kks handbook rev b

Upload: lrpatra

Post on 07-Aug-2018

1.129 views

Category:

Documents


62 download

TRANSCRIPT

  • 8/20/2019 KKS Handbook Rev B

    1/63

     

    Dwg. No. / Doc.

    Int Doc N°

    Rev

    LOTR-VSPO-AC90-9-0050-TR

    2840-004970

    B

    EMPLOYER. HYDROELECTRICA – S. A. DRAWN KINASBERGER 2007.07.03

    PLANT HPP LOTRU CIUNGET CHECK TUNG 2007.07.18

    ORDER No.. 23674 APPR. SALLFERT 2007.08.03 SHEET 1 / 63 

    KKS HANDBOOK

    TABLE of CONTENT

    1. Introduction .. .................................................................................................................................... 2 

     2. Scope of KKS.. ................................................................................................................................... 3 

    2.1  Type of code............................................................................................................................................3 

    2.2  Break down levels, prefix and breakdown symbols .............................................................................4 

    2.3  KKS code................................................................................................................................................5 

    2.4  Contents of data characters...................................................................................................................5 

    2.5  Break down level 0.................................................................................................................................6 

    2.6 

    Break down level 1.................................................................................................................................6 

    2.7  Break down level 2.................................................................................................................................7 

    2.8  Break down level 3.................................................................................................................................8 

     3. Numbering .. ...................................................................................................................................... 9 

    3.1  FN numbering.........................................................................................................................................9 

    3.2  AN numbering ........................................................................................................................................9 

    3.3  Numbering of valves..............................................................................................................................9 

     4. Location Code ... ..............................................................................................................................11 

    4.1 

    Coding of structures ............................................................................................................................11 

     5. Identification of Cables ... ...............................................................................................................12 

    5.1  Cables....................................................................................................................................................12 

    5.2  Cable numbering .................................................................................................................................12 

    6. Identification of I&C equipment... .................................................................................................13 

    6.1  Signal identification.............................................................................................................................13 

    7. KKS Reference List... ......................................................................................................................15 

    7.1  Breakdown level 1................................................................................................................................15 

    7.2 

    Breakdown level 2................................................................................................................................37 

    7.3  Breakdown level 3................................................................................................................................45 

    7.4  Signal reference list .............................................................................................................................48 

  • 8/20/2019 KKS Handbook Rev B

    2/63

     

    Dwg. No. / Doc.

    Int Doc N°

    Rev

    LOTR-VSPO-AC90-9-0050-TR

    2840-004970

    B

    EMPLOYER. HYDROELECTRICA – S. A. DRAWN KINASBERGER 2007.07.03

    PLANT HPP LOTRU CIUNGET CHECK TUNG 2007.07.18

    ORDER No.. 23674 APPR. SALLFERT 2007.08.03 SHEET 2 / 63 

    1. Introduction

    The main purpose of this handbook is to define the methods used by Voith Siemens foridentification in mechanical, electrical, control and instrumentation engineering.For this purpose Voith Siemens has chosen the identification system KKS (G: KraftwerkKennzeichnen System, E: Identification Systems for Power Plants).Voith Siemens has certain guidelines which are within the limits given by VGB (TechnischeVereinigung der Grosskraftwerksbetreiber E.V.). These guidelines apply on thedifferent Break Down Levels (BDL) in the identification system.This KKS-handbook contains certain guidelines made by Voith Siemens.The KKS codes shown in this handbook are only for clarification and can not be useddirectly during any project.The guidelines do not replace the guidelines from VGB, listed in Chapter 1.The compendium of “Directives from the Owner to the Contractor regarding the use ofKKS for Voith Siemens” on the following pages has to be studied carefully prior to any workcarried out in connection with KKS coding.If there are any disputes between the Guidelines and the Handbook, the Handbookshall prevail.In this KKS Handbook there are special rules which apply for Voith Siemens and are notdescribed in the Guidelines. 

  • 8/20/2019 KKS Handbook Rev B

    3/63

     

    Dwg. No. / Doc.

    Int Doc N°

    Rev

    LOTR-VSPO-AC90-9-0050-TR

    2840-004970

    B

    EMPLOYER. HYDROELECTRICA – S. A. DRAWN KINASBERGER 2007.07.03

    PLANT HPP LOTRU CIUNGET CHECK TUNG 2007.07.18

    ORDER No.. 23674 APPR. SALLFERT 2007.08.03 SHEET 3 / 63 

    2. Scope of KKS

    The Identification System for Power Plants “KKS” serves to identify Power Plants,sections of plants and items of equipment in any kind of Power Plants according totask, type and location. It also serves to identify Sub Stations and overhead lines in thesame manner.The KKS key is based on the IEC and ISO standards together with the DIN 40719PART 2 (IEC 750).These KKS guidelines do not contain rules on:

    •  Combination of the code with other identification systems.•  Methods of marking, e.g. in control rooms, local control stations, labelling off

    components and identification of documents.•  Open text abbreviations.•  Identification/numbering of drawings.

    The following guidelines and explanations issued by VGB are valid, and where not incontradiction to the handbook, they do apply.

    •  KKS Guidelines (4th edition 1995)•  KKS-Application Commentaries, Part A General (1st edition 1988)•  KKS-Application Commentaries, Part B Engineering Discipline,

    Part B1, Identification in Mechanical Engineering (1st edition 1988)•  KKS-Application Commentaries, Part B Engineering Discipline,

    Part B2, Identification in Civil Engineering (1st edition 1988)•  KKS-Application Commentaries, Part B Engineering Discipline,

    Part B3, Identification in Electrical and Control and Instrumentation Engineering (1st

    edition 1988)•  KKS-Application Commentaries, Part B Engineering Discipline, Part B4,

    Identification in Electrical and Control and Instrumentation Engineering (1st edition1993) 

    2.1 Type of code

    The KKS has three different types of codes, which can be used together or separately.These codes are the process-related code, the point of installation code and thelocation code. These codes are subdivided into 3 and 4 Break Down Levels (BDL). 

    Process related Code

    Process related identification of systems and items of equipment according to theirfunction in mechanical, civil, electrical and control and instrumentation engineering. Asexample there are pipes, pumps, valves, motors, measurements, switches,transformers etc.

    Point of installation CodeIdentification of points of installation of electrical and control and instrumentationequipment in installation units e.g. in cabinets, panels, consoles etc.

    Location CodeIdentification of various structures, such as dams, tunnels, buildings, floors, and roomsand fire areas.This code is also used in connection with preventive maintenance of buildings and

    structures. Further more this code is used to identify the location of mechanical components in thesame manner as the point of installation code is used in electrical- and control and

  • 8/20/2019 KKS Handbook Rev B

    4/63

     

    Dwg. No. / Doc.

    Int Doc N°

    Rev

    LOTR-VSPO-AC90-9-0050-TR

    2840-004970

    B

    EMPLOYER. HYDROELECTRICA – S. A. DRAWN KINASBERGER 2007.07.03

    PLANT HPP LOTRU CIUNGET CHECK TUNG 2007.07.18

    ORDER No.. 23674 APPR. SALLFERT 2007.08.03 SHEET 4 / 63 

    instrumentation engineering. 

    2.2 Break down levels, prefix and breakdown symbols

    Definitions for prefixes and breakdown symbols for writing these codes are in DIN40719, part 2.The following fig. 1.1 shows the role of the codes on different BDL´s. 

    Fig. 1.1 Break Down Levels for various types of codes 

    The “full stop” breakdown symbol for point of installation identification must always be

    written. The prefix symbols may be omitted if the information content of the codesremains unambiguous.In front of these codes there is a BDL −1 and this BDL is used for identification ofPower Plants and Sub Stations. It does not belong to the KKS code issued by VGB, and is not usedby Voith Siemens, (see table 1.1 - 1.4).As an example the following is mentioned:

    BDL Area Example KKS-1 Plant Lotru HPP LOTR0 Part of a plant Unit 1 101 System Governor Hydraulic Unit MEX11

    2 Equipment (part of system) Pressure Measurement CP1013 Component (part of equipment) Pressure switch -S01

    Table 1.1 Example, use of Break Down Levels. 

  • 8/20/2019 KKS Handbook Rev B

    5/63

     

    Dwg. No. / Doc.

    Int Doc N°

    Rev

    LOTR-VSPO-AC90-9-0050-TR

    2840-004970

    B

    EMPLOYER. HYDROELECTRICA – S. A. DRAWN KINASBERGER 2007.07.03

    PLANT HPP LOTRU CIUNGET CHECK TUNG 2007.07.18

    ORDER No.. 23674 APPR. SALLFERT 2007.08.03 SHEET 5 / 63 

    2.3 KKS code

    The KKS code consists of alpha letters (A) and numbers (N). The code is divided in 4

    (0-3) BDL´s in the process related code and in 3 (0-2) BDL´s in the point of installationcode and the location code. 

    BDL 0 1 2 3

    DefinitionPart ofplant

    System code Equipment unit codeComponent

    code

    Name G F0  F1 F2 F3 FN  A1  A2  AN  A3  B1  B2  BN 

    Type of key (N) N (N) A A A N N A A N N N (A) A A N N

     

    Table 1.2 KKS codes. 

    2.4 Contents of data characters

    It shall be clearly stated that all explanations in this book are related to the processcode unless otherwise specified.In the KKS key the use of the alpha symbols (A) is defined in most cases. Still there aresome codes that are available for free use, see chapters 4.7 and 4.9. The definition ofthe use of numerical symbols (N) is defined in this book, according to the regulationsvalid by Voith Siemens.

    The letters I and O are not permitted except on BDL−

    1 and BDL 0 in the KKS code, toavoid misunderstanding between I and 1 (one) on one hand and O and 0 (zero) on theother hand. 

  • 8/20/2019 KKS Handbook Rev B

    6/63

     

    Dwg. No. / Doc.

    Int Doc N°

    Rev

    LOTR-VSPO-AC90-9-0050-TR

    2840-004970

    B

    EMPLOYER. HYDROELECTRICA – S. A. DRAWN KINASBERGER 2007.07.03

    PLANT HPP LOTRU CIUNGET CHECK TUNG 2007.07.18

    ORDER No.. 23674 APPR. SALLFERT 2007.08.03 SHEET 6 / 63 

    2.5 Break down level 0

    BDL 0 1 2 3

    DefinitionPart ofplant

    System code Equipment unit codeComponent

    code

    Name G F0  F1 F2 F3 FN  A1  A2  AN  A3  B1  B2  BN 

    Type of key (N) N (N) A A A N N A A N N N (A) A A N N

     Table 1.5 BDL 0. 

