leader in iaq presents advanced, state of the … · total air quality monitor contro zone cz8 •...

8
RUKS ENGINEERING LTD LEADER IN IAQ PRESENTS ADVANCED, STATE OF THE ART, REAL TIME, TOTAL AIR QUALITY MONITOR CONTROZONE CZ8 CONTROZONE CZ8 Track Multi Parameters Simultaneously; Total VOC, CO 2 , CO, Environment Ozone, Temperature, RH Continuous 24/7 display on 5.7 inch, Color, High Resolution, Programmable, Touch Screen LCD, or 4 Line x 20 Characters LCD with Membrane Switch Keypad Upto 32 Monitors connected to LAN. Access all features remotely Suitable for BacNet, ModBus, or EtherNet View Graphs and Reports of all or selected Parameters View Alarm Reports Time History and Real Time Records User selectable Upper and Lower Range, and Alarm Level User selectable Output Signal upto Five Parameters, 0-10 VDC, 0-5 VDC, 4-20mA Five NO Dry Contacts - User Assignable Eliminate stand alone Thermostat, Humidistat, and CO 2 Monitors. 2.0 USB, RS232, and Ethernet Outputs Standalone Mini BMS (BAS) Comprehensive, One Piece Air Quality Monitor, Energy Reduction Device, and Mini BMS (BAS) Cost effective as One Monitor Does All Various Models to Suit all Budgets & Needs CZ8 PD CZ8 AD CZ8 LAN CZ8 LAN CZ8 LAN

Upload: hoangkhuong

Post on 12-Apr-2018

213 views

Category:

Documents


0 download

TRANSCRIPT

RUKS ENGINEERING LTDLEADER IN IAQ PRESENTS

ADVANCED, STATE OF THE ART, REAL TIME, TOTAL AIR QUALITY MONITOR

CONTROZONE CZ8CONTROZONE CZ8

• Track Multi Parameters Simultaneously; • Total VOC, CO2, CO, Environment Ozone, Temperature, RH• Continuous 24/7 display on 5.7 inch, Color, High Resolution, Programmable, Touch Screen LCD, or 4 Line x 20 Characters LCD with Membrane Switch Keypad• Upto 32 Monitors connected to LAN. Access all features remotely• Suitable for BacNet, ModBus, or EtherNet • View Graphs and Reports of all or selected Parameters• View Alarm Reports• Time History and Real Time Records

• User selectable Upper and Lower Range, and Alarm Level• User selectable Output Signal upto Five Parameters, 0-10 VDC, 0-5 VDC, 4-20mA• Five NO Dry Contacts - User Assignable• Eliminate stand alone Thermostat, Humidistat, and CO2 Monitors. • 2.0 USB, RS232, and Ethernet Outputs• Standalone Mini BMS (BAS)• Comprehensive, One Piece Air Quality Monitor, • Energy Reduction Device, and Mini BMS (BAS)• Cost effective as One Monitor Does All• Various Models to Suit all Budgets & Needs

CZ8 PD CZ8 ADCZ8 LAN

CZ8 LAN CZ8 LAN

18 Automatic Road, Unit 18, Brampton, Ontario, L6S 5N5, Canada. Toll Free: 1877 RUKSENG (1 877 785 7364), Tel: (905) 789 9652, Fax: (905) 789 0381, [email protected] www.rukseng.com

2

MODE OF OPERATION

Comprises Sensor Section, common to all Models,and choice of many Monitor Sections and Communication protocol to suit all Budgets andNeeds - PD, AD, LAN, BacNet, ModBus, EtherNet.

Six Individual sensors provide continuous andrapid response to changing environmental conditions of TVOC/Odor, CO, CO2, EnvironmentOzone, Temperature, and RH. Each Sensor provides 0-10 VDC, 0-5 VDC or 4-20 mA (UserSpecified). Has 5 NO Dry Contacts, user assignable to any IAQ parameter. Provides accurate, precise, and timely input to operateIAQ Improvement and Energy Reduction Devices.Results in near perfect Indoor Air Quality, withoptimum savings in operating cost. Pays for itselfin few years.

Monitor Section receives input signals from Sensor Section, and displays readings in quantifiable units on LCD Screen.

