APPLICATION/INSTALLATION PROCEDURES FOR
LOW PRESSURE PUMPING UNITS (DISTRICT MAINTAINED)
SIMPLEX
1. Make application for service, and
Pay connection fee Sign Maintenance Agreement Discuss location of pumping unit with District Staff Receive District Standard Details
2. Purchase low pressure pumping unit and appurtenances (Assessed areas – low pressure pumping unit price included in assessment) 3. Arrange for pick up of low pressure pumping unit and appurtenances (at District)
Contractor to conduct Continuity test on pumps upon pickup. 4. Arrange for MANDATORY preconstruction meeting at site with:
District Inspector (Call Rick Philbrick to setup 561-262-3456) Contractor Property Manager or Homeowner Electrician Plumber
5. Inspection schedule must be followed (listed in chronological oder): A. Wetwell Inspection
Plumbness/Level Anti-floatation Concrete Rim elevation to be 2”-3” above finished grade
P a g e | 2
B. Electrical Inspection
After electrical appurtenances are installed and approved by Municipality or County, District to be notified for inspection (24 hour notice required).
Contractor/homeowner not to energize control panel until all inspections have been completed and approved and, only with District inspector on site.
C. Pump Startup Test
Continuity test Draw down test Pressure test on 1.25” effluent line
D. Plumbing Inspection
Plumbing may be moved from septic tank to wet well upon a passing pump startup and must be inspected by District staff.
E Septic Tank Abandonment and Fill
Tank pumped out Pressure washed Rupture tank Fill
Please note: All District inspections require 24 hour notice. The District strives to be proactive during the construction phase and unscheduled inspections will be made to assess progress and for conformance to LRD specifications. M:\LOW PRESSURE APPLICATION INSTALLATION PROCEDURES.doc
4'(MAX)
DWELLING
R/W LINE
LOW PRESSURE FORCE MAIN
CONTROL PANEL (SEE SECTION VIEW)
1.25
" FO
RC
E M
AIN
FUSED DISCONNECT-30AMP*
SERVICE BOX
ISOLATION VALVE
3' (TYP.)
CL
CL
VALVE BOX
EDGE OF ROAD
3' DIAMETER WET-WELLWITH PUMP.
DR
IVE
WA
Y2-WAYCLEAN OUT**
APRIL, 2012LP-1
LOXAHATCHEE RIVER DISTRICT
TYPICAL RESIDENTIALGRINDER SYSTEM LAYOUT (PLAN VIEW)REVISION:
N.T.S.
*FOR DUPLEX INSTALLATIONS (5,000 sq ft or more) USE 60 AMP FUSEABLE DISCONNECT.
**REPLACE EXISTING CLEANOUT IF NOT 2-WAY.
PR
OP
ER
TY L
INE
PR
OP
ER
TY L
INE
(TY
P.)
(1) SCH.80 PVC OR
2-WAY CLEAN OUT**
FUSED DISCONNECT-30AMP *
HOSE BIB
(POWER FROM HOUSE)
36" FLEX CONDUIT TO PANEL
FLOW
(1)-4"x4" JUNCTION BOX
***(1) - 2" SCH 80 PVCELEC. CONDUIT
PANEL TO TANK.
FIBERGLASSTANK - 3' DIA.
W/ PUMP INSIDE
*FOR DUPLEX INSTALLATIONS (5,000 sq ft or more) USE 60 AMP FUSEABLE DISCONNECT.
**REPLACE EXISTING CLEANOUT IF NOT 2-WAY.
CONTROL PANEL MOUNTED TO HOUSE.PANEL TO BE 3' LEFT OR RIGHT (CENTERLINETO CENTERLINE) FROM TANK LOCATION.
APRIL, 2012LP-2
LOXAHATCHEE RIVER DISTRICTTYPICAL RESIDENTIAL
GRINDER SYSTEM LAYOUT (SECTION VIEW)REVISION:
N.T.S.
***FOR DUPLEX STATIONS, USE TWO (2) - 2" SCH. 80 CONDUITS
(MAX)
CLEAN OUT
4'
LP-3ALTERNATE RESIDENTIAL GRINDER SYSTEM LAYOUT (PLAN VIEW)
CLEAN OUT
DWELLING
R/W LINE
LOW PRESSURE FORCE MAIN
1.25
" FO
RC
E M
AIN
SERVICE BOX
ISOLATION VALVE
EDGE OF ROAD
DR
IVE
WA
Y
APRIL, 2012
LOXAHATCHEE RIVER DISTRICT
REVISION: N.T.S.
