National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 • Fax: 617-770-0700 • www.nfpa.org MEMORANDUM TO: Technical Committee on Residential Sprinkler Systems FROM: Elena Carroll, Project Administrator DATE: December 7, 2016 SUBJECT: NFPA 13R First Draft Technical Committee FINAL Ballot Results (A2018) According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. 31 Members Eligible to Vote 2 Members Not Returned (Hoover, Flancher) 16 Members Voted Affirmative on All Revisions 6 Members Vote Affirmative with Comment on one or more Revisions (Bell, Klein, Schwab, Skare, Towler, Yu) 8 Members Voted Negative on one or more Revisions (Asp, Bell, Cronin, Deegan, Nickelson, Schwab, Skare, Victor) 0 Members Abstained The attached report shows the number of affirmative, negative, and abstaining votes as well as the explanation of the vote for each revision. To pass ballot, each revision requires: (1) a simple majority of those eligible to vote and (2) an affirmative vote of 2 /3 of ballots returned. See Sections 3.3.4.3.(c) and 4.4.10.1 of the Regulations Governing the Development of NFPA Standards.

Upload: others

Post on 18-Mar-2020

8 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

National Fire Protection Association

1 Batterymarch Park, Quincy, MA 02169-7471

Phone: 617-770-3000 • Fax: 617-770-0700 • www.nfpa.org

M E M O R A N D U M

TO: Technical Committee on Residential Sprinkler Systems

FROM: Elena Carroll, Project Administrator

DATE: December 7, 2016

SUBJECT: NFPA 13R First Draft Technical Committee FINAL Ballot Results

(A2018)

According to the final ballot results, all ballot items received the necessary affirmative

votes to pass ballot.

31 Members Eligible to Vote

2 Members Not Returned (Hoover, Flancher)

16 Members Voted Affirmative on All Revisions

6 Members Vote Affirmative with Comment on one or more Revisions (Bell,

Klein, Schwab, Skare, Towler, Yu)

8 Members Voted Negative on one or more Revisions (Asp, Bell, Cronin,

Deegan, Nickelson, Schwab, Skare, Victor)

0 Members Abstained

The attached report shows the number of affirmative, negative, and abstaining votes as

well as the explanation of the vote for each revision.

To pass ballot, each revision requires: (1) a simple majority of those eligible to vote and

(2) an affirmative vote of 2/3 of ballots returned. See Sections 3.3.4.3.(c) and 4.4.10.1 of

the Regulations Governing the Development of NFPA Standards.

Page 2: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

First Revision No. 55-NFPA 13R-2016 [ Global Input ]

Rename section titles as follows (striking "Design Criteria"):

7.1 Inside Dwelling Unit.

7.2* Outside Dwelling Unit.

7.3 Garages.

Submitter Information Verification

Submitter Full Name: David Hague

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Tue Aug 23 08:55:04 EDT 2016

Committee Statement

Committee Statement: Coordination with Chapter 7 title change

Response Message:

Public Input No. 102-NFPA 13R-2016 [Sections 7.1, 7.2, 7.3]

Ballot Results

This item has passed ballot

31 Eligible Voters

2 Not Returned

29 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Flancher, Dawn M.

Hoover, Tonya L.

Affirmative All

Asp, Roland A.

Bell, Kerry M.

Benn, Fred

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

1 of 116 12/7/2016 1:13 PM

Page 3: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

Bradley, Frederick C.

Browning, Chase A.

Buuck, Daniel

Cronin, Bradford T.

Deegan, Thomas G.

Feid, Jeffrey

Haagensen, Dana R.

Isman, Kenneth E.

Klein, Marshall A.

Mathias, Daniel J.

Nickelson, David A.

O'Brian, Michael

Pilette, Maurice M.

Puchovsky, Milosh T.

Schwab, Peter T.

Skare, Eric J.

Skinner, Timothy J.

Stanley, George W.

Towler, Michael

Townley, Donald R.

Trim, Martin C. W.

Van Walraven, Ed

Victor, Terry L.

Viola, John F.

Webb, Ronald N.

Yu, Hong-Zeng

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

2 of 116 12/7/2016 1:13 PM

Page 4: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

First Revision No. 29-NFPA 13R-2016 [ Section No. 1.1 [Excluding any Sub-Sections] ]

This standard shall cover the design and installation of automatic sprinkler systems for protection againstfire hazards in residential occupancies up to and including four stories in height that are located inbuildings not exceeding 60 ft (18 m) in height above grade plane.

Submitter Information Verification

Submitter Full Name: David Hague

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 14 15:38:42 EDT 2016

Committee Statement

CommitteeStatement:

At a recent ICC code hearing, there was extensive discussion about whether the 4-story limit inNFPA 13R relates to grade plane, as defined in the building code. It does not.

Although the existing NFPA 13R text was thought to be clear that the 4-story limit is not with respectto grade plane (which is why "in height" was repeated in the existing scope text), it has becomeapparent that the existing text needs to be slightly adjusted to better convey this point. This isparticularly important with respect to application of NFPA 13R to buildings that are constructed inaccordance with pedestal building options under model building codes. Proper application of thestandard to pedestal construction, consistent with this proposal, is clearly conveyed in the NFPAResidential Sprinkler Systems Handbook, but adjusting the scoping text should help to eliminate anyremaining confusion.

ResponseMessage:

Public Input No. 37-NFPA 13R-2016 [Section No. 1.1 [Excluding any Sub-Sections]]

Ballot Results

This item has passed ballot

31 Eligible Voters

2 Not Returned

29 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Flancher, Dawn M.

Hoover, Tonya L.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

3 of 116 12/7/2016 1:13 PM

Page 5: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

Affirmative All

Asp, Roland A.

Bell, Kerry M.

Benn, Fred

Bradley, Frederick C.

Browning, Chase A.

Buuck, Daniel

Cronin, Bradford T.

Deegan, Thomas G.

Feid, Jeffrey

Haagensen, Dana R.

Isman, Kenneth E.

Klein, Marshall A.

Mathias, Daniel J.

Nickelson, David A.

O'Brian, Michael

Pilette, Maurice M.

Puchovsky, Milosh T.

Schwab, Peter T.

Skare, Eric J.

Skinner, Timothy J.

Stanley, George W.

Towler, Michael

Townley, Donald R.

Trim, Martin C. W.

Van Walraven, Ed

Victor, Terry L.

Viola, John F.

Webb, Ronald N.

Yu, Hong-Zeng

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

4 of 116 12/7/2016 1:13 PM

Page 6: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

First Revision No. 32-NFPA 13R-2016 [ Chapter 2 ]

Chapter 2 Referenced Publications

2.1 General.

The documents or portions thereof listed in this chapter are referenced within this standard and shall beconsidered part of the requirements of this document.

2.2 NFPA Publications.

National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471.

NFPA 13, Standard for the Installation of Sprinkler Systems, 2016 2019 edition.

NFPA 20, Standard for the Installation of Stationary Pumps for Fire Protection, 2016 2019 edition.

NFPA 22, Standard for Water Tanks for Private Fire Protection, 2013 2018 edition.

NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems,2014 2017 edition.

NFPA 101®, Life Safety Code®, 2015 2018 edition.

NFPA 220, Standard on Types of Building Construction, 2015 2018 edition.

NFPA 750, Standard on Water Mist Fire Protection Systems, 2014 2019 edition.

NFPA 5000®, Building Construction and Safety Code®, 2015 2018 edition.

2.3 Other Publications.

2.3.1 ANSI Publications.

American National Standards Institute, Inc., 25 West 43rd Street, 4th Floor, New York, NY 10036.

ANSI B36.10M, Welded and Seamless Wrought Steel Pipe , 2004.

2.3.1 ASME Publications.

American Society of Mechanical Engineers ASME International , Two Park Avenue, New York, NY10016-5990.

ASME A17.1, Safety Code for Elevators and Escalators, 2004 2013 .

ASME B16.1, Gray Iron Pipe Flanges and Flanged Fittings, Classes 25, 125, and 250,2010 2015 .

ASME B16.3, Malleable Iron Threaded Fittings, Classes 150 and 300,2006 2011 .

ASME B16.4, Gray Iron Threaded Fittings, Classes 125 and 250,2006 2011 .

ASME B16.5, Pipe Flanges and Flanged Fittings, NPS 1/2 through NPS 24 Metric/InchStandard,2009 2013 .

ASME B16.9, Factory-Made Wrought Buttwelding Fittings, 2007 2012 .

ASME B16.11, Forged Fittings, Socket-Welding and Threaded, 2009 2011 .

ANSI/ ASME B16.15, Cast Bronze Copper Alloy Threaded Fittings, Classes 125 and 250 , 2009 2013 .

ASME B16.18, Cast Copper Alloy Solder Joint Pressure Fittings, 2001 2012 .

ASME B16.22, Wrought Copper and Copper Alloy Solder Joint Pressure Fittings, 2001 2013 .

ASME B16.25, Buttwelding Ends, 2007 2012 .

ASME B36.10M, Welded and Seamless Wrought Steel Pipe , 2015.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

5 of 116 12/7/2016 1:13 PM

Page 7: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

2.3.2 ASTM Publications.

ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959.

ASTM A53/A53M, Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded andSeamless, 2012.

ASTM A135/A135M, Standard Specification for Electric-Resistance-Welded Steel Pipe, 2009 (2014) ,reapproved 2014 .

ASTM A234/A234M, Standard Specification for Piping Fittings of Wrought Carbon Steel and Alloy Steelfor Moderate and High Temperatures, 2013e1 2015 .

ASTM A795/A795M, Standard Specification for Black and Hot-Dipped Zinc-Coated (Galvanized) Weldedand Seamless Steel Pipe for Fire Protection Use, 2013.

ASTM B32, Standard Specification for Solder Metal, 2008, reapproved 2014 .

ASTM B43, Standard Specification for Seamless Red Brass Pipe, Standard Sizes , 2009 2015 .

ASTM B88, Standard Specification for Seamless Copper Water Tube, 2009 2014 .

ASTM B251, Standard Specification for General Requirements for Wrought Seamless Copper andCopper-Alloy Tube, 2010.

ASTM B813, Standard Specification for Liquid and Paste Fluxes for Soldering Applications of Copper andCopper-Alloy Tube, 2010 2016 .

ASTM F437, Standard Specification for Threaded Chlorinated Poly (Vinyl Chloride) (CPVC) Plastic PipeFittings, Schedule 80, 2009 2015 .

ASTM F438, Standard Specification for Socket-Type Chlorinated Poly (Vinyl Chloride) (CPVC) PlasticPipe Fittings, Schedule 40, 2009 2015 .

ASTM F439, Standard Specification for Socket-Type Chlorinated Poly (Vinyl Chloride) (CPVC) PlasticPipe Fittings, Schedule 80, 2009 2013 .

ASTM F442/F442M , Standard Specification for Chlorinated Poly (Vinyl Chloride) (CPVC) Plastic Pipe(SDR-PR), 2009 2015a .

2.3.3 AWS Publications.

American Welding Society, 550 NW LeJeune Road, Miami, FL 33126. 8869 NW 36 Street, #130, Miami,FL 33166-6672.

AWS A5.8/A5.8M , Specification for Filler Metals for Brazing and Braze Welding, 2004. 2011, Amendment1, 2012.

AWS B2.1/B2.1M , Specification for Welding Procedure and Performance Qualification,2009. 2014,Amendment 1, 2015.

2.3.4 Other Publications.

Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003.

2.4 References for Extracts in Mandatory Sections.

NFPA 13, Standard for the Installation of Sprinkler Systems, 2016 2019 edition.

NFPA 5000®, Building Construction and Safety Code®, 2015 2018 edition.

Submitter Information Verification

Submitter Full Name: David Hague

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 14 15:45:28 EDT 2016

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

6 of 116 12/7/2016 1:13 PM

Page 8: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

Committee Statement

Committee Statement: Referenced current SDO names, addresses, standard names, numbers, and editions.

Response Message:

Public Input No. 1-NFPA 13R-2015 [Chapter 2]

Ballot Results

This item has passed ballot

31 Eligible Voters

2 Not Returned

29 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Flancher, Dawn M.

Hoover, Tonya L.

Affirmative All

Asp, Roland A.

Bell, Kerry M.

Benn, Fred

Bradley, Frederick C.

Browning, Chase A.

Buuck, Daniel

Cronin, Bradford T.

Deegan, Thomas G.

Feid, Jeffrey

Haagensen, Dana R.

Isman, Kenneth E.

Klein, Marshall A.

Mathias, Daniel J.

Nickelson, David A.

O'Brian, Michael

Pilette, Maurice M.

Puchovsky, Milosh T.

Schwab, Peter T.

Skare, Eric J.

Skinner, Timothy J.

Stanley, George W.

Towler, Michael

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

7 of 116 12/7/2016 1:13 PM

Page 9: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

Townley, Donald R.

Trim, Martin C. W.

Van Walraven, Ed

Victor, Terry L.

Viola, John F.

Webb, Ronald N.

Yu, Hong-Zeng

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

8 of 116 12/7/2016 1:13 PM

Page 10: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

First Revision No. 1-NFPA 13R-2016 [ New Section after 3.3.1 ]

3.3.2 Carport.

A freestanding or attached covered structure open on at least two sides that provides shelter for motorvehicles.

Submitter Information Verification

Submitter Full Name: David Hague

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 14 11:33:15 EDT 2016

Committee Statement

CommitteeStatement:

The IBC indicates that a carport must be open on at least two sides. There has been someconfusion in that there are sometimes overhangs in front of garages that are only open on a singleside. These areas should be protected especially when there are living units above.

ResponseMessage:

Public Input No. 30-NFPA 13R-2016 [New Section after 3.3.1]

Ballot Results

This item has passed ballot

31 Eligible Voters

2 Not Returned

29 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Flancher, Dawn M.

Hoover, Tonya L.

Affirmative All

Asp, Roland A.

Bell, Kerry M.

Benn, Fred

Bradley, Frederick C.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

9 of 116 12/7/2016 1:13 PM

Page 11: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

Browning, Chase A.

Buuck, Daniel

Cronin, Bradford T.

Deegan, Thomas G.

Feid, Jeffrey

Haagensen, Dana R.

Isman, Kenneth E.

Klein, Marshall A.

Mathias, Daniel J.

Nickelson, David A.

O'Brian, Michael

Pilette, Maurice M.

Puchovsky, Milosh T.

Schwab, Peter T.

Skare, Eric J.

Skinner, Timothy J.

Stanley, George W.

Towler, Michael

Townley, Donald R.

Trim, Martin C. W.

Van Walraven, Ed

Victor, Terry L.

Viola, John F.

Webb, Ronald N.

Yu, Hong-Zeng

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

10 of 116 12/7/2016 1:13 PM

Page 12: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

First Revision No. 53-NFPA 13R-2016 [ Section No. 3.3.9 ]

3.3.10* Residential Occupancies.

Occupancies that include the following, as defined in NFPA 101: (1) apartment buildings, (2) lodging androoming houses, (3) board and care facilities, and (4) hotels, motels, and dormitories.

Supplemental Information

File Name Description

FR-53_A.3.3.10.docx New annex text

Submitter Information Verification

Submitter Full Name: David Hague

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Aug 01 08:19:26 EDT 2016

Committee Statement

CommitteeStatement:

NFPA 13R is appropriate for use in a residential occupancy. In the list of building types included inthis definition, there are situations where there will be mixed occupancies and NFPA 13R wouldnot be the appropriate sprinkler system for some of those occupancies.

