lecture-09 introduction to earthquake resistant analysis
TRANSCRIPT
1
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Lecture-09
Introduction to Earthquake Resistant Analysis & Design of
RC Structures (Part I)
1
By: Prof Dr. Qaisar Ali
Civil Engineering Department
UET Peshawar
www.drqaisarali.com
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Topics
Introduction
Earthquake Design Philosophy
Seismic Loading Criteria
Analysis for Seismic Loads
Approximate Lateral Load Analysis
References
2
2
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Introduction
Earth’s Interior
3
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Earthquake results from the sudden movement of
the tectonic plates in the earth’s crust.
4
Introduction
3
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Effect of Earthquake
The movement, taking place at the fault lines, causesenergy release which is transmitted through the earth inthe form of waves. These waves reach the structurecausing shaking.
5
Introduction
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Seismic Events around the globe
Mostly takes place at boundaries of Tectonic plates
6
Dots represents an earthquake
Introduction
4
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Types of Waves Generated Due to Earthquake
7
Body Waves Surface Waves
Introduction
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Displacement due to Earthquake
8
Introduction
5
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Horizontal and Vertical Shaking
Earthquake causes shaking of the ground in all three directions.
The structures designed for gravity loading (DL+LL) will benormally safe against vertical component of ground shaking.
The vertical acceleration during ground shaking either adds toor subtracts from the acceleration due to gravity.
9
Introduction
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Horizontal and Vertical Shaking
The structures are normally designed for horizontal shakingto minimize the effect of damages due to earthquakes.
10
Introduction
6
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Earthquake Types with respect to Depth of Focus
Shallow
Depth of focus varies between 0 and 70 km.
Deep
Depth of focus varies between 70 and 700 km.
11
Introduction
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Earthquake characteristics with respect to distancefrom epicenter
0.05 ≤ T ≤ 0.320 Hz ≥ f ≥ 3.33 Hz
Low period & high frequency field
0.3 ≤ T ≤ 1.0 sec3.33 Hz ≥ f ≥ 1 Hz
1.0 ≤ T ≤ 10 sec
25 km
Large period & low frequency field
Moderate period & low frequency field
Epicenter
1 Hz ≥ f ≥ 0.1 Hz
Near Field: 0 to 25 km
Intermediate Field: 25 to 50 km
Far Field: Beyond 50 km
12
Introduction
7
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Resonance risk for structures w.r.t near, intermediateand far field earthquakes
The natural time period of a structure is its important characteristicto predict behavior during an earthquake of certain time period(Resonance phenomenon).
For a particular structure, the natural time period is a function ofmass and stiffness {T = 2p√(m/k)}
“T” can be roughly estimated from: T = 0.1 × number of stories
13
Introduction
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Resonance risk for structures w.r.t near, intermediateand far field earthquakes
Low rise Structure
(upto 3 stories)
Epicenter
Medium rise Structure
(upto 5 stories)
High rise Structure
(Above 5 stories)
14
Introduction
8
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Earthquake Recording
Seismograph
Using multiple seismographsaround the world, accuratelocation of the epicenter of theearthquake, as well as itsmagnitude or size can bedetermined.
Working of seismograph shownin figure.
15
Introduction
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Earthquake Recording
Richter Scale
In 1935, Charles Richter (US)developed this scale.
The Richter scale is logarithmic,So, a magnitude 5 Richtermeasurement is ten timesgreater than a magnitude 4;while it is 10 x 10, or 100 timesgreater than a magnitude 3measurement.
16
Introduction
9
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Earthquake Recording
Some of the famous
earthquake records
17
Introduction
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Earthquake Occurrence
18
Introduction
10
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Seismic Zones
19
Introduction
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Importance of Architectural Features
The behavior of a building duringearthquakes depend critically on its overallshape, size and geometry, in addition tohow the earthquake forces are carried to theground.
20
Introduction
11
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Importance of Architectural Features
At the planning stage, architects and structural engineers mustwork together to ensure that the unfavorable features are avoidedand a good building configuration is chosen.
