Low Voltage Cables Product Catalogue

Upload: others

Post on 26-Feb-2020

10 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

Low Voltage CablesProduct Catalogue

Page 2: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

Factories and Regional Offices

Tai Sin Electric Limited24 Gul CrescentJurong TownSingapore 629531Tel: (+65) 6672 9292Fax: (+65) 6861 4084E-Mail: [email protected]: www.taisin.com.sg

Tai Sin Electric Cables(Malaysia) Sdn. Bhd.PTD 37433 & 37434Off Jalan Perindustrian Senai 3Kawasan Perindustrian Senai Fasa 3P.O.Box 73, 81400 SenaiJohor Darul Takzim, MalaysiaTel: (+60) 7 599 8888Fax: (+60) 7 599 8898E-Mail: [email protected]: www.taisin.com.my

Tai Sin Electric Cables(VN) Co., Ltd.No.20, VSIP II Street 2Viet Nam - Singapore Industrial Park 2Hoa Phu Ward, Thu Dau Mot TownBinh Duong Province, VietnamTel: (+84) 650 3635 088Fax: (+84) 650 3635 077E-Mail: [email protected]: www.taisin.com.vn

(Updated as at October 2014)

Page 3: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

CONTENTS

INTRODUCTION

HOW TO READ THIS CATALOGUE / APPLICABLE STANDARDS

BARE ANNEALED COPPER & PVC INSULATED CABLES

BARE STRANDED PLAIN ANNEALED COPPER CONDUCTOR ( SINGLE CORE )

COPPER IEC60228, BS EN60228

PVC CU / PVC ( SINGLE CORE )

PVC Insulated, Non-Sheathed Cable, 450 / 750V, SS358, IEC60227, BS EN50525-2-31

PVC CU / PVC ( SWITCHBOARD WIRES SINGLE CORE )

PVC Insulated, Non-Sheathed Cable, 0.6 /1kV, BS6231

PPS CU / PVC / PVC ( SINGLE CORE )

PVC Insulated, PVC Sheathed Cable, 0.6 /1kV, IEC60502

PPM CU / PVC / PVC ( 2 CORES - 5 CORES )

PVC Insulated, PVC Sheathed Cable, 0.6 /1kV, IEC60502

PCC CU / PVC / PVC ( MULTI-CORES )

PVC Insulated, PVC Sheathed Cable, 0.6/1kV, BS6346

PAP CU / PVC / PVC / AWA / PVC ( SINGLE CORE )

PVC Insulated, PVC Bedded, Aluminium Wire Armoured, PVC Sheathed Cable, 0.6 / 1kV, BS6346 (Specification Withdrawn)

PSP CU / PVC / PVC / SWA / PVC ( 2 CORES - 5 CORES )

PVC Insulated, PVC Bedded, Galvanised Steel Wire Armoured, PVC Sheathed Cable, 0.6 / 1kV, BS6346 (Specification Withdrawn)

PSP CU / PVC / PVC / SWA / PVC ( MULTI-CORES )

PVC Insulated, PVC Bedded, Galvanised Steel Wire Armoured, PVC Sheathed Cable, 0.6 / 1kV, BS6346 (Specification Withdrawn)

FLEXI-IMP (SINGLE CORE, 2 CORES - 4 CORES )

PVC Insulated Flexible Cable, PVC Insulated PVC Sheathed Flexible Cable, 250V / 440V, Imperial Unit BS 2004

XLPE INSULATED CABLES

XP CU / XLPE / PVC ( SINGLE CORE )

XLPE Insulated, PVC Sheathed Cable, 0.6 / 1kV, IEC60502

XP CU / XLPE / PVC ( 2 CORES - 5 CORES )

XLPE Insulated, PVC Sheathed Cable, 0.6 / 1kV, IEC60502

XP CU / XLPE / PVC ( MULTI-CORES )

XLPE Insulated, PVC Sheathed Cable, 0.6 / 1kV, IEC60502

XAP CU / XLPE / PVC / AWA / PVC ( SINGLE CORE )

XLPE Insulated, PVC Bedded, Aluminium Wire Armoured, PVC Sheathed Cable, 0.6 / 1kV, IEC60502

XSP CU / XLPE / PVC / SWA / PVC ( 2 CORES - 5 CORES )

XLPE Insulated, PVC Bedded, Galvanised Steel Wire Armoured, PVC Sheathed Cable, 0.6 / 1kV, IEC60502

XSP CU / XLPE / PVC / SWA / PVC ( MULTI-CORES )

XLPE Insulated, PVC Bedded, Galvanised Steel Wire Armoured, PVC Sheathed Cable, 0.6 / 1kV, IEC60502

XCP CU / XLPE / PVC / CT / PVC ( 3 CORES + 3 EARTH )

XLPE Insulated, PVC Bedded, Copper Tape Screened, PVC Sheathed Cable, 0.6 / 1kV, IEC60502

XCP CU / XLPE / PVC / CT / PVC ( 4 CORES )

XLPE Insulated, PVC Bedded, Copper Tape Screened, PVC Sheathed Cable, 0.6 / 1kV, IEC60502

XCAP CU / XLPE / PVC / CT / PVC / AWA / PVC ( SINGLE CORE )

XLPE Insulated, PVC Bedded, Copper Tape Screened, PVC Separation Sheath, Aluminium Wire Armoured, PVC Sheathed Cable,0.6 / 1kV, IEC60502

XCSP CU / XLPE / PVC / CT / PVC / SWA / PVC ( 4 CORES )

XLPE Insulated, PVC Bedded, Copper Tape Screened, PVC Separation Sheath, Galvanised Steel Wire Armoured,PVC Sheathed Cable, 0.6 / 1kV, IEC60502

1

2

4

5

6

7

8

10

12

13

15

17

18

19

21

23

24

26

28

29

30

31

Page 4: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

CONTENTS

LOW SMOKE ZERO HALOGEN FLAME RETARDANT CABLES

FRT-H CU / LSZH ( SINGLE CORE )

Cross-Linked LSZH Insulated, Non-Sheathed Cable, 450 / 750V (0.6 / 1kV*), BS EN50525-3-41, BS7211

FRT-XH CU / XLPE / LSZH ( SINGLE CORE )

XLPE Insulated, LSZH Sheathed Cable, 0.6 / 1kV, IEC60502

FRT-XH CU / XLPE / LSZH ( 2 CORES - 5 CORES )

XLPE Insulated, LSZH Sheathed Cable, 0.6 / 1kV, IEC60502

FRT-XH CU / XLPE / LSZH ( MULTI-CORES )

XLPE Insulated, LSZH Sheathed Cable, 0.6 / 1kV, IEC60502

FRT-XAH CU / XLPE / LSZH / AWA / LSZH ( SINGLE CORE )

XLPE Insulated, LSZH Bedded, Aluminium Wire Armoured, LSZH Sheathed Cable, 0.6 / 1kV, BS6724

FRT-XSH CU / XLPE / LSZH / SWA / LSZH ( 2 CORES - 5 CORES )

XLPE Insulated, LSZH Bedded, Galvanised Steel Wire Armoured, LSZH Sheathed Cable, 0.6 / 1kV, BS6724

FRT-XSH CU / XLPE / LSZH / SWA / LSZH ( MULTI-CORES )

XLPE Insulated, LSZH Bedded, Galvanised Steel Wire Armoured, LSZH Sheathed Cable, 0.6 / 1kV, BS6724

FRT-XCH CU / XLPE / LSZH / CT / LSZH ( 3 CORES + 3 EARTH )

XLPE Insulated, LSZH Bedded, Copper Tape Screened, LSZH Sheathed Cable, 0.6 / 1kV, IEC60502

FRT-XCH CU / XLPE / LSZH / CT / LSZH ( 4 CORES )

XLPE Insulated, LSZH Bedded, Copper Tape Screened, LSZH Sheathed Cable, 0.6 / 1kV, IEC60502

FRT-XCAH CU / XLPE / LSZH / CT / LSZH / AWA / LSZH ( SINGLE CORE )

XLPE Insulated, LSZH Bedded, Copper Tape Screened, LSZH Separation Sheath, Aluminium Wire Armoured, LSZH Sheathed Cable,0.6 / 1kV, IEC60502

FRT-XCSH CU / XLPE / LSZH / CT/ LSZH / SWA / LSZH ( 4 CORES )

XLPE Insulated, LSZH Bedded, Copper Tape Screened, LSZH Separation Sheath, Galvanised Steel Wire Armoured,LSZH Sheathed Cable, 0.6 / 1kV, IEC60502

LOW SMOKE ZERO HALOGEN FLAME RETARDANT FIRE RESISTANT CABLES

FR-H 110 CU / MGT / LSZH ( SINGLE CORE )

Mica Taped, Cross-linked Polyolefin LSZH Insulated, Non-Sheathed Cable, 450 / 750V (0.6 / 1kV*), BS7211

FR-XH CU / MGT / XLPE / LSZH ( SINGLE CORE )

Mica Taped, XLPE Insulated, LSZH Sheathed Cable, 0.6 / 1kV, IEC60502

FR-XH CU / MGT / XLPE / LSZH ( 2 CORES - 5 CORES )

Mica Taped, XLPE Insulated, LSZH Sheathed Cable, 0.6 / 1kV, IEC60502

FR-XH CU / MGT / XLPE / LSZH ( MULTI-CORES )

Mica Taped, XLPE Insulated, LSZH Sheathed Cable, 0.6 / 1kV, IEC60502

FR-XAH CU / MGT / XLPE / LSZH / AWA / LSZH ( SINGLE CORE )

Mica Taped, XLPE Insulated, LSZH Bedded, Aluminium Wire Armoured, LSZH Sheathed Cable, 0.6 / 1kV, IEC60502

FR-XSH CU / MGT / XLPE / LSZH / SWA / LSZH ( 2 CORES - 5 CORES )

Mica Taped, XLPE Insulated, LSZH Bedded, Galvanised Steel Wire Armoured, LSZH Sheathed Cable, 0.6 / 1kV, BS7846

FR-XSH CU / MGT / XLPE / LSZH / SWA / LSZH ( MULTI-CORES )

Mica Taped, XLPE Insulated, LSZH Bedded, Galvanised Steel Wire Armoured, LSZH Sheathed Cable, 0.6 / 1kV, BS7846

FR-XL CU / MGT / XLPE / LSZH ( MULTI-CORES )

Mica Taped, XLPE Insulated, LSZH Sheathed Cable, 300 / 500V, BS EN50288-7

FR-XOL CU / MGT / XLPE / OS / LSZH ( SINGLE PAIR )

Mica Taped, XLPE Insulated, Overall Aluminium Foil Screened, LSZH Sheathed Cable, 300 / 500V, BS EN50288-7

APPENDIX A - E

Appendix A - Schedule of Installation Methods of CablesAppendix B - Current Rating Capacity, Voltage Drop & Short Circuit RatingAppendix C - Rating FactorsAppendix D - Cable Cores Colour CodeAppendix E - Fire Performance Tests and Standards

TERMS & CONDITIONS OF SALES

32

33

34

36

38

39

41

43

44

45

46

47

48

49

51

53

54

56

58

60

61

66

74

79

80

82

Page 5: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

Since our incorporation in 1980 as Tai Sin Electric Cables Manufacturer Pte Ltd,we have expanded and diversified over the past three decades to establish ourselvesas the present Tai Sin Electric Limited. To cater for the robust growth in the regionalmarket, Tai Sin now operates three cable manufacturing plants located in Singapore,Malaysia and Vietnam, all of which are fully equipped with the latest manufacturingfacilitates and technologies to meet increasing demands.

Tai Sin stocks the widest range of the Power, Control, Instrumentation and SafetyCables for use in all areas of electrical and instrumentation installation for commercial,residential, industrial and infrastructure projects. Our cables and wires are

manufactured under strict quality control and designed to perform within fixed parameters of electrical, mechanicaland environmental tolerances and we assure you that our products will not present a safety hazard if used with care.

For 30 years, we have grown steadily based on a sound business philosophy of providing quality products usingleading edge technology, backed by unfailing excellence in customer service and faster turnaround time to maintaincustomer loyalty. These are the beliefs and values that give us the strength and confidence to continue to grow, exceland succeed in the exciting years ahead.

This catalogue illustrates the construction of our standard range of PVC & XLPE Cables & Wires, our Eco-Friendly, Non-Toxic range of Low Smoke Zero Halogen Flame Retardant Cables and our range of Low Smoke Zero Halogen FlameRetardant Fire Resistant Cables comply to various local and internationalstandards.

Every possible effort has been made to ensure that the information containedin this publication is correct and current at the time of printing. Tai Sinreserves the right to change the information and/or specifications at anytime without notice in light of technical improvement and continueddevelopment.

Reference to or extracts from the Singapore Standards (SS), British Standards(BS), International Electrotechnical Commission Standards (IEC), SingaporeProductivity & Standard Board CP5:1998 manual, current IEE WiringRegulations or other regulatory bodies are made with the belief that theyare true and accurate. Users are recommended to verify such claims withthe respective organisations independently.

Tables and data in Appendices A, B & C in this catalogue have been extracted with thanks from the IEE Wiring Regulations,17th Edition and BS 7671: 2008.

We hope that this catalogue will be useful to engineers and end-users to serve as their full reference guidelines.

INTRODUCTION

www.taisin.com.sg | 1

Page 6: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

This catalogue consists of three types of Low Voltage Cables and they are categorized into three different sections,1) PVC & XLPE Insulated Cables, 2) Low Smoke Zero Halogen Flame Retardant Cables and 3) Low Smoke Zero HalogenFlame Retardant Fire Resistant Cables. In each section, the cables are further categorized by its electrical componentand conductor sizes, which ranges from 0.5mm2 to 1000mm2, armoured and non- armoured and with or withoutcopper-taped screened.

In this catalogue we have given each cable a name accompanied with the various short and long descriptions basedon its material used.

For example:

To better understand the contents of the cable, we have included a 3-dimentional image plus a cross-sectional imageof the cable for easy reference of its structure and components. The technical specifications and figures are providedby our quality team to ensure the accurate use of our products. Technical properties such as Current Rating Factor andVoltage drop, and other essential technical details are provided in the Appendices at the last section of this catalogue.The latest Cable Installation Methods as well as the new harmonized wiring colour codes (as per IEE Wiring Regulations,17th Edition) are also provided in our Appendices for your easy reference.

For all other enquiries, please feel free to contact our friendly customer service hotline for further assistance.

HOW TO READ THIS CATALOGUE

ASTM D 2863Measuring the minimum oxygen concentration to support candle-like combustion of plastic (oxygen index).

BS2004 (Specification Withdrawn)PVC insulated cables and flexible cords for electric power and lighting.

BS6231Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring.

BS6346 (Specification Withdrawn)(withdrawn with no replacement) Electric cables, PVC insulated, armoured cables for voltages of 600 / 1000V and 1900 / 3300V.

BS6360(withdrawn and replaced by BS EN 60228:2005) Specification for conductors in insulated cables and cords.

BS6387 / SS299Performance requirements for cables required to maintain circuit integrity under fire conditions.

BS6724600 / 1000V armoured electric cables having thermosetting insulation and low emission of smoke and corrosive gases when affect by fire.

BS7211Thermosetting insulated cables (non- armoured) for electric power and lighting with low emission of smoke and corrosive gases when affectedby fire.

FR-XSHCU / MGT / XLPE / LSZH / SWA / LSZH ( 2 CORES - 5 CORES )

Mica Taped, XLPE Insulated, LSZH Bedded, Galvanised Steel Wire Armoured,LSZH Sheathed Cable, 0.6 / 1kV, BS7846

Full descriptionon the third line

This is the shortdescription

APPLICABLE STANDARDS

Below are the applicable standards that are used as reference in the construction of our low voltage cables.

2 | www.taisin.com.sg

Page 7: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

BS7629-1300 / 500V fire-resistant screened cables having low emission of smoke and corrosive gases when affect by fire.Part 1: Multicore and Multi-pair Cables.

BS7846600 / 1000V armoured fire-resistant electric cables having low emission of smoke and corrosive gases when affected by fire.

BS EN50288-7Multi-element metallic cables use in analogue and digital communication and control.Part 7: Sectional specification for instrumentation and control cables.

BS EN50525-2-31Single core non-sheathed cables with thermoplastic PVC insulation

BS EN50525-3-41Single core non-sheathed cables with halogen-free crosslinked insulation, and low emission of smoke

BS EN60228Conductors of insulated cables.

IEC60227-3Polyvinyl Chloride insulated cables of rated voltages up to and including 450 / 750V Part 3: Non-sheathed cables for fixed wiring.

IEC60228Conductors of insulated cables.

IEC60331Fire-resistant characteristics of electric cables.

IEC60332-1 / BS EN60332-1Tests in electric cables under fire conditions.Part 1: Method of test on a single vertical insulated wire or cable.

IEC60332-3-22 / BS EN60332-3-22Tests on electric and optical fibre cables under fire conditions.Part 3-22: Test for vertical flame spread of vertically-mounted bunched wires or cables (Category A).

IEC60332-3-24 / BS EN60332-3-24Tests on electric and optical fibre cables under fire conditions.Part 3-24: Test for vertical flame spread of vertically-mounted bunched wires or cables (Category C).

IEC60502-1Power cables with extruded insulation and their accessories for rated voltages from 1kV up to 30kV.Part 1: Cables for Rated Voltages of 1kV and 3kV.

IEC60754-1 / BS EN50267-2-1Tests on gases evolved during the combustion of materials from cables.Part 1: Methods of determination of amount of halogen acid gas evolved during combustion of polymeric materials taken from cables.

IEC60754-2 / BS EN50267-2-2Tests on gases evolved during combustion of materials from cables.Part 2: Determination of degree of acidity (corrosive) of gases by measuring pH and conductivity.

IEC61034-2 / BS EN61034-2Measurement of smoke density of electric cables burning under defined conditions.Part 2: Test procedure and requirements.

SS358-3Polyvinyl Chloride insulated cables of rated voltages up to and including 450 / 750V.Part 3: Non-sheathed cables for fixed wiring.

APPLICABLE STANDARDS

Below are the applicable standards that are used as reference in the construction of ourlow voltage cables.

www.taisin.com.sg | 3

Page 8: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

4 | www.taisin.com.sg

NominalConductor Area

(mm2)

No. and Diameterof Wires(no./mm)

Nominal Diameterof Conductor

(mm)

Maximum ConductorResistance at 20ºC

(Ω/km)

Nominal Weightper km of

Conductor (kg/km)

1.01.52.546

10162535507095

120150185240300400500630800

1000

7 / 0.437 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52

19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.5261 / 2.8561 / 3.20

127 / 2.52127 / 2.85127 / 3.20

1.291.592.012.553.124.055.106.427.568.90

10.7012.6014.2115.7517.6420.2522.6825.6528.8032.7637.0541.60

18.112.17.414.613.081.831.15

0.7270.5240.3870.2680.1930.1530.124

0.09910.0754 0.06010.04700.03660.02830.02210.0176

9.214.022.436.154.090.8

145.0229.0317.0429.0620.0860.0

1086.01334.01673.02199.02759.03528.04448.05744.07346.09260.0

Table 1

Bare Annealed CopperSTRANDED PLAIN ANNEALED COPPER CONDUCTOR ( SINGLE CORE )

IEC60228, BS EN 60228

CONSTRUCTIONConductor: Plain Annealed Copper, Class 2 Stranded

Circular or Compacted

Minimum Bending Radius: 3D for D < 10mm4D for 10mm ≤ D < 25mm6D for D ≥ 25mm

REFERENCE STANDARDSConductor: IEC60228, BS EN60228

Page 9: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

Component1. Plain Annealed Copper Wire

2. PV Compound

PVCCU / PVC ( SINGLE CORE )

PVC Insulated, Non-Sheathed Cable, 450 / 750V, SS358, BS EN50525-2-31, IEC60227

NominalConductor Area

(mm2)

No. and Diameterof Wires(no./mm)

Radial Thicknessof Insulation

(mm)

ApproximateWeight(kg/km)

SIN

GL

E C

OR

E

CONSTRUCTIONConductor: Plain Annealed Copper, Class 2

Stranded Circular or Compacted

Insulation: Polyvinyl Chloride (PVC)Compound Type C

Insulation Colour: Black, Green/Yellow, Red, Yellow,Blue, White, Brown, Grey or Others

ELECTRICAL CHARACTERISTICSOperating Voltage, Uo/U: 450/750V

Operating Temperature: -15ºC to 70ºC

Final Short Circuit Temperature: 160ºC for cable ≤ 300mm2

140ºC for cable >300mm2

Test Voltage: 2.5kV for 5 minutes

REFERENCE STANDARDSDesign Specification: SS358, BS EN50525-2-31, IEC60227

Conductor: IEC60228, BS EN60228

Flame Retardancy: IEC60332-1, BS EN60332-1

INSTALLATION REFERENCEMin. Bending Radius (mm): 6 x cable overall diameter

Max. Pulling Tension (N/mm2): 50

www.taisin.com.sg | 5

Mean Overall Diameter(Upper Limit)

(mm)

7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52

19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.5261 / 2.8561 / 3.20

127 / 2.52

0.70.80.80.81.01.01.21.21.41.41.61.61.82.02.22.42.62.82.8

3.44.24.85.46.88.09.8

11.013.015.017.019.021.023.526.529.533.537.041.0

22.734.050.070.9

117.5177.4282.0380.3515.8726.4

1002.91251.01538.71927.92522.63155.24018.05044.96443.4

1 x 1.51 x 2.51 x 41 x 6

1 x 101 x 161 x 251 x 351 x 501 x 701 x 95

1 x 1201 x 1501 x 1851 x 2401 x 3001 x 4001 x 5001 x 630

Table 2# For current rating and voltage drop, please refer to Table B1.1 and B2.1 on Page 66.

12

2

1

Page 10: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

12

PVCCU / PVC ( SWITCHBOARD WIRES SINGLE CORE )

PVC Insulated, Non-Sheathed Cable, 0.6 / 1kV, BS6231

NominalConductor Area

(mm2)

No. and Diameterof Wires(no./mm)

Radial Thicknessof Insulation

(mm)

ApproximateWeight(kg/km)

SIN

GL

E C

OR

E

1 x 0.51 x 0.751 x 1.01 x 1.51 x 2.51 x 41 x 6

1 x 101 x 161 x 251 x 351 x 501 x 701 x 95

1 x 1201 x 1501 x 1851 x 240

MinimumInsulation

Resistance at 70ºC(MΩ • km)

Mean OverallDiameter

(Upper Limit)(mm)

16 / 0.224 / 0.232 / 0.2

30 / 0.2550 / 0.2556 / 0.384 / 0.380 / 0.4

128 / 0.4200 / 0.4280 / 0.4400 / 0.4356 / 0.5485 / 0.5614 / 0.5765 / 0.5994 / 0.5

1125 / 0.5

0.80.80.80.80.80.80.81.01.01.21.21.41.41.61.61.82.02.2

2.62.83.03.33.74.34.96.37.49.1

10.312.213.816.117.619.722.323.9

11.314.517.523.034.050.271.0

119.3181.3280.9382.3544.1739.9

1005.21255.71565.62028.72304.1

0.01610.01410.01280.01110.00940.00770.00590.00580.00480.00470.00400.00390.00330.00320.00290.00290.00290.0028

CONSTRUCTIONConductor: Plain Annealed Copper, Class 5

Stranded Circular or Compacted

Insulation: Polyvinyl Chloride (PVC)Compound Type TI1

Insulation Colour: Black, Green/Yellow, Red, Yellow,Blue, White, Brown, Grey or Others

ELECTRICAL CHARACTERISTICSOperating Voltage, Uo/U: 0.6/1KV

Operating Temperature: -15ºC to 70ºC

Final Short Circuit Temperature: 160ºC

Test Voltage: 3.5kV for 5 minutes

REFERENCE STANDARDSDesign Specification: BS6231

Conductor: IEC60228, BS EN60228

Flame Retardancy: IEC60332-1, BS EN60332-1

INSTALLATION REFERENCEMin. Bending Radius (mm): 6 x cable overall diameter

Max. Pulling Tension (N/mm2): 50

6 | www.taisin.com.sg

Table 3# For current rating and voltage drop, please refer to Table B1.1 and B2.1 on Page 66.

Component1. Plain Annealed Copper Wire

2. PVC Compound

2

1

Page 11: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

www.taisin.com.sg | 7

Component1. Plain Annealed Copper Wire

2. PVC Compound3. PVC Compound

123

3

2

1

PPSCU / PVC / PVC ( SINGLE CORE )

PVC Insulated, PVC Sheathed Cable, 0.6/1kV, IEC60502

CONSTRUCTIONConductor: Plain Annealed Copper, Class 2

Stranded Circular or Compacted

Insulation: Polyvinyl Chloride (PVC)Compound Type A

Insulation Colour: Red or Black

Outer Sheath: Polyvinyl Chloride (PVC)Compound Type ST 1

Outer Sheath Colour: Grey

ELECTRICAL CHARACTERISTICSOperating Voltage, Uo/U: 0.6/1KV

Operating Temperature: -15ºC to 70ºC

Final Short Circuit Temperature: 160ºC for cable ≤ 300mm2

140ºC for cable >300mm2

Test Voltage: 3.5kV for 5 minutes

REFERENCE STANDARDSDesign Specification: IEC60502-1

Conductor: IEC60228, BS EN60228

Flame Retardancy: IEC60332-1, BS EN60332-1

INSTALLATION REFERENCEMin. Bending Radius (mm): 6 x cable overall diameter

Max. Pulling Tension (N/mm2): 50

NominalConductor Area

(mm2)

No. and Diameterof Wires(no./mm)

Radial Thicknessof Insulation

(mm)

Cable OverallDiameter

(mm)

ApproximateWeight(kg/km)

1 x 1.51 x 2.51 x 41 x 6

1 x 101 x 161 x 251 x 351 x 501 x 701 x 95

1 x 1201 x 1501 x 1851 x 2401 x 3001 x 4001 x 5001 x 6301 x 800

1 x 1000

7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52

19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.5261 / 2.8561 / 3.20

127 / 2.52127 / 2.85127 / 3.20

0.80.81.01.01.01.01.21.21.41.41.61.61.82.02.22.42.62.82.82.83.0

6.36.77.78.29.2

10.211.913.114.816.619.120.722.925.328.631.635.238.943.147.652.9

6880

108133180245357460604818

1113136316682077269233454228527566828407

10535

SIN

GL

E C

OR

E

Table 4# For current rating and voltage drop, please refer to Table B1.1 and B2.1 on Page 66.

Page 12: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

PPMCU / PVC / PVC ( 2 CORES - 5 CORES )

PVC Insulated, PVC Sheathed Cable, 0.6/1kV, IEC60502

CONSTRUCTIONConductor: Plain Annealed Copper, Class 2 Stranded

Circular, Compacted or Sectored

Insulation: Polyvinyl Chloride (PVC) CompoundType A

Insulation Colour: 2 Cores:Brown, Blue or Red, Black3 Cores:Brown, Black, Grey or Red, Yellow, Blue4 Cores:Brown, Black, Grey, Blue or Red, Yellow,Blue, Black5 Cores:Brown, Black, Grey, Blue, Green/Yellow orRed, Yellow, Blue, Black, Green/Yellow orWhite with Black numbering or Others

Assembly: Cores cabled together with filler andcovered with Polyester (PET) Tape

Outer Sheath: Polyvinyl Chloride (PVC) CompoundType ST 1

Outer Sheath Colour: Black

ELECTRICAL CHARACTERISTICSOperating Voltage, Uo/U: 0.6/1KV

Operating Temperature: -15ºC to 70ºC

Final Short Circuit Temperature: 160ºC for cable ≤ 300mm2

140ºC for cable >300mm2

Test Voltage: 3.5kV for 5 minutes

REFERENCE STANDARDSDesign Specification: IEC60502-1

Conductor: IEC60228, BS EN60228

Flame Retardancy: IEC60332-1, BS EN60332-1

INSTALLATION REFERENCEMin. Bending Radius (mm): 8 x cable overall diameter

Max. Pulling Tension (N/mm2): 50

NominalConductor Area

(mm2)

No. and Diameterof Wires(no./mm)

Radial Thicknessof Insulation

(mm)

Cable OverallDiameter

(mm)

ApproximateWeight(kg/km)

2 x 1.52 x 2.52 x 42 x 6

2 x 102 x 162 x 252 x 35

2 x 50 (S)2 x 70 (S)2 x 95 (S)

2 x 120 (S)2 x 150 (S)2 x 185 (S)2 x 240 (S)2 x 300 (S)

7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52

19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.52

0.80.81.01.01.01.01.21.21.41.41.61.61.82.02.22.4

10.411.213.314.416.318.421.824.124.126.830.633.136.740.645.350.1

153183250304409552789

100712781731232328513467430255366868

2 C

OR

ES

Table 5Note: (S) - Sectoral Stranded Conductors.# For current rating and voltage drop, please refer to Table B1.2 and B2.2 on Page 67.

