LiteMinderFast Transfer System
1.0 to 18.75KVA LED Compatible
LM Series InverterPure Sine Wave Modular
Inverter Technology
• Modularity:LiteMinder features unique inverter modules available in increments from 1.0 to 18.75 KVA capacities(see ordering guide). Modules are interconnected to build the required system capacity, and can even be field upgraded to increase system sizes ! Modules can be configured to provide Single Phase, Split Phase, and Three Phase outputs thereby eliminating costly, inefficient external transformers.
• ControlFeatures: A keypad and LCD display provides user interface and extensive status diagnostics. Self-test, Self-Diagnostics in compliance with UL 924 is field configurable, and stores 1,000 Test, Event and Alarm logs thereby eliminating the need for costly manual test and data recording.
• WebSiteMonitoring: unique web interface constantly monitors the system status and records all essential data. Users can log on, view, interact and download records as needed. The factory can also monitor, diagnose remotely.
• Diagnostics:In addition to Self-test, Self-Diagnostics, LiteMinder also includes unique startup diagnostics to aid in installation and maintenance: Eight individual startup alarms (Communications, Set-Up Conflict, Low Battery, Back-feed, Transfer/AC Fuse, Short/Overload, Miswire, Incorrect AC Input) eight individual Charger Alarms and eight individual Inverter Alarms.
MoDuLAr AC SySTEM
Evenlite’s LiteMinder Central Inverter System provides an innovative Emergency Lighting solution for today’s complex energy saving systems, light sources and maintenance requirements. The LiteMinder represents the pinnacle of engineering excellence with features not found in the traditional systems currently available:
2575 Metropolitan Drive • Trevose, PA 19053 USATel: (800) 872-0879 • Fax: (215) 244-4208www.evenlite.com
LiteMinder Modular Fast Transfer Sine Wave Inverter
LM-MOD 01/19
Warranty: (For full warranty details see warranty data sheet CPS-WAR)
Electronics: Evenlite Inc. warrants the LM series electronics assembly (except batteries) against defects in material and workmanship for a period of two years or three years with Factory Startup option.Battery: Evenlite Inc. warrants the LC series Lead Calcium batteries carry a 1 year full, 9 year pro-rated limited warranty.
• PWM MOSFET and IGBT ( Model Dependant) Inverter provide Pure Sine Wave output with less than 3% THD, and fully compatible with LED Lighting Loads
• Fast transfer for H.I.D. compatibility ensures smooth operation of combined lighting loads, transfers in less than 2 mS
• Modular inverter allows operation for single phase or three phase operation to order
• Less than 3% THD, load power factor 0.5 Lag to 0.5 Lead, 98% efficient in standby mode
• Automatic Low Voltage Disconnect (LVD) set at 1.67 VPC
• Automatic restart upon utility power return, no need to manually reset the system
• Input circuit breaker is provided sized to system rating
• Shorted circuit protected to 65KAIC tested and approved to UL 6180-5-1 standard
• UL924 compliant Self-Test/Self-Diagnostics are standard, with interactive LCD display
• Monthly and the annual 90 minute test can be programmed by the user for a specific date and time to ensure NFPA Code Compliance
• Up to 1000 events stored in the memory log on a “FIFO” basis, and is easily accessible thru the MMI
• MMI (Man-Machine Interface) consists of a 5 button keypad for easy menu navigation
• A 4x20 backlit White display with heads-up LED’s allow for a quick diagnosis of the system status and alarms
• Five LED indicators provide the status of the Inverter, Charger, AC present, Ready, and Switched Load (if provided with Switched Output Circuit Breakers)
• An additional six LED indicators provide the alarm status for Alarm Summary, Bypass (if equipped with Maintenance Bypass option) , CB Trip, Startup Fault, Charger Fault, and Inverter Fault
• A dedicated System Test button is provided for a user initiated 30 second on demand test
• An Alarm On/Off LED is provided to indicate that an audible alarm is present.