ResponseMessage:

Public Input No. 19-NFPA 13R-2016 [Section No. 3.3.9]

Ballot Results

This item has passed ballot

31 Eligible Voters

2 Not Returned

28 Affirmative All

0 Affirmative with Comments

1 Negative with Comments

0 Abstention

Not Returned

Flancher, Dawn M.

Hoover, Tonya L.

Affirmative All

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

11 of 116 12/7/2016 1:13 PM

Page 13: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

Asp, Roland A.

Bell, Kerry M.

Benn, Fred

Bradley, Frederick C.

Browning, Chase A.

Buuck, Daniel

Cronin, Bradford T.

Deegan, Thomas G.

Feid, Jeffrey

Haagensen, Dana R.

Isman, Kenneth E.

Klein, Marshall A.

Mathias, Daniel J.

Nickelson, David A.

O'Brian, Michael

Pilette, Maurice M.

Puchovsky, Milosh T.

Skare, Eric J.

Skinner, Timothy J.

Stanley, George W.

Towler, Michael

Townley, Donald R.

Trim, Martin C. W.

Van Walraven, Ed

Victor, Terry L.

Viola, John F.

Webb, Ronald N.

Yu, Hong-Zeng

Negative with Comment

Schwab, Peter T.

The committee statement would be be better language than the actual language on the ballot that is simplycopied from A.1.1.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

12 of 116 12/7/2016 1:13 PM

Page 14: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

First Revision No. 35-NFPA 13R-2016 [ Section No. 3.3.13 ]

3.3.14 System Working Pressure.

The maximum anticipated static (i.e., nonflowing) or residual flowing pressure applied to sprinkler systemcomponents exclusive of surge pressures. and of pressure from the fire department connection.

Submitter Information Verification

Submitter Full Name: David Hague

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 14 15:51:13 EDT 2016

Committee Statement

Committee Statement: Correlates with NFPA 13.

Bring to correlating TC.

Response Message:

Public Input No. 31-NFPA 13R-2016 [Section No. 3.3.13]

Ballot Results

This item has passed ballot

31 Eligible Voters

2 Not Returned

28 Affirmative All

1 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Flancher, Dawn M.

Hoover, Tonya L.

Affirmative All

Asp, Roland A.

Bell, Kerry M.

Benn, Fred

Bradley, Frederick C.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

13 of 116 12/7/2016 1:13 PM

Page 15: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

Browning, Chase A.

Buuck, Daniel

Cronin, Bradford T.

Deegan, Thomas G.

Feid, Jeffrey

Haagensen, Dana R.

Isman, Kenneth E.

Klein, Marshall A.

Mathias, Daniel J.

Nickelson, David A.

O'Brian, Michael

Pilette, Maurice M.

Puchovsky, Milosh T.

Schwab, Peter T.

Skare, Eric J.

Skinner, Timothy J.

Stanley, George W.

Townley, Donald R.

Trim, Martin C. W.

Van Walraven, Ed

Victor, Terry L.

Viola, John F.

Webb, Ronald N.

Yu, Hong-Zeng

Affirmative with Comment

Towler, Michael

"Non-flowing" should be in parenthesis, similar to "flowing".

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

14 of 116 12/7/2016 1:13 PM

Page 16: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

First Revision No. 2-NFPA 13R-2016 [ New Section after 5.2.2.2 ]

5.2.2.3

Pipe or tube listed for light-hazard occupancies shall be permitted to be installed in concealed spacesabove ordinary-hazard rooms.

Submitter Information Verification

Submitter Full Name: David Hague

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 14 11:48:34 EDT 2016

Committee Statement

CommitteeStatement:

In many residential buildings, there are private garages that exceed 400 square feet. However,many of these garages are protected with residential sprinklers or standard sprinklers with a .05density. These concealed spaces are generally wood floor trusses with dwelling units above. Theconcealed space itself is technically light hazard and in most cases it is a rated assembly. In thespirit of providing life safety verses property protection, non metallic piping should be allowed to runin these spaces even when the room is greater than 400 square feet.

ResponseMessage:

Public Input No. 48-NFPA 13R-2016 [New Section after 5.2.2.2]

Ballot Results

This item has passed ballot

31 Eligible Voters

2 Not Returned

27 Affirmative All

0 Affirmative with Comments

2 Negative with Comments

0 Abstention

Not Returned

Flancher, Dawn M.

Hoover, Tonya L.

Affirmative All

Asp, Roland A.

Benn, Fred

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

15 of 116 12/7/2016 1:13 PM

Page 17: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

Bradley, Frederick C.

Browning, Chase A.

Buuck, Daniel

Deegan, Thomas G.

Feid, Jeffrey

Haagensen, Dana R.

Isman, Kenneth E.

Klein, Marshall A.

Mathias, Daniel J.

Nickelson, David A.

O'Brian, Michael

Pilette, Maurice M.

Puchovsky, Milosh T.

Schwab, Peter T.

Skare, Eric J.

Skinner, Timothy J.

Stanley, George W.

Towler, Michael

Townley, Donald R.

Trim, Martin C. W.

Van Walraven, Ed

Victor, Terry L.

Viola, John F.

Webb, Ronald N.

Yu, Hong-Zeng

Negative with Comment

Bell, Kerry M.

I don't disagree with the intent of this revision, but the revised text would permit the use of listed plastic piping inconcealed spaces with a protective membrane that does not meet the minimum requirements specified in thelisting.

Cronin, Bradford T.

There was no supporting data submitted for the allowance of LH pipe to protect an OH area, above what isalready allowed for small spaces. I view this as a major change and we should give it some consideration before itgets a blanket allowance in this document. I also agree with the comment of K.Bell and that if this section remains,there should be some installation rules that are added to the document such that we are not in conflict with thelisting requirements.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

16 of 116 12/7/2016 1:13 PM

Page 18: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

First Revision No. 3-NFPA 13R-2016 [ New Section after 5.2.2.2 ]

5.2.2.2.1

Pipe or tube installed in accordance with 5.2.2.2 shall be permitted to be installed exposed, inaccordance with their listing.

Submitter Information Verification

Submitter Full Name: David Hague

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 14 11:59:00 EDT 2016

Committee Statement

CommitteeStatement:

New Section 5.2.2.1 is a clarification and makes NFPA 13R consistent with Section 6.3.9.6.1 ofNFPA 13.

In residential buildings with ordinary hazard rooms larger than 400 square feet, the installer isrequired to transition from listed nonmetallic pipe to metallic pipe. New Section 5.2.2.2.2 eliminatesthat issue. The requirement to install the pipe or tube within a 1-hour fire resistance-rated assemblywill insure the integrity of the piping systems until the sprinkler heads activate.

ResponseMessage:

Public Input No. 76-NFPA 13R-2016 [New Section after 5.2.2.2]

Ballot Results

This item has passed ballot

31 Eligible Voters

2 Not Returned

27 Affirmative All

2 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Flancher, Dawn M.

Hoover, Tonya L.

Affirmative All

Asp, Roland A.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

17 of 116 12/7/2016 1:13 PM

Page 19: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

Benn, Fred

Bradley, Frederick C.

Browning, Chase A.

Buuck, Daniel

Cronin, Bradford T.

Deegan, Thomas G.

Feid, Jeffrey

Haagensen, Dana R.

Isman, Kenneth E.

Klein, Marshall A.

Mathias, Daniel J.

Nickelson, David A.

O'Brian, Michael

Pilette, Maurice M.

Puchovsky, Milosh T.

Schwab, Peter T.

Skare, Eric J.

Skinner, Timothy J.

Stanley, George W.

Towler, Michael

Townley, Donald R.

Trim, Martin C. W.

Van Walraven, Ed

Victor, Terry L.

Viola, John F.

Webb, Ronald N.

Affirmative with Comment

Bell, Kerry M.

The second sentence of the committee statement does not appear to be relevant to the revision and should bedeleted.

Yu, Hong-Zeng

The new sub-section 5.2.2.2.2 accepted by the Committee is missing on this ballot.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

18 of 116 12/7/2016 1:13 PM

Page 20: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

First Revision No. 4-NFPA 13R-2016 [ Section No. 5.2.14.1.2 ]

5.2.14.1.2 Valve Closure Time.

Unless the requirements of 6.8.5 apply, listed Listed indicating valves shall not close in less than5 seconds when operated at maximum possible speed from the fully open position.

Submitter Information Verification

Submitter Full Name: David Hague

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 14 12:06:13 EDT 2016

Committee Statement

CommitteeStatement:

The allowance to use 1/4 turn valves on backflow preventers was removed in 2016. Thisreference was missed.

ResponseMessage:

Public Input No. 44-NFPA 13R-2016 [Section No. 5.2.14.1.2]

Ballot Results

This item has passed ballot

31 Eligible Voters

2 Not Returned

29 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Flancher, Dawn M.

Hoover, Tonya L.

Affirmative All

Asp, Roland A.

Bell, Kerry M.

Benn, Fred

Bradley, Frederick C.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

19 of 116 12/7/2016 1:13 PM

Page 21: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

Browning, Chase A.

Buuck, Daniel

Cronin, Bradford T.

Deegan, Thomas G.

Feid, Jeffrey

Haagensen, Dana R.

Isman, Kenneth E.

Klein, Marshall A.

Mathias, Daniel J.

Nickelson, David A.

O'Brian, Michael

Pilette, Maurice M.

Puchovsky, Milosh T.

Schwab, Peter T.

Skare, Eric J.

Skinner, Timothy J.

Stanley, George W.

Towler, Michael

Townley, Donald R.

Trim, Martin C. W.

Van Walraven, Ed

Victor, Terry L.

Viola, John F.

Webb, Ronald N.

Yu, Hong-Zeng

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

20 of 116 12/7/2016 1:13 PM

Page 22: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

First Revision No. 49-NFPA 13R-2016 [ Section No. 5.4.2 ]

5.4.2* Systems in Areas Subject to Freezing.

Piping in areas that Where any portion of a system is subject to freezing and the temperature cannot bemaintained reliably at or above 40°F (4°C), the pipe shall be protected by use of one of the followingmethods:

(1)

(2) Dry pipe system

(3) Preaction system

(4) Listed dry pendent, dry upright, or dry sidewall sprinklers extended from pipe in heated areas

(5) Heat tracing in accordance with 6.7.2.2

Submitter Information Verification

Submitter Full Name: David Hague

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 27 13:35:51 EDT 2016

Committee Statement

CommitteeStatement:

This FR is to correlate with NFPA 13 and Committee revision to section 9.1.2 of NFPA 13D.

There are communities where the outdoor temperature will get below 40 for short periods oftime, but the water in the pipe has sufficient thermal mass not to need freeze protection.

ResponseMessage:

Ballot Results

This item has passed ballot

31 Eligible Voters

2 Not Returned

28 Affirmative All

1 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Flancher, Dawn M.

* Antifreeze system using a listed antifreeze solution in accordance with NFPA 13

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

21 of 116 12/7/2016 1:13 PM

Page 23: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

Hoover, Tonya L.

Affirmative All

Asp, Roland A.

Bell, Kerry M.

Benn, Fred

Bradley, Frederick C.

Browning, Chase A.

Buuck, Daniel

Cronin, Bradford T.

Deegan, Thomas G.

Feid, Jeffrey

Haagensen, Dana R.

Isman, Kenneth E.

Klein, Marshall A.

Mathias, Daniel J.

Nickelson, David A.

O'Brian, Michael

Pilette, Maurice M.

Puchovsky, Milosh T.

Skare, Eric J.

Skinner, Timothy J.

Stanley, George W.

Towler, Michael

Townley, Donald R.

Trim, Martin C. W.

Van Walraven, Ed

Victor, Terry L.

Viola, John F.

Webb, Ronald N.

Yu, Hong-Zeng

Affirmative with Comment

Schwab, Peter T.

The committee statement would make excellent annex language because it indicates that the temperature of thespace that the wet pipe is installed can get below 40 degrees as long as the pipe does not freeze.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

22 of 116 12/7/2016 1:13 PM

Page 24: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

First Revision No. 50-NFPA 13R-2016 [ New Section after 6.2.2.2 ]

6.2.2.3

Standard response sprinklers shall be permitted in garages in accordance with 7.3.2 .

Submitter Information Verification

Submitter Full Name: David Hague

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 27 13:47:00 EDT 2016

Committee Statement

CommitteeStatement:

Currently all sprinklers outside the dwelling unit must be quick response or residential. In garages,many times it is difficult to route wet sprinkler piping to the limitations of a standard spray quickresponse sidewall sprinkler. In some configurations a dry system has to be installed. AllowingStandard response sprinklers will give the user more options.

ResponseMessage:

Public Input No. 25-NFPA 13R-2016 [Section No. 6.2.2]

Ballot Results

This item has passed ballot

31 Eligible Voters

2 Not Returned

28 Affirmative All

0 Affirmative with Comments

1 Negative with Comments

0 Abstention

Not Returned

Flancher, Dawn M.

Hoover, Tonya L.

Affirmative All

Asp, Roland A.

Benn, Fred

Bradley, Frederick C.

Browning, Chase A.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

23 of 116 12/7/2016 1:13 PM

Page 25: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

Buuck, Daniel

Cronin, Bradford T.

Deegan, Thomas G.

Feid, Jeffrey

Haagensen, Dana R.

Isman, Kenneth E.

Klein, Marshall A.

Mathias, Daniel J.

Nickelson, David A.

O'Brian, Michael

Pilette, Maurice M.

Puchovsky, Milosh T.

Schwab, Peter T.

Skare, Eric J.

Skinner, Timothy J.

Stanley, George W.

Towler, Michael

Townley, Donald R.

Trim, Martin C. W.

Van Walraven, Ed

Victor, Terry L.

Viola, John F.

Webb, Ronald N.

Yu, Hong-Zeng

Negative with Comment

Bell, Kerry M.

The need to allow the use of standard response sprinklers in the garage is not apparent to me.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

24 of 116 12/7/2016 1:13 PM

Page 26: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

First Revision No. 8-NFPA 13R-2016 [ New Section after 6.2.3.3.2 ]

6.2.3.3.3*

Sprinklers in closets containing ventless clothes dryers shall be of the intermediate-temperatureclassification or higher.

6.2.3.3.3.1

Sprinklers adjacent to diffusers shall not be required to meet 6.2.3.3.3 where the temperature from thediffuser does not exceed 100°F (38°C).

Supplemental Information

File Name Description

Artwork_FR_8_-_NFPA_13R.pdfNew art for A.6.2.3.3.3.1

FR-8_A.6.2.3.3.3.docx New annex text

Submitter Information Verification

Submitter Full Name: David Hague

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 14 12:28:44 EDT 2016

Committee Statement

CommitteeStatement:

Ventless clothes dryers placed within closets have the potential to raise ceiling temperatures above100 F (38 C) for sustained periods of time, potentially weakening the operating mechanisms ofordinary temperature rated fire sprinklers over months or years of use, leading to inadvertentoperations. While ventless clothes dryers have been used in Europe for many years, they are fairlynew to the North American market, where vented clothes dryers have been the norm. Moreexpensive than vented dryers, they generally incorporate condensers in a “two-loop” system to firstheat some incoming air, allowing it to absorb moisture from the damp clothes, then continuallycondense the heated moist air to release the water before recirculating the resulting dry air within theclothes dryer. Unlike vented dryers, where moist heated air is exhausted to the building exterior, thesedevices capture the water to a drain or pan, while the heat from the condensing cycle is exhaustedinto the immediate area.