21
Introduction
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Other Undesirable Scenarios
22
Introduction
12
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Soft Storey
23
Introduction
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Earthquake Design Philosophy
Performance level
24
13
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Building Code of Pakistan
In Pakistan, the design criteria for earthquake loading are basedon design procedures presented in chapter 5, division II ofBuilding Code of Pakistan, seismic provision 2007 (BCP, SP2007), which have been adopted from chapter 16, division II ofUBC-97 (Uniform Building Code), volume 2.
Seismic Loading Criteria
25
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Lateral Force Determination Procedures
The total design seismic force imposed by an earthquake onthe structure at its base is referred to as base shear “V” in theUBC-97.
The design seismic force can be determined based on:
Dynamic lateral force procedure [sec. 1631, UBC-97 or sec. 5.31, BCP-2007].
Static lateral force procedure [sec. 1630.2, UBC-97 or Sec. 5.30.2, BCP 2007],
Seismic Loading Criteria
26
14
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Dynamic Lateral Force Procedure
UBC-97 section 1631 include information on dynamic lateral forceprocedures that involve the use of:
Time history analysis.
Response spectrum analysis.
The details of these methods are presented in sections 1631.5and 1631.6 of the UBC-97.
Seismic Loading Criteria
27
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Dynamic Lateral Force Procedure
Time History Analysis (THA)
T
Ground acceleration
T
LateralDisplacement
Seismic Loading Criteria
28
15
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Dynamic Lateral Force Procedure
Response Spectrum Analysis (RSA)
T
a (ft/sec2)
T
Response
a (ft/sec2)
T
a (ft/sec2)
T
Response
Response
Ts1 = 0.3 sec
Ts2 = 1.0 sec
Ts3 = 2.0 sec
D1
D2
D3
(Ts1,D1)
(Ts2,D2)
(Ts3,D3)
Structural Time period
Peak Response
T
T
Seismic Loading Criteria
29
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
UBC-97 Response Spectrum Curve(Acceleration vs. Time period)
Dynamic Lateral Force Procedure
Response Spectrum Analysis (RSA)
Seismic Loading Criteria
30
16
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
=
Static Lateral Force Procedure
Seismic Loading Criteria
31
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Static Lateral Force Procedure
The total design base shear (V) in a given direction can be
determined from the following formula:
V = (CνI/RT) W
Where,
Cν = Seismic coefficient (Table 16-R of UBC-97).
I = Seismic importance factor (Table 16-K of UBC-97 )
R = numerical coefficient representative of inherent over strength andglobal ductility capacity of lateral force-resisting systems (Table 16-Nor 16-P).
W = the total seismic dead load defined in Section 1630.1.1.
Seismic Loading Criteria
32
17
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Static Lateral Force Procedure
The total design base need not exceed [ V = (2.5CaI/R) W ]
Where, Ca = Seismic coefficient (Table 16-Q of UBC-97)
The total design base shear shall not be less than [ V = 0.11CaIW ]
In addition for seismic zone 4, the total base shear shall also notbe less [ V = (0.8ZNνI/R) W ]
Where, Nν = near source factor (Table 16-T of UBC-97);
Z = Seismic zone factor (Table 16-I of UBC-97)
Seismic Loading Criteria
33
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Static Lateral Force Procedure
Steps for Calculation of “V”:
Step 1: Find Site Specific details.
Step 2: Determine Seismic Coefficients
Step 3: Determine Seismic Importance factor “I”
Step 4: Determine “R” factor
Step 5: Determine structure’s time period
Step 6:Determine base shear “V” and apply code maximum andminimum.
Step 7: Determine vertical distribution of “V”.
Seismic Loading Criteria
34
18
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Static Lateral Force Procedure
Steps for Calculation of “V”:
Step 1: Find Site Specific details.
Following list of data needs to be obtained:
Seismic Zone
Soil type
Past earthquake magnitude (required only for highest seismic zone).
Closest distance to known seismic source (required only for highest seismiczone).
Seismic Loading Criteria
35
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Static Lateral Force Procedure
Steps for Calculation of “V”:
Step 1: Site Specific details.
i. Seismic Zone
Source: BCP SP-2007
Seismic Loading Criteria
36
19
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Static Lateral Force Procedure
Steps for Calculation of “V”:
Step 1: Find Site Specific details.
ii. Soil Type
As per UBC code, if soil type is not known, type SD shall be taken.