PR
OP
ER
TY L
INE
PR
OP
ER
TY L
INE
APRIL, 2012LP-4
FINISHED GRADE
3.0'
(M
IN.)
4'-6
"±
.75" CONDUIT
PEDESTAL CAPRED ALARM LIGHT
2" PVC CONDUIT
CONDUIT CLAMP
HINGE SIDE
BACKFILL AND COMPACT MATERIAL
PLACE 4" OF #57 ROCK UNDER PEDESTAL
22" L
ON
G
18"
22"X6"X6"X.25" THICKFIBERGLASS ANGLES ATTACHEDTO SIDES OF PEDESTAL WITH 8S.S. SCREWS (EACH SIDE)
PADLOCK INSTALLED BY DISTRICT
POWER FROM DISCONNECT BOXTO CONTROL PANEL BOX
ELECTRICAL DISCONNECT BOX:SIMPLEX - 30 AMP W/ # 10 AWG
POWER CORDS TOPUMP & FLOATS
FP&L POWER INTODISCONNECT BOX WIRESIZE #10AWG MIN.
MIN
.
NOTE:CONTRACTOR SHALL FURNISH ANDINSTALL FIBERGLASS PEDESTAL ANDFIBERGLASS NEMA 4X ENCLOSUREAND DISCONNECT SWITCH.CONTRACTOR SHALL FURNISH ANDINSTALL ALL CONDUIT AND WIRESBETWEEN PEDESTAL FIXTURES ANDLOW PRESSURE PUMP & FLOATS.
FIBERGLASS PEDESTAL/POST7'-6" LONG X 6"X9" RECT. X 3"THICK, PEDESTAL WITH CAP.BURY 3.0' IN GROUND (MIN.) #H90R96516 MFG. BY: HIGGINSPOWER SOLUTIONS, INC., OROTHER PRE-MANUFACTUREDPOST WITH LRD APPROVAL.
FIBERGLASS ENCLOSURENEMA 4X
PANEL MOUNTING TABS(4 EACH)
LOXAHATCHEE RIVER DISTRICT
ALTERNATE RESIDENTIAL GRINDERSYSTEM LAYOUT FREE STANDING (1 OF 2)
N.T.S.REVISION:
4" X 4" PVC JUNCTION BOXOR PER LOCAL BUILDINGAUTHORITY.
* FOR RESIDENTIAL SIMPLEX STATIONS ONLY
TO F
LOA
TS
TO P
UM
P
FROM POWER SOURCE
PANEL
CL
PLAN VIEW
24"(MIN.)
DISCONNECT
1.5" 304 S.S. PIPE SUPPORT(TYP.) OR GALV. EMT OR ALUM.
CONTROL PANEL MOUNTINGS.S. SHALLOW UNISTRUT,UNISTRUT STRAP.
DISCONECT. USE 60 AMPFUSEABLE USE #6 AWG WIRE MIN.
1.5" 304 SS PIPE SUPPORT (TYP.) ORALUMINUM, OR GALVANIZED EMTIF GALVANIZED EMT, ALL PORTIONSIN CONCRETE SHALL BE COATED INBITUMASTIC TO 2" ABOVE CONC. PAD
POURED CONCRETE BASE12" DIA x 36" DEEP (TYP.)
NOTE:ALL GROUNDING TO BE PERN.E.C. AND/ OR LOCAL CODES
SEAL CONDUIT (TYP.)
NEMA 4XFIBERGLASSENCLOSURE
HASP & DISTRICTSUPPLIED LOCK
RED LIGHT "HIGH WATER ALARM" (SEE DETAIL)
ROUND 1.5" PVC CAP (TYP.)
JUNCTION BOXPER LOCAL BLDG.DEPT.
*(3) - 2" SCH 80 PVC
36" T
O C
EN
TER
OF
PA
NE
L36
" MIN
.
