    PACiS System Devices

    Configuration

    PCL

    PACiS Configuration TrainingPACiS Configuration TrainingPACiS Configuration TrainingPACiS Configuration Training

    CS&PCS&PCS&PCS&P – –– – Support Team Support Team Support Team Support Team

  • 8/20/2019 L2 V4 01 System Devices Configuration E 01

    2/38

    Schneider Electric 2- CS&P – System Devices Configuration – E01

    PACiS OI Server Configuration

    PACiS OI Client Configuration

    C264 Configuration PACiS Gateway Configuration

    Labels in Datapoint profiles

    Devices Redundancy

    • Content

  • 8/20/2019 L2 V4 01 System Devices Configuration E 01

    3/38

    Schneider Electric 3- CS&P – System Devices Configuration – E01

    PACiS OI Server Configuration

    PACiS OI Client Configuration

    C264 Configuration PACiS Gateway Configuration

    Labels in Datapoint profiles

    Devices Redundancy

    • Content

  • 8/20/2019 L2 V4 01 System Devices Configuration E 01

    4/38

    Schneider Electric 4- CS&P – System Devices Configuration – E01

    Under SCS/Ethernet Network

    Add from Object Entry window

    PACiS OI Server Attributes

    Network name (Never HMI) + IP@

    MV computation period

    Max number of presence

    days for event/value in SQLHistorian database

    Periodic SQL Historian DB backup

    Good Practice

    155

    Note : use OI configured in starting database 

    Follow Good Practice for

    addressing

    • Add / Configure PACiS OI Server

  • 8/20/2019 L2 V4 01 System Devices Configuration E 01

    5/38

    Schneider Electric 5- CS&P – System Devices Configuration – E01

    Basic = System Infos + IEC Mapping

    Note : use OI configured in starting

    database, all system information arealready configured 

    List of System Information :Operating Mode,Synchronisation Status, ...

    IEC 61850 Mapping

    • PACiS OI Server Sons

  • 8/20/2019 L2 V4 01 System Devices Configuration E 01

    6/38

    Schneider Electric 6- CS&P – System Devices Configuration – E01

    Possible sons

    Klaxon for audible alarm

    Serial Printer

    Sequence of Events / System

    Log Book

    Printer Name as installed on thePC (spool name)for main and backup 

    • Printer

    Used when main printer breaks downUsed when main printer breaks downUsed when main printer breaks downUsed when main printer breaks downduring starting of backup printer during starting of backup printer during starting of backup printer during starting of backup printer 

    Used during orderingUsed during orderingUsed during orderingUsed during orderingprocess of dated eventsprocess of dated eventsprocess of dated eventsprocess of dated events

    • PACiS OI Server Sons

  • 8/20/2019 L2 V4 01 System Devices Configuration E 01

    7/38

    Schneider Electric 7- CS&P – System Devices Configuration – E01

    • Klaxon

    Klaxon action (immediate/defer) and

    acknowledgement (auto/manu).

    Klaxon can be executed on one SPC in

    one C264 (horn).If not configured => PACiS OI Server PCuses the buzzer

    Note : Relation “warns audibly” (gives an audible warning) to determine whichalarms are triggering the klaxon 

    Note 2 : The SPC must be direct execute, without dependency, withoutinterlock, with “on” and “off” orders possibility.

    • PACiS OI Server Sons

  • 8/20/2019 L2 V4 01 System Devices Configuration E 01

    8/38

    Schneider Electric 8- CS&P – System Devices Configuration – E01

    PACiS OI Server Configuration

    PACiS OI Client Configuration

    C264 Configuration PACiS Gateway Configuration

    Labels in Datapoint profiles

    Devices Redundancy

    • Content

  • 8/20/2019 L2 V4 01 System Devices Configuration E 01

    9/38

    Schneider Electric 9- CS&P – System Devices Configuration – E01

    Under SCS/Ethernet Network

    Add from Object Entry window

    PACiS OI Client Attributes

    Network name + IP@same if installed on same PC asOI Server 

    Follow Good Practice for

    addressing

    • Add / Configure PACiS OI Client

  • 8/20/2019 L2 V4 01 System Devices Configuration E 01

    10/38

    Schneider Electric 10- CS&P – System Devices Configuration – E01

    Basic = System Infos + Relation to OI Server + Relation to graphic part 

    Link Status :Status of the Link between OI Client andOI server 

    Link to OI Server- all clients are linked with PACiSOI Server Main or Backup.- At least 1 OI Client has to be

