load list for b127 cluster well platform
DESCRIPTION
electTRANSCRIPT
Specification / Requisition
Document No. : B127-LS-EL-0005 Rev. A Sheet : 1 of 3
Project No. : 2090 / 1764
PC1764001-00 © 2010 Aker Solutions
Aker Powergas Pvt. Ltd. www.akersolutions.com
Document Title : Load List for B-127 Cluster Well Platform.
A INFORMATION S2 SAK NMC SBL
Revision Issued for PEM Status Level
Prepared by/ Date
Checked by/ Date
Approved by/ Date
Project : B-127 CLUSTER WELL PLATFORM PROJECT
Client : OIL & NATURAL GAS CORPORATION LTD
Pre-Bid
Aker Powergas Pvt Ltd
Revision Record Sheet
Document No. : B127-LS-EL-0005 Rev. A Sheet : 2 of 3
Document Title : Load List for B-127 Cluster Well Platform. Project : B-127 CLUSTER WELL PLATFORM PROJECT
Client : OIL & NATURAL GAS CORPORATION LTD Project No. : 2090/1764
PC1764002-00 Load List.doc
Date Details of Revision Rev.
23.03.2012 ISSUED FOR INFORMATION. AISSUED FOR PREBID
Specification / Requisition
Document No. : B127-LS-EL-0005 Rev. Sheet : 3 of 3
Project No. : 2090/1764
Document Title : Load List for B-127 Cluster Well Platform.
PC1764001-00
Enter the Rev of each document enclosed under the current revision of this EDL. Even if document is not revised, repeat the Document Rev under the current revision of EDL.
Document Title Document Number Document Rev
EDL Rev. No. of Sheets
A B C 0 1 2
Load List for B-127 Well Platform B127-LS-EL-0001 6 A
Load List for B-157 Well Platform B127-LS-EL-0002 5 A
Load List for B-55-5 Well Platform B127-LS-EL-0003 5 A
Load List for ZC Well Platform B127-LS-EL-0004 5 A
Notes:
1
2 Nav Aid wattage is calculated based on current data available from vendor and average current drawn specified for the same
in previous similar projects.
Reference Documents:-
1 Electrical Design Criteria for Well Platforms , SECTION 3.5 , Vol. II Rev 4
2 Functional Specification for Solar Power System - FS 4007, Rev. 3
3 Functional Specification for Navigational Aids System - FS 4003, Rev. 4
CLIENT : ONGC
23.03.2012 23.03.2012 23.03.2012 DOCUMENT NO: SHT 1 OF 6SAK NMC SBL
PEM MADE APP REV REVSTATUS BY & DATE BY & DATE BY & DATE STATUS A
PROJECT : B-127 CLUSTER WELL PLATFORM PROJECT
ELECTRICAL LOAD LIST FOR B127 PLATFORM.
PC80
1230
1-00
ISSUED FOR ENQUIRY AS2
This is preliminary load list.The load data is based on the experience on similar ONGC Projects.
TITLE : ELECTRICAL LOAD LIST FOR B127 PLATFORM.
Aker Power Gas Pvt. Ltd.
OIL AND NATURAL GASCORPORATION LTD. INDIA
B-127-LS-EL-0001
Page 1 of 6
PROJECT NO 2090/1764
DOC NO.: B-127-LS-EL-0001DATE: 3/23/2012REV : A
ON OFF ON OFF ON OFF
1 Nav Aid Lanterns 4 24 0.4 0.5 0.4 0.50 1.2 12.00 0.13 3.33 0.005 7.22 7.6 30.42 P
TOTAL 1.20 0.13 0.005 7.60 30.42
P: PRELIMINARY D: DESIGN APPROVED F: FINAL
Aker Powergas Pvt. Ltd.ELECTRICAL LOAD LIST
(B127 - System I : 24V DC )NAV-AIDS SYSTEM
Client:
Total Daily load =
Sr. No. Load Description Qty. Duty
Cycle Status Remarks
ONGC
Average daily power drain @
worse case(Ah/Day)
30.42 AH/DAY
Flasher Quiescent current (A)
AV. Daily power drain
@ 24V
AV. Daily power drain including battery charge/discharge, efficiency
Rated Voltage
Morse code "U" Nav-Aids Lanterns 15 Sec.
AV. Lamp current incl.
Surge
SH. 2 OF 6
PROJECT NO 2090/1764DOC NO.: B-127-LS-EL-0001 DATE: 3/23/2012REV : A
Client:
Sr. No. Load Description Qty. Rated
Voltage
Unit Load (Watt)
Total Load (Watt)
Run Up Time In
Hrs./Day
Energy Consumed in
Ah/Day
Energy Consumed in
WH/Day
Unit Load @ 24V DC (Amp.)
Total Load 24V DC (Amp.)
Duty Cycle/ Load
Factor
Average Current
Drawn @ 24V (Amp.)
Status Remarks
1 Illumination for Level Gauge 4 24 50 200 0.25 2.0833 50 2.083333333 8.333333 0.01042 0.086805556 P Run-Up time of 0.25hr/day is assumed.
2 WELL HEAD PLC
2.1 Electronic transmitter (FT, TT, PT, LT) 44 24 0.5 22 24 22.0000 528 0.020833333 0.916667 1 0.916666667 P
2.2 Isolating barriers 61 24 1.6 97.6 24 97.6000 2342.4 0.066666667 4.066667 1 4.066666667 P
2.3 PLC System 1 24 300 300 24 300.0000 7200 12.5 12.5 1 12.5 P
2.4 Patch Panel 2 24 100 200 24 200.0000 4800 4.166666667 8.333333 1 8.333333333 P
2.5 Ethernet switches 20 24 5 100 24 100.0000 2400 0.208333333 4.166667 1 4.166666667 P
2.6 Magnetically latched, pulse operated SOV 6 24 15 90 1 3.7500 90 0.625 3.75 0.04167 0.15625 P Run-Up time of 1 hr/day is assumed.
