Liebert ® RDU-M Dynamic Environment Monitoring for Secure Data Center Infrastructure

Upload: others

Post on 19-Apr-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Liebert RDU-M BR - AP14ENT-LiebertRDUMV1-BR...Emerson Network Power provides 24x7 data center infrastructure management and network monitoring software, hardware, systems and services

Liebert® RDU-MDynamic Environment Monitoring for Secure Data Center Infrastructure

Page 2: Liebert RDU-M BR - AP14ENT-LiebertRDUMV1-BR...Emerson Network Power provides 24x7 data center infrastructure management and network monitoring software, hardware, systems and services

Manage critical equipment activity involving data center power and

thermal management at multiple sites and site monitoring around the

clock. Emerson Network Power provides 24x7 data center infrastructure

management and network monitoring software, hardware, systems and

services to provide continuous oversight and security of data centers,

computer rooms and network closets, as well as applications for different

market verticals.

Page 3: Liebert RDU-M BR - AP14ENT-LiebertRDUMV1-BR...Emerson Network Power provides 24x7 data center infrastructure management and network monitoring software, hardware, systems and services

3

Challenge: Infrastructure Management Need: A solution for centralized management of the entire infrastructure

Challenge: Heat DensityNeed: Environmental Monitoring at Room and Rack Level

Challenge: Power DensityNeed: Effi cient power management tools

Challenge: Accessibility Need: Access type monitoring for rack or data center

Challenge: AvailabilityNeed: Thresholds, event generation and notifi cation capabilities

Mission critical facilities are vulnerable to threats such as excessive heat, power problems, unwanted access, humidity and air impurities to name a few. Data center management doesn’t stop in investing to air and power infrastructure equipments, monitoring plays an integral part of the entire infrastructure. Critical infrastructure monitoring is the key to assuring high availability and maximizing the investments made in these critical facilities.

Infrastructure Challenges

Page 4: Liebert RDU-M BR - AP14ENT-LiebertRDUMV1-BR...Emerson Network Power provides 24x7 data center infrastructure management and network monitoring software, hardware, systems and services

4

System IntegratedSimple installation and automatic system integration of monitoring equipments present in the data center using standard port connections for power, image and video, environment and access & control applications

Real-time MonitoringProvides real-time access and information to environmental, power, cooling and security aspects of the data center and reported via email and SMS

Remote Management Capable of intelligent management of equipments and applications from a remote location

Multi-level monitoring for the entire critical infrastructureProvided room level, rack level and equipment level monitoring

Liebert® RDU-M

Facility Safety Security & Peace of mindSimplified use and

maintenance

Multiple pre-alarm threshold, modes and levels providing preventive alerts to administrators

Full video surveillance of the facility that includes recording, replay and image capture of the facility

Intelligent room and door access functionality issued to authorized IT personnel

Linux operating system; reliable and less frequently affected by virus. Multi-level system management that provides different access levels to different administrators.

Capable of backup and querying of historical data of devices, system operations, alarm notifi cations sent to administrators

User-friendly and customizable graphic interface for a holistic view of the data center

Provides report and analysis of data center and equipment operation including PUE statistics

IP network connectivity, standard network cable connection and web remote access capability

System cloning and critical data backup function for simple and convenient maintenance

The Liebert® RDU-M provides round the clock visibility and holistic monitoring approach to your data center. This infrastructure management platform delivers real time monitoring and dynamic management of the entire IT facility from room, rack and equipment level. The Liebert® RDU-M monitoring software is already installed in a server like hardware appliance that can easily fi t in racks and cabinets. It is also capable of managing multiple monitoring systems, all at the same time, as it easily integrates environmental and security systems placed in the data center. The Liebert® RDU-M best applies from small, medium-sized and cloud-ready data centers and applications.

