low_voltage_switchboard

26
Low-Voltage Switchboard SIVACON 8PT AUTOMATICA

Upload: phuc-tran

Post on 26-Dec-2014

188 views

Category:

Documents


3 download

TRANSCRIPT

Page 1: Low_Voltage_Switchboard

Low-Voltage Switchboard SIVACON 8PT

AUTOMATICA

Page 2: Low_Voltage_Switchboard

Low-Voltage Switchboard SIVACON 8PT

AUTOMATICA

SIVACON: The Obvious Solution forGlobal Challenges

• Safety and proven quality for every system by type testing ( TTA )

• Know-how of technological leader SIEMENS

• Manufactured by AUTOMATICA - authorisedSIVACON Technology Partner

• Globally applicable switchgear of SIEMENS

• A product of the German`s technology made in ROMANIA

Page 3: Low_Voltage_Switchboard

Low-Voltage Switchboard SIVACON 8PT

AUTOMATICA

The Unique Combination

• High standard

• Type-tested

• Know-how

• Image & resources

• Close customer contact

• High flexibility

• Regional experience

AUTOMATICA

•SIVACON•Technology

•Partner

Proximity to the customer +

World trade name

Page 4: Low_Voltage_Switchboard

Low-Voltage Switchboard SIVACON 8PT

AUTOMATICA

PartnershipCertificate

Page 5: Low_Voltage_Switchboard

Low-Voltage Switchboard SIVACON 8PT

AUTOMATICA

AUTOM

ATICA

IT Tool SIMARIS SIVACON Goal: Support for the Business Success

Page 6: Low_Voltage_Switchboard

Low-Voltage Switchboard SIVACON 8PT

AUTOMATICA

SIVACON 8PT - Design Overview

Applicable as - Power Center- Main Distribution Board- Sub Distribution Board- Motor Control Center

- Process Automation

3 Main Current classes- 3200 A- 4000 A- 7400 A

Innovative Module Technology

Manufacturing friendly concept

Page 7: Low_Voltage_Switchboard

Low-Voltage Switchboard SIVACON 8PT

AUTOMATICA

Busbar Systems 8PT

Rated current up to 3200 A up to 4000 A up to 7400 A30 kA up to 80 kA/1s 30 kA up to 100 kA/1s 150 kA/1s

17,3 kA up to 45 kA/3s 17,3 kA up to 80 kA/3s 120 kA/3sRated peak withstand current 75 kA up to 200 kA 75 kA up to 250 kA 375 kA

Poles1 x 40 x 10 3 x 40 x 10 3 x 80 x 10 + 3 x 40 x 10

up to up to up to2 x 100 x 10 3 x 100 x 10 3 x 100 x 10 + 3 x 100 x 10

Busbar location

Cubicle depth 600 / 800 / 1000 mm 800 / 1000 / 1200 mm 800 / 1000 / 1200 mm

Cubicle height 2200 mm 2200 mm 2600 mm

Rated short-time withstand current

Cross section per phase

at the top

3- and 4-pole

Page 8: Low_Voltage_Switchboard

Low-Voltage Switchboard SIVACON 8PT

AUTOMATICA

Circuit-Breaker Design -Type FCB

Compact, Reliable and User-Friendly

Functions: Supply, Feeder, or Coupling Cubicle

- cubicle width: 600, 800, 1000, 1200 mm

- Equipped with withdrawable or fixed mounted 3WN or 3WL circuit breakers

- Current range from 630 to 6300 A

- Reliable travel of the circuit breaker while the door is closed

- Cable or busbar connection optionally from above or below

Page 9: Low_Voltage_Switchboard

Low-Voltage Switchboard SIVACON 8PT

AUTOMATICA

Outgoing Feeders Fixed-mounted Design - Type OFF

Economical, Reliable and Variable

- cubicle width: 600mm (without separate cable connection compartment)

800mm, 1000, 1200 mm

- Any combination of modular cable feeders

- Installation of non-fused and fused devices of nominal current up to 630 A (3NP, 3RV, 3VF, 3VL, 3KL)