Component1. Plain Annealed Copper Wire

2. PVC Compound3. PVC Compound

3

2

1

8 | www.taisin.com.sg

13 2

Page 13: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

www.taisin.com.sg | 9

NominalConductor Area

(mm2)

No. and Diameterof Wires(no./mm)

Radial Thicknessof Insulation

(mm)

Cable OverallDiameter

(mm)

ApproximateWeight(kg/km)

3 x 1.53 x 2.53 x 43 x 6

3 x 103 x 163 x 253 x 35

3 x 50 (S)3 x 70 (S)3 x 95 (S)

3 x 120 (S)3 x 150 (S)3 x 185 (S)3 x 240 (S)3 x 300 (S)3 x 400 (S)

4 x 1.54 x 2.54 x 44 x 6

4 x 104 x 164 x 254 x 35

4 x 50 (S)4 x 70 (S)4 x 95 (S)

4 x 120 (S)4 x 150 (S)4 x 185 (S)4 x 240 (S)4 x 300 (S)4 x 400 (S)4 x 500 (S)

5 x 1.55 x 2.55 x 45 x 6

5 x 105 x 165 x 255 x 355 x 505 x 705 x 95

5 x 1205 x 1505 x 1855 x 2405 x 300

7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52

19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.5261 / 2.85

7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52

19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.5261 / 2.8561 / 3.20

7 / 0.537 / 0677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52

19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.52

0.80.81.01.01.01.01.21.21.41.41.61.61.82.02.22.42.6

0.80.81.01.01.01.01.21.21.41.41.61.61.82.02.22.42.62.8

0.80.81.01.01.01.01.21.21.41.41.61.61.82.02.22.4

10.911.814.115.317.319.623.325.728.331.736.439.543.848.554.560.168.2

11.812.815.316.718.921.525.628.432.736.742.245.951.156.363.370.279.788.0

12.713.816.618.220.723.528.231.436.541.848.252.958.465.073.781.7

182223311388535737

107513891825249133784158506462928144

1008612800

216267379477669932

13721785238832694437546966908287

10766133731696821161

250313448569804

11291672219829464068550668208306

103311342516683

3 C

OR

ES

PPMCU / PVC / PVC ( 2 CORES - 5 CORES )

PVC Insulated, PVC Sheathed Cable, 0.6/1kV, IEC60502

Table 6Note: (S) - Sectoral Stranded Conductors.# For current rating and voltage drop, please refer to Table B1.2 and B2.2 on Page 67.

4 C

OR

ES

5 C

OR

ES

Page 14: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

Component1. Plain Annealed Copper Wire

2. PVC Compound3. PVC Compound

123

PCCCU / PVC / PVC ( MULTI-CORES )

PVC Insulated, PVC Sheathed Cable, 0.6/1kV, BS6346

CONSTRUCTIONConductor: Plain Annealed Copper, Class 2

Stranded Circular or Compacted

Insulation: Polyvinyl Chloride (PVC) CompoundType TI1

Insulation Colour: 2 Cores:Brown, Blue or Red, Black3 Cores:Brown, Black, Grey or Red, Yellow, Blue4 Cores:Brown, Black, Grey, Blue or Red, Yellow,Blue, Black5 Cores:Brown, Black, Grey, Blue, Green/Yellow orRed, Yellow, Blue, Black, Green/ Yellow orWhite with Black numbering or Others7 Cores & above:White with Black numbering or Others

Assembly: Cores cabled together and covered withPolyester (PET) Tape

Outer Sheath: Polyvinyl Chloride (PVC) CompoundType TM 1

Outer Sheath Colour: Black

ELECTRICAL CHARACTERISTICSOperating Voltage, Uo/U: 0.6/1KV

Operating Temperature: -15ºC to 70ºC

Final Short Circuit Temperature: 160ºC

Test Voltage: 3.5kV for 5 minutes

REFERENCE STANDARDSDesign Specification: BS6346, In-House

Conductor: IEC60228, BS EN60228

Flame Retardancy: IEC60332-1, BS EN60332-1

INSTALLATION REFERENCEMin. Bending Radius (mm): 8 x cable overall diameter

Max. Pulling Tension (N/mm2): 50

NominalConductor Area

(mm2)

No. and Diameterof Wires(no./mm)

Radial Thicknessof Insulation

(mm)

Cable OverallDiameter

(mm)

ApproximateWeight(kg/km)

MU

LTI-

CO

RE

S

23457

101219202437

No. of Cores

1.5

7 / 0.537 / 0.537 / 0.537 / 0.537 / 0.537 / 0.537 / 0.537 / 0.537 / 0.537 / 0.537 / 0.53

0.60.60.60.60.60.60.60.60.60.60.6

8.99.3

10.110.911.915.015.418.119.221.124.2

129157189221280390441640684801

1149

Table 7Note: Other conductor sizes and core configurations are available upon request.# For current rating and voltage drop, please refer to Table B1.2 and B2.2 on Page 67.

10 | www.taisin.com.sg

3

2

1

Page 15: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

www.taisin.com.sg | 11

PCCCU / PVC / PVC ( MULTI-CORES )

PVC Insulated, PVC Sheathed Cable, 0.6/1kV, BS6346

NominalConductor Area

(mm2)

No. and Diameterof Wires(no./mm)

Radial Thicknessof Insulation

(mm)

Cable OverallDiameter

(mm)

ApproximateWeight(kg/km)

MU

LTI-

CO

RE

S

23457

101219202437

23457

101219202437

No. of Cores

2.5

4

7 / 0.677 / 0.677 / 0.677 / 0.677 / 0.677 / 0.677 / 0.677 / 0.677 / 0.677 / 0.677 / 0.67

7 / 0.857 / 0.857 / 0.857 / 0.857 / 0.857 / 0.857 / 0.857 / 0.857 / 0.857 / 0.857 / 0.85

0.70.70.70.70.70.70.70.70.70.70.7

0.80.80.80.80.80.80.80.80.80.80.8

10.511.112.013.014.117.618.221.422.725.128.8

12.012.713.815.016.420.821.525.327.129.934.4

177219266313399548626918979

11511667

232294361430556780896

1329142616812454

Table 8Note: Other conductor sizes and core configurations are available upon request.# For current rating and voltage drop, please refer to Table B1.2 and B2.2 on Page 67.

Page 16: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

12 | www.taisin.com.sg

Component1. Plain Annealed Copper Wire

2. PVC Compound3. PVC Compound

4. Aluminium Wire Armoured5. PVC Compound

12345

PAPCU / PVC / PVC / AWA / PVC ( SINGLE CORE )

PVC Insulated, PVC Bedded, Aluminium Wire Armoured, PVC Sheathed Cable, 0.6 / 1kV,BS6346 (Specification Withdrawn)

CONSTRUCTIONConductor: Plain Annealed Copper, Class 2 Stranded

Circular or Compacted

Insulation: Polyvinyl Chloride (PVC) CompoundType TI1

Insulation Colour: Black

Bedding: Polyvinyl Chloride (PVC) CompoundType TM 1

Bedding Colour: Black

Armour: Aluminium Wire Armoured (AWA)

Outer Sheath: Polyvinyl Chloride (PVC) CompoundType TM 1

Outer Sheath Colour: Black

ELECTRICAL CHARACTERISTICSOperating Voltage, Uo/U: 0.6/1KV

Operating Temperature: -15ºC to 70ºC

Final Short Circuit Temperature: 160ºC for cable ≤ 300mm2

140ºC for cable >300mm2

Test Voltage: 3.5kV for 5 minutes

REFERENCE STANDARDSDesign Specification: BS6346 (Specification Withdrawn)

Conductor: IEC60228, BS EN60228

Flame Retardancy: IEC60332-1, BS EN60332-1

INSTALLATION REFERENCEMin. Bending Radius (mm): 8 x cable overall diameter

Max. Pulling Tension (N/mm2): 50

5

4

3

2

1

NominalConductor Area

(mm2)

No. andDiameterof Wires(no./mm)

RadialThickness

of Insulation(mm)

Cable OverallDiameter

(mm)

ApproximateWeight(kg/km)

1 x 501 x 701 x 95

1 x 1201 x 1501 x 1851 x 2401 x 3001 x 4001 x 5001 x 6301 x 800

1 x 1000

19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.5261 / 2.8561 / 3.20

127 / 2.52127 / 2.85127 / 3.20

1.41.41.61.61.82.02.22.42.62.82.82.83.0

19.121.123.426.328.330.734.036.841.845.349.555.660.7

16910181328168620062443310137194861595674539523

11749

SIN

GL

E C

OR

E

Table 9# For current rating and voltage drop, please refer to Table B1.3 and B2.3 on Page 68.

DiameterUnder Armour

(mm)

Armour Wire Diameter

(mm)

13.515.317.619.621.623.826.929.733.537.041.045.750.6

1.251.251.251.601.601.601.601.602.002.002.002.502.50

Page 17: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

www.taisin.com.sg | 13

PSPCU / PVC / PVC / SWA / PVC ( 2 CORES - 5 CORES )

PVC Insulated, PVC Bedded, Galvanised Steel Wire Armoured, PVC Sheathed Cable,0.6 / 1kV, BS6346 (Specification Withdrawn)

Component1. Plain Annealed Copper Wire

2. PVC Compound3. PVC Compound

4. Galvanised Steel Wire Armoured5. PVC Compound

12345

CONSTRUCTIONConductor: Plain Annealed Copper, Class 2 Stranded

Circular, Compacted or Sectored

Insulation: Polyvinyl Chloride (PVC) CompoundType TI1

Insulation Colour: 2 Cores:Brown, Blue or Red, Black3 Cores:Brown, Black, Grey or Red, Yellow, Blue4 Cores:Brown, Black, Grey, Blue or Red, Yellow,Blue, Black5 Cores :Brown, Black, Grey, Blue, Green/Yellow orRed, Yellow, Blue, Black, Green/Yellow orWhite with Black numbering or Others

Assembly: Cores cabled together with filler andcovered with Polyester (PET) Tape

Bedding: Polyvinyl Chloride (PVC) CompoundType TM 1

Bedding Colour: Black

Armour: Galvanized Steel Wire Armoured (SWA)

Outer Sheath: Polyvinyl Chloride (PVC) CompoundType TM 1

Outer Sheath Colour: Black

ELECTRICAL CHARACTERISTICSOperating Voltage, Uo/U: 0.6/1KV

Operating Temperature: -15ºC to 70ºC

Final Short Circuit Temperature: 160ºC for cable ≤ 300mm2

140ºC for cable >300mm2

Test Voltage: 3.5kV for 5 minutes

REFERENCE STANDARDSDesign Specification: BS6346 (Specification Withdrawn)

Conductor: IEC60228, BS EN60228

Flame Retardancy: IEC60332-1, BS EN60332-1

INSTALLATION REFERENCEMin. Bending Radius (mm): 8 x cable overall diameter

Max. Pulling Tension (N/mm2): 70

5

4

3

2

1

NominalConductor Area

(mm2)

No. andDiameterof Wires(no./mm)

RadialThickness

of Insulation(mm)

Cable OverallDiameter

(mm)

ApproximateWeight(kg/km)

2 x 1.52 x 2.52 x 42 x 6

2 x 102 x 162 x 252 x 35

2 x 50 (S)2 x 70 (S)2 x 95 (S)

2 x 120 (S)2 x 150 (S)2 x 185 (S)2 x 240 (S)2 x 300 (S)

7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52

19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.52

0.60.70.80.81.01.01.21.21.41.41.61.61.82.02.22.4

12.313.515.016.319.922.026.729.228.331.335.138.141.646.452.356.7

265319392471745933

1435173020532613352741804939627180688635

2 C

OR

ES

Table 10Note: (S) - Sectoral Stranded Conductors.# For current rating and voltage drop, please refer to Table B1.4 and B2.4 on Page 69.

DiameterUnder Armour

(mm)

ArmourWire Diameter

(mm)

7.58.7

10.211.314.016.119.922.221.224.226.829.632.936.542.246.2

0.900.900.900.901.251.251.601.601.601.602.002.002.002.502.502.50

Page 18: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

14 | www.taisin.com.sg

PSPCU / PVC / PVC / SWA / PVC ( 2 CORES - 5 CORES )

PVC Insulated, PVC Bedded, Galvanised Steel Wire Armoured, PVC Sheathed Cable,0.6 / 1kV, BS6346 (Specification Withdrawn)

NominalConductor Area

(mm2)

No. andDiameterof Wires(no./mm)

RadialThickness

of Insulation(mm)

Cable OverallDiameter

(mm)

ApproximateWeight(kg/km)

Table 11Note: (S) - Sectoral Stranded Conductors.# For current rating and voltage drop, please refer to Table B1.4 and B2.4 on Page 69.

3 x 1.53 x 2.53 x 43 x 6

3 x 103 x 163 x 253 x 35

3 x 50 (S)3 x 70 (S)3 x 95 (S)

3 x 120 (S)3 x 150 (S)3 x 185 (S)3 x 240 (S)3 x 300 (S)3 x 400 (S)

4 x 1.54 x 2.54 x 44 x 6

4 x 104 x 164 x 254 x 35

4 x 50 (S)4 x 70 (S)4 x 95 (S)

4 x 120 (S)4 x 150 (S)4 x 185 (S)4 x 240 (S)4 x 300 (S)4 x 400 (S)

5 x 1.55 x 2.55 x 45 x 6

5 x 105 x 165 x 255 x 355 x 505 x 70

7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52

19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.5261 / 2.85

7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52

19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.5261 / 2.85

7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52

19 / 1.7819 / 2.14

0.60.70.80.81.01.01.21.21.41.41.61.61.82.02.22.42.6

0.60.70.80.81.01.01.21.21.41.41.61.61.82.02.22.42.6

0.60.70.80.81.01.01.21.21.41.4

12.714.115.717.820.923.228.230.831.035.739.442.648.254.459.764.072.9

13.515.017.719.122.526.330.733.634.038.242.146.954.259.066.372.683.3

14.316.218.920.625.528.333.437.343.048.0

293363454644884

114117462155266637094710563471448894

110041318216480

344416629752

104915542131264034744533582774079238

11108139501692121961

376483716870

138918102520313743775669

3 C

OR

ES

5 C

OR

ES

DiameterUnder Armour

(mm)

ArmourWire Diameter

(mm)

7.99.3

10.912.115.017.321.423.823.827.531.034.038.244.249.353.251.7

8.710.212.013.416.619.523.726.425.829.833.536.944.048.655.561.470.7

9.511.213.214.718.721.526.229.334.639.4

0.900.900.901.251.251.251.601.601.602.002.002.002.502.502.502.502.50

0.900.901.251.251.251.601.601.602.002.002.002.502.502.502.502.503.15

0.900.901.251.251.601.601.601.602.002.00

4 C

OR

ES

Page 19: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

www.taisin.com.sg | 15

PSPCU / PVC / PVC / SWA / PVC ( MULTI-CORES )

PVC Insulated, PVC Bedded, Galvanised Steel Wire Armoured, PVC Sheathed Cable,0.6 / 1kV, BS6346 (Specification Withdrawn)

12345

CONSTRUCTIONConductor: Plain Annealed Copper, Class 2 Stranded

Circular or Compacted

Insulation: Polyvinyl Chloride (PVC) CompoundType TI1

Insulation Colour: White with Black numbering or Others

Assembly: Cores cabled together and covered withPolyester (PET) Tape

Bedding: Polyvinyl Chloride (PVC) CompoundType TM 1

Bedding Colour: Black

Armour: Galvanized Steel Wire Armoured (SWA)

Outer Sheath: Polyvinyl Chloride (PVC) CompoundType TM 1

Outer Sheath Colour: Black

ELECTRICAL CHARACTERISTICSOperating Voltage, Uo/U: 0.6/1KV

Operating Temperature: -15ºC to 70ºC

Final Short Circuit Temperature: 160ºC

Test Voltage: 3.5kV for 5 minutes

REFERENCE STANDARDSDesign Specification: BS6346 (Specification Withdrawn)

Conductor: IEC60228, BS EN60228

Flame Retardancy: IEC60332-1, BS EN60332-1

INSTALLATION REFERENCEMin. Bending Radius (mm): 8 x cable overall diameter

Max. Pulling Tension (N/mm2): 70

NominalConductor

Area(mm2)

No. andDiameterof Wires(no./mm)

RadialThickness

of Insulation(mm)

Cable OverallDiameter

(mm)

ApproximateWeight(kg/km)

No. of Cores

Table 12Note: Other conductor sizes and core configurations are available upon request.# For current rating and voltage drop, please refer to Table B1.4 and B2.4 on Page 69.

MU

LTI-

CO

RE

S

57

101219202437

1.5

7 / 0.537 / 0.537 / 0.537 / 0.537 / 0.537 / 0.537 / 0.537 / 0.53

0.60.60.60.60.60.60.60.6

14.315.219.019.422.223.626.229.3

390458706763

1006122013991804

DiameterUnder Armour

(mm)

ArmourWire Diameter

(mm)

Component1. Plain Annealed Copper Wire

2. PVC Compound3. PVC Compound

4. Galvanised Steel Wire Armoured5. PVC Compound

5

4

3

2

1

9.510.413.313.716.217.519.422.3

0.90.9

1.251.251.251.61.61.6

Page 20: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

16 | www.taisin.com.sg

PSPCU / PVC / PVC / SWA / PVC ( MULTI-CORES )

PVC Insulated, PVC Bedded, Galvanised Steel Wire Armoured, PVC Sheathed Cable,0.6 / 1kV, BS6346 (Specification Withdrawn)

NominalConductor

Area(mm2)

No. andDiameterof Wires(no./mm)

RadialThickness

of Insulation(mm)

Cable OverallDiameter

(mm)

ApproximateWeight(kg/km)

No. of Cores

Table 13Note: Other conductor sizes and core configurations are available upon request.# For current rating and voltage drop, please refer to Table B1.4 and B2.4 on Page 69.

MU

LTI-

CO

RE

S

57

101219202437

57

101219202437

2.5

4

7 / 0.677 / 0.677 / 0.677 / 0.677 / 0.677 / 0.677 / 0.677 / 0.67

7 / 0.857 / 0.857 / 0.857 / 0.857 / 0.857 / 0.857 / 0.857 / 0.85

0.70.70.70.70.70.70.70.7

0.80.80.80.80.80.80.80.8

16.518.221.722.326.627.930.334.0

19.220.526.427.130.932.735.540.8

589694920

10021519161218542451

755903

156016952261241127553674

DiameterUnder Armour

(mm)

ArmourWire Diameter

(mm)

11.212.215.716.319.720.823.226.7

13.214.519.520.223.825.228.032.3

1.251.251.251.251.61.61.61.6

1.251.252.02.02.02.02.02.0

Page 21: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

www.taisin.com.sg | 17

FLEXI-IMP( SINGLE CORE, 2 CORES - 4 CORES )

PVC Insulated Flexible Cable, PVC Insulated PVC Sheathed Flexible Cable,250V / 440V, Imperial Unit BS 2004

CONSTRUCTIONConductor: Plain Annealed Copper, Class 5 Stranded

Circular

Insulation: Polyvinyl Chloride (PVC) CompoundType TI1

Insulation Colour: Single Core:Black, Blue, White, Brown, Green, Grey orOthers2 Cores:Blue,Brown3 Cores:Blue, Brown, Green/Yellow4 Cores:Blue, Brown, Black, Green/Yellow

Outer Sheath: Polyvinyl Chloride (PVC) Compound(For 2, 3, 4 cores only) Type T6

Outer Sheath Colour: Grey(For 2, 3, 4 cores only)

ELECTRICAL CHARACTERISTICSOperating Voltage, Uo/U: 250/440V

Operating Temperature: -15ºC to 70ºC

Final Short Circuit Temperature: 160ºC

Test Voltage: 1.5kV for 5 minutes

REFERENCE STANDARDSDesign Specification: BS2004 (Specification Withdrawn)

Conductor: BS3360, BS EN60228

Flame Retardancy: IEC60332-1, BS EN60332-1

INSTALLATION REFERENCEMin. Bending Radius (mm): 5D for D < 10mm

6D for 10mm ≤ D < 25mm

Max. Pulling Tension (N/mm2): 15

NominalConductor Area

(mm2)

No. and Diameterof Wire(no./in)

Radial Thicknessof Insulation

(mm)

Cable OverallDiameter

(mm)

ApproximateWeight

(kg/100yd)

1 x 0.411 x 0.871 x 1.171 x 2.051 x 3.221 x 4.74

2 x 0.412 x 0.872 x 1.172 x 2.052 x 3.222 x 4.74

3 x 0.413 x 0.873 x 1.173 x 2.053 x 3.223 x 4.74

4 x 0.414 x 0.874 x 1.174 x 2.054 x 3.224 x 4.74

14 / 0.007623 / 0.007640 / 0.007670 / 0.0076

110 / 0.0076162 / 0.0076

14 / 0.007623 / 0.007640 / 0.007670 / 0.0076

110 / 0.0076162 / 0.0076

14 / 0.007623 / 0.007640 / 0.007670 / 0.0076

110 / 0.0076162 / 0.0076

14 / 0.007623 / 0.007640 / 0.007670 / 0.0076

110 / 0.0076162 / 0.0076

0.640.640.640.640.640.78

0.640.640.640.640.640.78

0.640.640.640.640.640.78

0.640.640.640.640.640.78

2.42.73.03.53.94.8

6.77.17.89.4

10.311.7

7.07.58.39.9

11.013.2

7.68.19.7

10.711.914.0

1.01.31.82.73.85.5

5.16.07.7

11.515.020.5

5.77.09.1

13.818.226.6

6.78.3

12.116.722.231.2

SIN

GL

E C

OR

E

Table 14

2 C

OR

ES

3 C

OR

ES

4 C

OR

ES

Page 22: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

18 | www.taisin.com.sg

XPCU / XLPE / PVC ( SINGLE CORE )

XLPE Insulated, PVC Sheathed Cable, 0.6 / 1kV, IEC60502

Component1. Plain Annealed Copper Wire

2. Cross-linked PolyethyleneCompound

3. PVC Compound

123

3

2

1

CONSTRUCTIONConductor: Plain Annealed Copper, Class 2

Stranded Circular or Compacted

Insulation: Cross-linked Polyethylene (XLPE)Compound

Insulation Colour: Natural

Outer Sheath: Polyvinyl Chloride (PVC)Compound Type ST2

Outer Sheath Colour: Black

ELECTRICAL CHARACTERISTICSOperating Voltage, Uo/U: 0.6/1KV

Operating Temperature: -15ºC to 90ºC

Final Short Circuit Temperature: 250ºC

Test Voltage: 3.5kV for 5 minutes

REFERENCE STANDARDSDesign Specification: IEC60502-1

Conductor: IEC60228, BS EN60228

Flame Retardancy: IEC60332-1, BS EN60332-1

INSTALLATION REFERENCEMin. Bending Radius (mm): 8 x cable overall diameter

Max. Pulling Tension (N/mm2): 50

NominalConductor Area

(mm2)

No. and Diameterof Wires(no./mm)

Radial Thicknessof Insulation

(mm)

Cable OverallDiameter

(mm)

ApproximateWeight(kg/km)

1 x 161 x 251 x 351 x 501 x 701 x 95

1 x 1201 x 1501 x 1851 x 2401 x 3001 x 4001 x 5001 x 6301 x 800

1 x 1000

7 / 1.707 / 2.147 / 2.52

19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.5261 / 2.8561 / 3.20

127 / 2.52127 / 2.85127 / 3.20

0.70.90.91.01.11.11.21.41.61.71.82.02.22.42.62.8

9.611.312.514.116.118.220.022.224.427.530.333.937.642.447.352.4

225338443582814

1097136516762081270033554262533868578701

10891

SIN

GL

E C

OR

E

Table 15# For current rating and voltage drop, please refer to Table B1.5 and B2.5 on Page 70.

Page 23: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

www.taisin.com.sg | 19

NominalConductor Area

(mm2)

No. and Diameterof Wires(no./mm)

Radial Thicknessof Insulation

(mm)

Cable OverallDiameter

(mm)

ApproximateWeight(kg/km)

2 x 1.52 x 2.52 x 42 x 6

2 x 102 x 162 x 252 x 35

2 x 50 (S)2 x 70 (S)2 x 95 (S)

2 x 120 (S)2 x 150 (S)2 x 185 (S)2 x 240 (S)2 x 300 (S)

7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52

19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.25 37 / 2.5261 / 2.2561 / 2.52

0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.8

10.010.811.913.014.917.020.422.722.425.428.231.234.938.143.247.4

123153197252358505754984

12371711228728563523438756787028

2 C

OR

ES

Table 16Note: (S) - Sectoral Stranded Conductors.# For current rating and voltage drop, please refer to Table B1.6 and B2.6 on Page 71.

XPCU / XLPE / PVC ( 2 CORES - 5 CORES )

XLPE Insulated, PVC Sheathed Cable, 0.6 / 1kV, IEC60502

Component1. Plain Annealed Copper Wire

2. Cross-linked PolyethyleneCompound

3. PVC Compound

123

CONSTRUCTIONConductor: Plain Annealed Copper, Class 2 Stranded

Circular, Compacted or Sectored

Insulation: Cross-linked Polyethylene (XLPE)Compound

Insulation Colour: 2 Cores:Brown, Blue or Red, Black3 Cores:Brown, Black, Grey or Red, Yellow, Blue4 Cores:Brown, Black, Grey, Blue or Red, Yellow,Blue, Black5 Cores:Brown, Black, Grey, Blue, Green/ Yellow orRed, Yellow, Blue, Black, Green/Yellow orWhite with Black numbering or Others

Assembly: Cores cabled together with filler andcovered with Polyester (PET) Tape

Outer Sheath: Polyvinyl Chloride (PVC) CompoundType ST2

Outer Sheath Colour: Black

ELECTRICAL CHARACTERISTICSOperating Voltage, Uo/U: 0.6/1KV

Operating Temperature: -15ºC to 90ºC

Final Short Circuit Temperature: 250ºC

Test Voltage: 3.5kV for 5 minutes

REFERENCE STANDARDSDesign Specification: IEC60502-1

Conductor: IEC60228, BS EN60228

Flame Retardancy: IEC60332-1, BS EN60332-1

INSTALLATION REFERENCEMin. Bending Radius (mm): 8 x cable overall diameter

Max. Pulling Tension (N/mm2): 50

3

2

1

Page 24: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

20 | www.taisin.com.sg

XPCU / XLPE / PVC ( 2 CORES - 5 CORES )

XLPE Insulated, PVC Sheathed Cable, 0.6 / 1kV, IEC60502

NominalConductor Area

(mm2)

No. and Diameterof Wires(no./mm)

Radial Thicknessof Insulation

(mm)

Cable OverallDiameter

(mm)

ApproximateWeight(kg/km)

3 x 1.53 x 2.53 x 43 x 6

3 x 103 x 163 x 253 x 35

3 x 50 (S)3 x 70 (S)3 x 95 (S)

3 x 120 (S)3 x 150 (S)3 x 185 (S)3 x 240 (S)3 x 300 (S)3 x 400 (S)

4 x 1.54 x 2.54 x 44 x 6

4 x 104 x 164 x 254 x 35

4 x 50 (S)4 x 70 (S)4 x 95 (S)

4 x 120 (S)4 x 150 (S)4 x 185 (S)4 x 240 (S)4 x 300 (S)4 x 400 (S)4 x 500 (S)

5 x 1.55 x 2.55 x 45 x 6

5 x 105 x 165 x 255 x 355 x 505 x 705 x 95

5 x 1205 x 1505 x 1855 x 2405 x 300

7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52

19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.5261 / 2.85

7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52

19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.5261 / 2.8561 / 3.20

7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52

19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.52

0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.82.0

0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.82.02.2

0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.8

10.511.412.513.815.818.121.824.225.028.932.635.840.445.050.554.663.7

11.312.313.615.017.219.823.926.727.031.435.339.144.849.857.163.472.880.8

12.113.314.716.618.821.626.329.334.240.045.350.656.262.870.878.3

150190252328477684

103513641766248033384166514764248335

1029713234

182233312411605876

13341766228432314354546367558446

11016137171755821991

214278375496737

10721640217628494170561770568680

108601409317520

3 C

OR

ES

Table 17Note: (S) - Sectoral Stranded Conductors.# For current rating and voltage drop, please refer to Table B1.6 and B2.6 on Page 71.

4 C

OR

ES

5 C

OR

ES

Page 25: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

www.taisin.com.sg | 21

XPCU / XLPE / PVC ( MULTI-CORES )

XLPE Insulated, PVC Sheathed Cable, 0.6 / 1kV, IEC60502

Component1. Plain Annealed Copper Wire

2. Cross-linked PolyethyleneCompound

3. PVC Compound

123

CONSTRUCTIONConductor: Plain Annealed Copper, Class 2 Stranded

Circular or Compacted

Insulation: Cross-linked Polyethylene (XLPE)Compound

Insulation Colour: White with Black numbering or Others

Assembly: Cores cabled together and covered withPolyester (PET) Tape

Outer Sheath: Polyvinyl Chloride (PVC) CompoundType ST2

Outer Sheath Colour: Black

ELECTRICAL CHARACTERISTICSOperating Voltage, Uo/U: 0.6/1KV

Operating Temperature: -15ºC to 90ºC

Final Short Circuit Temperature: 250ºC

Test Voltage: 3.5kV for 5 minutes

REFERENCE STANDARDSDesign Specification: IEC60502-1

Conductor: IEC60228, BS EN60228

Flame Retardancy: IEC60332-1, BS EN60332-1

INSTALLATION REFERENCEMin. Bending Radius (mm): 8 x cable overall diameter

Max. Pulling Tension (N/mm2): 50

57

101219202437

1.5

7 / 0.537 / 0.537 / 0.537 / 0.537 / 0.537 / 0.537 / 0.537 / 0.53

0.70.70.70.70.70.70.70.7

12.113.316.416.919.520.522.525.6

214278391441635676801

1142

Table 18Note: Other conductor sizes and core configurations are available upon request.# For current rating and voltage drop, please refer to Table B1.6 and B2.6 on Page 71.

