kit motorized unit for um switch or changeover switch · 2017. 2. 22. · um-c35277z um-c21277z...
TRANSCRIPT
181180
UM
UM-S
UM-C
UM-S
UM-C
1 2 3 4 5 6U M S
1 2 3 4 5 6U M C
1 2 3 4 5 6U M S
1 2 3 4 5 6U M C
Motorized units to automate the drive system of the switch-disconnectors and changeover switches, with a high level of reliability, safety and ease of operation even in extreme situations.
According to:EN55011 CISPR11IEC 60947-1 & 3IEC 61000, parts 3 & 4RoHS
series
series
series
series
Supply voltage 230 Vac/dc. For switch - disconnectors S5 & S6 sizes 1 and 2.
Supply voltage 230 Vac/dc. For changeover switches S5F or CCF sizes 0 up to 2.
Supply voltage 120 - 230 - 277 Vac/dc. For switch - disconnectors S5 sizes 3 up to 5.
Supply voltage 120 - 230 - 277 Vac/dc. For changeover switches S5F & CCF sizes 2 up to 4.
The motorized unit kits are manufactured with high safety self-extinguishing materials, providing an excellent level of electrical insulation, low smoke emission and high resistance to electromechanical stress.
They comply with environmental requirements and undergo strict quality controls for a reliable product that meets the most demanding requirements.
IEC60947-1 and 3. Low voltage devices. General part and switch - disconnectors.
IEC61000-6, Parts 2 and 4. Electromagnetic compatibility in industrial environments, immunity and emission.
According to European Standard 2014/35/UE for low voltage.
According to European standard 2014/30/UE of EMC.
They consist of a body housing the motor, gears, electronics to command and control. They are equipped with a selector for automatic-manual-lock operating modes.
The kit concept simplifies both logistics and maintenance, for easy and simple assembly on the changeover switch or switch - disconnector as required.
Motorized operation
Motorized operation
Manual operation(maintenance or emergency)
Manual operation(maintenance or emergency)
seriesKit motorized unit for switch or changeover switch
Testing and approvals:
183182
UM
-SUM
-S
UM-S31120ZUM-S32120Z
UM-S31230ZUM-S32230Z
UM-S2A230Z
UM-S31277ZUM-S32277Z
UM-S32120ZUM-S21120Z
UM-S32230ZUM-S21230Z
UM-S1A230Z
UM-S32277ZUM-S21277Z
120 Vac/dc 230 Vac/dc 277 Vac/dc 230 Vac/dc
UM T0
UM T2 - T3
31C
1= 1
83 C
2 =
249
C1= 73 C2 = 45
396167
153184
ø5,5
11298
16 10
88,5
88,5
172
455
312
56
396
503
T2=2
55/T
3=28
6
T2=487/T3=544
396
T2=311/T3=342
447459552
A3A1
312 T2=175/T3=232
A2
A1
396435
31
C1= 217 C2 = 275
C1=
190
C2
= 26
0
C1= 225 C2 = 286C1= 73 C2 = 46
C1=
167
C2
= 23
5
C1= 99,5 C2 = 129 C1= 290 C2 = 320
C1=
217
C2
= 27
4
C1= 108 C2 = 141
C1= 298 C2 = 332
UM T0
UM T2-T3
Technical information
UM T0
UM-S11120Z UM-S11230Z UM-S11277Z
103 315 68 15
250
76
90145
43 8
12,5
serie
s series
UM-SMotorized unit kit for switch S5000 & S6000
MOTORIZED UNIT I SWITCH - DISCONNECTORS O-I MOTORIZED UNIT I SWITCH - DISCONNECTORS O-I
Dimensions (mm)
Size 2 | UM T0
Size 4 | UM T3Size 5 | UM T3
Size 1 | UM T0
Size 3 *(m1) | UM T3Size 3 | UM T2
Size 3 | UM T2
Pos. Direction Pos. Operating time
0 I 750 ms
I 0 750 ms
*(m1) For 2000A size 3.
For inverted mounting there are references for with inverted frontal plates. Supply under request.
