PACiS System Devices
Configuration
PCL
PACiS Configuration TrainingPACiS Configuration TrainingPACiS Configuration TrainingPACiS Configuration Training
CS&PCS&PCS&PCS&P – –– – Support Team Support Team Support Team Support Team
-
8/20/2019 L2 V4 01 System Devices Configuration E 01
2/38
Schneider Electric 2- CS&P – System Devices Configuration – E01
PACiS OI Server Configuration
PACiS OI Client Configuration
C264 Configuration PACiS Gateway Configuration
Labels in Datapoint profiles
Devices Redundancy
• Content
-
8/20/2019 L2 V4 01 System Devices Configuration E 01
3/38
Schneider Electric 3- CS&P – System Devices Configuration – E01
PACiS OI Server Configuration
PACiS OI Client Configuration
C264 Configuration PACiS Gateway Configuration
Labels in Datapoint profiles
Devices Redundancy
• Content
-
8/20/2019 L2 V4 01 System Devices Configuration E 01
4/38
Schneider Electric 4- CS&P – System Devices Configuration – E01
Under SCS/Ethernet Network
Add from Object Entry window
PACiS OI Server Attributes
Network name (Never HMI) + IP@
MV computation period
Max number of presence
days for event/value in SQLHistorian database
Periodic SQL Historian DB backup
Good Practice
155
Note : use OI configured in starting database
Follow Good Practice for
addressing
• Add / Configure PACiS OI Server
-
8/20/2019 L2 V4 01 System Devices Configuration E 01
5/38
Schneider Electric 5- CS&P – System Devices Configuration – E01
Basic = System Infos + IEC Mapping
Note : use OI configured in starting
database, all system information arealready configured
List of System Information :Operating Mode,Synchronisation Status, ...
IEC 61850 Mapping
• PACiS OI Server Sons
-
8/20/2019 L2 V4 01 System Devices Configuration E 01
6/38
Schneider Electric 6- CS&P – System Devices Configuration – E01
Possible sons
Klaxon for audible alarm
Serial Printer
Sequence of Events / System
Log Book
Printer Name as installed on thePC (spool name)for main and backup
• Printer
Used when main printer breaks downUsed when main printer breaks downUsed when main printer breaks downUsed when main printer breaks downduring starting of backup printer during starting of backup printer during starting of backup printer during starting of backup printer
Used during orderingUsed during orderingUsed during orderingUsed during orderingprocess of dated eventsprocess of dated eventsprocess of dated eventsprocess of dated events
• PACiS OI Server Sons
-
8/20/2019 L2 V4 01 System Devices Configuration E 01
7/38
Schneider Electric 7- CS&P – System Devices Configuration – E01
• Klaxon
Klaxon action (immediate/defer) and
acknowledgement (auto/manu).
Klaxon can be executed on one SPC in
one C264 (horn).If not configured => PACiS OI Server PCuses the buzzer
Note : Relation “warns audibly” (gives an audible warning) to determine whichalarms are triggering the klaxon
Note 2 : The SPC must be direct execute, without dependency, withoutinterlock, with “on” and “off” orders possibility.
• PACiS OI Server Sons
-
8/20/2019 L2 V4 01 System Devices Configuration E 01
8/38
Schneider Electric 8- CS&P – System Devices Configuration – E01
PACiS OI Server Configuration
PACiS OI Client Configuration
C264 Configuration PACiS Gateway Configuration
Labels in Datapoint profiles
Devices Redundancy
• Content
-
8/20/2019 L2 V4 01 System Devices Configuration E 01
9/38
Schneider Electric 9- CS&P – System Devices Configuration – E01
Under SCS/Ethernet Network
Add from Object Entry window
PACiS OI Client Attributes
Network name + IP@same if installed on same PC asOI Server
Follow Good Practice for
addressing
• Add / Configure PACiS OI Client
-
8/20/2019 L2 V4 01 System Devices Configuration E 01
10/38
Schneider Electric 10- CS&P – System Devices Configuration – E01
Basic = System Infos + Relation to OI Server + Relation to graphic part
Link Status :Status of the Link between OI Client andOI server
Link to OI Server- all clients are linked with PACiSOI Server Main or Backup.- At least 1 OI Client has to be
connected on each OI Server.Link to graphic partthe client will show the views
configured under the chosenworkspace
• PACiS OI Client Sons and Relations
-
8/20/2019 L2 V4 01 System Devices Configuration E 01
11/38