NominalConductor Area

(mm2)

No. and Diameterof Wires(no./mm)

Radial Thicknessof Insulation

(mm)

Cable OverallDiameter

(mm)

ApproximateWeight(kg/km)

No. of Cores

MU

LTI-

CO

RE

S

3

2

1

Page 26: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

22 | www.taisin.com.sg

XPCU / XLPE / PVC ( MULTI-CORES )

XLPE Insulated, PVC Sheathed Cable, 0.6 / 1kV, IEC60502

57

101219202437

57

101219202437

2.5

4

7 / 0.677 / 0.677 / 0.677 / 0.677 / 0.677 / 0.677 / 0.677 / 0.67

7 / 0.857 / 0.857 / 0.857 / 0.857 / 0.857 / 0.857 / 0.857 / 0.85

0.70.70.70.70.70.70.70.7

0.70.70.70.70.70.70.70.7

13.314.518.018.621.622.725.128.6

14.716.220.220.824.325.628.332.6

278364574586856910

10821560

375496705809

1199127315192229

NominalConductor Area

(mm2)

No. and Diameterof Wires(no./mm)

Radial Thicknessof Insulation

(mm)

Cable OverallDiameter

(mm)

ApproximateWeight(kg/km)

No. of Cores

MU

LTI-

CO

RE

S

Table 19Note: Other conductor sizes and core configurations are available upon request.# For current rating and voltage drop, please refer to Table B1.6 and B2.6 on Page 71.

Page 27: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

www.taisin.com.sg | 23

NominalConductor Area

(mm2)

No. andDiameterof Wires(no./mm)

RadialThickness

of Insulation(mm)

Cable OverallDiameter

(mm)

ApproximateWeight(kg/km)

1 x 501 x 701 x 95

1 x 1201 x 1501 x 1851 x 2401 x 3001 x 4001 x 5001 x 6301 x 800

1 x 1000

SIN

GL

E C

OR

E

Table 20# For current rating and voltage drop, please refer to Table B1.7 and B2.7 on Page 72.

ArmourWire Diameter

(mm)

DiameterUnder Armour

(mm)

19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.5261 / 2.8561 / 3.20

127 / 2.52127 / 2.85127 / 3.20

1.01.11.11.21.41.61.71.82.02.22.42.62.8

13.215.217.118.920.923.126.028.632.435.940.345.450.3

1.251.251.251.61.61.61.61.62.02.02.02.52.5

19.521.523.425.927.930.133.235.840.844.549.155.660.9

89711501444178721052535317838404921602975519646

11897

XAPCU / XLPE / PVC / AWA / PVC ( SINGLE CORE )

XLPE Insulated, PVC Bedded, Aluminium Wire Armoured, PVC Sheathed Cable,0.6 / 1kV, IEC60502

Component1. Plain Annealed Copper Wire

2. Cross-linked Polyethylene Compound3. PVC Compound

4. Aluminium Wire Armoured5. PVC Compound

12345

CONSTRUCTIONConductor: Plain Annealed Copper, Class 2 Stranded

Circular or Compacted

Insulation: Cross-linked Polyethylene (XLPE)Compound

Insulation Colour: Natural

Bedding: Polyvinyl Chloride (PVC) CompoundType ST2

Bedding Coolur: Black

Armour: Aluminium Wire Armoured (AWA)

Outer Sheath: Polyvinyl Chloride (PVC) CompoundType ST2

Outer Sheath Colour: Black

ELECTRICAL CHARACTERISTICSOperating Voltage, Uo/U: 0.6/1KV

Operating Temperature: -15ºC to 90ºC

Final Short Circuit Temperature: 250ºC

Test Voltage: 3.5kV for 5 minutes

REFERENCE STANDARDSDesign Specification: IEC60502-1

Conductor: IEC60228, BS EN60228

Flame Retardancy: IEC60332-1, BS EN60332-1

INSTALLATION REFERENCEMin. Bending Radius (mm): 8 x cable overall diameter

Max. Pulling Tension (N/mm2): 50

5

4

3

2

1

Page 28: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

24 | www.taisin.com.sg

Component1. Plain Annealed Copper Wire

2. Cross-linked Polyethylene Compound3. PVC Compound

4. Galvanised Steel Wire Armoured5. PVC Compound

12345

5

4

3

2

1

XSPCU / XLPE / PVC / SWA / PVC ( 2 CORES - 5 CORES )

XLPE Insulated, PVC Bedded, Galvanised Steel Wire Armoured, PVC Sheathed Cable,0.6 / 1kV, IEC60502

CONSTRUCTIONConductor: Plain Annealed Copper, Class 2 Stranded

Circular, Compacted or Sectored

Insulation: Cross-linked Polyethylene (XLPE)Compound

Insulation Colour: 2 Cores:Brown, Blue or Red, Black3 Cores:Brown, Black, Grey or Red, Yellow, Blue4 Cores:Brown, Black, Grey, Blue or Red, Yellow,Blue, Black5 Cores:Brown, Black, Grey, Blue, Green/Yellow orRed, Yellow, Blue, Black, Green/Yellow orWhite with Black numbering or Others

Assembly: Cores cabled together with filler andcovered with Polyester (PET) Tape

Bedding: Polyvinyl Chloride (PVC) Compound TypeST2 or ST2 PVC Tape

Bedding Colour: Black

Armour: Galvanized Steel Wire Armoured (SWA)

Outer Sheath: Polyvinyl Chloride (PVC) CompoundType ST2

Outer Sheath Colour: Black

ELECTRICAL CHARACTERISTICSOperating Voltage, Uo/U: 0.6/1kV

Operating Temperature: -15ºC to 90ºC

Final Short Circuit Temperature: 250ºC

Test Voltage: 3.5kV for 5 minutes

REFERENCE STANDARDSDesign Specification: IEC60502-1

Conductor: IEC60228, BS EN60228

Flame Retardancy: IEC60332-1, BS EN60332-1

INSTALLATION REFERENCEMin. Bending Radius (mm): 8 x cable overall diameter

Max. Pulling Tension (N/mm2): 70

NominalConductor Area

(mm2)

No. andDiameterof Wires(no./mm)

RadialThickness

of Insulation(mm)

Cable OverallDiameter

(mm)

ApproximateWeight(kg/km)

2 x 1.52 x 2.52 x 42 x 6

2 x 102 x 162 x 252 x 35

2 x 50 (S)2 x 70 (S)2 x 95 (S)

2 x 120 (S)2 x 150 (S)2 x 185 (S)2 x 240 (S)2 x 300 (S)

2 C

OR

ES

Table 21Note: (S) - Sectoral Stranded Conductors.# For current rating and voltage drop, please refer to Table B1.8 and B2.8 on Page 73.

ArmourWire Diameter

(mm)

DiameterUnder Armour

(mm)

7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52

19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.52

0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.8

8.39.1

10.211.313.215.318.721.021.224.226.829.632.936.542.246.2

0.90.90.90.9

1.251.251.61.61.62.02.02.02.02.52.52.5

13.914.715.816.919.521.625.728.028.331.735.338.341.846.852.957.1

445498573658913

11221603192121322736362642955065643482599793

Page 29: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

www.taisin.com.sg | 25

XSPCU / XLPE / PVC / SWA / PVC ( 2 CORES - 5 CORES )

XLPE Insulated, PVC Bedded, Galvanised Steel Wire Armoured, PVC Sheathed Cable,0.6 / 1kV, IEC60502

NominalConductor Area

(mm2)

No. andDiameterof Wires(no./mm)

RadialThickness

of Insulation(mm)

Cable OverallDiameter

(mm)

ApproximateWeight(kg/km)

3 x 1.53 x 2.53 x 43 x 6

3 x 103 x 163 x 253 x 35

3 x 50 (S)3 x 70 (S)3 x 95 (S)

3 x 120 (S)3 x 150 (S)3 x 185 (S)3 x 240 (S)3 x 300 (S)3 x 400 (S)

4 x 1.54 x 2.54 x 44 x 6

4 x 104 x 164 x 254 x 35

4 x 50 (S)4 x 70 (S)4 x 95 (S)

4 x 120 (S)4 x 150 (S)4 x 185 (S)4 x 240 (S)4 x 300 (S)4 x 400 (S)

5 x 1.55 x 2.55 x 45 x 6

5 x 105 x 165 x 255 x 355 x 505 x 705 x 95

5 x 1205 x 1505 x 1855 x 240

3 C

OR

ES

Table 22Note: (S) - Sectoral Stranded Conductors.# For current rating and voltage drop, please refer to Table B1.8 and B2.8 on Page 73.

ArmourWire Diameter

(mm)

DiameterUnder Armour

(mm)

7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52

19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.5261 / 2.85

7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52

19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.5261 / 2.85

7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52

19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.25

0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.82.0

0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.82.0

0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.7

8.89.7

10.812.114.116.420.122.523.827.531.034.038.242.649.353.261.7

9.610.611.913.315.518.122.225.025.829.833.536.944.048.655.561.470.2

10.411.613.014.617.119.924.627.632.838.243.348.255.061.268.6

0.90.90.90.9

1.251.251.61.61.62.02.02.02.52.52.52.52.5

0.90.90.9

1.251.251.61.61.61.62.02.02.52.52.52.52.5

3.15

0.90.9

1.251.251.251.61.61.62.02.02.52.52.52.52.5

14.415.316.417.720.422.727.129.531.135.839.742.948.553.160.264.573.4

15.216.217.519.621.825.129.232.233.338.542.447.254.559.566.873.183.8

16.017.219.320.923.426.931.634.841.347.153.458.765.972.580.5

487551643755

1057133719372353275938274825577173018741

111981335716606

541617733966

123417062306285533594671593575469404

11315141441709222157

597690918

108914031973269533454502590176329585

118071419317700

4 C

OR

ES

5 C

OR

ES

Page 30: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

26 | www.taisin.com.sg

Component1. Plain Annealed Copper Wire

2. Cross-linked Polyethylene Compound3. PVC Compound

4. Galvanised Steel Wire Armoured5. PVC Compound

12345

XSPCU / XLPE / PVC / SWA / PVC ( MULTI-CORES )

XLPE Insulated, PVC Bedded, Galvanised Steel Wire Armoured, PVC Sheathed Cable,0.6 / 1kV, IEC60502

CONSTRUCTIONConductor: Plain Annealed Copper, Class 2 Stranded

Circular or Compacted

Insulation: Cross-linked Polyethylene (XLPE)Compound

Insulation Colour: White with Black numbering or Others

Assembly: Cores cabled together and covered withPolyester (PET) Tape

Bedding: Polyvinyl Chloride (PVC) Compound TypeST2

Bedding Colour: Black

Armour: Galvanized Steel Wire Armoured (SWA)

Outer Sheath: Polyvinyl Chloride (PVC) CompoundType ST2

Outer Sheath Colour: Black

ELECTRICAL CHARACTERISTICSOperating Voltage, Uo/U: 0.6/1kV

Operating Temperature: -15ºC to 90ºC

Final Short Circuit Temperature: 250ºC

Test Voltage: 3.5kV for 5 minutes

REFERENCE STANDARDSDesign Specification: IEC60502-1

Conductor: IEC60228, BS EN60228

Flame Retardancy: IEC60332-1, BS EN60332-1

INSTALLATION REFERENCEMin. Bending Radius (mm): 8 x cable overall diameter

Max. Pulling Tension (N/mm2): 70

NominalConductor

Area(mm2)

No. andDiameterof Wires(no./mm)

RadialThickness

of Insulation(mm)

CableOverall

Diameter(mm)

ApproximateWeight(kg/km)

No. of Cores

57

101219202437

1.5

7 / 0.537 / 0.537 / 0.537 / 0.537 / 0.537 / 0.537 / 0.537 / 0.53

0.70.70.70.70.70.70.70.7

MU

LTI-

CO

RE

S

ArmourWire

Diameter(mm)

DiameterUnder

Armour(mm)

10.411.614.715.217.818.820.823.9

0.90.9

1.251.251.251.61.61.6

16.017.221.021.524.125.827.830.9

597692986

10591326152717242167

Table 23Note: Other conductor sizes and core configurations are available upon request.# For current rating and voltage drop, please refer to Table B1.8 and B2.8 on Page 73.

5

4

3

2

1

Page 31: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

www.taisin.com.sg | 27

XSPCU / XLPE / PVC / SWA / PVC ( MULTI-CORES )

XLPE Insulated, PVC Bedded, Galvanised Steel Wire Armoured, PVC Sheathed Cable,0.6 / 1kV, IEC60502

NominalConductor

Area(mm2)

No. andDiameterof Wires(no./mm)

RadialThickness

of Insulation(mm)

CableOverall

Diameter(mm)

ApproximateWeight(kg/km)

No. of Cores

57

101219202437

57

101219202437

2.5

4

7 / 0.677 / 0.677 / 0.677 / 0.677 / 0.677 / 0.677 / 0.677 / 0.67

7 / 0.857 / 0.857 / 0.857 / 0.857 / 0.857 / 0.857 / 0.857 / 0.85

0.70.70.70.70.70.70.70.7

0.70.70.70.70.70.70.70.7

MU

LTI-

CO

RE

S

ArmourWire

Diameter(mm)

DiameterUnder

Armour(mm)

11.612.816.316.919.921.023.426.9

13.014.518.519.122.623.926.631.1

0.91.251.251.251.61.61.61.6

1.251.251.61.61.61.61.62.0

17.219.122.623.226.928.030.434.1

19.320.825.526.129.630.933.839.5

690907

116912531743184920902700

9181090155516782189229826593807

Table 24Note: Other conductor sizes and core configurations are available upon request.# For current rating and voltage drop, please refer to Table B1.8 and B2.8 on Page 73.

Page 32: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

28 | www.taisin.com.sg

Component1. Plain Annealed Copper Wire

2. Cross-linked Polyethylene Compound3. PVC Compound

4. Copper Tape5. PVC Compound

12345

XCPCU / XLPE / PVC / CT / PVC ( 3 CORES + 3 EARTH )

XLPE Insulated, PVC Bedded, Copper Tape Screened, PVC Sheathed Cable, 0.6 / 1kV, IEC60502

CONSTRUCTIONConductor: Plain Annealed Copper, Class 2 Stranded

Circular or Compacted

Insulation: Cross-linked Polyethylene (XLPE)Compound

Insulation Colour: Brown, Black, Grey, Green/Yellow (x3) orRed, Yellow, Blue, Green/Yellow (x3) orOthers

Assembly: Cores cabled together with filler andcovered with Polyester (PET) Tape

Bedding: Polyvinyl Chloride (PVC) CompoundType ST2

Bedding Colour: Black

Screen: Copper Tape

Outer Sheath: Polyvinyl Chloride (PVC) CompoundType ST2

Outer Sheath Colour: Black

ELECTRICAL CHARACTERISTICSOperating Voltage, Uo/U: 0.6/1kV

Operating Temperature: -15ºC to 90ºC

Final Short Circuit Temperature: 250ºC

Test Voltage: 3.5kV for 5 minutes

REFERENCE STANDARDSDesign Specification: IEC60502-1

Conductor: IEC60228, BS EN60228

Flame Retardancy: IEC60332-1, BS EN60332-1

INSTALLATION REFERENCEMin. Bending Radius (mm): 8 x cable overall diameter

Max. Pulling Tension (N/mm2): 50

CombinedEarth Size

(mm2)

No. andDiameterof Wires(no./mm)

RadialThickness of

Insulation(mm)

ApproximateWeight(kg/km)

NominalConductor Area

(mm2)

3 x 1.53 x 2.53 x 43 x 6

3 x 103 x 163 x 253 x 353 x 503 x 703 x 95

3 x 1203 x 1503 x 1853 x 2403 x 300

3 C

OR

ES

+ 3

EA

RT

H

Cable OverallDiameter

(mm)

DiameterUnder Screen

(mm)

4.5 (3 x 1.5)4.5 (3 x 1.5)4.5 (3 x 1.5)7.5 (3 x 2.5)

12 (3 x 4)18 (3 x 6)

30 (3 x 10)30 (3 x 10)30 (3 x 10)48 (3 x 16)48 (3 x 16)75 (3 x 25)75 (3 x 25)

105 (3 x 35)150 (3 x 50)150 (3 x 50)

7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52

19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.52

0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.8

11.712.313.114.616.819.223.224.927.432.435.240.543.849.056.060.0

16.817.418.219.721.924.328.330.032.537.941.346.850.355.963.367.9

490537606736964

126317822111255435444569579167858415

1083713082

Table 25# For current rating and voltage drop, please refer to Table B1.6 and B2.6 on Page 71.

5

4

3

2

1

Page 33: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

www.taisin.com.sg | 29

Component1. Plain Annealed Copper Wire

2. Cross-linked Polyethylene Compound3. PVC Compound

4. Copper Tape5. PVC Compound

12345

XCPCU / XLPE / PVC / CT / PVC ( 4 CORES )

XLPE Insulated, PVC Bedded, Copper Tape Screened, PVC Sheathed Cable, 0.6 / 1kV, IEC60502

CONSTRUCTIONConductor: Plain Annealed Copper, Class 2 Stranded

Circular, Compacted or Sectored

Insulation: Cross-linked Polyethylene (XLPE)Compound

Insulation Colour: Brown, Black, Grey, Green/Yellow orOthers

Assembly: Cores cabled together with filler andcovered with Polyester (PET) Tape

Bedding: Polyvinyl Chloride (PVC) CompoundType ST2

Bedding Colour: Black

Screen: Copper Tape

Outer Sheath: Polyvinyl Chloride (PVC) CompoundType ST2

Outer Sheath Colour: Black

ELECTRICAL CHARACTERISTICSOperating Voltage, Uo/U: 0.6/1kV

Operating Temperature: -15ºC to 90ºC

Final Short Circuit Temperature: 250ºC

Test Voltage: 3.5kV for 5 minutes

REFERENCE STANDARDSDesign Specification: IEC60502-1

Conductor: IEC60228, BS EN60228

Flame Retardancy: IEC60332-1, BS EN60332-1

INSTALLATION REFERENCEMin. Bending Radius (mm): 8 x cable overall diameter

Max. Pulling Tension (N/mm2): 50

No. and Diameterof Wires(no./mm)

Radial Thicknessof Insulation

(mm)

Diameter UnderScreen(mm)

Cable OverallDiamter

(mm)

ApproximateWeight(kg/km)

NominalConductor Area

(mm2)

4 x 1.54 x 2.54 x 44 x 6

4 x 104 x 164 x 254 x 35

4 x 50 (S)4 x 70 (S)4 x 95 (S)

4 x 120 (S)4 x 150 (S)4 x 185 (S)4 x 240 (S)4 x 300 (S)

7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52

19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.52

0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.8

9.710.712.013.415.618.222.325.125.429.833.537.342.847.454.760.6

4 C

OR

ES

14.115.116.417.820.022.626.729.530.034.639.143.149.053.861.568.2

392460559679905

120717212178273637485047625676349361

1202315025

Table 26Note: (S) - Sectoral Stranded Conductors.# For current rating and voltage drop, please refer to Table B1.6 and B2.6 on Page 71.

5

4

3

2

1

Page 34: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

30 | www.taisin.com.sg

Component1. Plain Annealed Copper Wire

2. Cross-linked Polyethylene Compound3. PVC Compound

4. Copper Tape5. PVC Compound

6. Aluminium Wire Armoured7. PVC Compound12345

XCAPCU / XLPE / PVC / CT / PVC / AWA / PVC ( SINGLE CORE )

XLPE Insulated, PVC Bedded, Copper Tape Screened, PVC Separation Sheath, Aluminium Wire Armoured,PVC Sheathed Cable, 0.6 / 1kV, IEC60502

CONSTRUCTIONConductor: Plain Annealed Copper, Class 2 Stranded

Circular or Compacted

Insulation: Cross-linked Polyethylene (XLPE)Compound

Insulation Colour: Natural

Bedding: Polyvinyl Chloride (PVC) CompoundType ST2

Bedding Colour: Black

Screen: Copper Tape

Separation Sheath: Polyvinyl Chloride (PVC) CompoundType ST2

Separation Sheath Colour: Black

Armour: Aluminium Wire Armoured (AWA)

Outer Sheath: Polyvinyl Chloride (PVC) CompoundType ST2

Outer Sheath Colour: Black

ELECTRICAL CHARACTERISTICSOperating Voltage, Uo/U: 0.6/1kV

Operating Temperature: -15ºC to 90ºC

Final Short Circuit Temperature: 250ºC

Test Voltage: 3.5kV for 5 minutes

REFERENCE STANDARDSDesign Specification: IEC60502-1

Conductor: IEC60228, BS EN60228

Flame Retardancy: IEC60332-1, BS EN60332-1

INSTALLATION REFERENCEMin. Bending Radius (mm): 8 x cable overall diameter

Max. Pulling Tension (N/mm2): 50

No. andDiameterof Wires(no./mm)

RadialThickness

of Insulation(mm)

DiameterUnder Screen

(mm)

Cable OverallDiameter

(mm)

ApproximateWeight(kg/km)

NominalConductor

Area(mm2)

1 x 701 x 95

1 x 1201 x 1501 x 1851 x 2401 x 3001 x 4001 x 5001 x 6301 x 800

1 x 1000

19 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.5261 / 2.8561 / 3.20

127 / 2.52127 / 2.85127 / 3.20

1.11.11.21.41.61.71.82.02.22.42.62.8

15.217.219.021.023.226.128.732.536.040.445.550.4

SIN

GL

E C

OR

E

Armour WireDiameter

(mm)

DiameterUnder

Armour(mm)

18.720.622.424.626.829.732.336.139.644.249.554.6

1.61.61.61.61.62.02.02.02.02.52.52.5

25.727.629.431.634.037.940.744.748.454.459.965.4

1655201023522829334441745141627175279446

1162514114

Table 27# For current rating and voltage drop, please refer to Table B1.7 and B2.7 on Page 72.

6

5

4

3

2

1

7

67

Page 35: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

www.taisin.com.sg | 31

1234

XCSPCU / XLPE / PVC / CT / PVC / SWA / PVC ( 4 CORES )

XLPE Insulated, PVC Bedded, Copper Tape Screened, PVC Separation Sheath,Galvanised Steel Wire Armoured, PVC Sheathed Cable, 0.6 / 1kV, IEC60502

CONSTRUCTIONConductor: Plain Annealed Copper, Class 2 Stranded

Circular, Compacted or Sectored

Insulation: Cross-linked Polyethylene (XLPE)Compound

Insulation Colour: Brown, Black, Grey, Green/Yellow or Red,Yellow, Blue, Green/Yellow or Others

Assembly: Cores cabled together with filler andcovered with Polyester (PET) Tape

Bedding: Polyvinyl Chloride (PVC) CompoundType ST2

Bedding Colour: Black

Screen: Copper Tape

Separation Sheath: Polyvinyl Chloride (PVC) CompoundType ST2

Separation Sheath Colour: Black

Armour: Galvanized Steel Wire Armoured (SWA)

Outer Sheath: Polyvinyl Chloride (PVC) CompoundType ST2

Outer Sheath Colour: Black

ELECTRICAL CHARACTERISTICSOperating Voltage, Uo/U: 0.6/1kV

Operating Temperature: -15ºC to 90ºC

Final Short Circuit Temperature: 250ºC

Test Voltage: 3.5kV for 5 minutes

REFERENCE STANDARDSDesign Specification: IEC60502-1

Conductor: IEC60228, BS EN60228

Flame Retardancy: IEC60332-1, BS EN60332-1

INSTALLATION REFERENCEMin. Bending Radius (mm): 8 x cable overall diameter

Max. Pulling Tension (N/mm2): 70

No. and Diameterof Wires(no./mm)

Radial Thicknessof Insulation

(mm)

Armour WireDiameter

(mm)

ApproximateWeight(kg/km)

NominalConductor Area

(mm2)

4 x 1.54 x 2.54 x 44 x 6

4 x 104 x 164 x 254 x 35

4 x 50 (S)4 x 70 (S)4 x 95 (S)

4 x 120 (S)4 x 150 (S)4 x 185 (S)4 x 240 (S)4 x 300 (S)

7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52

19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.52

0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.8

1.251.251.251.251.601.601.601.602.002.002.502.502.502.502.503.15

4 C

OR

ES

Cable OverallDiameter

(mm)

19.520.521.823.226.128.733.036.037.342.147.652.058.162.971.079.0

880986

1126129617322136281833944186542173368782

10495124671559919597

Table 29Note: (S) - Sectoral Stranded Conductors.# For current rating and voltage drop, please refer to Table B1.8 and B2.8 on Page 73.

Component1. Plain Annealed Copper Wire

2. Cross-linked Polyethylene Compound3. PVC Compound

4. Copper Tape5. PVC Compound

6. Galvanised Steel Wire Armoured7. PVC Compound

6

5

4

3

2

1

7

567

Page 36: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

32 | www.taisin.com.sg

Component1. Plain Annealed Copper Wire

2. Cross-linked Polyolefin Low SmokeZero Halogen Compound

12

FRT-HCU / LSZH ( SINGLE CORE )

Cross-Linked Polyolefin LSZH Insulated, Non-Sheathed Cable, 450 / 750V (0.6 / 1kV*),BS EN50525-3-41, BS7211

CONSTRUCTIONConductor: Plain Annealed Copper, Class 2

Stranded Circular or Compacted

Insulation: Cross-linked Polyolefin (LSZH)Low Smoke Zero HalogenCompound

Insulation Colour: Black, Green/Yellow, Red, Yellow,Blue, White, Brown, Grey or Others

ELECTRICAL CHARACTERISTICSOperating Voltage: 450 / 750V (0.6/1kV*)

Operating Temperature: -15ºC to 90ºC

Final Short Circuit Temperature: 250ºC

Test Voltage: 3.5kV for 5 minutes

REFERENCE STANDARDSDesign Specification: BS EN50525-3-41, BS7211

Conductor: IEC60228, BS EN60228

Flame Retardancy: IEC60332-3-22, BS EN60332-3-22

Low Smoke Zero Halogen: IEC61034-2, BS EN61034-2IEC60754-1, IEC60754-2BS EN50267-2-1, BS EN50267-2-2

INSTALLATION REFERENCEMin. Bending Radius (mm): 6 x cable overall diameter

Max. Pulling Tension (N/mm2): 50

NominalConductor Area

(mm2)

No. and Diameterof Wires(no./mm)

Radial Thicknessof Insulation

(mm)

Cable OverallDiameter

(mm)

ApproximateWeight(kg/km)

1 x 1.51 x 2.51 x 41 x 6

1 x 101 x 161 x 251 x 351 x 501 x 701 x 95

1 x 1201 x 1501 x 1851 x 2401 x 3001 x 4001 x 5001 x 630

7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52

19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.5261 / 2.8561 / 3.20

127 / 2.52

0.70.80.80.81.01.01.21.21.41.41.61.61.82.02.22.42.62.82.8

3.13.74.34.86.27.29.0

10.211.913.716.017.619.621.824.927.731.134.638.6

25375373

121180283379513716987

12271509188924683084392349206269

SIN

GL

E C

OR

E

Table 30Note: For FRT-H cables, Cross-Linked LSZH Compound will be used as the insulation material.# For current rating and voltage drop, please refer to Table B1.5 and B2.5 on Page 70.* Condition apply.

2

1

Page 37: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

www.taisin.com.sg | 33

Component1. Plain Annealed Copper Wire

2. Cross-linked Polyethylene Compound3. Low Smoke Zero Halogen

(LSZH) Compound

123

3

2

1

FRT-XHCU / XLPE / LSZH ( SINGLE CORE )

XLPE Insulated, LSZH Sheathed Cable, 0.6 / 1kV, IEC60502

CONSTRUCTIONConductor: Plain Annealed Copper, Class 2

Stranded Circular or Compacted

Insulation: Cross-linked Polyethylene (XLPE)Compound

Insulation Colour: Natural

Outer Sheath: Low Smoke Zero Halogen (LSZH)Compound with Anti-Termite Charateristic and UV Resistant

Outer Sheath Colour: Black

ELECTRICAL CHARACTERISTICSOperating Voltage: 0.6/1kV

Operating Temperature: -15ºC to 90ºC

Final Short Circuit Temperature: 250ºC

Test Voltage: 3.5kV for 5 minutes

REFERENCE STANDARDSDesign Specification: IEC60502-1

Conductor: IEC60228, BS EN60228

Flame Retardancy: IEC60332-3-22, BS EN60332-3-22

Low Smoke Zero Halogen: IEC61034-2, BS EN61034-2IEC60754-1, IEC60754-2BS EN50267-2-1, BS EN50267-2-2

INSTALLATION REFERENCEMin. Bending Radius (mm): 8 x cable overall diameter

Max. Pulling Tension (N/mm2): 50

NominalConductor Area

(mm2)

No. and Diameterof Wires(no./mm)

Radial Thicknessof Insulation

(mm)

Cable OverallDiameter

(mm)

ApproximateWeight(kg/km)

1 x 1.51 x 2.51 x 41 x 6

1 x 101 x 161 x 251 x 351 x 501 x 701 x 95

1 x 1201 x 1501 x 1851 x 2401 x 3001 x 4001 x 5001 x 6301 x 800

1 x 1000

7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52

19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.5261 / 2.8561 / 3.20

127 / 2.52127 / 2.85127 / 3.20

0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.82.02.22.42.62.8

6.16.57.17.68.69.6

11.312.514.116.118.220.022.224.427.530.333.937.642.447.352.4

7589

110136186254367472612837

1114137416752066266132914159518866388394

10479

SIN

GL

E C

OR

E

Table 31# For current rating and voltage drop, please refer to Table B1.5 and B2.5 on Page 70.