Page 5: Liebert RDU-M BR - AP14ENT-LiebertRDUMV1-BR...Emerson Network Power provides 24x7 data center infrastructure management and network monitoring software, hardware, systems and services

5

Liebert® RDU-M Models

RDU-MP RDU-MI RDU-MII

Centralized management platform for RDU-A and RDU-SIC

Can manage RDU-A and/or RDU-SIC up to 32 connections Can manage Emerson Door Access systems up to 32 sets

Centralized management platform for RDU-A and RDU-SIC

Can manage RDU-A and/or RDU-SIC up to 128 connections. Door = 64 IP Camera = 64

Centralized management platform for RDU-A and RDU-SIC

Can manage RDU-A and/or RDU-SIC up to 256 connections. Door = 256 IP Camera = 256

Features:

Offers a user-friendly GUI to set up and manage data center infrastructure appliances

Real-time monitoring on environmental, power, cooling, and security in data center

Video surveillance supports video recording/back up/replaying/picture capturing/voice transmission/timed recording and recording action triggered by alarm

Room access control managementRelay actions triggered by alarm or events Alarm notifi cation by Email, SMSReport and analysis on data center / device operation; PUE statistics

Page 6: Liebert RDU-M BR - AP14ENT-LiebertRDUMV1-BR...Emerson Network Power provides 24x7 data center infrastructure management and network monitoring software, hardware, systems and services

6

The Liebert RDU-M provides a holistic view of the infrastructure while monitoring the data center environment and the equipment status in real-time.

Page 7: Liebert RDU-M BR - AP14ENT-LiebertRDUMV1-BR...Emerson Network Power provides 24x7 data center infrastructure management and network monitoring software, hardware, systems and services

7777

3D Capabilities

3D Graphical Image

Critical Alarm

3D Thermal Mapping

Rack Zoom

Collapse

Zoom In

Space Usage

Page 8: Liebert RDU-M BR - AP14ENT-LiebertRDUMV1-BR...Emerson Network Power provides 24x7 data center infrastructure management and network monitoring software, hardware, systems and services

8

Features: High performance and high speed video protocol processor Optimized H.264 video compression algorithm for smooth transmission of the HD image at low bandwidth Built-in Web Server functionality, facilitates the real time monitoring and management setting of the front end of the equipment through standard IE explorer Supports remote system upgrade Connectivity: DNS, LAN and Internet (ADSL, Cable Modem) Supported network protocols: HTTP, TCP/ IP, UDP, STMP, DDNS, DNS, SNTP, DHCP, FTP Supports two-way voice intercom and voice broadcasting Self-adaptive network technology and automatic adjustment of video frame rate according to network bandwidth Alarm functions for video loss and motion detection (confi gurable area and sensitivity) Built-in high-speed dome decoder protocol Video recording / Still image capture Automatic recovery function and connection during network interruption or disturbances Supports up to 32GB of SD 2.0 protocol Installation: Flat or wall mounted

Data Center Video Surveillance & Monitoring System

Hemisphere & Bullet Camera High Sensitivity LCD Automatic white balance tracking and gain control Digital signal processing and CCD aperture

RDU-M

LAN/WAN - TCP/IP

Video Surveillance

Network Video Recorder (NVR)IP Camera twork Video Recorder (NV

Network Video Recorder (NVR)IP Camera Network Video Recorder (NVR

Page 9: Liebert RDU-M BR - AP14ENT-LiebertRDUMV1-BR...Emerson Network Power provides 24x7 data center infrastructure management and network monitoring software, hardware, systems and services

9

Battery Monitoring System

Liebert RDU-M also monitors the state of batteries in real time. It provides battery discharge data, playback and understand the discharge trend.

RDU-A G2

Modbus 485

1. The battery group voltage, resistance, and maximum, minimum, average value of temperature, etc.2. Monitoring of battery state, the alarm information and charge and discharge state.3. Monitoring of battery discharge data, discharge playback, to understand the discharge trend.

