set to address 10

Processor B = Address 11

S1 - Address Dip Switch (Table 1)

Start at address 0

Each SIO address in the bus must be unique

Set switches prior to powering up

Normal LED Function

A1/B1 Heartbeat / On-Line Status

Off-Line: 1 second cycle, 200 ms ON / 800 ms OFF

On-Line Non-encrypted: flash cycle of 800 ms ON / 200 ms OFF

On-Line Encrypted: 4 flash cycles in 700 ms ON / 300 ms OFF

Waiting firmware download: flash cycle of 100 ms ON / 100 ms OFF

A2/B2 SIO Communication Port Status

A3/B3 OFF – N/A

A4/B4 OFF – N/A

Dig

ital A

ux

iliary

Inp

ut 1

(Mon

itore

d b

y P

rocesso

r A - F

igu

re 1

)

Dig

ital A

ux

iliary

Inp

ut 2

(Mon

itore

d b

y P

rocesso

r A - F

igu

re 1

)

Dig

ital A

ux

iliary

Inp

ut 3

(Mon

itore

d b

y P

rocesso

r A - F

igu

re 1

)

Dig

ital A

ux

iliary

Inp

ut 4

(Mon

itore

d b

y P

rocesso

r A - F

igu

re 1

)

Dig

ital A

uxilia

ry In

pu

t 5

(Mon

itore

d b

y P

rocesso

r A - F

igu

re 1

)

Dig

ital A

ux

iliary

Inp

ut 6

(Mon

itore

d b

y P

rocesso

r A - F

igu

re 1

)

Dig

ital A

ux

iliary

Inp

ut 7

(Mon

itore

d b

y P

rocesso

r A - F

igu

re 1

)

Dig

ital A

uxilia

ry In

pu

t 8

(Mon

itore

d b

y P

rocesso

r A - F

igu

re 1

)

Dig

ital A

ux

iliary

Inp

ut 9

(Mon

itore

d b

y P

rocesso

r A - F

igu

re 1

)

Dig

ital A

uxilia

ry In

pu

t 10

(Mon

itore

d b

y P

rocesso

r A - F

igu

re 1

)

Dig

ital A

uxilia

ry In

pu

t 1

(Mon

itore

d b

y P

rocesso

r B - F

igu

re 1

)

Dig

ital A

ux

iliary

Inp

ut 2

(Mon

itore

d b

y P

rocesso

r B - F

igu

re 1

)

Dig

ital A

ux

iliary

Inp

ut 3

(Mon

itore

d b

y P

rocesso

r B - F

igu

re 1

)

Dig

ital A

ux

iliary

Inp

ut 4

(Mon

itore

d b

y P

rocesso

r B - F

igu

re 1

)

Dig

ital A

ux

iliary

Inp

ut 5

(Mon

itore

d b

y P

rocesso

r B - F

igu

re 1

)

Dig

ital A

ux

iliary

Inp

ut 6

(Mon

itore

d b

y P

rocesso

r B - F

igu

re 1

)

Dig

ital A

ux

iliary

Inp

ut 7

(Mon

itore

d b

y P

rocesso

r B - F

igu

re 1

)

Dig

ital A

ux

iliary

Inp

ut 8

(Mon

itore

d b

y P

rocesso

r B - F

igu

re 1

)

Dig

ital A

ux

iliary

Inp

ut 9

(Mon

itore

d b

y P

rocesso

r B - F

igu

re 1

)

Dig

ital A

uxilia

ry In

pu

t 10

(Mon

itore

d b

y P

rocesso

r B - F

igu

re 1

)

Revised: 10/2013

Page 16: M5 Hardware Quick Reference · 1. Set S1 - Configuration DIP Switch DIPs 1 & 2 ON 2. Set S1 - Configuration DIP Switch DIPs 3 & 4 OFF 3. Apply power to the M5-IC LEDs 1 & 2 and LEDs

OviewTOC

Address 1 2 3 4 5 6 7 8

0 Off Off Off Off Off On On Off

1 On Off Off Off Off On On Off

2 Off On Off Off Off On On Off

3 On On Off Off Off On On Off

4 Off Off On Off Off On On Off

5 On Off On Off Off On On Off

6 Off On On Off Off On On Off

7 On On On Off Off On On Off

8 Off Off Off On Off On On Off

9 On Off Off On Off On On Off

10 Off On Off On Off On On Off

11 On On Off On Off On On Off

12 Off Off On On Off On On Off

13 On Off On On Off On On Off

14 Off On On On Off On On Off

15 On On On On Off On On Off

16 Off Off Off Off On On On Off

17 On Off Off Off On On On Off

18 Off On Off Off On On On Off

19 On On Off Off On On On Off

20 Off Off On Off On On On Off

21 On Off On Off On On On Off

22 Off On On Off On On On Off

23 On On On Off On On On Off

24 Off Off Off On On On On Off

25 On Off Off On On On On Off

26 Off On Off On On On On Off

27 On On Off On On On On Off

28 Off Off On On On On On Off

29 On Off On On On On On Off

30 Off On On On On On On Off

31 N/A – – – – – – – –

Table 1: S1 - Address Dip Switch

INx

INx

INx

INx

1K, 1%

1K, 1%Standard Supervised Circuit,

Normally Closed Contact

1K, 1%

1K, 1%Standard Supervised Circuit,

Normally Open Contact

Unsupervised Circuit,

Normally Closed Contact

Unsupervised Circuit,

Normally Open Contact

Figure 1: Input Wiring Configurations

© 2016 RS2 Technologies, LLC. - All rights reserved.M5-20IN Details

Page 17: M5 Hardware Quick Reference · 1. Set S1 - Configuration DIP Switch DIPs 1 & 2 ON 2. Set S1 - Configuration DIP Switch DIPs 3 & 4 OFF 3. Apply power to the M5-IC LEDs 1 & 2 and LEDs