2.7 Multivariable Transmitter 9 24 35 315 24 315.0000 7560 1.458333333 13.125 1 13.125 P
2.8 Coriolis Flow Meter 0 24 7 0 24 0.000 0 0.292 0.000 1 0.000 P
2.9 Pressure Switch 22 24 1.2 26.4 0.01 0.0110 0.264 0.0500 1.1000 0.0004 0.0005 P
2.10 Limit Switch 0 24 1.2 0 0.01 0.0000 0 0.0500 0.0000 0.0004 0.0000 P
2.11 Solenoid Valve 15 24 24 360 0.01 0.1500 3.6 1.0000 15.0000 0.0004 0.0063 P
3 F&G PLC
3.1 Hydrogen Detectors 3 24 4.6 13.8 24 13.8000 331.2 0.191666667 0.575 1 0.575 P
3.2 HC Gas Detectors 23 24 7.5 172.5 24 172.5000 4140 0.3125 7.1875 1 7.1875 P
3.3 H2S Gas Detectors 23 24 4.2 96.6 24 96.600 2318.4 0.175 4.025 1.000 4.025 P
3.4 Heat Detectors 10 24 0.25 2.5 24 2.500 60 0.010 0.104 1.000 0.104 P
3.5 Relays and timers 0 24 10 0 24 0.0000 0 0.416666667 0 1 0 P
3.6 Flashing beacons 4 24 33.6 134.4 0.25 1.4000 33.6 1.4 5.6 0.01042 0.058333333 P Run-Up time of 0.25hr/day is assumed.
3.7 Electronic hooter 4 24 6 24 0.25 0.2500 6 0.25 1 0.01042 0.010416667 P Run-Up time of 0.25hr/day is assumed.
3.8 Smoke Detectors 20 24 0.25 5 24 5.000 120 0.010 0.208 1.000 0.208 P
3.9 F&G PLC 1 24 300 300 24 300.0000 7200 12.5 12.5 1 12.5 P
4 DCS
Aker Powergas Pvt. Ltd.ELECTRICAL LOAD LIST
(B127: 24V DC )
ONGC
Page 3 of 6
PROJECT NO 2090/1764DOC NO.: B-127-LS-EL-0001 DATE: 3/23/2012REV : A
Client:
Aker Powergas Pvt. Ltd.ELECTRICAL LOAD LIST
(B127: 24V DC )
ONGC
4.1 Wet Gas Meter 0 24 35 0 24 0.0000 0 1.458333333 0 1 0 P
4.2 Electronic transmitter (FT, TT, PT, LT) 65 24 0.5 32.5 24 32.5000 780 0.020833333 1.354167 1 1.354166667 P
4.3 Pig detectors 6 24 1.2 7.2 0.01 0.0030 0.072 0.0500 0.3000 0.0004 0.0001 P
4.4 Isolating barriers 70 24 1.6 112 24 112.0000 2688 0.066666667 4.666667 1 4.666666667 P
4.5 Limit Switch 48 24 1.2 57.6 0.01 0.0240 0.576 0.0500 2.4000 0.0004 0.0010 P
4.6 Solenoid Valve 1 24 24 24 0.01 0.0100 0.24 1.0000 1.0000 0.0004 0.0004 P
4.7 Coriolis Flow Meter 1 24 7 7 24 7.000 168 0.292 0.292 1 0.292 P
5 SDP PLC
5.1 Electronic transmitter (FT, TT, PT, LT) 4 24 0.5 2 24 2.0000 48 0.020833333 0.083333 1 0.083333333 P
5.2 Isolating barriers 4 24 1.6 6.4 24 6.4000 153.6 0.066666667 0.266667 1 0.266666667 P
5.3 Pressure Switch 50 24 1.2 60 0.01 0.0250 0.6 0.0500 2.5000 0.0004 0.0010 P
5.4 Solenoid Valve 24 24 24 576 0.01 0.2400 5.76 1.0000 24.0000 0.0004 0.0100 P
5.5 Electronic hooter 1 24 6 6 0.25 0.0625 1.5 0.25 0.25 0.01042 0.002604167 P
5.6 PLC System 1 24 300 300 24 300.0000 7200 12.5 12.5 1 12.5 P
6 CO2 Snuffing system
6.1 Solenoid Valve 1 24 24 24 0.01 0.0100 0.24 1.0000 1.0000 0.0004 0.0004 P
6.2 Limit Switch 4 24 1.2 4.8 0.01 0.0020 0.048 0.0500 0.2000 0.0004 0.0001 P
6.3 Pressure Switch 1 24 1.2 1.2 0.01 0.0005 0.012 0.0500 0.0500 0.0004 0.0000 P
6.4 Detectors 4 24 1.2 4.8 0.01 0.0020 0.048 0.0500 0.2000 0.0004 0.0001 P
6.5 Hooter 1 24 9.6 9.6 0.01 0.0040 0.096 0.4000 0.4000 0.0004 0.0002 P
6.6 Panel (Internal Load) 1 24 9.6 9.6 0.01 0.0040 0.096 0.4000 0.4000 0.0004 0.0002 P
7 Flow Computer 2 24 7 14 24 14.000 336 0.292 0.583 1.000 0.583 P
3,719 2,107 50,567 155 88
97 Amps171 Amps
TOTAL AVERAGE DEMAND: TOTAL PEAK DEMAND:
Note : These instrumentation loads will be fed from 24V DC power supply from Sagar Laxmi Platform and shall not be considered while designing Solar Power System.
Page 4 of 6
PROJECT NO 2090/1764DOC NO.: B-127-LS-EL-0001DATE: 3/23/2012REV : A
Client:
Remarks
1 PGC-PM-01 PGC Main Motor PGC C Motor 3000 0.89 2670 0.90 0.92 2902.17 1405.59 0.00 0.00 0.00 0.00 Preliminary
Aker Powergas Pvt. Ltd.