APRIL, 2012LP-5
LOXAHATCHEE RIVER DISTRICT
ALTERNATE RESIDENTIALGRINDER SYSTEM LAYOUT FREE STANDING (2 OF 2)
N.T.S.
FRONT ELEVATION
REVISION:
* FOR RESIDENTIAL DUPLEX STATIONS ONLY
11"
12"
TO CONTROL PANEL 4" MIN. OF #57 STONE BASE
PVC UNION
2'MAX.
CL
2"
VA
RIE
S (
5' O
R 6
')
*
(NATURAL OR NATIVE SOIL UNDER BASE)
CL
3'-0
" (M
IN.)
* *
**
SCH. 80 PVC PIPING (INSIDE)
** * *
*
*
PLACE 8 BAGS OF DRY CONCRETE MIXEQUALLY SPACED AROUND CIRCUMFERENCEOF THE FLOATATION COLLAR.
DRILL 2" OPENING FOR 1.25"PIPE & GROMMET FOR THEF.M. CONNECTION LOCATEAND ORIENT IN FIELD
TO F.M. CONNECTIONAT R/W LINE (SEEDETAIL LP-9)
DRILL 3" OPENING FOR 2"GROMMET FOR THEELECTRICAL CONNECTIONLOCATE AND ORIENT INFIELD
INLET
DRILL 5" OPENING FORSEWER SERVICECONNECTION, LOCATEAND ORIENT IN FIELD
VACUUM BREAKER ASSEMBLY:1.25" TEE W/1.25" SLIP X .75"FEMALE THREAD BUSHING, 1.75"PVC NIPPLE, .75" CHECK VALVEINVERTED POSITION W/ (2) - .75"90° BENDS
S.S.FLOAT & 6-HOOKCABLE HOLDER
STAINLESS STEELMOUNTING STAND(BY PUMP MFG.)
SUBMERSIBLEGRINDER PUMP (2HPMIN.DUAL-SEAL) (SEESPECIFICATIONS)
36" MIN. DIA. REINFORCEDFIBREGLASS BASIN, MUSTMEET ASTM "D-3753"SPECIFICATION.
MERCURY SWITCH LEVELCONTROL-MINI ROTOFLOAT BY ANCHORSCIENTIFIC W/INTERNALWEIGHT
WET WELLCONNECTIONS FOR 1.25",2" & 4" PIPE (SEE DETAILLP-20) (SEE NOTE)
1.25"SCH. 80PVCPIPING
ALUM. LID W/ 2/3RDHINGED SINGLE LEAFLOCKABLE DOOR300PSF RATED
NEW PUMPLOCATIONROTATED 90°OFFSET
2 - 1.25" PVC BALL VALVES (SOC X SOC)
1.25" TEE WITH THREADEDCAP (SUPPLIED BY DISTRICT)
METER BOX "NDS" MODEL NO.113 BC WITH GREEN COVERMARKED "SEWER" ON LID(12"X17" SIZE) (SUPPLIED BYDISTRICT)
6" ANTI-FLOTATION COLLAR
1.25" RISER PIPE LENGTH TO BE VERIFIEDAND CUT IN FIELD TO MATCH F.M. OUTLET
*
1.25" PVC WYE BALL CHECK VALVE
WET WELL SHALL BE FIBERGLASS WITHPRE-PIPED PUMP DISCHARGE ASSEMBLY.
SCH. 40 PVC PIPING (OUTSIDE) SUPPLIEDBY MANUFACTURER TO VALVE BOX
NOTE:CONNECTION TO WET-WELL FOR ELECTRICAL ANDSEWER OPENINGS SHALL BE INSTALLED BYCONTRACTOR WITH 1.25", 2" OR 4" RUBBERGROMMETS SUPPLIED BY THE MANUFACTURER,GRINDER PUMP SHALL BE "BARNES SERIES SGVF".
*** PUMP SPECIFICATIONS:BARNES-GRINDER PUMP #SGVF2022L, 2HP, 230V, 1PH, 60HZ, 5.13" IMPELLER
APRIL, 2012LP-6
LOXAHATCHEE RIVER DISTRICT
RESIDENTIAL SIMPLEXTYPICAL WET WELL
N.T.S.REVISION:
XFMR1R
MS
C CC
BREAKERS
2R S
R
A
N B
C MP
B
A
ETM
RL
AL
GFI
ATB ASB
AH
BREAKERS
CAP.PACK
APRIL, 2012LP-7
LOXAHATCHEE RIVER DISTRICTN.T.S.