    The KKS key allows the use of alpha- and numerical symbols on BDL 0. The definition ofthe use of numerical symbols (N) is defined in this book, according to the regulations

    valid by Voith Siemens.

    BDL 0 Description1 Unit 12 Unit 23 Unit 3x Unit x0 Common related

    Table 1.6 BDL 0 definition

    2.6 Break down level 1

    BDL 0 1 2 3

    DefinitionPart ofplant

    System code Equipment unit codeComponent

    code

    Name G F0  F1 F2 F3 FN  A1  A2  AN  A3  B1  B2  BN 

    Type of key N N (N) A A A N N A A N N N (A) A A N N

     

    Table 1.7 BDL 1. 

    The first seat in this BDL (F0) is used if there are two or more identical systems in thePower Plant (Sub Station) e.g. main machine sets, which have to be coded separately.When one system is common for more than one main system or there is no systemcounting, the F0 = 0 (zero), else the systems are numbered from 1 to 9. When F0 is not used, it is notwritten in the code. On this BDL (F1, F2, F3) the original KKS key applies. Some keys (F2, F3) in this group are given free for use so that they can be used as itsuits the purpose of coding. This also applies to some keys on BDL 2 (A2) and on BDL 3 (B2).Some keys (F3) in the group of ancillary systems are given free for use to separatesystems in various buildings.The use of these characters has been defined by Voith Siemens, and this is shown in

    chapter 7.1The FN numbers are used for coding within the same system. As an example the main

  • 8/20/2019 KKS Handbook Rev B

    7/63

     

    Dwg. No. / Doc.

    Int Doc N°

    Rev

    LOTR-VSPO-AC90-9-0050-TR

    2840-004970

    B

    EMPLOYER. HYDROELECTRICA – S. A. DRAWN KINASBERGER 2007.07.03

    PLANT HPP LOTRU CIUNGET CHECK TUNG 2007.07.18

    ORDER No.. 23674 APPR. SALLFERT 2007.08.03 SHEET 7 / 63 

    code for a generator rotor is MKA10 and for a generator stator the main code is MKA20. 

    2.7 Break down level 2

    BDL 0 1 2 3

    DefinitionPart ofplant

    System code Equipment unit codeComponent

    code

    Name G F0  F1 F2 F3 FN  A1  A2  AN  A3  B1  B2  BN 

    Type of key N N (N) A A A N N A A N N N (A) A A N N

     

    Table 1.8 BDL 2. 

    In the KKS key equipment is coded/defined by A1, A2 e.g. valves, pumps, switches etc..The AN number is a consecutive number which is used to number identical equipment,which is identified by A1, A2, within the same system.It has been decided by Voith Siemens how these numbers shall be used in case of parallel and serialconnected systems in the mechanical engineering and also in the electricalpart, where 3 phase systems are coded and A3 is used to separate e.g. cores inmeasurement transformers see chapter 4.When A3 is not used, it is not written in the code. 

  • 8/20/2019 KKS Handbook Rev B

    8/63

     

    Dwg. No. / Doc.

    Int Doc N°

    Rev

    LOTR-VSPO-AC90-9-0050-TR

    2840-004970

    B

    EMPLOYER. HYDROELECTRICA – S. A. DRAWN KINASBERGER 2007.07.03

    PLANT HPP LOTRU CIUNGET CHECK TUNG 2007.07.18

    ORDER No.. 23674 APPR. SALLFERT 2007.08.03 SHEET 8 / 63 

    2.8 Break down level 3

    BDL 0 1 2 3

    DefinitionPart ofplant

    System code Equipment unit codeComponent

    code

    Name G F0  F1 F2 F3 FN  A1  A2  AN  A3  B1  B2  BN 

    Type of key N N (N) A A A N N A A N N N (A) A A N N

     

    Table 1.9 BDL 3. 

    B1 and B2 are defined in the KKS key and BN is used to number components inside thesame system or equipment.

    The coding of electrical components is according to DIN 40719, part 2. 

  • 8/20/2019 KKS Handbook Rev B

    9/63

     

    Dwg. No. / Doc.

    Int Doc N°

    Rev

    LOTR-VSPO-AC90-9-0050-TR

    2840-004970

    B

    EMPLOYER. HYDROELECTRICA – S. A. DRAWN KINASBERGER 2007.07.03

    PLANT HPP LOTRU CIUNGET CHECK TUNG 2007.07.18

    ORDER No.. 23674 APPR. SALLFERT 2007.08.03 SHEET 9 / 63 

    3. Numbering

    The KKS code allows a certain possibility of free/individual use of numbering codeelements. This chapter shows the rules for using the FN and the AN numbers. The rulesdefined here are binding for the KKS coding for Voith Siemens.In some cases it is possible to use some other way of numbering, in those casesVoith Siemens will set the standard for that numbering.The sources for this are the KKS Guidelines from VGB, together with Part A and Part B(booklets B1, B2, B3 and B4) also from VGB.1. Numbering starts again when one of the preceding code elements changes.2. Numbering may be done in units or decades. It depends on the system that’sbeing used.3. Numbering is as a rule in the direction of flow.4. Numbering shall be from left to right or from top to bottom. It is permitted to use

    numbering that exists in old Power Plants though it isn’t in the right direction.5. It is preferred to use gaps in the numbering, to simplify later changes.The numbering with FN and AN shall always be in the direction of a flow as often aspossible. If however the flow has two directions, one direction shall be defined as“NORMAL OPERATION”.

    3.1 FN numbering

    FN numbering is used to divide systems in parts or subsystems. FN is done in decades(10,20,30....etc.) or consecutive (11,12,13,14......etc)

    FN

    numbering should be minimised. If no further FN

    numbering is needed then thedecade 10 should be used in the FN seat.Numbering with FN in large plumbing systems should be clearly divided, e.g. by areas,by levels, by machinery and by large parts of machinery with decade numbering butwith consecutive numbering in parallel connected system.Example of FN numbering is found in chapter 3, Identification in mechanicalengineering. Upper and lower guide valves are numbered in decades (10,20,30 ...) butindividual parts of the guide valves are numbered consecutively (11,12,13 ...). 

    3.2 AN numbering

    AN numbering is used to divide systems in single parts. AN numbering shall be indecades (_10, _20, _30 ….) or in consecutive (_11, _12, _13 …..).For numbering of electrical and pipe line systems separations shall be clear. E.g. usedecade numbering for separation along main branches and use consecutive numberingfor separation along parallel connected branches. 

    3.3 Numbering of valves

    Decades numbering shall be used for valves in a main piping system, 010, 020, 030,etc. when their role/function changes, e.g. when pressure, temperature etc. change.

    In sub-piping systems, valves like bypass valves, control valves etc. shall be numbered011, 012, 013.... or 021, 022, 023... etc.

  • 8/20/2019 KKS Handbook Rev B

    10/63

     

    Dwg. No. / Doc.

    Int Doc N°

    Rev

    LOTR-VSPO-AC90-9-0050-TR

    2840-004970

    B

    EMPLOYER. HYDROELECTRICA – S. A. DRAWN KINASBERGER 2007.07.03

    PLANT HPP LOTRU CIUNGET CHECK TUNG 2007.07.18

    ORDER No.. 23674 APPR. SALLFERT 2007.08.03 SHEET 10 / 63 

    Consecutive numbering is also used for valves for control circuits, air- and waterdrainage, instrument valves, sampling valves and safety valves. They are numberedwith _01, _02, _11,_12,...etc.The numbering of the following valves shall be grouped by counting in hundreds in the

    following way:

    0_ _ - valves in main-pipings

    1_ _ - valves in precontrol-pipings

    2_ _ - valves for filling

    3_ _ - valves in measuring-circuits

    4_ _ - valves in drainage, discharge and flushing pipings

    5_ _ - valves in vent-pipings

    6_ _ - valves in sampling pipes7_ _ - safety- valves

    8_ _ - condensate-drain-instruments

    9_ _ - assembly valves

    Numbering of measurement points

    Measurement points numbering is consecutive and shall be grouped by the hundredsin the following way:0 _ _ for analog meters with control and alarm purposes. 1 _ _ for digital meters with control and alarm purposes

    3 _ _ for indicating local meters, sight-glasses, meters with no control or alarmpurpose and meters which are not connected to remote control

  • 8/20/2019 KKS Handbook Rev B

    11/63

     

    Dwg. No. / Doc.

    Int Doc N°

    Rev

    LOTR-VSPO-AC90-9-0050-TR

    2840-004970

    B

    EMPLOYER. HYDROELECTRICA – S. A. DRAWN KINASBERGER 2007.07.03

    PLANT HPP LOTRU CIUNGET CHECK TUNG 2007.07.18

    ORDER No.. 23674 APPR. SALLFERT 2007.08.03 SHEET 11 / 63 

    4. Location Code

    4.1 Coding of structures

    The location code is used by Voith Siemens to code structures like dams, tunnels, buildingsand part of buildings like rooms etc.The location code is also used to code the location of machinery in a similar way as thepoint of installation code is used for electrical equipment.The KKS code consists of alpha letters (A) and numbers (N). The code is divided inbreakdown levels (BDL´s). The location code has 3 (0-2) BDL´s which are used in asimilar way as the point of installation code.

    BDL 0 1 2

    DefinitionPart ofplant

    Structure code Room code

    Name G F0  F1 F2 F3 FN  A1  A2  AN  A3 

    Type of key (N) N (N) A A A N N (A) (N) N N (A)

    F0 on BDL 1 is used where distinction between systems is needed, either in PowerPlants or in Sub Stations, where more than one identical system exists. When onesystem is common for other systems and identical and there is no system groupingthen F0 is 0, otherwise the systems are numbered from 1 to 9.

    All structures coded with the location code have the letter U on BDL 1 ( F1). The nexttwo letters (F2,F3) are normally the two first letters from the process code which istypical or dominating for the structure.An example is a structure for the gates, which has the code ULP, as the gates arecoded on BDL 1, with LP_ in the two first designation places for data characters.The main group of structures should be used in the same manner as the KKS-codedescribes in VGB, book B2. 

  • 8/20/2019 KKS Handbook Rev B

    12/63

     

    Dwg. No. / Doc.