Stand by (B)Continuous (A)
Input Power
Intermittent (C)
ONGC
ELECTRICAL LOAD LIST(B127 - 6.9kV LOADS)
Sr. No. Equipment No. Description
0100% 20
Vendor Load Feeder Rating in kW
Load Factor
Absorbed Load, kW
P.F. ( LAG) at
absorbed load
Efficiency at
absorbed load
SH. 5 OF 6
PROJECT NO 2090/1764DOC NO.: B-127-LS-EL-0001DATE: 3/23/2012REV : A
Client:
Remarks
A) PGC Auxillary Load
1 OCI Transfer Pump PGC C Motor 2.2 0.89 1.958 0.90 0.92 2.13 1.03 0.00 0.00 0.00 0.00 Preliminary
2 OCI Injection Pump PGC C Motor 0.37 0.89 0.3293 0.90 0.92 0.36 0.17 0.00 0.00 0.00 0.00 Preliminary
3 OCI Injection Pump PGC S Motor 0.37 0.89 0.3293 0.90 0.92 0.00 0.00 0.36 0.17 0.00 0.00 Preliminary
4 Crude Condensate Pump PGC C Motor 2.2 0.89 1.958 0.90 0.92 2.13 1.03 0.00 0.00 0.00 0.00 Preliminary
B) Lighting Transformer Package I Ligting 20 (25kVA) 0.85 17 1.00 0.950 0.00 0.00 0.00 0.00 17.89 0.00 Preliminary
C) HPU (B-59 S/S) Package C Supply 75 0.85 63.75 0.90 0.900 70.83 34.31 0.00 0.00 0.00 0.00 Preliminary
D) HVAC Package C Supply 75 0.85 63.75 0.90 0.900 70.83 34.31 0.00 0.00 0.00 0.00 Preliminary
Equipment No.Sr. No. Description
100% 20
Vendor Load Feeder Rating in kW
Load Factor
Absorbed Load, kW
Aker Powergas Pvt. Ltd.
Stand by (B)Continuous (A)
Input Power
Intermittent (C)
ONGC
ELECTRICAL LOAD LIST(B127 - 440V LOADS)
P.F. ( LAG) at
absorbed load
Efficiency at
absorbed load 0
SH. 6 OF 6
Notes:
1
2 Nav Aid wattage is calculated based on current data available from vendor and average current drawn specified for the same in previous similar projects.
Reference Documents:-
1 Electrical Design Criteria for Well Platforms , SECTION 3.5 , Vol. II Rev 4
2 Functional Specification for Hybrid Power System - FS 4007A, Rev. 0
3 Functional Specification for Navigational Aids System - FS 4003, Rev. 4
CLIENT : ONGC
23.03.2012 23.03.2012 23.03.2012 DOCUMENT NO: SHT 1 OF 5SAK NMC SBL
PEM MADE APP REV REVSTATUS BY & DATE BY & DATE BY & DATE STATUS A
PROJECT : B-127 CLUSTER WELL PLATFORM PROJECT
ELECTRICAL LOAD LIST FOR B157 WELL PLATFORM
PC80
1230
1-00
ISSUED FOR ENQUIRY AS2
This is preliminary load list.The load data is based on the experience on similar ONGC Projects.
TITLE : ELECTRICAL LOAD LIST FOR B157 WELL PLATFORM.
Aker Power Gas Pvt. Ltd.
OIL AND NATURAL GASCORPORATION LTD. INDIA
B-127-LS-EL-0002
Page 1 of 5
PROJECT NO 2090/1764DOC NO.: B-127-LS-EL-0002DATE: 3/23/2012REV : A
Sr. No. Load Description Qty. Rated
Voltage
Unit Load (Watt)
Total Load (Watt)
Run Up Time In Hrs./Day
Energy Consumed in
Ah/Day
Energy Consumed in WH/Day
Unit Load @ 24V DC
(Amp.)
Total Load 24V
DC (Amp.)
Duty Cycle/ Load
Factor
Average Current
Drawn @ 24V (Amp.)
Status Remarks
1 RTU PLC
1.1 Wet Gas Meter 1 24 35 35 24 35.000 840 1.458 1.458 1 1.458 P Run-Up time of 0.25 hr/day is assumed.
1.2 Electronic Transmitter (FT, TT, PT, LT) 13 24 0.5 6.5 24 6.500 156 0.021 0.271 1 0.271 P
1.3 Pig Detectors 1 24 1.2 1.2 0.01 0.001 0.012 0.050 0.050 0.00042 0.000 P
1.4 Isolating Barriers 13 24 1.6 20.8 24 20.800 499.2 0.067 0.867 1 0.867 P
1.5 PLC System 1 24 300 300 24 300.000 7200 12.500 12.500 1 12.500 P
1.6 Microwave Radio during Transmit Micro Radio during Receive Microwave Radio during Sleep Mode 1 24 272 272 24 272.000 6528 11.333 11.333 1 11.333 P
2 WELL HEAD PLC
2.1 Electronic Transmitter (FT, TT, PT, LT) 10 24 0.5 5 24 5.000 120 0.021 0.208 1.000 0.208 P
2.2 Isolating Barriers 10 24 1.6 16 24 16.000 384 0.067 0.667 1.000 0.667 P
2.3 PLC System 1 24 300 300 24 300.000 7200 12.500 12.500 1.000 12.500 P
2.4 Patch Panel 2 24 100 200 24 200.000 4800 4.167 8.333 1.000 8.333 P
2.5 Ethernet Switches 20 24 5 100 24 100.000 2400 0.208 4.167 1.000 4.167 P
2.6 Magnetically Latched, pulse operated SOV 6 24 15 90 1 3.750 90 0.625 3.750 0.042 0.156 P
TOTAL 1,347 1,260 30,218 57 53
10% MARGIN 135 126 3,022 6 5
TOTAL (WITH 10% MARGIN ) 1,482 1,386 33,240 63 58
58 Amps63 Amps
P: PRELIMINARY D: DESIGN APPROVED C: CERTIFIED F : Final
TOTAL AVERAGE DEMAND: TOTAL PEAK DEMAND:
Aker Powergas Pvt. Ltd.ELECTRICAL LOAD LIST
(B157 - System I : 24V DC )TELEMETRY & WELL HEAD SYSTEM
ONGCClient:
Page 2 of 5
PROJECT NO 2090/1764
DOC NO.: B-127-LS-EL-0002DATE: 3/23/2012REV : A
Sr. No. Load Description Qty. Rated
VoltageUnit Load
(Watt)Total Load
(Watt)
Run Up Time In
Hrs./Day
Energy Consumed in Ah/Day
Energy Consumed in WH/Day
Unit Load @ 24V
DC (Amp.)
