lectures notes of: refrigeration and air conditioning

73
Modern University For Information and Technology Mechanical Engineering Department Lectures Notes Of: Refrigeration and Air Conditioning MENG 319 Prepared By Dr: Mona Mousa (First Edition 2021)

Upload: others

Post on 20-Dec-2021

1 views

Category:

Documents


0 download

TRANSCRIPT

1

Modern University For Information and Technology

Mechanical Engineering Department

Lectures Notes Of: Refrigeration

and Air Conditioning

MENG 319

Prepared By Dr: Mona Mousa

(First Edition 2021)

Refrigeration

1. Introduction Refrigeration is the action of cooling, and in practice this requires removal of of heat energy that can be converted into work is limited. As the heat flows

from hot to cold a certain amount of energy may be converted into work and

extracted. It can be used to drive a generator, for example.

The minimum amount of work to drive a refrigerator can be defined in terms of the

absolute temperature scale. Figure 1.1 shows a reversible engine E driving a

reversible heat pump P; Q and W represent the flow of heat and work. They are

called reversible machines because they have the highest efficiency that can be

visualised, and because there are no losses, E and P are identical machines.

The arrangement shown results in zero external effect because the reser- voirs

experience no net gain or loss of heat. If the efficiency of P were to be higher, i.e.

if the work input required for P to lift an identical quantity of heat Q2 from the

cold reservoir were to be less than W, the remaining part of W could power

another heat pump. This could lift an additional amount of heat.

The result would be a net flow of heat from the low temperature to the high temperature

without any external work input, which is impossible. The rela- tionship between Q1, Q2

and W depends only on the temperatures of the hot and cold reservoirs. The French

physicist Sadi Carnot (1796–1832) was the The ideal ‘never-attainable-in-practice’ ratio

of work output to heat input (W/Q1) of the reversible engine E equals: Temperature

Difference (T1 T0) divided by the Hot Reservoir Temperature (T1).

In Figure 1.1 the device P can be any refrigeration device we care to invent,

and the work of Kelvin tells us that the minimum work, W necessary to lift a quantity of

heat Q2 from temperature T0 to temperature T1

The temperatures must be measured on an absolute scale i.e. one that starts at absolute zero.

The Kelvin scale has the same degree intervals as the Celsius scale, so that ice melts at

273.16 K, and water at atmospheric pressure boils at 373.15 K. On the Celsius scale,

absolute zero is –273.15°C. Refrigeration

‘efficiency’ is usually defined as the heat extracted divided by the work input. This is

called COP, coefficient of performance. The ideal or Carnot COP takes.

Figure 1.1 Ideal heat engine, E, driving an ideal refrigerator (heat pump), P

The Refrigeration Cycle

In this cycle a unit mass of fluid is subjected to four processes after which it returns to

its original state. The compression and expansion processes, shown as vertical lines,

take place at constant entropy. A constant entropy (isentropic) process is a reversible or

an ideal process. Ideal expansion and compression engines are defined in Section 1.2.

The criterion of perfection is that no entropy is generated during the process, i.e. the

quantity ‘s’ remains constant. The add- ition and rejection of heat takes place at constant

temperature and these pro- cesses are shown as horizontal lines. Work is transferred into

the system during compression and out of the system during expansion. Heat is

transferred across the boundaries of the system at constant temperatures during

evaporation and condensation. In this cycle the net quantities of work and heat are in

propor- tions which provide the maximum amount of cooling for the minimum amount

of work. The ratio is the Carnot coefficient of performance (COP).

This cycle is sometimes referred to as a reversed Carnot cycle because the original

concept was a heat engine and for power generation the cycle operates in a clockwise

direction, generating net work.

SIMPLE VAPOUR COMPRESSION CYCLE

The vapour compression cycle is used for refrigeration in preference to gas cycles;

making use of the latent heat enables a far larger quantity of heat to be extracted for a

given refrigerant mass flow rate. This makes the equipment as compact as possible.

A liquid boils and condenses – the change between the liquid and the gaseous states –

at a temperature which depends on its pressure, within the limits of its

Heat is put into the fluid at the lower temperature and pressure thus pro- viding the

latent heat to make it vaporize. The vapour is then mechanically compressed to a higher

pressure and a corresponding saturation temperature at which its latent heat can be

rejected so that it changes back to a liquid. The cycle is shown in Figure 1.2. The cooling

effect is the heat transferred to the working fluid in the evaporation process, i.e. the

change in enthalpy between the fluid entering and the vapour leaving the evaporator.

In order to study this process more closely, refrigeration engineers use a pressure–enthalpy

or P–h diagram. This diagram is a useful way of describing the liquid and gas phase of a

substance. On the vertical axis is pressure, P, and on the horizontal, h, enthalpy. The

saturation curve defines the boundary of pure liquid and pure gas, or vapour. In the

region marked vapour, the fluid is superheated vapour. In the region marked liquid, it is

subcooled liquid. At pres- sures above the top of the curve, there is no distinction between

liquid and vapour. Above this pressure the gas cannot be liquefied. This is called the

critical pres- sure. In the region beneath the curve, there is a mixture of liquid and vapour.

The simple vapour compression cycle is superimposed on the P–h dia- gram. The

evaporation process or vaporization of refrigerant is a constant pressure process and

therefore it is represented by a horizontal line. In the compression process the energy

used to compress the vapour turns into heat and increases its temperature and enthalpy,

so that at the end of compression the vapour state is in the superheated part of the

diagram and outside the sat- uration curve. A process in which the heat of compression

raises the enthalpy of the gas is termed adiabatic compression. Before condensation can

start, the vapour must be cooled. The final compression temperature is almost always

above the condensation temperature as shown, and so some heat is rejected at a

temperature above the condensation temperature. This represents a deviation from the

ideal cycle. The actual condensation process is represented by the part of the horizontal

line within the saturation curve.

When the simple vapour compression cycle is shown on the temperature– entropy

diagram, the deviations from the reversed Carnot cycle can be identified by shaded

areas. The adiabatic compression process continues beyond the point where the

condensing temperature is reached. Expansion is a constant enthalpy process. It is

drawn as a vertical line on the P–h diagram. No heat is absorbed or rejected during this

expansion, the liquid just passes through a valve. Since the reduction in pressure at this

valve must cause a corresponding drop in temperature, some of the fluid will flash off

into vapour to remove the energy for this cooling. The volume of the working fluid

therefore increases at the valve by this amount of flash gas, and gives riseto its name,

the expansion valve. No attempt is made to recover energy from the expansion process,

e.g. by use of a turbine. This is a second deviation from the ideal cycle. The work that

could potentially be recovered is represented by the shaded rectangle

Example1.1

A refrigeration circuit is to cool a room at 0°C using outside air at 30°C to reject the heat.

The refrigerant is R134a. The temperature difference at the evaporator and the condenser is

5 K. Find the Carnot COP for the process, the Carnot COP for the refrigeration cycle and the

ideal vapour compression cycle COP when using R134a.

Solution

Multi-Evaporator And Cascade Systems

The objectives of this lesson are to:

1. Discuss the advantages and applications of multi-evaporator systems

compared to single stage systems.

2. Describe multi-evaporator systems using single compressor and a pressure

reducing valve with:

a) Individual expansion valves.

b) Multiple expansion valves.

3. Describe multi-evaporator systems with multi-compression, intercooling and

flash gas removal.

4. Describe multi-evaporator systems with individual compressors and multiple

expansion valves.

