    and Concrete Structures

    Chiew Sing-Pingv v

    Nanyang Technological University, Singapore

    12 J uly 2013

  • 7/27/2019 Lecture 2 by Chiew Sing Ping FOR CIVIL AND STRUCTURE

    2/51

    Scope of Presentation

    M t ri l

    Com osite columns

    Composite beams Composite slabs

    2

  • 7/27/2019 Lecture 2 by Chiew Sing Ping FOR CIVIL AND STRUCTURE

    3/51

    Design Codes for Composite Structures

    Effective 1 st April 2015: Till 31 st March 2015:

    Eurocode 1- for loadings

    BS 6399- for loadings

    - - for concrete properties and some

    of the concrete related checks- for construction stage, design of pure

    beam(such as longitudinal shear)

    Eurocode 3 (many Parts)BS 5950-6- for design of profiled steel sheeting

    - ,pure steel beam and profiled steelsheeting

    - .- for design of composite beamBS5950-4

    Eurocode 4 Part 1-1- general rules of buildings - for design of composite slabBS 5400-5-

    - for the structural fire design-BS 5950-8

    - for structural fire desi n

    3

  • 7/27/2019 Lecture 2 by Chiew Sing Ping FOR CIVIL AND STRUCTURE

    4/51

    Design Safety Factors

    Eurocodes British Standards

    Load safet factors 1.35 G + 1.5 1.4 G + 1.6 BS5950 1.2 G k + 1.5 Q k (BS5400-5)

    Material

    Structural steel 1.0 1.0 (BS5950)

    1.05 (BS5400-5)sa etyfactors

    Concrete 1.5 1.5

    Reinforcement 1.15 1.15

    4

  • 7/27/2019 Lecture 2 by Chiew Sing Ping FOR CIVIL AND STRUCTURE

    5/51

    Material Strength

    Concrete and steel strengths in EC4 and BS5950

    BS5950 EC4

    ConcreteNormal C30 C50 C20/25 C60/75

    Structural steel 355 N/mm 2 460 N/mm 2

    Cube strength Cylinder strength / Cube strength

    The ranges are narrower compared to EC2 (C12/15 C90/105) and EC32

    composite members with very high concrete and steel strengths.

    5

  • 7/27/2019 Lecture 2 by Chiew Sing Ping FOR CIVIL AND STRUCTURE

    6/51

    Concrete Strength

    One of the most noticeable differences in Eurocodes is the wayconcre e s reng s spec e roug ou .

    the cube strength f cu is used.

    ,the cylinder strength f ck is used.

    6

  • 7/27/2019 Lecture 2 by Chiew Sing Ping FOR CIVIL AND STRUCTURE

    7/51

    BS

    Cube strength2

    Will differentstrength gives Converting from

    the concrete

    resistance ? strength toequivalent plastic

    Cylinder strength

    20 N/mm 2

    . cu . .

    = = 2

    No difference!7

  • 7/27/2019 Lecture 2 by Chiew Sing Ping FOR CIVIL AND STRUCTURE

    8/51

    Steel Strength

    EC3 has additional ductility requirements compared toBS5950 in terms of stress ratio, elongation and strainratio.

    Normal strength steel high strength steel

    f u/f y 1.10

    f u/f y 1.05 (EC3-1-12)

    f /f 1.10 UK NA to EC3-1-12 less than 15%

    Elongation at failure not less than

    10%u y y

    stain u 15 y

    8

  • 7/27/2019 Lecture 2 by Chiew Sing Ping FOR CIVIL AND STRUCTURE

    9/51

    ProblemSome product standards only have requirements on the nominal yieldand tensile strengths, or their minimum values. The stress ratio calculatedaccor ng to t ese nomna va ues cannot comp y w t t e uct tyrequirement.

    Standard Grade omna y estrength (MPa) omna ens estrength (MPa) Stress ratio

    AS 1397.

    G550 550 550 1.00

    AS 1595 CA 500 500 510 1.02

    EN 10326 S550GD 550 560 1.02

    ISO 4997 CH550 550 550 1.00

    AS 1397: Steel sheet and strip hot-dip zinc-coated or aluminium/zinc-coatedAS 1595: Cold-rolled, unalloyed, steel sheet and strip

    -ISO 4997: Cold-reduced carbon steel sheet of structural quality

    9

  • 7/27/2019 Lecture 2 by Chiew Sing Ping FOR CIVIL AND STRUCTURE

    10/51

    Profiled Steel Sheeting

    Most types of profiled steel sheeting are manufactured from.