RS2 Technologies, LLC - 400 Fisher Street, Suite G - Munster, IN 46321 - (877) 682-3532 - Fax (219) 836-9102www.rs2tech.com

Mechanical Specifications

Dimensions 3.5" (88.9mm) W x 10.25" (260.35mm) L

Temperature -55ºC to +85ºC, storage

0ºC to +70ºC, operat ing

Humidity 5% to 95% RHNC

D17

D16

D15

D18

12

34

57

68

OFF ONS1

234 1

TB

1

TB

2

J2

S1 - Address Dip Switch (Table 1)

Start at address 0

Each SIO address in the bus must be unique

Set switches prior to powering up

J2 – M5 Backplane Connector

(Slots 1-5)

+V

DC

DO1

-VD

C

+V

DC

DO2

-VD

C

+V

DC

DO4

-VD

C

+V

DC

DO5

-VD

C

+V

DC

DO8

-VD

C

+V

DC

DO6

-VD

C

+V

DC

D07

-VD

C

-VD

C

+V

DC

DO3

+V

DC

DO16

-VD

C

+V

DC

DO14

-VD

C

+V

DC

DO13

-VD

C

+V

DC

DO15

-VD

C

+V

DC

DO11

-VD

C

+V

DC

DO10

-VD

C

+V

DC

DO12

-VD

C

+V

DC

DO9

-VD

C

TB

3

TB

4

TB

5

D7

D9

D8

D10

D13

D12

D11

D14

D5

D20

D19

D6

TOC DetailM5-16DO Quick Reference

+V

DC

DC IN

GN

D

Normal LED Function

LED 1 Heartbeat / On-Line Status

Off-Line: 1 second cycle, 200 ms ON / 800 ms OFF

On-Line Non-encrypted: flash cycle of 800 ms ON / 200 ms OFF

On-Line Encrypted: 4 flash cycles in 700 ms ON / 300 ms OFF

Waiting firmware download: flash cycle of 100 ms ON / 100 ms OFF

LED 2 SIO Communication Port Status

LED 3 OFF – N/A

LED 4 OFF – N/A

LED 5-20 (Table 2)

Dig

ital A

uxilia

ry O

utp

ut 1

(40

mA

@+

5 to

24

Vd

c –

Exp

. 2)

Dig

ital A

uxilia

ry O

utp

ut 2

(40

mA

@+

5 to

24

Vd

c –

Exp

. 2)

Dig

ital A

uxilia

ry O

utp

ut 3

(40

mA

@+

5 to

24

Vd

c –

Exp

. 2)

Dig

ital A

uxilia

ry O

utp

ut 4

(40

mA

@+

5 to

24

Vd

c –

Exp

. 2)

Dig

ital A

uxilia

ry O

utp

ut 5

(40

mA

@+

5 to

24

Vd

c –

Exp

. 2)

Dig

ital A

uxilia

ry O

utp

ut 6

(40

mA

@+

5 to

24

Vd

c –

Exp

. 2)

Dig

ital A

uxilia

ry O

utp

ut 7

(40

mA

@+

5 to

24

Vd

c –

Exp

. 2)

Dig

ital A

uxilia

ry O

utp

ut 8

(40

mA

@+

5 to

24

Vd

c –

Exp

. 2)

Dig

ital A

uxilia

ry O

utp

ut 9

(40

mA

@+

5 to

24

Vd

c –

Exp

. 2)

Dig

ital A

uxilia

ry O

utp

ut 1

0

(40

mA

@+

5 to

24

Vd

c –

Exp

. 2)

Dig

ital A

uxilia

ry O

utp

ut 1

1

(40

mA

@+

5 to

24

Vd

c –

Exp

. 2)

Dig

ital A

uxilia

ry O

utp

ut 1

2

(40

mA

@+

5 to

24

Vd

c –

Exp

. 2)

Dig

ital A

uxilia

ry O

utp

ut 1

3

(40

mA

@+

5 to

24

Vd

c –

Exp

. 2)

Dig

ital A

uxilia

ry O

utp

ut 1

4

(40

mA

@+

5 to

24

Vd

c –

Exp

. 2)

Dig

ital A

uxilia

ry O

utp

ut 1

5

(40

mA

@+

5 to

24

Vd

c –

Exp

. 2)

Dig

ital A

uxilia

ry O

utp

ut 1

6

(40

mA

@+

5 to

24

Vd

c –

Exp

. 2)

Exte

rnal P

ow

er S

ou

rce

(24

Vd

c M

ax. - E

xp

. 1)

Revised: 10/2013

Page 18: M5 Hardware Quick Reference · 1. Set S1 - Configuration DIP Switch DIPs 1 & 2 ON 2. Set S1 - Configuration DIP Switch DIPs 3 & 4 OFF 3. Apply power to the M5-IC LEDs 1 & 2 and LEDs