    connected on each OI Server.Link to graphic partthe client will show the views

    configured under the chosenworkspace 

    • PACiS OI Client Sons and Relations

  • 8/20/2019 L2 V4 01 System Devices Configuration E 01

    11/38

    Schneider Electric 11- CS&P – System Devices Configuration – E01

    PACiS OI Server Configuration

    PACiS OI Client Configuration

    C264 Configuration PACiS Gateway Configuration

    Labels in Datapoint profiles

    Devices Redundancy

    • Content

  • 8/20/2019 L2 V4 01 System Devices Configuration E 01

    12/38

    Schneider Electric 12- CS&P – System Devices Configuration – E01

    Under SCS/Ethernet Network

    Add from Object Entry window

    Note1 : use C264 configured in starting database 

    Note2 : create new C264 by copy/paste of existing one 

    • Add / Configure MiCOM C264

  • 8/20/2019 L2 V4 01 System Devices Configuration E 01

    13/38

    Schneider Electric 13- CS&P – System Devices Configuration – E01

    General Tab

    Network name + IP@

    Computer Name

    IRIG-B signal or not

    80TE=C264 / 40TE=C264C

    Follow Good Practice for

    addressing

    • MiCOM C264 Attributes

  • 8/20/2019 L2 V4 01 System Devices Configuration E 01

    14/38

    Schneider Electric 14- CS&P – System Devices Configuration – E01

    BI Filtering Tab

    Note : used for SPS, DPS and MPS acquisition on DI board 

    Toggling applied on validated signal 

    Toggling parameters

    Debouncing / Filtering => signal

    validation

    F ilt e r in g tim e

    t 0   t 1t 2

    D e b o u c in gt im e

    Debouncing / Filtering => signalvalidation 

    Timetag => t0 or t2 (configurable) 

    • MiCOM C264 Attributes

  • 8/20/2019 L2 V4 01 System Devices Configuration E 01

    15/38

    Schneider Electric 15- CS&P – System Devices Configuration – E01

    Measurements Tab

    Note 1 : Transmission periods are used if MV is declared as “periodic” 

    Long period = N x short period 

    AI board acquisition cycle

    Debouncing / Filtering => signal

    validation for Digital Measurements

    CT/VT board acquisition frequency(neighbourhood of 0)

    MV transmission cycle on SBUS andLHMI

    Note 2 : too small transmission periods values has strong impact on SQLHistorian database filling => default values are too small 

    • MiCOM C264 Attributes

  • 8/20/2019 L2 V4 01 System Devices Configuration E 01

    16/38

    Schneider Electric 16- CS&P – System Devices Configuration – E01

    Counter Tab

    Note : Applicable for single or double counters 

    Debouncing / Filtering => signal

    validation for counted Digital Input

    Miscellaneous Tab

    Avoid endless C264 reboot on faultdetection, define a number of faults

    acceptable during a period.

    • MiCOM C264 Attributes

  • 8/20/2019 L2 V4 01 System Devices Configuration E 01

    17/38

    Schneider Electric 17- CS&P – System Devices Configuration – E01

    Basic = System Infos + 3 boards (CPU,BIU,GHU) + IEC Mapping

    I/O Boards :Naming Good Practice : 

    Slot#__ 

    IEC 61850 Mapping

    Created by Automatic Addressingfunction 

    PLC Object

    C264 Automations 

    • MiCOM C264 Sons

  • 8/20/2019 L2 V4 01 System Devices Configuration E 01

    18/38

    Schneider Electric 18- CS&P – System Devices Configuration – E01

    Basic = System Infos + 3 boards (CPU,BIU,GHU) + IEC Mapping

    List of System Information :Operating Mode,Synchronisation Status, ...

    Note : use C264 configured in startingdatabase, all system information arealready configured 

    • MiCOM C264 Sons

  • 8/20/2019 L2 V4 01 System Devices Configuration E 01

    19/38

    Schneider Electric 19- CS&P – System Devices Configuration – E01

    Possible sons = Object Entry Window

    HardwareLBUS per protocol 

    TBUS

    Local C264 printer

    Add / Configure I/O board

    Note : another method is to copy/paste existing board 

    Physical Board Number Relation made by automatic @(to remove when duplication) 

    • MiCOM C264 Sons

  • 8/20/2019 L2 V4 01 System Devices Configuration E 01

    20/38

    Schneider Electric 20- CS&P – System Devices Configuration – E01

    PACiS OI Server Configuration

    PACiS OI Client Configuration

    C264 Configuration PACiS Gateway Configuration

    Labels in Datapoint profiles

    Devices Redundancy

    • Content

  • 8/20/2019 L2 V4 01 System Devices Configuration E 01

    21/38

    Schneider Electric 21- CS&P – System Devices Configuration – E01

    Under SCS/Ethernet NetworkAdd from Object Entry window

    Note1 : use GTW configured in starting database 

    PACiS GTW Attributes

    Network name + IP@

    Follow Good Practice foraddressing

    • Add / Configure PACiS Gateway

  • 8/20/2019 L2 V4 01 System Devices Configuration E 01

    22/38

    Schneider Electric 22- CS&P – System Devices Configuration – E01

    Basic = System Infos + 8 serial ports + IEC Mapping

    List of System Information :Operating Mode,Synchronisation Status, ...