PD - 5.7 Inch Color, Graphics, Touch Screen, UserProgrammable Monitor, for high end applications.AD - 4 Line x 20 Characters, Back Lit Monochrome LCD, Programmable Touch PadMembrane Switch, for Mid Price Range applications.LAN - Blank Cover with Pilot Lamp to indicatePower On. Connects on LAN for display and all

operating functions.BacNet, ModBus, or EtherNet communicationprotocol.

ControZone CZ8 is fully factory assembled. Suitable for use as IAQ Monitor or for IndustrialApplications; on Reaction Vessels, EnclosedSpace, Petrochemical and Refineries, for detection or precise readings

SUGGESTED APPLICATIONS

• Operation of Fresh Air or Exhaust Air Fan, or Damper• Economizer• Ozone Generator• Heat Recovery Wheel • Cooling, Heating, and RH Control Devices• Obtain best IAQ and Minimize HVAC Plant Operating Cost• Produce precise Time History records to demonstrate superior Indoor Air Quality, to resolve disputes, and as irrefutable evidence, in the event of Law Suits• Detect specific VOC/Gas in STP, or in industries, to initiate corrective action

CONTROZONE CZ8 DOES IT ALL

Casinos, Discos, Bars, High Smoke Areas; Where Air Quality with Low operating cost is a challenge.

RUKS CONTROZONE CZ8 IS THE SOLUTION.

Auditoriums, Cinema Halls, Banquet Halls, EntertainmentCenters; High Quality, USP, and control over rising operating costhelp stay ahead of Competition.

RUKS CONTROZONE CZ8 IS YOUR SILENT PARTNER.

18 Automatic Road, Unit 18, Brampton, Ontario, L6S 5N5, Canada. Toll Free: 1877 RUKSENG (1 877 785 7364), Tel: (905) 789 9652, Fax: (905) 789 0381, [email protected] www.rukseng.com

3

Call Centers, Software Development Facilities, Corporate Offices, Banks;Improved IAQ, Odor and Smoke Abatement, and ReducedCO2, and visual demonstration are essential.

RUKS CONTROZONE CZ8 IS THE MONITOR OFCHOICE.

Malls, Shopping Centers, Retail Outlets;Reduced Capital and Operating Cost, Smoke and Odor FreeEnvironment, Bring in more Customers and improve BottomLine.

RUKS CONTROZONE CZ8 IS THE DEPENDABLE AND ECONOMICAL SOLUTION.

PRODUCT SPECIFICATIONS

Size: 9-1/2” x 4-3/8” x 7-1/4” (H) / 241 mm

x 111 mm x 184 mm (H)

Weight: 5.5 lbs (2.5 Kg)

Input Power: 12 V AC/DC, 3 Amps. AC/DC Power

Adapter included. Specify 110 V or 220 V

Case: 18 G CRS Powder Coated

Rating: Continuous

Display: 5.7 Inch, Color, Touch Screen, 320 x 240

Resolution, Programmable LCD, or 4 Line x 20

Character, Back Lit Monochrome LCD with

Programmable Membrane Touch Pad, or Blank

Cover with Pilot Lamp to indicate Power On. LAN

with remote access. Upto 32 Monitors on one

circuit - BacNet, ModBus, or EtherNet

communication protocol

Operating Range: 32ºF to 140ºF (0ºC to 60ºC).

0 to 100% RH Non Condensing

Mounting: Space, Duct, Plenum, Chamber, Vessel

Warmup Time: Approximately 3 Minutes

Parameters Tracked: TVOC, CO2, CO,

Environment Ozone, Temperature and RH.

Output: 0-10 VDC, 0-5 VDC, 4-20 mA (User

Specified), and Five user assignable NO Dry

Contacts

Hardware Output: (Any one) PD, AD, LAN,

BacNet, ModBus, EtherNet

Battery for Real Time Clock and Backup: Lithium,

Factory installed.

