lab/slv1 and lab/slv1-bss user manual · hauptstraße 119 – 121 telefon +49-6205-3948-0 e-mail...
TRANSCRIPT
Hauptstraße 119 – 121 Telefon +49-6205-3948-0 E-Mail [email protected] D-68804 Altlußheim Telefax +49-6205-37560 Web www.et-system.de
LAB/SLV1 and LAB/SLV1-BSS User manual Version information
Version: 1.0
Software upgrade might change or add product features. Please acquire the latest
version of the manual from our website or contact technical support.
Hauptstraße 119 – 121 Telefon +49-6205-3948-0 E-Mail [email protected] D-68804 Altlußheim Telefax +49-6205-37560 Web www.et-system.de
Summary of Safety Requirement
Please review the following safety precautions carefully before putting the
equipment into operation so as to avoid any personal injury or damage to the
equipment and any product connected to it. To prevent potential hazards, please
follow the instructions specified in this manual to use the instrument properly.
Use Proper Cables
Please choose the proper specification cable according to the equipment
specification within the local country could be used.
Ground the Equipment
The equipment is grounded through the Protective Earth Bus. To avoid electric
shock, connect the earth terminal to the Protective Earth terminal before connecting
any input or output terminals.
Use Proper Overvoltage Protection
Ensure that no overvoltage (such as that caused by a bolt of lightning) can reach the
product. Otherwise, the operator might be exposed to the danger of an electric shock.
Avoid Circuit or Wire Exposure
Do not touch exposed junctions and components when the unit is powered on.
Keep Equipment Surfaces Clean and Dry
To avoid dust or moisture from affecting the performance of the equipment, keep the
surfaces of the equipment clean and dry.
I
Hauptstraße 119 – 121 Telefon +49-6205-3948-0 E-Mail [email protected] D-68804 Altlußheim Telefax +49-6205-37560 Web www.et-system.de
Safety Notices and Symbols
Safety Notices in this Manual:
WARNING Indicates a potentially hazardous situation or practice which, if not avoided, will
result in serious injury or death.
CAUTION Indicates a potentially hazardous situation or practice which, if not avoided, could
result in damage to the product or loss of important data.
Safety Terms in this Manual: DANGER It calls attention to an operation, if not correctly performed, could result in injury
or hazard immediately.
WARNING
CAUTION
It calls attention to an operation, if not correctly performed, could result in
potential injury or hazard. It calls attention to an operation, if not correctly performed, could result in
damage to the product or other devices connected to the product.
Safety Symbols on the Product or in this Manual:
Hazardous Safety Warning Protective Earth Test Ground Chassis Ground Voltage Terminal
II
Hauptstraße 119 – 121 Telefon +49-6205-3948-0 E-Mail [email protected] D-68804 Altlußheim Telefax +49-6205-37560 Web www.et-system.de
Important Safety Instructions
Please read this manual thoroughly before putting the equipment into
operation. Pay regard to the following safety instructions and keep this manual
nearby for future purpose.
INITIAL OPERATION
This operating manual is based on the state of technology at the time of printing.
However, it is possible that despite regular control and correction, the present document
contains printing errors or deficiencies. ET System electronic GmbH assumes no liability
for any technical, printing or translational errors within this manual.
UNPACKING
Please make sure that the shipping carton and the packaging is free of damage. If
external damage is found, it is important to record the type of damage. Please keep
the original packaging to ensure the device is adequately protected in case it needs
to be transported in the future or claims for compensation need to be asserted.
SETTING UP
To avoid electric shocks and product failure, the device should be installed in a
temperature and humidity controlled indoor environment. The ambient temperature
must not exceed 40℃. The device must never be exposed to liquids or extreme
humidity.
VISUAL INSPECTION
The unit must be examined immediately for defects or damages in transit. Damage
caused during transport may be loose or broken control knobs and bent or broken
connectors. Do not use the device if any physical damage is apparent. Please inform
the carriers and a representative of ET System electronic immediately.
MAINS OPERATION
Make sure to verify the model number and voltage stated on the nameplate.
Damages due to wrong power feed are not covered by guarantee conditions.
III
Hauptstraße 119 – 121 Telefon +49-6205-3948-0 E-Mail [email protected] D-68804 Altlußheim Telefax +49-6205-37560 Web www.et-system.de
CAUTION
The unit must only be operated when connected directly to the mains. To
avoid damage, do not connect the unit to isolating transformers, auto-
transformers, magnetic current limiters or similar devices.
INTENDED USE The device corresponds to protection class I and has a galvanic isolation between the input and the output circuit. The device must be grounded on the input side, since the grounding ensures protection against contact. In the case of locally variable devices, the earth is connected to the device by means of a cold-plug connector, and the ground is connected to the screw terminal provided for locally-variable devices (screw contacts at the grid input). In the case of devices with high leakage current (marking on the device), the existing grounding bolt must additionally be connected to the domestic installation earth. For compliance with the EMC and safety regulations (CE, approvals), the device may only be operated with PE connected. The device may only be operated by trained personnel and in accordance with the instructions for use. Typical fields of application are laboratories, industry and service engineering. Applications which can lead to injuries or death in the event of a fault in the device are not permitted.