    Note : use GTW configured in startingdatabase, all system information arealready configured IEC 61850 Mapping

    1 to 4 protocols with the

    relevant SCADA mapping

    8 serial communication ports

    • PACiS Gateway Sons

  • 8/20/2019 L2 V4 01 System Devices Configuration E 01

    23/38

    Schneider Electric 23- CS&P – System Devices Configuration – E01

    PACiS OI Server Configuration

    PACiS OI Client Configuration

    C264 Configuration PACiS Gateway Configuration

    Labels in Datapoint profiles

    Devices Redundancy

    • Content

  • 8/20/2019 L2 V4 01 System Devices Configuration E 01

    24/38

    Schneider Electric 24- CS&P – System Devices Configuration – E01

    All Devices Operating Mode (OI, C264, GTW) => MPS

    MiCOM C264 Boards status => MPS

    Note 1 : TEST Mode N/A for OI and GTW 

    Note 1 : Applicable for all kind of boards 

    Note 2 : Special status Missing = in configuration not in rack 

    Too Many = in rack not in configuration OK Empty = used at SMT only

    Note 2 : Useful for graphical animation 

    • System Information Labels in Profiles

  • 8/20/2019 L2 V4 01 System Devices Configuration E 01

    25/38

    Schneider Electric 25- CS&P – System Devices Configuration – E01

    ISaGRAF Status => MPS (under C264/PLC)

    PACiS OI Printer Status (parallel or LAN) (SOE/SLB) => MPS

    Note : Not Activated = No ISaGRAF configured 

    Cycle too long = cycle > 2s Queue Overflow = ISaGRAF overflow 

    Note 2 : N/A for C264 printer 

    Parallel :Parallel :Parallel :Parallel : LAN :LAN :LAN :LAN :

    • System Information Labels in Profiles

  • 8/20/2019 L2 V4 01 System Devices Configuration E 01

    26/38

    Schneider Electric 26- CS&P – System Devices Configuration – E01

    Central Archive => MPS (under OIS)

    PACiS OI Redundancy Status => MPS (under OIS)

    • System Information Labels in Profiles

  • 8/20/2019 L2 V4 01 System Devices Configuration E 01

    27/38

    Schneider Electric 27- CS&P – System Devices Configuration – E01

    PACiS OI Server Configuration

    PACiS OI Client Configuration

    C264 Configuration PACiS Gateway Configuration

    Labels in Datapoint profiles

    Devices Redundancy

    • Content

  • 8/20/2019 L2 V4 01 System Devices Configuration E 01

    28/38

    Schneider Electric 28- CS&P – System Devices Configuration – E01

    Create Redundant C264

    • Select C264 and “Create Backup”

    • Redundant C264 parameters

    • Redundant MiCOM C264

  • 8/20/2019 L2 V4 01 System Devices Configuration E 01

    29/38

    Schneider Electric 29- CS&P – System Devices Configuration – E01

    Create Redundant OI Server

    • Select OI Server and “Create Backup”

    • Redundant OI Server parameters

    • Redundant PACiS OI Server

  • 8/20/2019 L2 V4 01 System Devices Configuration E 01

    30/38

    Schneider Electric 30- CS&P – System Devices Configuration – E01

    On PACiS 4.6.0, Hot redundancy principle :

    • OI Client is connected to “preferred” OI Server. If server not availableit will immediately try connect to the other one.

     

    Client BClient A Client C

    IEC 61850 Station Bus

    Server 1 Server 2

    SQL database SQL database

    • Both OI server perform DP acquisition simultaneously. There is aconsolidating mechanism insuring all data are the same on both.

    • Hot Redundancy in PACiS OI Server

  • 8/20/2019 L2 V4 01 System Devices Configuration E 01

    31/38

    Schneider Electric 31- CS&P – System Devices Configuration – E01

    • Each OI server is managing its own system DP. These are not

    consolidating because each server is aware of status of the other one.

    • Master OI can :- acquire DP from IEC servers.- be connected to OI Client.- perform archives (Historian) and manage alarms.- accept and manage controls from any OI Client (directly

    connected to itself or connected to OI Slave).- print events on SOE printers

    • Slave OI can :

    - acquire DP from IEC servers.- be connected to OI Client.- perform archives (Historian) and manage alarms.

    - propagate controls from its OI Client (directly connected toitself) to OI Master which will manage the controls.