Sensor Details: VOC CO2 CO Environment O3 Temperature RHType HMOS Non Dispersive Compact HMOS Thermistor Polymer Infra Red Solid EC Linear Sensor CapacitiveRange and 0-100 PPM 0-1000 PPM 0-400 PPM 0-0.14 PPM 50-120ºF 0-100%Alarm 0-1000 PPM 0-2000 PPM 0-140 PPB 10-50ºC(Field Selectable)Calibration Gas Isobutylene CO2 CO O3 Response Time Nearly Instantaneous for all Sensors Output Signal (User Specified) 0-10 VDC, 0-5VDC, 4-20 mA, for all ParametersDry Contact NO, 24 V AC/DC, 3 Amps, 5 Contacts user assignable to any parameter. BAS/BMS Interface 0-10 VDC Analog Output.

18 Automatic Road, Unit 18, Brampton, Ontario, L6S 5N5, Canada. Toll Free: 1877 RUKSENG (1 877 785 7364), Tel: (905) 789 9652, Fax: (905) 789 0381, [email protected] www.rukseng.com

4

Monitor Display Programmable Time Enclosure Type of Password Dry 0-10V User Set History Mount Protected Contacts analog Alarm for Records User Output All Sensors Selectable for all Sensors CZ8 PD Color, � Graphic 18 G CRS Space or � 5 Nos � �

Graphic Pattern or Powder Duct Touch Numeric Coated Screen Values CZ8 AD 4 Line � Numeric 18 G CRS Space or � 5 Nos � �

x 20 Values Powder Duct Character Coated CZ8 LAN Lamp for Through Display 18 G CRS Space or � 5 Nos Set � �

Power On Laptop or PC on Laptop Powder Duct through or PC Coated Laptop or PC

CZ8 PDDisplays all IAQ Parameters in attractive graphic, user friendly format on a large 5.7 inch color, Programmable Touch Screen. Provides Time History Records in Graphic or Tabular Formats. Enhanced Display with attractive colors well suited for high end applications.

CZ8 ADScrolls all IAQ parameters on 4 Line x 20 Character Back Lit Monochrome LCD, with Programmable Touch Pad MembraneSwitch. Provides all other features of CZ8-PD except Time HistoryRecords. Practical, Functional and Cost Effective Solution for MidPrice Range Applications.

CZ8 LANAll IAQ parameters, features, and functions transmitted on LAN to PCor laptop. Supports BacNet, ModBus, or EtherNet (choose one) protocol. Interface to BAS/BMS. All parameters can be viewed, alarmset, Dry contacts activated or deactivated, graphs and charts displayed, reports generated through one center location, on PC orlaptop. Factory provided enhanced Ruks Software provides easy anduser friendly operation. Caters well to modern technology communication protocols, reduces time for start up and routine dataaccess by eliminating manpower to visit each Monitor, precursor forfuture development to access over IP, and above all is cost effectiveas individual displays are eliminated.

CZ8 - MODELS & FEATURES

Communication Capabilities (Choose any one) - LAN, BacNet, ModBus, EtherNet. Maximum number ofMonitors per circuit = 32.

18 Automatic Road, Unit 18, Brampton, Ontario, L6S 5N5, Canada. Toll Free: 1877 RUKSENG (1 877 785 7364), Tel: (905) 789 9652, Fax: (905) 789 0381, [email protected] www.rukseng.com

5

• Upto 32 Monitors on a Single Circuit

• Local Area Network (LAN)

• BacNet

• ModBus

• EtherNet

LAN CONFIGURATION

18 Automatic Road, Unit 18, Brampton, Ontario, L6S 5N5, Canada. Toll Free: 1877 RUKSENG (1 877 785 7364), Tel: (905) 789 9652, Fax: (905) 789 0381, [email protected] www.rukseng.com

6

ADDITIONAL FEATURES

• Easy Installation. Factory provided Back Plate is attached to wall or panel. CZ8 gently slides on to the back plate. Reduces installation time to just few minutes. • Easy electrical connections. All field wiring terminate on factory provided FIQD (Female Insulated Quick Disconnect) for snap on connection.• Wide viewing angle with excellent visibility. High resolution, bright, color graphics PD Screen provides easy and attractive visibility.• Architect’s delight as it blends well with most interior decor and adds elegance. • Unit installed fan delivers room air over the sensor element for quick, accurate and reliable readings. • Flexible use options: Monitor may be duct mounted, or installed in the space to be monitored. Unit mounted selector switch allows easy change over to admit sampled air from duct or from space into the Monitor. • High rating on NO Dry Contacts - 3 Amps 24 V allows direct connection to most controlling devices such as Damper Actuator, Solenoid Valve, Electrical Contactor, or any other On Off device.• 5 Dry Contacts provide easy connection to