    Int Doc N°

    Rev

    LOTR-VSPO-AC90-9-0050-TR

    2840-004970

    B

    EMPLOYER. HYDROELECTRICA – S. A. DRAWN KINASBERGER 2007.07.03

    PLANT HPP LOTRU CIUNGET CHECK TUNG 2007.07.18

    ORDER No.. 23674 APPR. SALLFERT 2007.08.03 SHEET 12 / 63 

    5. Identif ication of Cables

    5.1 Cables

    All cables shall be labelled with the following minimum information on each end of the cable:• Cable number• From information (Location)• The functionality group to which the cable belongs

    Identification structure

    Breakdown level no. 0 1 2

    Breakdown level title Group Location Cable numberType of character (N)N AAANN - N N N N

    Example 1 CXA01 - 4 0 0 1

    Cable from cubicle 1CXA01Cable number 4001Whole cable-number: 1CXA01-4001

    5.2 Cable numbering

    Cable shall be numbered sequentially. Numbers shall be issued from a common database to

    prevent duplication. The counting number is classified by voltage level.Numbering for breakdown level 2:

    0001 to 0999 Power cables > 1 kV

    1001 to 1999 Power cables 60 V

    3001 to 3499 Measuring cables > 60 V

    3501 to 3750 CT-cables > 60 V

    3751 to 3999 VT-cables > 60 V

    4001 to 4999 Control cables

  • 8/20/2019 KKS Handbook Rev B

    13/63

     

    Dwg. No. / Doc.

    Int Doc N°

    Rev

    LOTR-VSPO-AC90-9-0050-TR

    2840-004970

    B

    EMPLOYER. HYDROELECTRICA – S. A. DRAWN KINASBERGER 2007.07.03

    PLANT HPP LOTRU CIUNGET CHECK TUNG 2007.07.18

    ORDER No.. 23674 APPR. SALLFERT 2007.08.03 SHEET 13 / 63 

    6. Identif ication of I&C equipment

    6.1 Signal identi fication

    General signal designation:

    The component code level is used to identify the various signals from measured dataand signal processing identified on the system and equipment levels. 

    BDL 0 1 2 3

    DefinitionPart ofplant

    System code Equipment unit code Signal code

    Name G F0  F1 F2 F3 FN  A1  A2  AN  A3  B1  B2  BN 

    Type of key N N (N) A A A N N A A N N N (A) A A N N

     Prefix X, Y or Z Signal range Signal number  

    The initial letters X, Y and Z have the following meaning:X Signal originsY Signal applications

    Z Gated signalsThe signal areas or application areas are identified by the second alpha character B2.The two numerical characters BN specify the individual signal type or application.

  • 8/20/2019 KKS Handbook Rev B

    14/63

     

    Dwg. No. / Doc.

    Int Doc N°

    Rev

    LOTR-VSPO-AC90-9-0050-TR

    2840-004970

    B

    EMPLOYER. HYDROELECTRICA – S. A. DRAWN KINASBERGER 2007.07.03

    PLANT HPP LOTRU CIUNGET CHECK TUNG 2007.07.18

    ORDER No.. 23674 APPR. SALLFERT 2007.08.03 SHEET 14 / 63 

    Signal area code letters:

    X Z YSignalarea Definition binary/analog Description

    x x x A Automatic control (group control, ...) binaryx x B Individual control (drive control, ...) binaryx x C Individual closed-loop control binary/analog not turbine governor, no field signalsx x x D free to usex x x E Excitation signals binaryx x x F Protection signals binaryx x G Contact binary field devicesx x x H Limit value derived from analog values binaryx x x J Black-box signals analogx x x K Black-box signals binaryx x x L Control room and control station signals

    x x M static individual or group fault signals binaryx x x N Operating and monitoring signals binaryx x x P Operating and monitoring signals analogx x x Q Analog signals analog field devices, ...x x R Higher-level control binary/analog no field signalsx S Steps of control sequences binaryx x x T Turbine governor signalsx x x U gated signals - free to use binary/analogx x x V gated signals - free to use binary/analogx x x W gated signals - free to use binary/analog

    X not available do not useY not available do not useZ not available do not use

    The Signals 51 to 99 are the antivalent comparable signals or applications.

    For example: XB01 … ON

    XB51 … NOT ON

    The predefined signal numbers are listed in chapter 7.4 of this document.

  • 8/20/2019 KKS Handbook Rev B

    15/63

     

    Dwg. No. / Doc.

    Int Doc N°

    Rev

    LOTR-VSPO-AC90-9-0050-TR

    2840-004970

    B

    EMPLOYER. HYDROELECTRICA – S. A. DRAWN KINASBERGER 2007.07.03

    PLANT HPP LOTRU CIUNGET CHECK TUNG 2007.07.18

    ORDER No.. 23674 APPR. SALLFERT 2007.08.03 SHEET 15 / 63 

    7. KKS Reference List

    7.1 Breakdown level 1

    A Grid and distribution systemsB Power Transmission and Auxiliary Power SupplyC Instrumentation and control equipmentG Water supply and disposalL Steam, water, gas cyclesM Main machine setsP Cooling water systemsQ Auxiliary systemsS Ancillary SystemsU StructuresX Heavy MachineryZ Workshop and office equipment

  • 8/20/2019 KKS Handbook Rev B

    16/63

     

    Dwg. No. / Doc.

    Int Doc N°

    Rev

    LOTR-VSPO-AC90-9-0050-TR

    2840-004970

    B

    EMPLOYER. HYDROELECTRICA – S. A. DRAWN KINASBERGER 2007.07.03

    PLANT HPP LOTRU CIUNGET CHECK TUNG 2007.07.18

    ORDER No.. 23674 APPR. SALLFERT 2007.08.03 SHEET 16 / 63 

    KKS Code

    BDL1 Description Remark

    Grid and distribution systems Grid and distribution systems

    > 420kV-Systems > 420kV-Systems

    ABA 420kV-System Unit 1, busbar 1

    ABB 420kV-System Unit 2, busbar 2

     AB

    ABC 420kV-System Feeder, coupling, not busbar 1 nor busbar 2

    380 (-420) kV-Sys tems 380 (-420) kV-Sys tems

    ACA 380 - 420 kV-System Unit 1, busbar 1

    ACB 380 - 420 kV-System Unit 2, busbar 2

     AC

    ACC 380 - 420 kV-System Feeder, coupling, not busbar 1 nor busbar 2

    220 (-245) kV-Sys tems 220 (-245) kV-Sys tems

    ADA 220 - 245 kV-System Unit 1, busbar 1

    ADB 220 - 245 kV-System Unit 2, busbar 2

    ADC 220 - 245 kV-System Feeder, coupling, not busbar 1 nor busbar 2

     AD

    ADT Transformer General-purpose transformer

    110 (-150) kV-Sys tems 110 (-150) kV-Sys tems

    AEA 110 - 150 kV-System Unit 1, busbar 1

    AEB 110 - 150 kV-System Unit 2, busbar 2

     AE

    AEC 110 - 150 kV-System Feeder, coupling, not busbar 1 nor busbar 2

    AET Transformer General-purpose transformer

    60 (-72) kV-Systems 60 (-72) kV-Systems

    AFA 60 - 72 kV-System Unit 1, busbar 1

    AFB 60 - 72 kV-System Unit 2, busbar 2

     AF

    AFC 60 - 72 kV-System Feeder, coupling, not busbar 1 nor busbar 2

    45 (-50) kV-Systems 45 (-50) kV-Systems

    AGA 45 - 50 kV-System Unit 1, busbar 1

    AGB 45 - 50 kV-System Unit 2, busbar 2

     AG

    AGC 45 - 50 kV-System Feeder, coupling, not busbar 1 nor busbar 2

    30 (-35) kV-Systems 30 (-35) kV-Systems

    AHA 30 - 35 kV-System Unit 1, busbar 1

    AHB 30 - 35 kV-System Unit 2, busbar 2

     AH

    AHC 30 - 35 kV-System Feeder, coupling, not busbar 1 nor busbar 2

    20 (-25) kV-Systems 20 (-25) kV-Systems

    AJA 20 - 25kV-System Unit 1, busbar 1

    AJB 20 - 25kV-System Unit 2, busbar 2

     AJ

    AJC 20 - 25kV-System Feeder, coupling, not busbar 1 nor busbar 2

    10 (-15) kV-Systems 10 (-15) kV-Systems

    AKA 10 - 15kV-System Unit 1, busbar 1

    AKB 10 - 15kV-System Unit 2, busbar 2

     AK

    AKC 10 - 15kV-System Feeder, coupling, not busbar 1 nor busbar 2

    6 (5) kV-Systems 6 (5) kV-Systems

    ALA 5 - 6kV-System Unit 1, busbar 1

    ALB 5 - 6kV-System Unit 2, busbar 2

     AL

    ALC 5 - 6kV-System Feeder, coupling, not busbar 1 nor busbar 2

    1 (-3) kV-Systems 1 (-3) kV-Systems

    AMA 1 - 3kV-System Unit 1, busbar 1

    AMB 1 - 3kV-System Unit 2, busbar 2

     A

     AM

    AMC 1 - 3kV-System Feeder, coupling, not busbar 1 nor busbar 2

  • 8/20/2019 KKS Handbook Rev B

    17/63

     

    Dwg. No. / Doc.

    Int Doc N°

    Rev

    LOTR-VSPO-AC90-9-0050-TR

    2840-004970

    B

    EMPLOYER. HYDROELECTRICA – S. A. DRAWN KINASBERGER 2007.07.03

    PLANT HPP LOTRU CIUNGET CHECK TUNG 2007.07.18

    ORDER No.. 23674 APPR. SALLFERT 2007.08.03 SHEET 17 / 63 

    < 1kV-Systems < 1kV-Systems

    ANA 500 - 1000V 3-phase system Low voltage switchgear 500-1000V, 3-phase AC

    ANB

  • 8/20/2019 KKS Handbook Rev B

    18/63

     

    Dwg. No. / Doc.