Total Load 24V
DC (Amp.)
Duty Cycle/ Load
Factor
Average Current
Drawn @ 24V (Amp.)
Status Remarks
1 Illumination for Level Gauge 2 24 50 100 0.25 1.042 25 2.083 4.167 0.010 0.043 PRun-Up time of 0.25hr/day is assumed.
2 Co2 Snuffing System
2.1 Solenoid Valve 1 24 24 24 0.01 0.0100 0.24 1.0000 1.0000 0.0004 0.0004 P
2.2 Limit Switch 4 24 1.2 4.8 0.01 0.0020 0.048 0.0500 0.2000 0.0004 0.0001 P
2.3 Pressure Switch 1 24 1.2 1.2 0.01 0.0005 0.012 0.0500 0.0500 0.0004 0.0000 P
2.4 Detectors 4 24 1.2 4.8 0.01 0.0020 0.048 0.0500 0.2000 0.0004 0.0001 P
2.5 Hooter 1 24 9.6 9.6 0.01 0.0040 0.096 0.4000 0.4000 0.0004 0.0002 P
2.6 Panel (Internal Load) 1 24 9.6 9.6 0.01 0.0040 0.096 0.4000 0.4000 0.0004 0.0002 P
3 Lighting System
3.1 Electrical/Telemetry Room Lighting 2 24 60 120 3 15.000 360 2.500 5.000 0.125 0.625 P Electrical Design BasisSection 3.5, Clause No. 3.5.7.8
3.2 Battery Room Lighting 2 24 60 120 3 15.000 360 2.500 5.000 0.125 0.625 P Electrical Design BasisSection 3.5, Clause No. 3.5.7.8
3.3 Bunk House 2 24 60 120 3 15.000 360 2.500 5.000 0.125 0.625 P Electrical Design BasisSection 3.5, Clause No. 3.5.7.8
4 Down Hole Instrument 1 24 51 51 24 51.000 1224 2.125 2.125 1 2.125 P
TOTAL 565 98 2,330 24 5
10% MARGIN 57 10 233 2 1
TOTAL (WITH 10% MARGIN ) 622 108 2,563 26 6
6 Amps
26 Amps
P: PRELIMINARY D: DESIGN APPROVED F: FINAL
Aker Powergas Pvt. Ltd.ELECTRICAL LOAD LIST
(B157 - System II : 24V DC )LIGHTING, CO2 SNUFFING SYSTEM
Client: ONGC
TOTAL AVERAGE DEMAND:
TOTAL PEAK DEMAND:
SH. 3 OF 5
PROJECT NO 2090/1764DOC NO.: B-127-LS-EL-0002DATE: 3/23/2012
REV : A
Sr. No. Load Description Qty. Rated Voltage
Unit Load (Watt)
Total Load (Watt)
Run Up Time In
Hrs./Day
Energy Consume
d in Ah/Day
Energy Consumed in WH/Day
Unit Load @ 24V
DC (Amp.)
Total Load 24V DC (Amp.)
Duty Cycle/ Load
Factor
Average Current
Drawn @ 24V
(Amp.)
Status Remarks
1 FIRE AND GAS PLC
1.1 Hydrogen Detectors 3 24 4.6 13.8 24 13.800 331.2 0.192 0.575 1.000 0.575 P
1.2 HC Gas Detectors 8 24 7.5 60 24 60.000 1440 0.313 2.500 1.000 2.500 P
1.3 H2S Gas Detectors 8 24 4.2 33.6 24 33.600 806.4 0.175 1.400 1.000 1.400 P
1.4 Heat Detectors 10 24 0.25 2.5 24 2.500 60 0.010 0.104 1.000 0.104 P
1.5 Smoke Detectors 20 24 0.25 5 24 5.000 120 0.010 0.208 1.000 0.208 P
1.6 Flashing beacons 4 24 33.6 134.4 0.25 1.400 33.6 1.400 5.600 0.010 0.058 P Run-Up time of 0.25hr/day is assumed.
1.8 Electronic hooter 4 24 6 24 0.25 0.250 6 0.250 1.000 0.010 0.010 P Run-Up time of 0.25hr/day is assumed.
1.9 Relays & Timers 0 24 6 0 0.25 0.000 0 0.250 0.000 0.010 0.000 P Run-Up time of 0.25hr/day is assumed.
1.10 F&G PLC 1 24 300 300 24 300.000 7200 12.500 12.500 1.000 12.500 P
2 SDP PLC
2.1 Pressure Switch 8 24 1.2 9.6 0.01 0.004 0.096 0.050 0.400 0.0004 0.0002 P
2.2 Solenoid Valve 1 24 24 24 0.01 0.010 0.24 1.000 1.000 0.0004 0.0004 P
2.3 Limit Switch 2 24 1.2 2.4 0.01 0.001 0.024 0.050 0.100 0.0004 0.0000 P
2.4 PLC System 1 24 300 300 24 300.000 7200 12.500 12.500 1.0000 12.5000 P
TOTAL 910 717 17,198 38 3010% MARGIN 91 72 1,720 4 3
TOTAL (WITH 10% MARGIN ) 1,001 789 18,918 42 33
33 Amps42 Amps
P: PRELIMINARY D: DESIGN APPROVED C: CERTIFIED F : Final
TOTAL PEAK DEMAND:
Aker Powergas Pvt. Ltd.ELECTRICAL LOAD LIST
(B157 - System III : 24V DC )FIRE & GAS, SDP PLC SYSTEM
Client: ONGC
TOTAL AVERAGE DEMAND:
SH. 4 OF 5
PROJECT NO 2090/1764
DOC NO.: B-127-LS-EL-0002DATE: 3/23/2012REV : A
ON OFF ON OFF ON OFF
1 Nav Aid Lanterns 4 24 0.4 0.5 0.4 0.50 1.2 12.00 0.13 3.33 0.005 7.22 7.6 30.42 P
TOTAL 1.20 0.13 0.005 7.60 30.42
P: PRELIMINARY D: DESIGN APPROVED F: FINAL
Aker Powergas Pvt. Ltd.ELECTRICAL LOAD LIST
(B157 - System IV : 24V DC )NAV-AIDS SYSTEM
Client:
Total Daily load =
Sr. No. Load Description Qty. Duty
Cycle Status Remarks
ONGC
Average daily power drain @
worse case(Ah/Day)
30.42 AH/DAY
Flasher Quiescent current
(A)
AV. Daily power
drain @ 24V
AV. Daily power drain including battery charge/discharge, efficiency
Rated Voltage
Morse code "U" Nav-Aids Lanterns 15 Sec.AV.