5. Discuss limitations of multi-stage systems.

6. Describe briefly cascade systems.

7. Describe briefly the working principle of auto-cascade cycle.

At the end of the lecture, the student should be able to:

1. Explain the need for multi-evaporator systems

2. Evaluate the performance of:

a) Multi-evaporator systems with single compressor and individual

expansion valves

b) Multi-evaporator systems with single compressor and multiple

expansion valves

3. Evaluate the performance of multi-evaporator systems with multi-

compression, intercooling and flash gas removal 4. Evaluate the performance of multi-evaporator systems with individual

compressors and multiple or individual expansion valves 5. Evaluate the performance of cascade systems 6. Describe the working principle of auto-cascade systems

13.1. Introduction

As mentioned in Chapter 12, there are many applications where refrigeration is required at different temperatures. For example, in a typical food processing plant, cold air may be required at –30

oC for freezing and at +7

oC for cooling of food

products or space cooling. One simple alternative is to use different refrigeration systems to cater to these different loads. However, this may not be economically viable due to the high total initial cost. Another alternative is to use a single refrigeration system with one compressor and two evaporators both operating at

−30oC. The schematic of such a system and corresponding operating cycle on P-h

diagram are shown in Figs.1(a) and (b). As shown in the figure the system consists of a single compressor and a single condenser but two evaporators. Both evaporators-I and II operate at same evaporator temperature (-30

oC) one evaporator (say

Evaporator-I) caters to freezing while the other (Evaporator-II) caters to product cooling/space conditioning at 7

oC. It can be seen that operating the evaporator at –

30oC when refrigeration is required at +7

oC is thermodynamically inefficient as the

system irreversibilities increase with increasing temperature difference for heat transfer. The COP of this simple system is given by:

In addition to this there will also be other difficulties such as: evaporator catering to space cooling (7

oC) may collect frost leading to blockage of air-flow passages, if a liquid is to

chilled then it may freeze on the evaporator and the moisture content of air may become too low leading to water losses in the food products. In such cases multi-stage systems with multiple evaporators can be used. Several multi- evaporator combinations are possible in practice. Some of the most common ones are discussed below.

13.2. Individual evaporators and a single compressor with a pressure-reducing valve

13.2.1. Individual expansion valves:

Figures 2 (a) and (b) show system schematic and P-h diagram of a multi-

evaporator system that uses two evaporators at two different temperatures and a single compressor. This system also uses individual expansion valves and a pressure regulating valve (PRV) for reducing the pressure from that corresponding to the high temperature evaporator to the compressor suction pressure. The PRV also maintains the required pressure in high temperature evaporator (Evaporator-II). Compared to the earlier system, this system offers the advantage of higher refrigeration effect at the high temperature evaporator [(h6-h4) against (h7-h5)]. However, this advantage is counterbalanced by higher specific work input due to the operation of compressor in

Heat

j t

Condenser

3 2

4

Evaporator-I (-30

oC)

Refrigeration

at –30oC

4

Evaporator-II at –30

oC

Refrigeration at +7

oC

1 1

Compressor

1

P

3

2

4 1 -30oC

h

Fig.1(a) & (b): A single stage system with two evaporators

superheated region. Thus ultimately there may not be any improvement in system

COP due to this arrangement. It is easy to see that this modification does not result in

significant improvement in performance due to the fact that the refrigerant vapour at the

intermediate pressure is reduced first using the PRV and again increased using

compressor. Obviously this is inefficient. However, this system is still preferred to the

earlier system due to proper operation of high temperature evaporator.

- I

Heat rejection

Condenser

3 2

4

Evaporator - II 6

+7oC

Refrigeration at

+7oC

8 1

PRV

Compressor

5

Evaporator - I 7

-30oC

Refrigeration at

-30oC

P

3

2

4 +7

oC

5

-30oC

6

7 1 8

h

Fig.2(a) & (b): Multi-evaporator system with single compressor and individual

expansion valves

The COP of the above system is given by:

. .

where .

m I and .

m II are the refrigerant mass flow rates through evaporator I and II

respectively. They are given by:

Enthalpy at point 2 (inlet to compressor) is obtained by applying mass and

energy balance to the mixing of two refrigerant streams, i.e.,

. .

If the expansion across PRV is isenthalpic, then specific enthalpy h8 will be equal to h6.

13.2.2. Multiple expansion valves:

Figures 3 (a) and (b) show system schematic and P-h diagram of a multi-

evaporator with a single compressor and multiple expansion valves. It can be seen

from the P-h diagram that the advantage of this system compared to the system with

individual expansion valves is that the refrigeration effect of the low temperature

evaporator increases as saturated liquid enters the low stage expansion valve. Since

the flash gas is removed at state 4, the low temperature evaporator operates more

efficiently.

The COP of this system is given by:

.

where m I and m II are the refrigerant mass flow rates through evaporator I and II

respectively. They are given by: .

I

Condenser

3

2 4

Evaporator - II 7

5

9 1

PRV

Compressor - I

6

Evaporator - I

8

P

3

2

+7oC

5 4

6

-30oC

7

8 1 9

h

Fig.3(a) & (b): Multi-evaporator system with single compressor and multiple

expansion valves

Enthalpy at point 2 (inlet to compressor) is obtained by applying mass and energy

balance to the mixing of two refrigerant streams, i.e.,

. .

If the expansion across PRV is isenthalpic, then specific enthalpy h7 will be equal to h9.

COP obtained using the above multi-evaporator systems is not much higher compared to single stage system as refrigerant vapour at intermediate pressure is first

throttled then compressed, and compressor inlet is in superheated region. Performance

can be improved significantly if multiple compressors are used in place of a single

compressor.

3. Multi-evaporator system with multi-compression, intercooling

and flash gas removal

Figures 4(a) and (b) show the schematic and P-h diagram of a multi- evaporator system which employs multiple compressors, a flash tank for flash gas removal and intercooling. This system is good for low temperature lift applications with different refrigeration loads. For example one evaporator operating at say –40

oC for

quick freezing of food products and other evaporator operating at –25oC for

storage of frozen food. As shown in the system schematic, the pressure in the high temperature evaporator (Evaporator-II) is same as that of flash tank. Superheated vapour from the low-stage compressor is cooled to the saturation temperature in the flash tank. The low temperature evaporator operates efficiently as flash gas is removed in the flash tank. In addition the high-stage compressor (Compressor-II) operates efficiently as the suction vapour is saturated. Even though the high stage compressor has to handle higher mass flow rate due to de-superheating of refrigerant in the flash tank, still the total power input to the system can be reduced substantially, especially with refrigerants such as ammonia.

The COP of this system is given by:

. .

.

where m I

and .

m e,II are the refrigerant mass flow rates through evaporator I and II

respectively. They are given by: .

m II is the mass flow rate of refrigerant through the high-stage compressor which can

be obtained by taking a control volume which includes the flash tank and high temperature evaporator (as shown by dashed line in the schematic) and applying mass and energy balance:

mass balance:

. . . . . . . .

m5 + m 2 = m7 + m3 ; m5 = m II = m3 & m 2 = m I = m7

energy balance:

6

3

2

. .

m5 h 5 + m2 h 2 + Qe,II = m7 h 7 + m3h 3

from known operating temperatures and evaporator loads (Qe,I and Qe,II) one can get the mass flow rate through the high stage compressor and system COP from the above equations.

Condenser

5 6

Evaporator - II

4

3b 3

Compressor - II

Qe,II

3a

6

Flash chamber

Control volume for

finding mass flow rate

through Compressor-II

2

7 1 Compressor - I

8

Evaporator - I

Qe,I

P

5 4

7

8 1

h

Fig.4(a) & (b): Multi-evaporator system with multiple compressors and a flash tank for

flash gas removal and intercooling

4. Multi-evaporator system with individual compressors and

multiple expansion valves

Figures 5(a) and (b) show the schematic and P-h diagram of a multi-

evaporator system which employs individual compressors and multiple expansion

valves.

The COP of this combined system is given by:

.

where .

m I and .

m II are the refrigerant mass flow rates through evaporator I and II

respectively. They are given by:

.