The condensers in combination machines that both wash and dry the clothes are generally water-cooled, such that quantities of cold water are used to condense the moisture evaporated from theclothes during the drying cycle, and pumped away through the drain line. But the standalone dryerunits are air-cooled, using the ambient air as a heat sink. While this heat can be dissipated in a largelaundry room, it can be expected to raise the temperatures within a laundry closet to levelsunacceptable for ordinary temperature rated sprinklers. All standalone ventless dryers in the marketare reportedly of this type.

Text for 6.2.3.3.3.1: This is language that is similar to NFPA 13 8.3.2.5 (9). In many places HVAC Airhandlers do not produce high temperatures. The ability to ignore the spacing away from thesediffusers simplifies the installation.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

25 of 116 12/7/2016 1:13 PM

Page 27: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

ResponseMessage:

Public Input No. 92-NFPA 13R-2016 [New Section after A.6.2.3.3]

Public Input No. 45-NFPA 13R-2016 [New Section after 6.2.3.3.3]

Public Input No. 100-NFPA 13R-2016 [New Section after 6.2.3.3.2]

Ballot Results

This item has passed ballot

31 Eligible Voters

2 Not Returned

29 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Flancher, Dawn M.

Hoover, Tonya L.

Affirmative All

Asp, Roland A.

Bell, Kerry M.

Benn, Fred

Bradley, Frederick C.

Browning, Chase A.

Buuck, Daniel

Cronin, Bradford T.

Deegan, Thomas G.

Feid, Jeffrey

Haagensen, Dana R.

Isman, Kenneth E.

Klein, Marshall A.

Mathias, Daniel J.

Nickelson, David A.

O'Brian, Michael

Pilette, Maurice M.

Puchovsky, Milosh T.

Schwab, Peter T.

Skare, Eric J.

Skinner, Timothy J.

Stanley, George W.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

26 of 116 12/7/2016 1:13 PM

Page 28: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

Towler, Michael

Townley, Donald R.

Trim, Martin C. W.

Van Walraven, Ed

Victor, Terry L.

Viola, John F.

Webb, Ronald N.

Yu, Hong-Zeng

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

27 of 116 12/7/2016 1:13 PM

Page 29: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

First Revision No. 11-NFPA 13R-2016 [ Section No. 6.2.3.3.3 ]

6.2.3.3.4

Sprinklers installed near specific heat sources that are identified in Table 6.2.3.3.4 shall be of thetemperature rating indicated in Table 6.2.3.3.4 unless sprinklers are listed for positioning closer to theheat source.

Table 6.2.3.3.4 Minimum Distances for Ordinary and Intermediate Temperature Residential Sprinklers

Heat Source

From Edge

of Source to OrdinaryTemperature Sprinkler

From Edge of Source toIntermediate Temperature Sprinkler

in. mm in. mm

Side of open or recessedfireplace

36 900 12 300

Front of recessed fireplace 60 1500 36 900

Coal- or wood-

burning stove42 1050 12 300

Kitchen range 18 450 9 225

Wall oven 18 450 9 225

Hot air flues 18 450 9 225

Uninsulated heat ducts 18 450 9 225

Uninsulated hot water pipes 12 300 6 150

Side of ceiling- orwall-mounted hot air diffusers

24 600 12 300

Front of wall-mounted hot airdiffusers

36 900 18 450

Hot water heater or furnace 6 150 3 75

Light fixture:

0 W–250 W 6 150 3 75

 250 W–499 W 12 300 6 150

Submitter Information Verification

Submitter Full Name: David Hague

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 14 12:36:27 EDT 2016

Committee Statement

CommitteeStatement:

The language provided in the table provides ambiguous information about spacing sprinklers withregard to fireplaces. These diagrams provide additional clarification. Alternatively, the Annexcomment could be attached to 6.2.3.3.3.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

28 of 116 12/7/2016 1:13 PM

Page 30: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

ResponseMessage:

Public Input No. 91-NFPA 13R-2016 [Section No. 6.2.3.3.3]

Ballot Results

This item has passed ballot

31 Eligible Voters

2 Not Returned

21 Affirmative All

1 Affirmative with Comments

7 Negative with Comments

0 Abstention

Not Returned

Flancher, Dawn M.

Hoover, Tonya L.

Affirmative All

Benn, Fred

Bradley, Frederick C.

Browning, Chase A.

Buuck, Daniel

Cronin, Bradford T.

Feid, Jeffrey

Haagensen, Dana R.

Isman, Kenneth E.

Klein, Marshall A.

Mathias, Daniel J.

O'Brian, Michael

Pilette, Maurice M.

Puchovsky, Milosh T.

Skinner, Timothy J.

Stanley, George W.

Townley, Donald R.

Trim, Martin C. W.

Van Walraven, Ed

Viola, John F.

Webb, Ronald N.

Yu, Hong-Zeng

Affirmative with Comment

Towler, Michael

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

29 of 116 12/7/2016 1:13 PM

Page 31: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

Further review/discussion of the annex diagrams is needed to confirm their intent/graphical representation.

Negative with Comment

Asp, Roland A.

In Terraview, this FR appears to be deleting section 6.2.3.3.4 and table 6.2.3.3.4 (these were section and table6.2.3.3.3 in 2016 edition). I believe the committee agreed to include diagrams in the annex for distances forsprinklers near fireplaces but not to delete this section and table.

Bell, Kerry M.

I support the introduction of the new figure addressing the location of sprinklers to fireplaces, but I don't believe itis appropriate to delete the entire table.

Deegan, Thomas G.

While I agree with adding information regarding fireplaces, I do not agree with removing the text of 6.2.3.3.4 as isindicated by the stricken text. I believe this text adds value (although it could stand to be updated) and this textremains in NFPA 13D. I believe NFPA 13R and NFPA 13D should be consistent in this regard.

Nickelson, David A.

I agree with the additional information on fireplaces, but I am not in agreement with removing the table. The tabledoes need to be updated, but it still needs to remain for now.

Schwab, Peter T.

Is the intent of this first revision to delete the table or is this a Terraview "issue". I am in favor of the fireplacediagrams but we should not be deleting this table?

Skare, Eric J.

I believe there is a problem with this first revision. The intent of the committee was to approve the inclusion of the"fireplace figures" in the Annex, not delete the entire section and table.

Victor, Terry L.

I agree with the other negative ballots on this FR. The intend was to add two figures to the annex illustratingspacing around a fireplace. The table itself was never meant to be deleted and should remain in the document.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

30 of 116 12/7/2016 1:13 PM

Page 32: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

First Revision No. 12-NFPA 13R-2016 [ New Section after 6.4.6.1.1 ]

6.4.6.1.1

Pendent and upright sprinklers that have not been listed with specific positioning criteria or deflector-to-ceiling distances shall be positioned so that the deflectors are within 1 in. to 4 in. (25.4 mm to102 100 mm) of the ceiling. unless otherwise permitted by 6.4.6.1.1.1 .

6.4.6.1.1.1

Pendent-type residential sprinklers located under or adjacent to beams in accordance with 7.1.1.3.1shall be installed in accordance with one of the following:

(1) Pendent, recessed pendent, and flush-type pendent sprinklers shall be permitted to be installeddirectly under a beam having a maximum depth of 14 in. (350 mm) with the sprinkler deflector 1 in.to 2 in. (25 mm to 50 mm) below the beam, or in accordance with the manufacturer’s instructionsfor recessed or flush sprinklers if the deflector is less than 1 in. (25 mm) below the beam.

(2) Pendent sprinklers, including flush-type pendent sprinklers, shall be permitted to be installedadjacent to beams when the vertical centerline of the sprinkler is no greater than 2 in. (50 mm)from the edge of the beam and with the sprinkler deflector 1 in. to 2 in. (25 mm to 50 mm) belowthe beam, or in accordance with the manufacturer’s instructions for flush sprinklers if the deflectoris less than 1 in. (25 mm) below the beam.

Submitter Information Verification

Submitter Full Name: David Hague

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 14 13:04:47 EDT 2016

Committee Statement

CommitteeStatement:

Both NFPA 13D and NFPA 13R allow for installation of sprinklers below beamed ceilings in thedischarge criteria, however, as the listing for installation below beams up to 14 inches has beenremoved from their certification for this application in response to the FPRF research on this topic in2011, the proper installation of the sprinklers below the beamed ceilings needs to be addressed inthe installation chapter of NFPA 13R and 13D. These proposals address the deflector distancebelow the beams.

ResponseMessage:

Public Input No. 82-NFPA 13R-2016 [New Section after 6.4.6.1.1]

Ballot Results

This item has passed ballot

31 Eligible Voters

2 Not Returned

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

31 of 116 12/7/2016 1:13 PM

Page 33: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

29 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Flancher, Dawn M.

Hoover, Tonya L.

Affirmative All

Asp, Roland A.

Bell, Kerry M.

Benn, Fred

Bradley, Frederick C.

Browning, Chase A.

Buuck, Daniel

Cronin, Bradford T.

Deegan, Thomas G.

Feid, Jeffrey

Haagensen, Dana R.

Isman, Kenneth E.

Klein, Marshall A.

Mathias, Daniel J.

Nickelson, David A.

O'Brian, Michael

Pilette, Maurice M.

Puchovsky, Milosh T.

Schwab, Peter T.

Skare, Eric J.

Skinner, Timothy J.

Stanley, George W.

Towler, Michael

Townley, Donald R.

Trim, Martin C. W.

Van Walraven, Ed

Victor, Terry L.

Viola, John F.

Webb, Ronald N.

Yu, Hong-Zeng

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

32 of 116 12/7/2016 1:13 PM

Page 34: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

First Revision No. 51-NFPA 13R-2016 [ Section No. 6.4.6.3.2 ]

6.4.6.3.2* Within Closets and Compartments .

In all closets and compartments that are enclosed by walls and a door and that are not larger than 400 ft3

(11.33 m3), including those housing mechanical equipment, pendent, upright, and sidewall residentialsprinklers shall be permitted to be installed in either of the following situations:

(1) Within 18 in. (460 mm) of the ceiling to avoid obstructions near the ceiling where the compartment isenclosed by walls and a door

(2) At the highest ceiling level without regard to obstructions or minimum distances to walls

Submitter Information Verification

Submitter Full Name: David Hague

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 27 14:15:27 EDT 2016

Committee Statement

CommitteeStatement:

This first revision will correlate with the new first revision in NFPA 13D on this same concept.This first revision will accomplish what the submitter of PI 26 is seeking.

ResponseMessage:

Public Input No. 46-NFPA 13R-2016 [New Section after 6.4.6.3.2]

Ballot Results

This item has passed ballot

31 Eligible Voters

2 Not Returned

29 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Flancher, Dawn M.

Hoover, Tonya L.

Affirmative All

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

33 of 116 12/7/2016 1:13 PM

Page 35: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

Asp, Roland A.

Bell, Kerry M.

Benn, Fred

Bradley, Frederick C.

Browning, Chase A.

Buuck, Daniel

Cronin, Bradford T.

Deegan, Thomas G.

Feid, Jeffrey

Haagensen, Dana R.

Isman, Kenneth E.

Klein, Marshall A.

Mathias, Daniel J.

Nickelson, David A.

O'Brian, Michael

Pilette, Maurice M.

Puchovsky, Milosh T.

Schwab, Peter T.

Skare, Eric J.

Skinner, Timothy J.

Stanley, George W.

Towler, Michael

Townley, Donald R.

Trim, Martin C. W.

Van Walraven, Ed

Victor, Terry L.

Viola, John F.

Webb, Ronald N.

Yu, Hong-Zeng

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

34 of 116 12/7/2016 1:13 PM

Page 36: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

First Revision No. 14-NFPA 13R-2016 [ Section No. 6.5.3 ]

6.5.3

A test connection shall be installed that permits the testing of the alarm mechanisms.

Submitter Information Verification

Submitter Full Name: David Hague

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 14 13:45:29 EDT 2016

Committee Statement

Committee Statement: Delete this section. 6.10 adequately addresses test connections.

Response Message:

Public Input No. 11-NFPA 13R-2016 [Section No. 6.5.3]

Ballot Results

This item has passed ballot

31 Eligible Voters

2 Not Returned

29 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Flancher, Dawn M.

Hoover, Tonya L.

Affirmative All

Asp, Roland A.

Bell, Kerry M.

Benn, Fred

Bradley, Frederick C.

Browning, Chase A.

Buuck, Daniel

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

35 of 116 12/7/2016 1:13 PM

Page 37: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

Cronin, Bradford T.

Deegan, Thomas G.

Feid, Jeffrey

Haagensen, Dana R.

Isman, Kenneth E.

Klein, Marshall A.

Mathias, Daniel J.

Nickelson, David A.

O'Brian, Michael

Pilette, Maurice M.

Puchovsky, Milosh T.

Schwab, Peter T.

Skare, Eric J.

Skinner, Timothy J.

Stanley, George W.

Towler, Michael

Townley, Donald R.

Trim, Martin C. W.

Van Walraven, Ed

Victor, Terry L.

Viola, John F.

Webb, Ronald N.

Yu, Hong-Zeng

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

36 of 116 12/7/2016 1:13 PM

Page 38: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

First Revision No. 36-NFPA 13R-2016 [ New Section after 6.5.4 ]

6.5.4 Waste and Linen Handling Systems.

6.5.4.1

A sprinkler shall be installed within the chute at alternate floor levels in buildings over two stories inheight, with a mandatory sprinkler located at the lowest service level.

6.5.4.2

Gravity chutes shall be protected internally by automatic sprinklers unless they are lined in accordancewith 6.2.2.6.1 of NFPA 82 .

Submitter Information Verification

Submitter Full Name: David Hague

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 14 15:56:31 EDT 2016

Committee Statement

CommitteeStatement:

Chapter 6 does not exempt building service chutes. This language specifies design criteriawhen chute sprinklers are installed.

ResponseMessage:

Public Input No. 24-NFPA 13R-2016 [New Section after 7.2.5]

Ballot Results

This item has passed ballot

31 Eligible Voters

2 Not Returned

29 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Flancher, Dawn M.

Hoover, Tonya L.

Affirmative All

Asp, Roland A.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

37 of 116 12/7/2016 1:13 PM

Page 39: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

Bell, Kerry M.

Benn, Fred

Bradley, Frederick C.

Browning, Chase A.

Buuck, Daniel

Cronin, Bradford T.

Deegan, Thomas G.

Feid, Jeffrey

Haagensen, Dana R.

Isman, Kenneth E.

Klein, Marshall A.

Mathias, Daniel J.

Nickelson, David A.

O'Brian, Michael

Pilette, Maurice M.

Puchovsky, Milosh T.

Schwab, Peter T.

Skare, Eric J.

Skinner, Timothy J.

Stanley, George W.

Towler, Michael

Townley, Donald R.

Trim, Martin C. W.

Van Walraven, Ed

Victor, Terry L.

Viola, John F.

Webb, Ronald N.