OviewTOC

Table 2: Output Status LEDs

On = Energized

Output Number Associated LED

1 D72 D83 D94 D105 D116 D127 D138 D149 D15

10 D1611 D1712 D1813 D1914 D2015 D516 D6

Table 1: S1 - Address Dip Switch

Address 1 2 3 4 5 6 7 8

0 Off Off Off Off Off On On Off

1 On Off Off Off Off On On Off

2 Off On Off Off Off On On Off

3 On On Off Off Off On On Off

4 Off Off On Off Off On On Off

5 On Off On Off Off On On Off

6 Off On On Off Off On On Off

7 On On On Off Off On On Off

8 Off Off Off On Off On On Off

9 On Off Off On Off On On Off

10 Off On Off On Off On On Off

11 On On Off On Off On On Off

12 Off Off On On Off On On Off

13 On Off On On Off On On Off

14 Off On On On Off On On Off

15 On On On On Off On On Off

16 Off Off Off Off On On On Off

17 On Off Off Off On On On Off

18 Off On Off Off On On On Off

19 On On Off Off On On On Off

20 Off Off On Off On On On Off

21 On Off On Off On On On Off

22 Off On On Off On On On Off

23 On On On Off On On On Off

24 Off Off Off On On On On Off

25 On Off Off On On On On Off

26 Off On Off On On On On Off

27 On On Off On On On On Off

28 Off Off On On On On On Off

29 On Off On On On On On Off

30 Off On On On On On On Off

31 On On On On On On On Off

Explanation 1: External Power Source

Digital Output

Power Source

+5 to 24VdcFuse

TB5

+VDC

DC

IN

GND

Explanation 2: Output Wiring

Protect relay contacts and reduce EMI emissions by using a contact protection circuit as close to the load as possib le (12 inches [30cm] recommended). The circuit s effectiveness decreases the further away it is.

Protect against accidental overloads by wiring in an inline fuse to the common side of the re lay.

Important! The external relay's coil current must be restricted to 40mA. The 5 volt relay coil resistance must be 125 ohms. The 12 volt relay coil resistance must be 300 ohms. The 24 volt relay coil resistance must be 600 ohms.

Suppression Diode SelectionDiode Current Rating > 1x Strike CurrentDiode Break Down Voltage: 4x Strike Voltage12Vdc or 24Vdc Str ike, Diode 1N4002 (100V / 1A) Typical

+VDC

DO

x

-VDC

External RelayDC

Suppression Diode

Fuse

Suppression Diode

+5 to 24Vdc

40mA Max.

© 2016 RS2 Technologies, LLC. - All rights reserved.M5-16DO Details

Page 19: M5 Hardware Quick Reference · 1. Set S1 - Configuration DIP Switch DIPs 1 & 2 ON 2. Set S1 - Configuration DIP Switch DIPs 3 & 4 OFF 3. Apply power to the M5-IC LEDs 1 & 2 and LEDs

M5-16DOR Quick Reference

RS2 Technologies, LLC - 400 Fisher Street, Suite G - Munster, IN 46321 - (877) 682-3532 - Fax (219) 836-9102www.rs2tech.com

TOC Detail

Mechanical Specifications

Dimensions 3.5" (88.9mm) W x 10.25" (260.35mm) L

Temperature -55ºC to +85ºC, storage

0ºC to +70ºC, operat ing

Humidity 5% to 95% RHNC

12

34

57

68

OFF ONS1

234 1 TB1TB2TB3TB4

NO C

RLY 12 RLY 11

CNO NCCNO

RLY 10

NCCNO

RLY 9

NO C

RLY 8 RLY 7

CNO NCCNO

RLY 6

NCCNO

RLY 5

NO C

RLY 4 RLY 3

CNO NCCNO

RLY 2

NCCNO

RLY 1

J3

RLY 8 RLY 7 RLY 6 RLY 5 RLY 4 RLY 3 RLY 2 RLY 1RLY 9RLY 10RLY 11RLY 16 RLY 15 RLY 14 RLY 13 RLY 12

S1 - Address Dip Switch (Table 1)

Start at address 0

Each SIO address in the bus must be unique

Set switches prior to powering up

Normal LED Function

LED 1 Heartbeat / On-Line Status

Off-Line: 1 second cycle, 200 ms ON / 800 ms OFF

On-Line Non-encrypted: flash cycle of 800 ms ON / 200 ms OFF

On-Line Encrypted: 4 flash cycles in 700 ms ON / 300 ms OFF

Waiting firmware download: flash cycle of 100 ms ON / 100 ms OFF

LED 2 SIO Communication Port Status

LED 3 OFF – N/A

LED 4 OFF – N/A

NO C

RLY 16 RLY 15

CNO NCCNO

RLY 14

NCCNO

RLY 13

J3 – M5 Backplane Connector

(Slots 1-5)

Aux

iliary

Ou

tput 1

- Form

C

(2A

@30

Va

c/d

c re

sis

tive - E

xp

. 1)

Aux

iliary

Ou

tput 2

- Form

C

(2A

@30

Va

c/d

c re

sis

tive - E

xp

. 1)

Aux

iliary

Ou

tput 3

- Form

A

(2A

@30

Va

c/d

c re

sis

tive - E

xp

. 2)

Aux

iliary

Ou

tput 4

- Form

A

(2A

@30

Va

c/d

c re

sis

tive - E

xp

. 2)

Aux

iliary

Ou

tput 5

- Form

C

(2A

@30

Va

c/d

c re

sis

tive - E

xp

. 1)

Aux

iliary

Ou

tput 6

- Form

C

(2A

@30

Va

c/d

c re

sis

tive - E

xp

. 1)

Aux

iliary

Ou

tput 7

- Form

A

(2A

@30

Va

c/d

c re

sis

tive - E

xp

. 2)

Aux

iliary

Ou

tput 8

- Form

A

(2A

@30

Va

c/d

c re

sis

tive - E

xp

. 2)