The inlet to the condenser (state 5) is obtained by applying mass and energy

balance to the process of mixing of refrigerant vapours from Compressors I and II.

5. Limitations of multi-stage systems

Though multi-stage systems have been very successful, they have certain

limitations. These are:

a) Since only one refrigerant is used throughout the system, the refrigerant used

should have high critical temperature and low freezing point.

b) The operating pressures with a single refrigerant may become too high or too low. Generally only R12, R22 and NH3 systems have been used in multi-stage systems as other conventional working fluids may operate in vacuum at very low evaporator temperatures. Operation in vacuum leads to leakages into the system and large compressor displacement due to high specific volume.

c) Possibility of migration of lubricating oil from one compressor to other leading to

compressor break-down.

The above limitations can be overcome by using cascade systems.

7

1

5 Condenser

6

2 7 Wc,II

Evaporator - II

8

Qe,II

9

Evaporator - I

1

Compressor - II

3

4

Compressor - I

Wc,I

Qe,I

P

6 2 5 4

8

9 3

h

Fig.5(a) & (b): Multi-evaporator system with individual compressors and multiple

expansion valves

6. Cascade Systems

In a cascade system a series of refrigerants with progressively lower boiling

points are used in a series of single stage units. The condenser of lower stage system

is coupled to the evaporator of the next higher stage system and so on. The component

where heat of condensation of lower stage refrigerant is supplied for vaporization of

next level refrigerant is called as cascade condenser. Figures 16(a) and (b) show the

schematic and P-h diagrams of a two-stage cascade refrigeration system. As shown, this

system employs two different refrigerants operating in two individual cycles. They

are thermally coupled in the cascade condenser. The refrigerants selected should have

suitable pressure-temperature characteristics. An example of refrigerant combination is the use of carbon dioxide (NBP = -78.4

oC, Tcr = 31.06

oC) in low

temperature cascade and ammonia (NBP = -33.33oC, Tcr = 132.25

oC) in high

temperature cascade. It is possible to use more than two cascade stages, and it is also possible to combine multi-stage systems with cascade systems.

Applications of cascade systems:

i. Liquefaction of petroleum vapours

ii. Liquefaction of industrial gases

iii. Manufacturing of dry ice

iv. Deep freezing etc.

Advantages of cascade systems:

i. Since each cascade uses a different refrigerant, it is possible to select a

refrigerant that is best suited for that particular temperature range. Very high

or very low pressures can be avoided

ii. Migration of lubricating oil from one compressor to the other is prevented

In practice, matching of loads in the cascade condenser is difficult, especially during

the system pull-down. Hence the cascade condensers are normally oversized. In

addition, in actual systems a temperature difference between the condensing and

evaporating refrigerants has to be provided in the cascade condenser, which leads to loss

of efficiency. In addition, it is found that at low temperatures, superheating (useful

or useless) is detrimental from volumetric refrigeration effect point-of-view, hence in

cascade systems, the superheat should be just enough to prevent the entry of liquid into

compressor, and no more for all refrigerants.

Optimum cascade temperature:

For a two-stage cascade system working on Carnot cycle, the optimum

cascade temperature at which the COP will be maximum, Tcc,opt is given by:

Tcc,opt = Te .Tc (13.18)

where Te and Tc are the evaporator temperature of low temperature cascade and condenser temperature of high temperature cascade, respectively.

2

3’ 2’

2

4’ 1’

4 1

h

Fig.6(a) & (b): A two-stage cascade refrigeration system

For cascade systems employing vapour compression refrigeration cycle, the

optimum cascade temperature assuming equal pressure ratios between the stages is

given by:

⎛ ⎞ ⎜ ⎟

T = ⎜ b1

+ b 2 ⎟

Low temp. refrigerant Pdischarge

High temp. refrigerant

ΔT

Psuction

7. Auto-cascade systems

An auto-cascade system may be considered as a variation of cascade system,

in which a single compressor is used. The concept of auto-cascade system was first

proposed by Ruhemann in 1946. Figure 13.7(a) shows the schematic of a two-stage auto-

cascade cycle and Fig.137(b) shows the vapour pressure curves of the two

Qc,out

Partial condenser

Compressor

Condenser

Evaporator

Qe,in

Fig.7(a): Schematic of a two-stage auto-cascade system

refrigerants used in the cycle on D˘hring plot.

In a two-stage auto-cascade system two different working fluids; a low boiling point (low temperature) refrigerant and a high boiling point (high temperature) refrigerant are used. The vapour mixture consisting of both these refrigerants is compressed in the compressor to a discharge pressure (Pdischarge). When this high pressure mixture flows through the partial condenser, the high temperature refrigerant

P

Te Te,h Tc,l Tc

T

Fig.7(b): Schematic illustrating principle of two-stage auto-

cascade system on D˘hring plot

can condense by rejecting heat (Qc,out) to the external heat sink, if its partial

pressure in the mixture is such that the saturation temperature corresponding to the

partial pressure is higher than the external heat sink temperature. Since the saturation temperature of the low temperature refrigerant is much lower than the external heat sink

temperature at its partial pressure, it cannot condense in the partial condenser, hence, remains as vapour. Thus it is possible theoretically to separate the high temperature

refrigerant in liquid form from the partial condenser. Next this high temperature, high

pressure liquid is expanded through the expansion valve into the condenser operating at a pressure Psuction. Due to the expansion of the high temperature refrigerant

liquid from Pdischarge to Psuction, its temperature drops to a sufficiently low value

(Te,h) so that when the low temperature, high pressure refrigerant vapour comes

in contact with the high temperature, low pressure refrigerant in the condenser it can condense at a temperature Tc,l. This condensed, high pressure, low temperature

refrigerant is then throttled to the suction pressure and is then made to flow through the

evaporator, where it can provide the required refrigeration effect at a very low temperature Te. Both the high temperature refrigerant from condenser and low

temperature refrigerant vapour from evaporator can be mixed as they are at the same

pressure. This mixture is then compressed in the compressor to complete the cycle. Thus using a single compressor, it is possible to obtain refrigeration at very low

temperatures using the auto-cascade system. In practice, more than two stages with more than two refrigerants can be used to achieve very high temperature lifts.

However, in actual systems, it is not possible to separate pure refrigerants in the partial condenser as some amount of low temperature refrigerant condenses in the partial

condenser and some amount of high temperature refrigerant leaves the partial condenser in vapour form. Thus everywhere in the system, one encounters refrigerant mixtures of

varying composition. These systems are widely used in the liquefaction of natural gas.

Questions: 1. Multi-evaporator systems are:

a) Widely used when refrigeration is required at different temperatures

b) When humidity control in the refrigerated space is required

c) When the required temperature lift is small

d) All of the above

Ans.: a) and b)

2. Multi-evaporator systems with a single compressor and a pressure reducing valve:

a) Yield very high COPs compared to multi-evaporator, single stage systems

b) Yield lower compressor discharge temperature compared to single stage systems

c) Yield slightly higher refrigeration effect in the low temperature evaporator

compared to single stage systems

d) Yield slightly higher refrigeration effect in the high temperature evaporator

compared to single stage systems

Ans.: d)

3. Compared to individual expansion valves, multiple expansion valves:

a) Yield higher refrigeration effect in the low temperature evaporator

b) Yield higher refrigeration effect in the high temperature evaporator

c) Yield lower compressor discharge temperature

d) Decrease the quality of refrigerant at the inlet to low temperature evaporator

Ans.: a) and d)

4. Compared to multi-evaporator and single compressor systems, multi-evaporator

systems with multiple compressors:

a) Yield higher COP

b) Decrease maximum cycle temperature

c) Yield higher refrigeration effect

d) All of the above

Ans.: a) and b)