    Int Doc N°

    Rev

    LOTR-VSPO-AC90-9-0050-TR

    2840-004970

    B

    EMPLOYER. HYDROELECTRICA – S. A. DRAWN KINASBERGER 2007.07.03

    PLANT HPP LOTRU CIUNGET CHECK TUNG 2007.07.18

    ORDER No.. 23674 APPR. SALLFERT 2007.08.03 SHEET 18 / 63 

    AYE Fire alarm system Fire alarm system

    AYF Clock system Clock system

    AYG Remote control system Remote control system

    AYH Telemetry system Telemetry system

    AYJ Remote metering system Remote metering systemAYK HF carrier telephone system HF carrier telephone system

    AYP Optical monitoring system Optical monitoring system

    AYQ General gas alarm system (if not assignedto specific system)

    General gas alarm system (if not assigned tospecific system)

    AYS Radiotelephone system Radiotelephone system

    KKS Code

    BDL1 Description Remark

    Power Transmission and AuxiliaryPower Supply

    Power Transmission and Auxiliary PowerSupply

    Power transmission Power transmission

    BAA Generator leads Generator leads from excl. generator bushings,incl. current- and voltage transformers, coolingand ventilation systems to excl. generatortransformer low side bushings or to excl. auxiliarypower transformer high side bushing test

    BAB Generator star point Foundation cabinetsBAC Generator circuit breaker Generator circuit breaker, also commutating pole

    circuit breaker, incl. cooling systemBAT Generator transformer Generator transformers, including cooling systemBAU Earthing and Iightning protection

    equipment Earthing and lightning protection equipmentBAX Fluid supply system for control and

    protection equipment Fluid supply system for control and protectionequipment

    BA

    BAY Protection Electrical control and protection equipment

    Medium-voltage distribution Medium-voltage distribution boards andtransformers, normal system

    BBA .kV Medium voltage distribution Medium voltage distribution 1 normal systemBBB .kV Medium voltage distribution Medium voltage distribution 2 normal systemBBC .kV Medium voltage distribution Medium voltage distribution 3 normal systemBBD .kV Medium voltage distribution Medium voltage distribution 4 normal systemBBT Unit transformer (or Auxiliary power

    transformers)Medium voltage auxiliary power transformers

    BBX Fluid supply system for control andprotection equipment

    Fluid supply system for control and protectionequipment

    BB

    BBY Protection Electrical control and protection equipmentMedium voltage distributi on boardsand transformers, general-purpose

    Medium voltage distributi on boards andtransformers, general-purpose

    BCA Start-up distribution Medium voltage start-up, offsite, general-purposedistribution

    BCT Start-up transformer Start-up, offsite, general-purpose transformers

    BCX Fluid supply system for control andprotection equipment

    Fluid supply system for control and protectionequipment

    BC

    BCY Protection Electrical control and protection equipment

    Low voltage main distribution Low voltage main distribution boards andtransformers, normal system

    BFA 0, .kV Low voltage main distribution Low voltage main distribution 1, normal system

    BFB 0, .kV Low voltage main distribution Low voltage main distribution 2, normal system

    B

    BF

    BFC 0, .kV Low voltage main distribution Low voltage main distribution 3, normal system

  • 8/20/2019 KKS Handbook Rev B

    19/63

     

    Dwg. No. / Doc.

    Int Doc N°

    Rev

    LOTR-VSPO-AC90-9-0050-TR

    2840-004970

    B

    EMPLOYER. HYDROELECTRICA – S. A. DRAWN KINASBERGER 2007.07.03

    PLANT HPP LOTRU CIUNGET CHECK TUNG 2007.07.18

    ORDER No.. 23674 APPR. SALLFERT 2007.08.03 SHEET 19 / 63 

    BFD 0, .kV Low voltage main distribution Low voltage main distribution 4, normal system

    BFT 0, .kV Auxiliary transformer Low voltage auxiliary power transformers

    BFX Fluid supply system for control andprotection equipment

    Fluid supply system for control and protectionequipment

    BFY Protection ProtectionLow voltage main distribution Low voltage main distribution boards and

    transformers, general purpose

    BHA 0, .kV Low voltage main distribution Low voltage main distribution 1, general purpose

    BHB 0, .kV Low voltage main distribution Low voltage main distribution 2, general purpose

    BHC 0, .kV Low voltage main distribution Low voltage main distribution 3, general purpose

    BHD 0, .kV Low voltage main distribution Low voltage main distribution 4, general purpose

    BHT 0, .kV Auxiliary transformer Low voltage auxiliary power transformers

    BHX Fluid supply system for control andprotection equipment

    Fluid supply system for control and protectionequipment

    BH

    BHY Protection Protection

    Low voltage sub distribution Low voltage sub distribution boards and

    transformers, normal systemBJA 0, .kV Low voltage sub distribution Low voltage sub distribution 1, normal system

    BJB 0, .kV Low voltage sub distribution Low voltage sub distribution 2, normal system

    BJC 0, .kV Low voltage sub distribution Low voltage sub distribution 3, normal system

    BJD 0, .kV Low voltage sub distribution Low voltage sub distribution 4, normal system

    BJT 0, .kV Auxiliary transformer Low voltage auxiliary power transformers

    BJX Fluid supply system for control andprotection equipment

    Fluid supply system for control and protectionequipment

    BJ

    BJY Protection Protection

    Low voltage sub distribution Low voltage sub distribution boards andtransformers, general purpose

    BLA 0, .kV Low voltage sub distribution Low voltage sub distribution 1, general purpose

    BLB 0, .kV Low voltage sub distribution Low voltage sub distribution 2, general purposeBLC 0, .kV Low voltage sub distribution Low voltage sub distribution 3, general purpose

    BLD 0, .kV Low voltage sub distribution Low voltage sub distribution 4, general purpose

    BLT 0, .kV Auxiliary transformer Low voltage auxiliary power transformers

    BLX Fluid supply system for control andprotection equipment

    Fluid supply system for control and protectionequipment

    BL

    BLY Protection Protection

    Low vol tage distribution (diesel)emergency power system

    Low voltage distribution boards andtransformers, (diesel) emergency powersystem 1

    BMA Low voltage emergency distribution board Low voltage emergency distribution boards(emergency diesel)

    BMB Low voltage emergency distribution board Emergency lightning and emergency distributionBMT Low voltage emergency power

    transformersLow voltage emergency power transformers

    BMX Fluid supply system for control andprotection equipment

    Fluid supply system for control and protectionequipment

    BM

    BMY Protection Electrical control and protection equipment

    Low vol tage distribution (diesel)emergency power system

    Low voltage distribution boards andtransformers, (diesel) emergency powersystem 2

    BNA Low voltage emergency distribution board Low voltage emergency distribution boards(emergency diesel)

    BNB Low voltage emergency distribution board Emergency lightning and emergency distribution

    BN

    BNT Low voltage emergency powertransformers

    Low voltage emergency power transformers

  • 8/20/2019 KKS Handbook Rev B

    20/63

     

    Dwg. No. / Doc.

    Int Doc N°

    Rev

    LOTR-VSPO-AC90-9-0050-TR

    2840-004970

    B

    EMPLOYER. HYDROELECTRICA – S. A. DRAWN KINASBERGER 2007.07.03

    PLANT HPP LOTRU CIUNGET CHECK TUNG 2007.07.18

    ORDER No.. 23674 APPR. SALLFERT 2007.08.03 SHEET 20 / 63 

    BNX Fluid supply system for control andprotection equipment

    Fluid supply system for control and protectionequipment

    BNY Protection Electrical control and protection equipment

    Power installations for electricalvariable-speed drives

    Power installations for variable-speed drives(e.g. for feedwater pump, excitationequipment, not power adjusters inswitchgear)

    BPA Frequency converter Power installations for variable-speed drives (freefor use)

    BPB Excitation transformer Power installations for variable-speed drives (freefor use)

    BPX Fluid supply system for control andprotection equipment

    Fluid supply system for control and protectionequipment

    BP

    BPY Protection Electrical control and protection equipment

    Low voltage distribution,uninterruptible power supply

    Low voltage distribution boards,uninterruptible (converter) power supply

    BRA 230VDC UPS-Emergency 1

    230VAC Safe Busbar 1

    Low voltage distribution boards, uninterruptible

    (converter) power supplyBRB 230VDC UPS-Emergency 2

    230VAC Safe Busbar 2Low voltage distribution boards, uninterruptible(converter) power supply

    BRU AC-Converter Converter (static), inverter

    BRX Fluid supply system for control andprotection equipment

    Fluid supply system for control and protectionequipment

    BR

    BRY Protection Electrical control and protection equipment

    Battery system Battery system

    BTA 220V Battery 1 Batteries (free for use)

    BTB 220V Battery 2 Batteries (free for use)

    BTC 125V Battery Batteries (free for use)

    BTL 220V Battery charger 1 Rectifiers, battery chargers (free for use)

    BTM 220V Battery charger 2 Rectifiers, battery chargers (free for use)

    BT

    BTN 125V Battery charger Rectifiers, battery chargers (free for use)

    DC Distribution, normal system DC Distribution boards, normal system

    BUA 220 VDC distribution board 1 DC Distribution boards, normal system (free foruse)

    BUB 220 VDC distribution board 1 DC Distribution boards, normal system (free foruse)

    BUC 110 VDC distribution board, common part 110 VDC distribution board, common part

    BUD 110 VDC distribution board, common part,fail safe

    110 VDC distribution board, common part, failsafe

    BUE 24VDC distribution board 1 24VDC distribution board 1

    BUF 24VDC distribution board 2 24VDC distribution board 2

    BUH 24VDC distribution board, common part 24VDC distribution board, common partBUX Fluid supply system for control and

    protection equipmentFluid supply system for control and protectionequipment

    BU

    BUY Protection Protection

    KKS Code

    BDL1 Description Remark

    Instrumentation and control equipment Instrumentation and control equipment

    Protective interlock Protective interlock

    C

    CA

    CAA Cabinet for protective interlock Cabinet for protective interlock (free for use)

  • 8/20/2019 KKS Handbook Rev B

    21/63

     

    Dwg. No. / Doc.