Aux

iliary

Ou

tput 1

2 - F

orm

A

(2A

@30

Va

c/d

c re

sis

tive - E

xp

. 2)

Aux

iliary

Ou

tput 1

1 - F

orm

A

(2A

@30

Va

c/d

c re

sis

tive - E

xp

. 2)

Aux

iliary

Ou

tput 1

0 - F

orm

C

(2A

@30

Va

c/d

c re

sis

tive - E

xp

. 1)

Aux

iliary

Ou

tput 9

- Form

C

(2A

@30

Va

c/d

c re

sis

tive - E

xp

. 1)

Aux

iliary

Ou

tput 1

3 - F

orm

C

(2A

@30

Va

c/d

c re

sis

tive - E

xp

. 1)

Aux

iliary

Ou

tput 1

4 - F

orm

C

(2A

@30

Va

c/d

c re

sis

tive - E

xp

. 1)

Aux

iliary

Ou

tput 1

5 - F

orm

A

(2A

@30

Va

c/d

c re

sis

tive - E

xp

. 2)

Aux

iliary

Ou

tput 1

6 - F

orm

A

(2A

@30

Va

c/d

c re

sis

tive - E

xp

. 2)

Revised: 5/2014

Page 20: M5 Hardware Quick Reference · 1. Set S1 - Configuration DIP Switch DIPs 1 & 2 ON 2. Set S1 - Configuration DIP Switch DIPs 3 & 4 OFF 3. Apply power to the M5-IC LEDs 1 & 2 and LEDs

OviewTOC

Table 1: S1 - Address Dip Switch

Address 1 2 3 4 5 6 7 8

0 Off Off Off Off Off On On Off

1 On Off Off Off Off On On Off

2 Off On Off Off Off On On Off

3 On On Off Off Off On On Off

4 Off Off On Off Off On On Off

5 On Off On Off Off On On Off

6 Off On On Off Off On On Off

7 On On On Off Off On On Off

8 Off Off Off On Off On On Off

9 On Off Off On Off On On Off

10 Off On Off On Off On On Off

11 On On Off On Off On On Off

12 Off Off On On Off On On Off

13 On Off On On Off On On Off

14 Off On On On Off On On Off

15 On On On On Off On On Off

16 Off Off Off Off On On On Off

17 On Off Off Off On On On Off

18 Off On Off Off On On On Off

19 On On Off Off On On On Off

20 Off Off On Off On On On Off

21 On Off On Off On On On Off

22 Off On On Off On On On Off

23 On On On Off On On On Off

24 Off Off Off On On On On Off

25 On Off Off On On On On Off

26 Off On Off On On On On Off

27 On On Off On On On On Off

28 Off Off On On On On On Off

29 On Off On On On On On Off

30 Off On On On On On On Off

31 On On On On On On On Off

Explanation 1: Form C Output Wiring Configurations

When controlling power to the door strike, the Normally Open and Common poles are used. When momentarily removing power to unlock the door, as with a mag lock, the Normally Closed and Common poles are used.

Use one of the two methods of transient clamping below to protect relay contacts and reduce EMI emissions . Locate the protection ci rcui t as close to the load as possible (12 inches [30cm] recommended). The circuit s effectiveness decreases the further away i t is.

Protect against accidental overloads by wiring in an inline fuse to the common side of the re lay.

AC Source – Suppression MOV Selection

Clamp Voltage > 1.5x Vac RMS24Vac Str ike, Panasonic ERZ-C07DK470 Typical

AC Source – Internal Relay

ACSuppression MOV

Fuse

Load

NC

CN

O

RL

Y

DC Source – Suppression Diode SelectionDiode Current Rating > 1x Strike CurrentDiode Break Down Voltage: 4x Strike Voltage12Vdc or 24Vdc Str ike, Diode 1N4002 (100V / 1A) Typical

DC Source – Internal Relay

DC

Fuse

Load

Suppression Diode

NC

CN

O

RL

Y

Explanation 2: Form A Output Wiring Configurations

When controlling power to the door strike, the Normally Open and Common poles are used. When momentarily removing power to unlock the door, as with a mag lock, the Normally Closed and Common poles are used. If the re lay does not have a Normally Closed pole, the relay must be configured by the host to be energized when in the locked state. Check with local building codes for proper egress door installation.

Use one of the two methods of transient clamping below to protect relay contacts and reduce EMI emissions . Locate the protection ci rcui t as close to the load as possible (12 inches [30cm] recommended). The circuit s effectiveness decreases the further away i t is.

Protect against accidental overloads by wiring in an inline fuse to the common side of the re lay.

DC Source – Suppression Diode SelectionDiode Current Rating > 1x Strike CurrentDiode Break Down Voltage: 4x Strike Voltage12Vdc or 24Vdc Str ike, Diode 1N4002 (100V / 1A) Typical

DC Source – Internal Relay

DC

Fuse

Load

Suppression Diode

CN

ORL

Y

AC Source – Suppression MOV Selection

Clamp Voltage > 1.5x Vac RMS24Vac Str ike, Panasonic ERZ-C07DK470 Typical

AC Source – Internal Relay

AC

Suppression MOV

Fuse

Load

CN

ORL

Y

© 2016 RS2 Technologies, LLC. - All rights reserved.M5-16DOR Details

Page 21: M5 Hardware Quick Reference · 1. Set S1 - Configuration DIP Switch DIPs 1 & 2 ON 2. Set S1 - Configuration DIP Switch DIPs 3 & 4 OFF 3. Apply power to the M5-IC LEDs 1 & 2 and LEDs