multiple number of controlled devices to enhance IAQ and achieve energy reduction.• All Dry Contacts are user assignable to any parameter. Provides flexibility.• Each IAQ parameter can be programmed to deliver 0-10VDC analog signal for modulating IAQ control or energy reduction devices, or for interface to BAS/BMS.• Password protected. Prevents unauthorized access.• CO2 Module is optional. Saves cost where CO2 monitoring is not required.• CO Module is optional. Saves cost where CO monitoring is not required. • Sensor circuit board is gold plated. Prevents oxidization of conductors commonly seen in low cost monitors. Preserves accuracy, reliability, and repeatability over long service life.• Ozone sensor is factory calibrated to NIST traceability. Sensors do not need field calibration over life of the Monitor.• All parts and components of Monitor are lead free and in conformity to ROHS.• Many different models to choose from. Suits all needs and budgets; high end to shoe string budget.• Factory provided stylus for touch screen Monitors.

Electrical connections on rear panelCZ8 with dimensions

18 Automatic Road, Unit 18, Brampton, Ontario, L6S 5N5, Canada. Toll Free: 1877 RUKSENG (1 877 785 7364), Tel: (905) 789 9652, Fax: (905) 789 0381, [email protected] www.rukseng.com

7

1. Monitoring, Regulation and Reporting of Air Quality shall be performed automatically on continuous basis, by Ruks ControZone CZ8 Total Air Quality Monitor.

2. The Monitor shall be suitable for tracking Total VOC, Carbon Dioxide, Carbon Monoxide, Environment Ozone, Temperature,and RH.

3. Monitor shall be rated for continuous operation, in indoor ambient 32ºF to 140ºF (0º to 60ºC) and RH 0 to 80% non Condensing.

4. IAQ shall comprise Sensor Section and Display Section. Sensor Section is common for all Monitors. Display Section is user selectable; PD, AD, LAN, BacNet, Modbus, or EtherNet.

5. The IAQ Monitor shall be suitable for easy field installation without opening the IAQ Monitor, by fixing the factory provided back plate, upon which the Monitor slides easily in. All necessary hardware for installation shall be provided by the manufacturer.

6. All electrical, power, control, and BAS/BMS wiring shall terminate on factory provided Female Insulated Quick Disconnect (FIQD). This shall snap fit in the terminal block in the Monitor. It shall be possible to field connect all cables without opening the Monitor.

7. Standard supply is without CO2 and CO Modules. CO2 and CO Modules may be added as Optional Item. This is factory installed option complete with factory programming of the Monitor. Reference to CO2 and CO in this section are valid only if these Modules are used.

SENSOR SECTION

8. The Sensor Section shall comprise independent Sensors to track each IAQ parameter, TVOC, Residual Ozone, CO2, CO, Temperature, and RH. Each Sensor shall be independently programmable. Units for display such as PPM, PPB, ºF or ºC shall be user selectable.

9. It shall be provided with 256 MB RAM, Micro Processor, Flash Memory, Real Time, and Lithium Battery back up.

10.Each Sensor shall deliver analog output signal approximately linearly proportional to the

readings in the range 0-10 V, 0 - 5 V, 4-20mA (specify at time of order). These may be interfaceable to BAS/BMS.

11.Shall have 5 numbers of Normally Open (NO) Dry Contacts, field assignable by user to any sensor, or multiple number of Dry Contacts may be assigned to one Sensor (example: Activation and Alarm may be assigned to the same Sensor). The Dry Contact shall be rated for 3 Amps on 24 V AC/DC. It shall be possible to program at field activation level for any IAQ parameter either on rising or dropping values.

12.Peripheral connectors shall be unit mounted and comprise one each of USB 2.0, RS 232 and Ethernet download.

13.Side panels of the Sensor Board shall be provided with factory installed female plug for connecting power adaptor, On Off switch, USB 2.0 and RS 232 connectors, selector switch for change over between space and duct mount, fan for sampling room air, and exhaust vent to discharge sampled room air.