5. In multi-stage systems:

a) The refrigerant used should have high critical temperature and high freezing point

b) The refrigerant used should have high critical temperature and low freezing point

c) There is a possibility of migration of lubricating oil from one compressor to other

d) Operating pressures can be too high or too low

Ans.: b), c) and d)

6. In cascade systems:

a) Different refrigerants are used in individual cascade cycles

b) There is no mixing of refrigerants and no migration of lubricating oil

c) Higher COPs compared to multi-stage systems can be obtained

d) Operating pressures need not be too high or too low

Ans.: a), b) and d)

7. Cascade systems are widely used for:

a) Large refrigeration capacity systems

b) Applications requiring large temperature lifts

c) Applications requiring very high efficiencies

d) All of the above

Ans.: b)

8. For a two-stage cascade system working on Carnot cycle and between low and high temperatures of –90

oC and 50

oC, the optimum cascade temperature at which the COP

will be maximum is given by:

a) –20oC

b) –30oC

c) –67oC

d) 0oC

Ans.: b)

9. In a two stage, auto-cascade system:

a) Two compressors and two refrigerants are used

b) A single compressor and a single refrigerant are used

c) A single compressor and two refrigerants are used

d) Two compressors and a single refrigerant are used

Ans.: c)

10. In a two stage, auto-cascade system:

a) Compressor compresses refrigerant mixture

b) Refrigerants are separated in partial condenser

c) Condensing temperature of low temperature refrigerant at discharge pressure is higher

than the boiling temperature of high temperature refrigerant at suction pressure d)

Condensing temperature of low temperature refrigerant at discharge pressure is lower

than the boiling temperature of high temperature refrigerant at suction pressure

Ans.: a), b) and c)

11. The figure given below shows a multi-evaporator, vapour compression refrigeration system working with ammonia. The refrigeration capacity of the high temperature evaporator operating at –6.7

oC is 5 TR, while it is 10 TR for the low

temperature evaporator operating at –34.4oC. The condenser pressure is 10.8 bar.

Assuming saturated conditions at the exit of evaporators and condenser, ammonia vapour to behave as an ideal gas with a gas constant of 0.4882 kJ/kg.K and isentropic index (cp/cv) of 1.29, and isentropic compression:

a) Find the required power input to compressor in kW b) Find the required power input if instead of using a single compressor,

individual compressors are used for low and high temperature evaporators.

Use the data given in the table:

10.8 bar

-6.7oC

5 TR

-34.4oC

10 TR

T,oC

Psat

(kPa)

hf (kJ/kg)

(sat.liquid) hg( kJ/kg) sat. vapour

-34.4 95.98 44.0 1417

-6.7 331.8 169.1 1455

27.7 1080.0 330.4 1485

Data for Problem 11

Ans.:

a) Single compressor: The P-h diagram for the above system is shown below:

P

3

2

4 -6.7

oC

5

-34.4oC

6

7 1 8

h

The required mass flow rate through the low temperature evaporator (mr,l) is given by:

mr,l = Qe,l/(h7 − h5) = (10 X 3.517)/(1417 − 330.4) = 0.03237 kg/s

The required mass flow rate through the high temperature evaporator (mr,h) is given by:

mr,h = Qe,h/(h6 − h4) = (5 X 3.517)/(1455 − 330.4) = 0.01564 kg/s

Assuming the refrigerant vapour to behave as an ideal gas, and assuming the variation

in specific heat of the vapour to be negligible, the temperature of the refrigerant after

mixing, i.e., at point 1 is given by:

T1 = (mr,l.T7 + mr,h.T6)/(mr,l + mr,h) = 247.6 K

Assuming isentropic compression and ideal gas behaviour, the power input to the

compressor,Wc

where mr is the refrigerant flow rate through the compressor (mr = mr,l + mr,h), R is the

gas constant (0.4882 kJ/kg.K), Pc and Pe are the discharge and suction pressures and k

is the isentropic index of compression ( = 1.29).

Substituting these values, the power input to the compressor is found to be:

1

Wc = 18.67 kW (Ans.)

Since the refrigerant vapour is assumed to behave as an ideal gas with constant

specific heat, and the compression process is assumed to be isentropic, the discharge

temperature T2 can be obtained using the equation:

Wc = mr.Cp(T2 – T1) = 18.67 kW

Substituting the values of mr, Cp (=2.1716 kJ/kg.K) and T1, the discharge temperature is found to be:

T2 = 427.67 K = 153.5oC

b) Individual compressors:

The P-h diagram with individual compressors is shown below:

P

6 2 5 4

7

8 3

h

The mass flow rates through evaporators will be same as before.

The power input to low temperature compressor (process 3 to 4), Wc,l

Similarly, for the high temperature compressor (process 1-2), the power input Wc,h

Therefore total power input is given by:

Wc = Wc,l + Wc,h = 12.13 + 2.75 = 14.88 kW (Ans.)

The compressor discharge temperatures for the low temperature and high temperature

compressor are found to be:

T4 = 411.16 K = 138.0oC

T2 = 347.27 K = 74.10oC

Comments: 1. Using individual compressors in place of a single compressor, the power input to

the system could be reduced considerably (≈ 20.3%). 2. In addition, the maximum compressor discharge temperature also could be reduced

by about 15oC.

3. In addition to this, the high temperature compressor operates at much lower

compression ratio, leading to low discharge temperatures and high volumetric

efficiency.

These are the advantages one could get by using individual compressors, instead of a

pressure regulating valve and a single compressor. However, in actual systems these

benefits will be somewhat reduced since smaller individual compressors generally

have lower isentropic and volumetric efficiencies.

4. A cascade refrigeration system shown in the figure given below uses CO2 as refrigerant for the low-stage and NH3 as the refrigerant for the high-stage. The system has to provide a

refrigeration capacity of 10 TR and maintain the refrigerated space at –36oC, when the

ambient temperature (heat sink) is at 43oC. A temperature difference of 7 K is required for

heat transfer in the evaporator, condenser and the cascade condenser. Assume the temperature lift (Tcond-Tevap) to be same for both CO2 and NH3 cycles and find a) Total power input to the

system; b) Power input if the cascade system is replaced with a single stage NH3 system

operating between same refrigerated space and heat sink.

The actual COP of the vapour compression system (COPact) can be estimated using

NH3 condenser

CO2 evaporator

43oC

NH3 Wc2

Cascade condenser

CO2

Wc1

- 36o

the equation:

= ⎡ −

T − T ⎤COPact

where

0.85 COPCarnot ⎢1 ⎣

c e

265 ⎥

COPCarnot = Carnot COP Tc =Condensing Temp., Te= Evaporator Temp.

Ans.: Since a temperature difference of & K is required for heat transfer, the CO2

evaporator and NH3 condenser temperatures are given by:

Te,CO2 = −36 −7 = -43

oC = 230 K

Tc,NH3 = 43 + 7 = 50oC = 323 K

In the cascade condenser,

Tc,CO2 = Te,NH3 + 7

Since the temperature lifts of CO2 and NH3 cycles are same,

(Tc,CO2 − Te,CO2) = (Tc,NH3 − Te,NH3)

From the above 4 equations, we obtain:

Tc,CO2 = 280 K Te,NH3 = 273 K

Substituting the values of temperatures in the expression for actual COP, we obtain:

COPCO2 = 3.17, and

COPNH3 = 3.77

The power input to CO2 compressor is given by,

Wc,CO2 = Qe,CO2/COPCO2 = 10 X 3.517 /3.17 = 11.1 kW

Since the heat rejected by the condenser of CO2 system is the refrigeration load for

the evaporator of NH3 system, the required refrigeration capacity of NH3 system is

given by:

Qe,NH3 = Qc,CO2 = Qe,CO2 + Wc,CO2 = 46.27 kW

Hence power input to NH3 compressor is given by:

Wc,NH3 = Qe,NH3/COPNH3 = 46.27 /3.77 = 12.27 kW

Therefore, the total power input to the system is given by:

Wc.total = Wc,CO2 + Wc,NH3 = 23.37 kW (Ans.)

b) If instead of a cascade system, a single stage NH3 is used then, the actual COP of

the system is:

COPNH3,1st = 1.363

Power input to single stage ammonia system is given by:

Wc,NH3,1st = Qe/ COPNH3,1st = 35.17/1.363 = 25.8 kW (Ans.)