Normal LED Function

LED A Heartbeat

LED H M5 Back plane communication

LED 1-8 SIO Communication (Rapid pulse)

TOC DetailM5-MUX8 Quick Reference

RS2 Technologies, LLC - 400 Fisher Street, Suite G - Munster, IN 46321 - (877) 682-3532 - Fax (219) 836-9102www.rs2tech.com

Mechanical Specifications

Dimensions 3.5" (88.9mm) W x 10.25" (260.35mm) L

Temperature -55ºC to +85ºC, storage

0ºC to +50ºC, operat ing

Humidity 5% to 95% RHNC

4321

ON

OF

F

S1

234 1

TB1TB2

J2

S1 - Dip Switch(Table 1)

Default = OFF, ON, ON, OFF

J2 – M5 Backplane Connector

(Slots 1-5)

TB3TB4

READER 8

TR

+

TR

-

GN

D

12

V

READER 7

TR

+

TR

-

GN

D

12

V

READER 6

TR

+

TR

-

GN

D

12

V

READER 5

TR

+

TR

-

GN

D

12

V

READER 4T

R+

TR

-

GN

D

12

V

READER 3

TR

+

TR

-

GN

D

12

V

READER 1

TR

+

TR

-

GN

D

12

V

READER 2

TR

+

TR

-

GN

D

12

V

Revised: 12/2016

678 5 AH

J3

1

3

2J3 - M5-MUX8 Power Selector

(Explanation 1)

Read

er P

ort 8

(Exp

lana

tion

2)

10

.4 - 1

2.9

Vdc

, 300

mA

ma

x/p

ort

Read

er P

ort 7

(Exp

lana

tion

2)

10

.4 - 1

2.9

Vdc

, 300

mA

ma

x/p

ort

Read

er P

ort 6

(Exp

lana

tion

2)

10

.4 - 1

2.9

Vdc

, 300

mA

ma

x/p

ort

Read

er P

ort 5

(Exp

lana

tion

2)

10

.4 - 1

2.9

Vdc

, 300

mA

ma

x/p

ort

Read

er P

ort 4

(Exp

lana

tion

2)

10

.4 - 1

2.9

Vdc

, 300

mA

ma

x/p

ort

Read

er P

ort 3

(Exp

lana

tion

2)

10

.4 - 1

2.9

Vdc

, 300

mA

ma

x/p

ort

Read

er P

ort 2

(Exp

lana

tion

2)

10

.4 - 1

2.9

Vdc

, 300

mA

ma

x/p

ort

Read

er P

ort 1

(Exp

lana

tion

2)

10

.4 - 1

2.9

Vdc

, 300

mA

ma

x/p

ort

Page 22: M5 Hardware Quick Reference · 1. Set S1 - Configuration DIP Switch DIPs 1 & 2 ON 2. Set S1 - Configuration DIP Switch DIPs 3 & 4 OFF 3. Apply power to the M5-IC LEDs 1 & 2 and LEDs

OviewTOC

© 2016 RS2 Technologies, LLC. - All rights reserved.

Explanation 1: J3 M5-MUX8 Power Selector & Reader Port 7

One M5-MUX8 Installed Within The M5 Enclosure

J3 must be set to 2 & 3

No additional power is required

J3

1

3

2

Two M5-MUX8 Installed Within The Same M5 Enclosure

J3 must be set to 2 & 3 (first board)

J3 must be set to 1 & 2 (second board)

Additional power is required (Figure 1)

The 12V output on reader port 7 of the second M5-MUX8 is not current limi ted

1

3

2

J3 (second board)J3 (fi rst board)

1

3

2

Figure 1

TB1VIN

VIN

GN

D

GN

D

VIN

M5-IC or M5-COMG

rou

nd

+1

2V

dc

Gro

un

d

+1

2V

dc

TB4

READER 7

DA

TA

LE

D

GN

D

12

V

Second M5-MUX8

Table 1: S1 - Dip Switch

S1-1

OFF

ON

OFF

ON

S1-2

OFF

OFF

ON

ON

S1-3

ON

ON

ON

ON

Baud Rate

9,600

19,200

38,400

38,400

S1-4

OFF

OFF

OFF

OFF

Explanation 2: Wiring

J4 - Termination(Figure 5)

J3

J2

Re

lay

1

Re

lay

2

TB

1

TB

2

TB

3

TB

4

J4

GN

D

BZ

R

LE

D

CL

K/D

1

DA

T/D

0

VO

TR

+

TR

-

GN

D

K2

NC

NO

C

K1

NC

NO

C VIN

GN

D

I2 I2 I1 I1

AB

Retrofit InstallationsThe existing 4-conductor F/2F reader cabling must be evaluated for RS-485 use. Communication baud rate may have to be reduced if errors occur.

New InstallationsUse a single, shielded twisted pair cable rated for RS-485 serial communication.

RE

AD

ER

TR+

TR-

GND

12V

12V GND

TR-TR+

MR-50Wire the M5-MUX8 reader port to the MR50 as shown. Refer to the MR-50 Quick Reference sheet for more information on reader, input and door strike relay wi ring.