• A dedicated Alarm Silence On/Off push button allows the user to silence the audible alarm
• SD card slot allows the user to download all Test, Event and Alarm Logs
• The Meter Menu allows the user to access the Input and Output Voltages, Output Current, Output VA, Battery Voltage, Battery Current, Battery Power, Temperature, System Days, Inverter minutes and Inverter Events
• Crest factor >4 for high inrush demanding loads, overload 120 percent for 10 minutes, 400 percent for 500mS
• The inverter and battery cabinets are constructed from 14 gauge CRS and are powder painted with no visible outside bolts or hardware
• Internally the inverter has all galvanized or painted steel parts for all modules and shelves to resist corrosion and provide high durability
• Installer friendly front mounted battery terminals for easier and faster installation
• VRLA Maintenance Free Lead Calcium Battery’s provide the required 90 minute minimum run time
• Battery recharge time is less than 24 hours, meets all UL 924 and NFPA101 Life Safety Code requirements
• Operating temperature 20˚ to 30˚ C
• Three Rate Charger circuit is fully temperature compensated for added reliability
• Brownout protection set for 85% of the nominal line voltage
• Electronics are warranted for 2 years and the VRLA batteries have a 10 year warranty, optional factory startup increases the warranty to 3 years
• Listed to UL924, and meets NFPA101 Life Safety Code, NFPA70-NEC and OSHA Requirements,1.0-2.8KVA models meet CSA C22.2 No. 141-10
LiteMinder Modular Fast Transfer Sine Wave InverterorDErING GuIDE Single Phase
LM
Model VARating PhaseConfiguration InputVoltage OutputVoltage OutputBreakerConfiguration Options
LM 1000VA1600VA2200VA2800VA3000VA3200VA4200VA5200VA6250VA8250VA10500VA*12500VA*
* 2 7 7 V A CONLY
1P Single Phase 120 or 277(L-N)
IA 120V (L-N)
IB 277V (L-N)
OA 120V (L-N)
OB 277V (L-N)
*C(n)20A Normally On Output Breaker*O(n)20A Normally Off Output Breaker*S(n)20A Switched Output Breaker(n) = Quanity RequiredBB Indicates Special Breaker Current
Requirement, Contact FactoryQuantityLimitations(Any combination of output types)1000VA8 x 20A Normally On without TA option4 x 20A Normally Off With or Without TA Option4 x 20A Switched With or Without TA Option5 x 20A Normally On with TA Option1600-3200VA11 x 20A Normally On without TA option6 x 20A Normally off With or Without TA Option6 x 20A Switched With or Without TA Option7 x 20A Normally On with TA Option4200-6250VA12 x 20A Normally On without TA option6 x 20A Normally Off With or Without TA Option6 x 20A Switched With or Without TA Option8 x 20A Normally On with TA Option8250-12500VA24 x 20A Normally On without TA option12 x 20A Normally Off With or Without TA Option12 x 20A Switched With or Without TA Option16 x 20A Normally On with TA Option
*TATrip Alarm for all circuit breakers
TB 1 Summary / 2 programmable terminal block for form C dry contacts
MB Internal Maintenance Bypass Switch (make before break)
DT Delayed Transfer, 60 msZ4 Seismic Zone 4 certified RA Remote Annunciator KE Keyed Lock
M(n) Maintenance Plan, n= years (5 max.)