BACKPLATE LAYOUT (TYP.)
ENCLOSURE & DEADFRONT(TYP.)
RESIDENTIAL SIMPLEXCONTROL PANEL LAYOUT
OH
BILL OF MATERIALS
GE START RELAY, 16104MARS STRT CAP 250V 124-156MF, 11148
CAP.PACK: MARS RUN CAP OVAL 45MF/440V, 12448
* OR APPROVED EQUAL
GRINDER PUMP'STO MATCH
PANEL & COMPONENTS SHALL CONFORM TOINDUSTRIAL UL LISTING PRE SEC. 508 N.E.C.
*
BCG
BROBROY NEMA 4X, RJ1816HPLSQ-D, QOU230SQ-D, QOU115SQ-D, 8502SBO2VO2SSQ-D, B25SQ-D, 9070T50D13CONTR. DYN. 120VAC, HMA303MCGILL 20A, 910003BACO 22M, L20SA50STONCO, VP11GCRFLOYD BELL, MC09201QIDEC, SR3B05SQ-D, ZB4BA0SQ-D, ZB4BA2PASS SEYMOUR, 1595WBUSS, MDL-1
SQ-D, 9065SEO5IDEC, RR2PULAC24VIDEC, SR2P06
FIBERGLASS ENCLOSUREPUMP & MAIN BREAKERSGFI & CONTROL BREAKERSSTARTEROVLD HTR ELEMENTTRANSFORMER 50VAELAPSED TIME METERHAND OFF AUTO SWITCHRUN LIGHTALARM LIGHTALARM HORNALARM SILENCE RELAYALARM SILENCE BUTTONALARM TEST BUTTON15 AMP GFI RCPTFUSE 1A
OVERLOAD RELAYCONTROL RELAY8-PIN SOCKET
ENCPCB/MCBCCB/GCBMSOLXFMRETMHOARLALAH*ASRASBATBGFIFU1
OLCR1-2CR1-2
CAPACITORPACK SUPPORT
DETAIL
AL
ENCLOSURE & DEADFRONT(TYP.)
4X TYPE LATCHES
4X TYPE LATCHES
PADLOCKING HASPAND STAPLE18
"
16"
18"
16"
STARTRELAY
TERMINALSTRIP
BUSS, MDL-2FUSE 2AFU2BUSS, BKS82021FUSE BLOCKFU1-2
REVISION:
ALTECH, TSF6O12WPTERMINAL STRIPTS
RC
SC
CB1-30AMPMS
RED
BLU
1SR
25
BLK
WHT GRINDER2 HP
15.0 F.L.A.
CBM-30AMP
CB2-15AMP
CB3-15AMP
120/240 VOLT1 PHASE3 WIRE
LS3
LS1
CR1
1 3CR2
LS2 CR1
FU2- 2AMP
FU1- 1AMP
AUTOPUMPOFFHAND
SW
8 6
CR1
TS OL MS
ETM
A RUNNING
CR2
1 3CR3
47
1
R LIGHTALARM
HORNALARM
CR3
PB2
LS1-
PU
MP
ON
PU
MP
OFF
HIG
H A
LAR
M
LS2-
LS3-
SE
E N
OTE
4TS
TERMINAL STRIP
76541 2 3 8
NOTES:
RELAYSILENCE
1 2 43
65
7 8
TEST
N N
2 #10
2 W21
3
45
6 7
8
12119
10
13
14
15
W
RED
BLKBLK
SILENCE
GFI
OL2 #12
16
PB1
WHT
BLK
RED
24 VOLT
120 VOLTTR- 50 VA
1.) PANEL GROUND TERMINAL MUST BE CONNECTED TO EARTH GROUND.2.) FACTORY WIRING IS SHOWN FIELD WIRING IS SHOWN3.) RECOMMENDED TIGHTENING TORQUES FOR TERMINALS 240 VOLT POWER
30 POUND INCHES. 120 VOLT POWER, CONTROL & LOW VOLTAGE -20 POUND INCHES.
4.) THERMAL SAFETY SWITCH (TS) CONTACTS ARE NOT IN ALL MOTORS. IFMOTOR DOES NOT HAVE SWITCH, THESE TERMINALS MUST BE JUMPERED.