S6000 size 1&2 + UM T0
S5000 size 3 (2000 A) + UMT3
S5000 size 1&2 + UM T0
S5000 size 3 + UM T2 / S5000 size 4 + UM T3
S5000 size 5 + UM T3
A1
size 3-UM T2 290size 3-UM T3 455 (2000A)
A2
size 4-UM T3 381 (1000-1250A)size 4-UM T3 441 (1600-2000A)
A3
size 5-UM T3 543 (2000-2500A)size 5-UM T3 603 (3150A)
Rated operational voltage 230Vac/dcOperating voltage range (based in our own tests) (S5|S6 size 1) ΔV 0,85*V to 1,15*VOperating voltage range (based in our own tests) (S5|S6 size 2) ΔV 0,9*V to 1,1*VOperating voltage range according to IEC 60947-6 ΔV 0,95*V to 1,10*VCable section of voltage supply mm2 1,5 - 2,5Cable section area Input Signals mm2 0,5 - 1,5Cable section area Auto-Lock mode Outputs mm2 0,5 - 1,5Inrush Current (Irms) A 1,1Use current mA 45Protective Fuse (Ref. F1AL250V | Littelfuse) A 1Operating angle 0-90º (0 - I)Number of UM T0 operations (S5|S6 size 1) Cycles 10000Number of UM T0 operations (S5|S6 Size 2) Cycles 5000Operation rate (0-I-0) (S5|S6 size 1) Cycles/hour 120Operation rate (0-I-0) (S5|S6 size 2 ) Cycles/hour 60Operating temperature - 25ºC + 55ºCTransportation and storage temperature - 40ºC + 70ºCWeight Kg 1,8
Rated operational voltage 120Vac/dc 230Vac/dc 277Vac/dcFrecuency Hz 50/60Operating voltage range (based in our own tests) ΔV 0,85*V to 1,15*VOperating voltage range according to IEC 60947-6 ΔV 0,95*V to 1,10*VCable of voltage supply mm2 1,5 - 2,5Cable section area Input & MODBUS Signals mm2 0,5 - 1,5Cable section area Outputs mm2 0,5 - 1,5Inrush Current A 17Nominal Current during operation UM T2 A 4,75 2,5 2,1Nominal Current during operation UM T3 A 7,5 3,9 3,3Use current (Irms) A 0,041Use current (Imax) A 0,275Contacts operating time ms 180 168 174Number of UM T2 operations for S5 size 3 1000 - 1250A *(1) *(2) Cycles 3000 / 10000Operation rate (0-I-0) for S5 size 3 1000 - 1250A *(1) Cycles/hour 20 / 120Number of UM T3 operations for S5 size 3 2000A *(1) *(2) Cycles 3000 / 6000Operation rate (0-I-0) for S5 size 3 2000A *(1) Cycles/hour 20 / 40Number of UM T3 operations for S5 size 4 1000 - 2000A *(1) *(2) Cycles 3000 / 6000Operation rate (0-I-0) for S5 size 4 1000 - 2000A *(1) Cycles/hour 20 / 40Number of UM T3 operations for S5 size 5 2000 - 3150A *(1) *(2) Cycles 3000 / 6000Operation rate (0-I-0) for S5 size 5 2000 - 3150A *(1) Cycles/hour 20 / 40Operating temperature T/Un RH90% - 25ºC + 55ºCTransportation and storage temperature RH90% - 40ºC + 70ºCWeight T2/T3 Kg 3,96 / 4,4*(1) According to IEC 60947-3 / Based in our own tests *(2) Please consult us for more operations
S5
S5 S6
According to IEC 60947-3
185184
UM
-CUM
-C
UM-C35120Z
UM-C21120Z
UM-C35230Z
UM-C21230ZUM-C1A230Z
UM-C35277Z
UM-C21277ZUM-C31120Z UM-C31230Z
UM-C0A230Z
UM-C31277Z
120 Vac/dc 230 Vac/dc 277 Vac/dc
230 Vac/dc
UM T2 - T3
396167
153184
ø5,5
489
396
C2
+ T2
= 33
9 C
3 +
T3=
367
396
S5F
CCF
C2
+ T2
=470
C3
+ T3
=523
C2 + T2=321 C3 + T3=424
C2 + T2=283 C3 + T3=311
UM T0
UM T2-T3
UM-C2A230Z
216
223
121310
247
30
260
30 3029
4
186
145
250
83
60
94
UM T0
250
76
90145
43 8
103 315 68 15
12,5
16
11298
10
88,5
88,5
172
455
312
56
532
459
552447
162
353
312
83 133
serie
s series
CCF size 2 + UM T0CCF size 1 + UM T0S5000F size 0 + UM T0
UM-CMotorized unit kit for changeover switch S5000F & CCF
MOTORIZED UNIT I CHANGEOVER SWITCHES I-O-II MOTORIZED UNIT I CHANGEOVER SWITCHES I-O-II
Dimensions (mm)
Size 4 | UM T3
Size 2 | UM T2
Size 0 | UM T0
Size 1 | UM T0Size 2 | UM T0
Size 3 | UM T3
Technical informationAccording to IEC 60947-3
Pos. Direction Pos. Operating time
0 I 750 ms
I 0 750 ms
0 II 750 ms
II 0 750 ms
I II 1,5 sec
II I 1,5 sec
For inverted mounting there are references for with inverted frontal plates. Supply under request.