Battery Monitoring System

Battery Monitoring System

RDU-M

LAN/WAN - TCP/IP

Page 10: Liebert RDU-M BR - AP14ENT-LiebertRDUMV1-BR...Emerson Network Power provides 24x7 data center infrastructure management and network monitoring software, hardware, systems and services

10

Environment Monitoring System

Alarm Management

Temperature/Humidity SensorsMonitor room temperature and humidity

Smoke SensorsMonitor fi re / smoke in the room or cabinet

Water Stripe SensorDetects water perimeter leakage

IR DetectorA thermographic camera or infrared camera is a device that forms an image using infrared radiation

Alarm Beacon Flashing LED beaconprovides visual exception event notifi cation

LAN/WAN - TCP/IP

Email Phone Alarm SMS(No Voice)

Buzzer Alarm via Contact Closure

Modem

Windows 7 server

m

Buzzer Multimedia SMS Voice

Page 11: Liebert RDU-M BR - AP14ENT-LiebertRDUMV1-BR...Emerson Network Power provides 24x7 data center infrastructure management and network monitoring software, hardware, systems and services

11

Requirements on Client Operating Environment

WEB Browser IE 6.0 or above version

Hardware Configuration Hard disk: 1G and above, memory, 1G and above,

network card, 10MB and above

Network BandwidthOptimizeIT server bandwidth: 10MB and above

Client bandwidth requirement: 10MB and above

Power Supply

AC power supply equipment (each power supply equipment)

RDU-MP 350W, Auto Ranging(100 – 240 VAC, 50/60 Hz).

RDU-MI 350W, Auto Ranging(100 – 240 VAC, 50/60 Hz)

RDU-MII Redundant power infeed, 350W x 2, Auto Ranging

(100 – 240 VAC, 50/60 Hz).

Voltage 100-240VAC, 50/60Hz

Maximum Surge CurrentUnder the typical circuit condition and within the operating range of the

overall system environment, the surge current of every power equipment is likely to reach 25A within 10millisecond or even a shorter time.

Liebert®

RDU-M Hardware Technical Specifications

Category RDU-MP RDU-MI RDU-MII

Weight 8Kg 8Kg 15Kg

Dimension 42.6 x 431 x 393.7 (mm) 42.6 x 431 x 393.7 (mm) 42.9 x 434.0 x 612.6 (mm)

1.67” x 17.1” x 15.5” 1.67” x 17.1” x 15.5” 1.69” x 17.10” x 24.12”

(with mounting bracket and bezel)

RDU Integration 2-layers 2-layers 3-layers

RDU RDU-A, RDU-SIC RDU-A, RDU-SICRDU-MII/MI/MP, RDU-A, RDU-SIC

Quantity allowed <=32 (IP Address) <=128 (IP Address)<=256 (IP Address)and <=16 RDU-M

Video Surveillance

Camera Type Not Available IP Camera (Dome/Box) IP Camera (Dome/Box)

Quantity allowed None <=64 (IP Address) <=256 (IP Address)

Quantity of door access controller allowed

<=32 <=64 <=256

Page 12: Liebert RDU-M BR - AP14ENT-LiebertRDUMV1-BR...Emerson Network Power provides 24x7 data center infrastructure management and network monitoring software, hardware, systems and services

12

The Liebert® RDU-A G2 is an infrastructure management solution from Emerson Network Power that allows data center administrators to manage environmental conditions i.e. temperature and humidity, leak, smoke, vibrations and digital inputs and outputs. It is also capable of monitoring infrastructure appliances such as UPS, precision cooling units, generator sets and etc. The Liebert® RDU-A G2 is equipped with a built-in web server, eliminating the need to perform a software installation.