5.) LAYOUT TO MEET CUSTOMER'S REQUIREMENTS.
LP-8
LOXAHATCHEE RIVER DISTRICT
RESIDENTIAL SIMPLEXELECTRICAL SCHEMATICAPRIL, 2012
N.T.S.REVISION:
2
1
2 #14
TYPICAL ROAD CROSSING SECTION VIEW
2"GRADE
PROPERTY LINE
(TY
P.)
5'
PLAN VIEW
E.M.S.
R/W
LIN
EE.M.S.
(TYP)12"
12" 6"
E.M.S.
18"
GRADE
18"
1.5" PVC SCH.40(SINGLE SERVICE)
NOTE:SERVICE PIPE TOPUMP UNIT, MIN.12" BELOW GRADE
EDGE OF SERVICE BOX SHALL BE 18"BEHIND SIDEWALK OR R/W LINE
1.5" PVC SCH.40 (SINGLE SERVICE)
LOW PRESSURE FORCE MAIN
12" NIPPLE W/GLUED CAP (TYP)
ISOLATION VALVE(SEE NOTE #2)
LOW PRESSUREFORCE MAIN
1.5" 90° SERVICE LATERAL
VALVE BOX SHALL BE TYLER UNION:141-Q FOR 22"X30"DEPTH142-R FOR 30"X42"DEPTHWITH COVER MARKED "SEWER"SEE NOTE #6
NOTES:1. ACTUAL LOCATIONS OF SERVICES SHALL BE DETERMINED IN FIELD BY RESIDENT ENGINEER DEPENDING UPON EXISTING CONDITIONS & LOCATION OF EXISTING SEPTIC TANK.2. IN R.O.W. ALL BALL VALVES SHALL BE FORD BRASS BALL VALVE CURB STOP #B11-666 FOR 1.5"
3. SEE PLAN SHEET FOR LOCATION OF SERVICES.4. 4" MIN. OF #57 ROCK BEDDING SHALL BE PLACED BELOW VALVE BOXES.5. VALVES INSIDE SERVICE BOX SHALL BE SCH 40 1.5" PVC BALL VALVE, SLIP X SLIP. CHECK VALVE SHALL BE 2" "FLOWMATIC" PVC BALL CHECK VALVE, (MODEL-208S) SLIP X SLIP WITH 2"X1.5" BUSHINGS.
SERVICE BOX:CDR FLARED SERVICE BOXMODEL #B10111812A(11"X18"X12") WITH COVER#C00111802A. COVER MARKED"SEWER" AND COLORED GREEN.ALSO REFER TO NOTE # 5.
IF ROAD CROSSING IS NECESSARY,SERVICE LATERAL TO BE INSTALLED VIAPNUEMATIC MOLE METHOD
12" MAX.
SEE NOTE #4
W/ FORD QT67 OPERATING NUT, USE BRASS NIPPLES EACH SIDE OF BRASS BALL VALVES.
APRIL, 2012LP-22
LOXAHATCHEE RIVER DISTRICT
TYPICAL SINGLE SERVICE SCHEMATICN.T.S.
36" M
IN.
(TY
P)
REVISION:
6. WHERE SERVICES ARE BORED UNDER A ROADWAY, A VALVE BOX SHALL BE CONSTRUCTED WITH THE ISOLATIONVALVE (SEE DETAILS ABOVE). OTHERWISE, THE ISOLATION VALVE SHALL BE DIRECT BURIED WITH AN EMS MARKERAND NO VALVE BOX.
R/W LINE
E.M.S. MARKER
PROPERTY LINE
PLAN VIEW
E.M.S.
(TYP)12"
12" 6"
18" EDGE OF SERVICE BOX SHALL BE 18"BEHIND SIDEWALK OR R/W LINE
1.5" PVC SCH.40 (DOUBLE SERVICE)
SCH 40 PVC LOWPRESSURE FORCE MAIN
12" NIPPLE W/GLUED CAP (TYP)
R/W
LIN
E
24"
(TY
P.)
(TY
P.)