    10

  • 7/27/2019 Lecture 2 by Chiew Sing Ping FOR CIVIL AND STRUCTURE

    11/51

    Headed Stud Shear Connector

    In BS 5950, the resistances of headed studs in solid slabare given for various combinations of height, diameter andconcrete strength but the physics behind these numbers are

    not explained.

    n , e res s ance s expresse n wo equa onsgoverned by the strength of concrete and steel.

    11

  • 7/27/2019 Lecture 2 by Chiew Sing Ping FOR CIVIL AND STRUCTURE

    12/51

    Characteristic Resistance Q k of Headed Studs inNormal Concrete (BS 5950-3.1 Table 5)

    mens ons o ea e s u s ear connectors

    arac er s c s reng oconcrete (f cu )

    Nominal shank Nominal As-welded diameter

    (mm)

    height(mm)

    height(mm)

    N/mm 2 N/mm 2 N/mm 2 N/mm 2

    25 100 95 146 154 161 168

    22 100 95 119 126 132 13919 100 95 95 100 104 109

    16 75 70 70 74 78 82

    13 65 60 44 47 49 52

    12

  • 7/27/2019 Lecture 2 by Chiew Sing Ping FOR CIVIL AND STRUCTURE

    13/51

    Design Resistance of Headed Studs in Solidoncre e a

    shown here as (1) and (2).

    2u

    Rd V

    0.8 4 f d P

    = (1)

    2

    ck cm0.29 d f E = = schV

    .d

    The two equations represent the 2 possible failure modes:i failure in the shank of headed stud and ii failure in concrete.

    13

  • 7/27/2019 Lecture 2 by Chiew Sing Ping FOR CIVIL AND STRUCTURE

    14/51

    steel failure

    Failure in the headed stud

    - concretecrushes

    14Failure in concrete

  • 7/27/2019 Lecture 2 by Chiew Sing Ping FOR CIVIL AND STRUCTURE

    15/51

    Comparison of Characteristic Resistances invar ous es gn o es

    arac er s c res s ance o s ear s u , RkHeaded shear studs embedded Characteristic strength of concrete (N/mm 2)

    n so concre e s a onormal weight concrete 25 30 35 40

    : ar :

    BS5950: Part 3.1: 2010 95 100 104 109EC4: Part 1.1: 2004 81.0 92.1 100.6 102.1

    o es: omna s an ame er = mm

    Nominal height = 100mm while as-welded height = 95mm

    .

    15

  • 7/27/2019 Lecture 2 by Chiew Sing Ping FOR CIVIL AND STRUCTURE

    16/51

    Characteristic Resistance of Stud (EC4 and BS5950)

    160

    120

    140BS (d=22mm, h=100mm)EC (d=22mm, h=100mm)

    100 BS (d=19mm,h=100mm)EC (d=19mm, h=100mm)BS ( d=16mm, h=75mm) ( k

    N )

    60

    EC (d=16mm, h=75mm) P

    R k

    40

    0

    Concrete strength (N/mm 2)

    16

  • 7/27/2019 Lecture 2 by Chiew Sing Ping FOR CIVIL AND STRUCTURE

    17/51

    In general, the resistance of headed stud shear connectorsdetermined by EC4 is lowe than BS5950.

    more headed studs are needed in EC4 design !

    17

  • 7/27/2019 Lecture 2 by Chiew Sing Ping FOR CIVIL AND STRUCTURE

    18/51

    Design Resistance of Headed Studs inompos e a

    The design resistance of headed stud connector in compositeslab with profiled steel sheeting is more complex than in a solidslab. It is influenced by the following factors:

    The direction of the ribs relative to direction of span of thecom osite beam;

    The mean breadth b0 and depth hp of profiled steel sheeting;

    The diamete d and height h sc of the headed shea stud;

    The numbe n of the headed studs in one trou h;

    Whether or not a headed stud is central within a trough.