Seismic Loading Criteria
37
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Static Lateral Force Procedure
Steps for Calculation of “V”:
Step 1: Find Site Specific details.
iii. Past Earthquake magnitude: This is required only for seismic zone 4to decide about seismic source type so that certain additional coefficientscan be determined.
iv. Distance to known seismic zone is also required to determineadditional coefficients for zone 4.
Seismic Loading Criteria
38
20
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Static Lateral Force Procedure
Steps for Calculation of “V”:
Step 2: Determination of Seismic Coefficients.
Cv:
Nv (required only for zone 4):
Seismic Loading Criteria
39
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Static Lateral Force Procedure
Steps for Calculation of “V”:
Step 2: Determination of Seismic Coefficients.
Ca:
Na (required only for zone 4):
Seismic Loading Criteria
40
21
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Static Lateral Force Procedure
Steps for Calculation of “V”:
Step 3: Determination of Seismic Importance Factor.
Seismic Loading Criteria
41
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Static Lateral Force Procedure
Steps for Calculation of “V”:
Step 4: Determination of “R” Factor.
R factor basically reduces base shear “V” to make the systemeconomical. However the structure will suffer some damage as explainedin the earthquake design philosophy.
R factor depends on overall structural response of the structure underlateral loading.
For structures exhibiting good performance, R factor will be high.
Seismic Loading Criteria
42
22
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Static Lateral Force Procedure
Steps for Calculation of “V”:
Step 4: Determination of “R” Factor.
Seismic Loading Criteria
43
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Static Lateral Force Procedure
Steps for Calculation of “V”:
Step 5: Determination of structure’s time period.
Structural Period (By Method A, UBC 97): For all buildings, the value Tmay be approximated from the following formula:
T = Ct (hn)3/4
Where,
Ct = 0.035 (0.0853) for steel moment-resisting frames.
Ct = 0.030 (0.0731) for reinforced concrete moment-resisting frames and eccentrically
braced frames.
Ct = 0.020 (0.0488) for all other buildings.
hn = Actual height (feet or meters) of the building above the base to the nth level.
Seismic Loading Criteria
44
23
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Static Lateral Force Procedure
Steps for Calculation of “V”:
Step 6: Determination of Base Shear (V).
Calculate base shear meeting the following criteria:
0.11CaIW ≤ V = (CνI/RT) W ≤ (2.5CaI/R) W
For zone 4, the total base shear shall also not be less than:
V = (0.8ZNνI/R) W
Seismic Loading Criteria
45
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Static Lateral Force Procedure
Steps for Calculation of “V”:
Step 7: Vertical Distribution of V to storeys.
The joint force at a particular level x of the structure is given as:
Fx = (V – Ft)ωxhx/∑ωihi (UBC sec. 1630.5)
{ i ranges from 1 to n, where n = number of stories }
Ft = Additional force that is applied to the top level (i.e., the roof) in addition to the Fx force at that level.
Ft = 0.07TV {for T > 0.7 sec}
Ft = 0 {for T ≤ 0.7 sec}
Seismic Loading Criteria
46
24
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Static Lateral Force Procedure
Example: Calculation of “V” for E-W interior frame of the given
structure. Structure is located in Peshawar. Soil type is stiff.
25 ft
25 ft
25 ft
25 ft
20 ft
20 ft
20 ft
10 ft
10 ft
10 ft (floor to floor)
SDL = NilLL = 144 psf
SDL = NilLL = 144 psf
SDL = NilLL = 144 psf
fc′ = 4 ksify = 60 ksi
Slab-Beam Frame
Structure
Seismic Loading Criteria
47
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Static Lateral Force Procedure
Example:
E-W interior frame4 spans @ 25′-0″
3 spans @
20′-0″
l2 = 20′
Seismic Loading Criteria
48
25
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
49
Static Lateral Force Procedure
Example:
Step 1: Site specific details.
i. Seismic Zone:
From seismic zoning map of
Pakistan, Peshawar lies in
seismic zone 2B (Z = 0.20)
Seismic Loading Criteria
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Static Lateral Force Procedure
Example:
Step 1: Site specific details.
ii. Soil Type: Stiff soil is classified as SD (stiff soil).
Seismic Loading Criteria
50
26
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Static Lateral Force Procedure
Example:
Step 1: Site specific details.
iii. Past earthquake magnitude: Not determined as it required for zone
4 only.
iv. Distance to known seismic zone: Not determined as it is required
for zone 4 only.