Yu, Hong-Zeng

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

38 of 116 12/7/2016 1:13 PM

Page 40: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

First Revision No. 15-NFPA 13R-2016 [ Section No. 6.6.5 [Excluding any Sub-Sections] ]

Except as provided for in 6.6.5.1, sprinklers shall not be required in any lanais, porches, balconies,corridors, carports, porte cocheres, and stairs that are open and attached.

Supplemental Information

File Name Description

FR-15_A.6.6.5.docx New annex material and deletes figures A.6.6.5(a) through (e)

Submitter Information Verification

Submitter Full Name: David Hague

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 14 13:55:26 EDT 2016

Committee Statement

CommitteeStatement:

A blog in regards to lanais can be found at

http://sprinkler.blog.nfpa.org/2015/01/introducing-audrey-goldstein-the-fire-sprinkler-initiatives-newest-blogger.html

The technical committee should indicate whether lanais are the same as porches andbalconies and sprinklers can be omitted.

ResponseMessage:

Public Input No. 15-NFPA 13R-2016 [Section No. 6.6.5 [Excluding any Sub-Sections]]

Ballot Results

This item has passed ballot

31 Eligible Voters

2 Not Returned

29 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Flancher, Dawn M.

Hoover, Tonya L.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

39 of 116 12/7/2016 1:13 PM

Page 41: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

Affirmative All

Asp, Roland A.

Bell, Kerry M.

Benn, Fred

Bradley, Frederick C.

Browning, Chase A.

Buuck, Daniel

Cronin, Bradford T.

Deegan, Thomas G.

Feid, Jeffrey

Haagensen, Dana R.

Isman, Kenneth E.

Klein, Marshall A.

Mathias, Daniel J.

Nickelson, David A.

O'Brian, Michael

Pilette, Maurice M.

Puchovsky, Milosh T.

Schwab, Peter T.

Skare, Eric J.

Skinner, Timothy J.

Stanley, George W.

Towler, Michael

Townley, Donald R.

Trim, Martin C. W.

Van Walraven, Ed

Victor, Terry L.

Viola, John F.

Webb, Ronald N.

Yu, Hong-Zeng

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

40 of 116 12/7/2016 1:13 PM

Page 42: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

First Revision No. 17-NFPA 13R-2016 [ New Section after 6.6.6.1 ]

6.6.6.2

Spaces that contain fuel-fired equipment shall also comply with 6.6.6.3 or 6.6.6.4 .

6.6.6.3

Where the fuel-fired equipment is above all occupied areas, sprinkler protection shall not be required inthe concealed space.

6.6.6.4

Where fuel-fired equipment is below or on the same level as occupied areas, at least one quick-response intermediate-temperature sprinkler shall be installed above the equipment or at the wallseparating the space with the fuel-fired equipment from the occupied space.

Submitter Information Verification

Submitter Full Name: David Hague

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 14 14:03:47 EDT 2016

Committee Statement

CommitteeStatement:

The change reflects recent revisions made to NFPA 13D, Section 8.3.5.1, recognizing that fuel-firedequipment in attics is not uniquely hazardous to warrant the complexity of having to install a singlesprinkler in an attic space that will often be required to be protected from freezing. Given thepending prohibition of anti-freeze systems, having to install a freeze-protected single sprinkler over afuel-fired appliance will become even more difficult in the future.

ResponseMessage:

Public Input No. 109-NFPA 13R-2016 [New Section after 6.6.6.1]

Ballot Results

This item has passed ballot

31 Eligible Voters

2 Not Returned

29 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Flancher, Dawn M.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

41 of 116 12/7/2016 1:13 PM

Page 43: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

Hoover, Tonya L.

Affirmative All

Asp, Roland A.

Bell, Kerry M.

Benn, Fred

Bradley, Frederick C.

Browning, Chase A.

Buuck, Daniel

Cronin, Bradford T.

Deegan, Thomas G.

Feid, Jeffrey

Haagensen, Dana R.

Isman, Kenneth E.

Klein, Marshall A.

Mathias, Daniel J.

Nickelson, David A.

O'Brian, Michael

Pilette, Maurice M.

Puchovsky, Milosh T.

Schwab, Peter T.

Skare, Eric J.

Skinner, Timothy J.

Stanley, George W.

Towler, Michael

Townley, Donald R.

Trim, Martin C. W.

Van Walraven, Ed

Victor, Terry L.

Viola, John F.

Webb, Ronald N.

Yu, Hong-Zeng

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

42 of 116 12/7/2016 1:13 PM

Page 44: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

First Revision No. 18-NFPA 13R-2016 [ Section No. 6.6.7 ]

6.6.7

Sprinklers shall not be required in closets (regardless of size) on exterior balconies and exteriorbreezeways/ corridors, regardless of size, as long as the closet does not have doors or unprotectedpenetrations directly into the dwelling unit.

Submitter Information Verification

Submitter Full Name: David Hague

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 14 14:06:25 EDT 2016

Committee Statement

CommitteeStatement:

The term "Breezeway" is not defined in this standard or the IBC. The correct term iscorridor.

Response Message:

Public Input No. 28-NFPA 13R-2016 [Section No. 6.6.7]

Ballot Results

This item has passed ballot

31 Eligible Voters

2 Not Returned

29 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Flancher, Dawn M.

Hoover, Tonya L.

Affirmative All

Asp, Roland A.

Bell, Kerry M.

Benn, Fred

Bradley, Frederick C.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

43 of 116 12/7/2016 1:13 PM

Page 45: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

Browning, Chase A.

Buuck, Daniel

Cronin, Bradford T.

Deegan, Thomas G.

Feid, Jeffrey

Haagensen, Dana R.

Isman, Kenneth E.

Klein, Marshall A.

Mathias, Daniel J.

Nickelson, David A.

O'Brian, Michael

Pilette, Maurice M.

Puchovsky, Milosh T.

Schwab, Peter T.

Skare, Eric J.

Skinner, Timothy J.

Stanley, George W.

Towler, Michael

Townley, Donald R.

Trim, Martin C. W.

Van Walraven, Ed

Victor, Terry L.

Viola, John F.

Webb, Ronald N.

Yu, Hong-Zeng

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

44 of 116 12/7/2016 1:13 PM

Page 46: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

First Revision No. 19-NFPA 13R-2016 [ New Section after 6.7.2.1 ]

6.7.2.1.1

Piping shall be permitted to be exposed to temperatures less than 40°F (4°C) when in accordance with5.4.4 .

Submitter Information Verification

Submitter Full Name: David Hague

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 14 14:14:44 EDT 2016

Committee Statement

Committee Statement: This is a pointer to 5.4.4 so it will not be overlooked when applying 6.7.2.1.

Response Message:

Public Input No. 56-NFPA 13R-2016 [New Section after 6.7.2.1]

Ballot Results

This item has passed ballot

31 Eligible Voters

2 Not Returned

29 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Flancher, Dawn M.

Hoover, Tonya L.

Affirmative All

Asp, Roland A.

Bell, Kerry M.

Benn, Fred

Bradley, Frederick C.

Browning, Chase A.

Buuck, Daniel

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

45 of 116 12/7/2016 1:13 PM

Page 47: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

Cronin, Bradford T.

Deegan, Thomas G.

Feid, Jeffrey

Haagensen, Dana R.

Isman, Kenneth E.

Klein, Marshall A.

Mathias, Daniel J.

Nickelson, David A.

O'Brian, Michael

Pilette, Maurice M.

Puchovsky, Milosh T.

Schwab, Peter T.

Skare, Eric J.

Skinner, Timothy J.

Stanley, George W.

Towler, Michael

Townley, Donald R.

Trim, Martin C. W.

Van Walraven, Ed

Victor, Terry L.

Viola, John F.

Webb, Ronald N.

Yu, Hong-Zeng

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

46 of 116 12/7/2016 1:13 PM

Page 48: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

First Revision No. 20-NFPA 13R-2016 [ New Section after 6.8.7 ]

6.8.8

In multistory buildings, a control valve per floor shall not be required.

Submitter Information Verification

Submitter Full Name: David Hague

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 14 14:16:50 EDT 2016

Committee Statement

CommitteeStatement:

Currently 6.16.4 indicates that zoning per floor is not required. However, that is for buildings withalarm systems. Buildings without alarm systems should not be required to be isolated per floor.

ResponseMessage:

Public Input No. 6-NFPA 13R-2016 [New Section after 6.8.7]

Ballot Results

This item has passed ballot

31 Eligible Voters

2 Not Returned

29 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Flancher, Dawn M.

Hoover, Tonya L.

Affirmative All

Asp, Roland A.

Bell, Kerry M.

Benn, Fred

Bradley, Frederick C.

Browning, Chase A.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

47 of 116 12/7/2016 1:13 PM

Page 49: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

Buuck, Daniel

Cronin, Bradford T.

Deegan, Thomas G.

Feid, Jeffrey

Haagensen, Dana R.

Isman, Kenneth E.

Klein, Marshall A.

Mathias, Daniel J.

Nickelson, David A.

O'Brian, Michael

Pilette, Maurice M.

Puchovsky, Milosh T.

Schwab, Peter T.

Skare, Eric J.

Skinner, Timothy J.

Stanley, George W.

Towler, Michael

Townley, Donald R.

Trim, Martin C. W.

Van Walraven, Ed

Victor, Terry L.

Viola, John F.

Webb, Ronald N.

Yu, Hong-Zeng

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

48 of 116 12/7/2016 1:13 PM

Page 50: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

First Revision No. 21-NFPA 13R-2016 [ New Section after 6.8.8 ]

6.8.10*

Each connection from a standpipe that is part of a combined system to a sprinkler system or floor shallhave an individual control valve and check valve.

Supplemental Information

File Name Description

FR-21_A.6.8.10.docx Includes annex language and extracted figures from NFPA 13.

Submitter Information Verification

Submitter Full Name: David Hague

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 14 14:22:30 EDT 2016

Committee Statement

Committee Statement: This language is found in NFPA 13 & 14. The rules should be in NFPA 13R as well.

Response Message:

Public Input No. 34-NFPA 13R-2016 [New Section after 6.8.8]

Ballot Results

This item has passed ballot

31 Eligible Voters

2 Not Returned

29 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Flancher, Dawn M.

Hoover, Tonya L.

Affirmative All

Asp, Roland A.

Bell, Kerry M.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

49 of 116 12/7/2016 1:13 PM

Page 51: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

Benn, Fred

Bradley, Frederick C.

Browning, Chase A.

Buuck, Daniel

Cronin, Bradford T.

Deegan, Thomas G.

Feid, Jeffrey

Haagensen, Dana R.

Isman, Kenneth E.

Klein, Marshall A.

Mathias, Daniel J.

Nickelson, David A.

O'Brian, Michael

Pilette, Maurice M.

Puchovsky, Milosh T.

Schwab, Peter T.

Skare, Eric J.

Skinner, Timothy J.

Stanley, George W.

Towler, Michael

Townley, Donald R.

Trim, Martin C. W.

Van Walraven, Ed

Victor, Terry L.

Viola, John F.

Webb, Ronald N.

Yu, Hong-Zeng

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

50 of 116 12/7/2016 1:13 PM

Page 52: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

First Revision No. 22-NFPA 13R-2016 [ New Section after 6.10.3 ]

6.10.4

The test connection shall be permitted to be located at any point on the system side of the alarm flowdevice.

Submitter Information Verification

Submitter Full Name: David Hague

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 14 14:33:25 EDT 2016

Committee Statement

CommitteeStatement:

This clarifies that the test connection can be located at any point downstream of the flowswitch or pressure switch.

ResponseMessage:

Public Input No. 12-NFPA 13R-2016 [New Section after 6.10.3]

Ballot Results

This item has passed ballot

31 Eligible Voters

2 Not Returned

29 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Flancher, Dawn M.

Hoover, Tonya L.

Affirmative All

Asp, Roland A.

Bell, Kerry M.

Benn, Fred

Bradley, Frederick C.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

51 of 116 12/7/2016 1:13 PM

Page 53: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

Browning, Chase A.

Buuck, Daniel

Cronin, Bradford T.

Deegan, Thomas G.

Feid, Jeffrey

Haagensen, Dana R.

Isman, Kenneth E.

Klein, Marshall A.

Mathias, Daniel J.

Nickelson, David A.

O'Brian, Michael

Pilette, Maurice M.

Puchovsky, Milosh T.

Schwab, Peter T.

Skare, Eric J.

Skinner, Timothy J.

Stanley, George W.

Towler, Michael

Townley, Donald R.

Trim, Martin C. W.

Van Walraven, Ed

Victor, Terry L.

Viola, John F.

Webb, Ronald N.

Yu, Hong-Zeng

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

52 of 116 12/7/2016 1:13 PM

Page 54: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

First Revision No. 23-NFPA 13R-2016 [ New Section after 6.11.5 ]

6.11.6

In buildings with mixed occupancies where the nonresidential occupancy/occupancies is protected withan NFPA 13 system, a single fire department connection in accordance with NFPA 13 shall bepermitted.

Submitter Information Verification

Submitter Full Name: David Hague

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 14 14:51:40 EDT 2016

Committee Statement

CommitteeStatement:

Since the committee has indicate that a building can have both NFPA 13 and 13R systems inthe same building, guidance is needed in regards to FDC arrangement and sizing.

ResponseMessage:

Public Input No. 59-NFPA 13R-2016 [New Section after 6.11.5]

Ballot Results

This item has passed ballot

31 Eligible Voters

2 Not Returned

29 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Flancher, Dawn M.

Hoover, Tonya L.

Affirmative All

Asp, Roland A.

Bell, Kerry M.

Benn, Fred

Bradley, Frederick C.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

53 of 116 12/7/2016 1:13 PM

Page 55: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

Browning, Chase A.

Buuck, Daniel

Cronin, Bradford T.

Deegan, Thomas G.

Feid, Jeffrey

Haagensen, Dana R.

Isman, Kenneth E.

Klein, Marshall A.

Mathias, Daniel J.

Nickelson, David A.

O'Brian, Michael

Pilette, Maurice M.

Puchovsky, Milosh T.

Schwab, Peter T.

Skare, Eric J.

Skinner, Timothy J.

Stanley, George W.

Towler, Michael

Townley, Donald R.

Trim, Martin C. W.

Van Walraven, Ed

Victor, Terry L.

Viola, John F.

Webb, Ronald N.

Yu, Hong-Zeng

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

54 of 116 12/7/2016 1:13 PM

Page 56: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

First Revision No. 37-NFPA 13R-2016 [ Chapter 7 [Title Only] ]

Discharge Design Criteria

Submitter Information Verification

Submitter Full Name: David Hague

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 14 16:04:35 EDT 2016

Committee Statement

CommitteeStatement:

All subsections use "design." Putting this in the title of the chapter and deleting it fromsubsections simplifies the document and clarifies intent.

ResponseMessage:

Public Input No. 101-NFPA 13R-2016 [Chapter 7 [Title Only]]

Ballot Results

This item has passed ballot

31 Eligible Voters

2 Not Returned

29 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Flancher, Dawn M.

Hoover, Tonya L.

Affirmative All

Asp, Roland A.

Bell, Kerry M.

Benn, Fred

Bradley, Frederick C.

Browning, Chase A.

Buuck, Daniel

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

55 of 116 12/7/2016 1:13 PM

Page 57: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

Cronin, Bradford T.