    18

  • 7/27/2019 Lecture 2 by Chiew Sing Ping FOR CIVIL AND STRUCTURE

    19/51

    Reduction Factor k

    Design shear resistance is taken as the resistance in a solid slabt

    b 0 b 0

    s c c

    h p

    p /

    2

    h P

    h

    sc07.0 hb maxt,

    p pr

    t

    hhn

    - . . . -and 0.63 and 0.34 for open trough profiles

    For the EC4 these values are about 17% lower than the BS for re-entrant profiles, but about 40% higher than the BS for open trough profiles.19

  • 7/27/2019 Lecture 2 by Chiew Sing Ping FOR CIVIL AND STRUCTURE

    20/51

    Upper Limit k t,max for the Reduction Factor k tGenerally, most profiled sheet sheeting is designed such that their limitingvalue dominates , so the reduction factor is independent of the geometr

    EC4 BS 5950-3.1

    steelsheeting

    connectors per

    trough

    of sheet

    (mm)Stud not exceeding20mm in diameter and

    welded through

    Stud notexceeding19mm in

    profiled steel sheeting diameter

    - n r=11.0 0.85

    1.0 trough

    . .

    n r=21.0>1.0

    0.700.8 0.8

    Opentrough

    nr=1 .

    >1.0

    .

    1.00.82

    = 1.0 0.70> . .

    For open trough profiles , the reduction factor in EC4 BS5950or re-en ran roug pro es , e re uc on ac or n

    20

  • 7/27/2019 Lecture 2 by Chiew Sing Ping FOR CIVIL AND STRUCTURE

    21/51

    Characteristic resistance of shear stud P kN

    Headed shear studs incom osite slab with rofiled

    Characteristic strength of concrete f cu(N/mm 2)

    steel sheeting 25 30 35 40

    BS5950: Part 3:2010

    e-en ran

    Open trough 77.9 82 85.3 89.4

    EC4: Part 1.1: 2004 68.9 75.5 85.5 86.8

    n =1

    Notes: Nominal shank diameter = 19mmNominal height = 100mm while as-welded height = 95mm

    The resistance of shear stud in composite slab determined in EC4 is upto 27% lower than that given in BS 5950.

    21

  • 7/27/2019 Lecture 2 by Chiew Sing Ping FOR CIVIL AND STRUCTURE

    22/51

    Top-Down Construction

    piles installed during the foundation stage

    22

  • 7/27/2019 Lecture 2 by Chiew Sing Ping FOR CIVIL AND STRUCTURE

    23/51

    Installation of a kingpost into the barrette pile

    23

  • 7/27/2019 Lecture 2 by Chiew Sing Ping FOR CIVIL AND STRUCTURE

    24/51

    KingPost in column

    bars

    24Casting column head

    C l i h

  • 7/27/2019 Lecture 2 by Chiew Sing Ping FOR CIVIL AND STRUCTURE

    25/51

    Column Design ApproachCross section resistance (yielding)

    Resistance to com ression Resistance to momentReduced moment resistance under com ressive force i.e. interaction between compression and bending

    Member bucklin resistance Axial buckling resistance

    interaction between compression and bending

    LBAF cr

    Types of elastic analysisand design

    25 e

    Si lifi d M h d (EC4 Cl 6 7 3 4)

  • 7/27/2019 Lecture 2 by Chiew Sing Ping FOR CIVIL AND STRUCTURE

    26/51

    Simplified Method (EC4 Clause 6.7.3.4)

    Desi n Conce ts

    Design based on the

    Axial(similar to pure steel column)

    Design based on second-order

    analysis with equivalent member e 0mper ec on s mp e me o

    member incombined Design based on second orderanalysis with equivalent membe

    and bending Imperfection (simplified method)e 0

    26

    A i l C i R i

  • 7/27/2019 Lecture 2 by Chiew Sing Ping FOR CIVIL AND STRUCTURE

    27/51

    Axial Compression Resistance

    Compression resistance of composite column

    A A A N ++= ssccya p ,

    = + +

    steel concrete reinforcement

    yk a ck c/ f sk s/ f

    27

    A i l B kli R i t

  • 7/27/2019 Lecture 2 by Chiew Sing Ping FOR CIVIL AND STRUCTURE

    28/51

    Axial Buckling Resistance

    N .