Comments:

1) Using a cascade system the power consumption could be reduced by about 9.5 %. 2) More importantly, in actual systems, the compared to the single stage system, the compressors of cascade systems will be operating at much smaller pressure ratios, yielding high volumetric and isentropic efficiencies and lower discharge temperatures. Thus cascade systems are obviously beneficial compared to single stage systems for large temperature lift applications. 3. The performance of the cascade system can be improved by reducing the temperature difference for heat transfer in the evaporator, condenser and cascade condenser, compared to larger compressors.

Refrigeration Cycle components

Evaporators

An evaporator, like condenser is also a heat exchanger. In an evaporator, the refrigerant boils or

evaporates and in doing so absorbs heat from the substance being refrigerated. The name evaporator refers

to the evaporation process occurring in the heat exchanger

Types of Evaporators 1.Shell and Tube Evaporator

Liquid cooling evaporators may be direct expansion or flooded type. Flooded evaporators have a body

of fluid boiling in a random manner, the vapour leaving at the top. In the case of ammonia, any oil

present will fall to the bottom and be drawn off from the drain pot or oil drain connection.

Shell and Tube Evaporator

2.Direct Expansion Type-Shell and Tube

Direct Expansion Type-Shell and Tube

3.Double Pipe Type Evaporator

Double Pipe Type Evaporator 4.Direct Expansion Fin and Tube

Direct Expansion Fin and Tube

5.Embede Tube, Plate Surface Evaporator

Embede Tube, Plate Surface Evaporator

Condenser Classification of condensers:

Based on the external fluid, condensers can be classified as:

a) Air cooled condensers

b) Water cooled condensers, and

c) Evaporative condensers

-------------------------------------------------------------------------------------------

a) Air cooled condensers

As the name implies, in air-cooled condensers air is the external fluid, i.e., the refrigerant rejects heat to air

flowing over the condenser. Air-cooled condensers can be further classified into natural convection type or

forced convection type.

1-Natural Convection And Forced Convection Type b- Water Cooled Condenser

In water cooled condensers water is the external fluid. Depending upon the construction, water cooled

condensers can be further classified into:

1. Double pipe or tube-in-tube type

2. Shell-and-coil type

3. Shell-and-tube type ---------------------------------------------------------------------------------------

1. Double pipe or tube-in-tube type

2. Shell-and-coil type

3. Shell-and-tube type

c- Evaporative Condenser.

Air cooled vs water cooled condensers:

The expansion device

The expansion devices used in refrigeration systems can be divided into fixed opening type or variable

opening type. As the name implies, in fixed opening type the flow area remains fixed, while in variable

opening type the flow area changes with changing mass flow rates. There are basically seven types of

refrigerant expansion devices. These are:

1. Hand (manual) expansion valves

2. Capillary Tubes

3. Orifice

4. Constant pressure or Automatic Expansion Valve (AEV)

5. Thermostatic Expansion Valve (TEV)

6. Float type Expansion Valve

a) High Side Float Valve

b) Low Side Float Valve

7. Electronic Expansion Valve

One of the above seven types, Capillary tube and orifice belong to the fixed opening type, while the rest

belong to the variable opening type. Of the seven types, the hand operated expansion valve is not used when

an automatic control is required. The orifice type expansion is used only in some special applications. Hence

these two are not discussed here.

2-A capillary tube is a long, narrow tube of constant diameter. The word “capillary” is a misnomer since

surface tension is not important in refrigeration application of capillary tubes. Typical tube diameters of

refrigerant capillary tubes range from 0.5 mm to 3 mm and the length ranges from 1.0 m to 6 m.

The pressure reduction in a capillary tube occurs due to the following two factors:

The refrigerant has to overcome the frictional resistance offered by tube walls. This leads to some pressure

drop, and the liquid refrigerant flashes (evaporates) into mixture of liquid and vapour as its pressure

reduces. The density of vapour is less than that of the liquid. Hence, the average density of refrigerant

decreases as it flows in the tube. The mass flow rate and tube diameter (hence area) being constant, the

velocity of refrigerant increases since m = ρVA. The increase in velocity or acceleration of the refrigerant

also requires pressure drop.

3. Orifice

In variable area type expansion devices, such as automatic and thermostatic expansion

valves, the pressure reduction takes place as the fluid flows through an orifice of varying

area. Let A1and A2 be the areas at the inlet and the outlet of the orifice where, A1> A2. Let

V1 and V2 be the velocities, P1 and P2 are the pressures and ρ1and ρ2 be the densities at

the inlet and outlet respectively of the orifice as shown

4. Constant pressure or Automatic Expansion Valve (AEV)

An Automatic Expansion Valve (AEV) also known as a constant pressure expansion valve acts in such a

manner so as to maintain a constant pressure and thereby a constant temperature in the evaporator. The

schematic diagram of the valve is shown in Figure. As shown in the figure, the valve consists of an

adjustment spring that can be adjusted to maintain the required temperature in the evaporator. This exerts

force Fs on the top of the diaphragm.

The atmospheric pressure, Po also acts on top of the diaphragm and exerts a force of Fo = P oAd,

Ad being the area of the diaphragm. The evaporator pressure Pe acts below the diaphragm. The force due

to evaporator pressure is Fe= Pe Ad. The net downward force Fo + Fs - Fe is fed to the needle by the

diaphragm. This net force along with the force due to follow-up spring Ffs controls the location of the needle

with respect to the orifice and thereby controls the orifice opening.

If Fe+ Ffs> Fs+ Fo the needle will be pushed against the orifice and the valve will be fully closed.

7

5. Thermostatic Expansion Valve (TEV)

6. Float type Expansion Valve

Float type expansion valves are normally used with flooded evaporators in large capacity

refrigeration systems. A float type valve opens or closes depending upon the liquid level as sensed

by a buoyant member, called as float. The float could take the form of a hollow metal or plastic ball,

a hollow cylinder or a pan. Thus the float valve always maintains a constant liquid level in a chamber

called as float chamber. Depending upon the location of the float chamber, a float type expansion

valve can be either a low-side float valve or a high-side float valve Version

a) High Side Float Valve

b) Low Side Float Valve

7. Electronic Expansion Valve

An electronic expansion valve consists of an orifice and a needle in front it. The needle moves up and down

in response to magnitude of current in the heating element. A small resistance allows more current to flow

through the heater of the expansion valve, as a result the valve opens wider. A small negative coefficient

thermistor is used if superheat control is desired. The thermistor is placed in series with the heater of the

expansion valve. The heater current depends upon the thermistor resistance that depends upon the

refrigerant condition. Exposure of thermistor to superheated vapour permits thermistor to selfheat thereby

lowering its resistance and increasing the heater current.

This opens the valve wider and increases the mass flow rate of refrigerant. This process continues until the

vapour becomes saturated and some liquid refrigerant droplets appear. The liquid refrigerant will cool the

thermistor and increase its resistance. Hence in presence of liquid droplets the thermistor offers a large

resistance, which allows a small current to flow through the heater making the valve opening narrower. The

control of this valve is independent of refrigerant and refrigerant pressure; hence it works in reverse flow

direction also. It is convenient to use it in year-round-air-conditioning systems, which serve as heat pumps

in winter with reverse flow. In another version of it the heater is replaced by stepper motor, which opens

and closes the valve with a great precision giving a proportional control in response to temperature sensed

by an element.