Schneider Electric 11- CS&P – System Devices Configuration – E01
PACiS OI Server Configuration
PACiS OI Client Configuration
C264 Configuration PACiS Gateway Configuration
Labels in Datapoint profiles
Devices Redundancy
• Content
-
8/20/2019 L2 V4 01 System Devices Configuration E 01
12/38
Schneider Electric 12- CS&P – System Devices Configuration – E01
Under SCS/Ethernet Network
Add from Object Entry window
Note1 : use C264 configured in starting database
Note2 : create new C264 by copy/paste of existing one
• Add / Configure MiCOM C264
-
8/20/2019 L2 V4 01 System Devices Configuration E 01
13/38
Schneider Electric 13- CS&P – System Devices Configuration – E01
General Tab
Network name + IP@
Computer Name
IRIG-B signal or not
80TE=C264 / 40TE=C264C
Follow Good Practice for
addressing
• MiCOM C264 Attributes
-
8/20/2019 L2 V4 01 System Devices Configuration E 01
14/38
Schneider Electric 14- CS&P – System Devices Configuration – E01
BI Filtering Tab
Note : used for SPS, DPS and MPS acquisition on DI board
Toggling applied on validated signal
Toggling parameters
Debouncing / Filtering => signal
validation
F ilt e r in g tim e
t 0 t 1t 2
D e b o u c in gt im e
Debouncing / Filtering => signalvalidation
Timetag => t0 or t2 (configurable)
• MiCOM C264 Attributes
-
8/20/2019 L2 V4 01 System Devices Configuration E 01
15/38
Schneider Electric 15- CS&P – System Devices Configuration – E01
Measurements Tab
Note 1 : Transmission periods are used if MV is declared as “periodic”
Long period = N x short period
AI board acquisition cycle
Debouncing / Filtering => signal
validation for Digital Measurements
CT/VT board acquisition frequency(neighbourhood of 0)
MV transmission cycle on SBUS andLHMI
Note 2 : too small transmission periods values has strong impact on SQLHistorian database filling => default values are too small
• MiCOM C264 Attributes
-
8/20/2019 L2 V4 01 System Devices Configuration E 01
16/38
Schneider Electric 16- CS&P – System Devices Configuration – E01
Counter Tab
Note : Applicable for single or double counters
Debouncing / Filtering => signal
validation for counted Digital Input
Miscellaneous Tab
Avoid endless C264 reboot on faultdetection, define a number of faults
acceptable during a period.
• MiCOM C264 Attributes
-
8/20/2019 L2 V4 01 System Devices Configuration E 01
17/38
Schneider Electric 17- CS&P – System Devices Configuration – E01
Basic = System Infos + 3 boards (CPU,BIU,GHU) + IEC Mapping
I/O Boards :Naming Good Practice :
Slot#__
IEC 61850 Mapping
Created by Automatic Addressingfunction
PLC Object
C264 Automations
• MiCOM C264 Sons
-
8/20/2019 L2 V4 01 System Devices Configuration E 01
18/38
Schneider Electric 18- CS&P – System Devices Configuration – E01
Basic = System Infos + 3 boards (CPU,BIU,GHU) + IEC Mapping
List of System Information :Operating Mode,Synchronisation Status, ...
Note : use C264 configured in startingdatabase, all system information arealready configured
• MiCOM C264 Sons
-
8/20/2019 L2 V4 01 System Devices Configuration E 01
19/38
Schneider Electric 19- CS&P – System Devices Configuration – E01
Possible sons = Object Entry Window
HardwareLBUS per protocol
TBUS
Local C264 printer
Add / Configure I/O board
Note : another method is to copy/paste existing board
Physical Board Number Relation made by automatic @(to remove when duplication)
• MiCOM C264 Sons
-
8/20/2019 L2 V4 01 System Devices Configuration E 01
20/38
Schneider Electric 20- CS&P – System Devices Configuration – E01
PACiS OI Server Configuration
PACiS OI Client Configuration
C264 Configuration PACiS Gateway Configuration
Labels in Datapoint profiles
Devices Redundancy
• Content
-
8/20/2019 L2 V4 01 System Devices Configuration E 01
21/38
Schneider Electric 21- CS&P – System Devices Configuration – E01
Under SCS/Ethernet NetworkAdd from Object Entry window
Note1 : use GTW configured in starting database
PACiS GTW Attributes
Network name + IP@
Follow Good Practice foraddressing
• Add / Configure PACiS Gateway
-
8/20/2019 L2 V4 01 System Devices Configuration E 01
22/38
Schneider Electric 22- CS&P – System Devices Configuration – E01
Basic = System Infos + 8 serial ports + IEC Mapping
List of System Information :Operating Mode,Synchronisation Status, ...