    Rd pl, N

    The buckling reduction factorEC3 a roach Plastic resistance

    0.1

    12 =

    a1.0

    x Euler buckling-+

    ( ) 22.0-15.0 ++= c

    Rk pl, N = 0.0 1.0 2.0cr

    28

  • 7/27/2019 Lecture 2 by Chiew Sing Ping FOR CIVIL AND STRUCTURE

    29/51

    Bucklin Curve - EC3

    29

    B kli C EC4

  • 7/27/2019 Lecture 2 by Chiew Sing Ping FOR CIVIL AND STRUCTURE

    30/51

    Buckling Curve EC4

    Cross-section Limits Axis of Buckling curveuc ng S235 - S460

    Concrete encased sectiony-y b

    z-z c

    Partially concrete encased y-y b

    z-z c

    Concrete filled circular and s 3% any a

    s

    For steel column, the buckling curve is related to steel section and steelstrength.

    For composite column, the buckling curve is related to the cross-section..

    30

    Example Comparison of Design Approach

  • 7/27/2019 Lecture 2 by Chiew Sing Ping FOR CIVIL AND STRUCTURE

    31/51

    Example - Comparison of Design Approach

    Design based on Design based on seconduc ng

    curve

    equivalent member

    imperfection

    Ed

    Buckling curve bMember L/200 e

    Resistance of

    axial N = 4320 kN N = 4108 kNcompression

    Comparison 1.05Rd(X) Rd(e0) Ed

    Note: design based on the use of member imperfection e 0 leads to

    the EC3 buckling curve approach.Design data:

    31

    f y=355N/mm 2, f ck =25N/mm 2, f sk =500N/mm 2,Cross-section: 350mm 350mm, steel section: 254 254 UC73.Column length: 5.0m, 4 bars of 20mm diameter

    Example Comparison of Design Approach

  • 7/27/2019 Lecture 2 by Chiew Sing Ping FOR CIVIL AND STRUCTURE

    32/51

    Example - Comparison of Design Approach

    Design based on the EC3 Design based on second order analysisbuckling curve approach with equivalent member imperfection

    approachRd N Rd e N

    Rd( ) pl,Rd = N N N0Ed,max Rd(e ) 0= k N e

    The maximum resistance can be0.1

    -

    122

    +

    =

    Npl,RdEd,max M pl,Rd M

    ( ) 22.0-15.0 ++= 0Rd(e ) 0 M pl,Rd =kN e M Rd(e0)

    Npm,Rd

    cr

    Rk pl,

    N N =

    0 pl,Rd Rd (e )

    pl,Rd pm,Rd

    -= -

    N N

    N N M

    Second order effect factor k:2

    ef,II( )

    =

    EI

    Mpl,Rd Mpl,Rd

    1=k Easier approach !

    32

    cr,e 2cr L0Rd(e ) cr,eff -

    Resistance of Members in combined

  • 7/27/2019 Lecture 2 by Chiew Sing Ping FOR CIVIL AND STRUCTURE

    33/51

    ompress on an en ng The EC3 bucklin curve a roach can be ado ted focomposite column under axial compression, however, thisapproach is not suitable fo composite column subjected to

    axial compression and bending moment.

    In design of slender RC column, an accidental eccentricity of

    the axial load in the column is introduced to calculate themaximum moment at mid-height of the column.

    Simila to slende RC column, equivalent initial bowimperfections (member imperfections) are used in the design of compos e co umn o s mp ca on.

    33

    Bending Moment due to Member Imperfection

  • 7/27/2019 Lecture 2 by Chiew Sing Ping FOR CIVIL AND STRUCTURE

    34/51

    Bending Moment due to Member Imperfection

    NEd 0

    design axial load NEd on a composite column,.