Page 38: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

34 | www.taisin.com.sg

Component1. Plain Annealed Copper Wire

2. Cross-linked Polyethylene Compound3. Low Smoke Zero Halogen

(LSZH) Compound

123

3

2

1

FRT-XHCU / XLPE / LSZH ( 2 CORES - 5 CORES )

XLPE Insulated, LSZH Sheathed Cable, 0.6 / 1kV, IEC60502

CONSTRUCTIONConductor: Plain Annealed Copper, Class 2 Stranded

Circular, Compacted or Sectored

Insulation: Cross-linked Polyethylene (XLPE)Compound

Insulation Colour: 2 Cores:Brown, Blue or Red, Black3 Cores:Brown, Black, Grey or Red, Yellow, Blue4 Cores:Brown, Black, Grey, Blue or Red, Yellow,Blue, Black5 Cores:Brown, Black, Grey, Blue, Green/Yellow orRed, Yellow, Blue, Black, Green/Yellow orWhite with Black numbering or Others

Assembly: Cores cabled together with filler andcovered with Polyester (PET) Tape

Outer Sheath: Low Smoke Zero Halogen (LSZH)Compound with Anti-Termite Charateristic and UV Resistant

Outer Sheath Colour: Black

ELECTRICAL CHARACTERISTICSOperating Voltage: 0.6/1kV

Operating Temperature: -15ºC to 90ºC

Final Short Circuit Temperature: 250ºC

Test Voltage: 3.5kV for 5 minutes

REFERENCE STANDARDSDesign Specification: IEC60502-1

Conductor: IEC60228, BS EN60228

Flame Retardancy: IEC60332-3-22, BS EN60332-3-22

Low Smoke Zero Halogen: IEC61034-2, BS EN61034-2IEC60754-1, IEC60754-2BS EN50267-2-1, BS EN50267-2-2

INSTALLATION REFERENCEMin. Bending Radius (mm): 8 x cable overall diameter

Max. Pulling Tension (N/mm2): 50

NominalConductor Area

(mm2)

No. and Diameterof Wires(no./mm)

Radial Thicknessof Insulation

(mm)

Cable OverallDiameter

(mm)

ApproximateWeight(kg/km)

2 x 1.52 x 2.52 x 42 x 6

2 x 102 x 162 x 252 x 35

2 x 50 (S)2 x 70 (S)2 x 95 (S)

2 x 120 (S)2 x 150 (S)2 x 185 (S)2 x 240 (S)2 x 300 (S)

7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52

19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.52

0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.8

10.010.811.913.014.917.020.422.722.425.428.231.234.938.743.247.4

137170220280399561841

109612401694224827823418423354586736

2 C

OR

ES

Table 32Note: (S) - Sectoral Stranded Conductors.# For current rating and voltage drop, please refer to Table B1.6 and B2.6 on Page 71.

Page 39: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

www.taisin.com.sg | 35

FRT-XHCU / XLPE / LSZH ( 2 CORES - 5 CORES )

XLPE Insulated, LSZH Sheathed Cable, 0.6 / 1kV, IEC60502

NominalConductor Area

(mm2)

No. and Diameterof Wires(no./mm)

Radial Thicknessof Insulation

(mm)

Cable OverallDiameter

(mm)

ApproximateWeight(kg/km)

3 x 1.53 x 2.53 x 43 x 6

3 x 103 x 163 x 253 x 35

3 x 50 (S)3 x 70 (S)3 x 95 (S)

3 x 120 (S)3 x 150 (S)3 x 185 (S)3 x 240 (S)3 x 300 (S)3 x 400 (S)

4 x 1.54 x 2.54 x 44 x 6

4 x 104 x 164 x 254 x 35

4 x 50 (S)4 x 70 (S)4 x 95 (S)

4 x 120 (S)4 x 150 (S)4 x 185 (S)4 x 240 (S)4 x 300 (S)4 x 400 (S)4 x 500 (S)

5 x 1.55 x 2.55 x 45 x 6

5 x 105 x 165 x 255 x 355 x 505 x 705 x 95

5 x 120

7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52

19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.5261 / 2.85

7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52

19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.5261 / 2.8561 / 3.20

7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52

19 / 1.7819 / 2.1419 / 2.5237 / 2.03

0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.82.0

0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.82.02.2

0.70.70.70.70.70.70.90.91.01.11.11.2

10.511.412.513.815.818.121.824.225.028.932.635.840.445.050.554.663.7

11.312.313.615.017.219.823.926.727.031.435.339.144.849.857.163.472.880.8

12.113.314.716.318.821.626.329.334.240.045.350.6

159201265344500715

1082142417512434325640474967616979789852

12567

189242323425624901

13731815225431624241530265038104

10515130581662520785

223288388512759

1102168522342845398953486689

3 C

OR

ES

4 C

OR

ES

Table 33Note: (S) - Sectoral Stranded Conductors.# For current rating and voltage drop, please refer to Table B1.6 and B2.6 on Page 71.

5 C

OR

ES

Page 40: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

36 | www.taisin.com.sg

Component1. Plain Annealed Copper Wire

2. Cross-linked Polyethylene Compound3. Low Smoke Zero Halogen

(LSZH) Compound

123

CONSTRUCTIONConductor: Plain Annealed Copper, Class 2 Stranded

Circular or Compacted

Insulation: Cross-linked Polyethylene (XLPE)Compound

Insulation Colour: White with Black numbering or Others

Assembly: Cores cabled together and covered withPolyester (PET) Tape

Outer Sheath: Low Smoke Zero Halogen (LSZH)Compound with Anti-Termite Charateristic and UV Resistant

Outer Sheath Colour: Black

ELECTRICAL CHARACTERISTICSOperating Voltage: 0.6/1kV

Operating Temperature: -15ºC to 90ºC

Final Short Circuit Temperature: 250ºC

Test Voltage: 3.5kV for 5 minutes

REFERENCE STANDARDSDesign Specification: IEC60502-1

Conductor: IEC60228, BS EN60228

Flame Retardancy: IEC60332-3-22, BS EN60332-3-22

Low Smoke Zero Halogen: IEC61034-2, BS EN61034-2IEC60754-1, IEC60754-2BS EN50267-2-1, BS EN50267-2-2

INSTALLATION REFERENCEMin. Bending Radius (mm): 8 x cable overall diameter

Max. Pulling Tension (N/mm2): 50

NominalConductor Area

(mm2)

No. and Diameterof Wires(no./mm)

Radial Thicknessof Insulation

(mm)

Cable OverallDiameter

(mm)

ApproximateWeight(kg/km)

57

101219202437

MU

LTI-

CO

RE

S

Table 34Note : Other conductor sizes & core configurations are available upon request.# For current rating and voltage drop, please refer to Table B1.6 and B2.6 on Page 71.

No. of Cores

7 / 0.537 / 0.537 / 0.537 / 0.537 / 0.537 / 0.537 / 0.537 / 0.53

1.5

0.70.70.70.70.70.70.70.7

12.113.116.216.719.320.322.325.4

223309417467652688803

1122

3

2

1

FRT-XHCU / XLPE / LSZH ( MULTI-CORES )

XLPE Insulated, LSZH Sheathed Cable, 0.6 / 1kV, IEC60502

Page 41: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

www.taisin.com.sg | 37

FRT-XHCU / XLPE / LSZH ( MULTI-CORES )

XLPE Insulated, LSZH Sheathed Cable, 0.6 / 1kV, IEC60502

NominalConductor Area

(mm2)

No. and Diameterof Wires(no./mm)

Radial Thicknessof Insulation

(mm)

Cable OverallDiameter

(mm)

ApproximateWeight(kg/km)

57

101219202437

57

101219202437

MU

LTI-

CO

RE

S

Table 35Note : Other conductor sizes & core configurations are available upon request.# For current rating and voltage drop, please refer to Table B1.6 and B2.6 on Page 71.

No. of Cores

7 / 0.677 / 0.677 / 0.677 / 0.677 / 0.677 / 0.677 / 0.677 / 0.67

7 / 0.857 / 0.857 / 0.857 / 0.857 / 0.857 / 0.857 / 0.857 / 0.85

2.5

4

0.70.70.70.70.70.70.70.7

0.70.70.70.70.70.70.70.7

13.314.317.818.421.422.524.928.4

14.716.020.020.624.125.428.132.4

288394536606863910

10671515

388523719820

1189125414762145

Page 42: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

38 | www.taisin.com.sg

Component1. Plain Annealed Copper Wire

2. Cross-linked Polyethylene Compound3. Low Smoke Zero Halogen

(LSZH) Compound4. Aluminium Wire Armoured5. Low Smoke Zero Halogen

(LSZH) Compound12345

5

4

3

2

1

FRT-XAHCU / XLPE / LSZH / AWA / LSZH ( SINGLE CORE )

XLPE Insulated, LSZH Bedded, Aluminium Wire Armoured, LSZH Sheathed Cable,0.6 / 1kV, BS6724

CONSTRUCTIONConductor: Plain Annealed Copper, Class 2

Stranded Circular or Compacted

Insulation: Cross-linked Polyethylene (XLPE)Compound

Insulation Colour: Natural

Bedding: Low Smoke Zero Halogen (LSZH)Compound

Bedding Colour: Black

Armour: Aluminium Wire Armoured (AWA)

Outer Sheath: Low Smoke Zero Halogen (LSZH)Compound with Anti-Termite Charateristic and UV Resistant

Outer Sheath Colour: Black

ELECTRICAL CHARACTERISTICSOperating Voltage: 0.6/1kV

Operating Temperature: -15ºC to 90ºC

Final Short Circuit Temperature: 250ºC

Test Voltage: 3.5kV for 5 minutes

REFERENCE STANDARDSDesign Specification: BS6724

Conductor: IEC60228, BS EN60228

Flame Retardancy: IEC60332-3-22, BS EN60332-3-22

Low Smoke Zero Halogen: IEC61034-2, BS EN61034-2IEC60754-1, IEC60754-2BS EN50267-2-1, BS EN50267-2-2

INSTALLATION REFERENCEMin. Bending Radius (mm): 8 x cable overall diameter

Max. Pulling Tension (N/mm2): 50

NominalConductor Area

(mm2)

No. and Diameterof Wires(no./mm)

DiameterUnder Armour

(mm)

Cable OverallDiameter

(mm)

ApproximateWeight(kg/km)

1 x 501 x 701 x 95

1 x 1201 x 1501 x 1851 x 2401 x 3001 x 4001 x 5001 x 6301 x 800

1 x 1000

SIN

GL

E C

OR

E

Table 36# For current rating and voltage drop, please refer to Table B1.7 and B2.7 on Page 72.

ArmourWire Diameter

(mm)

19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.5261 / 2.8561 / 3.20

127 / 2.52127 / 2.85127 / 3.20

12.914.916.818.621.023.226.128.732.536.040.445.550.4

1.251.251.251.251.61.61.61.62.02.02.02.52.5

18.620.622.725.227.830.233.135.940.744.449.055.560.6

93211491463176221812633327939665044616877119840

12071

Page 43: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

www.taisin.com.sg | 39

Component1. Plain Annealed Copper Wire

2. Cross-linked Polyethylene Compound3. Low Smoke Zero Halogen

(LSZH) Compound4. Galvanised Steel Wire Armoured

5. Low Smoke Zero Halogen(LSZH) Compound12345

FRT-XSHCU / XLPE / LSZH / SWA / LSZH ( 2 CORES - 5 CORES )

XLPE Insulated, LSZH Bedded, Galvanised Steel Wire Armoured, LSZH Sheathed Cable,0.6 / 1kV, BS6724

CONSTRUCTIONConductor: Plain Annealed Copper, Class 2 Stranded

Circular, Compacted or Sectored

Insulation: Cross-linked Polyethylene (XLPE)Compound

Insulation Colour: 2 Cores:Brown, Blue or Red, Black3 Cores:Brown, Black, Grey or Red, Yellow, Blue4 Cores:Brown, Black, Grey, Blue or Red, Yellow,Blue, Black5 Cores:Brown, Black, Grey, Blue, Green/Red,Yellow, Blue, Black, Green/Yellow or Whitewith Black numbering or Others

Assembly: Cores cabled together with filler andcovered with Polyester (PET) Tape

Bedding: Low Smoke Zero Halogen (LSZH)Compound

Bedding Colour: Black

Armour: Galvanized Steel Wire Armoured (SWA)

Outer Sheath: Low Smoke Zero Halogen (LSZH)Compound with Anti-Termite Charateristic and UV Resistant

Outer Sheath Colour: Black

ELECTRICAL CHARACTERISTICSOperating Voltage: 0.6/1kV

Operating Temperature: -15ºC to 90ºC

Final Short Circuit Temperature: 250ºC

Test Voltage: 3.5kV for 5 minutes

REFERENCE STANDARDSDesign Specification: BS6724

Conductor: IEC60228, BS EN60228

Flame Retardancy: IEC60332-3-22, BS EN60332-3-22

Low Smoke Zero Halogen: IEC61034-2, BS EN61034-2IEC60754-1, IEC60754-2BS EN50267-2-1, BS EN50267-2-2

INSTALLATION REFERENCEMin. Bending Radius (mm): 8 x cable overall diameter

Max. Pulling Tension (N/mm2): 70

5

4

3

2

1

RadialThickness of

Insulation (mm)

ApproximateWeight(kg/km)

No. andDiameter of

Wires (no./mm)

NominalConductorArea (mm2)

Cable OverallDiameter

(mm)

2 x 1.52 x 2.52 x 42 x 6

2 x 102 x 162 x 252 x 35

2 x 50 (S)2 x 70 (S)2 x 95 (S)

2 x 120 (S)2 x 150 (S)2 x 185 (S)2 x 240 (S)2 x 300 (S)

2 C

OR

ES

DiameterUnder Armour

(mm)

ArmourWire Diameter

(mm)

7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52

19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.52

0.60.70.70.70.70.70.90.91.01.11.11.21.41.61.71.8

7.68.89.9

11.012.915.018.421.120.723.726.729.532.836.840.945.3

0.90.90.90.90.9

1.251.61.61.61.62.02.02.02.52.52.5

12.313.714.815.918.720.825.128.027.831.035.038.041.546.951.255.8

341418496585769

10811496201421352728364243415117657480259596

Table 37Note : (S) - Sectoral Stranded Conductors.# For current rating and voltage drop, please refer to Table B1.8 and B2.8 on Page 73.

Page 44: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

40 | www.taisin.com.sg

FRT-XSHCU / XLPE / LSZH / SWA / LSZH ( 2 CORES - 5 CORES )

XLPE Insulated, LSZH Bedded, Galvanised Steel Wire Armoured, LSZH Sheathed Cable,0.6 / 1kV, BS6724

RadialThickness of

Insulation (mm)

ApproximateWeight(kg/km)

No. andDiameter of

Wires (no./mm)

NominalConductorArea (mm2)

Cable OverallDiameter

(mm)

3 x 1.53 x 2.53 x 43 x 6

3 x 103 x 163 x 253 x 35

3 x 50 (S)3 x 70 (S)3 x 95 (S)

3 x 120 (S)3 x 150 (S)3 x 185 (S)3 x 240 (S)3 x 300 (S)3 x 400 (S)

4 x 1.54 x 2.54 x 44 x 6

4 x 104 x 164 x 254 x 35

4 x 50 (S)4 x 70 (S)4 x 95 (S)

4 x 120 (S)4 x 150 (S)4 x 185 (S)4 x 240 (S)4 x 300 (S)4 x 400 (S)

5 x 1.55 x 2.55 x 45 x 6

5 x 105 x 165 x 255 x 355 x 505 x 70

3 C

OR

ES

DiameterUnder Armour

(mm)

ArmourWire Diameter

(mm)

7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52

19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.5261 / 2.85

7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52

19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.5261 / 2.85

7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52

19 / 1.7819 / 2.14

0.60.70.70.70.70.70.90.91.01.11.11.21.41.61.71.82.0

0.60.70.70.70.70.70.90.91.01.11.11.21.41.61.71.82.0

0.60.70.70.70.70.70.90.91.01.1

8.09.4

10.511.813.816.120.222.623.327.030.933.938.142.948.052.360.8

8.810.311.613.015.217.822.325.125.329.733.437.242.747.354.660.569.7

9.611.312.714.316.820.024.727.732.738.1

0.90.90.90.9

1.251.251.61.61.61.61.62.02.52.52.52.52.5

0.90.90.9

1.251.251.251.61.61.62.02.02.52.52.52.52.5

3.15

0.90.90.9

1.251.251.61.61.62.02.0

12.714.315.416.719.622.127.129.730.435.139.442.648.053.058.563.071.9

13.515.216.518.821.024.529.232.232.638.242.147.152.857.865.371.682.7

14.516.218.520.122.826.931.835.041.046.8

375463556669981

128319592418275136104873582473008832

109791315316378

416526642880

115615312335291433514717598876259164

11059139391686521985

478599752

1007135219772764345645535961

4 C

OR

ES

Table 38Note : (S) - Sectoral Stranded Conductors.# For current rating and voltage drop, please refer to Table B1.8 and B2.8 on Page 73.

5 C

OR

ES

Page 45: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

www.taisin.com.sg | 41

Component1. Plain Annealed Copper Wire

2. Cross-linked Polyethylene Compound3. Low Smoke Zero Halogen

(LSZH) Compound4. Galvanised Steel Wire Armoured

5. Low Smoke Zero Halogen(LSZH) Compound12345

5

4

3

2

1

FRT-XSHCU / XLPE / LSZH / SWA / LSZH ( MULTI-CORES )

XLPE Insulated, LSZH Bedded, Galvanised Steel Wire Armoured, LSZH Sheathed Cable,0.6 / 1kV, BS6724

CONSTRUCTIONConductor: Plain Annealed Copper, Class 2 Stranded

Circular or Compacted

Insulation: Cross-linked Polyethylene (XLPE)Compound

Insulation Colour: White with Black numbering or Others

Assembly: Cores cabled together and covered withPolyester (PET) Tape

Bedding: Low Smoke Zero Halogen (LSZH)Compound

Bedding Colour: Black

Armour: Galvanized Steel Wire Armoured (SWA)

Outer Sheath: Low Smoke Zero Halogen (LSZH)Compound with Anti-Termite Charateristic and UV Resistant

Outer Sheath Colour: Black

ELECTRICAL CHARACTERISTICSOperating Voltage: 0.6/1kV

Operating Temperature: -15ºC to 90ºC

Final Short Circuit Temperature: 250ºC

Test Voltage: 3.5kV for 5 minutes

REFERENCE STANDARDSDesign Specification: BS6724

Conductor: IEC60228, BS EN60228

Flame Retardancy: IEC60332-3-22, BS EN60332-3-22

Low Smoke Zero Halogen: IEC61034-2, BS EN61034-2IEC60754-1, IEC60754-2BS EN50267-2-1, BS EN50267-2-2

INSTALLATION REFERENCEMin. Bending Radius (mm): 8 x cable overall diameter

Max. Pulling Tension (N/mm2): 70

NominalConductor

Area(mm2)

No. andDiameterof Wires(no./mm)

RadialThickness of

Insulation(mm)

DiameterUnder Armour

(mm)

ApproximateWeight(kg/km)

57

101219202437

MU

LTI-

CO

RE

S

Cable OverallDiameter

(mm)

Table 39Note : Other conductor sizes & core configurations are available upon request.# For current rating and voltage drop, please refer to Table B1.8 and B2.8 on Page 73.

Armour WireDiameter

(mm)

No. of Cores

1.5

7 / 0.537 / 0.537 / 0.537 / 0.537 / 0.537 / 0.537 / 0.537 / 0.53

0.60.60.60.60.60.60.60.6

9.610.513.413.816.317.619.522.4

0.90.9

1.251.251.251.61.61.6

14.515.419.219.622.323.826.429.3

478571849908

1168139615942015

Page 46: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

42 | www.taisin.com.sg

FRT-XSHCU / XLPE / LSZH / SWA / LSZH ( MULTI-CORES )

XLPE Insulated, LSZH Bedded, Galvanised Steel Wire Armoured, LSZH Sheathed Cable,0.6 / 1kV, BS6724

NominalConductor

Area(mm2)

No. andDiameterof Wires(no./mm)

RadialThickness of

Insulation(mm)

DiameterUnder Armour

(mm)

ApproximateWeight(kg/km)

57

101219202437

57

101219202437

MU

LTI-

CO

RE

S

Cable OverallDiameter

(mm)

Armour WireDiameter

(mm)

No. of Cores

2.5

4

7 / 0.677 / 0.677 / 0.677 / 0.677 / 0.677 / 0.677 / 0.677 / 0.67

7 / 0.857 / 0.857 / 0.857 / 0.857 / 0.857 / 0.857 / 0.857 / 0.85

0.70.70.70.70.70.70.70.7

0.70.70.70.70.70.70.70.7

11.312.315.816.419.820.923.326.8

12.714.018.419.022.523.826.531.0

0.90.9

1.251.251.61.61.61.6

1.251.251.251.61.61.62.02.0

16.217.921.822.426.728.030.433.9

18.519.825.125.729.431.133.839.3

599729

107911721704182320662659

8421002150416262150228926333759

Table 40Note : Other conductor sizes & core configurations are available upon request.# For current rating and voltage drop, please refer to Table B1.8 and B2.8 on Page 73.

Page 47: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

www.taisin.com.sg | 43

Component1. Plain Annealed Copper Wire

2. Cross-linked Polyethylene Compound3. Low Smoke Zero Halogen

(LSZH) Compound4. Copper Tape

5. Low Smoke Zero Halogen(LSZH) Compound12345

FRT-XCHCU / XLPE / LSZH / CT / LSZH ( 3 CORES + 3 EARTH )

XLPE Insulated, LSZH Bedded, Copper Tape Screened, LSZH Sheathed Cable, 0.6 / 1kV, IEC60502

CONSTRUCTIONConductor: Plain Annealed Copper, Class 2 Stranded

Circular or Compacted

Insulation: Cross-linked Polyethylene (XLPE)Compound

Insulation Colour: Brown, Black, Grey, Green/Yellow (x3) orRed, Yellow, Blue, Green/Yellow (x3) orOthers

Assembly: Cores cabled together with filler andcovered with Polyester (PET) Tape

Bedding: Low Smoke Zero Halogen (LSZH)Compound

Bedding Colour: Black

Screen: Copper Tape

Outer Sheath: Low Smoke Zero Halogen (LSZH)Compound with Anti-Termite Charateristic and UV Resistant

Outer Sheath Colour: Black

ELECTRICAL CHARACTERISTICSOperating Voltage: 0.6/1kV

Operating Temperature: -15ºC to 90ºC

Final Short Circuit Temperature: 250ºC

Test Voltage: 3.5kV for 5 minutes

REFERENCE STANDARDSDesign Specification: IEC60502-1

Conductor: IEC60228, BS EN60228

Flame Retardancy: IEC60332-3-22, BS EN60332-3-22

Low Smoke Zero Halogen: IEC61034-2, BS EN61034-2IEC60754-1, IEC60754-2BS EN50267-2-1, BS EN50267-2-2

INSTALLATION REFERENCEMin. Bending Radius (mm): 8 x cable overall diameter

Max. Pulling Tension (N/mm2): 50

No. andDiameter of

Wires (no./mm)

ApproximateWeight(kg/km)

CombinedEarth Size

(mm2)

NominalConductorArea (mm2)

Cable OverallDiameter

(mm)

3 x 1.53 x 2.53 x 43 x 6

3 x 103 x 163 x 253 x 353 x 503 x 703 x 95

3 x 1203 x 1503 x 1853 x 2403 x 300

3 C

OR

ES

+ 3

EA

RT

H

RadialThickness of

Insulation (mm)

DiameterUnder Screen

(mm)

4.5 (3 x 1.5)4.5 (3 x 1.5)4.5 (3 x 1.5)7.5 (3 x 2.5)

12 (3 x 4)18 (3 x 6)

30 (3 x 10)30 (3 x 10)30 (3 x 10)48 (3 x 16)48 (3 x 16)75 (3 x 25)75 (3 x 25)

105 (3 x 35)150 (3 x 50)150 (3 x 50)

7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52

19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.52

0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.8

11.712.313.114.616.819.223.224.927.432.435.240.943.849.056.360.3

16.817.418.219.721.924.328.330.032.737.940.946.449.955.563.467.6

485532602734966

127117962131274337634658590569198584

1134313373

Table 41# For current rating and voltage drop, please refer to Table B1.6 and B2.6 on Page 71.

5

4

3

2

1

Page 48: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

44 | www.taisin.com.sg

Component1. Plain Annealed Copper Wire

2. Cross-linked Polyethylene Compound3. Low Smoke Zero Halogen

(LSZH) Compound4. Copper Tape

5. Low Smoke Zero Halogen(LSZH) Compound12345

5

4

3

2

1

FRT-XCHCU / XLPE / LSZH / CT / LSZH ( 4 CORES )

XLPE Insulated, LSZH Bedded, Copper Tape Screened, LSZH Sheathed Cable, 0.6 / 1kV, IEC60502

CONSTRUCTIONConductor: Plain Annealed Copper, Class 2 Stranded

Circular, Compacted or Sectored

Insulation: Cross-linked Polyethylene (XLPE)Compound

Insulation Colour: Brown, Black, Grey, Green/Yellow or Others

Assembly: Cores cabled together with filler andcovered with Polyester (PET) Tape

Bedding: Low Smoke Zero Halogen (LSZH)Compound

Bedding Colour: Black

Screen: Copper Tape

Outer Sheath: Low Smoke Zero Halogen (LSZH)Compound with Anti-Termite Charateristic and UV Resistant

Outer Sheath Colour: Black

ELECTRICAL CHARACTERISTICSOperating Voltage, Uo/U: 0.6/1kV

Operating Temperature: -15ºC to 90ºC

Final Short Circuit Temperature: 250ºC

Test Voltage: 3.5kV for 5 minutes

REFERENCE STANDARDSDesign Specification: IEC60502-1

Conductor: IEC60228, BS EN60228

Flame Retardancy: IEC60332-1, BS EN60332-1

Low Smoke Zero Halogen: IEC61034-2, BS EN61034-2IEC60754-1, IEC60754-2BS EN50267-2-1, BS EN50267-2-2

INSTALLATION REFERENCEMin. Bending Radius (mm): 8 x cable overall diameter

Max. Pulling Tension (N/mm2): 50

No. and Diameterof Wires(no./mm)

Radial Thicknessof Insulation

(mm)

DiameterUnder Screen

(mm)

Cable OverallDiameter

(mm)

ApproximateWeight(kg/km)

NominalConductor Area

(mm2)

4 x 1.54 x 2.54 x 44 x 6

4 x 104 x 164 x 25

4 x 35 (S)4 x 50 (S)4 x 70 (S)4 x 95 (S)

4 x 120 (S)4 x 150 (S)4 x 185 (S)4 x 240 (S)4 x 300 (S)

7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52

19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.52

0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.8

9.710.712.013.415.618.222.325.125.429.833.537.342.847.454.760.6

4 C

OR

ES

14.415.416.718.120.322.927.029.830.334.939.043.048.953.761.867.9

371441544668907

122917702264272137345069625476229333

1229615030

Table 42Note: (S) - Sectoral Stranded Conductors.# For current rating and voltage drop, please refer to Table B1.6 and B2.6 on Page 71.