    Int Doc N°

    Rev

    LOTR-VSPO-AC90-9-0050-TR

    2840-004970

    B

    EMPLOYER. HYDROELECTRICA – S. A. DRAWN KINASBERGER 2007.07.03

    PLANT HPP LOTRU CIUNGET CHECK TUNG 2007.07.18

    ORDER No.. 23674 APPR. SALLFERT 2007.08.03 SHEET 21 / 63 

    CAB Cabinet for protective interlock Cabinet for protective interlock (free for use)

    CAC Cabinet for protective interlock Cabinet for protective interlock (free for use)

    CAD Cabinet for protective interlock Cabinet for protective interlock (free for use)

    CAE Cabinet for protective interlock Cabinet for protective interlock (free for use)

    Functional group control, Subloopcontrol

    Functional group control, Subloop control

    CBA Cabinet for protective interlock - turbine Cabinets for functional group control (free for use)CBB Cabinet for protective interlock - generator

    Cabinets for functional group control (free for use)CBC Cabinet for protective interlock - auxiliary

    control Cabinets for functional group control (free for use)CBD Control cabinet 4 Cabinets for functional group control (free for use)CBE Control cabinet 5 Cabinets for functional group control (free for use)CBF Control cabinet 6 Cabinets for functional group control (free for use)CBP Cabinet for synchronization Cabinet for synchronization

    CB

    CBQ Cabinet for auxiliary power changeover Cabinet for auxiliary power changeover

     Annunciat ion Annunciat ionCE

    CEJ Fault recording Fault recording

    Measurement, recordi ng Measurement, recordi ng

    CFA Cabinet for measurement 1 Cabinet for measurement (free for use)

    CFB Cabinet for measurement 2 Cabinet for measurement (free for use)

    CFC Cabinet for measurement 3 Cabinet for measurement (free for use)

    CFD Cabinet for measurement 4 Cabinet for measurement (free for use)

    CF

    CFQ Cabinet for metering Cabinet for recording (meters, pen recorders)

    Closed-loop control Closed-loop control

    CGA Closed-loop control cabinet Cabinets for closed-loop control (free for use)

    CG

    CGB Closed-loop control cabinet Cabinets for closed-loop control (free for use)

    Protection ProtectionCHA Cabinets for protection system 1 Cabinets for generator and transformer protection

    (free for use)

    CHC Cabinets for protection system 2 Cabinets for generator and transformer protection(free for use)

    CHC Cabinets for protection system 3 Cabinets for generator and transformer protection(free for use)

    CHD Cabinets for protection system 4 Cabinets for generator and transformer protection(free for use)

    CH

    CHY Protection Protection , emergency stop cabinet

    Unit coordination level Unit coordination level

    CJA Unit control system Unit control system

    CJ

    CJD Start-up control, setpoint control Start-up control, setpoint control

    Process computer system Process computer system

    CKA Online supervisory and diagnosticcomputer 1

    Online supervisory and diagnostic computer (freefor use)

    CKB Online supervisory and diagnosticcomputer 2

    Online supervisory and diagnostic computer (freefor use)

    CKC Online supervisory and diagnosticcomputer 3

    Online supervisory and diagnostic computer (freefor use)

    CKF Process computer joint control Process computer joint control

    CKM Patrol monitoring system Access control computer (free for use)

    CKN Process computer system 1 Process computer system (free for use)

    CKP Process computer system 2 Process computer system (free for use)

    CK

    CKQ Process computer system 3 Process computer system (free for use)

  • 8/20/2019 KKS Handbook Rev B

    22/63

     

    Dwg. No. / Doc.

    Int Doc N°

    Rev

    LOTR-VSPO-AC90-9-0050-TR

    2840-004970

    B

    EMPLOYER. HYDROELECTRICA – S. A. DRAWN KINASBERGER 2007.07.03

    PLANT HPP LOTRU CIUNGET CHECK TUNG 2007.07.18

    ORDER No.. 23674 APPR. SALLFERT 2007.08.03 SHEET 22 / 63 

    Instrumentation and control equipment Instrumentation and control equipment

    CMA Instrumentation and control system 1 Instrumentation and control equipment (free foruse)

    CMB Instrumentation and control system 2 Instrumentation and control equipment (free foruse)

    CMC Instrumentation and control system 3 Instrumentation and control equipment (free foruse)

    CM

    CMD Instrumentation and control system 4 Instrumentation and control equipment (free foruse)

    Marshalling rack Marshalling racks

    CVA Marshalling rack, system 1 Marshalling racks (cabinets)

    CVB Marshalling rack, system 2 Marshalling racks (cabinets)

    CVC Marshalling rack, system 3 Marshalling racks (cabinets)

    CVD Marshalling rack, system 4 Marshalling racks (cabinets)

    CVG Marshalling rack Marshalling rack water treatment system

    CVM Marshalling rack Marshalling rack heavy machinery, generator

    CVP Marshalling rack Marshalling rack cooling water system

    CV

    CVQ Marshalling rack Marshalling rack auxiliary plant

    Control room Control rooms

    CWA Main control console 1 Main control console 1

    CWB Main control console 2 Main control console 2

    CWC Main control console 3 Main control console 3

    CWD Main control console 4 Main control console 4

    CWD Plotter table Plotter table

    CWF Main control panels 1 Main control panels 1

    CW

    CWF Main control panels 1 Main control panels 1

    Local control station Local control stations

    CXA Local control station - turbine Local control station - turbine

    CXC Local control station - water treatmentsystem

    Local control station - water treatment system

    CXD Local control station - diesel engine plant Local control station - diesel engine plant

    CXG Local control station - process drainagesystem

    Local control station - process drainage system

    CXM Local control station - generator Local control station - generator

    CX

    CXP Local control station - cooling watersystem

    Local control station - cooling water system

    Communication equipment Communication equipment

    CYA Telephone system Telephone system (PABX)

    CYB Control console telephone system Control console telephone system

    CYE Fire alarm system Fire alarm system

    CYF Clock system Clock system

    CYG Remote control system Remote control system

    CYK HF carrier telephone system HF carrier telephone system

    CYL Radio paging system Radio paging system

    CYN Public address system Public address system

    CYP Optical monitoring system Optical monitoring system

    CY

    CYS Radiotelephone system Radiotelephone system

    KKS Code

    BDL1 Description Remark

  • 8/20/2019 KKS Handbook Rev B

    23/63

     

    Dwg. No. / Doc.

    Int Doc N°

    Rev

    LOTR-VSPO-AC90-9-0050-TR

    2840-004970

    B

    EMPLOYER. HYDROELECTRICA – S. A. DRAWN KINASBERGER 2007.07.03

    PLANT HPP LOTRU CIUNGET CHECK TUNG 2007.07.18

    ORDER No.. 23674 APPR. SALLFERT 2007.08.03 SHEET 23 / 63 

    Water supply and disposal Water supply and disposal

    Raw water suppl y Raw water suppl y

    GAA Extraction, mechanical cleaning Extraction, mechanical cleaning from incl. intaketo incl. mechanical cleaning system outlet

    GAC Piping and channel system Piping and channel system from excl. intake orfrom excl. outlet of other system to excl. inlet toother system

    GAD Storage system Storage system from incl. storage system inlet toincl. storage system outlet, incl. intake and outfall

    GAF Pump system Pump system from incl. pump system suctionnozzle to incl. pump system discharge nozzle

    GAV Lubricant supply system Lubricant supply system

    GAX Fluid supply system for control andprotection equipment

    Fluid supply system for control and protectionequipment

    GA

    GAY Control and protection equipment Control and protection equipment. Only formechanical equipment (pneumatic or hydraulic)

    Distribution systems Distribution systems (not drinking water)

    GHC Distribution systems after treatment(demineralization) tanks

    GH

    GHD Distribution systems after treatm. (others)Distribution systems after treatment (others)

    Drinking water supply Drinking water supply

    GKA Receiving point Online supervisory and diagnostic computer (freefor use)

    GKB Storage, forwarding, distribution system Online supervisory and diagnostic computer (freefor use)

    GKC Drinking water supply Drinking water supply

    GKD Drinking water supply Drinking water supply (free for use)

    GKE Drinking water supply Drinking water supply (free for use)

    GKF Drinking water supply Drinking water supply (free for use)

    GKG Drinking water supply Drinking water supply (free for use)GKH Drinking water supply Drinking water supply (free for use)

    GKJ Drinking water supply Drinking water supply (free for use)

    GKX Fluid supply system for control andprotection equipment

    Fluid supply system for control and protectionequipment

    GK

    GKY Protection Protection

    Dewatering syst em Dewatering syst em

    GMA Dewatering system Dewatering system (free for use)

    GMB Dewatering system Dewatering system (free for use)

    GMC Dewatering system Dewatering system (free for use)

    GMD Dewatering system Dewatering system (free for use)

    GME Dewatering system Dewatering system (free for use)

    GMF Dewatering system Dewatering system (free for use)

    GMG Dewatering system GT wash water

    GMH Dewatering system Boiler house

    GMM Storage dewatering system Storage dewatering system

    GMP Dewatering system Pump house

    GMT Dewatering system Sprinkler system

    GMX Fluid supply system for control andprotection equipment

    Fluid supply system for control and protectionequipment

    G

    GM

    GMY Protection Protection

    Drainage system Drainage system

    GQA drainage system drainage system (free for use)

    GQ

    GQA GQA10 drainage pit, pumps and level switches drainage pit, pumps and level switches

  • 8/20/2019 KKS Handbook Rev B

    24/63

     

    Dwg. No. / Doc.

    Int Doc N°

    Rev

    LOTR-VSPO-AC90-9-0050-TR

    2840-004970

    B

    EMPLOYER. HYDROELECTRICA – S. A. DRAWN KINASBERGER 2007.07.03

    PLANT HPP LOTRU CIUNGET CHECK TUNG 2007.07.18

    ORDER No.. 23674 APPR. SALLFERT 2007.08.03 SHEET 24 / 63 

    GQB drainage system drainage system (free for use)

    GQC drainage system drainage system (free for use)

    GQD drainage system drainage system (free for use)

    GQE drainage system drainage system (free for use)

    GQG drainage system  GT wash waterGQH drainage system  Boiler houseGQM Storage process drainage system Storage process drainage system

    GQP drainage system Pump house

    GQT drainage system Sprinkler system

    GQX Fluid supply system for control andprotection equipment

    Fluid supply system for control and protectionequipment

    GQY Protection Protection

    KKS Code

    BDL1 Description Remark

    Steam, water, gas cycles Steam, water, gas cycl es

    Water impounding works forhydroelectric power plant

    Water impounding works for hydroelectricpower plant

    LNA Water niveau metering Water niveau metering at the water impoundingwork

    LNB Trash rack, trash/fish barrier Trash rack, trash/fish barrier

    LNC Dam, weir system Dam, weir system

    LND Spillway Spillway

    LNE Drainage system Drainage system

    LNF Pump system Pump system

    LNV Lubricant supply system Lubricant supply system

    LNW Sealing water supply system from incl. sealing water supply main isolatingvalve to excl. casing nozzle of sealing water user

    LNX Fluid supply system for control andprotection equipment

    Fluid supply system for control and protectionequipment

    LN

    LNY Protection Protection

    Intake system, upper water system forhydroelectric pow erplant

    Intake system, upper water system forhydroelectric powerplant

    LPA Cleaning system Separate out and collect floating matter fromheadrace

    LPB Isolating equipment Isolating equipment

    LPC Piping and penstock system from incl. receiving point to incl. discharge intoturbine system, incl. connecting piping for pump

    systemLPE Surge tank Surge tank

    LPV Lubricant supply system Lubricant supply system

    LPW Sealing water supply system from incl. sealing water supply main isolatingvalve to excl. casing nozzle of sealing water user

    LPX Fluid supply system for control andprotection equipment

    Fluid supply system for control and protectionequipment

    LP

    LPY Protection Protection

    Tail race system, under water systemfor hydroelectric power plant

    Tail race system, under water system forhydroelectric power plant

    LQA Underwater piping and culvert system Underwater piping and culvert system

    LQB Surge tank Surge tank

    L

    LQ

    LQC Isolating equipment Isolating equipment

  • 8/20/2019 KKS Handbook Rev B

    25/63

     

    Dwg. No. / Doc.