INFO & CONTACT ADDRESSES
ET System electronic GmbH was founded in 1986 in the heart of the Rhine-Neckar-Triangle. As a subsidiary of a leading electricity utility group, the company quickly took on a leading role in the area of laboratory power electronics and associated electrical measurement. The existing know-how in power technologies in the 90s gave rise to the “Power Solutions” product division as a strong extension of the historical “Test & Measurement” range. Since 1997, we have been working successfully as an independent, privately held company with customers in all lines of business from industry, medical care, railway technology and automotive electronics. By means of our high vertical range of manufacture and our ever expanding development division we can fast and flexibly adjust to our customers’ requirements. Necessary approvals such as CSA, UL, VDE, TÜV etc. are flexibly carried out by qualified personnel. The approvals procedures are performed within the scope of development planning and thus do not negatively impact the start of manufacturing. Permanent manufacturing control through accredited laboratories and an ISO 9001 compliant quality management system guarantee a constant high-level series-production quality. We offer repairs and adjustment for units outside of our warranty period. Please contact your local distributor for further information:
IV
Germany Great Britain France Korea
ET System electronic GmbH Hauptstraße 119-121
68804 Altlußheim
Germany
ET Power Systems Ltd. The Bridge Business Centre
Chesterfield S41 9FG
United Kingdom
ET Systeme electronic 4 rue Ampère
38080 L’Isle d’Abeau
France
ET System electronic Korea Corporation
DaeHyeon Techno World 1203 19,Ojengongeup-gil,
Uiwang-si, Gyeonggi-do 437-753
Republic of Korea
Phone: +49 (0) 6205 39480
Fax: +49 (0) 6205 37560
Phone: +44 (0) 1246 452909
Fax: +44 (0) 1246 452942
Phone: +33 (0) 474 278234
Fax: +33 (0) 474 278068
Phone: +82 (0) 31 451 4491
Fax : +82 (0) 31 453 4459
em@il: [email protected] web: www.et-system.de
em@il: [email protected] web: www.et-system.com
em@il: [email protected] web: www.et-system.fr
em@il: [email protected] [email protected] web: www.et-system.kr
Hauptstraße 119 – 121 Telefon +49-6205-3948-0 E-Mail [email protected] D-68804 Altlußheim Telefax +49-6205-37560 Web www.et-system.de
SLV1 & BSS Series Overview1
Main Features Fast transition between source and sink
Simulation of battery
Electrical isolation to grid
TFT display with touch operation
Emergency Stop button on front panel
Indicator light for working status on front panel
Forced air cooling
Highly dynamic inverter
Three operation mode of constant voltage,
constant current, constant power
DC output contactor
External sense terminals for line drop compensation
Insulation monitoring
Customer specific design BSS-60-1000
Characteristic of Output for BSS-60-1000
1 Note: SLV1 & BSS series have similar functions, but different output characteristic, please refer to the curve below, and detailed characteristic refer to datasheet of product
V
Hauptstraße 119 – 121 Telefon +49-6205-3948-0 E-Mail [email protected] D-68804 Altlußheim Telefax +49-6205-37560 Web www.et-system.de
Characteristic of Output for SLV1-60-1000
Applications
Application Scenarios
Simulation of battery or energy storage system, test Battery simulation performance of motor and motor’s Energy Recovery
System
Testing battery Cycle life, Capacity, Performance of charge & discharge
Testing PV inverter Simulation of photovoltaic characteristics
(Option)
VI
Hauptstraße 119 – 121 Telefon +49-6205-3948-0 E-Mail [email protected] D-68804 Altlußheim Telefax +49-6205-37560 Web www.et-system.de
Document Overview
Chapter 1 Quick Start
Introduce the appearance, front panel, rear panel as well as user interface of power
source. In addition, it provides the detailed procedures of power connection, power-
on inspection and fuse replacement.
Chapter 2 GUI Control Software
Introduce the function and operation method of product’s control software in detail.
Chapter 3 Remote Control
Introduce how to realize the remote control of the equipment.
Appendix A — Specification of SLV1
Series List the specifications of SLV1 Series.
Appendix B — Specification of BSS
Series List the specifications of BSS Series.
VII
Hauptstraße 119 – 121 Telefon +49-6205-3948-0 E-Mail [email protected] D-68804 Altlußheim Telefax +49-6205-37560 Web www.et-system.de
Content
Chapter 1 Quick Start ........................................................ ......................................... 1
1.1 General Inspection ........................................................................................................ 2
1.2 Appearance and outline ................................................................................................ 3
1.3 Front Panel .................................................................................................................... 3
1.4 Rear Panel .................................................................................................................... 4
1.5 Connect to Power .......................................................................................................... 5
1.6 Power-on Inspection ...................................................................................................... 6
1.7 Replace the Fuse .......................................................................................................... 7
1.8 User Interface ................................................................................................................ 8
Chapter 2 Control Software ........................................................................................ 9
2.1 Setting ......................................................................................................................... 10
2.2 Normal Mode ............................................................................................................... 11
2.2.1 Constant Voltage Mode ........................................................................................ 11
2.2.2 Constant Current Mode ........................................................................................ 12
2.2.3 Constant Power Mode .......................................................................................... 13
2.2.4 Constant Resistance Mode (OPTION)................................................................... 13
2.3 Battery Mode ............................................................................................................... 14
2.3.1 Battery Simulation ................................................................................................. 14
2.3.2 Battery Tester ....................................................................................................... 15
2.4 PV Mode (OPTION)............................................................................................... 17
2.4.1 I-V Curve Setting .................................................................................................. 17
2.4.2 Dynamic MPPT Test ............................................................................................. 19
2.4.2 Static MPPT Test .................................................................................................. 20
2.5 Wave Monitoring ......................................................................................................... 20
2.6 Fault Monitoring ........................................................................................................... 22
2.7 Query ....................................................................................................................... .... 23
2.7.1 History Log ............................................................................................................ 23
2.7.2 History Data .......................................................................................................... 23
Chapter 3 Remote Control ....................................................................................... 25
3.1 Computer Setting ........................................................................................................ 25
3.2 Software Setting .......................................................................................................... 25
3.3 Remote Control ........................................................................................................... 26
Appendix A — Specification of SLV1 Series ............................................................ 27
Appendix B — Specification of BSS Series .............................................................. 31
Hauptstraße 119 – 121 Telefon +49-6205-3948-0 E-Mail [email protected] D-68804 Altlußheim Telefax +49-6205-37560 Web www.et-system.de
Chapter 1 Quick Start
The contents of this chapter are as follows:
General Inspection
Appearance and outline
Front Panel
Rear Panel
Connect to Power
Power-on Inspection
Replace the Fuse
User Interface
1 / 44
Hauptstraße 119 – 121 Telefon +49-6205-3948-0 E-Mail [email protected] D-68804 Altlußheim Telefax +49-6205-37560 Web www.et-system.de
1.1 General Inspection
1. Inspect the packaging
If the packaging has been damaged, do not dispose the damaged packaging or
cushioning materials until the shipment has been checked for completeness and has
passed both electrical and mechanical inspection.