M5-MUX8 Details

Page 23: M5 Hardware Quick Reference · 1. Set S1 - Configuration DIP Switch DIPs 1 & 2 ON 2. Set S1 - Configuration DIP Switch DIPs 3 & 4 OFF 3. Apply power to the M5-IC LEDs 1 & 2 and LEDs

Revised: 5/2014

Mechanical Specifications

Dimensions 3.5" (88.9mm) W x 10.25" (260.35mm) L

Temperature -55ºC to +85ºC, storage

0ºC to +70ºC, operat ing

Humidity 5% to 95% RHNC

TOC Detail

12

34

56

78

S1OFF ON

1

2

3

4

5

6JP1

JP2

J7

TB11TB12

RLY1RLY2RLY3RLY4RLY5RLY6RLY7RLY8

M2000 Base Quick Reference

RS2 Technologies, LLC - 400 Fisher Street, Suite G - Munster, IN 46321 - (877) 682-3532 - Fax (219) 836-9102www.rs2tech.com

D13

D14

D1

D2

D3

D4

D5D6D12 D11 D10D9 D8D7

TB1 101 TB31 4

TB2 101 TB51 4

TB41 4

TB61 4

TB71

3

TB8

18

Digital Inputs - (Figure 1)

TB1 (IN1 - IN5) TB2 (IN6 - IN10)

PIN 1 Reader 1 Door Contact – DI 1 PIN 1 Reader 3 REX – DI 6

PIN 2 Reader 1 Door Contact – DI 1 return PIN 2 Reader 3 REX – DI 6 return

PIN 3 Reader 1 REX – DI 2 PIN 3 Reader 4 Door Contact – DI 7

PIN 4 Reader 1 REX – DI 2 return PIN 4 Reader 4 Door Contact – DI 7 return

PIN 5 Reader 2 Door Contact – DI 3 PIN 5 Reader 4 REX – DI 8

PIN 6 Reader 2 Door Contact – DI 3 return PIN 6 Reader 4 REX – DI 8 return

PIN 7 Reader 2 REX – DI 4 PIN 7 Auxiliary Input 9 – DI 9

PIN 8 Reader 2 REX – DI 4 return PIN 8 Auxiliary Input 9 – DI 9 return

PIN 9 Reader 3 Door Contact – DI 5 PIN 9 Auxiliary Input 10 – DI 10

PIN 10 Reader 3 Door Contact – DI 5 return PIN 10 Auxiliary Input 10 – DI 10 return

Readers - 12Vdc Only (Explanations 2 & 3)

TB3 (Reader Port 1) TB4 (Reader Port 2)

PIN 1 +12Vdc PIN 1 +12Vdc

PIN 2 GND PIN 2 GND

PIN 3 Reader Data 1 – DI PIN 3 Reader Data 1 – DI

PIN 4 Reader LED – DO1 PIN 4 Reader LED – DO2

TB5 (Reader Port 3) TB6 (Reader Port 4)

PIN 1 +12Vdc PIN 6 +12Vdc

PIN 2 GND PIN 7 GND

PIN 3 Reader Data 1 – DI PIN 8 Reader Data 1 – DI

PIN 4 Reader LED – DO3 PIN 9 Reader LED – DO4

S1 - Address Dip Switch (Table 1)

Start at address 0

Each SIO address in the bus must be unique

Set switches prior to powering up

TB7 - RS-485 Bus Port 2

(2 wire ONLY! - Figure 2)

JP1 - Terminat ion

(Figure 2)

JP2 - Always set to LO

TB8

PIN 1 18Vac (Do not use 24 Vac)

PIN 2 18Vac (Do not use 24 Vac)

PIN 3 GND

PIN 4 +12Vdc out

PIN 5 Tamper Switch (GND)

PIN 6 Tamper Switch

PIN 7 12V Battery +

PIN 8 12V Battery –

TB91 6

TB101 61 61 6

J7 - M5-IC Connector

Outputs - (Explanation 1)

TB9 (Out 1 - Out 2) TB10 (Out 3 - Out 4)

PIN 1 Door Strike 1 – C PIN 1 Door Strike 2 – C

PIN 2 Door Strike 1 – NC PIN 2 Door Strike 2 – NC

PIN 3 Door Strike 1 – NO PIN 3 Door Strike 2 – NO

PIN 4 Auxiliary Output 2 – C PIN 4 Auxiliary Output 4 – C

PIN 5 Auxiliary Output 2 – NC PIN 5 Auxiliary Output 4 – NC

PIN 6 Auxiliary Output 2 – NO PIN 6 Auxiliary Output 4 – NO

TB11 (Out 5 - Out 6) TB12 (Out 7 - Out 8)

PIN 1 Door Strike 3 – C PIN 1 Door Strike 4 – CPIN 2 Door Strike 3 – NC PIN 2 Door Strike 4 – NCPIN 3 Door Strike 3 – NO PIN 3 Door Strike 4 – NOPIN 4 Auxiliary Output 6 – C PIN 4 Auxiliary Output 8 – CPIN 5 Auxiliary Output 6 – NC PIN 5 Auxiliary Output 8 – NC

PIN 6 Auxiliary Output 6 – NO PIN 6 Auxiliary Output 8 – NO

LEDs

D1 Off-Line / On-Line and Battery Status

Off-Line: 1 second cycle, 200ms ON / 800ms OFF

On-Line: 1 second cycle, 800ms ON / 200ms OFF

Double Flash: Battery Low

D2 Host Communicat ion Activity

D3 J7 Communication Activity

D4 RS-485 Bus Communication Activity

D5 Output 1 - ON = Energized

D6 Output 3 - ON = Energized

D7 Output 5 - ON = Energized

D8 Output 2 - ON = Energized

D9 Output 6 - ON = Energized

D10 Output 4 - ON = Energized

D11 Output 7 - ON = Energized

D12 Output 8 - ON = Energized

D13 Unassigned

D14 Unassigned

MountsReplace card puller with mounting screws.