Seismic Loading Criteria
51
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Static Lateral Force Procedure
Example:
Step 2: Determination of Seismic Coefficients.
For seismic zone 2B, only Ca and Cv determination is required.
Seismic Loading Criteria
52
27
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
53
Static Lateral Force Procedure
Example:
Step 3: Determination of Seismic Importance Factor.
I = 1.00 (Standard Occupancy
Structures)
Seismic Loading Criteria
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Static Lateral Force Procedure
Example:
Step 4: Determination of “R” Factor.
R = 8.5 (Concrete SMRF)
Seismic Loading Criteria
54
28
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Static Lateral Force Procedure
Example:
Step 5: Determination of Structure’s time period.
By method A:
T = Ct (hn)3/4
Ct = 0.003; hn = 30 ft
T = 0.003 × (30)3/4 = 0.384 sec
Seismic Loading Criteria
55
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Static Lateral Force Procedure
Example:
Step 6: Determination of base shear (V).
Base Shear (V) = {CvI/RT}W
W (self weight of E-W interior frame + super imposed dead load)
= 613 kips
25 % floor live load will also be added up (for warehouses, see
UBC sec.1630.1.1.)
W = 613 + 0.25 0.144 20×(4×25) = 685 kips
Seismic Loading Criteria
56
29
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Static Lateral Force Procedure
Example:
Step 6: Determination of base shear (V).
V = {CvI/RT}W = {0.40 1.00/ (8.5 0.384)} 685 = 83.94 kips
The total design base need not exceed the following:
V = (2.5CaI/R) W = {(2.5 × 0.28 × 1.00)/ (8.5)} × 685 = 56.41 kips,
The total design base shear shall not be less than the following:
V = 0.11CaIW = 0.11 × 0.28 × 1.00 × 685= 21.098 kips, O.K.
Therefore, V = 56.41 kip (8 % of seismic weight W)
Seismic Loading Criteria
57
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Static Lateral Force Procedure
Example:
Step 7: Vertical distribution of V to storeys.
Fx = (V – Ft)ωxhx/∑ωihi
∑ωihi = 228 ×10 + 228×20 + 228×30 = 13680 kip
F1 = (56.41 – 0) × 228 × 10/ {(13680)} = 9.402 kip
Storey forces for other stories are given in table below:
Table Storey shears.Level
xhx (ft) wx (kip) wxhx (ft-kip) wxhx /(Swihi) Fx (kip)
3 30 228 6840 0.5 28.212 20 228 4560 0.33 18.611 10 228 2280 0.166 9.36
Swihi = 13680 Check SFx =V = 56.18 kip OK
Seismic Loading Criteria
58
30
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Static Lateral Force Procedure
Example (Storey Forces):
Same forces will be obtained for other E-W interior frame because it has
same dimensions and loading conditions as of E-W interior frame
considered.
Half values shall be applied to E-W exterior frames.
Seismic Loading Criteria
59
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Static Lateral Force Procedure
Example (Storey Forces):
Note: Base shear can
also be computed for
complete structure and
then can be divided to
different frames.
25 ft25 ft25 ft25 ft
20 ft
20 ft
20 ft
28.21 kips
18.61 kips
9.36 kips
28.21 kips
18.61 kips
9.36 kips
14.1 kips
9.3 kips
4.68 kips
14.1 kips
9.3 kips
4.68 kips
Seismic Loading Criteria
60
31
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Base Shear using UBC Response Spectra
Example:
Seismic Loading Criteria
Period (sec)
Spectral Acceleration
(g’s)
Ca = 0.28
Cv = 0.4
Ts = Cv/2.5Ca = 0.57 sec
To = 0.2Ts = 0.114 sec
R = 8.5; W = 685 kips
Now, T of given structure = 0.384 sec
At T = 0.384 sec,
Spectral acceleration = 0.7g
V = W × (a/g)/R = 56 kips
Base shear computed here is same as
computed using the static lateral force
procedure.
Ca = 0.28
2.5Ca = 0.7
Cv/T
0.114 0.57
Line at T = 0.384 sec
61
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Seismic Loading Criteria
Automated lateral force procedure of SAP2000
Steps for the given 3D structure are shown next.