    • Hot Redundancy in PACiS OI Server

    H R d d i PACiS OI S

  • 8/20/2019 L2 V4 01 System Devices Configuration E 01

    32/38

    Schneider Electric 32- CS&P – System Devices Configuration – E01

    • Standalone OI can :- acquire DP from IEC servers.- be connected to OI Client.

    - perform archives (Historian) and manage alarms.- accept and manage controls from its OI Client (directlyconnected to itself) as the other Standalone OI; but in that case ControlUniqueness is done at C264 level.

    - print events on connected SOE printers

    • Performances (typical switching time):

    Less than 60sEthernet disconnection

    Less than 20sApplication stop

    Less than 20sPC power off

    OI Client switching timeOI server failure

    • Hot Redundancy in PACiS OI Server

    H t R d d i PACiS OI S

  • 8/20/2019 L2 V4 01 System Devices Configuration E 01

    33/38

    Schneider Electric 33- CS&P – System Devices Configuration – E01

     

    Server 1 Server 2

    START-UP START-UP

    WAITSTANDALONE

    SLAVEMASTER

    Both OI are connected on Ethernet and visible.

     

    Server 1 Server 2

    MASTER SLAVE

    GOING TO

    STANDALONE

    STANDALONE

    PC halted

    PC start-up

    START-UP

    MASTERSLAVE

    OI Master shuts down then restarts

    OI is proceeding consolidating messages beforegoing to Standalone.

    • Hot Redundancy in PACiS OI Server

    H t R d d i PACiS OI S

  • 8/20/2019 L2 V4 01 System Devices Configuration E 01

    34/38

    Schneider Electric 34- CS&P – System Devices Configuration – E01

    One OI is not connected and reconnects. One OI is not connected and reconnects.

     

    Server 1 Server 2

    START-UP START-UP

    STANDALONESTANDALONE

    Ethernet connexion

    MASTER

    SHUTDOWN

    START-UP

    SLAVE

    Case 1 : no OI client connected on OI server 1

    Server 1 Server 2

    START-UP START-UP

    STANDALONESTANDALONE

    Ethernet connexion

    SHUTDOWN

    START-UP

    SLAVEMASTER

    Case 2 : OI server 2 with less OI clients connected than OI server 1 (means

    that the number of OI clients connected is exchanged between OI servers)

    • Hot Redundancy in PACiS OI Server

    H t R d d i PACiS OI S

  • 8/20/2019 L2 V4 01 System Devices Configuration E 01

    35/38

    Schneider Electric 35- CS&P – System Devices Configuration – E01

    Fault Tolerance automation : principle of MASTER/SLAVE election

    1. The 1st server that starts is MASTER2. In case of Ethernet reconnection, the criteria for MASTER election

    are, from highest priority to lowest :

    a. There is a control in progress on one serverb. The quantity of connected clientsc. The first one configured in SCE

    The client connection to preferred server principle and theMASTER/SLAVE election have no correlation

    • Hot Redundancy in PACiS OI Server

    H t R d d i PACiS OI S

  • 8/20/2019 L2 V4 01 System Devices Configuration E 01

    36/38

    Schneider Electric 36- CS&P – System Devices Configuration – E01

    SQL consolidation

    Objective : ensure both OI servers Historian database are in line

    How :

    At SQL level onlyEvery 2 minutes (based on clock time : 8h00, 8h02, 8h04, …) :

    • Compare both databases• Fix discrepancies (if any)• Tag every consolidated event

    • Next consolidation starts from 1st event not tagged

    • Hot Redundancy in PACiS OI Server

    Hot Redundancy in PACiS OI Server

  • 8/20/2019 L2 V4 01 System Devices Configuration E 01

    37/38

    Schneider Electric 37- CS&P – System Devices Configuration – E01

    On PACiS 4.6.0, Hot redundancy configuration :1. Preferred server of OI Client is chosen using relation “Has for HMI

    server ”2. Good Practice is to select at least 1 OI Client per OI Server .3. Files “servers.dat” are automatically created by SCE during

    generation. There is no need to manually install it after DB switch.

    • Hot Redundancy in PACiS OI Server

    • Buffered Reports for PACiS OI Server

  • 8/20/2019 L2 V4 01 System Devices Configuration E 01

    38/38

    Schneider Electric 38- CS&P – System Devices Configuration – E01

    Buffered reports is used to retrieve max 1000 events stored in C264 incase of C264 disconnection from OI Server (PACiS GTW DOES NOTsupport buffered reports)

    Add relation under SCS : Has for buffered report client :  

    Functionality can be tested on OI event viewer (printer is depending onits own buffer) 

    A Buffer overflow DP is reached in that case.

    • Buffered Reports for PACiS OI Server