Compressors The purpose of the compressor in the vapour compression cycle is to compress

THE PISTON COMPRESSION PROCESS

The piston type is very widely used, being adaptable in size, number of cylinders, speed and method of

drive. It works on the two-stroke cycle (see Figure 4.4). Automatic pressure-actuated suction and

discharge valves are used as shown in Figure 4.4. As the piston descends on the suction stroke, the

suction valve opens to admit gas from the evaporator. At the bottom of the stroke, this valve will close

again as the compression stroke begins. When the cylinder pressure becomes higher than that in the

discharge pipe, the discharge valve opens and the compressed gas passes to the condenser.

Schematic of Linde’s horizontal, double acting compressor

Double acting cylinder

Air Conditioning

Introduction to Air Conditioning Air conditioning may be required in buildings which have a high heat gain and as a result a high

internal temperature. The heat gain may be from solar radiation and/or internal gains such as people,

lights and business machines. The diagram below shows some typical heat gains in a room.

If the inside temperature of a space rises to about 25

oC then air-conditioning will probably be

necessary to maintain comfort levels. This internal temperature (around 25oC) may change depending

on some variables such as: Window blinds or shading methods

Heat absorbing glass

Heat reflecting glass

Operable windows

Higher ceilings

Smaller windows on south facing facades

Alternative lighting schemes.

If air conditioning is the only answer to adequate comfort in a building then the main choice of system can be considered.

Full comfort air conditioning can be used in summer to provide cool air (approx. 13oC to

18oC) in summer and warm air (approx. 28

oC to 36

oC) in winter.

Also the air is cleaned by filters, dehumidified to remove moisture or humidified to add

moisture.

Air conditioning systems fall into three main categories, and are detailed in the following pages;

Plant Central systems.

Room Air Conditioning Units.

Fan Coil Units.

1. Central plant systems have one central source of conditioned air which is distributed in a

network of ductwork.

Room air conditioning units are self-contained package units which can be positioned in

each room to provide cool air in summer or warm air in winter.

Fan coil units are room units and incorporate heat exchangers piped with chilled water and a fan

to provide cool air.

There are other forms of air conditioning such as:

Chilled Beams.

Induction Units.

Variable Air Volume Units.

Dual Duct Systems.

Chilled Ceiling.

But we will consider the more commonly used methods first. Typical central plant air

conditioning system.

The system shown above resembles a balanced ventilation system with plenum heating but with

the addition of a cooling coil.

In winter the heater battery will be on and the cooling coil will probably be switched off for the

majority of buildings. In summer the heater battery will not need to have the same output and the

cooling coil will be switched on.

A humidifier may be required to add moisture to the air when it is 'dry’. This is when outdoor air

has a low humidity of around 20% to 30%.

In the U.K. low humidity are rare and therefore humidification is sometimes not used. In

dryer regions humidification is required through most of the year whereas in tropical air

conditioning one of the main features of the system is the ability to remove moisture from warm

moist air.

Dampers are used in air conditioning central plant systems to control the amount of air in each

duct. It is common to have 20% fresh air and 80% recirculated air to buildings. In buildings with

high occupancy the fresh air quantity should be calculated based on C.I.B.S.E. data, this may

require a higher percentage of fresh air (i.e. more than 20%).

Filters are required to remove particles of dust and general outdoor pollution. This filter is

sometimes called a coarse filter or pre-filter. A removable fibreglass dust filter is positioned in

the fresh air intake duct or in larger installation oil filled viscous filter may be used.

The secondary filter, after the mix point, is used to remove fine dust particles or other

contaminant picked up in the rooms and recirculated back into the plant. A removable bag filter is

generally used for this where a series of woven fibre bags are secured to a framework which can

be slid out of the ductwork or air handling unit (A.H.U.) for replacement.

1-Air Handling Units

Air handling units (A.H.U.) are widely used as a package unit which incorporates all the main

plant items as shown below. Pipe work, ductwork and electrical connections are made after

the unit is set in place on site.

Since air conditioning plant rooms tend to be at roof level, the larger A.H.U.'s are lifted into

place by crane before the roof is fixed.

In some cases it is usual to place the fan in front of (that is upstream of) the heater battery and

cooling coil. This is because fans operate best if the system resistance is at the outlet rather than

the inlet of the impeller. This is shown on the schematic diagrams above.

The photograph below shows a typical air handling unit with handles on the doors for access

to equipment.

2-Room Air Conditioning Units

These units use refrigerant to transfer cooling effect into rooms.

Room air conditioning units fall into two main categories:

Split type

Window/wall units.

Split Air Conditioners

Split air conditioners have two main parts, the outdoor unit is the section which generates the

cold refrigerant gas and the indoor unit uses this cold refrigerant to cool the air in a space. The

outdoor unit uses a compressor and air cooled condenser to provide cold refrigerant to a

cooling coil in the indoor unit. A fan then blows air across the cooling coil and into the room.

The indoor unit can either be ceiling mounted (cassette unit), floor mounted or duct type. The

drawing below shows a ceiling mounted (cassette unit).

The photograph above shows a ceiling mounted cassette and an outdoor unit. Window / Wall Units

Window or wall units are more compact than split units since all the plant items are contained

in one box.

Window units are installed into an appropriate hole in the window and supported from a metal

frame.

Wall units like the one shown below are built into an external wall and contain all the necessary

items of equipment to provide cool air in summer and some may even provide heating in winter.

A small

Hermetically sealed compressor is used to provide refrigerant gas at the pressure required to

operate the refrigeration cycle. The condenser is used to condense the refrigerant to a liquid

which is then reduced in pressure and piped to the cooling coil.

Generally central plant systems are used in large prestigious buildings where a high quality

environment is to be achieved. Cassette units and other split systems can be used together

with central plant systems to provide a more flexible design.

Each system has its own advantages and the following is a summary of some of the main

advantages and disadvantages.

Central Plant Systems - Advantages:

1. Noise in rooms is usually reduced if plant room is away from occupied spaces.

2. The whole building can be controlled from a central control station. This means that

optimum start and stop can be used and a weather compensator can be utilised.

3. Also time clocks can bring air conditioning on and off at appropriate times.

4. Maintenance is centralised in the plant room. Plant is easier to access

Central Plant Systems - Disadvantages:

1. Expensive to install a complete full comfort air-conditioning system throughout a

building.

2. Space is required for plant and to run ductwork both vertically in shafts and horizontally

in ceiling spaces.

3. Individual room control is difficult with central plant.

4. Many systems have been tried such as Variable Air Volume (VAV), dual duct systems

and zone re-heaters. Zone re-heaters are probably more successful than the rest.

Room Air Conditioning Units - Advantages:

1. Cheaper to install.

2. Individual room control.

3. Works well where rooms have individual requirements.

4. No long runs of ductwork.

5. Can be used to heat as well as cool if a reversing valve is fitted.

Room Air Conditioning Units - Disadvantages:

1. Sometimes the indoor unit fan becomes noisy.

2. Noisy compressor in outdoor unit.

3. Each unit or group of units has a filter, compressor and refrigeration pipe work that needs

periodic maintenance and possible re-charging. Units have course filters therefore

filtration is not as good as with AHU’s.

4. The installation may require long runs of refrigerant pipe work which, if it leaks into the

building, can be difficult to remedy.

5. Not at robust as central plant.

6. The majority of room air conditioners just recalculate air in a room. With no fresh air

supply although most manufacturers make units with fresh air capability.

7. Cooling output is limited to about 9 kW maximum per unit, Therefore many units would

be required to cool rooms with high heat gains.

Air Conditioning process The aim of this section is to allow students to size air conditioning plant such as;

cooling coil, heater battery and

humidifier.