    The design bending moment for the compositee 0 co umn engt cons ere ot secon -or e

    effects of end moment and imperfection is given

    0Ed 2Ed 1Ed.max e N k M k M +=

    NEd k1, k 2 are the factors of second order effects

    Ed cr,eff

    =1- /

    k N N

    re a e o en momen ra o

    34

    Member Imperfections for Composite Column

  • 7/27/2019 Lecture 2 by Chiew Sing Ping FOR CIVIL AND STRUCTURE

    35/51

    p p

    Cross-sectionAxis of

    bucklingBuckling

    curveMember

    imperfection (e )Concrete encased section y-y b L/200

    -y

    Partially concrete encasedSection

    y-y b L/200z

    z-z c L/150

    Circular and rectangular y-y a L/300

    z

    o ow sec onz-z b L/200

    Circular hollow section with

    zy

    additional I-section

    -

    z-z b L/200zy

    Partially encased H sectionwith crossed H section

    any b L/200y

    35

    Improvement in the Design of Column in

  • 7/27/2019 Lecture 2 by Chiew Sing Ping FOR CIVIL AND STRUCTURE

    36/51

    p gom ne ompress on an en ng

    Compared to EC4 (1994), the simplified method for

    second order analysis and equivalent member (initial bow)im erfection which takes into account the effects of residualstresses and geometrical imperfections.

    method for composite columns, the scope of the simplified.

    36

    Ed M 1 Edk M

  • 7/27/2019 Lecture 2 by Chiew Sing Ping FOR CIVIL AND STRUCTURE

    37/51

    Ed 1 Ed pl,Rd

    The influence of imperfection is takeninto account indirectly in the interaction

    . d relevant amount to account for themoment due to the member

    (a) EC4: 1994 imperfection.

    Ed, max M 1 Ed 2 Ed 0k M k N e+d pl,Rd

    The member im erfection can be takeninto account in the global analysis andhence it is not necessary to allow for

    37e mper ec on n e ana ys s o e

    interaction curve.(b) EC4: 2004

    Design of Composite Beam

  • 7/27/2019 Lecture 2 by Chiew Sing Ping FOR CIVIL AND STRUCTURE

    38/51

    Design of Composite Beam

    Nc,f

    p

    The concrete slab works best in com ression while the steel section

    ,

    works best in tension; hence, a large moment resistance is generatedas a force couple.

    Resistance mobilization in both the concrete slab and the steel sectionis limited b the shear connection alon the concrete interface.

    38

    Failure Modes of Composite Beam

  • 7/27/2019 Lecture 2 by Chiew Sing Ping FOR CIVIL AND STRUCTURE

    39/51

    p

    IV

    IV

    I-I resistance to sagging moment and vertical shearII-II resistance to hogging moment and shear and M-V interactionIII-III shear connection @ the steel concrete interfaceIV-IV lateral torsional buckling

    - ong u na s ear o e concre e ange

    39

    Lateral Torsional Buckling Resistance

  • 7/27/2019 Lecture 2 by Chiew Sing Ping FOR CIVIL AND STRUCTURE

    40/51

    g

    In BS5950-3.1, no equation is provided to calculate thelateral torsional buckling resistance of continuous compositebeam under hogging moment over the internal support.

    When checking LTB, the methods given in BS5950-1.

    ,with steel beam in EC3.

    40

    BS5950-3.1 EC4

  • 7/27/2019 Lecture 2 by Chiew Sing Ping FOR CIVIL AND STRUCTURE

    41/51

    b b x p S =

    Rd LTRd b, =1=

    Where pb is determined by TB With:

    2

    LT LT LT + TB t t

    0.5

    LTcr M

    =( ) ( )

    st 2 2

    s

    4 /=

    1+ 2 / +0.05 /

    a hv

    a h x ( ) ( )2 2cr c 4 a at s a afz/ / M k C L G I k L E I = + (EC4)

    0.522

    cr 1 2 2+w cr T z

    cr z z

    M C L I EI

    =

    (EC3)

    EC4 EC3 BS5950-3.1 EC4 /BSRatioEC4/EC3

    Ratio

    41a era - ors ona

    buckling 546 kNm 531 kNm 479 kNm 1.14 1.03

    Elastic Critical Moment

  • 7/27/2019 Lecture 2 by Chiew Sing Ping FOR CIVIL AND STRUCTURE

    42/51

    Inverted- U frame ABCD resisting lateral-torsional buckling

    , cr so-called continuous inverted U-frame model.

    The model iven in EC4 takes into account the lateral dis lacement of thebottom flange causing bending of the steel web and the rotation of the topflange that is resisted by bending of the concrete slab.