1.5" 90° BEND
1.5" 90° BEND
1.5" TEE (VERTICAL) 1.5" SCH. 40 PVC
(TYP)12"
E.M.S.
TYPICAL SINGLE SERVICE BOX.LOCATION ALONG R/W LINETO BE DETERMINED IN FIELD.(SAME AS LISTED ABOVE)
24"
TYPICAL ROAD CROSSING SECTION VIEW
2"GRADE
E.M.S.
SERVICE BOX:CDR FLARED SERVICE BOX MODEL #B10111812A(11"X18"X12") WITH COVER #C00111802A. COVER MARKED"SEWER" AND COLORED GREEN. ALSO REFER TO NOTE # 5.
1.5" PVC SCH.40(SINGLE SERVICE)
NOTE:SERVICE PIPE TOPUMP UNIT, MIN.12" BELOW GRADE
LOW PRESSUREFORCE MAIN
1.5" 90°
NOTES:1. ACTUAL LOCATIONS OF SERVICES SHALL BE DETERMINED IN FIELD BY RESIDENT ENGINEER DEPENDING UPON EXISTING CONDITIONS & LOCATION OF EXISTING SEPTIC TANK.2. IN R.O.W. ALL BALL VALVES SHALL BE FORD BRASS BALL VALVE CURB STOP #B11-666 FOR 1.5"
3. SEE PLAN SHEET FOR LOCATION OF SERVICES.4. MIN. 4" OF #57 ROCK BEDDING SHALL BE PLACED BELOW SERVICE BOXES.5. VALVES INSIDE SERVICE BOX SHALL BE SCH 40 1.5" PVC BALL VALVE, SLIP X SLIP. CHECK VALVE SHALL BE 2" "FLOWMATIC" PVC BALL CHECK VALVE, (MODEL-208S) SLIP X SLIP WITH 2"X1.5" BUSHINGS.
12" MAX.
SEE NOTE #4
W/ FORD QT67 OPERATING NUT, USE BRASS NIPPLES EACH SIDE OF BRASS BALL VALVES.
APRIL, 2012LP-23
LOXAHATCHEE RIVER DISTRICT
TYPICAL DOUBLE SERVICE SCHEMATICN.T.S.
E.M.S.
18"
GRADE
ISOLATION VALVE(SEE NOTE #2)
REVISION:
VALVE BOX SHALL BE TYLER UNION:141-Q FOR 22"X30"DEPTH142-R FOR 30"X42"DEPTHWITH COVER MARKED "SEWER"SEE NOTE #6
6. WHERE SERVICES ARE BORED UNDER A ROADWAY, A VALVE BOX SHALL BE CONSTRUCTED WITH THE ISOLATIONVALVE (SEE DETAILS ABOVE). OTHERWISE, THE ISOLATION VALVE SHALL BE DIRECT BURIED WITH AN EMS MARKER
AND NO VALVE BOX.
36" M
IN.
(TY
P)
SERVICE LATERAL
R/W LINE
IF ROAD CROSSING IS NECESSARY,SERVICE LATERAL TO BE INSTALLED VIAPNUEMATIC MOLE METHOD
1. LOW PRESSURE PUMPING UNITS SHALL BE LOCATED SO THAT SURFACE WATER RUN OFF SHALL NOT INTERFEREWITH ELECTRICAL COMPONENTS.
2. MANUFACTURER SHALL SUPPLY AND ATTACH ELECTRICAL CONTROL PANEL SCHEMATIC TO INSIDE FACE OF CONTROL PANEL DOOR (LAMINATED).
3. THE DISTRICT WILL BE CERTIFYING ALL LOW PRESSURE LIFT STATIONS WHEN COMPLETE. MANUFACTURERSHALL SCHEDULE A START UP TEST AND SUBMIT ALL AS-BUILT DATA TO THE DISTRICT FOR CERTIFICATION.
4. LIFT STATION AND CONTROL PANEL SHALL BE LOCATED SO THAT BOTH ARE ACCESSIBLE FOR MAINTENANCE.
5. WHERE FEASIBLE, HOMEOWNER SHALL PROVIDE WATER HOSE BIB. HOSE FOR MAINTENANCE OPERATIONS.
6. AIR RELEASE VALVE AND/OR VACUUM RELIEF VALVES SHALL BE PROVIDED ON ALL LOW PRESSURE FORCEMAIN INSTALLATION IMMEDIATELY UPSTREAM OF DISCHARGE POINT TO REGIONAL GRAVITY OR FORCE MAINSYSTEMS.