Liebert®

RDU-A G2

The Liebert® RDU-A G2 allows data center managers to perform the following operations through a secure web page:

Monitoring of the health and status of the equipment Monitoring of environmental conditions i.e. temperature and humidity, leak and smoke. Improved communication speed in transmitting control or commands to the equipment and parameter setting Data and logs of historical information of alarms and notifi cations

3rd Party Communications: SNMP Modbus 485 Dry contacts

The Liebert® RDU-A G2 serves as the communication gateway for the equipment and the Liebert® RDU-M solution. It intelligently collects and communicates data and commands, giving IT administrators a comprehensive view of what’s happening at the equipment level of the facility.

FRONT

BACK

Mechanical SpecificationsExternal model Measurement Valve Error

IRM-HOST2

Height 43mm <±0.5 mmWidth 440mm <±1 mm

Depth 311mm <±1 mm

Weight <8kg

IRM-4COMIRM-8DIAI

IRM-8DOAO

Height 20mm <±0.5 mm

Width 158mm <±1 mm

Depth 199mm <±1 mm

Weight <1kg

Environment Conditions Item Requirement

Application location Usually in data center or computer room, with air conditioner

Working temperature -10ºC ~ +60ºC

Relative humidity 5%RH ~ 95%RH, no condensing

Working environment Dust: compliant with the indoor requirements of GR-63. No corrosive gas, fl ammable gas, oily mist, steam,

water drops or salt

Air pressure 70kpa ~ 106kpa

Storage temperature -40ºC ~ +70ºC

Cooling Natural cooling

Power distribution network TT/TN

Protection level IP20

Page 13: Liebert RDU-M BR - AP14ENT-LiebertRDUMV1-BR...Emerson Network Power provides 24x7 data center infrastructure management and network monitoring software, hardware, systems and services

13

Access Control System

The access control system of the Liebert RDU-M primarily provides security and prevention of unauthorized access or entry to the data center facility. The hardware components of this access control system is based on leading international facility security designs that is also equipped with high adaptability to monitoring systems, clock technology, surge and lightning protection design, anti-interference and anti-static designs.

Access Control BoxDimensions: (L×W×H): 380mm×200mm×69.5mmMaximum

ConnectionDistance:

1200m

Display:6-digit red LED, displaying numbers or simple Englishcharacters

Lock Driving Interface:

NO/NC contacts

Contact Capacity: DC12V/2A/25Sec, DC24V/2A/25Sec, AC75V/3A/25Sec

Card Reader Port:

Wigan Signal Input Effective Low Level (or OC Door Conduction): -0.7V- +0.7V, IOUT MAX =8mA Wigan Signal Input Effective High Level (or OC Door Shut-off): high resistance -+4.0V, IOUTMAX=0mA Wigan 26BIT, 34BIT,Wigan Signal Input Effective High Level (or OC Door Shut-off): high resistance -+4.0V, IOUTMAX=0mA Wigan 26BIT, 34BIT, 36BIT and 44BIT card

numberautomatic identifi cation

Operating Temperature:

-10oC~50oC

Storage Temperature:

-30oC ~70oC

Humidity: 5% ~ 95%RH (no condensation)

Fingerprint ReaderDimension: 155mm(L) * 52mm(W) * 39mm(D) ±5%Weight: 0.2Kg±5%Working Voltage: 12VDC±5%Working Current: 300mA±5%Car Type: ID or IC cardFrequency: ID card: 125KHZ±5% IC card: 13.56MHZ±5%Reading distance: 50-100mm (without other same products interferences)Working

environment: -10~+55º C degree,

20%~90%-20~+70ºC, 5%~90%

ESD parameter: air discharge ±8KV

Page 14: Liebert RDU-M BR - AP14ENT-LiebertRDUMV1-BR...Emerson Network Power provides 24x7 data center infrastructure management and network monitoring software, hardware, systems and services

14

Electrical LocksetRated OperatingVoltage:

12V DC

Input Voltage Range: 10.8VDC-13.2VDCOperating Current: Single-opened: 0.48AMinimum Supply Current:

Single-Opened: at 800mA/12V DC input

Rated Power: single-opened: ≤6.2WRated Pulling Force: Single-Opened: 270Kg±5KgDoor Open Mode: 90o