Lamp current
incl. Surge
SH. 5 OF 5
Notes:
1
2 Nav Aid wattage is calculated based on current data available from vendor and average current drawn specified for the same in previous similar projects.
Reference Documents:-
1 Electrical Design Criteria for Well Platforms , SECTION 3.5 , Vol. II Rev 4
2 Functional Specification for Hybrid Power System - FS 4007A, Rev. 0
3 Functional Specification for Navigational Aids System - FS 4003, Rev. 4
CLIENT : ONGC
23.03.2012 23.03.2012 23.03.2012 DOCUMENT NO: SHT 1 OF 5SAK NMC SBL
PEM MADE APP REV REVSTATUS BY & DATE BY & DATE BY & DATE STATUS A
PROJECT : B-127 CLUSTER WELL PLATFORM PROJECT
ELECTRICAL LOAD LIST FOR B55-5 WELL PLATFORM.
PC80
1230
1-00
ISSUED FOR ENQUIRY AS2
This is preliminary load list. The load data is based on the experience on similar ONGC Projects.
TITLE :ELECTRICAL LOAD LIST FOR B-55-5 WELL PLATFORM.
Aker Power Gas Pvt. Ltd.
OIL AND NATURAL GASCORPORATION LTD. INDIA
B-127-LS-EL-0003
Page 1 of 5
PROJECT NO 2090/1764DOC NO.: B-127-LS-EL-0003DATE: 3/23/2012REV : A
Sr. No. Load Description Qty. Rated
Voltage
Unit Load (Watt)
Total Load (Watt)
Run Up Time In Hrs./Day
Energy Consumed in
Ah/Day
Energy Consumed in WH/Day
Unit Load @ 24V DC
(Amp.)
Total Load 24V
DC (Amp.)
Duty Cycle/ Load
Factor
Average Current
Drawn @ 24V (Amp.)
Status Remarks
1 RTU PLC
1.1 Wet Gas Meter 1 24 35 35 24 35.000 840 1.458 1.458 1 1.458 P Run-Up time of 0.25 hr/day is assumed.
1.2 Electronic Transmitter (FT, TT, PT, LT) 13 24 0.5 6.5 24 6.500 156 0.021 0.271 1 0.271 P
1.3 Pig Detectors 1 24 1.2 1.2 0.01 0.001 0.012 0.050 0.050 0.00042 0.000 P
1.4 Isolating Barriers 13 24 1.6 20.8 24 20.800 499.2 0.067 0.867 1 0.867 P
1.5 PLC System 1 24 300 300 24 300.000 7200 12.500 12.500 1 12.500 P
1.6 Microwave Radio during Transmit Micro Radio during Receive Microwave Radio during Sleep Mode 1 24 272 272 24 272.000 6528 11.333 11.333 1 11.333 P
2 WELL HEAD PLC
2.1 Electronic Transmitter (FT, TT, PT, LT) 10 24 0.5 5 24 5.000 120 0.021 0.208 1.000 0.208 P
2.2 Isolating Barriers 10 24 1.6 16 24 16.000 384 0.067 0.667 1.000 0.667 P
2.3 PLC System 1 24 300 300 24 300.000 7200 12.500 12.500 1.000 12.500 P
2.4 Patch Panel 2 24 100 200 24 200.000 4800 4.167 8.333 1.000 8.333 P
2.5 Ethernet Switches 20 24 5 100 24 100.000 2400 0.208 4.167 1.000 4.167 P
2.6 Magnetically Latched, pulse operated SOV 6 24 15 90 1 3.750 90 0.625 3.750 0.042 0.156 P
TOTAL 1,347 1,260 30,218 57 53
10% MARGIN 135 126 3,022 6 5
TOTAL (WITH 10% MARGIN ) 1,482 1,386 33,240 63 58
58 Amps63 Amps
P: PRELIMINARY D: DESIGN APPROVED C: CERTIFIED F : Final
TOTAL AVERAGE DEMAND: TOTAL PEAK DEMAND:
Aker Powergas Pvt. Ltd.ELECTRICAL LOAD LIST
(B55-5 - System I : 24V DC )TELEMETRY, WELL HEAD PLC SYSTEM
ONGCClient:
Page 2 of 5
PROJECT NO 2090/1764
DOC NO.: B-127-LS-EL-0003DATE: 3/23/2012REV : A
Sr. No. Load Description Qty. Rated
VoltageUnit Load
(Watt)Total Load
(Watt)
Run Up Time In
Hrs./Day
Energy Consumed in Ah/Day
Energy Consumed in WH/Day
Unit Load @ 24V
DC (Amp.)
Total Load 24V
DC (Amp.)
Duty Cycle/ Load
Factor
Average Current
Drawn @ 24V (Amp.)