Deegan, Thomas G.

Feid, Jeffrey

Haagensen, Dana R.

Isman, Kenneth E.

Klein, Marshall A.

Mathias, Daniel J.

Nickelson, David A.

O'Brian, Michael

Pilette, Maurice M.

Puchovsky, Milosh T.

Schwab, Peter T.

Skare, Eric J.

Skinner, Timothy J.

Stanley, George W.

Towler, Michael

Townley, Donald R.

Trim, Martin C. W.

Van Walraven, Ed

Victor, Terry L.

Viola, John F.

Webb, Ronald N.

Yu, Hong-Zeng

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

56 of 116 12/7/2016 1:13 PM

Page 58: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

First Revision No. 40-NFPA 13R-2016 [ New Section after 7.3.2 ]

7.3.3

Garages that serve only a single dwelling unit shall be considered as part of that dwelling unit.

Submitter Information Verification

Submitter Full Name: David Hague

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 14 16:10:42 EDT 2016

Committee Statement

CommitteeStatement:

A garage accessible from a single dwelling unit or from a shared hallway are no different. Theyare generally one or two car garages and the makeup of what is put in that garage is the sameregardless of how it is accessed.

ResponseMessage:

Public Input No. 63-NFPA 13R-2016 [Section No. 7.3.2]

Public Input No. 64-NFPA 13R-2016 [New Section after 7.3.2]

Public Input No. 65-NFPA 13R-2016 [Section No. 7.3.3.3]

Ballot Results

This item has passed ballot

31 Eligible Voters

2 Not Returned

29 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Flancher, Dawn M.

Hoover, Tonya L.

Affirmative All

Asp, Roland A.

Bell, Kerry M.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

57 of 116 12/7/2016 1:13 PM

Page 59: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

Benn, Fred

Bradley, Frederick C.

Browning, Chase A.

Buuck, Daniel

Cronin, Bradford T.

Deegan, Thomas G.

Feid, Jeffrey

Haagensen, Dana R.

Isman, Kenneth E.

Klein, Marshall A.

Mathias, Daniel J.

Nickelson, David A.

O'Brian, Michael

Pilette, Maurice M.

Puchovsky, Milosh T.

Schwab, Peter T.

Skare, Eric J.

Skinner, Timothy J.

Stanley, George W.

Towler, Michael

Townley, Donald R.

Trim, Martin C. W.

Van Walraven, Ed

Victor, Terry L.

Viola, John F.

Webb, Ronald N.

Yu, Hong-Zeng

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

58 of 116 12/7/2016 1:13 PM

Page 60: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

First Revision No. 41-NFPA 13R-2016 [ New Section after 7.4 ]

7.4 Attics.

7.4.1 Occupied Attics and Attics Used for Storage.

Attics that are intended for occupancy or storage shall comply with Section 7.1 , where the attic is partof the dwelling unit, or Section 7.2 , where the attic is outside of the dwelling unit.

7.4.1.1

Sprinkler temperature ratings shall comply with 6.2.3 .

7.4.2 Fuel-Fired Equipment.

Where fuel-fired equipment is installed in an attic that is not otherwise required to have sprinklers, thespace containing the fuel-fired equipment shall comply with 6.6.6.1 .

7.4.3* Other Attics.

Attics that are not required by 7.5.1 to have sprinklers shall be permitted to have protection inaccordance with one of the following.

(1) Protection complying with NFPA 13

(2) Protection using sprinklers specifically listed to provide attic protection in residential occupancies

using a discharge density of not less than 0.05 gpm/ft 2 (2.04 mm/min) and a design area of notless than four sprinklers

7.4.3.1

Sprinkler temperature ratings shall comply with 6.2.3 .

Supplemental Information

File Name Description

FR-41_A.7.4.3.docx New annex text.

Submitter Information Verification

Submitter Full Name: David Hague

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 14 16:12:27 EDT 2016

Committee Statement

CommitteeStatement:

Section 6.6.6 and 6.6.6.1 require sprinklers in attics that are intended for living or storage purposesand for attics that contain fuel-fired equipment, and it is helpful to provide guidance on attic protectionin Chapter 7 to correlate. In addition, model building codes are adding requirements for some otherattics to be protected with sprinklers or other acceptable means for protection of concealed spaces. Itis important for NFPA 13R to provide guidance on protection of attics for these situations as well. Theproposal parallels the design guidance for garages by offering an option to use not less than a 0.05gpm/sqft density and not less than a 4 sprinkler design basis. However, the minimum density and

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

59 of 116 12/7/2016 1:13 PM

Page 61: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

minimum number of sprinklers would have to be determined based on testing and a listing for thisspecific hazard, as validated by a listing agency. The second design option is necessary to state inNFPA 13R to provide an alternative to the general provisions in Section 6.6.8, which would otherwiserequire compliance with NFPA 13 as the only basis for attic sprinkler protection.

ResponseMessage:

Public Input No. 103-NFPA 13R-2016 [New Section after 7.4]

Ballot Results

This item has passed ballot

31 Eligible Voters

2 Not Returned

27 Affirmative All

1 Affirmative with Comments

1 Negative with Comments

0 Abstention

Not Returned

Flancher, Dawn M.

Hoover, Tonya L.

Affirmative All

Asp, Roland A.

Bell, Kerry M.

Benn, Fred

Bradley, Frederick C.

Browning, Chase A.

Buuck, Daniel

Cronin, Bradford T.

Feid, Jeffrey

Haagensen, Dana R.

Isman, Kenneth E.

Klein, Marshall A.

Mathias, Daniel J.

Nickelson, David A.

O'Brian, Michael

Pilette, Maurice M.

Puchovsky, Milosh T.

Skare, Eric J.

Skinner, Timothy J.

Stanley, George W.

Towler, Michael

Townley, Donald R.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

60 of 116 12/7/2016 1:13 PM

Page 62: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

Trim, Martin C. W.

Van Walraven, Ed

Victor, Terry L.

Viola, John F.

Webb, Ronald N.

Yu, Hong-Zeng

Affirmative with Comment

Schwab, Peter T.

I agree that the this language is needed to correlate with recent changes in the ICC. I also agree that if an attic isgoing to be used for storage or occupancy then it should be protected in accordance with NFPA 13. I feel that thelanguage in 7.4.1 should be changed to read "Attics that are intended for occupancy or storage shall be inaccordance with NFPA 13." The phrase "where the attic is part of the dwelling unit" or is "outside the dwelling unit"is confusing. Is it finished? If so it is another room. Also there needs to be annex language that indicates that theprescence of a scuttle hole does not mean that the attic is "intended" for storage or occupany.

Negative with Comment

Deegan, Thomas G.

There is not a product on the market that is consistent with 7.4.3(2). If a product is to be developed that providesa more efficient means of protecting certain attics, it shouldn't be limited by the criteria included in 7.4.3(2). Ibelieve that the wording after "occupancies" should be eliminated even though the limiting phrase "shall bepermitted to have" is included above.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

61 of 116 12/7/2016 1:13 PM

Page 63: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

First Revision No. 42-NFPA 13R-2016 [ Section No. 7.4 ]

7.5* Combustible Concealed Spaces.

Where unsprinklered combustible concealed spaces are present in a building residential occupancy , the

design area shall not be required to be increased to 3000 ft2 (279 m2) or any other value due to theexistence of the unsprinklered concealed spaces, regardless of the type of sprinklers used and whetherthe area is inside or outside of a dwelling unit.

Supplemental Information

File Name Description

FR-42_A.7.5.docx New annex text.

Submitter Information Verification

Submitter Full Name: David Hague

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 14 16:20:07 EDT 2016

Committee Statement

Committee Statement: The reference to building should be occupancy.

Response Message:

Public Input No. 62-NFPA 13R-2016 [Section No. 7.4]

Ballot Results

This item has passed ballot

31 Eligible Voters

2 Not Returned

29 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Flancher, Dawn M.

Hoover, Tonya L.

Affirmative All

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

62 of 116 12/7/2016 1:13 PM

Page 64: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

Asp, Roland A.

Bell, Kerry M.

Benn, Fred

Bradley, Frederick C.

Browning, Chase A.

Buuck, Daniel

Cronin, Bradford T.

Deegan, Thomas G.

Feid, Jeffrey

Haagensen, Dana R.

Isman, Kenneth E.

Klein, Marshall A.

Mathias, Daniel J.

Nickelson, David A.

O'Brian, Michael

Pilette, Maurice M.

Puchovsky, Milosh T.

Schwab, Peter T.

Skare, Eric J.

Skinner, Timothy J.

Stanley, George W.

Towler, Michael

Townley, Donald R.

Trim, Martin C. W.

Van Walraven, Ed

Victor, Terry L.

Viola, John F.

Webb, Ronald N.

Yu, Hong-Zeng

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

63 of 116 12/7/2016 1:13 PM

Page 65: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

First Revision No. 43-NFPA 13R-2016 [ Section No. 8.1.7 ]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

64 of 116 12/7/2016 1:13 PM

Page 66: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

8.1.7

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

65 of 116 12/7/2016 1:13 PM

Page 67: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

Working plans shall be drawn to an indicated scale, on sheets of uniform size, with a plan of each floor,and shall show those items from the following list that pertain to the design of the system:

(1) Project name

(2) Location, including street address

(3) Point of compass

Ceiling construction

(4) Full-height cross-section or schematic diagram, including structural member information, if requiredfor clarity, and including ceiling construction and method of protection for nonmetallic piping

(5) Ceiling/roof height and slopes not shown in the full-height cross section

(6) Location of partitions and fire walls

(7) Location and size of concealed spaces, attics, closets, and bathrooms

(8) Area per floor

(9) Any small enclosures in which no sprinklers are to be installed

(10) Size of the city main in the street and the city main test results including elevation of the test hydrant

(11) Make, manufacturer, type, temperature rating, sprinkler identification number, and nominal k-factor ofthe sprinkler

(12) Type and location of high-temperature sprinklers

(13) Number of sprinklers on each riser, per floor

(14) Type and location of alarm bells

(15) Type of pipe and fittings

(16) Pipe type and schedule of wall thickness

(17) Type of protection for nonmetallic pipe

(18) Location and size of riser nipples

(19) Types of fittings and joints and the locations of all welds and bends

(20) Types and locations of hangers, sleeves, and braces, and methods of securing sprinklers, whereapplicable

(21) All control valves, check valves, drain pipes, and test connections

(22) Underground pipe size, length, location, weight, material, and point of connection to the city main;type of valves, meters, and valve pits; and depth at which the top of the pipe is laid below grade

(23) Name and address of the contractor

(24) Nominal pipe size and lengths

(25) Where the equipment is to be installed as an addition to an existing system, enough of the existingsystem indicated on the plans to make all conditions clear

(26) A graphic representation of the scale used on all plans

(27) Hydraulic reference points shown on the plan that correspond with comparable reference points onthe hydraulic calculation sheets

(28) The minimum rate of water application and the design area of water application

(29) The total quantity of water and the pressure required noted at a common reference point for eachsystem

(30) Relative elevations of sprinklers, junction points, and supply or reference points

(31) Information about backflow preventers (e.g., manufacturer, size, type)

(32) Information about antifreeze solution used (e.g., type and amount)

(33) Size and location of hydrants, showing size and number of outlets; , including any static and residualhydrants that were used in flow tests shall be shown

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

66 of 116 12/7/2016 1:13 PM

Page 68: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

(34) Size, location, and piping arrangement of fire department connections

(35) Location of fuel-fired equipment and heating and air-conditioning equipment

(36) Location of closets on exterior balconies, and any doors or penetration between the closet and thedwelling unit

(37) Edition year of NFPA 13R to which the sprinkler system is designed

Submitter Information Verification

Submitter Full Name: David Hague

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 14 16:39:24 EDT 2016

Committee Statement

Committee Statement: Ceiling construction is found in the full height cross section. This change mirrors NFPA 13

Response Message:

Public Input No. 17-NFPA 13R-2016 [Section No. 8.1.7]

Public Input No. 16-NFPA 13R-2016 [Section No. 8.1.7]

Ballot Results

This item has passed ballot

31 Eligible Voters

2 Not Returned

28 Affirmative All

1 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Flancher, Dawn M.

Hoover, Tonya L.

Affirmative All

Asp, Roland A.

Bell, Kerry M.

Benn, Fred

Bradley, Frederick C.

Browning, Chase A.

Buuck, Daniel

Cronin, Bradford T.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

67 of 116 12/7/2016 1:13 PM

Page 69: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

Deegan, Thomas G.

Feid, Jeffrey

Haagensen, Dana R.

Isman, Kenneth E.

Klein, Marshall A.

Mathias, Daniel J.

Nickelson, David A.

O'Brian, Michael

Pilette, Maurice M.

Puchovsky, Milosh T.

Schwab, Peter T.

Skare, Eric J.

Skinner, Timothy J.

Stanley, George W.

Townley, Donald R.

Trim, Martin C. W.

Van Walraven, Ed

Victor, Terry L.

Viola, John F.

Webb, Ronald N.

Yu, Hong-Zeng

Affirmative with Comment

Towler, Michael

Further review/discussion to remove redundant wording (i.e. lines 15, 16, and 17).

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

68 of 116 12/7/2016 1:13 PM

Page 70: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

First Revision No. 52-NFPA 13R-2016 [ Chapter 9 ]

Chapter 9 Water Supply Supplies

9.1 Automatic. Number of Supplies.

Every automatic sprinkler system shall have at least one automatic water supply.

9.2 Minimum. Capacity.

Water supplies shall be capable of providing the required flow and pressure for all design areasdetermined using the requirements of Chapter 7 and the hydraulic procedures located in NFPA 13 .

9.2.1

The water supply shall be capable of supplying the system demand for at least 30 minutes. (See 7.1.1.3.)

9.3 Source.

The water supply source shall be one of the following:

A connection to a reliable waterworks system with or without a pump, as required

An elevated tank

A pressure tank installed in accordance with NFPA 13 and NFPA 22

A stored water source with an automatically operated fire pump

9.4 Fire Pump.

Where a fire pump is installed, the fire pump shall be installed in accordance with NFPA 20 .

9.4 Water Tanks.

Where a water tank is installed, the water tank shall be installed in accordance with NFPA 22 .

9.3* Domestic Demand.

9.3.1

Domestic For systems with common domestic/fire mains serving more than one dwelling unit, domesticdemand for the building being calculated shall be included as part of the overall system demand forsystems with common domestic/fire mains where no unless provisions are made to prevent the domesticwaterflow upon sprinkler system activation.

9.3.2

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

69 of 116 12/7/2016 1:13 PM

Page 71: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

Domestic demand shall be based upon Table 9.3.2(a) and Table 9.3.2(b) .