    ( ) ( )1/2

    2 2cr c 4 a at s a afz/ / M k C L G I k L E I = +

    42

    Composite Slab

  • 7/27/2019 Lecture 2 by Chiew Sing Ping FOR CIVIL AND STRUCTURE

    43/51

    p

    TrapezoidalOpen Trough (Trapezoidal)

    Re-entrant

    Possible modes of failure:

    Moment failure near mid-span regionDebonding within longitudinal shear span along the interface between

    43

    concrete slab and decking, i.e. shear bond ailure critical

    Longitudinal Shear

  • 7/27/2019 Lecture 2 by Chiew Sing Ping FOR CIVIL AND STRUCTURE

    44/51

    g

    How reliable is the shear bond alon the interface between

    concrete and profiled sheeting ?

    - non ductile failure, hence not so reliable.

    Mechanical interlocking due to indentations or

    - ductile failure with rational provision, hence morereliable.

    44

    Longitudinal Shear

  • 7/27/2019 Lecture 2 by Chiew Sing Ping FOR CIVIL AND STRUCTURE

    45/51

    End slip

    es se up

    45

    m-k Method

  • 7/27/2019 Lecture 2 by Chiew Sing Ping FOR CIVIL AND STRUCTURE

    46/51

    BS5950-4:

    p pbd mAV k = +

    r ps ss r cu

    m A B d V k f

    = + Concretestren th,vs s

    bL

    s v.

    m= 163.26

    m= 172.45k= 0.2491

    k= 0.0312

    46

    Comparison of Longitudinal Shear

  • 7/27/2019 Lecture 2 by Chiew Sing Ping FOR CIVIL AND STRUCTURE

    47/51

    EC4 BS5950-4Short span Long span Short span Long span

    . .

    k 0.2491 0.0312

    -resistance

    V (kN)

    79.3 60.1 74.3 56.2

    ,

    Test Short span 81.2 kN Long span 61.6 kN

    BS5950 provides a more conservative value for longitudinal shear resistance

    47

    Vertical Shear

  • 7/27/2019 Lecture 2 by Chiew Sing Ping FOR CIVIL AND STRUCTURE

    48/51

    BS 5950-4 EC4

    1/3

    v,Rd Rd,c 1 ck 1 pc w p

    v Rd min min 1 c wV v k b d = +

    v b s c

    1/3 1/31/4s cu1000.79 400=

    A f c

    m v 25b d d 3/ 2 1/2min ck 0.035v k f =

    BS 5950-4 EC4 Experiment

    153.6 kN107.8 kN118.7kN

    EC4 provides a more conservative value for vertical shear resistance

    48

    Punching Shear

  • 7/27/2019 Lecture 2 by Chiew Sing Ping FOR CIVIL AND STRUCTURE

    49/51

    BS 5950-4 EC4

    ( ) p s p cCritical perimeter -V D D v= p,Rd p p Rd V C d v=1/3

    1/31/4s cu

    c1000.79 400=

    25 A f v

    b d d 3/ 2 1/20.035v k =

    Rd Rd,c 1 ck min100v C k f v = m n c

    ( ) ( ) p c p f p f p c2 2 2 2 2 2 2C h b h a h d h = + + + + + ( ) ( )s p sCritical perimeter = 4 - +4 +4 length of load area D D d

    BS 5950-4 EC4 Experiment

    186 kN139 kN108kN

    -

    49

    Conclusions

  • 7/27/2019 Lecture 2 by Chiew Sing Ping FOR CIVIL AND STRUCTURE

    50/51

    1. Composite members with high strength steel and concreteou s e e scope o .2. Common grades of profiled steel sheeting cannot meet

    ,downgraded.

    .generally lower in EC4 compared to BS5950; Important to

    .4. For composite columns, the EC4 buckling curves are

    .

    However, unlike EC3, no special consideration for

    50

    Conclusions

  • 7/27/2019 Lecture 2 by Chiew Sing Ping FOR CIVIL AND STRUCTURE

    51/51

    5. The simplified design approach using second orderanalysis and equivalent membe imperfection without anyneed for member buckling resistance check is mucheas e o compos e co umn n com ne compress onand bending moment.

    . prov es gu ance o a era - ors ona uc ng c ecfor continuous composite beams taking into account the

    .7. EC4 also provides clear guidance for prototype testing

    profiled steel sheeting.