62
SAP2000 3D Model (20ft × 15 ft) panelsSeismic Zone: 2B
Soil Type: SDMethod A used for time period calculation
Mass source: SDL only
32
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures63
Seismic Loading Criteria
Static Lateral Force Procedure1. Automated Lateral Force Procedure of SAP2000
It is important to add SDL as Load for masssource with 3rd option selected to avoid load tobe taken two times.
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures64
Seismic Loading Criteria
Static Lateral Force Procedure
Case Study 2: Base shear calculation for E-W direction using
SAP2000 automated lateral load feature and comparison with
results of manually applied lateral loads.
1. Automated Lateral Force Procedure of SAP2000
33
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Analysis for Seismic Loads
Methods of Seismic (lateral load) Analysis
Exact: FEM using SAP 2000, etc.
This method was demonstrated in previous example
Approximate lateral load analysis:
This will be discussed next
65
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
ACI Requirements on Lateral Load Analysis
Unlike ACI 6.4 which allows separate floor analysis for
gravity loads, ACI R6.4 states that for lateral load analysis, a
full frame from top to bottom must be considered.
66
For Lateral LoadFor Gravity Load
Approximate Lateral Load Analysis
34
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Portal Method
This is a method used to estimate the effects of side swaydue to lateral forces acting on multistory building frame.
This method is specialized form of point of inflection method.
67
F3
F2
F1
Side sway (Δ)
Approximate Lateral Load Analysis
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Portal Method
Prepositions:
1. The total horizontal shear in all columns of a given storey is equal and
opposite to the sum of all horizontal loads acting above that storey.
This preposition follows from the requirement that horizontal
forces be in equilibrium at any level.
68
F3
F2
F1
H31 H32
H21 H22
H11 H12
H31 + H32 = F3
H21 + H22 = F3 + F2
H11+ H12 = F3 + F2 + F1
Approximate Lateral Load Analysis
35
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Portal Method
Prepositions:
2. The horizontal shear is the same in both exterior columns. The
horizontal shear in each interior column is twice that in exterior column.
This preposition is due to the fact that interior columns are generally more rigid than
exterior columns (interior column with larger axial load will require larger cross section).
69
H3
H2
F3
F2
F1
H3 2H3 2H3
H2 2H2 2H2
H1 2H1 2H1 H1
6 H3 = F3
or H3 = F3 /6H3 = F3 / 2nWhere n= no. of baysAnd 2H3 = F3 / n
Approximate Lateral Load Analysis
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Portal Method
Prepositions:
3. The inflection points of all members (columns and beams) are located
midway between the joints except for bottom storey.
70
F3
F2
F1
Point of Inflection
2h/3
h/3
Location of P.O.I depends on end restraints:
2h/3 (restraints with more resistance to rotation)
h/3 (restraints with less resistance to rotation)
At base (ideal hinge)
Approximate Lateral Load Analysis
36
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Portal Method Analysis Steps
Step 1: Location of points of inflection on frame using preposition 3.
71
F3
F2
F1
l1 l2 l3
Approximate Lateral Load Analysis
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Portal Method Analysis Steps
Step 2: Determine column shears using proposition 1 and 2.
72
F3
H3ext=F3/2n
F2
F1
l1 l2 l3
H3int=F3/n H3int=F3/n H3ext=F3/2n
H2ext=(F3 + F2)/2n H2int=(F3 + F2)/n H2int=(F3 + F2)/n H2ext=(F3 + F2)/2n
H1int=(F3 + F2 + F1)/n H1ext=(F3 + F2 + F1)/2n H1int=(F3 + F2 + F1)/n H1ext=(F3 + F2 + F1)/2n
n = number of bays
Approximate Lateral Load Analysis
37
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Portal Method Analysis Steps
Step 3a: Determine column moments from statics.