    Int Doc N°

    Rev

    LOTR-VSPO-AC90-9-0050-TR

    2840-004970

    B

    EMPLOYER. HYDROELECTRICA – S. A. DRAWN KINASBERGER 2007.07.03

    PLANT HPP LOTRU CIUNGET CHECK TUNG 2007.07.18

    ORDER No.. 23674 APPR. SALLFERT 2007.08.03 SHEET 25 / 63 

    LQE Cleaning system for pumped-storageoperation

    Cleaning system for pumped-storage operation

    LQV Lubricant supply system Lubricant supply system

    LQW Sealing water supply system from incl. sealing water supply main isolatingvalve to excl. casing nozzle of sealing water user

    LQX Fluid supply system for control andprotection equipment

    Fluid supply system for control and protectionequipment

    LQY Protection Protection

    Common installations for hydr oelectricpower plant

    Common installations for hydroelectricpower plant

    LS

    LSL Drainage system Drainage system

    KKS Code

    BDL1 Description Remark

    Main machine sets Main machine setsHydraulic turbine plant Hydraulic turbine plant

    Turbine Turbine from excl. turbine inlet or from excl. inletvalve to incl. turbine outlet or to excl. isolatingvalve, incl. draft tube

    MEA10 Spiral case Spiral case

    MEA20 Wicket gate, nozzles Wicket gate, nozzles

    MEA30 Runner, deflector runner, deflector

    MEA40 Shaft Shaft

    MEA50 Turbine brake system Turbine brake system

    MEA

    MEA60 Revision sealing Revision sealing

    Isolating valve blocking headwater before turbine MEA and/or

    setting headwater for turbine MEA

    MEB

    MEB10 Turbine main valve Turbine main valve

    Bearings Bearings

    MED10 Thrust bearing Thrust bearing

    MED

    MED20 Guide bearing Guide bearing

    Stabilizing air system Stabilizing air system from incl. air compressorto incl. outlet to turbine

    MEG10 Compressor Compressor

    MEG20 Pressure tank Pressure tank

    MEG

    MEG50 Instruments Instruments 

    Gear Transmission gear between prime mover anddriven machine, incl. turning gear, barring gear

    MEK10 Converter Converter

    MEK

    MEK20 Gearbox Gearbox

    Water depression air supply system from incl. air compressor to incl. outlet to turbine

    MEL10 Compressor Compressor

    MEL20 Pressure tank Pressure tank

    MEL30 Control Control

    MEL

    MEL50 Instruments Instruments

    Labyrinth cooling water system Labyrinth cooling water system

    MES10 Cooling water system pumps Cooling water system pumps

    MES20 Cooling water extraction Cooling water extraction

    MES30 Cooling water system filter Cooling water system filter

    MES40 Cooling water system distribution Cooling water system distribution

    MME

    MES

    MES70 Cooling water elevated tank Cooling water elevated tank 

  • 8/20/2019 KKS Handbook Rev B

    26/63

     

    Dwg. No. / Doc.

    Int Doc N°

    Rev

    LOTR-VSPO-AC90-9-0050-TR

    2840-004970

    B

    EMPLOYER. HYDROELECTRICA – S. A. DRAWN KINASBERGER 2007.07.03

    PLANT HPP LOTRU CIUNGET CHECK TUNG 2007.07.18

    ORDER No.. 23674 APPR. SALLFERT 2007.08.03 SHEET 26 / 63 

    Lubricant supply system from incl. lubricant tank to excl. user and fromexcl. user

    MEV10 Oil supply combined thrust and guidebearing

    Oil supply combined thrust and guide bearing

    MEV20 Oil supply thrust bearing Oil supply thrust bearing

    MEV30 Bearing load relieving Bearing load relieving

    MEV60 Oil mist extraction Oil mist extraction

    MEV70 Bearing oil elevated tank Bearing oil elevated tank

    MEV80 Lubricating grease system Lubricating grease system

    MEV

    MEV90 Lubricant water supply Lubricant water supply

    Sealing water supply system from incl. sealing water supply main isolatingvalve to excl. casing nozzle of sealing wateruser

    MEW10 Sealing water pump Sealing water pump

    MEW30 Sealing water conditioning Sealing water conditioning

    MEW

    MEW40 Sealing water distribution Sealing water distribution

    Hydraulic oil Non-electric control and protection equipment,

    incl. fluid supply systemMEX10 Oil pressure generation Oil pressure generation

    MEX20 Wicked gate, nozzle control Wicked gate, nozzle control

    MEX30 Runner- and deflector control Runner- and deflector control

    MEX50 Brake control Brake control

    MEX60 Pressure oil generation and control forshut-off valve

    Pressure oil generation and control for shut-offvalve

    MEX

    MEX70 Safety and emergency shutdownequipment

    Safety and emergency shutdown equipment

    Electrical control and protectionequipment

    Electrical control and protection equipment

    MEY10 Turbine governor Turbine governor

    MEY

    MEY30 Speed acquisition and evaluation Speed acquisition and evaluation

    Pumping turbine plant in pumped-storage power plants

    Pumping turbine plant in pumped-storagepower plants

    MFA Pumping turbine, pump and turbine asintegral unit

    Pumping turbine, pump and turbine as integralunit

    MFB Isolating equipment blocking headwater before turbine MFA and/orsetting headwater for turbine MFA

    MFD Bearings Bearings

    MFG Stabilizing air system Stabilizing air system from incl. air compressorto incl. outlet to turbine

    MFK Gear Transmission gear between motor generator setand pumping turbine

    MFL Water depression air supply system from incl. air compressor to incl. outlet to turbine

    MFM Start-up unit Start-up unit

    MFS Shaft gland cooling water system Shaft gland cooling water system

    MFV Lubricant oil supply system Lubricant oil supply system

    MFW Sealing fluid system Sealing fluid system

    MFX Control oil Fluid supply system for control and protectionequipment

    MF

    MFY Control and protection equipment Control and protection equipment

    Pumped-storage plant Pumped-storage plant

    MGA Storage pump (casing, shaft, runner, etc) Storage pump (casing, shaft, runner, etc)

    MGB Isolating valve blocking headwater before storage pump MGAand/or setting water for storage pump MGA

    MGD Bearings Bearings

    MG

    MGK Gear Transmission gear between motor generator setand storage pump

  • 8/20/2019 KKS Handbook Rev B

    27/63

     

    Dwg. No. / Doc.

    Int Doc N°

    Rev

    LOTR-VSPO-AC90-9-0050-TR

    2840-004970

    B

    EMPLOYER. HYDROELECTRICA – S. A. DRAWN KINASBERGER 2007.07.03

    PLANT HPP LOTRU CIUNGET CHECK TUNG 2007.07.18

    ORDER No.. 23674 APPR. SALLFERT 2007.08.03 SHEET 27 / 63 

    MGL Water depression air supply system from incl. air compressor to incl. outlet to turbine

    MGM Start-up unit Start-up unit

    MGS Shaft gland cooling water system Shaft gland cooling water system

    MGV Lubricant oil supply system Lubricant oil supply system

    MGW Sealing fluid system Sealing fluid systemMGX Control oil Fluid supply system for control and protection

    equipmentMGY Control and protection equipment Control and protection equipment

    Generator plant Generator plant

    Generator casing Generator, complete, incl. stator, rotor and allintegral cooling equipment to incl. generatorbushing

    MKA10 Generator rotor Generator rotor

    MKA20 Generator casing incl. stator Generator casing incl. stator

    MKA30 Generator air cooling Generator air cooling

    MKA40 Shaft Shaft

    MKA50 Mechanical brake devices Mechanical brake devices

    MKA

    MKA60 Moist exhaustion system Moist exhaustion system

    Excitation Generator exciter set, even with electricgenerator-brake (only if MKC is insufficient)

    MKB

    MKB10 Electric generator brake Electric generator brake

    Excitation Generator exciter set, even with electricgenerator-brake

    MKC

    MKC10 Excitation Excitation

    Bearings Bearings

    MKD10 Combined bearing (guide and thrust) Combined bearing (guide and thrust)

    MKD

    MKD20 Generator guide bearing Generator guide bearing

    Stator/rotor liquid cooling system, incl.

    coolant supply system

    Stator/rotor liquid cooling system, incl. coolant

    supply system

    MKF

    MKF10 Generator cooling water system Generator cooling water system

    Stator/rotor gas cooling system, incl.coolant supply system

    Stator/rotor gas cooling system, incl. coolantsupply system

    MKG

    MKG10 Generator gas cooling system Generator gas cooling system

    MKH Stator/rotor nitrogen cooling system, incl.coolant supply system

    Stator/rotor nitrogen cooling system, incl.coolant supply system

    MKQ Exhaust gas system Exhaust gas system (if separate system forgenerator)

    MKU Stator/rotor oil cooling system Stator/rotor oil cooling system, incl. coolantsupply system

    Lubricant supply system Lubricant supply system (if separate system forgenerator)

    MKV10 Oil supply combined bearing Oil supply combined bearing

    MKV20 Öil supply guide bearing Öil supply guide bearing

    MKV30 Bearing load relieving Bearing load relieving

    MKV

    MKV60 Oil mist exhaust Oil mist exhaust

    MKX Non el. Control system incl. Fluid supplysystem

    Non el. Control system incl. Fluid supply system

    MK

    MKY Electrical control and protectionequipment

    Electrical control and protection equipment

    Compressor plant Compressor plant

    MMA Compressor Compressor incl. internal system

    MMC Air intake piping system Air intake piping system

    MMD Bearings Bearings

    MM

    MME Intercooling system Intercooling system

  • 8/20/2019 KKS Handbook Rev B

    28/63

     

    Dwg. No. / Doc.