Page 49: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

www.taisin.com.sg | 45

Component1. Plain Annealed Copper Wire

2. Cross-linked Polyethylene Compound3. Low Smoke Zero Halogen (LSZH) Compound

4. Copper Tape5. Low Smoke Zero Halogen (LSZH) Compound

6. Aluminium Wire Armoured7. Low Smoke Zero Halogen (LSZH) Compound12345

6

5

4

3

2

FRT-XCAHCU / XLPE / LSZH / CT / LSZH / AWA / SWA / LSZH ( SINGLE CORE )

XLPE Insulated, LSZH Bedded, Copper Tape Screened, LSZH Separation Sheath,Aluminium Wire Armoured, LSZH Sheathed Cable, 0.6 / 1kV, IEC60502

CONSTRUCTIONConductor: Plain Annealed Copper, Class 2 Stranded

Circular or Compacted

Insulation: Cross-linked Polyethylene (XLPE)Compound

Insulation Colour: Natural

Bedding: Low Smoke Zero Halogen (LSZH)Compound

Bedding Colour: Black

Screen: Copper Tape

Separation Sheath: Low Smoke Zero Halogen (LSZH)Compound

Separation Sheath Colour: Black

Armour: Aluminium Wire Armoured (AWA)

Outer Sheath: Low Smoke Zero Halogen (LSZH)Compound with Anti-Termite Charateristic and UV Resistant

Outer Sheath Colour: Black

ELECTRICAL CHARACTERISTICSOperating Voltage: 0.6/1kV

Operating Temperature: -15ºC to 90ºC

Final Short Circuit Temperature: 250ºC

Test Voltage: 3.5kV for 5 minutes

REFERENCE STANDARDSDesign Specification: IEC60502-1

Conductor: IEC60228, BS EN60228

Flame Retardancy: IEC60332-3-22, BS EN60332-3-22

Low Smoke Zero Halogen: IEC61034-2, BS EN61034-2IEC60754-1, IEC60754-2BS EN50267-2-1, BS EN50267-2-2

INSTALLATION REFERENCEMin. Bending Radius (mm): 8 x cable overall diameter

Max. Pulling Tension (N/mm2): 50

RadialThickness of

Insulation(mm)

ApproximateWeight(kg/km)

No. andDiameter of

Wires(no./mm)

NominalConductor

Area(mm2)

Cable OverallDiameter

(mm)

SIN

GL

E C

OR

E

DiameterUnder Screen

(mm)

1 x 701 x 95

1 x 1201 x 1501 x 1851 x 2401 x 3001 x 4001 x 5001 x 6301 x 800

1 x 1000

ArmourWire Diameter

(mm)

19 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.5261 / 2.8561 / 3.20

127 / 2.52127 / 2.85127 / 3.20

1.11.11.21.41.61.71.82.02.22.42.62.8

15.317.219.021.023.226.128.732.536.040.445.550.4

18.720.622.424.626.829.732.336.139.644.249.554.6

1.61.61.61.61.62.02.02.02.02.52.52.5

25.727.629.431.434.037.940.744.748.454.459.965.4

1677211124632846353343835181631775789505

1169414193

Table 43# For current rating and voltage drop, please refer to Table B1.7 and B2.7 on Page72.

1

7

67

DiameterUnder Armour

(mm)

Page 50: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

46 | www.taisin.com.sg

12345

FRT-XCSHCU / XLPE / LSZH / CT / LSZH / SWA / LSZH ( 4 CORES )

XLPE Insulated, LSZH Bedded, Copper Tape Screened, LSZH Separation Sheath,Galvanised Steel Wire Armoured, LSZH Sheathed Cable, 0.6 / 1kV, IEC60502

CONSTRUCTIONConductor: Plain Annealed Copper, Class 2 Stranded

Circular, Compacted or Sectored

Insulation: Cross-linked Polyethylene (XLPE)Compound

Insulation Colour: Brown, Black, Grey, Green/Yellow or Red,Yellow, Blue, Green/Yellow or Others

Assembly: Cores cabled together with filler andcovered with Polyester (PET) Tape

Bedding: Low Smoke Zero Halogen (LSZH)Compound

Bedding Colour: Black

Screen: Copper Tape

Separation Sheath: Low Smoke Zero Halogen (LSZH)Compound

Separation Sheath Colour: Black

Armour: Galvanized Steel Wire Armoured (SWA)

Outer Sheath: Low Smoke Zero Halogen (LSZH)Compound with Anti-Termite Charateristic and UV Resistant

Outer Sheath Colour: Black

ELECTRICAL CHARACTERISTICSOperating Voltage: 0.6/1kV

Operating Temperature: -15ºC to 90ºC

Final Short Circuit Temperature: 250ºC

Test Voltage: 3.5kV for 5 minutes

REFERENCE STANDARDSDesign Specification: IEC60502-1

Conductor: IEC60228, BS EN60228

Flame Retardancy: IEC60332-3-22, BS EN60332-3-22

Low Smoke Zero Halogen: IEC61034-2, BS EN61034-2IEC60754-1, IEC60754-2BS EN50267-2-1, BS EN50267-2-2

INSTALLATION REFERENCEMin. Bending Radius (mm): 8 x cable overall diameter

Max. Pulling Tension (N/mm2): 70

Component1. Plain Annealed Copper Wire

2. Cross-linked Polyethylene Compound3. Low Smoke Zero Halogen (LSZH) Compound

4. Copper Tape5. Low Smoke Zero Halogen (LSZH) Compound

6. Galvanised Steel Wire Armoured7. Low Smoke Zero Halogen (LSZH) Compound

6

5

4

3

2

1

7

67

RadialThickness of

Insulation(mm)

ApproximateWeight(kg/km)

No. andDiameter of

Wires(no./mm)

NominalConductor

Area(mm2)

Cable OverallDiameter

(mm)

4 C

OR

ES

DiameterUnder

Armour(mm)

4 x 1.54 x 2.54 x 44 x 6

4 x 104 x 164 x 254 x 35

4 x 50 (S)4 x 70 (S)4 x 95 (S)

4 x 120 (S)4 x 150 (S)4 x 185 (S)4 x 240 (S)4 x 300 (S)

ArmourWire

Diameter(mm)

7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52

19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.52

0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.8

9.710.712.013.415.618.222.325.125.429.833.537.342.847.454.760.6

13.114.115.416.819.021.625.728.528.833.237.141.146.851.459.365.4

1.251.251.251.251.61.61.61.62.02.02.52.52.52.52.5

3.15

19.920.922.223.626.529.133.436.437.742.547.652.058.162.971.279.2

871981

1127130417582186291535354370565174138888

10632126411613320227

Table 44Note: (S) - Sectoral Stranded Conductors.# For current rating and voltage drop, please refer to Table B1.8 and B2.8 on Page 73.

DiameterUnderScreen(mm)

Page 51: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

www.taisin.com.sg | 47

Component1. Plain Annealed Copper Wire

2. Mica Tape3. Cross-linked Polyolefin Low Smoke

Zero Halogen Compound

123

FR-H 110CU / MGT / LSZH ( SINGLE CORE )

Mica Taped, Cross-linked Polyolefin LSZH Insulated, Non-Sheathed Cable, 450 / 750V (0.6 / 1kV*),BS7211

NominalConductor Area

(mm2)

No. and Diameterof Wires(no./mm)

Radial Thicknessof Insulation

(mm)

Cable OverallDiameter

(mm)

ApproximateWeight(kg/km)

1 x 1.51 x 2.51 x 41 x 6

1 x 101 x 161 x 251 x 351 x 501 x 701 x 95

1 x 1201 x 1501 x 1851 x 2401 x 3001 x 4001 x 5001 x 630

7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52

19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.5261 / 2.8561 / 3.20

127 / 2.52

0.70.80.80.81.01.01.21.21.41.41.61.61.82.02.22.42.62.82.8

4.14.85.35.97.38.3

10.111.212.914.717.018.720.622.925.928.732.135.639.6

32466284

135195299397533740

101512571524192625103131397549786333

SIN

GL

E C

OR

E

Table 45Note: For FR-H cables, Cross-linked LSZH Compound will be used as the insulation material.# For current rating and voltage drop, please refer to Table B1.5 and B2.5 on Page 70.* Condition apply.

CONSTRUCTIONConductor: Plain Annealed Copper, Class 2

Stranded Circular or Compacted

Fire Barrier: Mica Tape (MGT)

Insulation: Cross-linked Polyolefin (LSZH) LowSmoke Zero Halogen Compound

Insulation Colour: Orange or Others

ELECTRICAL CHARACTERISTICSOperating Voltage: 450 / 750V (0.6/1kV*)

Operating Temperature: -15ºC to 90ºC

Final Short Circuit Temperature: 250ºC

Test Voltage: 3.5kV for 5 minutes

REFERENCE STANDARDSDesign Specification: BS7211

Conductor: IEC60228, BS EN60228

Fire Resistance: BS6387 (C,W,Z), SS299 (C), IEC60331

Flame Retardancy: IEC60332-3-22, BS EN60332-3-22

Low Smoke Zero Halogen: IEC61034-2, BS EN61034-2IEC60754-1, IEC60754-2BS EN50267-2-1, BS EN50267-2-2

INSTALLATION REFERENCEMin. Bending Radius (mm): 8 x cable overall diameter

Max. Pulling Tension (N/mm2): 50

3

2

1

Page 52: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

48 | www.taisin.com.sg

Component1. Plain Annealed Copper Wire

2. Mica Tape3. Cross-linked Polyethylene Compound

4. Low Smoke Zero Halogen(LSZH) Compound

1234

4

3

2

1

FR-XHCU / MGT / XLPE / LSZH ( SINGLE CORE )

Mica Taped, XLPE Insulated, LSZH Sheathed Cable, 0.6 / 1kV, IEC60502

NominalConductor Area

(mm2)

No. and Diameterof Wires(no./mm)

Radial Thicknessof Insulation

(mm)

Cable OverallDiameter

(mm)

ApproximateWeight(kg/km)

1 x 1.51 x 2.51 x 41 x 6

1 x 101 x 161 x 251 x 351 x 501 x 701 x 95

1 x 1201 x 1501 x 1851 x 2401 x 3001 x 4001 x 5001 x 6301 x 800

1 x 1000

7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52

19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.5261 / 2.8561 / 3.20

127 / 2.52127 / 2.85127 / 3.20

0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.82.02.22.42.62.8

6.16.57.17.68.69.6

11.312.514.116.118.220.022.224.427.530.333.937.642.447.352.4

7892

114141192261376482624851

1131139316952088268733194190522266758436

10525

SIN

GL

E C

OR

E

Table 46# For current rating and voltage drop, please refer to Table B1.5 and B2.5 on Page 70.

CONSTRUCTIONConductor: Plain Annealed Copper, Class 2

Stranded Circular or Compacted

Fire Barrier: Mica Tape (MGT)

Insulation: Cross-linked Polyethylene (XLPE)Compound

Insulation Colour: Natural

Outer Sheath: Low Smoke Zero Halogen (LSZH)Compound with Anti-Termite Charateristic and UV Resistant

Outer Sheath Colour: Orange or Others

ELECTRICAL CHARACTERISTICSOperating Voltage: 0.6/1kV

Operating Temperature: -15ºC to 90ºC

Final Short Circuit Temperature: 250ºC

Test Voltage: 3.5kV for 5 minutes

REFERENCE STANDARDSDesign Specification: IEC60502-1

Conductor: IEC60228, BS EN60228

Fire Resistance: BS6387 (C,W,Z), SS299 (C), IEC60331

Flame Retardancy: IEC60332-3-22, BS EN60332-3-22

Low Smoke Zero Halogen: IEC61034-2, BS EN61034-2IEC60754-1, IEC60754-2BS EN50267-2-1, BS EN50267-2-2

INSTALLATION REFERENCEMin. Bending Radius (mm): 8 x cable overall diameter

Max. Pulling Tension (N/mm2): 50

Page 53: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

Component1. Plain Annealed Copper Wire

2. Mica Tape3. Cross-linked Polyethylene Compound

4. Low Smoke Zero Halogen(LSZH) Compound

1234

4

3

2

1

FR-XHCU / MGT / XLPE / LSZH ( 2 CORES - 5 CORES )

Mica Taped, XLPE Insulated, LSZH Sheathed Cable, 0.6 / 1kV, IEC60502

NominalConductor Area

(mm2)

No. and Diameterof Wires(no./mm)

Radial Thicknessof Insulation

(mm)

Cable OverallDiameter

(mm)

ApproximateWeight(kg/km)

2 x 1.52 x 2.52 x 42 x 6

2 x 102 x 162 x 252 x 35

2 x 50 (S)2 x 70 (S)2 x 95 (S)

2 x 120 (S)2 x 150 (S)2 x 185 (S)2 x 240 (S)2 x 300 (S)

7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52

19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.52

0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.8

12.112.914.015.117.019.122.524.823.426.429.232.236.039.844.248.4

186223277343409639933

119612921750230828523484430255286806

2 C

OR

ES

Table 47Note: (S) - Sectoral Stranded Conductors.# For current rating and voltage drop, please refer to Table B1.6 and B2.6 on Page 71.

CONSTRUCTIONConductor: Plain Annealed Copper, Class 2 Stranded

Circular, Compacted or Sectored

Fire Barrier: Mica Tape (MGT)

Insulation: Cross-linked Polyethylene (XLPE)Compound

Insulation Colour: 2 Cores:Brown, Blue or Red, Black3 Cores:Brown, Black, Grey or Red, Yellow, Blue4 Cores:Brown, Black, Grey, Blue or Red, Yellow,Blue, Black5 Cores:Brown, Black, Grey, Blue, Green/Yellow orRed, Yellow, Blue, Black, Green/Yellow orWhite with Black numbering or Others

Assembly: Cores cabled together with filler andcovered with Polyester (PET) Tape

Outer Sheath: Low Smoke Zero Halogen (LSZH)Compound with Anti-Termite Charateristic and UV Resistant

Outer Sheath Colour: Orange or Others

ELECTRICAL CHARACTERISTICSOperating Voltage: 0.6/1kV

Operating Temperature: -15ºC to 90ºC

Final Short Circuit 250ºCTemperature:

Test Voltage: 3.5kV for 5 minutes

REFERENCE STANDARDSDesign Specification: IEC60502-1

Conductor: IEC60228, BS EN60228

Fire Resistance: BS6387 (C,W,Z), SS299 (C,W,Z),IEC60331

Flame Retardancy: IEC60332-3-22, BS EN60332-3-22

Low Smoke Zero Halogen: IEC61034-2, BS EN61034-2IEC60754-1, IEC60754-2BS EN50267-2-1, BS EN50267-2-2

INSTALLATION REFERENCEMin. Bending Radius (mm): 8 x cable overall diameter

Max. Pulling Tension (N/mm2): 50

www.taisin.com.sg | 49

Page 54: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

FR-XHCU / MGT / XLPE / LSZH ( 2 CORES - 5 CORES )

Mica Taped, XLPE Insulated, LSZH Sheathed Cable, 0.6 / 1kV, IEC60502

Table 48Note: (S) - Sectoral Stranded Conductors.# For current rating and voltage drop, please refer to Table B1.6 and B2.6 on Page 71.

NominalConductor Area

(mm2)

No. and Diameterof Wires(no./mm)

Radial Thicknessof Insulation

(mm)

Cable OverallDiameter

(mm)

ApproximateWeight(kg/km)

3 x 1.53 x 2.53 x 43 x 6

3 x 103 x 163 x 253 x 35

3 x 50 (S)3 x 70 (S)3 x 95 (S)

3 x 120 (S)3 x 150 (S)3 x 185 (S)3 x 240 (S)3 x 300 (S)3 x 400 (S)3 x 500 (S)

4 x 1.54 x 2.54 x 44 x 6

4 x 104 x 164 x 254 x 35

4 x 50 (S)4 x 70 (S)4 x 95 (S)

4 x 120 (S)4 x 150 (S)4 x 185 (S)4 x 240 (S)4 x 300 (S)4 x 400 (S)4 x 500 (S)

5 x 1.55 x 2.55 x 45 x 6

5 x 105 x 165 x 255 x 355 x 505 x 705 x 95

5 x 120

7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52

19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.5261 / 2.8561 / 3.20

7/ 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52

19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.5261 / 2.8561 / 3.20

7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52

19 / 1.7819 / 2.1419 / 2.5237 / 2.03

0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.82.02.2

0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.82.02.2

0.70.70.70.70.70.70.90.91.01.11.11.2

12.713.614.816.018.020.324.026.526.329.933.236.441.345.651.955.865.271.4

13.814.816.117.519.722.326.529.229.733.737.541.746.751.558.664.274.184.9

15.016.117.519.121.624.429.132.237.042.848.153.4

213259328413577801

1183153418262511333141275056625680829952

1267115789

254312400508718

100614961949236732804364543066348239

10648131771675220967

301372480613872

1229183523972979413755056855

3 C

OR

ES

4 C

OR

ES

5 C

OR

ES

50 | www.taisin.com.sg

Page 55: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

Component1. Plain Annealed Copper Wire

2. Mica Tape3. Cross-linked Polyethylene Compound

4. Low Smoke Zero Halogen(LSZH) Compound

1234

4

3

2

1

FR-XHCU / MGT / XLPE / LSZH ( MULTI-CORES )

Mica Taped, XLPE Insulated, LSZH Sheathed Cable, 0.6 / 1kV, IEC60502

CONSTRUCTIONConductor: Plain Annealed Copper, Class 2 Stranded

Circular or Compacted

Fire Barrier: Mica Tape (MGT)

Insulation: Cross-linked Polyethylene (XLPE)Compound

Insulation Colour: White with Black numbering or Others

Assembly: Cores cabled together and covered withPolyester (PET)Tape

Outer Sheath: Low Smoke Zero Halogen (LSZH)Compound with Anti-Termite Charateristic and UV Resistant

Outer Sheath Colour: Orange or Others

ELECTRICAL CHARACTERISTICSOperating Voltage: 0.6/1kV

Operating Temperature: -15ºC to 90ºC

Final Short Circuit Temperature: 250ºC

Test Voltage: 3.5kV for 5 minutes

REFERENCE STANDARDSDesign Specification: IEC60502-1

Conductor: IEC60228, BS EN60228

Fire Resistance: BS6387 (C,W,Z), SS299 (C,W,Z),IEC60331

Flame Retardancy: IEC60332-3-22, BS EN60332-3-22

Low Smoke Zero Halogen: IEC61034-2, BS EN61034-2IEC60754-1, IEC60754-2BS EN50267-2-1, BS EN50267-2-2

INSTALLATION REFERENCEMin. Bending Radius (mm): 8 x cable overall diameter

Max. Pulling Tension (N/mm2): 50

NominalConductor Area

(mm2)

No. and Diameterof Wires(no./mm)

Radial Thicknessof Insulation

(mm)

Cable OverallDiameter

(mm)

ApproximateWeight(kg/km)

57

101219202437

MU

LTI-

CO

RE

S

Table 49Note: Other conductor sizes & core configurations are available upon request.# For current rating and voltage drop, please refer to Table B1.6 and B2.6 on Page 71.

No. of Cores

1.5

7 / 0.537 / 0.537 / 0.537 / 0.537 / 0.537 / 0.537 / 0.537 / 0.53

0.70.70.70.70.70.70.70.7

15.016.420.521.224.726.028.832.9

301400543608852899

10501470

www.taisin.com.sg | 51

Page 56: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

FR-XHCU / MGT / XLPE / LSZH ( MULTI-CORES )

Mica Taped, XLPE Insulated, LSZH Sheathed Cable, 0.6 / 1kV, IEC60502

NominalConductor Area

(mm2)

No. and Diameterof Wires(no./mm)

Radial Thicknessof Insulation

(mm)

Cable OverallDiameter

(mm)

ApproximateWeight(kg/km)

57

101219202437

57

101219202437

MU

LTI-

CO

RE

S

Table 50Note: Other conductor sizes & core configurations are available upon request.# For current rating and voltage drop, please refer to Table B1.6 and B2.6 on Page 71.

No. of Cores

2.5

4

7 / 0.677 / 0.677 / 0.677 / 0.677 / 0.677 / 0.677 / 0.677 / 0.67

7 / 0.857 / 0.857 / 0.857 / 0.857 / 0.857 / 0.857 / 0.857 / 0.85

0.70.70.70.70.70.70.70.7

0.70.70.70.70.70.70.70.7

16.117.722.222.926.828.331.335.9

17.519.324.425.229.531.134.539.8

372490670756

1077113713331892

480626862982

1422150117662561

52 | www.taisin.com.sg

Page 57: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

Component1. Plain Annealed Copper Wire

2. Mica Tape3. Cross-linked Polyethylene Compound

4. Low Smoke Zero Halogen(LSZH) Compound

5. Aluminium Wire Armoured6. Low Smoke Zero Halogen

(LSZH) Compound

12345

5

4

3

2

1

CONSTRUCTIONConductor: Plain Annealed Copper, Class 2

Stranded Circular or Compacted

Fire Barrier: Mica Tape (MGT)

Insulation: Cross-linked Polyethylene (XLPE)Compound

Insulation Colour: Natural

Bedding: Low Smoke Zero Halogen (LSZH)Compound

Bedding Colour: Black

Armour: Aluminium Wire Armoured (AWA)

Outer Sheath: Low Smoke Zero Halogen (LSZH)Compound with Anti-Termite Charateristic and UV Resistant

Outer Sheath Colour: Orange or Others

ELECTRICAL CHARACTERISTICSOperating Voltage: 0.6/1kV

Operating Temperature: -15ºC to 90ºC

Final Short Circuit Temperature: 250ºC

Test Voltage: 3.5kV for 5 minutes

REFERENCE STANDARDSDesign Specification: IEC60502-1

Conductor: IEC60228, BS EN60228

Fire Resistance: BS6387 (C,W,Z), SS299 (C,W,Z),IEC60331

Flame Retardancy: IEC60332-3-22, BS EN60332-3-22

Low Smoke Zero Halogen: IEC61034-2, BS EN61034-2IEC60754-1, IEC60754-2BS EN50267-2-1, BS EN50267-2-2

INSTALLATION REFERENCEMin. Bending Radius (mm): 10 x cable overall diameter

Max. Pulling Tension (N/mm2): 50

NominalConductor Area

(mm2)

No. andDiameterof Wires(no./mm)

DiameterUnder Armour

(mm)

Armour WireDiameter

(mm)

ApproximateWeight(kg/km)

Cable OverallDiameter

(mm)

Table 51# For current rating and voltage drop, please refer to Table B1.7 and B2.7 on Page 72.

1 x 501 x 701 x 95

1 x 1201 x 1501 x 1851 x 2401 x 3001 x 4001 x 5001 x 6301 x 800

1 x 1000

SIN

GL

E C

OR

E

19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.5261 / 2.8561 / 3.20

127 / 2.52127 / 2.85127 / 3.20

FR-XAHCU / MGT / XLPE / LSZH / AWA / LSZH ( SINGLE CORE )

Mica Taped, XLPE Insulated, LSZH Bedded, Aluminium Wire Armoured, LSZH Sheathed Cable,0.6 / 1kV, IEC60502

6

6

RadialThickness of

Insulation(mm)

1.01.11.11.21.41.61.71.82.02.22.42.62.8

14.316.318.220.122.024.327.129.733.537.041.446.551.4

1.251.251.251.61.61.61.61.62.02.02.02.52.5

20.522.524.427.028.931.234.236.841.845.550.156.661.9

99612651573193122692711337940565168630278569996

12269

www.taisin.com.sg | 53

Page 58: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

Component1. Plain Annealed Copper Wire

2. Mica Tape3. Cross-linked Polyethylene Compound

4. Low Smoke Zero Halogen(LSZH) Compound

5. Galvanised Steel Wire Armoured6. Low Smoke Zero Halogen

(LSZH) Compound

12345

5

4

3

2

1

FR-XSHCU / MGT / XLPE / LSZH / SWA / LSZH ( 2 CORES - 5 CORES )

Mica Taped, XLPE Insulated, LSZH Bedded, Galvanised Steel Wire Armoured, LSZH Sheathed Cable,0.6 / 1kV, BS7846

CONSTRUCTIONConductor: Plain Annealed Copper, Class 2 Stranded

Circular, Compacted or Sectored

Fire Barrier: Mica Tape (MGT)

Insulation: Cross-linked Polyethylene (XLPE)Compound

Insulation Colour: 2 Cores:Brown, Blue or Red, Black3 Cores:Brown, Black, Grey or Red, Yellow, Blue4 Cores:Brown, Black, Grey, Blue or Red, Yellow,Blue, Black5 Cores:Brown, Black, Grey, Blue, Green/ Yellow orRed, Yellow, Blue, Black, Green/Yellow orWhite with Black numbering or Others

Assembly: Cores cabled together with filler andcovered with Polyester (PET) Tape

Bedding: Low Smoke Zero Halogen (LSZH)Compound

Bedding Colour: Black

Armour: Galvanized Steel Wire Armoured (SWA)

Outer Sheath: Low Smoke Zero Halogen (LSZH)Compound with Anti-Termite Charateristic and UV Resistant

Outer Sheath Colour: Orange or Others

ELECTRICAL CHARACTERISTICSOperating Voltage: 0.6/1kV

Operating Temperature: -15ºC to 90ºC

Final Short Circuit Temperature: 250ºC

Test Voltage: 3.5kV for 5 minutes

REFERENCE STANDARDSDesign Specification: BS7846

Conductor: IEC60228, BS EN60228

Fire Resistance: BS6387 (C,W,Z), SS299 (C,W,Z),IEC60331

Flame Retardancy: IEC60332-3-22, BS EN60332-3-22

Low Smoke Zero Halogen: IEC61034-2, BS EN61034-2IEC60754-1, IEC60754-2BS EN50267-2-1, BS EN50267-2-2

INSTALLATION REFERENCEMin. Bending Radius (mm): 10 x cable overall diameter

Max. Pulling Tension (N/mm2): 70

6

6

NominalConductor Area

(mm2)

No. andDiameterof Wires(no./mm)

RadialThickness of

Insulation(mm)

DiameterUnder Armour

(mm)

ApproximateWeight(kg/km)

2 x 1.52 x 2.52 x 42 x 6

2 x 102 x 162 x 252 x 35

2 x 50 (S)2 x 70 (S)2 x 95 (S)

2 x 120 (S)2 x 150 (S)2 x 185 (S)2 x 240 (S)2 x 300 (S)

2 C

OR

ES

Cable OverallDiameter

(mm)

Table 52Note: (S) - Sectoral Stranded Conductors.# For current rating and voltage drop, please refer to Table B1.8 and B2.8 on Page 73.

Armour WireDiameter

(mm)

7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52

19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.52

0.60.70.70.70.70.70.90.91.01.11.11.21.41.61.71.8

9.611.012.613.215.017.020.623.221.824.827.830.634.038.042.046.4

0.90.90.90.9

1.251.251.61.61.61.62.02.02.02.52.52.5

11.416.017.018.220.222.926.730.229.032.236.239.242.848.252.457.0

438531607709888

12281657221022562859380445125298675682229847

54 | www.taisin.com.sg

Page 59: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

FR-XSHCU / MGT / XLPE / LSZH / SWA / LSZH ( 2 CORES - 5 CORES )

Mica Taped, XLPE Insulated, LSZH Bedded, Galvanised Steel Wire Armoured, LSZH Sheathed Cable,0.6 / 1kV, BS7846

NominalConductor Area

(mm2)

No. andDiameterof Wires(no./mm)

RadialThickness of

Insulation(mm)

DiameterUnder Armour

(mm)

ApproximateWeight(kg/km)

3 x 1.53 x 2.53 x 43 x 6

3 x 103 x 163 x 253 x 35

3 x 50 (S)3 x 70 (S)3 x 95 (S)

3 x 120 (S)3 x 150 (S)3 x 185 (S)3 x 240 (S)3 x 300 (S)3 x 400 (S)

4 x 1.54 x 2.54 x 44 x 6

4 x 104 x 164 x 254 x 35

4 x 50 (S)4 x 70 (S)4 x 95 (S)

4 x 120 (S)4 x 150 (S)4 x 185 (S)4 x 240 (S)4 x 300 (S)4 x 400 (S)

5 x 1.55 x 2.55 x 45 x 6

5 x 105 x 165 x 255 x 355 x 505 x 705 x 95

5 x 120

Cable OverallDiameter

(mm)

Armour WireDiameter

(mm)

7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52

19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.5261 / 2.85

7/ 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52

19 / 1.7819 / 2.1419 / 2.5237 / 2.0337 / 2.2537 / 2.5261 / 2.2561 / 2.5261 / 2.85

7 / 0.537 / 0.677 / 0.857 / 1.047 / 1.357 / 1.707 / 2.147 / 2.52

19 / 1.7819 / 2.1419 / 2.5237 / 2.03

0.60.70.70.70.70.70.90.91.01.11.11.21.41.61.71.82.0

0.60.70.70.70.70.70.90.91.01.11.11.21.41.61.71.82.0

0.60.70.70.70.70.70.90.91.01.11.11.2

10.211.712.814.116.118.222.524.924.728.131.634.639.143.649.553.662.4

11.212.914.115.617.820.224.927.628.132.135.739.344.749.156.261.471.1

12.314.215.617.219.622.727.630.635.540.946.451.5

0.90.90.90.9

1.251.251.61.61.61.62.02.02.52.52.52.52.5

0.90.90.9

1.251.251.251.61.61.62.02.02.52.52.52.52.5

3.15

0.90.90.9

1.251.251.61.61.62.02.02.52.5

15.016.717.819.122.024.329.532.131.935.540.243.449.153.860.164.473.6

16.017.919.121.523.726.331.934.835.540.744.549.354.959.767.072.684.2

17.319.220.823.125.729.734.838.043.949.756.461.9

477581677799

1139144021742627291637565029599375149046

112761346416724

541667782

1055133117092574316736225005629379619516

11386142841717922343

619755906

12101560221530513743485863178521

10194

3 C

OR

ES

Table 53Note: (S) - Sectoral Stranded Conductors.# For current rating and voltage drop, please refer to Table B1.8 and B2.8 on Page 73.