Operating Environment:

Temperature: 10oC ~ +50oCHumidity: 20% ~ 90% (no condensation)

Applicable Door Type:

Applicable to wood door, glass door without bottom frame

(with U support) and fi reproof door

Outside ButtonModel: EP67Maximum Switch Current:

48VDC, 2A

Operating Temperature:

-25oC ~ -105oC

Button Material: Brass with nickel platingPanel Material: Stainless steelMechanical Life: 1,000,000 timesProjecting Button

Size:¢ 22×2mm

Pane Size: 86×86×6mm

RDU-M

RDU-A G2

RS 485 Controller

Exit Button Card Reader

LockLock

Dual Swing Glass Door

Finger print / Card + Password

Access Management

LAN/WAN - TCP/IP

Page 15: Liebert RDU-M BR - AP14ENT-LiebertRDUMV1-BR...Emerson Network Power provides 24x7 data center infrastructure management and network monitoring software, hardware, systems and services

15

Device Management

Energy Management

1. Device status monitoring (PUE, Teamwork)2. Device Control and monitoring3. Individual monitoring interface for each device.

PUE Model PowerCalculate by the monitoring the power meter.

PUE Model EnergyCalculate by the direct reading of UPS power. Can also be computed by manual entry results

LAN/WAN - TCP/IP

Metered PDU

UPS, Cooling, etc.

Server, switch, etc.Light, camera, etc.

Power Meter

Power Meter

LAN/WAN - TCP/IP

OS Type1. Windows

LAN/WAN - TCP/IP

Based on Java Script, CSS, HTMLMobile

Page 16: Liebert RDU-M BR - AP14ENT-LiebertRDUMV1-BR...Emerson Network Power provides 24x7 data center infrastructure management and network monitoring software, hardware, systems and services

16

Applications: Small Computer Rooms

How much do you need to manage in small computer rooms / Data Centers?With this solution, top management monitoring platform is easy to achieve with user friendly graphics and confi gurations.

RDU-M

RDU-A G2

Infrastructure AppliancesInfrastructure Appliances

LAN/WAN - TCP/IP

Page 17: Liebert RDU-M BR - AP14ENT-LiebertRDUMV1-BR...Emerson Network Power provides 24x7 data center infrastructure management and network monitoring software, hardware, systems and services

17

Expanding your data center?With this solution, scaling to adapt to your current changes is manageable and easy to maintain.

RDU-M

RDU-A G2

RDU-A G2

Security and Infrastructure AppliancesSecurity and Infrastructu

Applications: Medium Sized Data Centers

LAN/WAN - TCP/IP

Page 18: Liebert RDU-M BR - AP14ENT-LiebertRDUMV1-BR...Emerson Network Power provides 24x7 data center infrastructure management and network monitoring software, hardware, systems and services

18

Cloud Ready?Data Centers on cloud need not to be expensive in terms of management. Scalability with security is the key.

MAIN NOC

Site B

Site C

Site D

Applications: Enterprise and Cloud Ready Data Centers

LAN/WAN - TCP/IP

Page 19: Liebert RDU-M BR - AP14ENT-LiebertRDUMV1-BR...Emerson Network Power provides 24x7 data center infrastructure management and network monitoring software, hardware, systems and services

19

Make your Data Center as Dynamic as Your Business

Change the way your data centers are managed—your top priority todayAn imperative to improving performance and controlling costs

� Power switching and controls for emergency, critical, standby and distributed power� Critical power management systems used locally or remotely� Load banks up to 15K for generator and UPS testing or exercising� Surge Protection Devices (SPD) for commercial and critical power markets� Related services include maintenance, commissioning, product upgrades and reliability assessments

POWER SWITCHING & CONTROLS

SERVICES

� Complete life-cycle approach from project launch to ongoing maintenance performance optimization� Largest service footprint in the industry: 945+ Service Field Engineers, 95+ Service Centres, 75+ Technical Support/Response in Asia Pacific� Project Management, Equipment Maintenance and Performance Optimization capabilities