Page 24: M5 Hardware Quick Reference · 1. Set S1 - Configuration DIP Switch DIPs 1 & 2 ON 2. Set S1 - Configuration DIP Switch DIPs 3 & 4 OFF 3. Apply power to the M5-IC LEDs 1 & 2 and LEDs

Exp. 4: Reader Input Wiring Configurations

Door contact and request to exit may be configured in one of four ways:

1. Unsupervised Wired to the F/2F Reader (Figure 2)

2. Supervised Wired to the F/2F Reader (Figure 3)

3. Wired to a M/R-J Box, WIU-2, or 4033-BGN (Not pictured)

4. Wired to the dedicated input on the M2000 Base

Figure 2

Door Contact Switch

Normally Closed

Contact

Request to Exit Switch

Normally Open

Contact

Figure 3

1K, 1%

1K, 1%

Door Contact Switch

Normally Closed

Contact

1K, 1%

1K, 1%

Request to Exit Switch

Normally Open

Contact

Table 1: S1 - Address Dip Switch

Address 1 2 3 4 5 6 7 8

0 Off Off Off Off Off On On Off

1 On Off Off Off Off On On Off

2 Off On Off Off Off On On Off

3 On On Off Off Off On On Off

4 Off Off On Off Off On On Off

5 On Off On Off Off On On Off

6 Off On On Off Off On On Off

7 On On On Off Off On On Off

8 Off Off Off On Off On On Off

9 On Off Off On Off On On Off

10 Off On Off On Off On On Off

11 On On Off On Off On On Off

12 Off Off On On Off On On Off

13 On Off On On Off On On Off

14 Off On On On Off On On Off

15 On On On On Off On On Off

16 Off Off Off Off On On On Off

17 On Off Off Off On On On Off

18 Off On Off Off On On On Off

19 On On Off Off On On On Off

20 Off Off On Off On On On Off

21 On Off On Off On On On Off

22 Off On On Off On On On Off

23 On On On Off On On On Off

24 Off Off Off On On On On Off

25 On Off Off On On On On Off

26 Off On Off On On On On Off

27 On On Off On On On On Off

28 Off Off On On On On On Off

29 On Off On On On On On Off

30 Off On On On On On On Off

31 On On On On On On On Off

Exp. 3: Reader Wiring

Supervised F/2F Reader

+12Vdc

Ground

Door DO(Reader LED)

Data 1

Exp. 2: RS-485 Sub-Panel Bus Termination

The M2000 Base has one 2 wire RS-485 sub-panel bus. The bus needs to be terminated at both the beginning and ending points.

JP1 is the termination jumper for the RS-485 Sub-Panel Bus.

Dra

in W

ire

Sh

ield

TB

7

GND

TR –

TR+

JP1

Exp. 1: Input Wiring Configurations

Normally Closed

Normally Opened

IN x

IN x

IN x

IN x

Normally Closed Supervised

Normally Opened Supervised1K, 1%

1K, 1%

1K, 1%

1K, 1%

Exp. 5: Output Wiring Configurations

Use one of the two methods of transient clamping below to protect relay contacts and reduce EMI emissions . Protect against accidental overloads by wiring in an inline fuse to the common side of the re lay.

AC Source – Internal Relay

ACSuppression MOV

Fuse

Load

OUT x

C

NC

NO

AC Source – Suppression MOV Selection

Clamp Voltage > 1.5x Vac RMS24Vac Str ike, Panasonic ERZ-C07DK470 Typical

AC Source – External Relay

External Relay

Suppression MOV AC

DISP

LED

GND

VOFuse

Load

To Reader s Green LED InputBlocking Diode

1N5817 Or

Equivalent

Suppression DiodeDC Source – Suppression Diode Selection

Diode Current Rating > 1x Strike CurrentDiode Break Down Voltage: 4x Strike Voltage12Vdc or 24Vdc Str ike, Diode 1N4002 (100V / 1A) Typical

DC Source – External Relay

DC

External Relay

Fuse

Load

Suppression Diode

To Reader s Green LED InputBlocking Diode

1N5817 Or

Equivalent

Suppression Diode

DATA

LED

GND

12V

RE

AD

ER

x

DC Source – Internal Relay

DC

Fuse

Load

Suppression Diode

OUT x

C

NC

NO

OviewTOC

4033-BGNWIU-2

© 2016 RS2 Technologies, LLC. - All rights reserved.M2000 Base Details

Page 25: M5 Hardware Quick Reference · 1. Set S1 - Configuration DIP Switch DIPs 1 & 2 ON 2. Set S1 - Configuration DIP Switch DIPs 3 & 4 OFF 3. Apply power to the M5-IC LEDs 1 & 2 and LEDs

TOC

J6 – HID Reader Supervision

The 2-pin connector J6 is the HID reader supervision connector. By default,

the connector is not jumpered and HID reader supervision is disabled. Place a

jumper over this connector to enable HID reader supervision.

Open: Disabled default

Closed: Enabled

J5 – Reserved

The 2-pin connector J5 is reserved.

Open: Disabled default

Closed: Enabled

J3 – Two-State Reporting Connector

The 2-pin connector J3 is the 2-state reporting connector. By default, this

connector is jumpered to enable 2-state reporting. Remove the jumper to

disable 2-state reporting.

Open: Disabled

Closed: Enabled default

J1 – Reader Interface Connector

J1-1: Door DI Common ReturnJ1-2: Door DI SwitchJ1-3: Exit DI Common ReturnJ1-4: Exit DI SwitchJ1-5: Wiegand Data 1J1-6: Wiegand Data 0J1-7: DO/LED Control Used to control door strike and activate green LED.J1-8: Beeper Control Signal switches to ground to activate the beeper.J1-9: -12Vdc Ground

J1-10: +12Vdc Power Fused power, 250mA maximum.