4 C

OR

ES

5 C

OR

ES

www.taisin.com.sg | 55

Page 60: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

Component1. Plain Annealed Copper Wire

2. Mica Tape3. Cross-linked Polyethylene Compound

4. Low Smoke Zero Halogen(LSZH) Compound

5. Galvanised Steel Wire Armoured6. Low Smoke Zero Halogen

(LSZH) Compound

12345

5

4

3

2

1

FR-XSHCU / MGT / XLPE / LSZH / SWA / LSZH ( MULTI-CORES )

Mica Taped, XLPE Insulated, LSZH Bedded, Galvanised Steel Wire Armoured, LSZH Sheathed Cable,0.6 / 1kV, BS7846

CONSTRUCTIONConductor: Plain Annealed Copper, Class 2 Stranded

Circular or Compacted

Fire Barrier: Mica Tape (MGT)

Insulation: Cross-linked Polyethylene (XLPE)Compound

Insulation Colour: White with Black numbering or Others

Assembly: Cores cabled together and covered withPolyester (PET) Tape

Bedding: Low Smoke Zero Halogen (LSZH)Compound

Bedding Colour: Black

Armour: Galvanized Steel Wire Armoured (SWA)

Outer Sheath: Low Smoke Zero Halogen (LSZH)Compound with Anti-Termite Charateristic and UV Resistant

Outer Sheath Colour: Orange or Others

ELECTRICAL CHARACTERISTICSOperating Voltage: 0.6/1kV

Operating Temperature: -15ºC to 90ºC

Final Short Circuit Temperature: 250ºC

Test Voltage: 3.5kV for 5 minutes

REFERENCE STANDARDSDesign Specification: BS7846

Conductor: IEC60228, BS EN60228

Fire Resistance: BS6387 (C,W,Z), SS299 (C,W,Z),IEC60331

Flame Retardancy: IEC60332-3-22, BS EN60332-3-22

Low Smoke Zero Halogen: IEC61034-2, BS EN61034-2IEC60754-1, IEC60754-2BS EN50267-2-1, BS EN50267-2-2

INSTALLATION REFERENCEMin. Bending Radius (mm): 10 x cable overall diameter

Max. Pulling Tension (N/mm2): 70

NominalConductor

Area(mm2)

No. andDiameterof Wires(no./mm)

RadialThickness of

Insulation(mm)

DiameterUnder Armour

(mm)

ApproximateWeight(kg/km)

57

101219202437

MU

LTI-

CO

RE

S

Cable OverallDiameter

(mm)

Table 54Note: Other conductor sizes & core configurations are available upon request.# For current rating and voltage drop, please refer to Table B1.8 and B2.8 on Page 73.

Armour WireDiameter

(mm)

No. of Cores

1.5

7 / 0.537 / 0.537 / 0.537 / 0.537 / 0.537 / 0.537 / 0.537 / 0.53

0.60.60.60.60.60.60.60.6

12.213.417.317.921.223.025.629.5

0.90.9

1.251.251.251.61.61.6

17.118.323.123.727.229.932.536.4

627737

110211861526184220842617

6

6

56 | www.taisin.com.sg

Page 61: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

FR-XSHCU / MGT / XLPE / LSZH / SWA / LSZH ( MULTI-CORES )

Mica Taped, XLPE Insulated, LSZH Bedded, Galvanised Steel Wire Armoured, LSZH Sheathed Cable,0.6 / 1kV, BS7846

NominalConductor

Area(mm2)

No. andDiameterof Wires(no./mm)

RadialThickness of

Insulation(mm)

DiameterUnder Armour

(mm)

ApproximateWeight(kg/km)

57

101219202437

57

101219202437

MU

LTI-

CO

RE

S

Cable OverallDiameter

(mm)

Table 55Note: Other conductor sizes & core configurations are available upon request.# For current rating and voltage drop, please refer to Table B1.8 and B2.8 on Page 73.

Armour WireDiameter

(mm)

No. of Cores

2.5

4

7 / 0.677 / 0.677 / 0.677 / 0.677 / 0.677 / 0.677 / 0.677 / 0.67

7 / 0.857 / 0.857 / 0.857 / 0.857 / 0.857 / 0.857 / 0.857 / 0.85

0.70.70.70.70.70.70.70.7

0.70.70.70.70.70.70.70.7

14.115.520.120.825.226.729.834.4

15.517.022.623.427.729.432.838.3

1.251.251.251.251.61.61.61.6

1.251.251.61.61.61.61.62.0

19.721.126.126.832.133.836.941.5

21.322.829.330.134.636.740.146.6

10071167136414752159229926173356

10261206182719682603278331924564

www.taisin.com.sg | 57

Page 62: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

Component1. Plain Annealed Copper Wire

2. Mica Tape3. Cross-linked Polyethylene Compound

4. Low Smoke Zero Halogen(LSZH) Compound

1234

FR-XLCU / MGT / XLPE / LSZH ( MULTI-CORES )

Mica Taped, XLPE Insulated, LSZH Sheathed Cable, 300 / 500V, BS EN50288-7

No. of Cores NominalConductor Area

(mm2)

No. and Diameterof Wires(no./mm)

Radial Thicknessof Insulation

(mm)

ApproximateWeight(kg/km)

23457

1012

MU

LTI-

CO

RE

S

Cable OverallDiameter

(mm)

1.0

7 / 0.437 / 0.437 / 0.437 / 0.437 / 0.437 / 0.437 / 0.43

0.60.60.60.60.60.60.6

9.39.8

10.812.013.217.017.6

90116143177232330380

CONSTRUCTIONConductor: Plain Annealed Copper, Class 2 Stranded

Circular or Compacted

Fire Barrier: Mica Tape (MGT)

Insulation: Cross-linked Polyethylene (XLPE)Compound

Insulation Colour: 2 Cores:Brown, Blue or Red, Black3 Cores:Brown, Black, Grey or Red, Yellow, Blue4 Cores:Brown, Black, Grey, Blue or Red, Yellow,Blue, Black5 Cores:Brown, Black, Grey, Blue, Green/Yellow orRed, Yellow, Blue Black Green/Yellow6 Cores and above:White with Black numberings or Others

Assembly: Cores cabled together and covered withPolyester (PET) Tape

Outer Sheath: Low Smoke Zero Halogen (LSZH)Compound with Anti-Termite Charateristic and UV Resistant

Outer Sheath Colour: Orange or Others

ELECTRICAL CHARACTERISTICSOperating Voltage: 300/500kV

Operating Temperature: -15ºC to 90ºC

Final Short Circuit Temperature: 250ºC

Test Voltage: 2kV for 1 minute

REFERENCE STANDARDSDesign Specification: BS EN50288-7

Conductor: IEC60228, BS EN60228

Fire Resistance: BS6387 (C,W,Z), SS299 (C,W,Z),IEC60331

Flame Retardancy: IEC60332-3-22, BS EN60332-3-22

Low Smoke Zero Halogen: IEC61034-2, BS EN61034-2IEC60754-1, IEC60754-2BS EN50267-2-1, BS EN50267-2-2

INSTALLATION REFERENCEMin. Bending Radius (mm): 8 x cable overall diameter

Max. Pulling Tension (N/mm2): 50

Table 56

4

3

2

1

58 | www.taisin.com.sg

Page 63: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

FR-XLCU / MGT / XLPE / LSZH ( MULTI-CORES )

Mica Taped, XLPE Insulated, LSZH Sheathed Cable, 300 / 500V, BS EN50288-7

No. of Cores NominalConductor Area

(mm2)

No. and Diameterof Wires(no./mm)

Radial Thicknessof Insulation

(mm)

ApproximateWeight(kg/km)

23457

1012

23457

1012

2345

MU

LTI-

CO

RE

S

Cable OverallDiameter

(mm)

1.5

2.5

4.0

7 / 0.537 / 0.537 / 0.537 / 0.537 / 0.537 / 0.537 / 0.53

7 / 0.677 / 0.677 / 0.677 / 0.677 / 0.677 / 0.677 / 0.67

7 / 0.857 / 0.857 / 0.857 / 0.85

0.60.60.60.60.60.60.6

0.70.70.70.70.70.70.7

0.70.70.70.7

9.910.511.712.814.118.218.8

11.312.013.214.516.220.921.6

12.413.214.515.9

105138179214282402464

142188236285388551640

182245310376

Table 57

www.taisin.com.sg | 59

Page 64: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

Component1. Plain Annealed Copper Wire

2. Mica Tape3. Cross-linked Polyethylene Compound

4. Tinned Copper Drain Wire5. Aluminium / Polyester Tape6. Low Smoke Zero Halogen

(LSZH) Compound12345

5

4

3

2

1

FR-XOLCU / MGT / XLPE / OS / LSZH ( SINGLE PAIR )

Mica Taped, XLPE Insulated, Overall Aluminium Foil Screened, LSZH Sheathed Cable,300 / 500V, BS EN50288-7

No. of Pairs NominalConductor Area

(mm2)

No. and Diameterof Wires(no./mm)

Radial Thicknessof Insulation

(mm)

ApproximateWeight(kg/km)

1P1P1PS

ING

LE

PA

IR

Cable OverallDiameter

(mm)

1.01.52.5

7 / 0.437 / 0.537 / 0.67

0.60.60.7

10.010.612.0

98113150

CONSTRUCTIONConductor: Plain Annealed Copper, Class 2 Stranded

Circular

Fire Barrier: Mica Tape (MGT)

Insulation: Cross-linked Polyethylene (XLPE)Compound

Insulation Colour: Black, White or Others

Lay Up: Pair - Cores twisted to pair

Wrap Film: Polyester Binder Tape

Overall Screen: Aluminium/Polyester Tape, with aTinned Copper Drain Wire 0.5mm2

(7/0.3mm) (OS)

Outer Sheath: Low Smoke Zero Halogen (LSZH)Compound with Anti-Termite Characteristic and UV Resistant

Outer Sheath Colour: Orange or Others

ELECTRICAL CHARACTERISTICSOperating Voltage, Uo/U: 300/500V

Operating Temperature: -15ºC to 90ºC

Final Short Circuit Temperature: 250ºC

Test Voltage: 2kV for 1 minute

REFERENCE STANDARDSDesign Specification: BS EN50288-7

Conductor: IEC60228, BS EN60228

Fire Resistance: BS6387 (C, W, Z), SS299 (C, W, Z),IEC60331

Flame Retardancy: IEC60332-3-22, BS EN60332-3-22

Low Smoke Zero Halogen: IEC61034-2, BS EN61034-2IEC60754-1, IEC60754-2BS EN50267-2-1, BS EN50267-2-2

INSTALLATION REFERENCEMin. Bending Radius (mm): 8 x cable overall diameter

Max. Pulling Tension (N/mm2): 50

Table 58Note: Class 5 conductors are available upon request.

6

6

60 | www.taisin.com.sg

Page 65: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

APPENDIX ATable A1.1Schedule of Installation Methods of cables (including Reference Methods)for determining current-carrying capacity

NOTE 1: The illustrations are not intended to depict actual product or installation practices but are indicative of the method described.NOTE 2: The installation and reference methods stated are in line with IEC. However, not all methods have a corresponding rating for all cable types.

Non-sheathed cables in conduit in a thermallyinsulated wall with an inner skin having athermal conductance of not less than 10 W/m2k

Multicore cable in conduit in a thermallyinsulated wall with an inner skin having athermal conductance of not less than 10 W/m2k

Multicore cable direct in a thermally insulatedwall with an inner skin having a thermalconductance of not less than 10 W/m2k

Non-sheathed cables in conduit on a woodenor masonry wall or spaced less than 0.3 x conduitdiameter from it c

Multicore cable in conduit on a wooden ormasonry wall or spaced less than 0.3 x conduitdiameter from it c

Non-sheathed cables in cable trunking on awooden or masonry wall6 - run horizontally b

7 - run vertically b, c

Multicore cable in cable trunking on a woodenor masonry wall8 - run horizontally b

9 - run vertically b, c

Non-sheathed cables in suspended cabletrunking b

Multicore cable in suspended cabletrunking b

Non-sheathed cables run in mouldings c, e

Non-sheathed cables in skirting trunking

Multicore cable in skirting trunking

Reference Methodto be used to determine

current-carrying capacity

Installation Method

Examples DescriptionNumber

1

2

3

4

5

67

89

10

11

12

13

14

A

A

A

B

B

B

B*

B

B

A

B

B

b Values given for Installation Method B in Appendix A are for a single circuit. Where there is more than one circuit in the trunking the group rating factor given in Table C2.1 is applicable,irrespective of the presence of an internal barrier or partition.

c Care is needed where the cable runs vertically and ventilation is restricted. The ambient temperature at the top of the vertical section can be much higher.

e The thermal resistivity of the enclosure is assumed to be poor because of the material of construction and possible air spaces. Where the construction is thermally equivalent to InstallationMethods 6 or 7, Reference Method B may be used.

* Still under consideration in IEC.

ROOM

ROOM

ROOM

6 7

9

10 11

TV

ICT

TV

ICT

13 14

8

www.taisin.com.sg | 61

Page 66: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

62 | www.taisin.com.sg

≥0.3 De

≥0.3 De

≥0.3 De

≥0.3 De

≥0.3 De

≥0.3 De

APPENDIX ATable A1.2Schedule of Installation Methods of cables (including Reference Methods)for determining current-carrying capacity

NOTE 1: The illustrations are not intended to depict actual product or installation practices but are indicative of the method described.NOTE 2: The installation and reference methods stated are in line with IEC. However, not all methods have a corresponding rating for all cable types.

Single-core or multicore cables:Fixed on (clipped direct), or spaced less than0.3 x cable diameter from a wooden or masonrywall c

Single-core or multicore cables:Fixed directly under wooden or masonry ceiling

Single-core or multicore cables:Spaced from a ceiling

Single-core or multicore cables:On unperforated tray run horizontally orvertically c, h

Single-core or multicore cables:On unperforated tray run horizontally orvertically c, h

Single-core or multicore cables:On brackets or on a wire mesh tray runhorizontally or vertically c, h

Single-core or multicore cables:Spaced more than 0.3 x the cable diameter froma wall

Single-core or multicore cables:On a ladder c

Single-core or multicore cable suspendedfrom or incorporating a support wire or harness

Reference Methodto be used to determine

current-carrying capacity

Installation Method

Examples DescriptionNumber

20

21

22

30

31

32

33

34

35

C

B(Higher than standard ambient temperatures

may occur with this installation method)

E, F or G*(Higher than standard ambient temperatures

may occur with this installation method)

Cwith item 2 of Table C2.1

E or F

E or F

E, F or Gg

E or F

E or F

c Care is needed where the cable runs vertically and ventilation is restricted. The ambient temperature at the top of the vertical section can be much higher.

f The thermal resistivity of the enclosure is assumed to be poor because of the material of construction and possible air spaces. Where the construction is thermally equivalent to InstallationMethods 6, 7, 8 or 9. Reference Method B may be used.

g The factor in Table C2.1 may also be used.

h De = the external diameter of a multicore cable:– 2.2 x the cable diameter when three single-core cables are bound in trefoil, or– 3 x the cable diameter when three single-core cables are laid in flat formation.

* Still under consideration in IEC.

Page 67: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

DeV

DeV

DeV

DeV

DeV

DeV

VDe

APPENDIX ATable A1.3Schedule of Installation Methods of cables (including Reference Methods)for determining current-carrying capacity

NOTE 1: The illustrations are not intended to depict actual product or installation practices but are indicative of the method described.NOTE 2: The installation and reference methods stated are in line with IEC. However, not all methods have a corresponding rating for all cable types.

Bare or non-sheathed cables on insulators

Single-core or multicore cables:In a building void c, h, i

Non-sheathed cables:- In conduit- In a building void- In masonry having a thermal resistivity not

greater than 2 K.m/W c, i, j

Single-core or multicore cables:- In conduit- In a building void- In masonry having a thermal resistivity not

greater than 2 K.m/W c, j

Non-sheathed cables:- In cable ducting- In a building void- In masonry having a thermal resistivity not

greater than 2 K.m/W c, i, j

Single-core or multicore cables:- In cable ducting- In a building void- In masonry having a thermal resistivity not

greater than 2 K.m/W c, i, j

Non-sheathed cables:- In cable ducting- In masonry having a thermal resistivity not

greater than 2 K.m/W c, h, i

Single-core or multicore cables:- In cable ducting- In masonry having a thermal resistivity not

greater than 2 K.m/W c, h, i

Single-core or multicore cables:- In a ceiling void- In a suspended floor h, i

Non-sheathed cables in flush cable trunkingin the floor

Reference Methodto be used to determine

current-carrying capacity

Installation Method

Examples DescriptionNumber

36

40

41

42

43

44

45

46

47

50

G

Where 1.5 De ≤ V ≤ 20 DeUse B

Where 1.5 De ≤ VUse B

Where 1.5 De ≤ VUse B

Where 1.5 De ≤ VUse B

Where 1.5 De ≤ VUse B

Where 1.5 De ≤ V ≤ 50 DeUse B

Where 1.5 De ≤ V ≤ 50 DeUse B

Where 1.5 De ≤ V ≤ 50 DeUse B

B

c Care is needed where the cable runs vertically and ventilation is restricted. The ambient temperature at the top of the vertical section can be much higher.

g The factors in table C2.1 may also be used.

h De = the external diameter of a multicore cable:- 2.2x the cable diameter when three single-core cables are bound in trefoil, or- 3x the cable diameter when three single-core cables are laid in flat formation.

i V = the smaller dimension or diameter of a masonry duct or void, or the vertical depth of a rectangular duct, floor or ceiling void or channel.

j De = external diameter of conduit or vertical depth of cable ducting.

DeV

www.taisin.com.sg | 63

Page 68: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

TV

ICT

TV

ICT

VDe

APPENDIX ATable A1.4Schedule of Installation Methods of cables (including Reference Methods)for determining current-carrying capacity

NOTE 1: The illustrations are not intended to depict actual product or installation practices but are indicative of the method described.NOTE 2: The installation and reference methods stated are in line with IEC. However, not all methods have a corresponding rating for all cable types.

Multicore cable in flush cable trunking in thefloor

Non-sheathed cables in flush trunking c

Multicore cable in flush trunking c

Non-sheathed cables or single-core cables

in conduit in an unventilated cable channel runhorizontally or vertically c, i, k, m

Non-sheathed cables in conduit in an open orventilated cable channel in the floor l, m

Sheathed single-core or multicore cable inan open or ventilated cable channel runhorizontally or vertically m

Single-core or multicore cable direct inmasonry having a thermal resistivity not greaterthan 2 K.m/W- Without added mechanical protection n, o

Single-core or multicore cable direct inmasonry having a thermal resistivity not greaterthan 2 K.m/W- With added mechanical protection n, o

(e.g. capping)

Non-sheathed cables or single-core cables

in conduit in masonry having a thermalresistivity not greater than 2 K.m/W o

Multicore cables in conduit in masonryhaving a thermal resistivity not greater than2 K.m/W o

Reference Methodto be used to determine

current-carrying capacity

Installation Method

Examples DescriptionNumber

51

52

53

54

55

56

57

58

59

60

B

B

B

Where 1.5 De ≤ VUse B

B

B

C

C

B

B

c Care is needed where the cable runs vertically and ventilation is restricted. The ambient temperature at the top of the vertical section can be much higher.

k De = external diameter of conduit.

i V = the smaller dimension or diameter of a masonry duct or void, or the vertical depth of a rectangular duct, floor or ceiling void or channel. The depth of the channel is more importantthan the width.

i For multicore cable installed as method 55, use current-carrying capacity for Reference Method B.

m It is recommended that these installation methods are used only in areas where access is restricted to authorized persons so that the reduction in current-carrying capacity and the fire hazarddue to the accumulation of debris can be prevented.

n For cables having conductors not greater than 16mm2, the current carrying capacity may be higher.

o Thermal resistivity of masonry is not greater than 2 K.m/W. The term masonry is taken to include brickwork, concrete, plaster and the like (excludes thermally insulating materials).

52 53

64 | www.taisin.com.sg

Page 69: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

Multicore unarmoured cable in conduit or incable ducting in the ground

Single-core unarmoured cable in conduit orin cable ducting in the ground

Sheathed, armoured or multicore cables

direct in the ground– Without added mechanical protection

(see note)

Sheathed, armoured or multicore cables

direct in the ground– With added mechanical protection

(eg. cable covers)(see note)

Reference Methodto be used to determine

current-carrying capacity

Installation Method

Examples DescriptionNumber

70

71

72

73

D

D

D

D

Note: The inclusion of directly buried cables is satisfactory where the soil thermal resistivity is of the order of 2.5K.m/W. For lower soil resistivities, the current-carrying capacity for directly buriedcables is appreciably higher than for cables in ducts.

APPENDIX ATable A1.5Schedule of Installation Methods of cables (including Reference Methods)for determining current-carrying capacity

NOTE 1: The illustrations are not intended to depict actual product or installation practices but are indicative of the method described.NOTE 2: The installation and reference methods stated are in line with IEC. However, not all methods have a corresponding rating for all cable types.

www.taisin.com.sg | 65

Page 70: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

APPENDIX BCurrent Carrying Capacity ( IN AMPERES )Table B1.1: Single-core copper conductor, 70ºC PVC insulated, non-armoured, with or without sheathed cables,Ambient air temperature: 30ºC, Ambient ground temperature: 20ºC, Soil thermal resistivity(cable buried in ground): 2.5K.m/W

ConductorCross-

SectionalArea

Reference Method A(enclosed in conduit

in thermally insulatingwall etc)

Reference Method B(enclosed in conduit

on wall or in trunking etc)

Reference Method C(clipped direct)

Reference Method F(in free air or on a perforated cable tray horizontal or vertical)

2 Cables,Single-Phase

a.c. or d.c.

Touching Spaced by One Cable Diameter

3 or 4 Cables,3-Phase a.c.

2 Cables,Single-Phase

a.c. or d.c.

3 or 4 Cables,3-Phase a.c.

2 Cables,Single-Phase

a.c. or d.c.Flat and

Touching

3 or 4 Cables,3-Phase

a.c. Flat andTouching or

Trefoil

2 Cables,Single-Phase

a.c. or d.c.Flat

3 Cables,3-Phasea.c. Flat

3 Cables,3-Phase

a.c. Trefoil

2 Cables, Single-Phasea.c. or d.c., or

3 Cables, 3-Phase a.c. Flat

Horizontal Vertical

AAAAAAAAAAAmm2

1.01.52.546

10162535507095

120150185240300400500630800

1000

1114.520263446618099

119151182210240273321367

–––––

10.513.518243142567389

108136164188216245286328

–––––

13.517.52432415776

101125151192232269300341400458546626720

––

1215.5212836506889

110134171207239262296346394467533611

––

15.5202737476587

114141182234284330381436515594694792904

10301154

14182533435979

104129167214261303349400472545634723826943

1058

–––––––

131162196251304352406463546629754868

100510861216

–––––––

114143174225275321372427507587689789905

10201149

–––––––

110137167216264308356409485561656749855971

1079

–––––––

146181219281341396456521615709852982

113812651420

–––––––

130162197254311362419480569659795920

107011881337

Voltage Drop ( IN mV/A/m )Table B2.1: Single-core copper conductor, 70ºC PVC insulated, non-armoured, with or without sheathed cables,Ambient air temperature: 30ºC, Conductor operating temperature: 70ºC

ConductorCross-

SectionalArea

2 Cables, Single-Phase a.c.

Reference Methods C & F(clipped direct, on tray or in free air)

Cables Spaced*,Flat

mV/A/mmm2

1.01.52.546

1016

2535507095

120150185240300400500630800

1000

3 or 4 Cables, 3-Phase a.c.

Reference Methods C & F(clipped direct, on tray or in free air)

2 Cablesd.c.

Cables Touching,Flat

Cables Touching,Trefoil

ReferenceMethods A & B

(enclosed inconduit ortrunking)

Cables Spaced*Cables Touching

ReferenceMethods A & B

(enclosed inconduit ortrunking)

mV/A/mmV/A/mmV/A/mmV/A/mmV/A/mmV/A/mmV/A/m

442918117.34.42.8

1.751.250.930.630.460.360.290.23

0.1800.1450.1050.0860.0680.0530.042

442918117.34.42.8

442918117.34.42.8

442918117.34.42.8

3825159.56.43.82.4

3825159.56.43.82.4

3825159.56.43.82.4

3825159.56.43.82.4

Note: *Spacings larger than one cable diameter will result in a larger voltage drop.

r x z1.80 0.33 1.801.30 0.31 1.300.95 0.30 1.000.65 0.29 0.720.49 0.28 0.560.39 0.27 0.470.31 0.27 0.410.25 0.27 0.370.195 0.26 0.330.160 0.29 0.310.130 0.26 0.290.110 0.26 0.280.094 0.25 0.27

– –

r x z1.75 0.20 1.751.25 0.195 1.250.93 0.190 0.950.63 0.185 0.660.47 0.180 0.500.37 0.175 0.410.30 0.175 0.340.24 0.170 0.290.185 0.165 0.250.150 0.165 0.220.120 0.160 0.200.098 0.155 0.1850.081 0.155 0.1750.068 0.150 0.1650.059 0.150 0.160

r x z1.75 0.29 1.801.25 0.28 1.300.93 0.28 0.970.63 0.27 0.690.47 0.27 0.540.37 0.26 0.450.29 0.26 0.390.24 0.26 0.350.185 0.25 0.310.150 0.25 0.290.115 0.25 0.270.093 0.24 0.260.076 0.24 0.250.061 0.24 0.250.050 0.24 0.24

r x z1.50 0.29 1.551.10 0.27 1.100.81 0.26 0.850.56 0.25 0.610.42 0.24 0.480.33 0.23 0.410.27 0.23 0.360.22 0.23 0.320.17 0.23 0.290.14 0.23 0.270.12 0.22 0.250.10 0.22 0.250.08 0.22 0.24

– –

r x z1.50 0.175 1.501.10 0.170 1.100.80 0.165 0.820.55 0.160 0.570.41 0.155 0.430.32 0.150 0.360.26 0.150 0.300.21 0.145 0.260.160 0.145 0.220.130 0.140 0.1900.105 0.140 0.1750.086 0.135 0.1600.072 0.135 0.1500.060 0.130 0.1450.052 0.130 0.140

r x z1.50 0.25 1.551.10 0.24 1.100.80 0.24 0.840.55 0.24 0.600.41 0.23 0.470.32 0.23 0.400.26 0.23 0.340.21 0.22 0.310.160 0.22 0.270.130 0.22 0.250.105 0.21 0.240.086 0.21 0.230.072 0.21 0.220.060 0.21 0.220.052 0.20 0.21

r x z1.50 0.32 1.551.10 0.32 1.150.80 0.32 0.860.55 0.31 0.630.40 0.31 0.510.32 0.30 0.440.26 0.30 0.400.21 0.30 0.360.160 0.29 0.340.130 0.29 0.320.100 0.29 0.310.081 0.29 0.300.066 0.28 0.290.053 0.28 0.290.044 0.28 0.28

BS 6004BS 6231SS 358IEC 60227IEC 60502-1

66 | www.taisin.com.sg

Page 71: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

APPENDIX BCurrent Carrying Capacity ( IN AMPERES )Table B1.2: Multi-core, 70ºC PVC insulated, PVC sheathed non-armoured cablesAmbient air temperature: 30ºC, Ambient ground temperature: 20ºC, Soil thermal resistivity (cable buried in ground): 2.5K.m/W

1.01.52.546

10162535507095

120150185240300400

*With or without a protective conductor.

ConductorCross-Sectional

Area

Reference Method A(enclosed in conduit in thermally

insulating wall etc)

Reference Method B(enclosed in conduit on a wall or

in trunking etc)

Reference Method C(clipped direct)

One 2-CoreCable*,

Single-Phasea.c. or d.c.

One 3-CoreCable* or

One 4-Core Cable,3-Phase a.c.

A

Reference Method E(in free air or on a perforated cable tray

horizontal or vertical)

One 2-CoreCable*,

Single-Phasea.c. or d.c.

One 3-core Cable*or One 4-Core

Cable,3-Phase a.c.

One 2-CoreCable*,

Single-Phasea.c. or d.c.

One 3-CoreCable* or

One 4-Core Cable,3-Phase a.c.

One 2-CoreCable*,

Single-Phasea.c. or d.c.

One 3-CoreCable* or

One 4-Core Cable,3-Phase a.c.

AAAAAAAmm2

1114

18.5253243577592

110139167192219248291334

1013

17.523293952688399

125150172196223261298

1316.5233038526990

111133168201232258294344394470

11.51520273446628099

118149179206225255297339402

1519.52736466385

112138168213258299344392461530634

13.517.5243241577696

119144184223259299341403464557

17223040517094

119148180232282328379434514593715

14.518.52534436080

101126153196238276319364430497597

Voltage Drop ( IN mV/A/m )Table B2.2: Multi-core 70ºC PVC insulated, PVC sheathed non-armoured cablesAmbient temperature: 30ºC, Conductor operating temperature: 70ºC

2-Core Cable, d.c.

mV/A/mmm2

1.01.52.546

1016

2535507095

120150185240300400

3 or 4 Core Cable, 3-Phase a.c.

mV/A/mmV/A/m

r x z1.75 0.170 1.751.25 0.165 1.250.93 0.165 0.940.63 0.160 0.650.47 0.155 0.500.38 0.155 0.410.30 0.155 0.340.25 0.150 0.290.190 0.150 0.240.155 0.145 0.210.115 0.145 0.185

2-Core Cable, Single-Phase a.c.ConductorCross-Sectional

Area

442918117.34.42.8

1.751.250.930.630.460.360.290.23

0.1800.1450.105

442918117.34.42.8

3825159.56.43.82.4

r x z1.50 0.145 1.501.10 0.145 1.100.80 0.140 0.810.55 0.140 0.570.41 0.135 0.430.33 0.135 0.350.26 0.130 0.290.21 0.130 0.250.165 0.130 0.210.135 0.130 0.1850.100 0.125 0.160

BS 6346IEC60502-1

Note: *Spacings larger than one cable diameter will result in a larger voltage drop.

www.taisin.com.sg | 67

Page 72: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

APPENDIX BCurrent Carrying Capacity ( IN AMPERES )Table B1.3: Single-core 70ºC PVC insulated, PVC sheathed armoured cables (non-magnetic armour)Ambient air temperature: 30ºC, Ambient ground temperature: 20ºC, Soil thermal resistivity (cable buried in ground): 2.5K.m/W

ConductorCross-

SectionalArea

Reference Method C(clipped direct)

Reference Method F(in free air or on a perforated cable tray horizontal or vertical)

2 Cables,Single-Phase

a.c. or d.c.flat

Touching Spaced by One Cable Diameter

3 or 4 Cables,3-Phase a.c.

flat

2 Cables,Single-Phase

a.c. or d.c.flat

3 Cables,3-Phase a.c.

flat

2 Cables,d.c.

2 Cables,Single-Phase a.c.

3 or 4 Cables,3-Phase a.c.