EW Extended Warranty to 5 Years (EW requires FS)
FSStartup commissioning on Site
WM Wall Mount Kit (1KW only)
*Maximum Number of Breaker Trip Alarms Model Dependant
Example: LM-12500-1P-IB-OB-S4-TA-FS
2575 Metropolitan Drive • Trevose, PA 19053 USATel: (800) 872-0879 • Fax: (215) 244-4208www.evenlite.com
LM-MOD 01/19
Model No of
Cabinets
Width Height Depth Weight
Inverter
Cabinet
*Weight
Battery
Cabinet
**Total
Shipping
Weight
Max. BTU’s/
Hr.
at Full Load
LM1000 1 24” 38” 13” 308 lbs. N/A 343 lbs. 68
LM1600 1 32” 52” 13.75” 414 lbs. N/A 449 lbs. 109
LM2200 1 32” 52” 13.75” 492 lbs. N/A 527 lbs. 150
LM2800 1 32” 52” 13.75” 570 lbs. N/A 605 lbs. 190
LM3200 1 32” 52” 13.75” 648 lbs. N/A 683 lbs. 209
LM4200 1 32” 50” 23” 995 lbs. N/A 1,030 lbs. 286
LM5200 1 32” 50” 23” 1,155 lbs. N/A 1,190 lbs. 355
LM6250 1 32” 50” 23” 1,280 lbs. N/A 1,350 lbs. 426
LM8250 2 32” 50” 23” 400 lbs. 1,570 lbs. 2,040 lbs. 563
LM10500 2 32” 50” 23” 400 lbs 1,890 lbs. 2,340 lbs. 716
LM12500 2 32” 50” 23” 400 lbs. 2,210 lbs. 2,660 lbs 852
* Battery/Inverter cabinet weight is with batteries installed ** Total shipping weight includes pallets and packaging *LM10500 and LM12500 are only offered in 277VAC input/output
LiteMinder Modular Fast Transfer Sine Wave InverterorDErING GuIDE Split & Two Phase
LM
Model VARatingPhaseConfiguration
InputVoltage OutputVoltage OutputBreakerConfiguration Options
LM 2200VA4200VA5200VA6250VA8250VA10500VA12500VA
1S Split Phase
2P Two Phase
ID 120V/120V/240V L-N / L-N / L-L 3 Wire + Ground
IC 120V/120V/208VIE 277V/277V/480V L-N / L-N / L-L
3 Wire + Ground
OD 120V/120V/240V L-N / L-N / L-L 3 Wire + Ground
OC 120V/120V/208V OE 277V/277V/480V L-N / L-N / L-L
3 Wire + Ground
*C(n)20A Normally On Output Breaker
*O(n)20A Normally Off Output Breaker
*S(n)20A Switched Output Breaker
(n) = Quanity Required
BB Indicates Special Breaker Current Requirement, Contact Factory
QuantityLimitations(Any combination of output types)2200VA6 x 20A Normally On without TA option4 x 20A Normally Off With or Without TA Option4 x 20A Switched With or Without TA Option4 x 20A Normally On with TA Option4200-12500VA24 x 20A Normally On without TA option
12 x 20A Normally Off With or Without TA Option
12 x 20A Switched With or Without TA Option16 x 20A Normally On with TA Option
Note: split and two phase inverters require breakers per phase so must be specified in multiples of two
*TATrip Alarm for all circuit breakers
TB 1 Summary / 2 program-mable terminal block for form C dry contacts
MB Internal Maintenance Bypass Switch (make before break)
DT Delayed Transfer, 60 ms Z4 Seismic Zone 4 Certified RA Remote Annunciator KE Keyed Lock
M(n) Maintenance Plan, n= years (5 max.)
EW Extended Warranty to 5 Years (EW requires FS)
FSStartup commissioning on Site
*Maximum Number of Breaker Trip Alarms Model Dependant
Example: LM-12500-2P-ID-OD-S4-TA-Z4-FS
2575 Metropolitan Drive • Trevose, PA 19053 USATel: (800) 872-0879 • Fax: (215) 244-4208www.evenlite.com
LM-MOD 01/19
Model No of Cabinets
Width Height Depth Weight Inverter Cabinet
*Weight Battery Cabinet
**Total Shipping Weight
Max. BTU’s/Hr.