S5FCCF
CCF
Rated operational voltage 230Vac/dcOperating voltage range (based in our own tests) (size 1) ΔV 0,85*V to 1,15*VOperating voltage range (based in our own tests) (size 2) ΔV 0,9*V to 1,1*VOperating voltage range according to IEC 60947-6 (size 1) ΔV 0,95*V to 1,10*VOperating voltage range according to IEC 60947-6 (size 2) ΔV 0,95*V to 1,1*VCable of voltage supply mm2 1,5 - 2,5Cable section area Input Signals mm2 0,5 - 1,5Cable section area Auto-Lock mode Outputs mm2 0,5 - 1,5Inrush Current (Irms) A 1,1Use current mA 45Protective Fuse (Ref. F1AL250V | Littelfuse) A 1Operating angle - 70º / 0º / +70º (I - 0 - II)Number of UM T0 operations (S5|S6 size 1) Cycles 10000Number of UM T0 operations (S5|S6 size 2) Cycles 5000Operation rate (0-I-II-0) (S5|S6 size 1) Cycles/hour 120Operation rate (0-I-II-0) (S5|S6 size 2) Cycles/hour 60Operating temperature - 25ºC + 55ºCTransportation and storage temperature - 40ºC + 70ºCWeight Kg 1,8
Rated operational voltage 120Vac/dc 230Vac/dc 277Vac/dcFrecuency Hz 50/60Operating voltage range (based in our own tests) ΔV 0,85*V to 1,15*VOperating voltage range according to IEC 60947-6 ΔV 0,95*V to 1,10*VCable of voltage supply mm2 1,5 - 2,5Cable section area Input & MODBUS Signals mm2 0,5 - 1,5Cable section area Outputs mm2 0,5 - 1,5Inrush Current A 17Nominal Current during operation UM T2 A 4,75 2,5 2,1Nominal Current during operation UM T3 A 7,5 3,9 3,3Use current (Irms) A 0,041Use current (Imax) A 0,275Operation time CCF size 2 - UM T2 ms 180 168 174Operation time S5F size 4 | CCF C3 UM T3 ms 166 148 154Number of UM T2 operations for CCF size 2 500 - 630A *(1) *(2) Cycles 4000 / 10000Operation rate (0-I-II-0) for CCF size 2 500 - 630A *(1) Cycles/hour 60 / 120Number of UM T2 operations for CCF size 2 800A *(1) *(2) Cycles 2500 / 10000Operation rate (0-I-II-0) for CCF size 2 800A *(1) Cycles/hour 20 / 120Number of UM T3 operations for S5F size 4| CCF size 3 *(1) *(2) Cycles 2500 / 7000Operation rate (0-I-II-0) for S5F size 4 | CCF size 3 *(1) Cycles/hour 20 / 60Operating temperature T/Un RH90% -25ºC +55ºCTransportation and storage temperature RH90% - 40ºC + 70ºCWeight T2/T3 Kg 3,96 / 4,4*(1) According to IEC 60947-3 / Based in our own tests *(2) Please consult us for more operations
CCF size 2&3 + UM T2 - T3
S5000F size 4 + UM T3
AVAILABLE ON
SEPTEMBER 2016
AVAILABLE ON
SEPTEMBER 2016