The consigner or carrier shall be liable for the damage to the product resulting from
shipment. Factory would not be responsible for free maintenance/rework or
replacement of the product.
2. Inspect the product
In case of any mechanical damage, missing parts, or failure in passing the electrical
and mechanical tests, contact your local sales representative.
3. Check the accessories
Please check the accessories according to the packing lists. If the accessories are
damaged or incomplete, please contact your local sales representative.
2 / 44
Hauptstraße 119 – 121 Telefon +49-6205-3948-0 E-Mail [email protected] D-68804 Altlußheim Telefax +49-6205-37560 Web www.et-system.de
1.2 Appearance and outline
The equipment adopts integrated
module design, the appearance is
simple and generous.
The front panel is composed of a
touch TFT LCD panel, a power
switch, indicator lights and an
emergency stop button.
The rear panel is composed of a
communication port and a line
voltage drop compensation terminal.
Figure 1-1 Front View Figure 1-2 Rear View
1.3 Front Panel
This section introduces the front panel of SLV1 & BSS series by taking BSS-100-
1000 (as shown in the figure below) as an example. The differences of models are
introduced separately.
Figure 1-3 Front Panel of SLV1 & BSS series
3 / 44
Hauptstraße 119 – 121 Telefon +49-6205-3948-0 E-Mail [email protected] D-68804 Altlußheim Telefax +49-6205-37560 Web www.et-system.de
1. LCD
12 inches TFT display. It is used to display the system parameter setting, system
output state, menu items, prompt messages, etc. The touch displayer panel is a
capacitive touch TFT screen, and is based on Windows operating system. GUI
Control software is designed on the platform of LabView.
2. LED Indicator of Status
LEDs indicate the working state of the power source in a concise manner. It includes
work indicator of power, indicator of standby mode, indicator of running and fault
indicator.
AC On While the input line is powered on, the light will be lit.
Standby System is standby.
Run System is running normally.
Fault There is a system error.
3. Rotary Switch
Turn on or off the power source. When the rotary switch is turned on, the power
source would be in standby mode.
4. Emergency Stop Button
The emergency stop button is only used when an unexpected emergency occurs. Do
not press this button in normal working condition.
1.4 Rear Panel
This section introduces the rear panel of SLV1 & BSS series by taking BSS-100-
1000 (as shown in the figures below) as examples. The introduction of each part is
as in Table 1-1.
Figure 1-4 Rear Panel of SLV1 & BSS series
4 / 44
Hauptstraße 119 – 121 Telefon +49-6205-3948-0 E-Mail [email protected] D-68804 Altlußheim Telefax +49-6205-37560 Web www.et-system.de
LAN This interface is a communication interface used for remote control
Debug The Debug port is reserved for firmware update or debug
External Sense Terminal of voltage compensation for long distance
The output voltages at the load can be directly monitored via the external sense on
the back of the power source, which is usually for long distance power transfer.
1.5 Connect to Power
SLV1 & BSS series power source supports the world grid standards, but a particular
product supports the GRID SYSTEM only for one country or region. Before the power
source is used, it is necessary to verify that the product specifications are consistent with
the Local GRID. And please connect the power following the steps below.
1. Check the input power
Make sure that specifications of the power source are consistent with the local GRID,
such as voltage and frequency.
2. Check the fuse
When the product leaves factory, the specified fuse is installed. Please check
whether the fuse matches the actual input voltage according to the "Input Power
Requirements" at the rear panel of the product.
5 / 44
Hauptstraße 119 – 121 Telefon +49-6205-3948-0 E-Mail [email protected] D-68804 Altlußheim Telefax +49-6205-37560 Web www.et-system.de
3. Connect the AC power
Connect the power source to AC power supply with proper
specification cable according to the product specification
within the local country could be used. Wiring methods refer
to the following steps.
A. Remove the lowest cover plate after opening the front
cabinet door, there are eight connection terminals in the
cabinet. Shown as figure 1-5.
B. Connect the Earthing Terminal Bus to Earth Line, make
sure the equipment is well grounded.
C. Connect the four connection terminals left-side with
power line, L1, L2, L3 and N are arranged from left to
right. D. Connect the four connection terminals right-side
with equipment to be powered, L1, L2, L3 and N are also
arranged from left to right.
Figure 1-5 Connection terminals of Power Source
WARNING
To avoid electric shock, make sure that the input line is power off, and the
power source is correctly grounded.
1.6 Power-on Inspection
Turn on the rotary switch at the front panel, the power source initializes and executes
self-test. If the power source passes the self-test, the control software will be displayed
6 / 44
Hauptstraße 119 – 121 Telefon +49-6205-3948-0 E-Mail [email protected] D-68804 Altlußheim Telefax +49-6205-37560 Web www.et-system.de
on LCD display, and the standby indicator will be lit; otherwise, the indicator of fault
will be lit.
CAUTION
When powering on the equipment after powering off it, make sure that the
time interval between the two operations is greater than 5s.
1.7 Replace the Fuse
The fuse specification is related to the product model and actual input voltage, as
shown in the table below. You can also refer to the "Input Power Requirements" at
the rear panel of the product. To replace the fuse, please refer to figure 1-6, and
follow the steps below.
1. Turn off the power source, and make sure the
input power has been cut off.
2. Remove the fuses to be replaced and replace
them with specified ones (please refer to the "Input
Power Requirements" at the rear panel of the
product).
Figure 1-6 Fuse mounting position
7 / 44
Hauptstraße 119 – 121 Telefon +49-6205-3948-0 E-Mail [email protected] D-68804 Altlußheim Telefax +49-6205-37560 Web www.et-system.de
WARNING
To avoid personal injuries, cut off the input of power before replacing the
fuse; to avoid electric shock or fire, replace a fuse corresponding to power
supply specification before connecting to power, and the power source is
correctly grounded.
1.8 User Interface
SLV1 & BSS series power source provides three operation mode (Normal Mode, Battery
Mode and PV Mode). The default mode is Normal Mode while the software is launched.
User can select the appropriate mode according to the application scenarios.
Also, the power source can be controlled in local and remote style. Both of which
have same interface and operation. The modes will be described in Chapter 2.
While the Power knob is turn on, it takes several seconds to initialize the controller
and other units. Make sure that the power’s output connection terminals are correctly
connected. Then, All the functions and parameters can be set and run via touch
panel displayer or GUI software.
8 / 44
Hauptstraße 119 – 121 Telefon +49-6205-3948-0 E-Mail [email protected] D-68804 Altlußheim Telefax +49-6205-37560 Web www.et-system.de
Chapter 2 Control Software
The contents of this chapter are as follows:
Setting
Normal Mode
Battery Mode
PV Mode
Wave Monitoring
Fault Monitoring
Query
9 / 44
Hauptstraße 119 – 121 Telefon +49-6205-3948-0 E-Mail [email protected] D-68804 Altlußheim Telefax +49-6205-37560 Web www.et-system.de
2.1 Setting
Before performing any test, to protect the device from accidental damage, the values
of Overvoltage protection(OVP) and Overcurrent protection(OIP) should be set
according to test requirements. Generally, the protection value should be slightly
higher than the normal supply voltage.
There are two steps to set the value of OVP and OIP. First, click the ’Hardware limits’
option of menu ‘Setting’ in Test Panel, the input boxes will appear at the bottom of
the test panel as shown in Figure 2-1. Then input appropriate value of OVP and OIP,
and click the ‘Apply’ button at last.
Before performing any test, make sure the hardware limits are set correctly, which
include overvoltage protection (OVP) and overcurrent protection (OCP) values.
Figure 2-1 Setting of Hardware Limits
CAUTION Default path of control software installed on the power source’s controller
is “C:\Software\”, The path can’t be changed, otherwise the software will
be not launched while power source powering on.
10 / 44
Hauptstraße 119 – 121 Telefon +49-6205-3948-0 E-Mail [email protected] D-68804 Altlußheim Telefax +49-6205-37560 Web www.et-system.de
2.2 Normal Mode
In Normal Mode, according to the control parameters it can be divided into constant
voltage mode (CV Mode), constant current (CC Mode), constant power (CP Mode)
and constant resistance (CR Mode) mode. While one of which is selected, the other
mode’s controls will be disabled and grayed out.
In CV mode, the output voltage equals the voltage setting value and the output
current is determined by the load; in CC mode, the output current equals the current
setting value and the output voltage is determined by the load; in CP mode, the
output power keeps the constant value set by operator. This section introduces the
operation method. At the same time, the real-time value measured will be displayed
on the top area of the control software panel, such as voltage, current, power and
resistance. The curve of voltage and current will be displayed on the wave control
shown as figure 2-2.
2.2.1 Constant Voltage Mode
In constant voltage mode, the parameter of voltage could be adjusted only, while the
value of voltage is set, the voltage will be output after pressing the power on button.
Figure 2-2. Panel of Constant Voltage Mode
11 / 44
Hauptstraße 119 – 121 Telefon +49-6205-3948-0 E-Mail [email protected] D-68804 Altlußheim Telefax +49-6205-37560 Web www.et-system.de
However, there is important step to follow for safety, user must confirm the operation
of “Power On” by click the “Start” button on pop-up window shown as figure 2-3.
Figure 2-3. Confirm Operation
2.2.2 Constant Current Mode
In constant current mode, the parameter of current could be adjusted only shown as
figure 2-4, while the value of current is set, the current will be output after pressing
the power on button. Same as the constant voltage mode, user must confirm the
operation of “Power On” by click the “Start” button.
Figure 2-4. Panel of Constant Current Mode
CAUTION
To avoid damage to the equipment, verify the capacity of the load and
make sure it is in good connection with the load before powering on the
power supply.
12 / 44
Hauptstraße 119 – 121 Telefon +49-6205-3948-0 E-Mail [email protected] D-68804 Altlußheim Telefax +49-6205-37560 Web www.et-system.de
2.2.3 Constant Power Mode
In constant Power mode, the parameter of power could be adjusted only shown as
figure 2-5, while the value of power is set, the power will be output after pressing the
power on button. User must confirm the operation of “Power On” by click the “Start”
button also.
Figure 2-5. Panel of Constant Power Mode
2.2.4 Constant Resistance Mode (OPTION)
In constant resistance mode, the parameter of resistance could be adjusted only
shown as figure 2-6, while the value of resistance is set, the output power of power
supply will be determined by the load. Also, user must confirm the operation of
“Power On” by click the “Start” button.
13 / 44
Hauptstraße 119 – 121 Telefon +49-6205-3948-0 E-Mail [email protected] D-68804 Altlußheim Telefax +49-6205-37560 Web www.et-system.de
Figure 2-6. Panel of Constant Resistance Mode
2.3 Battery Mode
There are two category operation mode for battery mode, battery simulation and
battery tester. While the power supply runs as battery simulator, the output electrical
characteristics of output just simulate the characteristics of the battery. While running
as battery tester, it performs as a charger or discharger of battery.
2.3.1 Battery Simulation
While running as simulator of battery or energy storage system, it can be used to test
performance of motor and motor’s Energy Recovery System.
Battery type, the numbers of batteries in series and parallel, cutoff limits, nominal
voltage, rated capacity and initial SOC can be set according to actual demand shown
as figure 2-7.
14 / 44
Hauptstraße 119 – 121 Telefon +49-6205-3948-0 E-Mail [email protected] D-68804 Altlußheim Telefax +49-6205-37560 Web www.et-system.de
Figure 2-7 Battery Simulation Mode
2.3.2 Battery Tester
The power supply can also perform as a charger of discharger of battery, usually it is
used to test cycle life, capacity, performance of charge & discharge.
15 / 44
Hauptstraße 119 – 121 Telefon +49-6205-3948-0 E-Mail [email protected] D-68804 Altlußheim Telefax +49-6205-37560 Web www.et-system.de
Figure 2-8 Battery Tester Mode
Figure 2-9 Test Step of Battery Test
In battery tester mode, the setting parameters include:
Mode
The charge type, including CC, CV, CP mode
Value of charge mode, such as 20A in CC mode, can be positive or negative,
Value while positive the power supply performs as a charger, and negative
performs as a discharger.
While
Terminating condition of charge or discharge. It could be the voltage, current
or duration of charge/discharge.
Value
The value of termination condition. While the real-time parameter reaches
the value, the next step will be executed.
Rest If needing a break between two steps, set a rest time in this control.
Selected Only this control is checked, the step will be executed.
WARNING
To avoid fire, please confirm the specification of battery and set the
parameters carefully due to the characteristics of different batteries.
16 / 44
Hauptstraße 119 – 121 Telefon +49-6205-3948-0 E-Mail [email protected] D-68804 Altlußheim Telefax +49-6205-37560 Web www.et-system.de
2.4 PV Mode (OPTION)
Simulation of PV arrays can be done with PV option. The equipment can be used to
simulate IV curves of various solar panels, under various temperature and irradiance
condition, and to test the MPPT characteristics according to EN 50530:2010.
2.4.1 I-V Curve Setting
I-V curves are created by entering simple parametric data. Each curve consists of
1024 data points. Irradiation level or temperature can be modified to test the
behavior of a grid tied inverter under realistic conditions for cloud shadowing and
panel temperature rise. There are three methods for setting I-V curve, such as PV1,
PV2 and Shadow.
For Setting of PV1
Figure 2-10 I-V Curve Setting for PV1
While setting, make sure that the parameters of PV array are set, such as I/U
Characteristic, temperature of environment, Irradiance, Uoc, Isc, Ump and Imp. Then
the I-V curve will be displayed on the Wave display area after the “Calculate” button
is pressed.
Notice: Uoc must be greater than Ump, Isc must be greater than Imp.
17 / 44
Hauptstraße 119 – 121 Telefon +49-6205-3948-0 E-Mail [email protected] D-68804 Altlußheim Telefax +49-6205-37560 Web www.et-system.de
For Setting of PV2
Figure 2-11 I-V Curve Setting for PV2
In PV2 setting page, the temperature of PV module, Irradiance, Uoc, Isc and FF can
be set, and I-V curve will be displayed on the Wave display area after the “Set”
button is pressed. For Setting of Shadow
Figure 2-12 I-V Curve Setting for Shadow 18 / 44
Hauptstraße 119 – 121 Telefon +49-6205-3948-0 E-Mail [email protected] D-68804 Altlußheim Telefax +49-6205-37560 Web www.et-system.de
In Shadow setting page, the temperature of PV module, Irradiance, Uoc, Isc, Ump
and Imp be set for two modules at most, and I-V curve will be displayed on the Wave
display area after the “Set” button is pressed.
2.4.2 Dynamic MPPT Test
Multiple IV curves can be stored and performed in sequence, and time for each step
can be modified individually.
Figure 2-13 Dynamic MPPT Test Window
The efficiency test of dynamic maximum power point tracking (MPPT) is performed
according to illumination = f(time). The irradiation conditions of 1000W/m2 at 25
degrees Celsius correspond to 100%.
The MPPT test consists of 3 test procedures, such as 10%-50% PDCn test, 30%-
100% PDCn test and SLOW switch machine test.
The default values of test procedures are referenced to EN 50530:2010. However,
user can modify the value according to the actual test requirements.
19 / 44
Hauptstraße 119 – 121 Telefon +49-6205-3948-0 E-Mail [email protected] D-68804 Altlußheim Telefax +49-6205-37560 Web www.et-system.de
2.4.2 Static MPPT Test
Figure 2-14 Static MPPT Test Window
According to EN 50530:2010, the measurement of the static MPPT efficiency must
be performed with test specifications as defined in Table 1 in the third section of
fourth chapter. These parameters can be set to the actual values required.
2.5 Wave Monitoring
The output waveform can be viewed in wave window. This window can be invoked
by clicking the ‘Wave’ option in ‘Measurement’ menu. The window is shown as
Figure 2-15.
20 / 44
Hauptstraße 119 – 121 Telefon +49-6205-3948-0 E-Mail [email protected] D-68804 Altlußheim Telefax +49-6205-37560 Web www.et-system.de
Figure 2-15 Wave Monitoring
In this window, the parameters below can be shown by checking on the
corresponding checkbox.
Output voltages, currents are displayed. The voltage and current of input are RMS
values.
Two cursors are available to help user to get readings on the chart. If this function is
required, please check the ‘Cursor1’ and ‘Cursor2’.
Label
Operation Description
Attribution
Sampling time Numeric display X axis shows sampling time. If the sampling time is
longer, it will capture more data.
Cursor 1 Check box Check “Cursor 1” to active cursor. Click on screen to
move white mark and show X, Y axis value.
Cursor 2 Check box Check “Cursor 2”to active cursor. Click on screen to
move white mark and show X, Y axis value.
Save Check box if “Save” is checked on, the measurement data will be
stored.
21 / 44
Hauptstraße 119 – 121 Telefon +49-6205-3948-0 E-Mail [email protected] D-68804 Altlußheim Telefax +49-6205-37560 Web www.et-system.de
Pause (Reading) Button The function of this button can be switched between
“reading” and “pause”. In “reading” function, real-time
waveforms are displayed; and when “pause”,
waveforms can be operated and played back.
Restore Button While ‘Save’ is checked on, the stored waveform will
displayed on the wave window.
Zoom In Button Only functional when “pause”.
History Data Button Clicking this button will invoke the History Data
window. History Data is to be described in the following
chapters.
2.6 Fault Monitoring
While the indicator of test windows turns red, specific faults can be viewed in the
window by click ‘Fault’ menu. The Fault window is shown as Figure 2-16.
Figure 2-16 Fault Window
The Fault monitoring window shows details of faults. There is no error if indicators
are “Green”, otherwise indicators turn “Red”. Click [Reset] button to reset the system
after faults are removed. If faults are not cleared, restart the system. Contact factory
if the faults CANNOT be cleared.
22 / 44
Hauptstraße 119 – 121 Telefon +49-6205-3948-0 E-Mail [email protected] D-68804 Altlußheim Telefax +49-6205-37560 Web www.et-system.de
2.7 Query
In this section, the functions of history log and history data is provided for browsing
history information.
2.7.1 History Log
Clicking ‘History Log’ option in Query menu, the history log function will be invoked,
and the alarm history and historical events within 30 days are displayed. The log
information including time of event and fault. And the logs fall into two categories of
alarm history and event history.
Figure 2-17 History Log Window
Alarm history records alarm history within 30 days, and Event history records
operation history within 30 days.
2.7.2 History Data
Select file name or group name, get a thumbnail waveform ‘File Content’: Read saved
file by default; or click ‘Read Wave’ to open file path, and choose which file to read.
23 / 44
Hauptstraße 119 – 121 Telefon +49-6205-3948-0 E-Mail [email protected] D-68804 Altlußheim Telefax +49-6205-37560 Web www.et-system.de
Figure 2-18 History Data Window
Label
Operation Description
Attribution
Read Wave Button Read waveform data. "Start time" and "Sampling time"
determine the data to be read.
Zoom in Button Zoom in waveform between white dash line and green
dash line
Restore Button Restore all waveforms.
24 / 44
Hauptstraße 119 – 121 Telefon +49-6205-3948-0 E-Mail [email protected] D-68804 Altlußheim Telefax +49-6205-37560 Web www.et-system.de
Chapter 3 Remote Control
3.1 Computer Setting
The remote-control software uses LAN interface to communicate with the power
supply. Before launching the remote-control software, network configuration of
computer that remote-control software is running should be configured as following
table.
IP Adress 192.168.1.X (X can be any number between 3 and 254)
Subnet Mask 255.255.255.0
STEP A:
Before the control software is installed on the remote computer, please download the
“LabVIEW Run-Time Engine 2014 SP1 - (32-bit) - Windows”, the file name
downloaded is “LVRTE2014SP1_f7Patchstd.exe”. The web link is:
http://www.ni.com/download/labview-run-time-engine-2014-sp1/5198/en/
While the file is downloaded, please install the “LabVIEW Run-Time Engine 2014
SP1 - (32-bit) - Windows”.
STEP B:
Unzip and copy the remote-control software “DC Software 1.0(Client).rar” to some
directory wanted, and then create desktop shortcuts for executable file “DC Software
1.0.exe”.
STEP C:
Run the desktop shortcuts for executable file “DC Software 1.0.exe” as administrator,
all facilities of the software is available.
3.2 Software Setting
And the default network configuration of power supply is shown in table below.
Network configuration can be activated in ‘communication’ option of ‘configuration’
menu. However, it is not recommended to change the default configuration. The
network configuration page is shown as figure 3-1.
IP Adress 192.168.1.2
Port 502
25 / 44
Hauptstraße 119 – 121 Telefon +49-6205-3948-0 E-Mail [email protected] D-68804 Altlußheim Telefax +49-6205-37560 Web www.et-system.de
Figure 3-1 Network Configuration
3.3 Remote Control
The remote-control software has same outline of interface and operation with the
software embedded on the power supply’s controller. If the remote-control mode is
desired, method of operation refers to chapter 3.
CAUTION
The power can be controlled via the GUI control software on the touch
panel and remote-control software at the same time, but it’s not
recommended. The proposed approach is that one of the control software
controls the operation of the power supply and the other monitors the
operating parameters.
26 / 44
Hauptstraße 119 – 121 Telefon +49-6205-3948-0 E-Mail [email protected] D-68804 Altlußheim Telefax +49-6205-37560 Web www.et-system.de
Appendix A — Specification of SLV1 Series
General Specification
Model2
SLV1 20 SLV1 40 SLV1 60 SLV1 100 SLV1 200 SLV1 300 SLV1 500
Rated Power 20kW 40kW 60kW 100kW 200kW 300kW 500kW
Current Range
5~150V 0~±133A 0~±267A 0~±400A 0~±667A 0~±1333A 0~±2000A 0~±3333A
5~300V 0~±67A 0~±133A 0~±200A 0~±333A 0~±667A 0~±1000A 0~±1667A
Voltage
5~600V 0~±33A 0~±67A 0~±100A 0~±167A 0~±333A 0~±500A 0~±833A Spec.
5~1000V 0~±20A 0~±40A 0~±60A 0~±100A 0~±200A 0~±300A 0~±500A
5~1500V 0~±13A 0~±27A 0~±40A 0~±67A 0~±133A 0~±200A 0~±333A
Max Current3
35A 70A 105A 175A 350A 525A 875A
Environment Specification
Operating Temperature 0℃ to +40℃, full load
Cooling Forced air cooling
Humidity 20~80% RH (no condensing)
Electrical Specification
Voltage supply L-L: 380V@50Hz, 3 Phase + N + PE
Operation Mode CV, CC, CP and optional CR
Efficiency ≥ 90%
Power Factor ≥ 0.95
Program Accuracy of Voltage 0.1 % of F.S.
Program Accuracy of Current 0.3 % of F.S.
Program Accuracy of Power 0.3 % of F.S.
Program Resolution of Voltage 0.2‰ of F.S.
Program Resolution of Current 0.2‰ of F.S. 2 The Full model name refer to Options Section. For SLV1 20, it identifies the power of product is 20kW
3 For line current at 360V LL
27 / 44
Hauptstraße 119 – 121 Telefon +49-6205-3948-0 E-Mail [email protected] D-68804 Altlußheim Telefax +49-6205-37560 Web www.et-system.de
Program Resolution of Power 0.2‰ of F.S.
Ripples &Noises 0.1 % of F.S.
Line Regulation 0.1 % of F.S.
Load Regulation 0.1 % of F.S. (typ)
Over Current X1.2, 60 seconds
Current rise time (10% to + 90%) < 5 ms (200 V, 800 V), <7.5 ms (1500 V)
Current rise time (-90% to + 90%) < 10 ms
Regulation time < 8 ms (0 - 100 % load change)
Short circuit proof < 2.0 KA
Overvoltage protection 0 – 110 % Umax
Overcurrent protection 0 – 110 % Imax
Protection type IP 20
Isolation between Line to Chassis 20MΩ,1kV
Output to Chassis 20MΩ,1kV
Communication Specification
Communication interface 100Mbps LAN
Communication protocol SCPI / TCP-IP
Mechanical specification
Model Dimensions / H×D×W Weight
SLV1-20-150 1700mm × 800mm × 800mm 800 Kg
SLV1-20-300 1700mm × 800mm × 800mm 800 Kg
SLV1-20-600 1700mm × 800mm × 800mm 800 Kg
SLV1-20-1000 2100mm × 800mm × 800mm 1100 Kg
SLV1-20-1500 1300mm × 800mm × 800mm 1300 Kg
SLV1-40-150 1700mm × 800mm × 800mm 900 Kg
SLV1-40-300 1700mm × 800mm × 800mm 900 Kg
SLV1-40-600 1700mm × 800mm × 800mm 900 Kg
28 / 44
Hauptstraße 119 – 121 Telefon +49-6205-3948-0 E-Mail [email protected] D-68804 Altlußheim Telefax +49-6205-37560 Web www.et-system.de
SLV1-40-1000 2100mm × 800mm × 800mm 1200 Kg
SLV1-40-1500 2300mm × 800mm × 800mm 1400 Kg
SLV1-60-150 1900mm × 800mm × 800mm 1000 Kg
SLV1-60-300 1900mm × 800mm × 800mm 1000 Kg
SLV1-60-600 1900mm × 800mm × 800mm 1000 Kg
SLV1-60-1000 2300mm × 800mm × 800mm 1300 Kg
SLV1-60-1500 1900mm × 800mm × 1600mm 1500 Kg
SLV1-100-150 1900mm × 800mm × 1600mm 1800 Kg
SLV1-100-300 1900mm × 800mm × 1000mm 1800 Kg
SLV1-100-600 1900mm × 800mm × 1000mm 1800 Kg
SLV1-100-1000 1900mm × 800mm × 1600mm 1800 Kg
SLV1-100-1500 1900mm × 800mm × 1600mm 2000 Kg
SLV1-200-150 2100mm × 800mm × 2400mm 3000 Kg
SLV1-200-300 2100mm × 800mm × 1600mm 2600 Kg
SLV1-200-600 2100mm × 800mm × 1600mm 2600 Kg
SLV1-200-1000 2100mm × 800mm × 2400mm 3000 Kg
SLV1-200-1500 2100mm × 800mm × 1600mm 2800 Kg
SLV1-300-150 2300mm × 800mm × 2400mm 3400 Kg
SLV1-300-300 2300mm × 800mm × 1600mm 2800 Kg
SLV1-300-600 2300mm × 800mm × 1600mm 2600 Kg
SLV1-300-1000 2300mm × 800mm × 2400mm 3200 Kg
SLV1-300-1500 2300mm × 800mm × 2400mm 3600 Kg
SLV1-500-150 2300mm × 800mm × 3200mm 4600 Kg
SLV1-500-300 2300mm × 800mm × 2400mm 3800 Kg
SLV1-500-600 2300mm × 800mm × 2400mm 3800 Kg
SLV1-500-1000 2300mm × 800mm × 2400mm 4000 Kg
SLV1-500-1500 2300mm × 800mm × 2400mm 4000 Kg
29 / 44
Hauptstraße 119 – 121 Telefon +49-6205-3948-0 E-Mail [email protected] D-68804 Altlußheim Telefax +49-6205-37560 Web www.et-system.de
Options
S L V 1 - 1 0 0 - 1 0 0 0 - X X X
Options
Voltage:1000V
Power:100kW
Bidirectional DC Source
Options Description
- CCR Customized current range, contact factory
- CVR Customized voltage range, contact factory
- PV Simulate I-V curves of various solar panels
- CR Constant Resister Mode
1. Specifications are warranted over an ambient temperature range of 25°± 5° C. Note: For applications over 500kW, capacity increases can be achieved in parallel, and maximum
capacity up to 1000kW.
30 / 44
Hauptstraße 119 – 121 Telefon +49-6205-3948-0 E-Mail [email protected] D-68804 Altlußheim Telefax +49-6205-37560 Web www.et-system.de
Appendix B — Specification of BSS Series
General Specification
Model4
BSS 20
BSS 40
BSS 60
BSS 100
BSS 200
BSS 300
BSS 500
Rated Power 20kW 40kW 60kW 100kW 200kW 300kW 500kW
Current Range
0~150V 0~±266A 0~±534A 0~±800A 0~±1334A 0~±2666A 0~±4000A 0~±6666
A
0~300V 0~±134A 0~±266A 0~±400A 0~±666A 0~±1334A 0~±2000A 0~±3334
A
Voltage
0~600V 0~±66A
0~±134A
0~±200A
0~±334A
0~±666A
0~±1000A
0~±1666A Spec.
0~1000V 0~±40A 0~±80A 0~±120A 0~±200A 0~±400A 0~±600A 0~±1000
A
0~1500V 0~±26A 0~±54A 0~±80A 0~±134A 0~±266A 0~±400A 0~±666A
Max Current5
35A 70A 105A 175A 350A 525A 875A
Environment Specification
Operating Temperature 0℃ to +40℃, full load
Cooling Forced air cooling
Humidity 20~80% RH (no condensing)
Electrical Specification
Voltage supply L-L: 380V@50Hz, 3 Phase + N + PE
Operation Mode CV, CC, CP and optional CR
Efficiency ≥ 90%
Power Factor ≥ 0.95
Program Accuracy of Voltage 0.1% of F.S.
Program Accuracy of Current 0.1% of F.S.
Program Accuracy of Power 0.1% of F.S.
Program Resolution of Voltage 0.02% of F.S.
Program Resolution of Current 0.02% of F.S.
4 The Full model name refer to Options Section. For BSS 20, it identifies the power of product is 20kW
5 For line current at 360V LL
31 / 44
Hauptstraße 119 – 121 Telefon +49-6205-3948-0 E-Mail [email protected] D-68804 Altlußheim Telefax +49-6205-37560 Web www.et-system.de
Program Resolution of Power 0.02% of F.S.
Ripples &Noises 0.1 % of F.S.
Line Regulation 0.1 % of F.S.
Load Regulation 0.1 % of F.S. (typ)
Over Current X1.2, 60 seconds
Current rise time (10% to + 90%) < 1 ms (200 V, 800 V), <1.3 ms (1500 V)
Current rise time (-90% to + 90%) < 2 ms
Regulation time < 1.5 ms (0 - 100 % load change)
Short circuit proof < 2.0 KA
Overvoltage protection 0 – 110 % Umax
Overcurrent protection 0 – 110 % Imax
Protection type IP 20
Isolation between Line to Chassis 20MΩ,1kV
Output to Chassis 20MΩ,1kV
Communication Specification
Communication interface 100Mbps LAN
Communication protocol SCPI / TCP-IP
Mechanical specifications
Model Dimensions / H×D×W Weight
BSS -20-150 1700mm × 800mm × 800mm 800 Kg
BSS -20-300 1700mm × 800mm × 800mm 800 Kg
BSS -20-600 1700mm × 800mm × 800mm 800 Kg
BSS -20-1000 2100mm × 800mm × 800mm 1100 Kg
BSS -20-1500 2300mm × 800mm × 800mm 1300 Kg
BSS -40-150 2100mm × 800mm × 800mm 1200 Kg
BSS -40-300 1700mm × 800mm × 800mm 900 Kg
BSS -40-600 1700mm × 800mm × 800mm 900 Kg
32 / 44
Hauptstraße 119 – 121 Telefon +49-6205-3948-0 E-Mail [email protected] D-68804 Altlußheim Telefax +49-6205-37560 Web www.et-system.de
BSS -40-1000 2100mm × 800mm × 800mm 1200 Kg
BSS -40-1500 2300mm × 800mm × 800mm 1400 Kg
BSS -60-150 2300mm × 800mm × 800mm 1300 Kg
BSS -60-300 1900mm × 800mm × 800mm 1000 Kg
BSS -60-600 1900mm × 800mm × 800mm 1000 Kg
BSS -60-1000 2300mm × 800mm × 800mm 1300 Kg
BSS -60-1500 1900mm × 800mm × 1600mm 1500 Kg
BSS -100-150 2300mm × 800mm × 1600mm 2400 Kg
BSS -100-300 1900mm × 800mm × 1600mm 1800 Kg
BSS -100-600 1900mm × 800mm × 1000mm 1800 Kg
BSS -100-1000 1900mm × 800mm × 1600mm 1800 Kg
BSS -100-1500 2300mm × 800mm × 1600mm 2200 Kg
BSS -200-150 1900mm × 800mm × 3200mm 4600 Kg
BSS -200-300 1900mm × 800mm × 2400mm 3400 Kg
BSS -200-600 2100mm × 800mm × 1600mm 2600 Kg
BSS -200-1000 1900mm × 800mm × 2400mm 3400 Kg
BSS -200-1500 1900mm × 800mm × 2400mm 3200 Kg
BSS -300-150 2100mm × 800mm × 4000mm 5600 Kg
BSS -300-300 2300mm × 800mm × 2400mm 4400 Kg
BSS -300-600 2300mm × 800mm × 1600mm 2800 Kg
BSS -300-1000 2100mm × 800mm × 2400mm 4000 Kg
BSS -300-1500 2300mm × 800mm × 2400mm 4400 Kg
BSS -500-150 2300mm × 800mm × 5600mm 8800 Kg
BSS -500-300 2300mm × 800mm × 3200mm 4600 Kg
BSS -500-600 2300mm × 800mm × 2400mm 3800 Kg
BSS -500-1000 2300mm × 800mm × 2400mm 4000 Kg
BSS -500-1500 2300mm × 800mm × 2400mm 4000 Kg
33 / 44
Hauptstraße 119 – 121 Telefon +49-6205-3948-0 E-Mail [email protected] D-68804 Altlußheim Telefax +49-6205-37560 Web www.et-system.de
Options
B S S - 1 0 0 - 1 0 0 0 - X X X
Options
Voltage:1000V
Power:100kW
Battery SImulation Source/Sink
Options Description
- CCR Customized current range, contact factory
- CVR Customized voltage range, contact factory
- PV Simulate I-V curves of various solar panels
- CR Constant Resister Mode
1. Specifications are warranted over an ambient temperature range of 25°± 5° C. Note: For applications over 500kW, capacity increases can be achieved in parallel, and maximum
capacity up to 1000kW.
34 / 44