    Int Doc N°

    Rev

    LOTR-VSPO-AC90-9-0050-TR

    2840-004970

    B

    EMPLOYER. HYDROELECTRICA – S. A. DRAWN KINASBERGER 2007.07.03

    PLANT HPP LOTRU CIUNGET CHECK TUNG 2007.07.18

    ORDER No.. 23674 APPR. SALLFERT 2007.08.03 SHEET 28 / 63 

    MMF Recooling system (Aftercooling) Recooling system (Aftercooling)

    MMG Final cooling system Final cooling system

    MMH Discharge piping system Discharge piping system

    MMV Lubricant supply system Lubricant supply system

    MMW Sealing water supply system Sealing water supply systemMMX Fluid supply system for control and

    protection equipmentFluid supply system for control and protectionequipment

    MMY Control and protection equipment Control and protection equipment

    Common installations for mainmachine sets

    Common installations for main machine sets

    MPA Foundation Foundation

    MPB Sheathing Sheathing

    MPG Frame, support structure Frame, support structure

    MPR Forced cooling system Forced cooling system

    MP

    MPS Drying and layup system Drying and layup system

    KKS Code

    BDL1 Description Remark

    Cooling water systems Cooling water systems

    Main cool ing water system Circulating (main cooling) water system

    PAA Extraction, mechanical cleaning for directcooling

    Extraction, mechanical cleaning for direct cooling

    PAB Main cooling water piping and culvertsystem

    Main cooling water piping and culvert system

    PAC Main cooling water pump system Main cooling water pump system

    PAD Cooling tower Cooling tower

    PAE Cooling tower pump systems Cooling tower pump systems

    PAF Condenser cleaning systems Condenser cleaning system incl. allappurtenances

    PAR Make-Up water piping system Make-Up water piping system

    PAS Make-Up water pump system Make-Up water pump system

    PAV Lubricant supply system Lubricant supply system

    PAX Fluid supply system for control andprotection equipment

    Fluid supply system for control and protectionequipment

    PA

    PAY Control and protection equipment Control and protection equipment

    Secondary cool ing water system,conventional area

    Service (secondary cooling) water system,conventional area

    PCA Extraction, mechanical cleaning for direct

    cooling

    Extraction, mechanical cleaning for direct cooling

    PCB Cooling water piping and culvert system Cooling water piping and culvert system

    PCC Cooling water pump system Cooling water pump system

    PCD Recirculation cooling system, outfallcooling system

    Recirculation cooling system, outfall coolingsystem

    PCE Cooling tower pump systems Cooling tower pump systems

    PCH Cleaning system for heat exchanger Cleaning system for heat exchanger

    PCM Secondary cooling water system forgenerator-, motorgenerator-cooling

    Secondary cooling water system for generator-,motorgenerator-cooling

    PCV Lubricant oil supply system Lubricant oil supply system

    PCX Control oil Fluid supply system for control and protectionequipment

    P

    PC

    PCY Control and protection equipment Control and protection equipment

  • 8/20/2019 KKS Handbook Rev B

    29/63

     

    Dwg. No. / Doc.

    Int Doc N°

    Rev

    LOTR-VSPO-AC90-9-0050-TR

    2840-004970

    B

    EMPLOYER. HYDROELECTRICA – S. A. DRAWN KINASBERGER 2007.07.03

    PLANT HPP LOTRU CIUNGET CHECK TUNG 2007.07.18

    ORDER No.. 23674 APPR. SALLFERT 2007.08.03 SHEET 29 / 63 

    Closed cooling water system,conventional area

    Closed cooling water s ystem, conventionalarea

    PGA Closed cooling water system forconventional area - filter

    Closed cooling water system for conventionalarea - filter

    PGB Closed cooling water system forconventional area - piping

    Closed cooling water system for conventionalarea - piping

    PGC Closed cooling water system forconventional area

    Closed cooling water system for conventionalarea

    PGM Cooling water system for generator-,motorgenerator-cooling

    Cooling water system for generator-,motorgenerator-cooling

    PG

    PGY Control and protection equipment Control and protection equipment

    Common equipment for cooling w atersystem

    Common equipment for cooling w ater systemPU

    PUA Common equipment for cooling watersystem

    Common equipment for cooling water system(free for use)

    KKS Code

    BDL1 Description Remark

     Auxi li ary systems Auxi li ary systems

    Central chemicals supply Central chemicals supply

    QCA Central chemicals supply Central chemicals supply

    QCB Central chemicals supply Central chemicals supply

    QCC Central chemicals supply Central chemicals supply

    QC

    QCD Central chemicals supply Central chemicals supply

    Central control air supply Central control air supply

    QFA Central control air generation system Central control air generation system

    QFB General control air supply, Compressedair

    Central control air distribution system

    QFC Instrument airReceiver, storage

    Central control air supply (free for use)

    QFD Adsorption Dryer Adsorption Dryer

    QFV Lube oil, Lube oil supply Lubricant oil supply system

    QFX Control oil Fluid supply system for control and protectionequipment

    QF

    QFY Control and protection equipment Control and protection equipment

    Central oil supply and disposal system Central oil supply and disposal system

    Q

    QS

    QSA Oil regeneration system Oil regeneration system

    KKS Code

    BDL1 Description Remark

     Anci ll ary Sys tems Anci ll ary Sys tems

    Heating, ventilation, air-conditioning(HVAC) systems for conventional area

    Room ventilation

    SAA Heating, ventilation, air-conditioning inconventional area

    Heating, ventilation, air-conditioning inconventional area

    SAB Heating, ventilation, air-conditioning inconventional area

    Heating, ventilation, air-conditioning inconventional area

    S

    SA

    SAC Heating, ventilation, air-conditioning inconventional area

    Heating, ventilation, air-conditioning inconventional area

  • 8/20/2019 KKS Handbook Rev B

    30/63

     

    Dwg. No. / Doc.

    Int Doc N°

    Rev

    LOTR-VSPO-AC90-9-0050-TR

    2840-004970

    B

    EMPLOYER. HYDROELECTRICA – S. A. DRAWN KINASBERGER 2007.07.03

    PLANT HPP LOTRU CIUNGET CHECK TUNG 2007.07.18

    ORDER No.. 23674 APPR. SALLFERT 2007.08.03 SHEET 30 / 63 

    SAH Heating, ventilation, air-conditioning inconventional area (Boiler house)

    Heating, ventilation, air-conditioning inconventional area (Boiler house)

    SAL Heating, ventilation, air-conditioning inconventional area (exhaust air)

    Heating, ventilation, air-conditioning inconventional area (exhaust air)

    SAM Heating, ventilation, air-conditioning inconventional area (machine hall)

    Heating, ventilation, air-conditioning inconventional area (machine hall)

    SAP Heating, ventilation, air-conditioning inconventional area (cooling water system)

    Heating, ventilation, air-conditioning inconventional area (cooling water system)

    Space heating systems Space heating systems

    SBA Space heating system Heating system (heating control room)

    SBB Space heating system Space heating systems (free for use)

    SBE Space heating system Space heating systems (internal heating system,district heating)

    SB

    SBL Space heating system Space heating systems (internal heating system,district heating)

    Stationary compressed air supplies Stationary compressed air supplies (only ifseparate service air exist to the instrument-

    air)SCA Compressed air generation system Compressed air generation system

    SCB Compressed air distribution system Compressed air distribution system

    SCC Vessel for compressed air Vessel for compressed air

    SC

    SCD Dryer Dryer

    Stationary cleaning systems Stationary cleaning systems

    SDA Stationary cleaning systems Stationary cleaning systems

    SDB Stationary cleaning systems Stationary cleaning systems

    SDC Stationary cleaning systems Stationary cleaning systems

    SD

    SDD Stationary cleaning systems Stationary cleaning systems

    Stationary fire protection systems Stationary fire protection systems

    SGA Fire water system, conventional area Fire water system, conventional areaSGC Spray deluge system, conventional area Spray deluge system, conventional area

    SGE Sprinkler system Sprinkler system

    SGF Foam fire-fighting system Foam fire-fighting system

    SGG Tank rook, tank shell cooling system Tank rook, tank shell cooling system

    SGJ CO2 fire-fighting systems CO2 fire-fighting systems

    SGK Halon fire-fighting systems Halon fire-fighting systems

    SGL Portable fire extinguisher Portable fire extinguisher

    SGX Fluid supply system for control andprotection equipment

    Fluid supply system for control and protectionequipment

    SG

    SGY Control and protection equipment Control and protection equipment

    Waterway facili ties Waterway facili ties

    SHA Intake system Intake system (upper pound)

    SHB Look chamber Lock chamber incl. chamber filling and emptyingsystem

    SHC Lock chamber gate (upstream) Lock chamber gate (upstream)

    SHD Lock chamber gate (intermediate) Lock chamber gate (intermediate)

    SHE Lock chamber gate (downstream) Lock chamber gate (downstream)

    SHF Discharge system (lower pound) Discharge system (lower pound)

    SHJ Anti icing system Anti icing system

    SHK Ship impact system Ship impact system

    SHL Leakage drainage system Leakage drainage system

    SHM Rest evacuation system Rest evacuation system

    SHS Minimum water system Minimum water system

    SH

    SHT Fish ladder Fish ladder

  • 8/20/2019 KKS Handbook Rev B

    31/63

     

    Dwg. No. / Doc.

    Int Doc N°

    Rev

    LOTR-VSPO-AC90-9-0050-TR

    2840-004970

    B

    EMPLOYER. HYDROELECTRICA – S. A. DRAWN KINASBERGER 2007.07.03

    PLANT HPP LOTRU CIUNGET CHECK TUNG 2007.07.18

    ORDER No.. 23674 APPR. SALLFERT 2007.08.03 SHEET 31 / 63 

    SHU Woodraft system Woodraft system

    SHV Lubricant supply system Lubricant supply system

    SHW Sealing water supply system Sealing water supply system

    SHX Fluid supply system for control and

    protection equipment

    Fluid supply system for control and protection

    equipmentSHY Control and protection equipment Control and protection equipment

    Cranes, stationary hoists andconveying appliances

    Cranes, stationary hoists and conveyingappliances

    SMA Cranes, stationary hoists and conveyingappliances

    Cranes, stationary hoists and conveyingappliances (free for use)

    SMB Cranes, stationary hoists and conveyingappliances

    Cranes, stationary hoists and conveyingappliances (free for use)

    SMC Cranes, stationary hoists and conveyingappliances

    Cranes, stationary hoists and conveyingappliances (free for use)

    SMD Cranes, stationary hoists and conveyingappliances

    Cranes, stationary hoists and conveyingappliances (free for use)

    SMG Cranes, stationary hoists and conveying

    appliances

    Cranes, stationary hoists and conveying

    appliances (water treatment)SMH Cranes, stationary hoists and conveying

    appliancesCranes, stationary hoists and conveyingappliances (Boiler house)

    SMM Cranes, stationary hoists and conveyingappliances

    Cranes, stationary hoists and conveyingappliances (Machine hall)

    SM

    SMP Cranes, stationary hoists and conveyingappliances

    Cranes, stationary hoists and conveyingappliances (Cooling water)

    Elevators Elevators

    SNA Elevator Elevators (free for use)

    SNB Elevator Elevators (free for use)

    SN

    SNC Elevator Elevators (free for use)

    Road installations Road installations

    SQA Road installations Road installations (free for use)SQB Road installations Road installations (free for use)

    SQC Road installations Road installations (free for use)

    SQD Road installations Road installations (free for use)

    SQ

    SQE Road installations Road installations (free for use)

    Workshop, stores, laboratoryequipment and staff amenities

    Workshop, stores, laboratory equipment andstaff amenities outside controlled area

    STA Workshop equipment Workshop equipment

    STC Maintenance areas Maintenance areas

    STE Stores and filling station equipment Stores and filling station equipment

    STG Laboratory equipment Laboratory equipment

    STP Staff amenities Staff amenities

    ST

    STY Control and protection equipment Control and protection equipment

    KKS Code

    BDL1 Description Remark

    Structures Structures

    Structures for grid and distributionsystems

    Structures for grid and distribution s ystems

    UAA Switchyard structure Switchyard structure

    UAB Grid system switchgear building Grid system switchgear building

    UAC Grid system control building Grid system control building

    U

    UA

    UAD Structures for grid and distribution system Structures for grid and distribution system

  • 8/20/2019 KKS Handbook Rev B

    32/63

     

    Dwg. No. / Doc.