Status Remarks
1 Illumination for Level Gauge 2 24 50 100 0.25 1.042 25 2.083 4.167 0.010 0.043 PRun-Up time of 0.25hr/day is assumed.
2 Co2 Snuffing System
2.1 Solenoid Valve 1 24 24 24 0.01 0.0100 0.24 1.0000 1.0000 0.0004 0.0004 P
2.2 Limit Switch 4 24 1.2 4.8 0.01 0.0020 0.048 0.0500 0.2000 0.0004 0.0001 P
2.3 Pressure Switch 1 24 1.2 1.2 0.01 0.0005 0.012 0.0500 0.0500 0.0004 0.0000 P
2.4 Detectors 4 24 1.2 4.8 0.01 0.0020 0.048 0.0500 0.2000 0.0004 0.0001 P
2.5 Hooter 1 24 9.6 9.6 0.01 0.0040 0.096 0.4000 0.4000 0.0004 0.0002 P
2.6 Panel (Internal Load) 1 24 9.6 9.6 0.01 0.0040 0.096 0.4000 0.4000 0.0004 0.0002 P
3 Lighting System
3.1 Electrical/Telemetry Room Lighting 2 24 60 120 3 15.000 360 2.500 5.000 0.125 0.625 P Electrical Design BasisSection 3.5, Clause No. 3.5.7.8
3.2 Battery Room Lighting 2 24 60 120 3 15.000 360 2.500 5.000 0.125 0.625 P Electrical Design BasisSection 3.5, Clause No. 3.5.7.8
3.3 Bunk House 2 24 60 120 3 15.000 360 2.500 5.000 0.125 0.625 P Electrical Design BasisSection 3.5, Clause No. 3.5.7.8
4 Down Hole Instrument 1 24 51 51 24 51.000 1224 2.125 2.125 1 2.125 P
TOTAL 565 98 2,330 24 5
10% MARGIN 57 10 233 2 1
TOTAL (WITH 10% MARGIN ) 622 108 2,563 26 6
6 Amps
26 Amps
P: PRELIMINARY D: DESIGN APPROVED F: FINAL
Aker Powergas Pvt. Ltd.ELECTRICAL LOAD LIST
(B55-5 - System II : 24V DC )LIGHTING, CO2 SNUFFING SYSTEM
Client: ONGC
TOTAL AVERAGE DEMAND:
TOTAL PEAK DEMAND:
SH. 3 OF 5
PROJECT NO 2090/1764DOC NO.: B-127-LS-EL-0003DATE: 3/23/2012REV : A
Sr. No. Load Description Qty. Rated Voltage
Unit Load (Watt)
Total Load (Watt)
Run Up Time In
Hrs./Day
Energy Consume
d in Ah/Day
Energy Consumed in WH/Day
Unit Load @ 24V
DC (Amp.)
Total Load 24V DC (Amp.)
Duty Cycle/ Load
Factor
Average Current
Drawn @ 24V
(Amp.)
Status Remarks
1 FIRE AND GAS PLC
1.1 Hydrogen Detectors 3 24 4.6 13.8 24 13.800 331.2 0.192 0.575 1.000 0.575 P
1.2 HC Gas Detectors 8 24 7.5 60 24 60.000 1440 0.313 2.500 1.000 2.500 P
1.3 H2S Gas Detectors 8 24 4.2 33.6 24 33.600 806.4 0.175 1.400 1.000 1.400 P
1.4 Heat Detectors 10 24 0.25 2.5 24 2.500 60 0.010 0.104 1.000 0.104 P
1.5 Smoke Detectors 43 24 0.25 10.75 24 10.750 258 0.010 0.448 1.000 0.448 P
1.6 Flashing beacons 4 24 33.6 134.4 0.25 1.400 33.6 1.400 5.600 0.010 0.058 P Run-Up time of 0.25hr/day is assumed.
1.8 Electronic hooter 4 24 6 24 0.25 0.250 6 0.250 1.000 0.010 0.010 P Run-Up time of 0.25hr/day is assumed.
1.9 Relays & Timers 0 24 6 0 0.25 0.000 0 0.250 0.000 0.010 0.000 P Run-Up time of 0.25hr/day is assumed.
1.10 F&G PLC 1 24 300 300 24 300.000 7200 12.500 12.500 1.000 12.500 P
2 SDP PLC
2.1 Pressure Switch 8 24 1.2 9.6 0.01 0.004 0.096 0.050 0.400 0.0004 0.0002 P
2.2 Solenoid Valve 1 24 24 24 0.01 0.010 0.24 1.000 1.000 0.0004 0.0004 P
2.3 Limit Switch 2 24 1.2 2.4 0.01 0.001 0.024 0.050 0.100 0.0004 0.0000 P
2.4 PLC System 1 24 300 300 24 300.000 7200 12.500 12.500 1.0000 12.5000 P
TOTAL 916 723 17,336 39 3110% MARGIN 92 72 1,734 4 3
TOTAL (WITH 10% MARGIN ) 1,008 795 19,070 43 34
34 Amps43 Amps
P: PRELIMINARY D: DESIGN APPROVED C: CERTIFIED F : Final
TOTAL PEAK DEMAND:
Aker Powergas Pvt. Ltd.ELECTRICAL LOAD LIST
(B55-5 - System III : 24V DC )FIRE & GAS, SDP PLC SYSTEM
Client: ONGC
TOTAL AVERAGE DEMAND:
SH. 4 OF 5
PROJECT NO 2090/1764DOC NO.: B-127-LS-EL-0003DATE: 3/23/2012REV : A
ON OFF ON OFF ON OFF
1 Nav Aid Lanterns 4 24 0.4 0.5 0.4 0.50 1.2 12.00 0.13 3.33 0.005 7.22 7.6 30.42 P
TOTAL 1.20 0.13 0.005 7.60 30.42
P: PRELIMINARY D: DESIGN APPROVED F: FINAL
Remarks
Total Daily load = 30.42 AH/DAY
AV. Daily power
drain @ 24V
AV. Daily power drain including battery charge/discharge, efficiency
Average daily power drain @
worse case(Ah/Day)
Status
Morse code "U" Nav-Aids Lanterns 15 Sec.
Duty Cycle
AV. Lamp
current incl.