Horizontal Vertical

AAAAAAAAAAAmm2

507095

120150185240300400500630800

1000

193245296342393447525594687763843919975

179225269309352399465515575622669710737

205259313360413469550624723805891976

1041

189238285327373422492547618673728777808

181231280324373425501567657731809886945

229294357415479548648748885

1035121814411685

216279340396458525622719851997

117413901627

229287349401449511593668737810893943

1008

217272332383429489568640707777856905967

230286338385436490566616674721771824872

212263313357405456528578632676723772816

Touching

3 Cables,3-Phase a.c.

trefoilHorizontal VerticalHorizontal Vertical

Voltage Drop ( IN mV/A/m )Table B2.3: Single-core 70ºC PVC insulated, PVC sheathed armoured cables (non-magnetic armour)Ambient temperature: 30ºC, Conductor operating temperature: 70ºC

Reference Method C & F(clipped direct, on tray or free air)

mm2 mV/A/m

ConductorCross-

SectionalArea

507095

120150185240300400500630800

1000

0.930.630.460.360.290.23

0.1800.1450.1050.0860.0680.0530.042

r x z0.93 0.22 0.950.64 0.21 0.680.48 0.20 0.520.39 0.195 0.430.31 0.190 0.370.26 0.190 0.320.20 0.180 0.270.160 0.180 0.240.140 0.175 0.220.120 0.170 0.210.105 0.165 0.1950.095 0.160 0.1850.091 0.155 0.180

2 Cables,d.c.

3 or 4 Cables, 3-Phase a.c.2 Cables, Single-Phase a.c.

Touching Spaced* Trefoil and Touching Flat and Touching Flat and Spaced*

Note: *Spacings larger than one cable diameter will result in a larger voltage drop.

mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m

r x z0.92 0.30 0.970.66 0.29 0.720.51 0.28 0.580.42 0.28 0.500.34 0.27 0.440.29 0.27 0.390.23 0.26 0.350.190 0.26 0.320.180 0.24 0.300.165 0.23 0.290.150 0.22 0.270.145 0.21 0.250.140 0.190 0.24

r x z0.80 0.190 0.820.56 0.180 0.580.42 0.175 0.450.33 0.170 0.370.27 0.165 0.320.22 0.160 0.270.175 0.160 0.230.140 0.155 0.210.120 0.130 0.1950.105 0.145 0.1800.091 0.145 0.1700.082 0.140 0.1600.079 0.135 0.155

r x z0.79 0.26 0.840.57 0.25 0.620.44 0.25 0.500.36 0.24 0.430.30 0.24 0.380.25 0.23 0.340.20 0.23 0.300.165 0.22 0.280.160 0.21 0.260.145 0.20 0.250.135 0.195 0.230.125 0.180 0.220.125 0.165 0.21

r x z0.79 0.34 0.860.59 0.32 0.680.47 0.31 0.570.40 0.30 0.500.34 0.30 0.450.29 0.29 0.410.24 0.28 0.370.20 0.28 0.340.21 0.25 0.320.190 0.24 0.300.175 0.22 0.280.170 0.195 0.260.165 0.170 0.24

BS 6346

68 | www.taisin.com.sg

Page 73: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

APPENDIX BCurrent Carrying Capacity ( IN AMPERES )Table B1.4: Multi-core 70ºC PVC insulated, PVC sheathed armoured cablesAmbient air temperature: 30ºC, Ambient ground temperature: 20ºC, Soil thermal resistivity (cable buried in ground): 2.5K.m/W

ConductorCross-Sectional

Area

Reference Method C(clipped direct)

A

Reference Method D(direct in ground or in ducting in ground,

in or around buildings)

One 2-Core Cable,Single-Phase

a.c. or d.c.

One 3 or 4-Core Cable,3-Phase a.c.

mm2

1.52.546

10162535507095

120150185240300400

Reference Method E(in free air or on a perforated cable tray

etc, horizontal or vertical)

One 2-Core Cable,Single-Phase

a.c. or d.c.

One 3 or 4-Core Cable,3-Phase a.c.

One 2-Core Cable,Single-Phase

a.c. or d.c.

One 3 or 4-Core Cable,3-Phase a.c.

AAAAA

212838496789

118145175222269310356405476547621

182533425877

102125151192231267306348409469540

223141537297

128157190241291336386439516592683

192635456283

110135163207251290332378445510590

22293746607899

119140173204231261292336379

1824303850648298

116143169192217243280316

Voltage Drop ( IN mV/A/m )Table B2.4: Multi-core 70ºC PVC insulated, PVC sheathed armoured cablesAmbient temperature: 30ºC, Conductor operating temperature: 70ºC

ConductorCross-Sectional Area

2-Core Cable,d.c.

mV/A/m

3 or 4-Core Cable,3-Phase a.c.

mm2

2-Core Cable,Single-Phase a.c.

mV/A/mmV/A/m

1.52.546

1016

2535507095

120150185240300400

2918117.34.42.8

1.751.250.930.630.460.360.290.23

0.1800.1450.105

2918117.34.42.8

25159.56.43.82.4

r x z1.75 0.170 1.751.25 0.165 1.250.93 0.165 0.940.63 0.160 0.650.47 0.155 0.500.38 0.155 0.410.30 0.155 0.340.25 0.150 0.290.190 0.150 0.240.155 0.145 0.210.115 0.145 0.185

r x z1.50 0.145 1.501.10 0.145 1.100.80 0.140 0.810.55 0.140 0.570.41 0.135 0.430.33 0.135 0.350.26 0.130 0.290.21 0.130 0.250.165 0.130 0.210.135 0.130 0.1850.100 0.125 0.160

BS 6346

Note: *Spacings larger than one cable diameter will result in a larger voltage drop.

www.taisin.com.sg | 69

Page 74: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

APPENDIX BCurrent Carrying Capacity ( IN AMPERES )Table B1.5: Single-core 90ºC XLPE / Cross-Linked LSZH / EPR insulated, unarmoured,with or without sheath (PVC / LSZH) cablesAmbient air temperature: 30ºC, Ambient ground temperature: 20ºC, Soil thermal resistivity (cable buried in ground): 2.5K.m/W

1.01.52.546

10162535507095

120150185240300400500630800

1000

14192635456181

106131158200241278318362424486

–––––

1317233140547395

117141179216249285324380435

–––––

172331425475

100133164198253306354393449528603683783900

––

15202837486688

117144175222269312342384450514584666764

––

192534465981

109143176228293355413476545644743868990

113012881443

17.5233141547499

130161209268326379436500590681793904

103311791323

–––––––

161200242310377437504575679783940

1083125413581520

–––––––

141176216279342400464533634736868998

115112751436

–––––––

135169207268328383444510607703823946

108812141349

–––––––

182226275353430500577661781902

10851253145415811775

–––––––

161201246318389454527605719833

10081169136214851671

ConductorCross-

SectionalArea

Reference Method A(enclosed in conduit

in thermally insulatingwall etc)

Reference Method B(enclosed in conduit

on a wall orin trunking etc)

Reference Method C(clipped direct)

Reference Method F(in free air or on a perforated cable tray etc,

horizontal or vertical etc)

2 Cables,Single-Phase

a.c. or d.c.

Touching Spaced by One Cable Diameter

3 or 4 Cables,3-Phase a.c.

2 Cables,Single-Phase

a.c. or d.c.

3 or 4 Cables,3-Phase a.c.

2 Cables,Single-Phase

a.c. or d.c.Flat and

Touching

3 or 4 Cables,3-Phase

a.c. Flat andTouching or

Trefoil

2 Cables,Single-Phase

a.c. or d.c.Flat

3 Cables,3-Phasea.c. Flat

3 Cables,3-Phase

a.c. Trefoil

2 Cables, Single-Phasea.c. or d.c., or

3 Cables, 3-Phase a.c. Flat

Horizontal Vertical

AAAAAAAAAAAmm2

Reference Method G(in free air)

Note: 1. Where a conductor operates at a temperature exceeding 70ºC it must be ascertained that the equipment connected to the conductor is suitable for the conductor operating temperature.2. Where cables in this table are connected to equipment or accessories designed to operate at a temperature not exceeding 70ºC, the current ratings given in the equivalent table for

70ºC thermoplastic insulated cables must be used.

ConductorCross-

SectionalArea

2 Cablesd.c.

2 Cables, Single-Phase a.c.

Reference MethodsA & B

(enclosed inconduit ortrunking)

mV/A/m

3 or 4 Cables, 3-Phase a.c.

Reference Methods C, F & G(clipped direct, on tray or in fre air)

Reference MethodsA & B

(enclosed inconduit ortrunking)

Reference Methods C, F & G(clipped direct, on tray or in free air)

mV/A/mmV/A/mmV/A/mmV/A/mmV/A/mmV/A/mmV/A/mmm2

1.01.52.546

1016

2535507095

120150185240300400500630800

1000

463119127.94.72.9

1.851.350.990.680.490.390.320.25

0.1900.1550.1200.0930.0720.0560.045

463119127.94.72.9

463119127.94.72.9

463119127.94.72.9

402716106.84.02.5

402716106.84.02.5

402716106.84.02.5

402716106.84.02.5

Voltage Drop ( IN mV/A/m )Table B2.5: Single-core 90ºC XLPE / Cross-Linked LSZH / EPR insulated, unarmoured, with or without sheath (PVC / LSZH) cablesAmbient temperature: 30ºC, Conductor operating temperature: 90ºC

Cables Touching,Trefoil

Cables Touching,Flat

Cables Spaced*,Flat

CablesTouching

CablesSpaced*

r x z1.85 0.31 1.901.35 0.29 1.351.00 0.29 1.050.70 0.28 0.750.51 0.27 0.580.41 0.26 0.480.33 0.26 0.430.27 0.26 0.370.21 0.26 0.330.175 0.25 0.310.140 0.25 0.290.120 0.25 0.280.100 0.25 0.27

– –

r x z1.85 0.190 1.851.35 0.180 1.350.99 0.180 1.000.68 0.175 0.710.49 0.170 0.520.39 0.165 0.430.32 0.165 0.360.26 0.165 0.300.20 0.160 0.250.160 0.160 0.220.130 0.155 0.200.105 0.155 0.1850.086 0.155 0.1750.072 0.150 0.1700.063 0.150 0.165

r x z1.85 0.28 1.851.35 0.27 1.350.99 0.27 1.000.68 0.26 0.730.49 0.26 0.560.39 0.25 0.470.32 0.25 0.410.25 0.25 0.360.195 0.25 0.310.155 0.25 0.290.125 0.24 0.270.098 0.24 0.260.078 0.24 0.250.064 0.24 0.250.054 0.24 0.24

r x z1.60 0.27 1.651.15 0.25 1.150.87 0.25 0.900.60 0.24 0.650.44 0.23 0.500.35 0.23 0.420.29 0.23 0.370.23 0.23 0.320.185 0.22 0.290.150 0.22 0.270.125 0.22 0.250.100 0.22 0.240.088 0.21 0.23

– –

r x z1.60 0.165 1.601.15 0.155 1.150.86 0.155 0.870.59 0.150 0.610.43 0.145 0.450.34 0.140 0.370.28 0.140 0.310.22 0.140 0.260.170 0.140 0.220.140 0.140 0.1950.110 0.135 0.1750.090 0.135 0.1600.074 0.135 0.1500.062 0.130 0.1450.055 0.130 0.140

r x z1.60 0.27 1.651.15 0.26 1.200.86 0.26 0.890.59 0.25 0.650.43 0.25 0.490.34 0.24 0.420.28 0.24 0.370.22 0.24 0.330.17 0.24 0.290.135 0.24 0.270.110 0.24 0.260.085 0.24 0.250.068 0.23 0.240.055 0.23 0.240.047 0.23 0.24

IEC 60502-1BS 7211*based on600/1000VapplicationBS 7889

Note: *Spacings larger than one cable diameter will result in a larger voltage drop.

r x z1.60 0.190 1.601.15 0.180 1.150.86 0.180 0.870.59 0.175 0.620.43 0.170 0.460.34 0.165 0.380.28 0.165 0.320.22 0.165 0.280.170 0.165 0.240.135 0.160 0.210.110 0.160 0.1950.088 0.160 0.1800.071 0.160 0.1700.059 0.155 0.1650.050 0.155 0.165

70 | www.taisin.com.sg

Page 75: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

APPENDIX BCurrent Carrying Capacity ( IN AMPERES )Table B1.6: Multi-core 90ºC XLPE / Cross-Linked LSZH / EPR insulated, unarmoured, thermoplastic (PVC / LSZH) sheathed cablesAmbient air temperature: 30ºC, Ambient ground temperature: 20ºC, Soil thermal resistivity (cable buried in ground): 2.5K.m/W

ConductorCross-Sectional

Area

Reference Method A(enclosed in conduit

in thermally insulating wall etc.)

A

Reference Method C(clipped direct)

One 2-Core Cable,Single-Phase

a.c. or d.c.

One 3 or 4-CoreCable*,

3-Phase a.c.

mm2

1.01.52.546

10162535507095

120150185240300400

Reference Method B(enclosed in conduit on a wall

or in trunking etc.)

One 3 or 4-CoreCable,

3-Phase a.c.

A

Voltage Drop ( IN mV/A/m )Table B2.6: Multi-core 90ºC XLPE / Cross-Linked LSZH / EPR insulated, unarmoured, thermoplastic (PVC / LSZH) sheathed cablesAmbient temperature: 30ºC, Conductor operating temperature: 90ºC

ConductorCross-Sectional Area

2-Core Cable,d.c.

mV/A/m

3 or 4-Core Cable,3-Phase a.c.

mm2

2-Core Cable,Single-Phase a.c.

mV/A/mmV/A/m

1.01.52.546

1016

2535507095

120150185240300400

463119127.94.72.9

1.851.350.980.670.490.390.310.25

0.1950.1550.120

463119127.94.72.9

402716106.84.02.5

r x z1.85 0.160 1.901.35 0.155 1.350.99 0.155 1.000.67 0.150 0.690.50 0.150 0.520.40 0.145 0.420.32 0.145 0.350.26 0.145 0.290.200 0.140 0.240.160 0.140 0.210.130 0.140 0.190

r x z1.60 0.140 1.651.15 0.135 1.150.86 0.135 0.870.59 0.130 0.600.43 0.130 0.450.34 0.130 0.370.28 0.125 0.300.22 0.125 0.260.175 0.125 0.210.140 0.120 0.1850.115 0.120 0.165

Reference Method E(in free air or on a perforated cable tray

etc, horizontal or vertical)

A

One 2-Core Cable,Single-Phase

a.c. or d.c.

A

One 3 or 4-CoreCable,

3-Phase a.c.

One 2-Core Cable,Single-Phase

a.c. or d.c.

AAAA

One 3 or 4-CoreCable,

3-Phase a.c.

One 2-Core Cable,Single-Phase

a.c. or d.c.

14.518.5253342577699

121145183220253290329386442

1316.5223038516889

109130164197227259295346396

17223040516991

119146175221265305334384459532625

1519.52635446080

105128154194233268300340398455536

192433455880

107138171209269328382441506599693803

17223040527196

119147179229278322371424500576667

212636496386

115149185225289352410473542641741865

182332425475

100127158192246298346399456538621741

Note: 1. Where a conductor operates at a temperature exceeding 70ºC it must be ascertained that the equipment connected to the conductor is suitable for the conductor operating temperature.2. Where cables in this table are connected to equipment or accessories designed to operate at a temperature not exceeding 70ºC, the current ratings given in the equivalent table for

70ºC thermoplastic insulated cables must be used.

Note: *Spacings larger than one cable diameter will result in a larger voltage drop.

IEC 60502-1BS 7629-1

www.taisin.com.sg | 71

Page 76: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

APPENDIX BCurrent Carrying Capacity ( IN AMPERES )Table B1.7: Single-core 90ºC XLPE / Cross-Linked LSZH / EPR insulated, armoured (non-magnetic armour),thermoplastic (PVC / LSZH) sheathed cablesAmbient air temperature: 30ºC, Ambient ground temperature: 20ºC, Soil thermal resistivity (cable buried in ground): 2.5K.m/W

ConductorCross-

SectionalArea

Reference Method C(clipped direct)

Reference Method F(in free air or on a perforated cable tray horizontal or vertical)

2 Cables,Single-Phase

a.c. or d.c.flat

Touching Spaced by One Cable Diameter

3 or 4 Cables,3-Phase a.c.

flat

2 Cables,Single-Phase

a.c. or d.c.flat

3 Cables,3-Phase a.c.

flat

2 Cables,d.c.

2 Cables,Single-Phase a.c.

3 or 4 Cables,3-Phase a.c.

Horizontal Vertical

AAAAAAAAAAAmm2

507095

120150185240300400500630800

1000

237303367425488557656755853962

108211701261

220277333383437496579662717791861904961

253322389449516587689792899

1016114612461345

232293352405462524612700767851935987

1055

222285346402463529625720815918

102711191214

284356446519600688815943

11371314152818092100

270349426497575660782906

10941266147417442026

282357436504566643749842929

1032113912041289

266337412477539614714805889989

109211551238

288358425485549618715810848923992

10421110

266331393449510574666755797871940978

1041

Touching

3 Cables,3-Phase a.c.

trefoilHorizontal VerticalHorizontal Vertical

Note: 1. Where a conductor operates at a temperature exceeding 70ºC it must be ascertained that the equipment connected to the conductor is suitable for the conductor operating temperature.2. Where cables in this table are connected to equipment or accessories designed to operate at a temperature not exceeding 70ºC, the current ratings given in the equivalent table for

70ºC thermoplastic insulated cables must be used.

Voltage Drop ( IN mV/A/m )Table B2.7: Single-core 90ºC XLPE / Cross-Linked LSZH / EPR insulated, armoured (non-magnetic armour), thermoplastic (PVC / LSZH)sheathed cablesAmbient temperature: 30ºC, Conductor operating temperature: 90ºC

Reference Method C & F(clipped direct, on tray or in free air)

mm2 mV/A/m

ConductorCross-

SectionalArea

507095

120150185240300400500630800

1000

0.980.670.490.390.310.25

0.1950.1550.1150.0930.0730.0560.045

r x z0.99 0.21 1.000.68 0.200 0.710.51 0.195 0.550.41 0.190 0.450.33 0.185 0.380.27 0.185 0.330.21 0.180 0.280.170 0.175 0.250.145 0.170 0.220.125 0.170 0.210.105 0.165 0.1950.090 0.160 0.1900.092 0.155 0.180

2 Cables,d.c.

3 or 4 Cables, 3-Phase a.c.2 Cables, Single-Phase a.c.

Touching Spaced* Trefoil and Touching Flat and Touching Flat and Spaced*

Note: *Spacings larger than one cable diameter will result in a larger voltage drop.

mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m

r x z0.98 0.29 1.000.69 0.29 0.750.53 0.28 0.600.43 0.27 0.510.36 0.27 0.450.30 0.26 0.400.24 0.26 0.350.195 0.25 0.320.180 0.24 0.300.165 0.24 0.290.150 0.23 0.270.145 0.23 0.270.140 0.21 0.25

r x z0.86 0.180 0.870.59 0.170 0.620.44 0.170 0.470.35 0.165 0.390.29 0.160 0.330.23 0.160 0.280.180 0.155 0.240.145 0.150 0.210.125 0.150 0.1950.105 0.145 0.1800.092 0.145 0.1700.086 0.140 0.1650.080 0.135 0.155

r x z0.84 0.25 0.880.60 0.25 0.650.46 0.24 0.520.38 0.24 0.440.31 0.23 0.390.26 0.23 0.340.21 0.22 0.300.170 0.22 0.280.160 0.21 0.270.145 0.20 0.250.135 0.195 0.240.130 0.180 0.230.125 0.170 0.21

r x z0.84 0.33 0.900.62 0.32 0.700.49 0.31 0.580.41 0.30 0.510.34 0.29 0.450.29 0.29 0.410.24 0.28 0.370.20 0.27 0.340.20 0.27 0.330.190 0.24 0.310.175 0.23 0.290.175 0.195 0.260.165 0.180 0.24

IEC 60502-1BS 5467BS 6724

72 | www.taisin.com.sg

Page 77: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

APPENDIX BCurrent Carrying Capacity ( IN AMPERES )Table B1.8: Multi-core 90ºC XLPE / Cross-Linked LSZH / EPR insulated, armoured, thermoplastic(PVC / LSZH) sheathed cablesAmbient air temperature: 30ºC, Ambient ground temperature: 20ºC, Soil thermal resistivity (cable buried in ground): 2.5K.m/W

Note: 1. Where a conductor operates at a temperature exceeding 70ºC it must be ascertained that the equipment connected to the conductor is suitable for the conductor operating temperature.2. Where cables in this table are connected to equipment or accessories designed to operate at a temperature not exceeding 70ºC, the current ratings given in the equivalent table for

70ºC thermoplastic insulated cables must be used.

Voltage Drop ( IN mV/A/m )Table B2.8: Multi-core 90ºC XLPE / Cross-Linked LSZH / EPR insulated, armoured, thermoplastic (PVC / LSZH) sheathed cablesAmbient temperature: 30ºC, Conductor operating temperature: 90ºC

ConductorCross-Sectional Area

2-Core Cable,d.c.

mV/A/m

3 or 4-Core Cable,3-Phase a.c.

mm2

2-Core Cable,Single-Phase a.c.

mV/A/mmV/A/m

1.52.546

1016

2535507095

120150185240300400

3119127.94.72.9

1.851.350.980.670.490.390.310.25

0.1950.1550.120

3119127.94.72.9

2716106.84.02.5

r x z1.85 0.160 1.901.35 0.155 1.350.99 0.155 1.000.67 0.150 0.690.50 0.150 0.520.40 0.145 0.420.32 0.145 0.350.26 0.145 0.290.20 0.140 0.240.16 0.140 0.210.13 0.140 0.190

r x z1.60 0.140 1.651.15 0.135 1.150.86 0.135 0.870.59 0.130 0.600.43 0.130 0.450.34 0.130 0.370.28 0.125 0.300.22 0.125 0.260.175 0.125 0.210.140 0.120 0.1850.115 0.120 0.165

ConductorCross-Sectional

Area

Reference Method C(clipped direct)

A

Reference Method D(direct in ground or in ducting in ground,

in or around buildings)

One 2-Core Cable,Single-Phase

a.c. or d.c.

One 3 or 4-Core Cable,3-Phase a.c.

mm2

1.52.546

10162535507095

120150185240300400

Reference Method E(in free air or on a perforated cable tray

etc, horizontal or vertical)

One 2-Core Cable,Single-Phase

a.c. or d.c.

One 3 or 4-Core Cable,3-Phase a.c.

One 2-Core Cable,Single-Phase

a.c. or d.c.

One 3 or 4-Core Cable,3-Phase a.c.

AAAAA

2736496285

110146180219279338392451515607698787

233142537394

124154187238289335386441520599673

2939526690

115152188228291354410472539636732847

253344567899

131162197251304353406463546628728

253343537191

116139164203239271306343395446

21283644587596

115135167197223251281324365

IEC 60502-1BS 5467BS 6724BS 7846

Note: *Spacings larger than one cable diameter will result in a larger voltage drop.

www.taisin.com.sg | 73

Page 78: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

APPENDIX CRating Factor for Ambient Temperature

The current-carrying capacities in this work standard are based upon the following reference ambient temperatures:i) For non-sheathed and sheathed cables in air, irrespective of the installation method : 30ºCii) For buried cables, either directly in the soil or in ducts in the ground : 20ºC

When the ambient temperature in the intended location of the non-sheathed or sheathed cables differs from the reference ambient temperature,please refer to the appropriate rating factors as below table (Table C1.1 and C1.2).

Table C1.1: Rating factors for ambient air

temperatures other than 30ºC to be applied to the

current-carrying capacities for cables in free air.

Table C1.2: Rating factors for ambient ground

temperatures other than 20ºC to be applied to the

current-carrying capacities for cables buried to

ground.

Ambient TemperatureºC

PVC XLPE

253035404550556065707580859095

1.031.000.940.870.790.710.610.50

–––––––

1.021.000.960.910.870.820.760.710.650.580.500.41

–––

Ground TemperatureºC

PVC XLPE

101520253035404550556065707580

1.101.051.000.950.890.840.770.710.630.550.45

––––

1.071.041.000.960.930.890.850.800.760.710.650.600.530.460.38

74 | www.taisin.com.sg

Table B3.1: Short Circuit Ratings for Low Voltage Cables

I = Short Circuit Rating (kA)

S = Nominal Conductor Area (mm2)

t = Duration of Short Circuit (Sec)

K = Insulation Material Specific Constant

XLPE & Cross-linked Polyolefin (XLSZH) Insulated Cable

K= 0.143

PVC Insulated Cable

K= 0.115 ( S ≤ 300 mm2)

K= 0.103 ( S > 300mm2)

NominalConductor Area

Short Circuit Ratingfor 1 second

XLPE & XLSZH

1.52.546

10162535507095

120150185240300400500630800

1000

(mm2)

Short Circuit Ratingfor 1 second

PVC

(kA) (kA)

0.21450.35750.5720.8581.43

2.2883.5755.0057.15

10.0113.58517.1621.45

26.45534.3242.957.271.5

90.09114.4143

0.17250.2875

0.460.691.151.84

2.8754.0255.758.05

10.92513.8

17.2521.275

27.634.541.251.5

64.8982.4103

The maximum permissible short circuit current of cables up to 1kVwith copper conductors could be calculated with the following formula

Where

APPENDIX BShort Circuit Rating

I (kA) = _______S

t x K

Page 79: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

Table C2.1: Rating factors for one circuit or one multicore cable or for a group of circuits,

or a group of multicore cables, to be used with current-carrying capacities of Tables B1.1

to Tables B1.8.

Arrangement(cables touching)

1

Number of circuits or multicore cables To be used withcurrent-carrying

capacities,Reference

2 3 4 5 6 7 8 9 12 16 20

Bunched in air,on a surface,

embedded orenclosed

Single layer on wallor floor

Single layermulticore on a

perforatedhorizontal or

vertical tray cablesystem

Single layermulticore on cableladder system or

cleats, etc

1.00

1.00

1.00

1.00

Note:1. These factors are applicable to uniform groups of cables, equally loaded.

2. Where horizontal clearances between adjacent cables exceeds twice their overall diameter, no rating factor need be applied.

3. The same factors are applied to: - groups of two or three single-core cables:- multicore cables.

4. If a system consists of both two- and three-core cables, the total number of cables is taken as the number of circuits, and the corresponding factor is applied to the tables for two loadedconductors for the two-core cables, and to the Tables for three loaded conductors for the three-core cables.

5. If a group consists of n single-core cables it may either be considered as n/2 circuits of two loaded conductors or n/3 circuits of three loaded conductors.

6. The rating factors given have been averaged over the range of conductor sizes and types of installation included in Tables B1.1 to B1.8 the overall accuracy of tabulated values is within 5%.

7. For some installations and for other methods not provided for in the above table, it may be appropriate to use factors calculated for specific cases, see for example Table C3.1 to C3.2.

8. When cables having differing conductor operating temperature are grouped together, the current rating is to be based upon the lowest operating temperature of any cable in the group.

9. If, due to known operating conditions, a cable is expected to carry not more than 30 % of its grouped rating, it may be ignored for the purpose of obtaining the rating factor for the rest of thegroup. For example, a group of N loaded cables would normally required a group rating factor of Cg applied to the tabulated It. However, if M cables in the group carry loads which are notgreater than 0.3 CgIt amperes the other cables can be sized by using the group rating factor corresponding to (N-M) cables.

0.80

0.85

0.88

0.87

0.70

0.79

0.82

0.82

0.65

0.75

0.77

0.80

0.60

0.73

0.75

0.80

0.57

0.72

0.73

0.79

0.54

0.72

0.73

0.79

0.52

0.71

0.72

0.78

0.50

0.70

0.72

0.78

0.45

0.70

0.72

0.78

0.41

0.70

0.72

0.78

0.38

0.70

0.72

0.78

MethodsA to F

Method C

MethodsE and F

Table C1.3: Rating factors for cables buried direct in the ground or in an underground conduit

system to BS EN 50086-2-4 for soil thermal resistivities other than 2.5 K.m/W to be applied

to the current-carrying capacities for Reference Method D

Thermal resistivity K.m/W

Rating factor for cables in buried ducts

Rating factor for direct buried cables

30.960.90

0.51.281.88

0.81.201.62

11.181.5

1.51.1

1.28

21.051.12

2.511

Note:1. The rating factors given have been averaged over the range of conductor sizes and types of installation included in the relevant tables in this appendix. The overall accuracy of rating factors is

within ± 5%.