73
F3
F2
F1
l1 l2 l3
H3ext H3int H3extH3int
H2ext H2int H2extH2int
H1ext H1int H1extH1int
h
h
h
M3ext= H3exth/2
M3ext= H3exth/2
M3int= H3inth/2
M3int= H3inth/2
M2ext= H2exth/2
M2ext= H2exth/2
M2int= H2inth/2
M2int= H2inth/2
M1ext= H1exth/3
M1ext= H1ext2h/3
M1int= H1inth/3
M1int= H1int2h/3
M3int= H3inth/2
M3int= H3inth/2
M2int= H2inth/2
M2int= H2inth/2
M1int= H1inth/3
M1int= H1int2h/3
M3ext= H3exth/2
M3ext= H3exth/2
M2ext= H2exth/2
M2ext= H2exth/2
M1ext= H1exth/3
M1ext= H1ext2h/3
Approximate Lateral Load Analysis
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Portal Method Analysis Steps
Step 3b: Determine beam moments from statics.
Beam moments at a joint can be determined from equilibrium. The beam
moments to the left (MBL) and right (MBR) of a joint can be determined
from the following formulae:
MBL= ∑Mcol/m
MBR= ∑Mcol/m
Where,
m = # of connecting beams at a joint.
∑Mcol = summation of column moments at a joint.
74
Approximate Lateral Load Analysis
38
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Portal Method Analysis Steps
Step 3b: Determine beam moments from statics.
75
F3
F2
F1
l1 l2 l3
M3ext
M3int
M2int
Note: The direction of beam moment shall be opposite to the direction of column moment.
M3int
MBL= M3ext/1
MBR= M3int/2
MBL= M3int/2
MBR= (M3int+M2int)/2 MBL= (M3int+M2int)/2
Approximate Lateral Load Analysis
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Portal Method Analysis Steps
Step 3c: Determine beam shear from statics.
As the point of inflection is assumed to lie at mid span, the beam shear
equals beam end moment divided by ½ beam span.
76
Approximate Lateral Load Analysis
39
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Portal Method Analysis Steps
Step 3c: Determine beam shear from statics.
77
F3
F2
F1
l1 l2 l3
MBLMBR
PL=MBL/0.5l1PR=MBR/0.5l1
MBLMBR
PL=MBL/0.5l2 PR=MBR/0.5l2PL PR
PL PR
PL PR
PL PR
PL PR
PL PR
PL PR
Approximate Lateral Load Analysis
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Portal Method Analysis Steps
Step 3d: Determine column axial force from statics.
For a segment (abc for example), the axial force shall be arithmeticsum of beam shears within that segment, but in opposite direction.
Axial force in lower storey shall be the sum of axial force in storeyunder question plus the axial forces in all above stories.
78
F3
F2
F1
l1 l2 l3
PL PRPL PR PR
PL PRPL PR PL PR
PL PRPL PR PL PR
a
b
c
Approximate Lateral Load Analysis
40
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Portal Method Analysis Steps
Step 3d: Determine column axial force from statics.
79
F3
F2
F1
l1 l2 l3
PL3 PR3PL3 PR3 PR3
PL2 PR2PL2 PR2 PL2 PR2
PL1 PR1PL1 PR1 PL1 PR1
PL3 PL3
PL3+PL2
PR3+PL3
Similarly all other column axial forces can be determined
PL3+PL2 +PL1
Approximate Lateral Load Analysis
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Portal Method (Case Study 1)
Lateral load analysis for E-W Interior Frame of given 3D
structure by portal method and its comparison with SAP2000.
The objective of this study is to check the level of accuracy of portal
method.
80
Approximate Lateral Load Analysis
41
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Portal Method (Case Study 1)
Given 3D structure.
25 ft 25 ft 25 ft 25 ft
20 ft
20 ft
20 ft
10 ft
10 ft
10 ft (floor to floor)
SDL = NilLL = 144 psf
SDL = NilLL = 144 psf
SDL = NilLL = 144 psf
fc′ = 4 ksify = 60 ksi
Slab-Beam Frame
Structure
Note: Zone 2BSDL = NilLL = 144 psfSlab = 7″
81
Approximate Lateral Load Analysis
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Portal Method (Case Study 1)
E-W Interior FrameF3 =28.21 kip
l1=25 ft l2=25 ft l3=25 ft
h=10 ft
F2 =18.61 kip
F1 =9.36 kip
h=10 ft
h=10 ft
l4=25 ft
82
Approximate Lateral Load Analysis
42
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Portal Method (Case Study 1)
Step 1: Locate points of inflection.F3 =28.21 kip
l1=25 ft l2=25 ft l3=25 ft l4=25 ft
F2 =18.61 kip
F1 =9.36 kip
For Hinge
83
Approximate Lateral Load Analysis
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Portal Method (Case Study 1)
Step 2: Determine column shear.F3 =28.21 kip
l1=25 ft l2=25 ft l3=25 ft l4=25 ft
F2 =18.61 kip
F1 =9.36 kip
H3ext=F3/2n H3int=F3/n
n = 4
7.05 7.05 3.5
5.85
3.5 7.05
5.8511.7 11.7 11.7
H2ext=(F3 + F2)/2n H2int=(F3 + F2)/n
H1int=(F3 + F2 + F1)/n H1ext=(F3 + F2 + F1)/2n
7.00 14.0 14.0 14.0 7.00
84
Approximate Lateral Load Analysis
43
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Portal Method (Case Study 1)
Step 2: Determine column shear (comparison with SAP).