J2 – Controller Interface Connector

J1-1: 12Vdc Power for WIU-2.J1-2: GroundJ1-3: Door DO/LED Control Used to control door strike and activate green LED.J1-4: Reader F/2F DataJ1-5: Strike Normally ClosedJ1-6: Strike CommonJ1-7: Strike Normally Opened

J3J2

13

42

56

7

J5

J6

J1

13

42

56

78

910

WIU-2 Quick Reference

RS2 Technologies, LLC - 400 Fisher Street, Suite G - Munster, IN 46321 - (877) 682-3532 - Fax (219) 836-9102www.rs2tech.com Revised: 10/2013

Page 26: M5 Hardware Quick Reference · 1. Set S1 - Configuration DIP Switch DIPs 1 & 2 ON 2. Set S1 - Configuration DIP Switch DIPs 3 & 4 OFF 3. Apply power to the M5-IC LEDs 1 & 2 and LEDs

TOC 4033-BGN Quick Reference

RS2 Technologies, LLC - 400 Fisher Street, Suite G - Munster, IN 46321 - (877) 682-3532 - Fax (219) 836-9102www.rs2tech.com

P2 – Controller Interface Connector

P2-1: +12Vdc PowerP2-2: -12Vdc GroundP2-3: Door Strike Control DOP2-4: Reader Data 1P2-5: Door Strike Relay Normally ClosedP2-6: Door Strike Relay CommonP2-7: Door Strike Relay Normally Open

P1 – Reader Interface Connector

P1-10: +12Vdc PowerP1-9: -12Vdc Ground & Door DI CommonP1-8: Beeper ControlP1-7: LED ControlP1-6: Wiegand Data 1P1-5: Wiegand Data 0P1-4: Exit DI SwitchP1-3: Exit DI CommonP1-2: Door DI SwitchP1-1: Not Used

U2 89

10

13

42

56

7

P1

13

42

56

7

P2

1

O N

23

4

SW1

14

ON

SW1 – Dipswitch

OFF ON

Dip 1 Not Used Not Used

Dip 2 CASI 3201 (C10103) Treats 32-bit cards as CASI BCD cards.HID Standard 26 (H10301)HID Standard 37 (H10302)HID Corporate 1000 (H103XX)

Dip 3 Use existing HID readers without the supervision feature. HID supervised mode – uses new HID readers with supervision feature.

Dip 4 No Two-State Switch status message sent to CASI panel. Two-State Switch supervised mode – sends status message to CASI panel.

Revised: 8/2014

Page 27: M5 Hardware Quick Reference · 1. Set S1 - Configuration DIP Switch DIPs 1 & 2 ON 2. Set S1 - Configuration DIP Switch DIPs 3 & 4 OFF 3. Apply power to the M5-IC LEDs 1 & 2 and LEDs

TOC

RS2 Technologies, LLC - 400 Fisher Street, Suite G - Munster, IN 46321 - (877) 682-3532 - Fax (219) 836-9102www.rs2tech.com

J10 – Door Strike Relay Connector

J10-5: Normally Open Contact NOJ10-4: Not UsedJ10-3: Normally Closed Contact NCJ10-2: Relay Power Common Return

J10-1: Relay Power Source

Jumper Settings

Description OFF ON

J4 Door and REX Supervision 2-State Supervision Default 4-State Supervision

J5 Reserved N/A Must be jumped across pins 1 and 2

J7 Cabinet Tamper Switch N/A Jumper ON if not used Default

J9 Reserved Default N/A

Revised: 8/2014

WIU-4 Quick Reference

J6

32

110

87

96

54

13

42

56

J3

J10

53

24

1

J8

42

13

J7

J5

J9

J4

J6 – Reader Interface Connector

J6-1: +12Vdc Reader Power* Fused power, 250mA maximum.J6-2: GroundJ6-3: Wiegand Data 0J6-4: Wiegand Data 1J6-5: Green LED Switches to ground during door unlock time.J6-6: Red LED Optional - Switches to ground during door unlock time.J6-7: Beeper Optional - Signal switches to ground to activate the beeper.J6-8: Tamper Select** Optional

0Vdc = no tamperOpen = tamper

J6-9: Tamper Common** Optional - Ground OutputJ6-10: +5Vdc Reader Power*

* Use J6-1 or J6-10 for reader power, not both.

** If not used, tie J6-8 to J6-9

J3 – Door and REX Connector

J3-1: +12Vdc Fused power, 250mA maximum.J3-2: GroundJ3-3: Door High 5Vdc output.J3-4: Door Common Return – 0-5Vdc input.J3-5: REX High 5Vdc output.

J3-6: REX Common Return – 0-5Vdc input.

J8 – Controller Interface Connector

J8-4: Reader F/2F DataJ8-3: Door DOJ8-2: GroundJ8-1: Power 12vDC power for WIU-4

Page 28: M5 Hardware Quick Reference · 1. Set S1 - Configuration DIP Switch DIPs 1 & 2 ON 2. Set S1 - Configuration DIP Switch DIPs 3 & 4 OFF 3. Apply power to the M5-IC LEDs 1 & 2 and LEDs

Back View

Explanation 1: Ground Traces

When using a sing le earth ground where all M5 enclosures are wired together via the RS-485 Bus, additional action is required.

If using unique earth grounds for each M5 enclosure, no additional action is required.