Note : use GTW configured in startingdatabase, all system information arealready configured IEC 61850 Mapping
1 to 4 protocols with the
relevant SCADA mapping
8 serial communication ports
• PACiS Gateway Sons
-
8/20/2019 L2 V4 01 System Devices Configuration E 01
23/38
Schneider Electric 23- CS&P – System Devices Configuration – E01
PACiS OI Server Configuration
PACiS OI Client Configuration
C264 Configuration PACiS Gateway Configuration
Labels in Datapoint profiles
Devices Redundancy
• Content
-
8/20/2019 L2 V4 01 System Devices Configuration E 01
24/38
Schneider Electric 24- CS&P – System Devices Configuration – E01
All Devices Operating Mode (OI, C264, GTW) => MPS
MiCOM C264 Boards status => MPS
Note 1 : TEST Mode N/A for OI and GTW
Note 1 : Applicable for all kind of boards
Note 2 : Special status Missing = in configuration not in rack
Too Many = in rack not in configuration OK Empty = used at SMT only
Note 2 : Useful for graphical animation
• System Information Labels in Profiles
-
8/20/2019 L2 V4 01 System Devices Configuration E 01
25/38
Schneider Electric 25- CS&P – System Devices Configuration – E01
ISaGRAF Status => MPS (under C264/PLC)
PACiS OI Printer Status (parallel or LAN) (SOE/SLB) => MPS
Note : Not Activated = No ISaGRAF configured
Cycle too long = cycle > 2s Queue Overflow = ISaGRAF overflow
Note 2 : N/A for C264 printer
Parallel :Parallel :Parallel :Parallel : LAN :LAN :LAN :LAN :
• System Information Labels in Profiles
-
8/20/2019 L2 V4 01 System Devices Configuration E 01
26/38
Schneider Electric 26- CS&P – System Devices Configuration – E01
Central Archive => MPS (under OIS)
PACiS OI Redundancy Status => MPS (under OIS)
• System Information Labels in Profiles
-
8/20/2019 L2 V4 01 System Devices Configuration E 01
27/38
Schneider Electric 27- CS&P – System Devices Configuration – E01
PACiS OI Server Configuration
PACiS OI Client Configuration
C264 Configuration PACiS Gateway Configuration
Labels in Datapoint profiles
Devices Redundancy
• Content
-
8/20/2019 L2 V4 01 System Devices Configuration E 01
28/38
Schneider Electric 28- CS&P – System Devices Configuration – E01
Create Redundant C264
• Select C264 and “Create Backup”
• Redundant C264 parameters
• Redundant MiCOM C264
-
8/20/2019 L2 V4 01 System Devices Configuration E 01
29/38
Schneider Electric 29- CS&P – System Devices Configuration – E01
Create Redundant OI Server
• Select OI Server and “Create Backup”
• Redundant OI Server parameters
• Redundant PACiS OI Server
-
8/20/2019 L2 V4 01 System Devices Configuration E 01
30/38
Schneider Electric 30- CS&P – System Devices Configuration – E01
On PACiS 4.6.0, Hot redundancy principle :
• OI Client is connected to “preferred” OI Server. If server not availableit will immediately try connect to the other one.
Client BClient A Client C
IEC 61850 Station Bus
Server 1 Server 2
SQL database SQL database
• Both OI server perform DP acquisition simultaneously. There is aconsolidating mechanism insuring all data are the same on both.
• Hot Redundancy in PACiS OI Server
-
8/20/2019 L2 V4 01 System Devices Configuration E 01
31/38
Schneider Electric 31- CS&P – System Devices Configuration – E01
• Each OI server is managing its own system DP. These are not
consolidating because each server is aware of status of the other one.
• Master OI can :- acquire DP from IEC servers.- be connected to OI Client.- perform archives (Historian) and manage alarms.- accept and manage controls from any OI Client (directly
connected to itself or connected to OI Slave).- print events on SOE printers
• Slave OI can :
- acquire DP from IEC servers.- be connected to OI Client.- perform archives (Historian) and manage alarms.
- propagate controls from its OI Client (directly connected toitself) to OI Master which will manage the controls.