� Easy to deploy solution for high density requirements� Provides the components of a high availability enterprise data centre into an enclosed aisle of racks� Integrated DCIM capabilities for building and IT facilities management and capacity planning� Visibility of critical infrastructure life signs in a local office, equipped with power protection solution suitable for remote locations or across a distributed network

� Fast and efficient deployment, anytime, anywhere� Pre-assembled and factory tested to ensure quality and reliability� Fully integrated power and climate systems� Custom designs available to meet individual site needs � Wide variety of applications: oil & gas, mining, military, telecom, data centres

MODULAR CONTAINERIZEDDATA CENTRE� Industry-tested power protection and back-up power solutions

� Uninterruptible Power Supplies: Desktop, Rack and Row based, Room and Site-based� Power Distribution Units: Room-based with metering & voltage transformation, Rack mountable with metering & management capabilities

AC POWER

� Industry’s most efficient and reliable management of heat� Achieve industry leading efficiency levels (PUE <1.1)� Complete line of energy efficient, and reliable technology solutions � Data centre controls and service to optimize efficiency and uptime

THERMAL MANAGEMENT

� Best-in-class DC Power Solutions adapted by major telecom providers around the globe� Modular system architecture minimizes capital investment while allowing future growth� Increased intelligence to match utilization to capacity� Streamlined technology that reduces failure points and ensures high reliability

ENERGY SYSTEMS

� Real-time, data centre optimization platform � Inventory management and site management and monitoring� Change planning� Energy Insight, Power Management and Thermal Management

DATA CENTRE INFRASTRUCTUREMANAGEMENT

It has never been more diffi cult to manage a data center. The demand for services, environmental complexity and criticality of availability is at an all-time high.

Add to those factors a constant pressure to control costs, and it is easy to understand why organizations are rethinking how they run the data center.

By implementing the right combination of hardware and software solutions to manage the data center infrastructure, you can:

Reduce day-to-day costs and time involved in operating and maintaining the data center

Enable better management decisions by getting the right information to the right people at the right time

Make better use of existing IT and infrastructure resources, optimize data center performance and improve system availability

Emerson Network Power is the trusted source for innovative solutions and expertise in power and precision cooling systems, integrated racks andenclosures, power switching and controls, monitoring and connectivity. With our Liebert®, Avocent and Aperture® brands, we’ve been delivering data center infrastructure management benefi ts for years.

Page 20: Liebert RDU-M BR - AP14ENT-LiebertRDUMV1-BR...Emerson Network Power provides 24x7 data center infrastructure management and network monitoring software, hardware, systems and services

While every precaution has been taken to ensure accuracy and completeness herein, Emerson Network Power assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or for any errors or omissions. Specifi cations are subject to change without notice.

Emerson Network Power and Liebert® are trademarks of Emerson Electric Co. or one of its affi liated companies. All other names and logos referred to are trade names, trademarks, or registered trademarks of their respective owners. ©2014 Emerson Electric Co.

Emerson Network Power Asia

PakistanT: 92-42-36622526 to 28F: 92-42-36622530

PhilippinesT: 63-2-7207400 F: 63-2-6203693

SingaporeT: 65-64672211F: 65-64670130

ThailandT: 66-2-6178260F: 66-2-6178277 to 78

VietnamT: 84-4-37628908F: 84-4-37628909

AustraliaT: 1800-065345F: 61-2-97438737

IndonesiaT: 62-21-2513003F: 62-21-2510622

JapanT: 81-3-54038564F: 81-3-54032919

KoreaT: 82-2-34831500F: 82-2-5927886

MalaysiaT: 603-78845000F: 603-78845188

New ZealandT: 64-3-3392060F: 64-3-3392063

www.EmersonNetworkPower.Asia

AP14ENT-Liebert®RDUMV2-BR