at Full Load
LM2200 2 24” 38” 13” 200 lbs 420 lbs. 635 lbs. 150
LM4200 2 32” 50” 23” 350 lbs. 680 lbs. 1,030 lbs. 286
LM5200 2 32” 50” 23” 350 lbs. 840 lbs. 1,190 lbs. 355
LM6250 2 32” 50” 23” 350 lbs. 1,000 lbs. 1,350 lbs. 426
LM8250 2 32” 50” 23” 375 lbs. 1,570 lbs. 2,020 lbs. 563
LM10500 2 32” 50” 23” 375 lbs 1,890 lbs. 2,340 lbs. 716
LM12500 2 32” 50” 23” 375 lbs. 2,210 lbs. 2,660 lbs 852
* Battery cabinet weight is with batteries installed ** Total shipping weight includes pallets and packaging
LiteMinder Modular Fast Transfer Sine Wave Inverter
2575 Metropolitan Drive • Trevose, PA 19053 USATel: (800) 872-0879 • Fax: (215) 244-4208www.evenlite.com
LM-MOD 01/19
orDErING GuIDE Three PhaseLM
Model VARatingPhaseConfiguration
InputVoltage OutputVoltage OutputBreakerConfiguration Options
LM 3000VA5200VA8250VA10500VA12500VA15750VA18750VA
3P Three Phase 120/208 or 277/480
IF 120V/208 L-N//L-L
IG 277V/480V L-N/L-L
4 wire + Ground
OF 120V/208 L-N//L-L
OG 277V/480V L-N/L-L
4 wire + Ground
*C(n)20A Normally On Output Breaker*O(n)20A Normally Off Output Breaker*S(n)20A Switched Output Breaker*(n) = Quantity Required
BB Indicates Special Breaker Current Requirement, Contact Factory
QuantityLimitations(Any combination of output types)3000VA6 x 20A Normally On without TA option3 x 20A Switched With or Without TA Option3 x 20A Normally Off With or Without TA Option3 x 20A Normally On with TA Option5200-18750VA24 x 20A Normally On without TA option
12 x 20A Switched With or Without TA Option
12 x 20A Normally Off With or Without TA Option15 x 20A Normally on with TA Option
Note: Three phase inverters require breakers per phase so must be specified in multiples of three
*TATrip Alarm for all circuit breakers
TB 1 Summary / 2 program-mable terminal block for form C dry contacts
MB Internal Maintenance Bypass Switch (make before break)
DT Delayed Transfer, 60 msZ4 Seismic Zone 4 Certified RA Remote Annunciator KE Keyed Lock
M(n) Maintenance Plan, n= years (5 max.)
EW Extended Warranty to 5 Years (EW requires FS)
FSStartup commissioning on Site
*Maximum Number of Breaker Trip Alarms Model Dependant
Example: LM-15750-3P-IG-OG-S6-TA-MB-FS
Model No of Cabinets
Width Height Depth Weight Inverter Cabinet
*Weight Battery Cabinet
**Total Shipping Weight
Max. BTU’s/Hr. at Full Load
LM3000 2 24” 38” 13” 218 lbs. 576 lbs. 820 lbs. 205
LM5200 2 32” 50” 23” 565 lbs. 1,060 lbs. 1,890 lbs. 355
LM8250 2 32” 50” 23” 565 lbs. 1,532 lbs. 2,210 lbs. 563
LM10500 2 32” 50” 23” 565 lbs. 1,850 lbs. 2,530 lbs. 716
LM12500 2 32” 50” 23” 565 lbs 2,161 lbs. 2,850 lbs. 853
LM15750 3 32” 50” 23” 565 lbs. 2,908 lbs. 3,630 lbs. 1,074
LM18750 3 32” 50” 23” 565 lbs. 3,380 lbs. 4,120 lbs. 1,279
* Battery cabinet weight is with batteries installed ** Total shipping weight includes pallets and packaging
LiteMinder Modular Fast Transfer Sine Wave Inverter
2575 Metropolitan Drive • Trevose, PA 19053 USATel: (800) 872-0879 • Fax: (215) 244-4208www.evenlite.com
LM-MOD 01/18
Mounting Slot Detail
1.38.31 Dia. holes for1/4” hardwareFloor MountingBrackets andCabinet to CabinetVertical Mounting
.75 x 2.13Slot forFloorMounting
AC Breaker Panel
24
4.0
38
Bracket, Floor Mounting
3 feet minimum clearancein front of all units
Man MachineInterface Panel
Master Inverter Cabinet
Floor Mounting Bolt Pattern
21.00
Mounting SlotSee Detail
Inter-cabinet Battery CablePorts for Vertical Mounting
9.97
1.51.5
621.