- Vertical busbar system with rated current: 1400A

- Type: 3- and 4-pole

- Device connection without hole punching or drilling

Page 10: Low_Voltage_Switchboard

Low-Voltage Switchboard SIVACON 8PT

AUTOMATICA

Outgoing Feeders Fixed-mounted Design OFFD for In-Line Fuse Switch-Disconnector 3NJ4

Economical, Reliable and Variable

- Cubicle width: 600 mm, 800 mm, 1000 mm

- Installation of in-line fuse switch-disconnectors

type 3NJ4

- Cable feeders up to 630 A

- Max. 25 cable feeders up to 160 A

- Current transformer available

- Internal separation max. Form 2b

Page 11: Low_Voltage_Switchboard

Low-Voltage Switchboard SIVACON 8PT

AUTOMATICA

Outgoing Feeders Plug-in Design OFPDfor In-Line Switch-Disconnector 3NJ6 with Fuses

Plugged in Swiftly, Always Safe

• Cubicle width: 1000mm, 1200mm

• Internal separation: Form 1, Form 2b, Form 3b, Form 4b

• 3- and 4- pole

• Rated current of the vertical busbar up to 2100A

• Short-circuit strength Ipk: 125 kA Icw: 50kA/1s

• Cable feeders up to 630A

• Up to 34 plug-in, in-line switch-disconnectors

• Degree of protection: up to IP41

Page 12: Low_Voltage_Switchboard

Low-Voltage Switchboard SIVACON 8PT

AUTOMATICA

Power Factor Correction Cubicle PFCLower Costs with Enhanced Safety

• Cubicle width: 800mm

• Ventilated up to IP42

• Non-choked power factor correction-unit 4RY (Modl) up to 500 kvar per unit

• Choked power factor correction-unit 4RF (Modl) up to 350 kvar

Page 13: Low_Voltage_Switchboard

Low-Voltage Switchboard SIVACON 8PT

AUTOMATICA

Cubicle for Customised Solution CCS

Plenty of Space for Flexibility

• Cubicle width: 600 mm, 800 mm, 1000 mm

• Internal separation: Form 1, Form 2b, Form 4a

• Cubicle-high doors

• Cubicle distribution busbar system :- Rated current: up to 1200 A- Rated short-time withstand current: up to 65kA/1s- 3- and 4-pole- Cross section per phase: 1 x 40 x 10 or

1 x 60 x 10 mm

• Standard mounting parts:- Transverse traverses- Mounting plate sheet metal

Page 14: Low_Voltage_Switchboard

Low-Voltage Switchboard SIVACON 8PT

AUTOMATICA

Plug-in Design OFPMVersatile with Safety

Functions: Motor Control Center in Plug-In Design

• Cubicle width: 1000mm

• Device compartment height: 1700mm

• Internal separation: Form 1 and 2b

• Fused and non-fused construction

• Motor feeders up to 250kW

• Cable feeders up to 630A

• High component density up to 22 plug-in modules per cubicle

Page 15: Low_Voltage_Switchboard

Low-Voltage Switchboard SIVACON 8PT

AUTOMATICA

Plug-in Design

• Vertical busbar system:

- Rated current: up to 1170A

- Short-circuit strength Ipk: up to 163 kA

Icw: up to 65 kA/1s

Icw : up to 50 kA/3s

- Type: 3- and 4-pole

- Cross section of vertical busbar per phase: 1 x 40 x 10 or1 x 60 x 10 mm

- Additionally with save-to-touch cover (IP20B)

- Sidewise guide rails for safe in-plugging

Page 16: Low_Voltage_Switchboard

Low-Voltage Switchboard SIVACON 8PT

AUTOMATICA

Plug-in unit

Power contacts 3- and 4-pole

Base plate

Device support

Terminal block for control circuit

Smallest height plug-in of unit: 75mm

Page 17: Low_Voltage_Switchboard

Low-Voltage Switchboard SIVACON 8PT

AUTOMATICA

Plug-in unit

Plug-in unit, module height 75 mmDirect on line starting for motors up to 11 kWFuseless design