Surge
Flasher Quiescent current
(A)
Sr. No. Load Description Qty. Rated
Voltage
Aker Powergas Pvt. Ltd.ELECTRICAL LOAD LIST
(B55- 5 System IV : 24V DC )NAV-AIDS SYSTEM
Client: ONGC
SH. 5 OF 5
Notes:
1
2 Nav Aid wattage is calculated based on current data available from vendor and average current drawn specified for the same in previous similar projects.
Reference Documents:-
1 Electrical Design Criteria for Well Platforms , SECTION 3.5 , Vol. II Rev 4
2 Functional Specification for Hybrid Power System - FS 4007A, Rev. 0
3 Functional Specification for Navigational Aids System - FS 4003, Rev. 4
CLIENT : ONGC
23.03.2012 23.03.2012 23.03.2012 DOCUMENT NO: SHT 1 OF 5SAK NMC SBL
PEM MADE APP REV REVSTATUS BY & DATE BY & DATE BY & DATE STATUS A
PROJECT : B-127 CLUSTER WELL PLATFORM PROJECT
ELECTRICAL LOAD LIST FOR ZC WELL PLATFORM
PC80
1230
1-00
ISSUED FOR ENQUIRY AS2
This is preliminary load list.The load data is based on the experience on similar ONGC Projects.
TITLE : ELECTRICAL LOAD LIST FOR ZC WELL PLATFORM.
Aker Power Gas Pvt. Ltd.
OIL AND NATURAL GASCORPORATION LTD. INDIA
B-127-LS-EL-0004
Page 1 of 5
PROJECT NO 2090/1764DOC NO.: B-127-LS-EL-0004DATE: 3/23/2012REV : A
Sr. No. Load Description Qty. Rated
Voltage
Unit Load (Watt)
Total Load (Watt)
Run Up Time In
Hrs./Day
Energy Consumed in
Ah/Day
Energy Consumed in WH/Day
Unit Load @ 24V DC
(Amp.)
Total Load 24V
DC (Amp.)
Duty Cycle/ Load
Factor
Average Current
Drawn @ 24V (Amp.)
Status Remarks
1 RTU PLC
1.1 Wet Gas Meter 0 24 35 0 24 0.0000 0 1.458333 0 1 0 P Run-Up time of 0.25 hr/day is assumed.
1.2 Electronic transmitter (FT, TT, PT, LT) 56 24 0.5 28 24 28.0000 672 0.020833 1.166667 1 1.166666667 P
1.3 Pig detectors 5 24 1.2 6 0.01 0.0025 0.06 0.0500 0.2500 0.0004 0.0001 P
1.4 Isolating barriers 56 24 1.6 89.6 24 89.6000 2150.4 0.066667 3.733333 1 3.733333333 P
1.5 Limit Switch 46 24 1.2 55.2 0.01 0.0230 0.552 0.0500 2.3000 0.0004 0.0010 P
1.6 PLC System 1 24 300 300 24 300.0000 7200 12.5 12.5 1 12.5 P
1.7Microwave Radio during TransmitMicro Radio during ReceiveMicrowave Radio during sleep mode
1 24 272 272 24 272.000 6528 11.333 11.333 1 11.333 P
2 WELL HEAD PLC
2.1 Electronic transmitter (FT, TT, PT, LT) 72 24 0.5 36 24 36.0000 864 0.020833 1.5 1 1.5 P
2.2 Isolating barriers 80 24 1.6 128 24 128.0000 3072 0.066667 5.333333 1 5.333333333 P
2.3 PLC System 1 24 300 300 24 300.0000 7200 12.5 12.5 1 12.5 P
2.4 Patch Panel 2 24 100 200 24 200.0000 4800 4.166667 8.333333 1 8.333333333 P
2.5 Ethernet switches 20 24 5 100 24 100.0000 2400 0.208333 4.166667 1 4.166666667 P
2.6 Magnetically latched, pulse operated SOV 6 24 15 90 1 3.7500 90 0.625 3.75 0.04167 0.15625 P
2.7 Multivariable Transmitter 13 24 35 455 24 455.0000 10920 1.458333 18.95833 1 18.95833333 P
2.8 Coriolis Flow Meter 2 24 7 14 24 14.000 336 0.292 0.583 1 0.583 P
2.9 Pressure Switch 25 24 1.2 30 0.01 0.0125 0.3 0.0500 1.2500 0.0004 0.0005 P
2.10 Limit Switch 2 24 1.2 2.4 0.01 0.0010 0.024 0.0500 0.1000 0.0004 0.0000 P
2.11 Solenoid Valve 8 24 24 192 0.01 0.0800 1.92 1.0000 8.0000 0.0004 0.0033 P
TOTAL 2,299 1,927 46,236 96 81
10% MARGIN 230 193 4,624 10 8
TOTAL (WITH 10% MARGIN ) 2,529 2,120 50,860 106 89
89 Amps106 Amps
P: PRELIMINARY D: DESIGN APPROVED C: CERTIFIED F : Final
TOTAL AVERAGE DEMAND: TOTAL PEAK DEMAND:
Aker Powergas Pvt. Ltd.ELECTRICAL LOAD LIST(ZC - System I : 24V DC )
TELEMETRY & WELL HEAD SYSTEMONGCClient:
Page 2 of 5
PROJECT NO 2090/1764
DOC NO.: B-127-LS-EL-0004DATE: 3/23/2012REV : A
Sr. No. Load Description Qty. Rated
VoltageUnit Load
(Watt)
Total Load (Watt)
Run Up Time In
Hrs./Day
Energy Consumed in Ah/Day
Energy Consume
d in WH/Day
Unit Load @ 24V
DC (Amp.)
Total Load 24V
DC (Amp.)
Duty Cycle/ Load
Factor
Average Current
Drawn @ 24V (Amp.)
Status Remarks
1 Illumination for Level Gauge 11 24 50 550 0.25 5.7292 137.5 2.083333 22.91667 0.010417 0.23871528 PRun-Up time of 0.25hr/day is assumed.