14.Sensor Section shall be provided with spigots for connecting pitot tubes, if duct mount option is used. It shall be possible to field connect factory provided pitot tubes without opening the Monitor.

15.Power supply shall be 12 V AC/DC 3 Amp. Adaptor 100 to 240 V / 12 V shall be factory provided.

16.The Monitor shall be factory provided with Lithium battery to power Real Time Clock andfor data storage.

17.For fail safe and long time operation, printed circuit boards shall be immersed in 24 carat gold 3 Micron thick. This is to reduce or prevent loss of accuracy due to oxidation of the conductor surface over time. The populated board shall be conformal coated to prevent damage from dust, moisture, condensation, traces of acid, and ozone.

18.All parts and components of the Monitor shall be lead free and shall comply to ROHS(Restriction in use of Hazardous Substances).

DISPLAY SECTION

Display Section may be PD or AD or LAN.

TECHNICAL SPECIFICATIONS OF CZ8 TOTAL IAQ MONITOR

INTERNATIONAL SALES AND DISTRIBUTION:

RUKS ENGINEERING LTD18 AUTOMATIC ROAD, UNIT 18 BRAMPTON, ONTARIO, L6S 5N5, CANADA Toll Free: 1 877 RUKSENG (1 877 785 7364)TEL: (905) 789 9652. FAX: (905) 789 0381 [email protected] www.rukseng.com

FACTORY:RUKS CANADA LTD.ONTARIO, CANADA

Specifications and other details subject to change without notice Cat #: RE CZ8 Rev 2-01/12

CZ8-PD

19.Display shall be on 5.7 inch, color, graphic, programmable touch screen, capable of displaying all or individual parameters, as chosen by the user.

20.Monitor shall be programmable at site by user through touch screen membrane. Programming Levels shall include System Set Up, Defining Upper and Lower Ranges, Alarm Levels, Bar or Line Graph, Alarm Reports, Time History and Real Time Reports with user specified time periods, defining levels for activation of NO Dry Contacts and Alarm levels, and defining if activation and alarm is on ascending or descending values. Real Time and Time History records shall be displayed in graphic or tabular format as chosen by user.

21. If set Alarm level is reached, color of display of the parameter concerned shall change from Green to Red.

22. If set Activation and or Alarm levels is reached, icons indicative of these shall appear at the bottom of the respective parameter.

23.The Display Section shall be factory integrated onto the Monitor Section to form one neat compact unit Model CZ8-PD.

24.The Monitor shall be CE Certified.25.Total Air Quality Monitor shall be CZ8-PD,

manufactured by Ruks Engineering Ltd, Canada. Country of manufacture shall be Canada.

CZ8-AD

26 Display shall be 4 Line x 20 Character, back lit monochrome LCD. Programming shall be by membrane touch pad keys. Each IAQ parameter shall scroll on the screen one after another. By pressing the prompted touch pad key, chosen

parameter shall remain hold steady till user commands it to scroll again.

27.User programmable features shall be same as described in Clause 20 under PD, except Real Time and Time History and graphic features are not available.

28. If set Activation and or Alarm levels is reached, icons indicative of these shall appear at the bottom of the respective parameter.

29.The Monitor shall be CE Certified.30.Total Air Quality Monitor shall be CZ8-AD,

manufactured by Ruks Engineering Ltd, Canada. Country of manufacture shall be Canada.

CZ8-LAN

31.Display on the Monitor shall be by pilot lamp for Power On.

32.LAN shall support upto 32 Monitors in one circuit. Any one of these Monitors may be connected to PC or Laptop. All features of the Monitor such as display of parameters, setup commands, activating alarms, assigning Dry Contacts, producing graphs and reports for any of the Monitors shall be performed from a single PC/Laptop location. Software necessary for PC/Laptop for such functions shall be factory provided.

33.0-10 VDC or 4 to 20 mA Analog Output for upto five parameters shall be available for interface to BAS/BMS.

34.Output protocol may be LAN, BacNet, Modbus, or EtherNet, as chosen by the user (Specify at time of order).

35.The Monitor shall be CE Certified.36.Total Air Quality Monitor shall be CZ8-LAN,

manufactured by Ruks Engineering Ltd, Canada. Country of manufacture shall be Canada.

YOUR DISTRIBUTOR: