lab report power quality 1

Upload: hakimkmk

Post on 06-Jul-2018

221 views

Category:

Documents


1 download

TRANSCRIPT

  • 8/18/2019 Lab Report Power Quality 1

    1/25

     

    LAB REPORT

    KKKZ 4044 POWER QUALITY LAB 1

    SESSION 2015/2016

    SINGLE PHASE POWER QUALITY MACHINE

    NAME : ABDUL HAKIM BIN ABDULLAH

    MATRIC ID : A 141188LECTURER : PROF. DR. M. A. HANNAN

    DEMO : MOHD FIRDAUS HAFIDZUDDIN

  • 8/18/2019 Lab Report Power Quality 1

    2/25

      1

    1.0 

    ABSTRACT

    Single phase machine normally is not very sensitive as three phase machine since the load

    for single phase usually consume low voltage demand compared to load in the industrial

    area which demand high voltage in its load system. Moreover, the load for single phase

    are not seem to be affected if power quality problem such as voltage sag, voltage swell orflicker occurs. But it may affected if the high power load was connected in the electrical

    system such as air conditioning, refrigerator and microwave was used at the same time

    using inappropriate electrical connection. In other cases, circuit breaker in industrial

    factories may tripped if the voltage supply not enough for load consumption in three

     phase machine because it is very sensitive to any power quality problem in the electrical

    system. Fluke 434 Power Quality Analyzer is an electrical equipment which is used in

    this experiment to locate, predict, prevent and troubleshoot problems in three- and

    single-phase power distribution systems. Troubleshooting is faster with on-screen display

    of trends and captured events, even while background recording continues. The new IEC

    (International Electrotechnical Commission) standards for transient, flicker, harmonics

    and power quality are built right in to take the guess work out of power quality. In this

    experiment, we have used NE9102 Distribution Trainer and Induction Motor as load to

    test the Fluke 434 Power Quality Analyzer to view the effect on dips & swells, transients,

    flicker and harmonics.

    2.0 INTRODUCTION

    A utility may define power quality as reliability and show statistics demonstrating that its

    system is 99.98 percent reliable. Criteria established by regulatory agencies are usually in

    this vein. A manufacturer of load equipment may define power quality as thosecharacteristics of the power supply that enable the equipment to work properly. These

    characteristics can be very different for different criteria. Power quality is ultimately a

    consumer-driven issue, and the end user’s point of reference takes precedence.  In general,

     power quality problem can be defined as any occurrence manifested in voltage, current or

    frequency deviations which results in failure or frequency deviations which results in

    failure or misoperation of end-use equipment.

    There are many misunderstandings regarding the causes of power quality problems.

    Figure 1 below show the result of the survey conducted by Courtesy of Georgia Power

    Company. Power quality sources can cause from inside and outside of the electrical

    system. For examples single phase to ground shorts on the distribution system, lightning,

    weather, utility switching, equipment failure, human error, common mode transients from

    load switching, grounding problem, load interactions, harmonic generating loads and total

    harmonic distortions.

  • 8/18/2019 Lab Report Power Quality 1

    3/25

      2

    Figure 1 : Results of a survey on the causes of power quality problems. (Courtesy of

    Georgia Power Co.)

    In a single phase electrical system, there are many types of power quality problem may

    occurs. Voltage sag, voltage swell, transient, harmonic distortion, electrical noise,

    flickering, notching and spikes are example of power quality problem in electrical system.

    There are a few method which can be used to overcome this power quality problem. For

    example, voltage sag problem can be solve by using mitigating devices such as

    ferroresonant transformer, magnetic synthesizers, active series compensator, UPS systems,

    motor generator set, dynamic voltage restorer, static transfer switch, flywheel energy

    storage systems and superconductor magnetic energy storage (SMES) device.

    3.0 METHODOLOGY

    1. Phase A(L1) conductor in main switchboard panel was clamped with current clamp of

    Fluke 434.

    2. Banana-inputs was connected to ground, phase A(L1) and neutral conductor for voltage

    connection. Phase 2(L2) was connected to investigate the line-to-line voltage.

    3. Choose single phase split phase configuration on the analyzer.

    4. Configure the nominal voltage and frequency of the single phase power system for the

    analyzer.

    5. Press the Menu button to enter measurement menu of the analyzer.

    6. Select Volts/Amps/Hertz   option to measure the voltage, current, frequency and crest

    factor for phase L1, L2 and Neutral of single phase power system before introducing any

    disturbance in the system. Observe the numerical values of the Volts/Amps/Hertz table.

  • 8/18/2019 Lab Report Power Quality 1

    4/25

      3

    Then, observe the waveforms trends of the voltage and current of the single phase power

    system.

    7. Repeat step 5 and select  Dips & Swells option to measure and record the numerical

    values and waveform trends of voltage and current for phase L1, L2 and Neutral of single

     phase power system before and after the disturbance injected into the power system.8. Switch on the distribution trainer, induction motor set and DC compound wound motor

    set consecutively for a few seconds to create a power quality disturbance in the system.

    Observe the waveform trends of the phases and neutral voltages and current.

    9. Record and compare the minimum and nominal values of each set of measurement.

    10. Repeat step 7 to select  Harmonics option to measure and record the numerical values

    and waveform trends of the voltage and current harmonics and Total Harmonics

    Disturbance (THD) value for phase L1, L2 and Neutral of single phase power system

     before and after the disturbance is injected into the power system. Repeat step 8. Observe

    the bar graphs of the phase and neutral current and voltage and record the THD value.

    11. Repeat step 7 and select Flicker  option. Leave the analyzer for measurement without

    any disturbance for one minutes to obtain the short-term flicker value Pst (1 min). Turn

    on and off the lighting switch of the fluorescent lamps on the table in the laboratory

    repeatedly and continuously for 1 minutes. Then, record the short-term flicker value Pst

    (1 min) and observe the flicker waveform trend. Then, wait another 1 minute for whole

    system settling down and record the short-term flicker value Pst (1 min) and observe

    flicker waveform trend again.

    12. Repeat step 7 and select Transients option. Repeat step 8 and observe the current and

    voltage waveforms for phase L1, L2 and Neutral of the single phase power system.Record the numerical values appear on the screen.

    4.0 RESULTS 

    4.1 Setup Configuration

    Before conducting the experiment we need to configure the nominal voltage and

    frequency. Figure 4.1 shows the result of configuring the nominal voltage and frequency

    of the single phase power system. The single phase connection from banana-input can beview in the setup configuration as shown in figure 2.

  • 8/18/2019 Lab Report Power Quality 1

    5/25

      4

    Figure 2 : Nominal voltage and frequency Figure 3 : Single phase connection

    4.2 Volts/Amps/Hertz

    Figure 4 : Numerical value for star

    connection

    Figure 5 : Numerical value for delta

    connection

    Figure 4 and 5 shows the differences between numerical value of star and delta

    connection. In figure 5, the phase L1 and L2 share the same value of their own rms

    voltage, peak voltage, crest factor and frequency. Moreover, rms current, peak current and

    crest factor for L2 was not displayed in the analyzer screen. Earlier, the nominal

    frequency was 50 Hz was decreases to 49.96 Hz.  A change in system frequency willcause change in speed of motors, change in magnetizing current will be there for

    transformers and induction motors will be affected with change in inductances. A huge

    increase will cause increase in harmonic currents and will cause heating of the system

    with insulation failure. Frequency of a system also decides the real power balance in a

     power system as line parameters will change with change in frequency. Figure 15 shows

    the nominal frequency of the single phase power system.

  • 8/18/2019 Lab Report Power Quality 1

    6/25

      5

    Figure 6 : Phase L1 Vrms Figure 7 : Phase L1 Irms 

    Figure 8 : Phase L2 Vrms  Figure 9 : Phase L2 Irms 

    Figure 10 : Phase N Vrms  Figure 11 : Phase N Irms 

  • 8/18/2019 Lab Report Power Quality 1

    7/25

      6

    Figure 12 : Phase L1 I peak   Figure 13 : Crest factor

    Figure 14 : Phase L2 I peak   Figure 15 : Nominal frequency

    Figure 16 : Phase N I peak  

  • 8/18/2019 Lab Report Power Quality 1

    8/25

      7

    4.3 Dips & Swell

    Figure 17 : Phase L1 Irms before disturbance Figure 18 : Phase L1 Vrms before disturbance

    Figure 19 : Phase L2 Irms before disturbance Figure 20 : Phase L2 Vrms before disturbance

    Figure 21 : Phase N Irms before disturbance Figure 22 : Phase N Vrms before disturbance

  • 8/18/2019 Lab Report Power Quality 1

    9/25

      8

    Figure 23 : Phase L1 Irms during disturbance Figure 24 : Phase L1 Vrms during disturbance

    Figure 25 : Phase L2 Irms during disturbance Figure 26 : Phase L2 Vrms during disturbance

    Figure 27 : Phase N Irms during disturbance Figure 28 : Phase N Vrms during disturbance

  • 8/18/2019 Lab Report Power Quality 1

    10/25

      9

    Figure 29 : Phase L1 Irms after disturbance Figure 30 : Phase L1 Vrms after disturbance

    Figure 31 : Phase L2 Irms after disturbance Figure 32 : Phase L2 Vrms after disturbance

    Figure 33 : Phase N Irms after disturbance Figure 34 : Phase N Vrms after disturbance

  • 8/18/2019 Lab Report Power Quality 1

    11/25

      10

    Figure 17 until 22 shows the Irms  and Vrms of the phase L1, L2 and Neutral before the

     power system experienced the load disturbance. From all those figures, we can see the

    waveform trends of all the phases are most likely to be smooth without any power quality

     problem either voltage dips or swells in this case. But it still occurs in small scale as can

     be seen in figure 18 and 20. This problems are causes by the switching on or off the load

    from other room at the old faculty building.

    Figure 23 until 28 shows the Irms  and Vrms of the phase L1, L2 and Neutral during the

     power system experienced the load disturbance. Figures in this range had shown a lot of

     problem compared to the previous waveform trends before injecting the load disturbance.

    All the phases for rms currents and voltages for phase L1, L2 and Neutral during load

    disturbance shows a dips and swells in their trends since the load was switch on at the

    same room as the fluke meter was measured.

    Figure 29 until 34 shows the Irms and Vrms of the phase L1, L2 and Neutral after the power

    system experienced the load disturbance. In this situation, the load was switch off but it

    seem to have few dips and swells before it was stabilize into its steady state voltage and

    current after switching off the load. The correct waveform trends should be taken few

    minutes later after switching the load to observe a correct waveform trends.

    The 90% level provides an indication of performance for the most sensitive equipment.

    The 80% level corresponds to an important break point on the ITI curve and some

    sensitive equipment may be susceptible to even short sags at this level. The 70% levelcorresponds to the sensitivity level of a wide group of industrial and commercial

    equipment and is probably the most important performance level to specify. The 50%

    level is important, especially for the semiconductor industry, since they have adopted a

    standard that specifies ride through at this level.

    Interruptions affect all customers so it is important to specify this level separately. These

    will usually have longer durations than the voltage sags. The first range of durations is up

    to 0.2 seconds (12 cycles at 60 Hz). This is the range specified by the semiconductor

    industry that equipment should be able to ride through sags as long as the minimum

    voltage is above 50%. The second range is up to 0.5 seconds. This corresponds to the

    specification in the ITIC standard for equipment ride through as long as the minimum

    voltage is above 70%. It is also an important break point in the definition of sag durations

    in IEEE 1159 (instantaneous vs. momentary). The third duration range is up to 3 seconds.

    This is an important break point in IEEE 1159 and in IEC standards (momentary to

    temporary).

  • 8/18/2019 Lab Report Power Quality 1

    12/25

      11

    4.4 Harmonics

    Figure 35 : THD Voltage before disturbance Figure 36 : THD Voltage after disturbance

    Figure 37 : THD current before disturbance Figure 38 : THD current after disturbance

    Figure 39 : THD power before disturbance Figure 40 : THD power after disturbance

  • 8/18/2019 Lab Report Power Quality 1

    13/25

      12

    Harmonic distortion originates in the nonlinear characteristics of devices and loads on the

     power system. Harmonic distortion levels are described by the complete harmonic

    spectrum with magnitudes and phase angles of each individual harmonic component. It is

    also common to use a single quantity, the total harmonic distortion (THD), as a measure

    of the effective value of harmonic distortion.Figure 35 shows the THD voltage with value

    1.6% drop to 1.5% after injecting load disturbance as shown in figure 36. In figure 37 and38 the THD current was drop drastically from 187.9% to 43.2%. In a while, figure 39 and

    40 shows a drop from 1.0% to 1.1% after injecting the load disturbance into the power

    system.

    IEEE Standard 519-2014 is a standard developed for utility companies and their

    customers in order to limit harmonic content and provide all users with better power

    quality. Some of the key areas of the standard are detailed in the following tables. Bear in

    mind that dealing with harmonics may still be required, whether or not the goal is to meet

    IEEE 519 standards. In low-voltage systems (600 V or less), capacitors are typically thelowest impedance at harmonic frequencies, and experience very high RMS currents and

    increased heat which causes them to fail.

  • 8/18/2019 Lab Report Power Quality 1

    14/25

      13

    4.5 Flicker

    Figure 41 : Before load disturbance Figure 42 : During load disturbance

    Figure 43 : Settling down after load

    disturbance

    Figure 44 : Flicker waveform trend

    From figure 41 until 43, the short-term flicker (Pst) for phase L1 increases from 0.08 to

    0.14 while decreases from 0.14 to 0.07 for phase L2. The flicker signal is defined by its

    rms magnitude expressed as a percent of the fundamental. Voltage flicker is measured

    with respect to the sensitivity of the human eye. Typically, magnitudes as low as 0.5

     percent can result in perceptible lamp flicker if the frequencies are in the range of 6 to 8

    Hz. In this case, the frequency is not affected by the load disturbance then producing the

    normal flicker waveform trend without any critical power quality problem as shown in

    figure 44.

    IEC 61000-4-15 defines the methodology and specifications of instrumentation for

    measuring flicker. The IEEE Voltage Flicker Working Group has recently agreed to adopt

    this standard as amended for 60 Hz power systems for use in North America. This

  • 8/18/2019 Lab Report Power Quality 1

    15/25

      14

    standard devises a simple means of describing the potential for visible light flicker

    through voltage measurements. The measurement method simulates the lamp/eye/brain

    transfer function and produces a fundamental metric called short-term flicker sensation

    (Pst). This value is normalized to 1.0 to represent the level of voltage fluctuations

    sufficient to cause noticeable flicker to 50 percent of a sample observing group. Another

    measure called long-term flicker sensation (Plt) is often used for the purpose of verifyingcompliance with compatibility levels established by standards bodies and used in utility

     power contracts. This value is a longer-term average of Pst samples.

    4.6 Transients

    Figure 45 : Voltages before load disturbance Figure 46 : Voltages during load disturbance

    Figure 47 : Currents before load disturbance Figure 48 : Currents during load disturbance

  • 8/18/2019 Lab Report Power Quality 1

    16/25

      15

    Figure 49 : Phase Neutral before disturbance Figure 50 : Phase Neutral during disturbance

    Figure 51 : Phase L1 before disturbance Figure 52 : Phase L1 during disturbance

    Figure 53 : Phase L2 before disturbance Figure 54 : Phase L2 during disturbance

  • 8/18/2019 Lab Report Power Quality 1

    17/25

      16

    Figure 55 : Voltages after load disturbance Figure 56 : Currents after load disturbance

    Figure 57 : Phase Neutral after disturbance Figure 58 : Phase L1 after disturbance

    Figure 59 : Phase L2 after disturbance Figure 60 : Transients configuration

  • 8/18/2019 Lab Report Power Quality 1

    18/25

      17

    Figure 45 until 54, shows the differences of waveform trends between the condition

     before injecting the load disturbance and during injected load disturbance. It seem to have

    some problem in power quality during the load disturbance as shown in figure 48, 50, 52

    and 54. However, the waveform trends of the transient return to be same as before

    injecting the load when the load disturbance was turned off.

    Transients are power quality disturbances that involve destructive high magnitudes of

    current and voltage or even both. It may reach thousands of volts and amps even in low

    voltage systems. However, such phenomena only exist in a very short duration from less

    than 50 nanoseconds to as long as 50 milliseconds. This is the shortest among power

    quality problems, hence, its name. Transients usually include abnormal frequencies,

    which could reach to as high as 5 MHz. Transients are also known as surge. According to

    IEEE 100, surge is a transient wave of voltage, current or power in an electric circuit.

    Other IEEE definitions suggest that it is the part of the change in a variable that

    disappears during transition from one steady-state operating condition to another. Suchdescription is too vague, which could be used to describe just about any unusual events

    occurring in the electrical system. Moreover, most electrical engineers would refer to the

    damped oscillatory transient phenomena in a RLC circuit when hearing such term.

    Sources of transients may come from switching activities such as opening and closing of

    disconnects on energized lines, capacitor bank switching, reclosing operations, tap

    changing on transformers, accidents, human error, animals and bad weather conditions

    and neighboring facilities. Damages due to such power quality problems are uncommon

    as compared to voltage sags(dips) and interruptions, but when it does occur it is moredestructive. To protect against transients, end-users may use Transient Voltage Surge

    Suppressors (TVSS), while utilities install surge arresters.

    5.0 DISCUSSION

    5.1 Dips & Swell

    A voltage sag also known as voltage dips is a decrease to between 0.1 and 0.9 p.u. in rms

    voltage or current at the power frequency for durations from 0.5 cycle to 1 min. The power quality community has used the term sag for many years to describe a

    short-duration voltage decrease. Although the term has not been formally defined, it has

     been increasingly accepted and used by utilities, manufacturers, and end users. The IEC

    definition for this phenomenon is dip. The two terms are considered interchangeable, with

    sag being the preferred synonym in the U.S. power quality community. Terminology used

    to describe the magnitude of a voltage sag is often confusing. A“20 percent sag” can refer

  • 8/18/2019 Lab Report Power Quality 1

    19/25

      18

    to a sag which results in a voltage of 0.8 or 0.2 p.u.. The preferred terminology would be

    one that leaves no doubt as to the resulting voltage level: “a sag to 0.8 p.u.” or “a sag

    whose magnitude was 20 percent.” When not specified otherwise, a 20 percent sag will

     be considered an event during which the rms voltage decreased by 20 percent to 0.8 p.u..

    The nominal, or base, voltage level should also be specified.

    Figure 61 : Voltage DipsA swell is defined as an increase to between 1.1 and 1.8 p.u. in rms voltage or current at

    the power frequency for durations from 0.5 cycle to 1 min. As with sags, swells are

    usually associated with system fault conditions, but they are not as common as voltage

    sags. One way that a swell can occur is from the temporary voltage rise on the unfaulted

     phases during a Single-Line to Ground (SLG) fault. Figure 62 illustrates a voltage swell

    caused by an SLG fault. Swells can also be caused by switching off a large load or

    energizing a large capacitor bank. Swells are characterized by their magnitude (rms value)

    and duration. The severity of a voltage swell during a fault condition is a function of the

    fault location, system impedance, and grounding. On an ungrounded system, with an

    infinite zero-sequence impedance, the line-to-ground voltages on the ungrounded phaseswill be 1.73 p.u. during an SLG fault condition. Close to the substation on a grounded

    system, there will be little or no voltage rise on the unfaulted phases because the

    substation transformer is usually connected delta-wye, providing a low-impedance

    zero-sequence path for the fault current. Faults at different points along four-wire, multi

    grounded feeders will have varying degrees of voltage swells on the unfaulted phases. A

    15 percent swell, like that shown in figure 62, is common on U.S. utility feeders. The

    term momentary overvoltage is used by many writers as a synonym for the term swell.

  • 8/18/2019 Lab Report Power Quality 1

    20/25

      19

    Figure 62 : Voltage Swells

    5.2 Harmonics

    Harmonics are sinusoidal voltages or currents having frequencies that are integer

    multiples of the frequency at which the supply system is designed to operate (termed the

    fundamental frequency; usually 50 or 60 Hz). Periodically distorted waveforms can be

    decomposed into a sum of the fundamental frequency and the harmonics. Harmonic

    distortion originates in the nonlinear characteristics of devices and loads on the power

    system. Harmonic distortion levels are described by the complete harmonic spectrum

    with magnitudes and phase angles of each individual harmonic component. It is also

    common to use a single quantity, the total harmonic distortion (THD), as a measure of the

    effective value of harmonic distortion. Figure 63 illustrates the waveform and harmonicspectrum for a typical adjustable-speed-drive (ASD) input current. Current distortion

    levels can be characterized by a THD value, as previously described, but this can often be

    misleading. For example, many adjustable-speed drives will exhibit high THD values for

    the input current when they are operating at very light loads. This is not necessarily a

    significant concern because the magnitude of harmonic current is low, even though its

    relative distortion is high. To handle this concern for characterizing harmonic currents in

    a consistent fashion, IEEE Standard 519-1992 defines another term, the total demand

    distortion (TDD). This term is the same as the total harmonic distortion except that the

    distortion is expressed as a percent of some rated load current rather than as a percent of

    the fundamental current magnitude at the instant of measurement. IEEE Standard

    519-1992 provides guidelines for harmonic current and voltage distortion levels on

    distribution and transmission circuits.

  • 8/18/2019 Lab Report Power Quality 1

    21/25

      20

    Figure 63 : Current waveform and harmonic spectrum for an ASD input current.

    5.3 Flicker

    Voltage fluctuations are systematic variations of the voltage envelope or a series of

    random voltage changes, the magnitude of which does not normally exceed the voltage

    ranges specified by American National Standard Institute (ANSI) C84.1 of 0.9 to 1.1 p.u.

    IEC 61000-2-1 defines various types of voltage fluctuations. We will restrict our

    discussion here to IEC 61000-2-1 Type (d) voltage fluctuations, which are characterized

    as a series of random or continuous voltage fluctuations. Loads that can exhibit

    continuous, rapid variations in the load current magnitude can cause voltage variations

    that are often referred to as flicker. The term flicker is derived from the impact of the

    voltage fluctuation on lamps such that they are perceived by the human eye to flicker. To

     be technically correct, voltage fluctuation is an electromagnetic phenomenon while

    flicker is an undesirable result of the voltage fluctuation in some loads. However, the two

    terms are often linked together in standards. Therefore, we will also use the common term

    voltage flicker to describe such voltage fluctuations. An example of a voltage waveformwhich produces flicker is shown in figure 64. This is caused by an arc furnace, one of the

    most common causes of voltage fluctuations on utility transmission and distribution

    systems. The flicker signal is defined by its rms magnitude expressed as a percent of the

    fundamental. Voltage flicker is measured with respect to the sensitivity of the human eye.

    Typically, magnitudes as low as 0.5 percent can result in perceptible lamp flicker if the

    frequencies are in the range of 6 to 8 Hz. IEC 61000-4-15 defines the methodology and

  • 8/18/2019 Lab Report Power Quality 1

    22/25

      21

    specifications of instrumentation for measuring flicker. The IEEE Voltage Flicker

    Working Group has recently agreed to adopt this standard as amended for 60Hz power

    systems for use in North America. This standard devises a simple means of describing the

     potential for visible light flicker through voltage measurements. The measurement

    method simulates the lamp/eye/brain transfer function and produces a fundamental metric

    called short-term flicker sensation (Pst). This value is normalized to 1.0 to represent thelevel of voltage fluctuations sufficient to cause noticeable flicker to 50 percent of a

    sample observing group. Another measure called long-term flicker sensation (Plt) is often

    used for the purpose of verifying compliance with compatibility levels established by

    standards bodies and used in utility power contracts. This value is a longer-term average

    of Pst samples.

    Figure 64 : Flicker

    5.4 Transients

    The term transients has long been used in the analysis of power system variations to

    denote an event that is undesirable and momentary in nature. The notion of a damped

    oscillatory transient due to an RLC network is probably what most power engineers think

    of when they hear the word transient. Other definitions in common use are broad in scope

    and simply state that a transient is “that part of the change in a variable that disappears

    during transition from one steady state operating condition to another.”  Unfortunately,

    this definition could be used to describe just about anything unusual that happens on the

     power system. A utility engineer may think of a surge as the transient resulting from a

    lightning stroke for which a surge arrester is used for protection. End users frequently use

    the word indiscriminantly to describe anything unusual that might be observed on the

     power supply ranging from sags to swells to interruptions. Because there are many

     potential ambiguities with this word in the power quality field, we will generally avoid

    using it unless we have specifically defined what it refers to. Transients can be classified

    into two categories, impulsive and oscillatory.

  • 8/18/2019 Lab Report Power Quality 1

    23/25

      22

    Figure 65 : Transients

    6.0 CONCLUSION

    Evolution of technology has create a lot of digital and graphical measuring devices in

    order to obtain and observe a data/result in a detail and efficient ways. Before digital and

    graphical device is used, analog device was a very important devices to be used in power

    system measurement. Nowadays, analog measuring devices was replaces by the digital

    and graphical measuring devices such as multimeter, oscilloscope, fluke clamp meter,

    insulation meter and many other devices. In this experiment, we are using fluke clamp

    meter to measure the voltage, current and frequency then observing the waveform trends

    of the power quality problem. The Fluke 434 power quality analyzers can locate, predict,

     prevent and troubleshoot problems in three- and single-phase power distribution systems.Troubleshooting is faster with on-screen display of trends and captured events, even

    while background recording continues. The new IEC standards for flicker, harmonics and

     power quality are built right in to take the guess work out of power quality.

  • 8/18/2019 Lab Report Power Quality 1

    24/25

      23

    Figure 66 : Summary of power quality problem

  • 8/18/2019 Lab Report Power Quality 1

    25/25

    7.0 REFERENCES 

    Roger C. Dugan, Mark F. McGranaghan, Surya Santoso, H. Wayne Beaty. Electrical

    Power System Quality. 2nd Edition.

    M. A. Hannan. 2016. Introduction to Power Quality. Lecture Slide.

    http://www.testequip.com/sale/details/HTS0174.html 

    http://ecmweb.com/power-quality-archive/power-quality-standards-industry-update 

    http://electrical-engineering-portal.com/9-most-common-power-quality-problems 

    http://www.power-solutions.com/power-quality 

    http://www.fluke.com/fluke/caen/community/fluke-news-plus/articlecategories/clamps/ac

    -dc-clamp-meter  

    https://www.quora.com/How-does-a-change-in-AC-frequency-affect-an-electrical-system 

    http://www.powerstandards.com/tutorials/sagsandswells.php 

    http://www.myronzucker.com/Asset/PDF-and-Excel-Charts/IEEE-519-Tables.html 

    http://www.testequip.com/sale/details/HTS0174.htmlhttp://www.testequip.com/sale/details/HTS0174.htmlhttp://ecmweb.com/power-quality-archive/power-quality-standards-industry-updatehttp://ecmweb.com/power-quality-archive/power-quality-standards-industry-updatehttp://electrical-engineering-portal.com/9-most-common-power-quality-problemshttp://electrical-engineering-portal.com/9-most-common-power-quality-problemshttp://www.power-solutions.com/power-qualityhttp://www.power-solutions.com/power-qualityhttp://www.fluke.com/fluke/caen/community/fluke-news-plus/articlecategories/clamps/ac-dc-clamp-meterhttp://www.fluke.com/fluke/caen/community/fluke-news-plus/articlecategories/clamps/ac-dc-clamp-meterhttp://www.fluke.com/fluke/caen/community/fluke-news-plus/articlecategories/clamps/ac-dc-clamp-meterhttps://www.quora.com/How-does-a-change-in-AC-frequency-affect-an-electrical-systemhttps://www.quora.com/How-does-a-change-in-AC-frequency-affect-an-electrical-systemhttp://www.powerstandards.com/tutorials/sagsandswells.phphttp://www.powerstandards.com/tutorials/sagsandswells.phphttp://www.myronzucker.com/Asset/PDF-and-Excel-Charts/IEEE-519-Tables.htmlhttp://www.myronzucker.com/Asset/PDF-and-Excel-Charts/IEEE-519-Tables.htmlhttp://www.myronzucker.com/Asset/PDF-and-Excel-Charts/IEEE-519-Tables.htmlhttp://www.powerstandards.com/tutorials/sagsandswells.phphttps://www.quora.com/How-does-a-change-in-AC-frequency-affect-an-electrical-systemhttp://www.fluke.com/fluke/caen/community/fluke-news-plus/articlecategories/clamps/ac-dc-clamp-meterhttp://www.fluke.com/fluke/caen/community/fluke-news-plus/articlecategories/clamps/ac-dc-clamp-meterhttp://www.power-solutions.com/power-qualityhttp://electrical-engineering-portal.com/9-most-common-power-quality-problemshttp://ecmweb.com/power-quality-archive/power-quality-standards-industry-updatehttp://www.testequip.com/sale/details/HTS0174.html