• Hot Redundancy in PACiS OI Server
H R d d i PACiS OI S
-
8/20/2019 L2 V4 01 System Devices Configuration E 01
32/38
Schneider Electric 32- CS&P – System Devices Configuration – E01
• Standalone OI can :- acquire DP from IEC servers.- be connected to OI Client.
- perform archives (Historian) and manage alarms.- accept and manage controls from its OI Client (directlyconnected to itself) as the other Standalone OI; but in that case ControlUniqueness is done at C264 level.
- print events on connected SOE printers
• Performances (typical switching time):
Less than 60sEthernet disconnection
Less than 20sApplication stop
Less than 20sPC power off
OI Client switching timeOI server failure
• Hot Redundancy in PACiS OI Server
H t R d d i PACiS OI S
-
8/20/2019 L2 V4 01 System Devices Configuration E 01
33/38
Schneider Electric 33- CS&P – System Devices Configuration – E01
Server 1 Server 2
START-UP START-UP
WAITSTANDALONE
SLAVEMASTER
Both OI are connected on Ethernet and visible.
Server 1 Server 2
MASTER SLAVE
GOING TO
STANDALONE
STANDALONE
PC halted
PC start-up
START-UP
MASTERSLAVE
OI Master shuts down then restarts
OI is proceeding consolidating messages beforegoing to Standalone.
• Hot Redundancy in PACiS OI Server
H t R d d i PACiS OI S
-
8/20/2019 L2 V4 01 System Devices Configuration E 01
34/38
Schneider Electric 34- CS&P – System Devices Configuration – E01
One OI is not connected and reconnects. One OI is not connected and reconnects.
Server 1 Server 2
START-UP START-UP
STANDALONESTANDALONE
Ethernet connexion
MASTER
SHUTDOWN
START-UP
SLAVE
Case 1 : no OI client connected on OI server 1
Server 1 Server 2
START-UP START-UP
STANDALONESTANDALONE
Ethernet connexion
SHUTDOWN
START-UP
SLAVEMASTER
Case 2 : OI server 2 with less OI clients connected than OI server 1 (means
that the number of OI clients connected is exchanged between OI servers)
• Hot Redundancy in PACiS OI Server
H t R d d i PACiS OI S
-
8/20/2019 L2 V4 01 System Devices Configuration E 01
35/38
Schneider Electric 35- CS&P – System Devices Configuration – E01
Fault Tolerance automation : principle of MASTER/SLAVE election
1. The 1st server that starts is MASTER2. In case of Ethernet reconnection, the criteria for MASTER election
are, from highest priority to lowest :
a. There is a control in progress on one serverb. The quantity of connected clientsc. The first one configured in SCE
The client connection to preferred server principle and theMASTER/SLAVE election have no correlation
• Hot Redundancy in PACiS OI Server
H t R d d i PACiS OI S
-
8/20/2019 L2 V4 01 System Devices Configuration E 01
36/38
Schneider Electric 36- CS&P – System Devices Configuration – E01
SQL consolidation
Objective : ensure both OI servers Historian database are in line
How :
At SQL level onlyEvery 2 minutes (based on clock time : 8h00, 8h02, 8h04, …) :
• Compare both databases• Fix discrepancies (if any)• Tag every consolidated event
• Next consolidation starts from 1st event not tagged
• Hot Redundancy in PACiS OI Server
Hot Redundancy in PACiS OI Server
-
8/20/2019 L2 V4 01 System Devices Configuration E 01
37/38
Schneider Electric 37- CS&P – System Devices Configuration – E01
On PACiS 4.6.0, Hot redundancy configuration :1. Preferred server of OI Client is chosen using relation “Has for HMI
server ”2. Good Practice is to select at least 1 OI Client per OI Server .3. Files “servers.dat” are automatically created by SCE during
generation. There is no need to manually install it after DB switch.
• Hot Redundancy in PACiS OI Server
• Buffered Reports for PACiS OI Server
-
8/20/2019 L2 V4 01 System Devices Configuration E 01
38/38
Schneider Electric 38- CS&P – System Devices Configuration – E01
Buffered reports is used to retrieve max 1000 events stored in C264 incase of C264 disconnection from OI Server (PACiS GTW DOES NOTsupport buffered reports)
Add relation under SCS : Has for buffered report client :
Functionality can be tested on OI event viewer (printer is depending onits own buffer)
A Buffer overflow DP is reached in that case.
• Buffered Reports for PACiS OI Server