Plug-in unit, module height 175 mmDOL starting and reversing formotors up to 45 kWFused design

Page 18: Low_Voltage_Switchboard

Low-Voltage Switchboard SIVACON 8PT

AUTOMATICA

Withdrawable-unit Design OFWHighly Available with Safety

Functions: Motor Control Center in Withdrawable-Unit Design

• Cubicle width: 600 / 1000mm

• Cable connecting compartment at the rear or at the right side in the cubicle

• Internal separation: Form 3b, Form 4b

• Module grid: 50 mm

• Up to 17 withdrawable units with 100mm per cubicle

• Fused and non-fused design

Page 19: Low_Voltage_Switchboard

Low-Voltage Switchboard SIVACON 8PT

AUTOMATICA

Withdrawable-unit Design - Withdrawable Principle

Disconnected position: Test position: Connected position:

Page 20: Low_Voltage_Switchboard

Low-Voltage Switchboard SIVACON 8PT

AUTOMATICA

Withdrawable-unit Design

• Vertical busbar system:

- Rated current: up to 1170A

- Short-circuit strength Ipk: up to 163 kAIcw: up to 65 kA/1s

Icw : up to 50 kA/3s

- Type: 3- and 4-pole

- Cross section of vertical busbar per phase: 1 x 40 x 10 or 1 x 60 x 10 mm

- Save-to-touch cover (IP20B)

Page 21: Low_Voltage_Switchboard

Low-Voltage Switchboard SIVACON 8PT

AUTOMATICA

Withdrawable-unit Design

• Disconnected, test, connected position

• Nominal current up to 630A

• With fused and non-fused design

• Unit sizes: 100, 150, 200, 300, 400, 500, 600, 700mm

• Positioning support to overcome the insertion forces

• Hinged front panel for module hight200mm

• Lockable in disconnected position

• Star-delta circuit from unit size 200mm

• 40-pole control plug with module slot for PROFIBUS connection

Page 22: Low_Voltage_Switchboard

Low-Voltage Switchboard SIVACON 8PT

AUTOMATICA

Withdrawable-unit Design - The intelligent connection between motor feeder and automation- / process control system

SIMOCODE-DP

PROFIBUS-DP cyclical exchange of dataof control-, and signal data. Moreover exchange of diagnostics by changing and parameterization at SPS-running-up

PC or PU withWin-SIMOCODE-DP/Professional

SIMATIC S5/S7/C7/M7 and PCS7 withPROFIBUS-DP Communication processor

PROFIBUS-DP-standard extension, online parameterization, diagnostics and test via acyclical reading and writing of data

Page 23: Low_Voltage_Switchboard

Low-Voltage Switchboard SIVACON 8PT

AUTOMATICA

Type-tested Switchgear and Controlgear Assembly ( TTA )

SIGNED, SEALED and DELIVERED SAFETYReference standard: IEC 60439-1

• Verification of temperature rise limits by test

• Verification of dielectric properties by test

• Verification of the short-circuit withstand strength by test

• Verification of the protective circuit

• Verification of clearances and creepage distances

• Verification of mechanical operation

• Verification of the degree of protection

Page 24: Low_Voltage_Switchboard

Low-Voltage Switchboard SIVACON 8PT

AUTOMATICA

SIVACONInternal arc testing

Test underinternal fault conditions

• Not specified in IEC 60439-1

• Special test to IEC 61641 (Report) orVDE 0660 Part 500,supplement 2

Page 25: Low_Voltage_Switchboard

Low-Voltage Switchboard SIVACON 8PT

AUTOMATICA

SIVACONInternal arcs - Test sequence

0 ms 40 ms 80 ms 120 ms

160 ms 200 ms 280 msArc strikes in circuit-breaker panel Burning duration tp = 310 ms U = 690 V + 5 % Icw = 52 kA

Page 26: Low_Voltage_Switchboard

Low-Voltage Switchboard SIVACON 8PT

AUTOMATICA

SIVACONTechnical informations / Operating Instructions