Table 9.3.2(a) Fixture Load Values

Facility Type Unit

Private Facilities (those within individual dwelling units)

Bathroom group with flush tank (including lavatory, water closet, and bathtub with shower) 6

Bathroom group with flush valve 8

Bathtub 2

Dishwasher 1

Kitchen sink 2

Laundry trays 3

Lavatory 1

Shower stall 2

Washing machine 2

Water closet with flush valve 6

Water closet with flush tank 3

Public Facilities

Bathtub 4

Drinking fountain 0

Kitchen sink 4

Lavatory 2

Service sink 3

Shower head 4

Urinal with 1 in. (25 mm) flush valve 10

Urinal with 3 ⁄4 in. (20 mm) flush valve 5

Urinal with flush tank 3

Washing machine [8 lb (3.63 kg)] 3

Washing machine [16 lb (7.26 kg)] 4

Water closet with flush valve 10

Water closet with flush tank 5

Table 9.3.2(b) Total Estimated Domestic Demand

Total Demand

Total Fixture Load Units[from Table 9.3.3(a)]

For Systems withPredominately Flush Tanks

For Systems withPredominately Load Units

gpm L/min gpm L/min

1 3 11.5 — —

2 5 19 — —

5 10 38 15 57

10 15 57 25 95

20 20 76 35 130

35 25 95 45 170

50 30 115 50 190

70 35 130 60 225

100 45 170 70 265

150 55 210 80 305

200 65 245 90 340

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

70 of 116 12/7/2016 1:13 PM

Page 72: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

Total Demand

Total Fixture Load Units[from Table 9.3.3(a)]

For Systems withPredominately Flush Tanks

For Systems withPredominately Load Units

250 75 285 100 380

350 100 380 125 475

500 125 475 150 570

750 175 660 175 660

1000 200 755 200 755

1500 275 1040 275 1040

2000 325 1230 325 1230

3500 500 1900 500 1900

9.3.2.1

Interpolation of Table 9.3.2(b) shall be allowed when calculating domestic demand.

9.3.3

Where more demanding domestic demands are specified, they shall be used.

9.3.4

Domestic demand shall be added to the hydraulic calculations at the point the piping becomescombined or common.

9.3.5

The flow and pressure of a public water supply shall be determined from waterflow test data or otherapproved method.

9.3.5.1

Water supply fluctuations must be addressed in the design of sprinkler systems, as required by theauthority having jurisdiction.

9.3.5.2

Safety factors must be addressed in the design of sprinkler systems, as required by the authority havingjurisdiction.

9.4 Connection from Waterworks System.

9.4.1

The requirements of the public health authority having jurisdiction shall be determined and followed.

9.4.2*

Where equipment is installed to guard against possible contamination of the public water system, suchequipment and devices shall be listed for fire protection service.

9.5 Types.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

71 of 116 12/7/2016 1:13 PM

Page 73: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

9.5.1*

Water supplies for sprinkler systems shall be one of the following or any combination thereof:

(1) A connection to an approved public or private waterworks system in accordance with Section9.6 .

(2) A connection including a fire pump in accordance with Section 9.7 .

(3) A connection to a water storage tank at grade or below grade in accordance with NFPA 22 andfilled from an approved source.

(4) A connection to a pressure tank in accordance with NFPA 13 and NFPA 22 and filled from anapproved source.

(5) A connection to a gravity tank in accordance with NFPA 22 and filled from an approved source.

(6) A penstock, flume, river, lake, pond, or reservoir in accordance with Section 9.8 .

(7) A source of recycled or reclaimed water where the building owner (or their agent) has analyzed thesource of the water and the treatment process (if any) that the water undergoes before beingmade available to the sprinkler system and determined that any materials, chemicals, orcontaminants in the water will not be detrimental to the components of the sprinkler system itcomes in contact with.

9.6 Connections to Waterworks Systems.

9.6.1

A connection to a reliable waterworks system shall be an acceptable water supply source.

9.6.2

The volume and pressure of a public or private water supply shall be determined from waterflow testdata or other approved method.

9.6.2.1

Where a waterflow test is used for the purposes of system design, the test shall be conducted no morethan 12 months prior to a working plan submittal unless otherwise approved by the authority havingjurisdiction.

9.7 Fire Pump.

A single automatically controlled fire pump in accordance with NFPA 20 shall be an acceptable watersupply source.

9.8 Penstocks, Flumes, Rivers, Lakes, or Reservoirs.

Water supply connections from penstocks, flumes, rivers, lakes, or reservoirs shall be arranged to avoidmud and sediment and shall be provided with approved double removable screens or approvedstrainers installed in an approved manner.

9.9 Non–Fire Protection Connections.

Sprinkler systems with non–fire protection connections shall not be permitted.

Supplemental Information

File Name Description

NFPA_13R_FR-52.docx Chapter 9 re-write. For Staff Use

FR-52_A.9.4.2.docx New annex text.

Submitter Information Verification

Submitter Full Name: David Hague

Organization: [ Not Specified ]

Street Address:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

72 of 116 12/7/2016 1:13 PM

Page 74: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

City:

State:

Zip:

Submittal Date: Wed Jul 27 15:16:56 EDT 2016

Committee Statement

CommitteeStatement:

This chapter needed some rework. I tried to make it more parallel NFPA 13 in regards to watersupplies. Domestic demand is required to be calculated but there were never defined values to use(only annex). This input brings those tables into the body of the standard. The annex language wascleaned up because it implied that a fire pump could supply both domestic and fire. The new a.9.5.1clarifies when a pump can supply both.

ResponseMessage:

Public Input No. 42-NFPA 13R-2016 [Section No. 9.6]

Public Input No. 35-NFPA 13R-2016 [New Section after 9.3]

Public Input No. 32-NFPA 13R-2016 [Chapter 9]

Ballot Results

This item has passed ballot

31 Eligible Voters

2 Not Returned

28 Affirmative All

1 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Flancher, Dawn M.

Hoover, Tonya L.

Affirmative All

Asp, Roland A.

Bell, Kerry M.

Benn, Fred

Bradley, Frederick C.

Browning, Chase A.

Buuck, Daniel

Cronin, Bradford T.

Deegan, Thomas G.

Feid, Jeffrey

Haagensen, Dana R.

Isman, Kenneth E.

Mathias, Daniel J.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

73 of 116 12/7/2016 1:13 PM

Page 75: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

Nickelson, David A.

O'Brian, Michael

Pilette, Maurice M.

Puchovsky, Milosh T.

Schwab, Peter T.

Skare, Eric J.

Skinner, Timothy J.

Stanley, George W.

Towler, Michael

Townley, Donald R.

Trim, Martin C. W.

Van Walraven, Ed

Victor, Terry L.

Viola, John F.

Webb, Ronald N.

Yu, Hong-Zeng

Affirmative with Comment

Klein, Marshall A.

I distinctly remember at the First Draft Meeting we had discussion about moving the old Fixture Load Values(Table A.9.6(a)) and Total Estimated Domestic Demand (Table A.9.6(b)) from the Annex to the body of the Code.We discussed that these Tables were from more than 30 years ago and that the recent Model Plumbing Codeshave revised similar requirements in their Codes to reflect modern, more energy and water saving efficient fixtureloads and water demands. We agreed that moving these Tables at this time into the body of the Code was not agood move until we reviewed the latest changes in the Model Plumbing Codes on this issue. We voted on deletingthe proposed new Section 9.3.2 and it passed. However on the ballot this Section is still shown as being part ofthe First Revision. Staff needs to recheck its records of the First Draft Meeting and revise FR #52 without includingSection 9.3.2 since it was the intent of the Committee to leave these Tables in the Annex.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

74 of 116 12/7/2016 1:13 PM

Page 76: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

First Revision No. 28-NFPA 13R-2016 [ Section No. 10.1.2 ]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

75 of 116 12/7/2016 1:13 PM

Page 77: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

10.1.2

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

76 of 116 12/7/2016 1:13 PM

Page 78: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

The installer shall complete the contractor’s material and test certificate(s) as shown in Figure 10.1.2 priorto asking for approval of the installation.

Figure 10.1.2 Contractor’s Material and Test Certificate for Aboveground Piping. [13:Figure 25.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

77 of 116 12/7/2016 1:13 PM

Page 79: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

78 of 116 12/7/2016 1:13 PM

Page 80: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

Submitter Information Verification

Submitter Full Name: David Hague

Organization: [ Not Specified ]

Street Address:

City:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

79 of 116 12/7/2016 1:13 PM

Page 81: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

State:

Zip:

Submittal Date: Thu Jul 14 15:10:42 EDT 2016

Committee Statement

CommitteeStatement:

Change the test certificate to state "Have copies of the following been provided to the owner orowner's representative". Currently it states Have copies of the following been left on thepremises.

Several AHJ's in South Florida have been requiring a copy of NFPA 25 to be left in each buildingon apartment complexes.

ResponseMessage:

Public Input No. 20-NFPA 13R-2016 [Section No. 10.1.2]

Ballot Results

This item has passed ballot

31 Eligible Voters

2 Not Returned

29 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Flancher, Dawn M.

Hoover, Tonya L.

Affirmative All

Asp, Roland A.

Bell, Kerry M.

Benn, Fred

Bradley, Frederick C.

Browning, Chase A.

Buuck, Daniel

Cronin, Bradford T.

Deegan, Thomas G.

Feid, Jeffrey

Haagensen, Dana R.

Isman, Kenneth E.

Klein, Marshall A.

Mathias, Daniel J.

Nickelson, David A.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

80 of 116 12/7/2016 1:13 PM

Page 82: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

O'Brian, Michael

Pilette, Maurice M.

Puchovsky, Milosh T.

Schwab, Peter T.

Skare, Eric J.

Skinner, Timothy J.

Stanley, George W.

Towler, Michael

Townley, Donald R.

Trim, Martin C. W.

Van Walraven, Ed

Victor, Terry L.

Viola, John F.

Webb, Ronald N.

Yu, Hong-Zeng

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

81 of 116 12/7/2016 1:13 PM

Page 83: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

First Revision No. 46-NFPA 13R-2016 [ Section No. 11.1.1 ]

11.1.1*

A supply of at least six spare sprinklers shall be maintained on the premises so that any sprinklers thathave operated or been damaged in any way can be promptly replaced. The quantity of spare sprinklersmaintained shall be as specified in 11.1.5 .

Submitter Information Verification

Submitter Full Name: David Hague

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 14 17:59:25 EDT 2016

Committee Statement

CommitteeStatement:

Section 11.1.5 specifies the various numbers of spare sprinklers required, based on the size ofthe system. Rather than state a minimum number, it would be cleaner to refer to the section thatspecifies how many are to be provided.

ResponseMessage:

Public Input No. 74-NFPA 13R-2016 [Section No. 11.1.1]

Ballot Results

This item has passed ballot

31 Eligible Voters

2 Not Returned

29 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Flancher, Dawn M.

Hoover, Tonya L.

Affirmative All

Asp, Roland A.

Bell, Kerry M.

Benn, Fred

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

82 of 116 12/7/2016 1:13 PM

Page 84: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

Bradley, Frederick C.

Browning, Chase A.

Buuck, Daniel

Cronin, Bradford T.

Deegan, Thomas G.

Feid, Jeffrey

Haagensen, Dana R.

Isman, Kenneth E.

Klein, Marshall A.

Mathias, Daniel J.

Nickelson, David A.

O'Brian, Michael

Pilette, Maurice M.

Puchovsky, Milosh T.

Schwab, Peter T.

Skare, Eric J.

Skinner, Timothy J.

Stanley, George W.

Towler, Michael

Townley, Donald R.

Trim, Martin C. W.

Van Walraven, Ed

Victor, Terry L.

Viola, John F.

Webb, Ronald N.

Yu, Hong-Zeng

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

83 of 116 12/7/2016 1:13 PM

Page 85: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

First Revision No. 45-NFPA 13R-2016 [ Section No. 11.1.5 ]

11.1.5

The stock of spare sprinklers shall include all types and ratings installed and shall be as follows:

(1) For systems serving a single-family dwelling — no fewer than two sprinklers

(2) For protected facilities having under 300 sprinklers — no fewer than six sprinklers

(3) For protected facilities having 300 to 1000 sprinklers — no fewer than 12 sprinklers

(4) For protected facilities having over 1000 sprinklers — no fewer than 24 sprinklers

Submitter Information Verification

Submitter Full Name: David Hague

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 14 17:56:32 EDT 2016

Committee Statement

CommitteeStatement:

It has become quite common to have four-story single-family dwellings and four-story townhomes,which the International Building Code requires sprinkler design in accordance with NFPA 13R inorder to have the fourth story. It becomes extremely expensive and over-burdensome for eachdwelling unit to have six spare sprinklers. From almost all aspects other than sprinkler hydraulicdesign, these dwellings are practically identical to homes protected by sprinkler systems designed byNFPA 13D, which requires no spare sprinklers. By minimizing the required number of sparesprinklers required for four-story single-family dwellings, the cost to the home buyers is therebyreduced.

ResponseMessage:

Public Input No. 75-NFPA 13R-2016 [Section No. 11.1.5]

Ballot Results

This item has passed ballot

31 Eligible Voters

2 Not Returned

29 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Flancher, Dawn M.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

84 of 116 12/7/2016 1:13 PM

Page 86: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

Hoover, Tonya L.

Affirmative All

Asp, Roland A.

Bell, Kerry M.

Benn, Fred

Bradley, Frederick C.

Browning, Chase A.

Buuck, Daniel

Cronin, Bradford T.

Deegan, Thomas G.

Feid, Jeffrey

Haagensen, Dana R.

Isman, Kenneth E.

Klein, Marshall A.

Mathias, Daniel J.

Nickelson, David A.

O'Brian, Michael

Pilette, Maurice M.

Puchovsky, Milosh T.

Schwab, Peter T.

Skare, Eric J.

Skinner, Timothy J.

Stanley, George W.

Towler, Michael

Townley, Donald R.

Trim, Martin C. W.

Van Walraven, Ed

Victor, Terry L.

Viola, John F.

Webb, Ronald N.

Yu, Hong-Zeng

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

85 of 116 12/7/2016 1:13 PM

Page 87: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

First Revision No. 30-NFPA 13R-2016 [ Section No. A.1.1 ]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

86 of 116 12/7/2016 1:13 PM

Page 88: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

A.1.1

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

87 of 116 12/7/2016 1:13 PM

Page 89: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

NFPA 13R is appropriate for use as an alternative to NFPA 13 only in those residential occupancies, asdefined in this standard, up to and including four aboveground stories in height., and limited to buildingsthat are It should be noted that model building codes contain special allowances for pedestal orpodium-style buildings, which permit the story height for structures above the pedestal to be measuredfrom the top surface of the pedestal, rather than from grade plane, and it is the intent of NFPA 13R tofollow this model building code method for determining the number of stories. Accordingly, it is possiblefor a four-story residential structure to be within the scope of NFPA 13R even when that structure isconstructed on top of a one-story pedestal. However, where this is allowed, model building codes willrequire the pedestal portion to be constructed using Type I construction, and the pedestal portion will berequired to be protected by an NFPA 13–compliant sprinkler system.

Regardless of whether a building does or does not involve a pedestal, NFPA 13R systems are alwayslimited to structures that do not exceed 60 ft (18 m) or less in height above grade plane, which is . Notethat model building codes do not allow building height to be measured from the top of a pedestal. Thatallowance only applies to determining the number of stories. The 60-foot overall height limit is consistentwith limits established by model building codes for buildings of Type V construction. The height of abuilding structure above grade plane is determined by model building codes, which base the height on theaverage height of the highest roof surface above grade plane. For further information on the buildingheight story limits, see model building codes.

Buildings that contain multiple occupancies (either separated or nonseparated), accessory occupancies,or incidental uses are often subject to special rules that may might restrict the use of NFPA 13R. Refer tothe adopted building code to determine whether such restrictions are applicable.