    Int Doc N°

    Rev

    LOTR-VSPO-AC90-9-0050-TR

    2840-004970

    B

    EMPLOYER. HYDROELECTRICA – S. A. DRAWN KINASBERGER 2007.07.03

    PLANT HPP LOTRU CIUNGET CHECK TUNG 2007.07.18

    ORDER No.. 23674 APPR. SALLFERT 2007.08.03 SHEET 32 / 63 

    UAE Structures for pneumatic control system Structures for pneumatic control system

    UAF Structures for grid and distribution system Structures for grid and distribution system

    UAG Structures for transformer Structures for transformer

    UAH Structures for supports and equipment Structures for supports and equipment

    UAX Special structures Special structuresUAY Bridges Bridges

    UAZ Culverts Culverts

    Structures for power transmission andauxiliary power supply

    Structures for power transmission andauxiliary power supply

    UBA Switchgear building Switchgear building

    UBB Structure for power transmission andauxiliary power supply

    Structure for power transmission and auxiliarypower supply

    UBC Structures for offsite system transformers Structures for offsite system transformers

    UBD Structures for low voltage auxiliary powertransformers

    Structures for low voltage auxiliary powertransformers

    UBE Structures for medium voltage auxiliarypower transformers

    Structures for medium voltage auxiliary powertransformers

    UBF Structures for generator transformers Structures for generator transformersUBG Structures for start-up transformers Structures for start-up transformers

    UBH Structures for oil collection pits Structures for oil collection pits

    UBJ Structures for transformer track Structures for transformer track

    UBK Transformer assembly building Transformer assembly building

    UBL Structures for busbars Structures for busbars

    UBM Structures for transformer cooling system Structures for transformer cooling system

    UBN Structures for emergency powergenerating set

    Structures for emergency power generating set

    UBP Emergency power generating and centralwater chiller building

    Emergency power generating and central waterchiller building

    UB

    UBQ Structures for emergency power generatorfuel supply system

    Structures for emergency power generator fuelsupply system

    Structures for instru mentation andcontrol

    Structures for instrumentation and control

    UCA Unit control room building Unit control room building

    UCB Control station building Control station building

    UCC Structure for instrumentation and control Structure for instrumentation and control (freefor use)

    UCD Structure for instrumentation and control Structure for instrumentation and control (freefor use)

    UCE Structure for instrumentation and control Structure for instrumentation and control (freefor use)

    UC

    UCF Structure for instrumentation and control Structure for instrumentation and control (freefor use)

    Structures for water supply anddisposal Structures for water supply and disposal

    UGA Structure for raw water supply Structure for raw water supply

    UGD Structure for demineralisation system Structure for demineralisation system

    UGE Structure for neutralisation system Structure for neutralisation system

    UGF Structure for fire water supply Structure for fire water supply

    UGG Structure for drinking water supply Structure for drinking water supply

    UGH Structure for rainwater Structure for rainwater

    UGK Flocculant mixing chamber Flocculant mixing chamber

    UGL Flocculator structure, flocculator Flocculator structure, flocculator

    UGN Treated water basin Treated water basin

    UGP Sludge thickener Sludge thickener

    UG

    UGQ Sludge dewatering building Sludge dewatering building

  • 8/20/2019 KKS Handbook Rev B

    33/63

     

    Dwg. No. / Doc.

    Int Doc N°

    Rev

    LOTR-VSPO-AC90-9-0050-TR

    2840-004970

    B

    EMPLOYER. HYDROELECTRICA – S. A. DRAWN KINASBERGER 2007.07.03

    PLANT HPP LOTRU CIUNGET CHECK TUNG 2007.07.18

    ORDER No.. 23674 APPR. SALLFERT 2007.08.03 SHEET 33 / 63 

    UGR Sludge storage building Sludge storage building

    UGU Structure for effluent disposal Structure for effluent disposal

    UGV Structure for sewage plant Structure for sewage plant

    Structu res for steam, water, gas-cycles Structu res for steam, water, gas-cycles

    ULN Intake system Intake system (upper pound)

    ULP Look chamber Lock chamber incl. chamber filling and emptyingsystem

    UL

    ULQ Lock chamber gate (upstream) Lock chamber gate (upstream)

    Structures for main machine sets Structures for main machine sets

    UME Hydraulic turbine building Hydraulic turbine building

    UMG Pumped storage turbine building Pumped storage turbine building

    UMJ Diesel engine building Diesel engine building

    UMM Compressor system building Compressor system building

    UM

    UMR Gas engine plant building Gas engine plant building

    Structures for circulating (cooling)

    water systems

    Structures for cir culating (cooling) water

    systems

    UPA Cooling water intake culvert Cooling water intake culvert

    UPB Secondary cooling water intake culvert Secondary cooling water intake culvert

    UPC Cooling water intake structure Cooling water intake structure

    UPD Secondary cooling water intake structure Secondary cooling water intake structure

    UPH Structure for cooling water treatment Structure for cooling water treatment

    UPJ Structure for secondary cooling watertreatment

    Structure for secondary cooling water treatment

    UPN Cooling water inlet culvert Cooling water inlet culvert

    UPP Secondary cooling water inlet culvert Secondary cooling water inlet culvert

    UPQ Biocide treatment building Biocide treatment building

    UPS Debris trough Debris trough

    UP

    UPT Screen wash water cleaning structure Screen wash water cleaning structure

    Structures for circulating (cooling)water systems

    Structures for cir culating (cooling) watersystems

    UQA Cooling water pump building Cooling water pump building

    UQB Secondary cooling water pump building Secondary cooling water pump building

    UQG Cooling water overflow structure, surgetank

    Cooling water overflow structure, surge tank

    UQH Screen wash water discharge culvert Screen wash water discharge culvert

    UQJ Cooling water seal pit incl. cooling wateraeration structure

    Cooling water seal pit incl. cooling wateraeration structure

    UQK Cooling water venting structure Cooling water venting structure

    UQL Secondary cooling water surge pond Secondary cooling water surge pond

    UQM Secondary cooling water collecting pond Secondary cooling water collecting pond

    UQN Cooling water outfall culvert Cooling water outfall culvert

    UQP Secondary cooling water outfall culvert Secondary cooling water outfall culvert

    UQQ Cooling water outfall structure Cooling water outfall structure

    UQR Secondary cooling water outfall system Secondary cooling water outfall system

    UQS Cooling water discharge culvert Cooling water discharge culvert

    UQT Secondary cooling water discharge culvert Secondary cooling water discharge culvert

    UQU Cooling water spillway structure incl.cooling water aeration structure

    Cooling water spillway structure incl. coolingwater aeration structure

    UQ

    UQV Structure for artificial cooling wateraeration

    Structure for artificial cooling water aeration

  • 8/20/2019 KKS Handbook Rev B

    34/63

     

    Dwg. No. / Doc.

    Int Doc N°

    Rev

    LOTR-VSPO-AC90-9-0050-TR

    2840-004970

    B

    EMPLOYER. HYDROELECTRICA – S. A. DRAWN KINASBERGER 2007.07.03

    PLANT HPP LOTRU CIUNGET CHECK TUNG 2007.07.18

    ORDER No.. 23674 APPR. SALLFERT 2007.08.03 SHEET 34 / 63 

    UQW Routing structure for cooling waterdischarge

    Routing structure for cooling water discharge

    Structures for circulating (cooling)water systems

    Structures for cir culating (cooling) watersystems

    URA Cooling tower structure (main coolingwater)

    Cooling tower structure (main cooling water)

    URB Cooling tower structure (secondarycooling water)

    Cooling tower structure (secondary coolingwater)

    URC Structure for cooling water system Structure for cooling water system

    URD Cooling tower pump structure (maincooling water)

    Cooling tower pump structure (main coolingwater)

    URE Cooling tower pump structure (secondarycooling water)

    Cooling tower pump structure (secondarycooling water)

    URF Structure for cooling water system Structure for cooling water system

    URG Cooling tower connection structure Cooling tower connection structure

    URH Cooling tower outlet structure Cooling tower outlet structure

    URJ Cooling tower outfall culvert Cooling tower outfall culvert

    URK Cooling tower return structure Cooling tower return structure

    URL Cooling tower return culvert Cooling tower return culvert

    URM Cooling water distribution building Cooling water distribution building

    URN Cooling tower bypass structure Cooling tower bypass structure

    URP Cooling tower blowdown structure Cooling tower blowdown structure

    UR

    URQ Cooling tower blowdown culvert Cooling tower blowdown culvert

    Structures for anciliary systems Structures for anciliary systems

    USA Structure for heating, ventilation, air-conditioning systems

    Structure for heating, ventilation, air-conditioningsystems

    USB Structure for heating systems Structure for heating systems

    USC Structure for stationary compressed airsupply

    Structure for stationary compressed air supply

    USG Fire pump house Fire pump house

    USH Structure for waterway facilities Structure for waterway facilities

    UST Workshop Workshop

    USU Storage building Storage building

    USV Laboratory building Laboratory building

    US

    USX Special structures Special structures

    Structures for auxiliary systems Structures for auxiliary systemsUT

    UTF Compressed air system building Compressed air system building

    General services struc tures General services struc tures

    UYA Office and staff amenities building Office and staff amenities building

    UYB Staff amenities building Staff amenities building

    UYC Administration building Administration building

    UYD Canteen Canteen

    UYE Gate house Gate house