2. The rating factors are applicable to cables drawn into buried ducts For cables laid direct in the ground the rating factors for thermal resistivities less than 2 5 K.m/W will be higher. Where moreprecise values, are required they may be calculated by methods given in BS 7769 (BS IEC 60287).

3. The rating factors are applicable to ducts buried at depths of up to 0.8 m.

www.taisin.com.sg | 75

APPENDIX CRating Factor for Soil Thermal Resistivities

Page 80: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

APPENDIX CTable C2.2: Rating factors for more than one circuit, cables laid directly in the

Ground-Reference Method D in Tables A1.1 to A1.5. Single-core or multicore cables.

Numberof circuits

Cable-to-cable clearance (a)

Nil (cablestouching)

One cablediameter

0.125m 0.25m 0.5m

23456

0.750.650.600.550.50

0.800.700.600.550.55

0.850.750.700.650.60

0.900.800.750.700.70

0.900.850.800.800.80

Note:1. Values given apply to an installation depth of 0.7m and a soil thermal resisitivity of 2.5K.m/W. These are average values for the range of cable sizes and types quoted for Table B1.1 to B1.8.

The process of averaging, together with rounding off, can result in some cases in errors of up to ± 10%. (Where more precise values are required they may be calculated by methods given inBS 7769 (BS IEC 60287)).

2. In case of a thermal resistivity lower than 2.5 K.m/W the rating factors can, in general, be increased and can be calculated by the methods given in BS 7769 (BS IEC 60287).

MulticoresCables

Single-CoreCables

aa

a a

Table C2.3: Rating factors for more than one circuit, cables laid in ducts in the ground

- Reference Method D in Tables B1.1 to B1.8

Numberof cables

Duct-to-duct Clearance (a)

Nil (ductstouching)

0.25m 0.5m 1.0m

23456

0.850.750.700.650.60

0.900.850.800.800.80

0.950.900.850.850.80

0.950.950.900.900.90

Note:1. Values given apply to an installation depth of 0.7m and a soil thermal resisitivity of 2.5K.m/W. These are average values for the range of cable sizes and types quoted for Table B1.1 to B1.8.

The process of averaging, together with rounding off, can result in some cases in errors of up to ± 10%. (Where more precise values are required they may be calculated by methodsgiven in BS 7769 (BS IEC 60287).

2. In case of a thermal resistivity lower than 2.5 K.m/W the rating factors can, in general, be increased and can be calculated by the methods given in BS 7769 (BS IEC 60287).

i. Multicore Cables in a Single-Way Ducts

MulticoresCables

a

Number ofsingle-corecircuits of

2 or 3 cables

Duct-to-duct Clearance (a)

Nil (ductstouching)

0.25m 0.5m 1.0m

23456

0.800.700.650.600.60

0.900.800.750.700.70

0.900.850.800.800.80

0.950.900.900.900.90

Note:1. Values given apply to an installation depth of 0.7m and a soil thermal resistivity of 2.5K.m/W. These are average values for the range of cable sizes and types quoted for Table B1.1 to B1.8.

The process of averaging, together with rounding off, can result in some cases in errors of up to ± 10%. (Where more precise values are required they may be calculated by methodsgiven in BS 7769 (BS IEC 60287)).

2. In case of a thermal resistivity lower than 2.5 K.m/W the rating factors can, in general, be increased and can be calculated by the methods given in BS 7769 (BS IEC 60287).

ii. Single-Core Cables in Non-Ferrous Single-Way Ducts

Single-CoresCables

a a

76 | www.taisin.com.sg

Page 81: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

Spaced

≥20mm

De De

Spaced

≥225mm De

De

≥20mm

SpacedDe De

APPENDIX CTable C3.1Rating factors for groups of more than one multicore cables, to be applied to referencecurrent-carrying capacities for multicore cables in free air- Reference Method E in Tables B 1.1 to B1.8

Perforated cable traysystems (Note 3)

Perforated cable traysystems (Note 3)

Vertical perforated cabletray systems (Note 4)

Vertical perforated cabletray systems (Note 4)

Unperforated cable traysystems

Cable ladder systems,cleats, wire mesh tray,etc (Note 3)

Cable ladder systems,cleats, wire mesh tray,etc (Note 3)

Note 1: Values given are averages for the cable types and range of conductor sizes considered in Tables B1.1 to B1.8. The spread of values is generally less than 5%.

Note 2: Factors apply to single layer groups of cables as shown above and do not apply when cables are installed in more than one layer touching each other. Values for such installations maybe significantly lower and must be determined by an appropriate method.

Note 3: Values are given for the vertical spacing between cable tras of 300mm and at least 20mm between cable trays and wall. For closer spacing the factors should be reduced.

Note 4: Values are given for horizontal spacing between cable trays of 225mm with cable trays mounted back to back. For closer spacing the factors should be reduced.

Installation Method in Table A1.1 to A1.5

31

31

31

31

30

32

33

34

32

33

34

Number of cables per tray or ladder

1

Numberof trays or

ladders

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

1.00

0.97

0.97

0.97

0.97

1.00

1.00

1.00

1.00

1.00

1.00

1

2

3

6

1

2

3

1

2

1

2

1

2

3

6

1

2

3

6

1

2

3

2

0.87

0.86

0.84

1.00

0.99

0.98

0.88

0.91

0.91

0.84

0.83

0.82

0.81

0.86

0.85

0.84

1.00

0.99

0.98

3

0.80

0.79

0.77

0.98

0.96

0.95

0.81

0.89

0.88

0.78

0.76

0.75

0.73

0.80

0.79

0.77

1.00

0.98

0.97

4

0.77

0.76

0.73

0.95

0.92

0.91

0.76

0.88

0.87

0.75

0.72

0.71

0.69

0.78

0.76

0.73

1.00

0.97

0.96

6

0.73

0.71

0.68

0.91

0.87

0.85

0.71

0.87

0.85

0.71

0.68

0.66

0.63

0.76

0.73

0.68

1.00

0.96

0.93

9

0.68

0.66

0.64

0.70

0.68

0.63

0.61

0.58

0.73

0.70

0.64

See item 4 of Table C2.1

See item 4 of Table C2.1

See item 4 of Table C2.1

Touching

≥20mm

Touching

≥225mm

Touching

≥20mm

Touching

≥300mm

≥20mm

≥300mm

≥300mm

www.taisin.com.sg | 77

Page 82: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

Spaced

≥225mm ≥2 De

De

≥300mm

≥2 De De

APPENDIX CTable C3.2Rating factors for groups of one or more circuits of single-core cables to be applied to referencecurrent-carrying capacity for one circuit of single-core cables in free air- Reference Method F in Tables B1.1 to B1.8

Use as a multiplierto rating for:

3

Perforated cable traysystems (Note 3)

Vertical perforated cabletray systems (Note 4)

Cable ladder systems,cleats, wire mesh tray,etc. (Note 3)

Perforated cable traysystems (Note 3)

Vertical perforated cabletray systems (note 4)

Cable ladder systems,cleats, wire mesh tray,etc. (Note 3)

Note 1: Values given are averages for the cable types and range of conductor sizes considered in Tables B1.1 to B1.8. The spread of values is generally less than 5%.

Note 2: Factors apply to single layer groups of cables (or trefoil groups) as shown above and do not apply when cables are installed in more than one layer touching each other. Values for suchinstallations may be significantly lower and must be determined by an appropriate method.

Note 3: Values are given for vertical spacing between cable trays of 300mm and at least 20mm between cable trays and wall. For closer spacing the factors should be reduced.

Note 4: Values are given for horizontal spacing between cable trays of 225mm with cable trays mounted back to back. For closer spacing the factors should be reduced.

Note 5: For circuits having more than one cable in parallel per phase, each three-phase set of conductors is to be considered as a circuit for the purpose of this table.

Installation Method in Table A1.1 to A1.5

31

31

32

33

34

31

31

32

33

34

Three cables inhorizontal formation

Three cables invertical formation

Three cables inhorizontal formation

Three cables in trefoilformation

Three cables in trefoilformation

Three cables in trefoilformation

Number of Three-Phase circuits per tray or ladder

21

Numberof trays or

ladders

0.87

0.81

0.78

0.96

0.89

0.86

0.96

0.89

0.86

0.89

0.86

1.00

0.93

0.90

0.91

0.87

0.85

0.86

0.84

0.97

0.93

0.90

0.98

0.93

0.92

0.91

0.90

1.00

0.95

0.94

0.98

0.96

0.95

0.96

0.95

1.00

0.98

0.97

1.00

0.97

0.96

1.00

1.00

1.00

0.97

0.96

1

2

3

1

2

1

2

3

1

2

3

1

2

1

2

3

Touching

≥225mm

Touching

≥300mm

Touching

≥300mm

≥2 De De

≥300mm

≥20mm

≥20mm

≥20mm

≥20mm

78 | www.taisin.com.sg

Page 83: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

APPENDIX DTable D1.1Cable Cores Colour Code

Function

Protective conductorFunctional earthing conductor

AC Power Circuit

Single Phase Circuit

- Phase- Neutral

Three Phase Circuit

- Phase1- Phase2- Phase3- Neutral

DC Two-Wire Unearthed Circuit

- Positive- Negative

DC Two-Wire Earthed Circuit

- Positive (of negative earth)- Negative (of negative earth)- Positive (of positive earth)- Negative (of positive earth)

DC Three-Wire Circuit

- Positive- Mid-wire (may be earthed)- Negative

Alpha-Numeric Existing Core Colours New Harmonized Core Colour

––

LN

L1L2L3N

L+L–

L+MNL–

L+ML–

Green / YellowCream

RedBlack

RedYellowBlueBlack

RedBlack

RedBlackBlackBlue

RedBlackBlue

Green / YellowCream

BrownBlue

BrownBlackGreyBlue

BrownGrey

BrownBlueBlueGrey

BrownBlueGrey

In March 2004, the Amendment No.2: AMD 14905 to BS 7671:2001 (IEE Wiring Regulations Sixteenth Edition) has been harmonized with the CENELECStandard HD 384.5.514: Identification including 514.3: Identification of conductor and with the CENELEC Harmonization Document HD 308 S2: 2001Identification of cores in cables and flexible cords.

The change in cable core colours is a major development that will affect the way wiring cable colours are distinguished and installed. Currently,for three phase fixed electrical installations, the wiring cable colours for the ìlineî connections are red, yellow and blue respectively. The new threephase harmonized cable core colours will be brown, black and grey, following that of the new BS 7671:2008 Requirements for electrical installations,IEE Wiring Regulations, 17th Edition. A number of countries in the European Union as well as Hong Kong and Singapore have implemented theseharmonized cable core colours.

For any new electrical installation that involved extension from existing wiring system, BS 7671 has been modified to align with these cable core colourswhere suitable marking/labelling method eg. Colour tapes, sleeves, discs or by alphanumeric (letters and/or numbers) is allowed. See below figures:-

L LN N

L LN N

SINGLE-PHASE CIRCUITSExisting Harmonized

L1 L1L2 L2L3 L3N N

THREE-PHASE CIRCUITSExisting Harmonized

L LN N

SINGLE-PHASE CIRCUITSExisting New

L1 L1L2 L2L3 L3N N

THREE-PHASE CIRCUITSExisting Harmonized

Label & Colour sleeze shall beprovided at interface.

Label & Colour sleeze shall beprovided at interface.

Identification of Cores in Cables

www.taisin.com.sg | 79

Page 84: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

A GUIDE TO FIRE PERFORMANCE TESTS & STANDARDS FOR CABLESCables and wires are like blood vessels in the body which keep us alive. They supply the essential energy to every part of residential, public,commercial and industrial buildings as well as vital infrastructure facilities, to provide power for lighting, computer systems, electrical appliancesand machinery, etc. Comply with various relevant performance standards to ensure integrity and reliability.

This guide provides you with an idea of the mandated tests and standards to ensure cables and wires meet international fire performancerequirements.

TYPES OF FIRE PERFORMANCE CABLESIt is important for cables to have fire survival properties because they are widely distributed throughout a building and can be the main cause offire transmission to unaffected areas. There are 2 types of characteristics for Fire Performance: Active - which ensures the cable, continues to transmitpower and signals during a fire, and Passive ñ which limits the spread of fire that can cause severe damage to property and reduces the emissionof fumes and toxic gases that can lead to loss of human lives.

These safety features are necessary to allow occupants of buildings and facilities to have the time to evacuate without being hurt or overcome byfire, toxic gases and fumes.

In Europe and the United States, where most of the fire performance standards originated, there is a slight difference in concerns over fire behaviour.The European countries are concerned about all aspects of fire-affected cables, including harmful halogen, smoke and gas contents, whereas theconcern over in the United States is the flame spread and smoke characteristics from cables.

Cables are therefore rated for their various Fire Resistant, Flame Retardant, Low Smoke Zero Halogen (LSZH) and Low Smoke Fume (LSF) characteristics.

FLAME RETARDANT CABLESFlame Retardant cables are designed to minimise the spread of flame in the event of a fire. Whether it is a single wire or a bundled wire cable, it issupposed to retard flame spread so that the fire may ideally be limited to a small area and allow for emergency response to put it out. Our PVC-based cables have this characteristic and are widely used for their low cost.

LOW SMOKE AND FUME CABLES (LSF)LSF cables are slow to ignite and they burn slowly. LSF cables emit much smaller amount of smoke and fumes, with characteristics similar to thatof LSZH-FRT cables. Although its emission will still have halogen but the content is much lesser than that from PVC cables. To ensure better fireperformance, LSF cables are manufactured with flame retardant PVC blended with HCL and smoke absorbent material for maximum efficiency.Low Smoke Zero Halogen Flame Retardant Cables (LSZH-FRT)

Halogens are harmful non-metal elements such as fluorine (F), chlorine (Cl), bromine (Br), iodine (I), and astatine (At). FRT cables are designed withspecial materials not only with self-extinguishing property, but also with low smoke and fume emissions without halogens, as well as an absenceof toxic gas emission in case of combustion. Thus, LSZH-FRT cables outperform PVC and LSF cables with additional protection from fire spread andthe emission of toxic gas and corrosive elements. These cables are suitable for use in inadequately ventilated areas such as those in aircraft, ships,and military facilities.

FIRE RESISTANT CABLESFire Resistant cables are designed with superior fire resistant property to continue to operate in the event of a fire for a specific period of time(usually between 30 and 180 minutes). They are specified for used in vital installations and essential support facilities, such as a fire alarm system,as they are designed to withstand fire and maintain circuit integrity. In such cables the stranded annealed copper conductor is sealed with a fire-resisting mica tape wrap, so that even after the insulation has been burnt phase-to phase and phase-to-earth contact can be prevented. They arealso designed to withstand mechanical shock and perform under wet condition.

STANDARDS FOR FLAME RETARDANCY (European & British Standards)There are three classes of tests for flame propagation in cables. They are the IEC 60332-1, IEC 60332-2 and IEC 60332-3 standards. The EuropeanCommittee for Electromechanical Standardization (CENELEC) - which adopts the standards of the International Electro-technical Committee (IEC)- uses the first two to assess flame propagation characteristics of a single wire, and the IEC 60332-3 for similar characteristics test for bundled cables,which is more stringent.

The British Standards for flame propagation test for single wire and bundled wires and cables are the BS EN 60332-1 (formerly known as BS4066-1) and BS EN 50266-2 (formerly known as BS 4066-3).

FLAME TEST ON SINGLE VERTICAL INSULATED WIRE/CABLE(IEC 60332-1, BS EN 60332-1)The flame propagation characteristic of a single wire or cable is tested using a 60cm cable specimen that is fixed vertically in a metal chamber. Acalibrated gas burner adjusted with the recommended flow rates of gas and air is lighted and applied at 45-degree angle on the surface of the testsample at 475 mm (+/- 5mm) from the lower edge of the upper horizontal clamp. The flame is applied continuously for a duration (60 - 480 sec)corresponding to the diameter of the wire/cable. After the flame has been extinguished, the specimen is cleaned and examined. It passes the testif the charring does not reach 50mm from the lower edge of the top clamp, or the charring does not extend beyond 475mm from the point of flameapplication.

FLAME TEST ON BUNCHED WIRES/CABLES(IEC 60332-3, BS EN 50266-2)This test comprises four categories (A, B, C & D) according to the volume of combustible material per metre of cable. It determines the bunchedcableís ability to limit flame spread.

The test sample consists of several pieces of cable each 3.5 m long, in order to have the required quantity of combustible material per metre ofspecimen. The cables are installed in a metal chamber on the front of a vertical ladder and are subjected to a gas burner flame for a specified timeunder controlled air flow. At the end of the specified duration, the burnt and charred portion of the cable must not be more than 2.5 m from theburner point.

APPENDIX E

80 | www.taisin.com.sg

Page 85: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

STANDARDS FOR FIRE RESISTANCEIEC 60331-11 (APPARATUS 750ºC)IEC 60331-21 (CABLES RATED UP TO 0.6/1.0kV)To verify circuit integrity in the event of a fire, the cable sample is held on a flame at about 750ºC for 3 hours under its rated voltage. The samplemust then be re-energised in not less than 12 hours after the test, and to pass, the specimen must not breakdown and circuit integrity must bemaintained.

BS6387This test is performed to investigate the cableís ability to maintain circuit integrity under three conditions - fire only, fire with spray of water, andfire with mechanical shock.

Resistance to fire - the cable while performing at its rated voltage is subjected to gas burner fire at the specified temperature for the respectivecategories - Category A - 3 hours at 650ºC, Category B - 3 hours at 750ºC and Category C - 3 hours at 950ºC.

Resistance to fire and water (Category W) is another cable specimen with rated voltage running is exposed for 15 minutes to flame at 650º C anda further 15 minutes to fire and a continuous spray of water.

Resistance to fire and mechanical shock in this test a new cable sample with rated voltage running is mounted on a vertical panel which is struckwith a steel bar for 15 minutes while subjected to a flame. The burning temperatures required for the respective categories are Category X (650ºC),Category Y (750ºC) and Category Z (950ºC).

STANDARDS FOR HALOGEN, SMOKE EMISSION, CORROSIVITY AND TOXICITYSMOKE DENSITY(IEC 61034-2, BS EN 61034-2)To measure the density of smoke from a burning cable, samples are placed horizontally in a 3 square metre metal cabinet and burned by flamefrom 100 cubic cm of alcohol in a metal tray. A fan is used to ensure uniformity of the smoke and light transmittance is measured by a photometricsystem in the cabinet. The result is expressed as percentage light transmittance and the specimen is rated to have passed the test if the value ismore than 60%, as the higher the percentage the less smoke is emitted.

HALOGEN EMISSION(IEC 60754-1, BS EN 50267-2-1)To determine the amount of corrosive gases, such as fluorine, chlorine, bromine, astatine and iodine released by the cable, samples of non-metallicmaterials (1g) are burned in a tubular oven at up to 800ºC. Controlled air flow inside the chamber absorbs the resulting gases in water, which istested for its acidity. If the specimen yields less than 5 mg/g of hydrochloric acid it is rated Halogen Free, but if the yield is between 5 mg/g and15 mg/g it is classed as Low Smoke & Fumes. The results do not determine whether the specimen is totally halogen free.

SMOKE CORROSIVELY(IEC 60754-2, BS EN 50267-2-2)This method determines the corrosiveness of the gases released from the cables by burning the insulation material in a furnace at ≤935ºC withrated air supply for 30 minutes. The effluent gases are absorbed into distilled water, which is then measured for its pH and conductivity. A pH-valueof above 4.3 and conductivity of over 10μS / mm must be achieved.

TOXICITY INDEX(ES713)This Naval Engineering Standard method is used to analyse noxious gas emitted from the burning specimen and the amount that each of the gascan cause fatality. Sample of the cable insulating material (~1.0 g) is burned in a chamber with a volume of 0.7-1m3 and the gases emitted duringcombustion are detected and collected in order to determine the quantities of the elements, such as carbon dioxide, carbon monoxide, sulphurdioxide, nitric oxide, acids, ammonia, etc. The Toxicity Index is derived from the calculated quantity of each gas produced when 100g (scaled up)of the material is burnt in air in a volume of 1m3 and the particular resulting concentration fatal to human when exposed to it for 30 minutes, thusdetermining the critical toxicity factor. The higher the index, the more toxic the insulating material when burnt in a fire. For example, the toxicityindex of a FRT cable is generally known to be lower than 5.

OTHER RELEVANT STANDARDSLIMITING OXYGEN INDEX (LOI)(ISO4589-2, BS ISO7211-3)LOI is defined as the minimum concentration of oxygen required to support flaming combustion in a flowing air mixture of oxygen and nitrogen(in this instance, the downward burning of a vertically-mounted test specimen such as a candle.) The oxygen concentration is recorded as volumepercentage. A higher LOI value (oxygen concentration) means better flame retardancy. For example, with 21% oxygen index the material will burnby itself automatically at room temperature; LSZH cables require a higher index between 33% and 42%. The test method allows accuracy of + 0.5%to be achieved.

TEMPERATURE INDEX (TI)(ISO4589, BS 2782.1)Research has shown that compared to the conventional oxygen index, higher temperature at which a material will burn in air is a better determinantof combustibility. When air temperature rises, the Oxygen Index Value falls, thus, the test for Temperature Index (TI) has been developed from theLOI method. The apparatus used for the TI test is essentially similar to that of the LOI test but the incoming combustion gas is heated. It tests theflammability of the sample with a small flame to find the optimum temperature at which the specimen will burn automatically. When a specimenburns automatically in the air with 21% oxygen, the temperature at this point is known as the TI. In the case of coal, the oxygen index will dropto 21% and it will burn automatically when the air temperature reaches 150ºC. This temperature for coal is recorded as its TI.

APPENDIX E

www.taisin.com.sg | 81

Page 86: Low Voltage Cables · 2019-08-16 · BS6231 Electric cables, single-core PVC insulated flexible cables of rated voltage 600 / 1000V for switchgear and control-gear wiring. BS6346

1. APPLICATION OF TERMS & CONDITIONS

These conditions govern the sales and purchase of goods ordered by Buyer from Seller (“the goods”) and shall override any terms and conditions whether previouslyor hereafter stipulated incorporated or referred to by Buyer whether orally in its purchase order or other documents.

2. DELIVERY

a. Any time for delivery named by Seller is an estimate only and Seller is not liable to make good any damage or loss arising out of any such delay.b. Delivery shall be deemed to have been made if seller delivers the goods to the location specificed by the Buyer and Delivery Order is endorsed by any person

present thereat. Seller not responsible to ensure the goods have been delivered to or is collected by Buyer or its authorized personnel and shall not be liablefor any loss or damage to Buyer by reason of unauthorized collection of the goods.

c. Should Buyer fail to take delivery of goods, Seller shall be entitled (without derogation of its rights under Law) to charge Buyer for storage and insurance forthe goods calculated from the date fixed for delivery.

d. The Seller reserves the right to deliver goods by installments and each installment shall be deemed to have been sold under a separate contract. Failure todeliver any installment shall not entitle the buyer to repudiate the contract.

e. Off loading and/or handling will in all events be the responsibility of the Buyer.f. If the goods to be delivered are, at the Buyer’s discretion, delivered to the destination other than the Buyer’s premises, the Seller will arrange such delivery for

the Buyer and all costs for carriage and insurance will be to the Buyer’s account.g. Availability of the goods when offered ex-stock is subject to such goods being sold in another transaction between the date when the Seller advises the goods

are available, and the date when it receives the Buyer’s order. Any delivery time offered for products made to special customer order is indicative only, and theSeller shall not be liable for any loss or damage whatsoever arising as a consequence or result of any such failure to deliver.

3. PRICE

The quoted price for the goods are subject to change in the event of any imposition or increase in taxes, levies or duties whatsoever on the goods, its componentsor raw materials.

4. PAYMENT

Payments for the goods shall be made within the time stipulated in the invoice. Interest at 1.5% per month will be charged on late payment.5. TIME OF THE ESSENCE

Time within which the Buyer is to pay for the goods shall be of the essence of this Contract.6. ACCEPTANCE

Buyer shall inspect the goods immediately upon delivery. Unless Seller receives notice that the goods are not in accordance with the Buyer’s order and the goodsreturned to Seller within 24 hours from the date of delivery, the goods shall be deemed to have been accepted by the Buyer PROVIDED ALWAYS Seller will notaccept return of used goods and Buyer shall not reject any goods which are in accordance with the Buyer’s order.

7. DESCRIPTION

Notwithstanding any description of the goods given by the Seller or Buyer, no sale of goods shall constitute or be construed as a sale by description.8. WARRANTIES

Save and except for written warranties (if any) given by Seller, the Seller does not give any warranties as to the quality, state, condition or fitness of the goods ortheir suitability for any purpose or for use under any specific conditions, notwithstanding that such purpose or condition may be known or made known to Seller.

9. DEFECTS

Save and except as notified pursuant to Clause 6) above, Seller shall be under no liability to Buyer either in contract or tort for loss, injury or damage sustained byBuyer or any third party by reason of defects in the goods whether latent or otherwise but Buyer will keep Seller indemnified against any such claim.

10. TITLE

Title to the goods remains vested in Seller receives the full purchase price. If such payment is overdue, the Seller may without prejudice to any other rights sue forthe purchase price, recover or re-sell the goods and the Buyer grants the Seller, its servants/agents the right and/or license to enter the Buyer’s premise and/or anyother premise where the goods are stored. If any of the goods are sold by Buyer before title has passed to Buyer, Buyer shall hold the proceeds of sale and all rightsagainst purchaser in trust for Seller.

11. RISK

Risk passes to Buyer upon delivery of goods to Buyer.12. DEFAULT

If Buyer fail to pay Seller on due date, commits a breach of any of its obligation herein, becomes insolvent or commits an act of bankruptcy, Seller may withoutprejudice to its other rights and without giving any notice, suspend/cancel further deliveries, stop any delivery in transit under this Contract or any other contractsand/or limit/cancel the Buyer’s credit as to time and/or amount for executed, executory or future orders, and/or request for securities or guarantees. Seller shallnot be liable to Buyer for any damages which Buyer may suffer or incur by reason thereof.

13. CANCELLATION OF CREDIT

Notwithstanding anything herein contained, Seller reserves the right to limit/cancel the credit of the Buyer as to time and/or amount without giving any reasonsthereof and to demand full settlement immediately of all sums that may be owing by Buyer notwithstanding that the credit period has not expired.

14. FORCE MAJEURE

Seller shall not be liable to Buyer for failure to deliver the goods by reason of any breakdown of plant, fire, explosion, Act of God, or outbreak of hostilities, nationalemergency, industrial disputes, shortage of labour, raw materials, energy or any causes beyond Seller’s control and which seller is unable to prevent by the exerciseof reasonable diligence, whether of the class of causes enumerated herein or not.

15. APPROPRIATION OF PAYMENTS

All payments received from the Buyer will be applied towards settlement of the Buyer’s oldest debts comprising the earliest invoices, debit notes (including debitnotes for overdue interest) and other charges howsoever arising PROVIDED ALWAYS Seller may appropriate any payments towards account of interest beforeprincipal in respect of any debt as the Seller shall in its absolute discretion deem fit.

16. STATEMENT OF ACCOUNT

All amounts stated in the invoices and statement of accounts of Seller shall be conclusive of the amounts due and owing by Buyer to Seller and shall be bindingagainst Buyer in any legal proceedings.

17. RIGHTS OF SET-OFF

Seller entitled to set-off against Buyer’s debts all monies now or hereafter standing to the credit of Buyer’s account with Seller and for this purpose Buyer shall giveirrevocable authority to Seller to collect on behalf of Buyer and give valid receipt and discharge in respect of all such monies owing to the Buyer.

18. WAIVER

No failure or delay by the Seller in exercising any rights hereunder shall operate as a waiver hereof nor shall any single or partial exercise of right preclude any furtherexercise thereof or the exercises of any other right.

19. SALE OF GOODS ACT (“the Act”)

The terms and conditions in favour of the Seller hereunder shall be in addition to and not in substitution for any term condition warranty expressed or implied infavour of the Seller under the Act or any statutory and re-enactment thereto for the time being enforced.

20. INFRINGEMENT OF PATENTS DESIGNS

Buyer shall indemnify Seller against all damages, claims, costs and expenses which Seller may become liable as a result or work done or goods sold in accordancewith Buyer’s specifications which involve infringement of any patents, registered designs or trademarks.

21. NOTICES

Any notices, communications or demands shall be deemed to have been sufficiently given if sent by prepaid post to the address of the addressee stated herein orto the addressee’s last known place of business and shall be presumed to have reached the address in ordinary course of post.

General Disclaimer We have taken reasonable measures to ensure that the information and data represented in this catalogue is accurate and current. However, Tai Sin makes no express or impliedwarranty regarding such information or data, and hereby expressly disclaims all responsibility and legal liability to persons or entities that use or access its content, based on their reliance on any informationor data that is available through this catalogue. We are not liable for all expenses, losses, damages and costs you might incur as a result of the information being inaccurate or incomplete in any way, andfor any reason.

TERMS & CONDITIONS OF SALES

82 | www.taisin.com.sg