The criteria in this standard are based on full-scale fire tests of rooms containing typical furnishings foundin residential living rooms, kitchens, and bedrooms. The furnishings were arranged as typically found indwelling units in a manner similar to that shown in Figure A.1.1(a), Figure A.1.1(b), and Figure A.1.1(c) .Sixty full-scale fire tests were conducted in a two-story dwelling in Los Angeles, California, and 16 testswere conducted in a 14 ft (4.3 m) wide mobile home in Charlotte, North Carolina. Sprinkler systemsdesigned and installed according to this standard are expected to prevent flashover within thecompartment of origin where sprinklers are installed in the compartment. A sprinkler system designed andinstalled according to this standard cannot, however, be expected to completely control a fire involving fuel

loads that are significantly higher than average for dwelling units [10 lb/ft2 (49 kg/m2)], configurations offuels other than those with typical residential occupancies, or conditions where the interior finish has anunusually high flame spread index (i.e., greater than 225).

To be effective, sprinkler systems installed in accordance with this standard need to open the sprinklersclosest to the fire before the fire exceeds the ability of the sprinkler discharge to extinguish or control thefire. Conditions that allow the fire to grow beyond that point before sprinkler activation or that interfere withthe quality of water distribution can produce conditions beyond the capabilities of the sprinkler systemdescribed in this standard. Unusually high ceilings or ceiling configurations that tend to divert the rising hotgases from sprinkler locations or change the sprinkler discharge pattern from its standard pattern canproduce fire conditions that cannot be extinguished or controlled by the systems described in thisstandard.

NFPA 13R references NFPA 13 in many aspects (i.e., hanging and bracing, design densities and spacingoutside of dwelling unit, painting and finish of sprinklers, welding, etc. and so on ). If this standard does notspecifically address a situation, NFPA 13 is a good resource that can be utilized by the installer and theauthority having jurisdiction for a solution. It is not the intent of this standard to require compliance withNFPA 13 when NFPA 13R is silent on a subject. Only AHJ approval should be required.

Figure A.1.1(a) Bedroom.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

88 of 116 12/7/2016 1:13 PM

Page 90: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

Figure A.1.1(b) Manufactured Home Bedroom.

Figure A.1.1(c) Living Room.

Submitter Information Verification

Submitter Full Name: David Hague

Organization: [ Not Specified ]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

89 of 116 12/7/2016 1:13 PM

Page 91: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 14 15:41:04 EDT 2016

Committee Statement

CommitteeStatement:

Clarifies application of NFPA 13R with respect to the height and story limits in modelbuilding codes.

Response Message:

Public Input No. 38-NFPA 13R-2016 [Section No. A.1.1]

Public Input No. 5-NFPA 13R-2015 [New Section after A.1.2]

Ballot Results

This item has passed ballot

31 Eligible Voters

2 Not Returned

29 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Flancher, Dawn M.

Hoover, Tonya L.

Affirmative All

Asp, Roland A.

Bell, Kerry M.

Benn, Fred

Bradley, Frederick C.

Browning, Chase A.

Buuck, Daniel

Cronin, Bradford T.

Deegan, Thomas G.

Feid, Jeffrey

Haagensen, Dana R.

Isman, Kenneth E.

Klein, Marshall A.

Mathias, Daniel J.

Nickelson, David A.

O'Brian, Michael

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

90 of 116 12/7/2016 1:13 PM

Page 92: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

Pilette, Maurice M.

Puchovsky, Milosh T.

Schwab, Peter T.

Skare, Eric J.

Skinner, Timothy J.

Stanley, George W.

Towler, Michael

Townley, Donald R.

Trim, Martin C. W.

Van Walraven, Ed

Victor, Terry L.

Viola, John F.

Webb, Ronald N.

Yu, Hong-Zeng

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

91 of 116 12/7/2016 1:13 PM

Page 93: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

First Revision No. 31-NFPA 13R-2016 [ Section No. A.1.2 ]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

92 of 116 12/7/2016 1:13 PM

Page 94: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

A.1.2

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

93 of 116 12/7/2016 1:13 PM

Page 95: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

Various levels of sprinkler protection are available to provide life safety and property protection. Thisstandard is designed to provide a high, but not absolute, level of life safety and a lesser level of propertyprotection. Greater protection to both life and property could be achieved by sprinklering all areas inaccordance with NFPA 13 , which permits the use of residential sprinklers in residential areas. both lifesafety and property protection, but to a lesser degree than would be achieved by using NFPA 13 .

This standard recommends, but does not require, sprinklering of all areas in the building; it permitssprinklers to be omitted in certain areas. These areas have been proved by NFPA statistics to be thosewhere the incidence of life loss from fires in residential occupancies is low. Such an approach provides areasonable degree of fire safety. (See Table A.1.2 for deaths and injuries in multifamily residentialbuildings.)

It should be recognized that the omission of sprinklers from certain areas could result in the developmentof untenable conditions in adjacent spaces. Where evacuation times could be delayed, additional sprinklerprotection and other fire protection features, such as detection and compartmentation, could benecessary.

Table A.1.2 Fires and Associated Deaths and Injuries in Apartments by Area of Origin; Annual Average of1986–1990 Structure Fires Reported to U.S. Fire Departments

Area of OriginCivilianDeaths

CivilianPercent

Fires Percent Injuries Percent

Bedroom 309 33.9 17,960 15.8 1,714 27.2

Living room, family room, or den 308 33.8 10,500 9.3 1,272 20.2

Kitchen 114 12.5 46,900 41.4 1,973 31.2

Interior stairway 29 3.2 1,040 0.9 91 1.4

Hallway or corridor 23 2.6 3,130 2.8 165 2.6

Exterior balcony or open porch 17 1.8 1,880 1.7 69 1.1

Dining room 10 1.1 800 0.7 69 1.1

Closet 9 1.0 2,120 1.9 116 1.8

Multiple areas 9 1.0 780 0.7 38 0.6

Tool room or other supply storageroom or area

8 0.9 1,250 1.1 53 0.8

Unclassified area 8 0.9 480 0.4 29 0.5

Exterior stairway 8 0.8 870 0.8 22 0.4

Bathroom 7 0.7 2,510 2.2 101 1.6

Heating equipment room or area 6 0.6 2,510 2.2 75 1.2

Exterior wall surface 5 0.5 2,150 1.9 26 0.4

Laundry room or area 4 0.4 3,380 3.0 89 1.4

Crawl space or substructure space 4 0.4 1,490 1.3 62 1.0

Wall assembly or concealed space 3 0.4 1,020 0.9 21 0.3

Attic or ceiling/roof assembly orconcealed space

3 0.3 1,100 1.0 18 0.3

Ceiling/floor assembly or concealedspace

3 0.3 560 0.5 18 0.3

Garage or carport* 3 0.3 1,290 1.1 36 0.6

Lobby or entranceway 3 0.3 670 0.6 31 0.5

Unclassified structural area 3 0.3 520 0.5 32 0.5

Unclassified storage area 3 0.3 430 0.4 22 0.3

Unclassified function area 3 0.3 250 0.2 13 0.2

Laboratory 2 0.3 80 0.1 3 0.0

Elevator or dumbwaiter 1 0.2 220 0.2 4 0.1

Sales or showroom area 1 0.2 110 0.1 3 0.1

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

94 of 116 12/7/2016 1:13 PM

Page 96: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

Area of OriginCivilianDeaths

CivilianPercent

Fires Percent Injuries Percent

Exterior roof surface 1 0.1 1,040 0.9 15 0.2

Unclassified means of egress 1 0.1 180 0.2 6 0.1

Office 1 0.1 120 0.1 4 0.1

Chimney 1 0.1 980 0.9 2 0.0

Personal service area 1 0.1 40 0.0 4 0.1

Library 1 0.1 10 0.0 0 0.0

Other known area 2 0.2 5,000 4.4 115 1.8

 Totals 912 100.0 113,390 100.0 6,313 100.0

Note: Fires are estimated to the nearest 10; civilian deaths and injuries are estimated to the nearest 1.

*Does not include dwelling garages coded as a separate property.

Source: 1986–1990 NFIRS and NFPA survey.

Submitter Information Verification

Submitter Full Name: David Hague

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 14 15:43:27 EDT 2016

Committee Statement

CommitteeStatement:

Clarification of intent. NFPA 13R is both a life-safety and property-protection standard. It isrecognized for property protection by model building codes, which grant construction incentives tobuildings protected by NFPA 13R systems, and sprinklers required for protection of balconies andgarages are primarily provided for property protection. Certainly, NFPA 13 provides an increasedlevel of protection for both life-safety and property protection, and the proposed revision makes thisclear.

ResponseMessage:

Public Input No. 106-NFPA 13R-2016 [Section No. A.1.2]

Ballot Results

This item has passed ballot

31 Eligible Voters

2 Not Returned

29 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

95 of 116 12/7/2016 1:13 PM

Page 97: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

Flancher, Dawn M.

Hoover, Tonya L.

Affirmative All

Asp, Roland A.

Bell, Kerry M.

Benn, Fred

Bradley, Frederick C.

Browning, Chase A.

Buuck, Daniel

Cronin, Bradford T.

Deegan, Thomas G.

Feid, Jeffrey

Haagensen, Dana R.

Isman, Kenneth E.

Klein, Marshall A.

Mathias, Daniel J.

Nickelson, David A.

O'Brian, Michael

Pilette, Maurice M.

Puchovsky, Milosh T.

Schwab, Peter T.

Skare, Eric J.

Skinner, Timothy J.

Stanley, George W.

Towler, Michael

Townley, Donald R.

Trim, Martin C. W.

Van Walraven, Ed

Victor, Terry L.

Viola, John F.

Webb, Ronald N.

Yu, Hong-Zeng

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

96 of 116 12/7/2016 1:13 PM

Page 98: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

First Revision No. 33-NFPA 13R-2016 [ Section No. A.3.3.1 ]

A.3.3.1 Bathroom.

A room is still considered a bathroom if it contains just a toilet. Additionally, two bathrooms can be that areadjacent to each other and are considered separate rooms, provided they are enclosed with the requiredlevel of construction. .

Submitter Information Verification

Submitter Full Name: David Hague

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 14 15:48:18 EDT 2016

Committee Statement

CommitteeStatement:

The requirement that the bathrooms "are enclosed with the required level of construction" shouldbe removed as the 20 minute thermal barrier behind fixtures was no longer required beginning inthe 2007 NFPA 13R. As long as each adjacent bathroom meets the definition of a bathroom, theyshould be considered separate rooms.

ResponseMessage:

Public Input No. 110-NFPA 13R-2016 [Section No. A.3.3.1]

Ballot Results

This item has passed ballot

31 Eligible Voters

2 Not Returned

28 Affirmative All

1 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Flancher, Dawn M.

Hoover, Tonya L.

Affirmative All

Asp, Roland A.

Bell, Kerry M.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

97 of 116 12/7/2016 1:13 PM

Page 99: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

Benn, Fred

Bradley, Frederick C.

Browning, Chase A.

Buuck, Daniel

Cronin, Bradford T.

Deegan, Thomas G.

Feid, Jeffrey

Haagensen, Dana R.

Isman, Kenneth E.

Klein, Marshall A.

Mathias, Daniel J.

Nickelson, David A.

O'Brian, Michael

Pilette, Maurice M.

Puchovsky, Milosh T.

Skare, Eric J.

Skinner, Timothy J.

Stanley, George W.

Towler, Michael

Townley, Donald R.

Trim, Martin C. W.

Van Walraven, Ed

Victor, Terry L.

Viola, John F.

Webb, Ronald N.

Yu, Hong-Zeng

Affirmative with Comment

Schwab, Peter T.

This should be correlated with NFPA 13D and NFPA 13.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

98 of 116 12/7/2016 1:13 PM

Page 100: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

First Revision No. 6-NFPA 13R-2016 [ Section No. A.5.1.1.1 ]

A.5.1.1.1

Compatible thread sealant or Teflon tape can be used in a CPVC sprinkler head adapter. However, acombination of the two cannot be used together. The manufacturer of the sprinkler head adapter haslisted installation instructions that must be followed for each sprinkler head adapter used.

Submitter Information Verification

Submitter Full Name: David Hague

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 14 12:14:19 EDT 2016

Committee Statement

Committee Statement: Remove the term "head". NFPA does not define a sprinkler head, only a sprinkler.

Response Message:

Public Input No. 10-NFPA 13R-2016 [Section No. A.5.1.1.1]

Ballot Results

This item has passed ballot

31 Eligible Voters

2 Not Returned

29 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Flancher, Dawn M.

Hoover, Tonya L.

Affirmative All

Asp, Roland A.

Bell, Kerry M.

Benn, Fred

Bradley, Frederick C.

Browning, Chase A.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

99 of 116 12/7/2016 1:13 PM

Page 101: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

Buuck, Daniel

Cronin, Bradford T.

Deegan, Thomas G.

Feid, Jeffrey

Haagensen, Dana R.

Isman, Kenneth E.

Klein, Marshall A.

Mathias, Daniel J.

Nickelson, David A.

O'Brian, Michael

Pilette, Maurice M.

Puchovsky, Milosh T.

Schwab, Peter T.

Skare, Eric J.

Skinner, Timothy J.

Stanley, George W.

Towler, Michael

Townley, Donald R.

Trim, Martin C. W.

Van Walraven, Ed

Victor, Terry L.

Viola, John F.

Webb, Ronald N.

Yu, Hong-Zeng

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

100 of 116 12/7/2016 1:13 PM

Page 102: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

First Revision No. 25-NFPA 13R-2016 [ Section No. A.6.6.2 ]

A.6.6.2

A room is still considered a bathroom if it contains just a toilet. Additionally, two bathrooms can be that areadjacent to each other and are considered separate rooms, provided they are enclosed with the requiredlevel of construction or compartments .

Submitter Information Verification

Submitter Full Name: David Hague

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 14 14:55:17 EDT 2016

Committee Statement

CommitteeStatement:

The requirement that the bathrooms "are enclosed with the required level of construction" shouldbe removed as the 20 minute thermal barrier behind fixtures was no longer required beginning inthe 2007 NFPA 13R. As long as each adjacent bathroom meets the definition of a bathroom, theyshould be considered separate rooms.

ResponseMessage:

Public Input No. 112-NFPA 13R-2016 [Section No. A.6.6.2]

Ballot Results

This item has passed ballot

31 Eligible Voters

2 Not Returned

29 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Flancher, Dawn M.

Hoover, Tonya L.

Affirmative All

Asp, Roland A.

Bell, Kerry M.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

101 of 116 12/7/2016 1:13 PM

Page 103: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

Benn, Fred

Bradley, Frederick C.

Browning, Chase A.

Buuck, Daniel

Cronin, Bradford T.

Deegan, Thomas G.

Feid, Jeffrey

Haagensen, Dana R.

Isman, Kenneth E.

Klein, Marshall A.

Mathias, Daniel J.

Nickelson, David A.

O'Brian, Michael

Pilette, Maurice M.

Puchovsky, Milosh T.

Schwab, Peter T.

Skare, Eric J.

Skinner, Timothy J.

Stanley, George W.

Towler, Michael

Townley, Donald R.

Trim, Martin C. W.

Van Walraven, Ed

Victor, Terry L.

Viola, John F.

Webb, Ronald N.