l1=25 ft l2=25 ft l3=25 ft l4=25 ft
3.5(4)
5.85(7)
7.00(11)
7.05(7)
11.7(13)
14.0(13)
7.05(7)
11.7(12)
14.0(13)
Portal MethodSAP 3D
85
Approximate Lateral Load Analysis
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Portal Method (Case Study 1)
Step 3a: Determine column moments.F3 =28.21 kip
l1=25 ft l2=25 ft l3=25 ft l4=25 ft
F2 =18.61 kip
F1 =9.36 kip
M = H ×h/2 (for all stories except bottom)M = H × h (for bottom storey)
7.05 7.05 3.5
5.85
3.5 7.05
5.8511.7 11.7 11.7
7.00 14.0 14.0 14.07.00
17.5
17.5
29.3
29.3
70 140
58.5
35.25
35.25
58.5
140
58.5
35.25
35.25
58.5
140
58.5
35.25
35.25
58.5
17.5
17.5
29.3
29.3
70
86
Approximate Lateral Load Analysis
44
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Portal Method (Case Study 1)
Step 3a: Determine column moments (comparison with SAP).
l1=25 ft l2=25 ft l3=25 ft l4=25 ft
17.5(28)
17.5(20)
35.25(39)
35.25(33)
35.25(37)
35.25(32)
29.3(45)
29.3(28)
58.5(69)
58.5(62)
58.5(65)
58.5(56)
70(111)
140(133)
140(129)
Portal MethodSAP 3D
87
Approximate Lateral Load Analysis
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Portal Method (Case Study 1)
Step 3b: Determine beam moments.F3 =28.21 kip
l1=25 ft l2=25 ft l3=25 ft l4=25 ft
F2 =18.61 kip
F1 =9.36 kip
MBL= ∑Mcol/m
MBR= ∑Mcol/m
17.5
17.5
29.329.3
70 140
58.5
35.25
35.25
58.5
140
58.5
35.25
35.25
58.5
140
58.5
35.25
35.25
58.5
17.5
17.5
29.329.3
70
17.5 17.5 17.5 17.5 17.5 17.5 17.5 17.5
46.8 46.8 46.8 46.8 46.8 46.8 46.8 46.8
99 99 99 99 99 99 99 99
88
Approximate Lateral Load Analysis
45
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Portal Method (Case Study 1)
Step 3b: Determine beam moments (comparison with SAP).
l1=25 ft l2=25 ft l3=25 ft l4=25 ft
17.5(19)
17.5(16)
17.5(14)
17.5(14)
46.8(46)
46.8(41)
46.8(37)
46.8(37)
99(99)
99(81)
99(70)
99(68)
Portal MethodSAP 3D
89
Approximate Lateral Load Analysis
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Portal Method (Case Study 1)
Step 3c: Determine beam shear.