7. FORCE MAIN DETECTABLE TAPE & MAGNETIC LOCATING DEVICES WILL BE INSTALLED OVER FORCE MAIN,VALVES, AND SERVICES.
APRIL, 2012LP-35
LOXAHATCHEE RIVER DISTRICT
GENERAL NOTESN.T.S.
REVISION:
Loxahatchee River District Water Reclamation | Environmental Education | River Restoration
2500 Jupiter Park Drive, Jupiter, Florida 33458‐8964 Telephone (561) 747‐5700 •Fax (561) 747‐9929 • www.loxahatcheeriver.org D. Albrey Arrington, Ph.D., Executive Director
Gordon M. Boggie Harvey M. Silverman Stephen B. Rockoff Dr. Matt H. Rostock Board Member Board Member Chairman Board Member Board Member
LOW PRESSURE SEWER SYSTEM
GENERAL OPERATING INSTRUCTIONS
GENERAL INFORMATION Your home is equipped with a wastewater disposal system known as a low pressure grinder pump system. The key element of the system is the self contained grinder pump unit. The fiberglass tank, which houses the pump, collects all the effluent from your house which previously discharged to a septic tank. The solid materials are then ground to a small size suitable for pumping as a slurry with the effluent water. The grinder pump generates sufficient pressure to pump this slurry from your home through a low pressure force main to the nearest existing sanitary collection system. There are shut off and check valves that isolate your pumping unit from the low pressure force main in the street right-of-way. These valves are located in boxes at your front property line and at the pumping unit. You should be familiar with their location and operation in the event on site repairs are necessary. Additionally, you should make a location sketch of the small PVC force main between the pumping unit and the street right-of-way line. Keep this sketch in a safe place for future reference. The District can assist you in locating these valves. Listed below are typical instructions that are being recommended to users of a grinder pump low pressure system:
1. The following items should not be introduced into any house sewer, either directly or through a garbage disposal unit:
a. Glass b. Metal c. Cloth (socks, rags, etc.) d. Plastic Objects (toys, utensils, etc.) e. Diapers, Diaper Wipes, Sanitary Napkins or Tampons f. Fats, Oils and Grease (FOG)
g. Bones and other grease laden products
2. Grease - Grease in the wet well is a major cause of system backups. Float switches, which regulate the liquid levels in the pumping chamber, can be made inoperative by accumulations of grease on the float system. As with any sewer system, every effort should be made to remove grease from dishes and eating utensils prior to operating dishwashers and garbage disposal units.
P a g e | 2
3. Never introduce into any sewer: a. Explosives b. Flammable Material c. Lubricating Oils and/or Grease d. Strong Chemicals e. Gasoline f. Paints
4. Unoccupied Homes - If your home is left unoccupied for longer than a week or two, the pump system should be purged, i.e. run clean water into the pumping until the pump starts. Turn off the water supply and allow the pump to run until it shuts off automatically. Do not disconnect power to the unit. 5. Power Failure - Obviously, like other household appliances a grinder pump cannot operate and dispose of wastewater without electrical power. The storage capacity of most units varies between 70 and 80 gallons. This is an adequate reserve for an average one family home for at least 24 hours if water usage is kept to a minimum. Keep in mind that the normal toilet uses about 3 to 5 gallons per flush. 6. Pump Failure Alarm - Your low pressure grinder pump contains a built in alarm signal which will activate in the event of a high liquid level in the basin. This signal is connected to a visual and/or audible alarm which will provide you with adequate warning that service is required. During the interval prior to the arrival of a service technician, water usage should be kept to a minimum. During normal working hours you can call 747-5709 for an emergency. After hours, the emergency number is 747-5708. 7. District Response in Emergencies – Maintenance of the pumping unit and its components will be the responsibility of the District for all residential and 3 phase non-residential low flow units. The covers all labor involved for emergency calls or normal maintenance and any parts or materials that are used.
M:\LOW PRESSURE SEWER SYSTEM\LOW PRESSURE APPLICATION INSTALLATION PROCEDURES.doc