Yu, Hong-Zeng

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

102 of 116 12/7/2016 1:13 PM

Page 104: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

First Revision No. 48-NFPA 13R-2016 [ Section No. A.6.6.6 ]

A.6.6.6

Concealed spaces are permitted to have small openings such as grilles for return air when the space isbeing used as a plenum. Such small openings do not disqualify the space from being considered as aconcealed space, and sprinklers are still permitted to be omitted. (See Section 7.5 for additionalinformation on attic sprinklers.)

Submitter Information Verification

Submitter Full Name: David Hague

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 14 18:03:54 EDT 2016

Committee Statement

Committee Statement: Correlation with the addition of the new Section 7.4 for attic protection.

Response Message:

Public Input No. 104-NFPA 13R-2016 [Section No. A.6.6.6]

Ballot Results

This item has passed ballot

31 Eligible Voters

2 Not Returned

28 Affirmative All

1 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Flancher, Dawn M.

Hoover, Tonya L.

Affirmative All

Asp, Roland A.

Bell, Kerry M.

Benn, Fred

Bradley, Frederick C.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

103 of 116 12/7/2016 1:13 PM

Page 105: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

Browning, Chase A.

Buuck, Daniel

Cronin, Bradford T.

Deegan, Thomas G.

Feid, Jeffrey

Haagensen, Dana R.

Isman, Kenneth E.

Mathias, Daniel J.

Nickelson, David A.

O'Brian, Michael

Pilette, Maurice M.

Puchovsky, Milosh T.

Schwab, Peter T.

Skare, Eric J.

Skinner, Timothy J.

Stanley, George W.

Towler, Michael

Townley, Donald R.

Trim, Martin C. W.

Van Walraven, Ed

Victor, Terry L.

Viola, John F.

Webb, Ronald N.

Yu, Hong-Zeng

Affirmative with Comment

Klein, Marshall A.

The Annex Note is providing just a reference to the new Section on attic sprinklers which is shown as Section 7.5in this FR. However, FR#41 shows this new attic section as Section 7.4. Since this new section on attic sprinklersmay be renumbered in the final draft of the Code, the actual Section number will need to be revised in the finaldraft of the next edition of the Code.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

104 of 116 12/7/2016 1:13 PM

Page 106: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

First Revision No. 26-NFPA 13R-2016 [ Section No. A.6.9 ]

A.6.9

These connections should be installed so that the valve can be opened fully and for a sufficient timeperiod to ensure a proper test without causing water damage. The drain should be designed and sized toverify the sufficiency of the water supply.

Submitter Information Verification

Submitter Full Name: David Hague

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 14 15:00:21 EDT 2016

Committee Statement

CommitteeStatement:

The purpose of the test connection is to verify that the water flow device is in proper workingorder. The way to verify the sufficiency of the water supply is to conduct a water flow test, notrunning water through the test connection.

ResponseMessage:

Public Input No. 14-NFPA 13R-2016 [Section No. A.6.9]

Ballot Results

This item has passed ballot

31 Eligible Voters

2 Not Returned

29 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Flancher, Dawn M.

Hoover, Tonya L.

Affirmative All

Asp, Roland A.

Bell, Kerry M.

Benn, Fred

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

105 of 116 12/7/2016 1:13 PM

Page 107: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

Bradley, Frederick C.

Browning, Chase A.

Buuck, Daniel

Cronin, Bradford T.

Deegan, Thomas G.

Feid, Jeffrey

Haagensen, Dana R.

Isman, Kenneth E.

Klein, Marshall A.

Mathias, Daniel J.

Nickelson, David A.

O'Brian, Michael

Pilette, Maurice M.

Puchovsky, Milosh T.

Schwab, Peter T.

Skare, Eric J.

Skinner, Timothy J.

Stanley, George W.

Towler, Michael

Townley, Donald R.

Trim, Martin C. W.

Van Walraven, Ed

Victor, Terry L.

Viola, John F.

Webb, Ronald N.

Yu, Hong-Zeng

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

106 of 116 12/7/2016 1:13 PM

Page 108: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

First Revision No. 27-NFPA 13R-2016 [ Section No. A.6.10 ]

A.6.10

These connections should be installed so that the valve can be opened fully and for a sufficient timeperiod to ensure a proper test without causing water damage. The test connection should be designedand sized to verify the sufficiency proper operation of the water supply and alarm mechanism(s) .

Submitter Information Verification

Submitter Full Name: David Hague

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 14 15:07:08 EDT 2016

Committee Statement

Committee Statement: The alarm connection is not used to verify sufficiency of the water supply.

Response Message:

Ballot Results

This item has passed ballot

31 Eligible Voters

2 Not Returned

29 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Flancher, Dawn M.

Hoover, Tonya L.

Affirmative All

Asp, Roland A.

Bell, Kerry M.

Benn, Fred

Bradley, Frederick C.

Browning, Chase A.

Buuck, Daniel

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

107 of 116 12/7/2016 1:13 PM

Page 109: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

Cronin, Bradford T.

Deegan, Thomas G.

Feid, Jeffrey

Haagensen, Dana R.

Isman, Kenneth E.

Klein, Marshall A.

Mathias, Daniel J.

Nickelson, David A.

O'Brian, Michael

Pilette, Maurice M.

Puchovsky, Milosh T.

Schwab, Peter T.

Skare, Eric J.

Skinner, Timothy J.

Stanley, George W.

Towler, Michael

Townley, Donald R.

Trim, Martin C. W.

Van Walraven, Ed

Victor, Terry L.

Viola, John F.

Webb, Ronald N.

Yu, Hong-Zeng

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

108 of 116 12/7/2016 1:13 PM

Page 110: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

First Revision No. 39-NFPA 13R-2016 [ Section No. A.7.1.1.3 ]

A.7.1.1.3

All residential sprinklers have been investigated under a flat, smooth, 8 ft (2.44 m) high horizontal ceiling.Some residential sprinklers have been investigated and listed for use under specific ceiling configurationssuch as a horizontal beamed ceiling. The performance of residential sprinklers under flat, smooth,horizontal ceilings has been well documented throughout the life of NFPA 13R. Prior to 2010, severalmanufacturers of residential sprinklers had performed testing and received listings for residentialsprinklers under certain slopes and in certain beam conditions. In 2010, the Fire Protection ResearchFoundation (FPRF) conducted a research project consisting of 76 FDS simulations and 12 full-scale firetests. The results have been used to develop system design criteria in a generic manner in order tosimplify the use of residential sprinklers. Some residential sprinkler listings still exist for situations beyondthe scope of the generic design. ( See the FPRF report, “Analysis of the Performance of ResidentialSprinkler Systems with Sloped or Sloped and Beamed Ceilings,” dated July 2010, for more information.)

For examples of selecting a compartment for consideration, see Figure A.7.1.1.3(a) and FigureA.7.1.1.3(b), which show examples of design configurations for compartments based on the presence oflintels to stop the flow of heat.

Figure A.7.1.1.3(a) Sprinkler Design Areas for Typical Residential Occupancy — Without Lintel.

Figure A.7.1.1.3(b) Sprinkler Design Areas for Typical Residential Occupancy — with Lintel.

Submitter Information Verification

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

109 of 116 12/7/2016 1:13 PM

Page 111: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

Submitter Full Name: David Hague

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 14 16:07:10 EDT 2016

Committee Statement

CommitteeStatement:

NFPA 13R, 2016 Figure A.7.1.1.3(b) depicts a minimum 8" lintel between the Dining Room andLiving Room. The 8" lintel alone does not meet the compartment definition which requires that theopening is limited to 8' width on any wall. Figure A.7.1.1.3(b) should be modified to depict amaximum 8' opening per the definition of a compartment found in NFPA 13R section 3.3.2.

ResponseMessage:

Public Input No. 81-NFPA 13R-2016 [Section No. A.7.1.1.3]

Ballot Results

This item has passed ballot

31 Eligible Voters

2 Not Returned

29 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Flancher, Dawn M.

Hoover, Tonya L.

Affirmative All

Asp, Roland A.

Bell, Kerry M.

Benn, Fred

Bradley, Frederick C.

Browning, Chase A.

Buuck, Daniel

Cronin, Bradford T.

Deegan, Thomas G.

Feid, Jeffrey

Haagensen, Dana R.

Isman, Kenneth E.

Klein, Marshall A.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

110 of 116 12/7/2016 1:13 PM

Page 112: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

Mathias, Daniel J.

Nickelson, David A.

O'Brian, Michael

Pilette, Maurice M.

Puchovsky, Milosh T.

Schwab, Peter T.

Skare, Eric J.

Skinner, Timothy J.

Stanley, George W.

Towler, Michael

Townley, Donald R.

Trim, Martin C. W.

Van Walraven, Ed

Victor, Terry L.

Viola, John F.

Webb, Ronald N.

Yu, Hong-Zeng

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

111 of 116 12/7/2016 1:13 PM

Page 113: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

First Revision No. 47-NFPA 13R-2016 [ Section No. A.7.3.3 ]

A.7.3.4

Garages serving a single dwelling unit include garages that are directly connected to the dwelling unit andgarages that are served by a common corridor with access limited to a single owner or tenant.

Residential sprinklers and quick-response sprinklers at 0.05 gpm/ft2 (2.04 L/min/m2) densities have notbeen tested for use in garages. However, field experience has shown that they will activate, sound analarm, and provide water distribution that will assist in controlling a fire.

Submitter Information Verification

Submitter Full Name: David Hague

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 14 18:00:14 EDT 2016

Committee Statement

Committee Statement: The fuel load/fire threat is effectively the same as that of an attached garage.

Response Message:

Public Input No. 73-NFPA 13R-2016 [Section No. A.7.3.3]

Ballot Results

This item has passed ballot

31 Eligible Voters

2 Not Returned

29 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Flancher, Dawn M.

Hoover, Tonya L.

Affirmative All

Asp, Roland A.

Bell, Kerry M.

Benn, Fred

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

112 of 116 12/7/2016 1:13 PM

Page 114: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

Bradley, Frederick C.

Browning, Chase A.

Buuck, Daniel

Cronin, Bradford T.

Deegan, Thomas G.

Feid, Jeffrey

Haagensen, Dana R.

Isman, Kenneth E.

Klein, Marshall A.

Mathias, Daniel J.

Nickelson, David A.

O'Brian, Michael

Pilette, Maurice M.

Puchovsky, Milosh T.

Schwab, Peter T.

Skare, Eric J.

Skinner, Timothy J.

Stanley, George W.

Towler, Michael

Townley, Donald R.

Trim, Martin C. W.

Van Walraven, Ed

Victor, Terry L.

Viola, John F.

Webb, Ronald N.

Yu, Hong-Zeng

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

113 of 116 12/7/2016 1:13 PM

Page 115: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

First Revision No. 54-NFPA 13R-2016 [ Chapter B ]

Annex B Informational References

B.1 Referenced Publications.

The documents or portions thereof listed in this annex are referenced within the informational sections ofthis standard and are not part of the requirements of this document unless also listed in Chapter 2 forother reasons.

B.1.1 NFPA Publications.

National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471.

NFPA 13, Standard for the Installation of Sprinkler Systems, 2016 2019 edition.

NFPA 20, Standard for the Installation of Stationary Pumps for Fire Protection, 2016 2019 edition.

NFPA 24, Standard for the Installation of Private Fire Service Mains and Their Appurtenances, 2016 2019edition.

NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems,2014 2017 edition.

NFPA 101 ® , Life Safety Code ® , 2018 edition.

“Analysis of the Performance of Residential Sprinkler Systems with Sloped or Sloped or BeamedCeilings,” Fire Protection Research Foundation, NFPA, July 2010.

B.1.2 Other Publications.

B.1.2.1 ASTM Publications.

ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959.

ASTM F437, Standard Specification for Threaded Chlorinated Poly (Vinyl Chloride) (CPVC) Plastic PipeFittings, Schedule 80, 2009 2015 .

ASTM F438, Standard Specification for Socket-Type Chlorinated Poly (Vinyl Chloride) (CPVC) PlasticPipe Fittings, Schedule 40, 2009 2015 .

ASTM F439, Standard Specification for Socket-Type Chlorinated Poly (Vinyl Chloride) (CPVC) PlasticPipe Fittings, Schedule 80, 2009 2013 .

IEEE/ ASTM SI10, Standard for Use of the International System of Units (SI): the Modern Metric System,2002 2010 .

B.1.2.2 AWWA Publications.

American Water Works Association, 6666 West Quincy Avenue, Denver, CO 80235.

AWWA M14, Backflow Prevention and Cross-Connection Control Recommended Practices , 2015.

B.1.2.3 ICC Publications.

International Code Council, 500 New Jersey Avenue, NW, 6th Floor, Washington, DC 20001-2070.

IBC International Building Code , 2015.

B.1.2.4 NFSA Publications.

National Fire Sprinkler Association, P.O. Box 1000 40 Jon Barrett Road , Patterson, NY 12563.

Valentine and Isman, Kitchen Cabinets and Residential Sprinklers, 2005.

Valentine and Isman, Interaction of Residential Sprinklers, Ceiling Fans and Similar Obstructions, 2005.

B.1.2.5 UL Publications.

Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL 60062-2096.

ANSI/UL 1626, Residential Sprinklers for Fire Protection Service, 2008.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

114 of 116 12/7/2016 1:13 PM

Page 116: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

B.2 Informational References. (Reserved)

B.3 References for Extracts in Informational Sections.

NFPA 13, Standard for the Installation of Sprinkler Systems, 2016 2019 edition.

NFPA 24, Standard for the Installation of Private Fire Service Mains and Their Appurtenances, 2016 2019edition.

Submitter Information Verification

Submitter Full Name: David Hague

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Aug 01 08:55:07 EDT 2016

Committee Statement

Committee Statement: Referenced current SDO names, addresses, standard names, numbers, and editions.

Response Message:

Public Input No. 2-NFPA 13R-2015 [Chapter B]

Public Input No. 8-NFPA 13R-2016 [Section No. B.1.2.1]

Public Input No. 79-NFPA 13R-2016 [Section No. B.1.2.3]

Ballot Results

This item has passed ballot

31 Eligible Voters

2 Not Returned

28 Affirmative All

1 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Flancher, Dawn M.

Hoover, Tonya L.

Affirmative All

Asp, Roland A.

Bell, Kerry M.

Benn, Fred

Bradley, Frederick C.

Browning, Chase A.

Buuck, Daniel

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

115 of 116 12/7/2016 1:13 PM

Page 117: M E M O R A N D U M - NFPA...Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4References for Extracts in Mandatory Sections

Cronin, Bradford T.

Deegan, Thomas G.

Feid, Jeffrey

Haagensen, Dana R.

Isman, Kenneth E.

Klein, Marshall A.

Mathias, Daniel J.

Nickelson, David A.

O'Brian, Michael

Pilette, Maurice M.

Puchovsky, Milosh T.

Schwab, Peter T.

Skinner, Timothy J.

Stanley, George W.

Towler, Michael

Townley, Donald R.

Trim, Martin C. W.

Van Walraven, Ed

Victor, Terry L.

Viola, John F.

Webb, Ronald N.

Yu, Hong-Zeng

Affirmative with Comment

Skare, Eric J.

The updated address for NFSA was provided to the Technical Committee by the NFPA 13D task groupresponsible for Annex B. It should be updated here as well.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...