F3 =28.21 kip
l1=25 ft l2=25 ft l3=25 ft l4=25 ft
F2 =18.61 kip
F1 =9.36 kip
PL= MBL/0.5l
PR= MBR/0.5l
17.5 17.5 17.5 17.5 17.5 17.5 17.5 17.5
46.8 46.8 46.8 46.8 46.8 46.8 46.8 46.8
99 99 99 99 99 99 99 99
1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4
3.74 3.74 3.74 3.74 3.74 3.74 3.74 3.74
7.92 7.92 7.92 7.92 7.92 7.92 7.92 7.92
90
Approximate Lateral Load Analysis
46
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Portal Method (Case Study 1)
Step 3c: Determine beam shear (comparison with SAP).
l1=25 ft l2=25 ft l3=25 ft l4=25 ft
1.4(1.8)
1.4(1.5)
3.74(4.4)
3.74(4)
7.92(9)
7.92(7)
Portal MethodSAP 3D
Approximate Lateral Load Analysis
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Portal Method (Case Study 1)
Step 3d: Determine column axial loads.F3 =28.21 kip
l1=25 ft l2=25 ft l3=25 ft l4=25 ft
F2 =18.61 kip
F1 =9.36 kip
1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4
3.74 3.74 3.74 3.74 3.74 3.74 3.74 3.74
7.92 7.92 7.92 7.92 7.92 7.92 7.92 7.92
1.4 0 0 0
0 0 0
0 0 0
5.14
13.06
1.4
5.14
13.06
92
Approximate Lateral Load Analysis
47
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Portal Method (Case Study 1)
Step 3d: Determine column axial loads (comparison with SAP).
l1=25 ft l2=25 ft l3=25 ft l4=25 ft
1.4(2)
13.06(17)
5.14(7)
0(-0.5)
0(-1.4)
0(-4.4)
0(0)
0(0)
0(0)
Portal MethodSAP 3D
93
Approximate Lateral Load Analysis
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Approximate Lateral Load Analysis
l1=20 ft l2=20 ft l3=20 ft l4=20 ft
16(16)
16(13)
31(22)
31(20)
26(26)
26(19)
52(38)
52(36)
61(68)
123(77)
Portal MethodSAP 3D
Portal Method (Case Study 1)
Similar comparison for 20 × 15 ft structure is shown below:
94
48
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Approximate Lateral Load Analysis
l1=20 ft l2=20 ft l3=20 ft l4=20 ft
16(12)
16(9)
16(8.5)
16(8)
41(29)
41(25)
41(22)
41(22)
87(64)
87(50)
87(43)
87(40)
Portal MethodSAP 3D
Portal Method (Case Study 1)
Similar comparison for 20 × 15 ft structure is shown below:
95
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Portal Method (Case Study 2)
Lateral Load Analysis of a frame corresponding to seismic
demand in seismic zones 1 to 4 using Portal Method.
96
Approximate Lateral Load Analysis
49
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Portal Method (Case Study 2)
20 ft 20 ft 20 ft 20 ft
15 ft
15 ft
15 ft
10.5 ft
10.5 ft
10.5 ft (floor to floor)
SDL = 40 psfLL = 60 psf
SDL = 40 psfLL = 60 psf
SDL = 40 psfLL = 60 psf
fc′ = 3 ksify = 40 ksi
Slab-Beam Frame
Structure
97
Approximate Lateral Load Analysis
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Portal Method (Case Study 2)
Zone 1 (Bending moments)
Ca = 0.12Cv = 0.18R = 8.5V = 20.04 kips
98
Approximate Lateral Load Analysis
50
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Portal Method (Case Study 2)
Zone 2A (Bending moments)
Ca = 0.22Cv = 0.32R = 8.5V = 36.74 kips
99
Approximate Lateral Load Analysis
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Portal Method (Case Study 2)
Zone 2B (Bending moments)
Ca = 0.28Cv = 0.40R = 8.5V = 46.76 kips
100
Approximate Lateral Load Analysis
51
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Portal Method (Case Study 2)
Zone 3 (Bending moments)
Ca = 0.36Cv = 0.54R = 8.5V = 60.11 kips
101
Approximate Lateral Load Analysis
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Portal Method (Case Study 2)
Zone 4 (Bending moments)
Ca = 0.44Cv = 0.64R = 8.5V = 73.47 kips
102
Approximate Lateral Load Analysis
52
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Portal Method (Case Study 2)
Comparison (Interior Negative Beam Moment)
Top
Intermediate
Bottom
103
Approximate Lateral Load Analysis
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Portal Method (Case Study 2)
Comparison (Column Moment)
Top
Intermediate
Bottom
104
Approximate Lateral Load Analysis
53
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
References
ACI 318-14
UBC-97
BCP SP-2007
Earthquake tips from IITK.Intermediate
Bottom
105
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
The End
106