2 Co2 Snuffing System
2.1 Solenoid Valve 1 24 24 24 0.01 0.0100 0.24 1.0000 1.0000 0.0004 0.0004 P
2.2 Limit Switch 4 24 1.2 4.8 0.01 0.0020 0.048 0.0500 0.2000 0.0004 0.0001 P
2.3 Pressure Switch 1 24 1.2 1.2 0.01 0.0005 0.012 0.0500 0.0500 0.0004 0.0000 P
2.4 Detectors 4 24 1.2 4.8 0.01 0.0020 0.048 0.0500 0.2000 0.0004 0.0001 P
2.5 Hooter 1 24 9.6 9.6 0.01 0.0040 0.096 0.4000 0.4000 0.0004 0.0002 P
2.6 Panel (Internal Load) 1 24 9.6 9.6 0.01 0.0040 0.096 0.4000 0.4000 0.0004 0.0002 P
3 Lighting System
3.1 Electrical/Telemetry Room Lighting 2 24 60 120 3 15.000 360 2.500 5.000 0.125 0.625 P Electrical Design BasisSection 3.5, Clause No. 3.5.7.8
3.2 Battery Room Lighting 2 24 60 120 3 15.000 360 2.500 5.000 0.125 0.625 P Electrical Design BasisSection 3.5, Clause No. 3.5.7.8
3.3 Bunk House 2 24 60 120 3 15.000 360 2.500 5.000 0.125 0.625 P Electrical Design BasisSection 3.5, Clause No. 3.5.7.8
4 Flow Computer 2 24 7 14 24 14.000 336 0.292 0.583 1.000 0.583 P
TOTAL 964 51 1,219 41 3
10% MARGIN 96 5 122 4 0
TOTAL (WITH 10% MARGIN ) 1,060 56 1,341 45 3
3 Amps
45 Amps
P: PRELIMINARY D: DESIGN APPROVED F: FINAL
Aker Powergas Pvt. Ltd.ELECTRICAL LOAD LIST(ZC - System II : 24V DC )
LIGHTING, CO2 SNUFFING SYSTEM SYSTEMClient: ONGC
TOTAL AVERAGE DEMAND:
TOTAL PEAK DEMAND:
SH. 3 OF 5
PROJECT NO 2090/1764DOC NO.: B-127-LS-EL-0004DATE: 3/23/2012
REV : A
Sr. No. Load Description Qty. Rated Voltage
Unit Load (Watt)
Total Load (Watt)
Run Up Time In
Hrs./Day
Energy Consume
d in Ah/Day
Energy Consumed in WH/Day
Unit Load @ 24V
DC (Amp.)
Total Load 24V DC (Amp.)
Duty Cycle/ Load
Factor
Average Current
Drawn @ 24V
(Amp.)
Status Remarks
1 FIRE AND GAS PLC
1.1 Hydrogen Detectors 3 24 4.6 13.8 24 13.8000 331.2 0.191667 0.575 1 0.575 P
1.2 HC Gas Detectors 32 24 7.5 240 24 240.0000 5760 0.3125 10 1 10 P
1.3 H2S Gas Detectors 32 24 4.2 134.4 24 134.400 3225.6 0.175 5.600 1.000 5.600 P
1.4 Heat Detectors 10 24 0.25 2.5 24 2.500 60 0.010 0.104 1.000 0.104 P
1.5 Relays and timers 0 24 10 0 24 0.0000 0 0.416667 0 1 0 P
1.6 Flashing beacons 4 24 33.6 134.4 0.25 1.4000 33.6 1.4 5.6 0.01041667 0.058333 P Run-Up time of 0.25hr/day is assumed.
1.8 Electronic hooter 4 24 6 24 0.25 0.2500 6 0.25 1 0.01041667 0.010417 P Run-Up time of 0.25hr/day is assumed.
1.9 Smoke Detectors 20 24 0.25 5 24 5.000 120 0.010 0.208 1.000 0.208 P
1.10 F&G PLC 1 24 300 300 24 300.0000 7200 12.5 12.5 1 12.5 P
2 SDP PLC
2.1 Pressure Switch 68 24 1.2 81.6 0.01 0.0340 0.816 0.0500 3.4000 0.0004 0.0014 P
2.2 Solenoid Valve 22 24 24 528 0.01 0.2200 5.28 1.0000 22.0000 0.0004 0.0092 P
2.3 Electronic hooter 3 24 6 18 0.25 0.1875 4.5 0.25 0.75 0.01041667 0.007813 P
2.4 PLC System 1 24 300 300 24 300.0000 7200 12.5 12.5 1 12.5 P
TOTAL 1,782 998 23,947 75 4210% MARGIN 178 100 2,395 8 4
TOTAL (WITH 10% MARGIN ) 1,960 1,098 26,342 83 46
46 Amps83 Amps
P: PRELIMINARY D: DESIGN APPROVED C: CERTIFIED F : Final
TOTAL PEAK DEMAND:
Aker Powergas Pvt. Ltd.ELECTRICAL LOAD LIST(ZC - System III : 24V DC )
FIRE & GAS, SDP PLC SYSTEMClient: ONGC
TOTAL AVERAGE DEMAND:
SH. 4 OF 5
PROJECT NO 2090/1764
DOC NO.: B-127-LS-EL-0004DATE: 3/23/2012REV : A
ON OFF ON OFF ON OFF
1 Nav Aid Lanterns 4 24 0.4 0.5 0.4 0.50 1.2 12.00 0.13 3.33 0.005 7.22 7.6 30.42 P
TOTAL 1.20 0.13 0.005 7.60 30.42
P: PRELIMINARY D: DESIGN APPROVED F: FINAL
Remarks
Total Daily load = 30.42 AH/DAY
AV. Daily power
drain @ 24V
AV. Daily power drain including battery charge/discharge, efficiency
Average daily power drain @
worse case(Ah/Day)
Status
Morse code "U" Nav-Aids Lanterns 15 Sec.
Duty Cycle
AV. Lamp
current incl.
Surge
Flasher Quiescent current
(A)
Sr. No. Load Description Qty. Rated
Voltage
Aker Powergas Pvt. Ltd.ELECTRICAL LOAD LIST(ZC - System IV : 24V DC )
NAV-AIDS SYSTEMClient: ONGC
SH. 1 OF 1