.330
Knockout patternidentical to left side
13
6x 2.0
3824.5
4x 1.75
2.56.5
Right Side
Top
4x 2.50
24
17.25 2.50
2x 1.75
16x dual knockout1-1/8” and 7/8” dia.
OverallMechanicalDimensions1KVASingleCabinet
LiteMinder Modular Fast Transfer Sine Wave Inverter
2575 Metropolitan Drive • Trevose, PA 19053 USATel: (800) 872-0879 • Fax: (215) 244-4208www.evenlite.com
LM-MOD 01/19
13.75
9.75
2.00
4x .88 and 1.13knockoutseach sideof cabinet
2x 1.75
2x 1.75
2.50 2x 2.50
32.00
27.00
45.00
6.504.00
16.00
7.86
55.00
45.87
35.53
4x .76 x 2.26slot
29.001.50
1.71
2x 10,46
6x .88 and 1.13knockouts forAC connection
Floor Mounting Bolt Pattern
12 Circuit BreakerPanel location
MMI InterfacePanel
36.00 min.clearancein front ofall units
OverallMechanicalDimensions1.6-3.0KVASingleCabinet
2575 Metropolitan Drive • Trevose, PA 19053 USATel: (800) 872-0879 • Fax: (215) 244-4208www.evenlite.com
LiteMinder Modular Fast Transfer Sine Wave Inverter
LM-MOD 01/18
Page 8
23.036”Min.
4.0
50.0
32.0
Clearancein front ofall units
Floor Mounting Bolt Pattern
26.84
O.406x per cabinetmounting holes
2.57
2x 13.28
2x 6.64
4.86
Inverter Cabinet
36.3
12 Circuit Breaker Panel location
MMIInterface Panel
.637
2575 Metropolitan Drive • Trevose, PA 19053 USATel: (800) 872-0879 • Fax: (215) 244-4208www.evenlite.com
Page 8
23.036”Min.
4.0
.050
32.0
Clearancein front ofall units
32.0
Floor Mounting Bolt Pattern
5.16 3x 26.84
O.406x per cabinet
mounting holes
2.57
2x 13.28
2x 6.64
4.86
Inverter Cabinet
Battery Cabinet No. 1 Battery Cabinet No. 2
Cabinet Configuration
Single Phase 16 - 24 Batteries - 1 Inverter cabinet, 1 Battery cabinet
Three Phase 8 - 24 Batteries - 1 Inverter cabinet, 1 Battery cabinetThree Phase 30 - 36 Batteries - 1 Inverter cabinet, 2 Battery cabinets
32.0
28.3
MMIInterface Panel
24 Circuit Breaker Panel location
Battery ConnectionKnockout locations
37.6
LM4200-6250 single phase uses a single cabinet for inverter and batteries
LM8250-12500 single phase requires two cabinets (inverter and batteries)
LM5200-12500 three phase requires two cabinets (inverter and batteries)
LM15750-18750 three phase requires three cabinets (inverter and batteries)
OverallMechanicalDimensions4.2to18.75KVA
2575 Metropolitan Drive • Trevose, PA 19053 USATel: (800) 872-0879 • Fax: (215) 244-4208www.evenlite.com
LiteMinder Modular Fast Transfer Sine Wave Inverter
LM-MOD 01/19
Inverter Power
Input Voltage
Input Current
Minimum Breaker Required
Suggested Feed Breaker
Inverter Power
Input Voltage
Input Current
Minimum Breaker Required
Suggested Feed Breaker