The notes are divided into several sections as

follows:

1. Psychometric for air conditioning.

2. The Psychometric chart.

3. Examples of psychometric properties.

4. Air conditioning plant for summer & winter.

5. Basic processes.

6. Typical air conditioning processes.

7. Annotation and room ratio.

8. Summer and winter cycles.

9. Examples.

The first section deals with Psychometric for air conditioning and discusses some properties of

moist air. A simplified psychometric chart is shown for familiarization, and some examples of

how to find air properties are provided.

A diagram of an air conditioning system is shown in schematic form in the section entitled AIR

Conditioning plant for summer & winter. Before sizing takes place the student should also

understand the processes that take place in air conditioning systems. There are four basic

processes for summer and winter air conditioning systems.

The following basic processes are

explained:

1. Mixing

2. Sensible Cooling and Heating

3. Cooling with Dehumidification

4. Humidification

The section on Typical Air Conditioning Processes shows winter and summer schematic

diagrams and psychometric charts. There are some more details that may be useful to

the designer of air conditioning systems. Further information is as follows: Annotation, Room

ratio when the processes have been superimposed onto a psychometric chart then calculations

may commence. These are as detailed in the following sections of the notes.

Summer and winter Cycles

1. Summer cycle psychometrics

2. Summer cycle calculations

3. Winter cycle psychometrics

4. Winter cycle calculations

5. Duct and Fan gains.

The final section is seven examples of plant sizing using psychometric

charts.

Psychometric for Air Conditioning

Psychometric is the study of air and water vapour mixtures.

Air is made up of five main gases i.e.

Nitrogen 78.03%, Oxygen 20.99%, Argon 0.94%, Carbon Dioxide 0.03%, and Hydrogen 0.01%

by volume.

The Ideal Gas Laws are used to determine psychometric data for air so that the engineer can

carry out calculations.

To make life easier a chart has been compiled with all the relevant psychometric data indicated.

This is called the Psychometric Chart. A typical chart is shown below.

Air at any state point can be plotted on the psychometric chart.

The information that can be obtained from a Psychometric Chart is as follows:

1. Dry bulb temperature

2. Wet bulb temperature

3. Moisture content

4. Percentage saturation

5. Specific enthalpy

6. Specific volume.

The following is a brief description of each of the properties of air.

1. Dry bulb temperature This is the air temperature measured by a mercury-in-glass thermometer.

2. Wet bulb temperature This is the air temperature measured by a mercury-in-glass thermometer which has the mercury bulb wetted by gauze that is kept moist by a reservoir of water. When exposed to

the environment the moisture evaporates from the wetted gauze, which gives a lower

reading on the thermometer. This gives an indication of how ‘dry’ or how ‘moist’ the air

is, since in ‘dry’ air the water will evaporate quickly from the gauze, which depresses the

thermometer reading.

3. Moisture content or specific humidity

This is the amount of moisture in air given in kg of moisture per kg of dry air e.g. for

room air at 21oC dry bulb and 15

oC wet bulb, the moisture content is about 0.008 kg/kg

d. a. This is a small mass of moisture (0.008 kg = 8 grams) per kg of dry air or 9.5 grams

per cubic metre of air.

4. Moist air It is a mixture of air and water vapour. The amount of water vapour present in the air

depends upon the absolute pressure and temperature of the mixture.

5. Standard air

It is moist air when the air has diffused the maximum amount of water vapour into it.

6. Dew point temperature It is the temperature of air recorded by a thermometer when the moisture present in it

begins to condense at constant pressure, thus the dew point temperature is the saturation

temperature corresponding to partial pressure of water vapour.

7. Relative humidity It is the ratio of the actual water vapour pressure of the air to the saturated water vapour

pressure of the air at the same temperature (PV, actual / PV, saturated).

8. Percentage saturation The Percentage saturation is another indication of the amount of moisture in air. This is

the ratio of the moisture content of moist air to the moisture content of saturated air at the

same temperature. When air is saturated it is at 100% saturation and cannot hold any

more moisture.

9. Specific enthalpy This is the amount of heat energy (kJ) in air per kg. If heat is added to the air at a heater

battery for example, then the amount to be added can be determined from Specific

enthalpy change.

10.Specific volume

This is the volume of moist air (dry air + water vapour) per unit mass. The units of

measurement are m3

per kg. Also specific volume = 1 / density.

11.Latent heat It is the heat which causes a change in phase with no change in the temperature.

12.Sensible heat It is the increase in heat content of air when the temperature rises as heat is added, or the

heat which causes a change in temperature.

The Psychometric Chart

The six properties of air previously discussed can be shown on one chart called a Psychometric

Chart. One of the purposes of the Psychometric Chart is to size heater batteries, cooling coils and

Psychometric Chart is to size heater batteries, cooling coils and humidifiers. A simplified

Psychometric Chart is shown below.

This chart is only for demonstration purposes. If accurate assessments are to be carried out use a

C.I.B.S.E. chart.

Using the Psychometric Chart

If any two properties of air are known then the other four can be found from the

psychometric chart.

Examples of Psychometric Properties

EXAMPLE 1

Find the moisture content of air at 25oC dry-bulb temperature and 25

oC wet-bulb

temperature.

Referring to the chart below, a vertical line is drawn upwards from 25oC dry-bulb

temperature until it intersects at 25oC wet-bulb temperature. This intersection point

happens to be on the 100% saturation line. The intersection point is highlighted and a

horizontal line is drawn to the right to find the corresponding moisture content. The

moisture content is therefore 0.020 kg/kg dry air.

EXAMPLE 2 Find the specific volume and wet-bulb temperature of air at 20

oC dry-bulb temperature

and 50% saturation.

Referring to the chart below, a vertical line is drawn upwards from 20oC dry-bulb

temperature until it intersects with the 50% saturation curve.

The intersection point is sometimes referred to as the state point.

The specific volume is found to be 0.84 m3/kg and the wet-bulb temperature is 14

oC

EXAMPLE 3 Find the specific volume, percentage saturation and moisture content of air at 15

oC

dry-bulb temperature and 10oC wet-bulb temperature.

Referring to the chart below, a vertical line is drawn upwards from 15oC dry-bulb

temperature until it intersects with the 10oC wet-bulb temperature line. This

intersection is the state point. The specific volumes found to be 0.823 m3/kg, the

percentage saturation 52% and the moisture content 0.0054 kg/kg d. a.

EXAMPLE 4 Find the specific volume, wet-bulb temperature, moisture content and specific enthalpy

of air at 35oC dry-bulb temperature and 30% saturation.

Referring to the chart below, a vertical line is drawn upwards from 35oC dry-bulb

temperature until it intersects with the 30% saturation curve.

This intersection is the state point.

The specific volume is found to be 0.883 m3/kg, the wet-bulb temperature is 22

oC,

the moisture content 0.011kg/kg d. a. and the specific enthalpy 65 kJ/kg.

Air conditioning plant for summer and winter

In the summer time when cooling is required by the air conditioning plant it will be necessary to

operate the cooling coil, re-heater and possibly other plant as well. In winter time the pre-heater

and re-heater battery will probably be on to provide warm air to overcome heat losses. Other

plant may be switched on as well. These plant items are shown in the diagram below.

The photographs below show some plant items.

Basic Air Conditioning Processes 1. Mixing

Where two air streams are mixed the psychometric process is shown as a straight line between two

air conditions on the psychometric chart, thus points 1 and 2 are joined and the mix point 3 will lie

on this line. Two air streams are mixed in air conditioning when fresh air (m1) is brought in from

outside and mixed with recirculated air (m2). The resulting air mixture is shown below as (m3).

The mixing ratio is fixed by dampers. Sometimes, in more sophisticated plant, modulating dampers

are used which are driven by electric motors to control the mixture of air entering the system. The

diagrams below show mixing of two air streams.