1000 120 10.4 13.0 20 5200 120 52.1 65.1 70208 6.0 7.5 20 208 30.0 37.6 40240 5.2 6.5 20 240 26.0 32.6 40277 4.5 5.6 20 277 22.6 28.2 30480 2.6 3.3 20 480 13.0 16.3 20
1600 120 16.7 20.8 30 6250 120 62.5 78.1 80208 9.6 12.0 20 208 36.1 45.1 50240 8.3 10.4 20 240 31.3 39.1 40277 7.2 9.0 20 277 27.1 33.8 40480 4.2 5.2 20 480 15.6 19.5 20
2200 120 22.9 28.6 30 8250 120 83.3 104.2 110208 13.2 16.5 20 208 48.1 60.1 70240 11.5 14.3 20 240 41.7 52.1 60277 9.9 12.4 20 277 36.1 45.1 50480 5.7 7.2 20 480 20.8 26.0 30
2800 120 29.2 36.5 40 10500 N/A N/A N/A N/A208 16.8 21.0 30 208 60.1 75.1 80240 14.6 18.2 20 240 52.1 65.1 70277 12.6 15.8 20 277 45.1 56.4 60480 7.3 9.1 20 480 26.0 32.6 40
3000 120 31.3 39.1 40 12500 N/A N/A N/A N/A208 18.0 22.5 30 208 75.1 93.9 100240 15.6 19.5 20 240 65.1 81.4 90277 13.5 16.9 20 277 56.4 70.5 80480 7.8 9.8 20 480 32.6 40.7 50
4200 120 41.7 52.1 60 Notes:208 24.0 30.0 30240 20.8 26.0 30277 18.1 22.6 30480 10.4 13.0 20 na - Not Available
KAIC Rating for all models = 65KAIC (UL rated per UL 61800-5-1)
2. Suggested Feed Breaker sizes are rounded up
in 10 Amp increments
EVENLITE Single Phase InvertersInput/Output Current Chart
1. Input Current = Output Current + Max Charge Current
2575 Metropolitan Drive • Trevose, PA 19053 USATel: (800) 872-0879 • Fax: (215) 244-4208www.evenlite.com
2575 Metropolitan Drive • Trevose, PA 19053 USATel: (800) 872-0879 • Fax: (215) 244-4208www.evenlite.com
LiteMinder Modular Fast Transfer Sine Wave Inverter
LM-MOD 01/192575 Metropolitan Drive • Trevose, PA 19053 USATel: (800) 872-0879 • Fax: (215) 244-4208www.evenlite.com
Inverter Power
Input Voltage
Input Current
Minimum Breaker Required
Suggested Feed Breaker
Inverter Power
Input Voltage
Input Current
Minimum Breaker Required
Suggested Feed Breaker
3000 120/208 10.4 13.0 20 10500 120/208 34.7 43.4 50277/480 4.5 5.6 20 277/480 15.0 18.8 20
4000 120/208 13.9 17.4 20 12500 120/208 43.4 54.3 60277/480 6.0 7.5 20 277/480 18.8 23.5 30
5200 120/208 17.4 21.7 30 15750 120/208 52.1 65.1 70277/480 7.5 9.4 20 277/480 22.6 28.2 30
8250 120/208 27.8 34.7 40 18750 120/208 62.5 78.1 80277/480 12.0 15.0 20 277/480 27.1 33.8 40
Notes:
3. Input Power requires 3 Wires, Neutral and Ground. Neutral is passed through and current carrying - Feeder Neutral to be sized same as Line conductors.
EVENLITE Three Phase InvertersInput/Output Current Chart
KAIC Rating for all models = 65KAIC (UL rated per UL 61800-5-1)
1. Input Current = Output Current + Max Charge Current
2. Suggested Feed Breaker sizes are rounded up in 10 Amp increments