By the conservation of mass formula: m1 + m2 = m3

By the conservation of energy formula: m1 h1 + m2 h2 = m3 h3

Where: m = mass flow rate of air (kg/s)

h = Specific enthalpy of air (kJ/kg) found from psychometric chart.

2. Sensible Cooling and Heating

When air is heated or cooled sensibly, that is, when no moisture is added or removed, this

process is represented by a horizontal line on a psychometric chart.

For sensible heating:

The amount of heating input to the air approximates to H1-2 = m * Cp * (t2 - t1) Or more

accurately from psychometric chart: H1-2 = m * (h2 - h1) Where: H = Heat or cooling energy (kW)

m Cp

t

= Mass flow rate of air (kg/s)

= Specific heat capacity of air, may be taken as 1.01 kJ/kg oC.

= Dry bulb temperature of air (oC)

h = Specific enthalpy of air (kJ/kg) found from psychometric chart.

3. Cooling with Dehumidification

The most commonly used method of removing water vapour from air (dehumidification) is to cool

the air below its dew point.

The dew point of air is when it is fully saturated i.e. at 100% saturation.

When air is fully saturated it cannot hold any more moisture in the form of water vapour.

If the air is cooled to the dew point air and is still further cooled then moisture will drop out of the air

in the form of condensate.

This can be shown on a psychometric chart as air sensibly cooled until it becomes fully saturated

(the dew point is reached) and then the air is cooled latently to a lower temperature.

This is apparent on the psychometric chart as a horizontal line for sensible cooling to the 100%

saturation curve and then the process follows the 100% saturation curve down to another point at a lower

temperature.

This lower temperature is sometimes called the Apparatus dew Point (ADP) of the cooling coil. In

reality the ADP of the cooling coil is close to the cooling liquid temperature inside the coil. Chilled

water or refrigerant may be the cooling liquid.

The psychometric process from state point 1 to 2 to 3 may be shown as a straight line for

simplicity as shown above with a yellow line.

Typical Air Conditioning Processes

The schematic diagram below shows a typical plant system for summer air conditioning.

The psychrometric diagram below shows a typical summer cycle.

Schematic diagram below shows a typical plant system for winter air conditioning.

The psychrometric diagram below shows a typical winter cycle.

Where Q2

U

= =

Amount of heat produced due to heat transmission through wall Transmission coefficient U of Wall (carrier H.B; page 66)

ΔTequivalent = =

Equivalent temp Equivalent temp difference (carrier H.B; page 62) +Correction factor

(carrier H.B; page, 63

Thermal loads sources include a) Solar heat gain. b) Transmission heat gain.

c) Internal heat gain.

d) Ventilation ,and infiltration.

Thermal load types divided into two types a) Sensible Heat. b) Latent Heat.

How to calculate sensible and latent heat effect on the building causes increasing internal

temperature of building?

a) Solar Heat Gain

By using the equation, Q=A*sc*q

Where Q = Aamount of heat produced due to solar radiation BTU/HR

A

SC

q

=

=

=

Area of window (FT2)

Overall factor for solar heat gain through glass (carrier H.B ; page 52)

Solar heat gain through ordinary glass (carrier H.B ; page 44)

b) Transmission Heat Gain include 1-Windows

Can be calculated by using equation Q1 = A * U * ΔT Where Q1 = Amount of heat produced due to heat transmission through window.

A

U

To

Tr

=

=

=

=

Area of window (FT2)

Transmission coefficient U of windows (carrier H.B ; page 76)

Out side temp F

Room temp, F

2-WALL

Can be calculated by using equation Q2 = A * U * ΔTequivalent

CFM = (space volume (FT3)*n of air change)/60

OR = Amount of air required for each person *number of person Qs

Ql

Gr/Ib

= =

=

CFM * 1.08 * (To-Ti) 0.68 ( (Gr/Ib)o – (Gr/Ib)i ) Moisture content

BTU/HR BTU/HR

3, 4, and 5 Floor, Paptions, Ceiling

Can be calculated by using equation Q3,4,5 = A * U * ΔT

Where Q3,4,5 = Amount of heat produced due to heat transmission through floor, part ion, and ceiling (BTU/HR)

A = Area of through floor, part ion, and ceiling.

ΔT = 0 or 5 when your neighbour hood space was conditioned . (To-

10) – Ti when your neighbour hood space was not conditioned .

(To- – Ti) when your neighbour hood space was not conditioned , and very hot .

6-ROOF

Can be calculated by using equation Q6 = A * U * ΔT

Q6

A

= =

Amount of heat produced due to heat transfer through roof Roof area

U = Transmission coefficient U –flat roof ((carrier H.B; page 71)

ΔTequivalent = =

Equivalent temp Equivalent temp difference (carrier H.B; page 63) +Correction factor

(carrier H.B; page, 63)

1- Internal heat gain 1. lighting

Q = Power (watt) * 3.4 BTU/HR for normal lighting

= Power (watt) * 4.2 BTU/HR for folarseat lighting

2. Electrical equipment

Q = Power (watt) * 3.4 BTU/HR

3. Electrical motors

Q = Power (HP) * 2545 BTU/HR

4. People

Human body dissipate two types of j heat Sensible heat gain can be calculated as follow

Qs = number of persons * Ssensible heat gain for each person.

Latent heat gain can be calculated as follow

QL= number of persons * Latent heat gain for each person.

D) Ventilation and infiltration

Thermal load due to infiltration can be neglected.

Thermal load due to ventilation can be calculated as follow

Amount of air required for ventilation can be calculated by using 2 ways

From points A, B, C, and D

A/C Capacity = Ggrand sensible heat gain + Grand latent heat gain BTU/HR

Air transmission

Flow of air through ducts To overcome the fluid friction and the resulting head, a fan is required in air conditioning systems. When a

fan is introduced into the duct through which air is flowing, then the static and total pressures at the section

where the fan is located rise. This rise is called as Fan Total Pressure (FTP). Then the required power

input to the fan is given by:

It can be easily shown that when applied between any two sections 1 and 2 of the duct, in which the fan is

located, the FTP is given by:

Estimation of pressure loss in ducts

As air flows through a duct its total pressure drops in the direction of flow.

The pressure drop is due to:

1. Fluid friction

2. Momentum change due to change of direction and/or velocity

The pressure drop due to friction is known as frictional pressure drop or friction loss, Δpf. The pressure

drop due to momentum change is known as momentum pressure drop or dynamic loss, Δpd. Thus the

total pressure drop Δpt is given by:

Dynamic losses in ducts

where K is the dynamic loss coefficient, which is normally obtained from experiments

Sources of Dynamic Losses

Sudden Enlargement

Finding Pressure Loss By The equal friction factor method The equal method of sizing ducts is often preferred because it is quite easy to use. The method

can be summarized to

1- Compute the necessary air flow volume in every room and branch of the system.

2- Se to compute the total air volume in the main system

3- Determine the maximum acceptable air flow velocity in the main duct.

4- Determine the major pressure drop in the main duct.

5- Use the major pressure drop for the main duct as a constant to determine the duct sizes

throughout the distribution system.

6- Determine the total resistance in the duct system by multiplying the static resistance with the

equivalent length of the longest run.

7- Compute balancing dampers.

Example:

References : 1-Refrigeration and air conditioning Fourth Edition, G.F.Hundy, A.R. Trott, T.C.Welch 2- adermacher, R., & Hwang, Y. (2005). Vapor compression heat pumps with refrigerant mixes. Boca Raton, FL: Taylor & Francis. 3- Haile, J. M. (2002). Lectures in Thermodynamics: Macatea Productions. 4-Flow Rates in Heating System. (n.d.). Retrieved 27th May 2015 from http://www.engineeringtoolbox.com/water-flow-rates-heating-systems-d_659.html. 5- Refrigeration and air conditioning, S.K. Mondoal. 6- Industrial Refrigeration Hand Book,Wilbert F. Stoecker.